BRE Global Assessment Report

Size: px
Start display at page:

Download "BRE Global Assessment Report"

Transcription

1 BRE Global Assessment Report An assessment of the fire performance of the Gebrik Insulating Brick Cladding System against BR 135, Third Edition Prepared for: Date: 13 April 2016 Aquarian Cladding Systems BRE Global Ltd Watford, Herts WD25 9XX Customer Services From outside the UK: T + 44 (0) F + 44 (0) E enquiries@bre.co.uk Prepared for: Aquarian Cladding Systems Eversea Business Centre 13 Gardens Road Clevedon Somerset BS21 7QQ

2 Prepared by Name Position Andrew C Russell Senior Consultant Date 13 April 2016 Signature Authorised by Name Position Richard A Jones Associate Director Date 13 April 2016 Signature Date of this report 13 April 2016 Date of next review 13 April 2021 This report is made on behalf of BRE Global and may only be distributed in its entirety, without amendment, and with attribution to BRE Global Ltd to the extent permitted by the terms and conditions of the contract. Assessment results relate only to the specimens tested. BRE Global has no responsibility for the design, materials, workmanship or performance of the product or specimens assessed. This report does not constitute an approval, certification or endorsement of the product assessed and no such claims should be made on websites, marketing materials, etc. Any reference to the results contained in this report should be accompanied by a copy of the full report, or a link to a copy of the full report. BRE Global s liability in respect of this report and reliance thereupon shall be as per the terms and conditions of contract with the client and BRE Global shall have no liability to third parties to the extent permitted in law. Commercial in Confidence BRE Global Ltd 2016 Page 1 of 19

3 Table of contents 1 Introduction 3 2 Scope 4 3 Supporting data BRE test report no Issue: BRE classification report no Issue: BRE test report no. P Issue: BRE classification report no. P Issue: Description of the proposed systems 9 5 Assessment General Layer 7 Kingspan Kooltherm K5 and K15 insulation board Layer 6 Outer sheathing board Layer 5 Cavity (proposal 1 only) Layer 4 Inner sheathing board (proposal 1 only) Layer 3 Structural framing systems (SFS) Proposal 1 (with cavity) Proposal 2 (without cavity) Layers 1 and 2 Internal plasterboard lining 13 6 Conclusion 14 7 Figures 15 8 Validity of the assessment Declaration by applicant BRE Global declaration 19 Commercial in Confidence BRE Global Ltd 2016 Page 2 of 19

4 1 Introduction Fire tests in accordance with BS :2005 have been successfully carried out on Gebrik Insulating Brick Cladding Systems. This assessment report considers the performance of these systems when incorporating variations to the tested designs. Commercial in Confidence BRE Global Ltd 2016 Page 3 of 19

5 2 Scope This assessment report considers the fire performance of the Gebrik Insulating Brick Cladding System against the criteria of BR 135, Third Edition, if tested in accordance with BS :2015. Commercial in Confidence BRE Global Ltd 2016 Page 4 of 19

6 3 Supporting data 3.1 BRE test report no Issue: 1 A fire test in accordance with BS :2005 was carried out on a Gebrik system on an SFS substrate on 08 April The system, as built, comprised of: Double layer of 12.5 mm wall board. 150mm steel frame insulated with 140mm mineral wool insulation. 12mm Cement calcium sheathing board. Breather membrane. 15mm timber battens. Intumescent expanding fire break. 12mm Cement calcium sheathing board. 60mm K5 insulation board. 60mm Gebrik panel with bonded brick slips. A sectional steel frame system (SFS) was installed between the floor slabs on the main cladding wall 4, with horizontal base and head tracks fixed to the concrete and steel substrate. Vertical rails were installed at nominal 600mm centres to form the steel frame. A double layer of 12.5mm Gyproc wall board was installed on the rear of the SFS and a single layer of cement based calcium sheathing board was fixed to the front of the SFS. The void within the steel frame was filled with 140mm of mineral wool insulation. A single layer of breather membrane was attached to the sheathing board. An array of 15mm rated timber battens was installed vertically and equally centred and mechanically fixed to the sheathing board. A second layer of sheathing board was attached to the timber battens to form a drainage cavity. At 2400mm and 4800mm from floor level a break in the sheathing board was formed and a continuous strip of intumescent expanding fire break fixed back to the first layer of sheathing board. A single layer of 60mm Kingspan Kooltherm K5 External wall board was mechanically attached to the sheathing board with single fixing and stainless steel washer placed in the centre of each board. A 60 mm single layer of Gebrik was mechanically fixed through the K5 insulation into the sheathing board through hidden fixing at a rate of 9 per whole panel and 5 on corner panels. Commercial in Confidence BRE Global Ltd 2016 Page 5 of 19

7 3.2 BRE classification report no Issue: 1 This report presents the classification of the system tested in BRE report no Issue: 1. The classification is carried out in accordance with the procedures given in BR 135 Fire performance of external thermal insulation for walls of multi-storey buildings, Third edition, Annex B The system, as tested, satisfied the criteria as follows: Results Test method & test number Parameter No. tests Fire spread test result time, ts (min) Compliance with parameters in Annex B BR135:2013 External fire spread >15 minutes Compliant BS : 2005 BRE Issue: 1 Internal fire spread Insulation layer 1 >15 minutes Compliant Internal fire spread Burn through >15 minutes Compliant 3.3 BRE test report no. P Issue: 2 A fire test in accordance with BS :2005 was carried out on a Gebrik Rainscreen Cladding System on 15 July The test specimen was installed onto face 4 of the BRE Global External Cladding Test Facility. This is a multi-faced test facility constructed from steel, with the cladding system affixed to the steel substructure. The build-up of the system (in order from the structural frame to the outer panels) comprised of: Double layer of 12.5mm plasterboard 150mm light gauge steel frame (Kingframe)/150mm Earthwool Flexi rock mineral wool insulation 12mm calcium silicate based cement building board (Y-wall) 15mm fire retardant battens 12mm calcium silicate based cement building board (Y-wall) 120mm K15 Kingspan insulation 1000mm x 75mm VRB Lite intumescent fire component installed both vertically and horizontally 60mm Gebrik panels, consisting of 43mm rigid polyurethane foam insulation (PUR) and 17mm façade brickslips and mortar Further detail of the composition of the wall is given below: A sectional light gauge steel frame system (SFS) was installed between the floor slab hangers on the main cladding wall 3, with horizontal base and head tracks fixed to the steel substrate. Vertical rails were installed at varying centres to accommodate the cladding system on to the test rig. Within the SFS was installed a 150mm layer of Earthwool Flexi. Commercial in Confidence BRE Global Ltd 2016 Page 6 of 19

8 A double layer of 12.5mm plasterboard was installed on the internal face of the SFS and a single layer of calcium silicate based cement building board was fixed to the front of the SFS. 15mm fire retardant battens were installed on the front of the calcium cement sheathing board, and on these was fixed a second layer of calcium silicate based cement building board. The insulation was directly fixed to the sheathing board using Ø4.8mm fixings and washers, including 2no stainless steel washers. The joints between the individual sheets were taped with aluminium tape. The insulation was 120mm Kingspan K15 panels supplied in 2.4m x 1.2m sheets. The Gebrik cladding system was mechanically fixed directly into the sheathing board through Isofixing washers, precast in the panels and corners, and through the K15 using Gebrik system fixings. A horizontal starter rail was installed at the base, which located the bottom of the first row of brick cladding panels and corners. The panels and corners were then installed row by row up the façade until the entire test area was fully clad. Once mechanically fixed, the horizontal and vertical chambers between panels and corners were fully filled with expandable PU foam prior to the stitching slips being applied with cement-based system adhesive. The entire façade was then pointed with mortar and allowed to cure for 13 days. The horizontal and vertical firebreaks located within the cavity were VRB Lite barriers, measuring 1000mm x 75mm, and were installed in the following locations: Horizontal fire breaks were installed above the hearth (for the width of the main wall), approximately 900mm above the hearth (full width of main and wing walls), and aligned with the top of the level 2 floor, and a final barrier was installed to close off the top of the system. A vertical firebreak was installed on the main wall to the left hand side of the hearth (between the wing and main walls) for the full height of the system. This was located approximately 430mm from the cement particle sheeting board layer on the wing wall. A second vertical fire break was installed on the wing wall for the full height of the system. This was located approximately 215mm from the cement particle sheeting board layer on the main wall. A third vertical fire break was installed to the right of the hearth and terminated at the horizontal fire break across the top of the hearth. This was approximately 450mm from the right hand edge of the system. The hearth opening was faced with a 120mm deep Gebrik head reveal to close the system and K15 insulation. The cavity was closed with the fire treated timber batten applied horizontally and the SFS was clad with calcium cement board. 3.4 BRE classification report no. P Issue: 2 This report presents the classification of the system tested in BRE report no. P Issue: 2. The classification is carried out in accordance with the procedures given in BR 135 Fire performance of external thermal insulation for walls of multi-storey buildings, Third edition, Annex B Commercial in Confidence BRE Global Ltd 2016 Page 7 of 19

9 The system, as tested, satisfied the criteria as follows: Results Test method & test number Parameter No. tests Fire spread test result time, ts (min) Compliance with parameters in Annex B BR135:2013 External fire spread >15 minutes Compliant Internal fire spread Insulation layer >15 minutes Compliant BS : 2005 BRE P Issue: 2 Cavity behind insulation 1 >15 minutes Compliant Cement particle board >15 minutes Compliant Internal fire spread Burn through >15 minutes Compliant Commercial in Confidence BRE Global Ltd 2016 Page 8 of 19

10 4 Description of the proposed systems The construction of the proposed wall systems are similar to those tested and comprise the following layers: Table 1 Tested and proposed systems Layer Tested Proposal 1 (with cavity) Proposal 2 (without cavity) mm Knauf Wallboard Any plasterboard Any plasterboard mm Knauf Wallboard Any plasterboard Any plasterboard 3 150mm structural framing system with 140mm stone mineral wool insulation 75mm to 200mm SFS with no insulation, stone mineral wool insulation, phenolic insulation, PUR insulation or EPS insulation 75mm to 200mm SFS with no insulation, stone mineral wool insulation, phenolic insulation, PUR insulation or EPS insulation 4 12mm cement sheathing board Minimum 9mm cement sheathing board, calcium silicate board, exterior grade plywood or Oriented Strand Board (OSB) Minimum 9mm cement sheathing board, calcium silicate board, exterior grade plywood or Oriented Strand Board (OSB) 5 15mm cavity with fire treated birch plywood battens with Tenmat FF102/15 1 or AIM VRB Lite 2 intumescent cavity barriers Minimum 15mm cavity with fire treated birch plywood battens, aluminium battens/brackets, steel battens/brackets with no insulation, stone mineral wool insulation, polyurethane insulation or phenolic insulation and Tenmat FF102/15 or AIM VRB Lite intumescent cavity barriers No cavity 6 12mm cement sheathing board Minimum 9mm cement sheathing board or calcium silicate board No cement sheathing board 7 60mm Kingspan Kooltherm K5 insulation board 1 120mm Kingspan Kooltherm K15 insulation board 2 Up to 70mm Kingspan Kooltherm K5 insulation board Up to 120mm Kingspan Kooltherm K15 insulation board Up to 70mm Kingspan Kooltherm K5 insulation board Up to 120mm Kingspan Kooltherm K15 insulation board 8 60mm Gebrik Insulating Brick Cladding System 3 60mm Gebrik Insulating Brick Cladding System 60mm Gebrik Insulating Brick Cladding System Commercial in Confidence BRE Global Ltd 2016 Page 9 of 19

11 Notes: 1. The specimen tested in BRE test report no Issue: 1 incorporated Tenmat FF102/15 cavity barriers and 60mm Kingspan Kooltherm K5 insulation board. 2. The specimen tested in BRE test report no. P Issue: 2 incorporated AIM VRB Lite cavity barriers and 120mm Kingspan Kooltherm K15 insulation board. 3. The specimen tested in BRE test report no. P Issue: 2 included Iso-fixings, which are polyamide washers cast into the Gebrik system to improve thermal performance and wind load resistance. Typical examples of the system with a cavity (proposal 1) are shown in figures 1 and 2 and typical examples of the system without a cavity (proposal 2) are shown in figures 3 and 4. Commercial in Confidence BRE Global Ltd 2016 Page 10 of 19

12 5 Assessment 5.1 General During the tests on the systems tested in BRE report nos Issue: 1 and P Issue: 2, the maximum external air temperature at level 2 remained below the limit of 600 C within 15 minutes of the start time, as did the temperature at the mid-depth of the insulation, at the mid-depth of the outer layer of cement sheathing board and at the mid-depth of the cavity. The approximate maximum temperatures in each test at each of these locations within the first 15 minutes are tabulated below: Table 2 Maximum temperatures measured at level 2 in tested systems BRE report no Issue: 1 (60mm Kingspan K5) BRE report no. P Issue: 2 (120mm Kingspan K15) Air temperature 380 C 390 C Gebrik panels 110 C K5/K15 insulation 105 C 90 C Cement sheathing board 130 C 50 C Cavity 100 C 40 C 5.2 Layer 7 Kingspan Kooltherm K5 and K15 insulation board The systems were tested with 60mm-thick Kingspan K5 (BRE report no Issue: 1) and 120mmthick Kingspan K15 (BRE report no. P Issue: 2). We have been advised by Kingspan Insulation that these two products have an identical formulation. The only difference is that K15 is foilfaced and K5 is tissue-faced. As the temperature at the mid-depth of the Gebrik panels was only 110 C, it is clear that the temperature of the Kingspan K5 or K15 insulation board will not be significantly different regardless of thickness. Therefore, both products are considered suitable for any thickness up to the maximum tested, although it should be noted that the maximum thickness available for K5 is only 70mm. 5.3 Layer 6 Outer sheathing board The tested systems each incorporated cement particle sheathing board. During the tests, the maximum temperature of this layer was 130 C when using 60mm Kingspan Kooltherm K5 insulation and 50 C when using 120mm Kingspan Kooltherm K15 insulation. These temperatures are sufficiently low to suggest that any alternative non-combustible sheathing board could be used, e.g. calcium silicate board. Reducing the board thickness to 9mm should have no significant impact at these temperatures. Commercial in Confidence BRE Global Ltd 2016 Page 11 of 19

13 5.4 Layer 5 Cavity (proposal 1 only) The cavity in both of the tested systems incorporated 15mm-deep timber battens with either Tenmat FF102/15 or AIM VRB Lite intumescent cavity barriers. The proposal is that the cavity depth may be increased, it may be formed using aluminium or steel brackets or battens and/or it may be filled with insulation. Increasing the depth of the cavity will, if anything, improve the overall performance of the system. The temperatures within the cavity will be lower and the temperature of the sheathing board on the internal face of the cavity will therefore also be lower. Using aluminium or steel brackets or battens to create the cavity will have no effect on the fire performance as both products are non-combustible. The maximum temperatures measured within the sheathing board on the outer face of the cavity suggest that the temperatures within the cavity are unlikely to be much greater than 100 C in the worst case when using the minimum thickness of insulation. This temperature is well below that required to ignite most flammable insulation materials. It is therefore reasonable to assume that this cavity could be filled with any insulation material that will not melt at this temperature, e.g. mineral wool, stone or glass, polyurethane insulation or phenolic insulation. 5.5 Layer 4 Inner sheathing board (proposal 1 only) The tested systems each incorporated cement particle sheathing board. Any alternative product is considered suitable from a fire viewpoint as the temperatures at this location will be well below that required to ignite even flammable products. Therefore we consider calcium silicate board, exterior grade plywood or Oriented Strand Board (OSB) all to be acceptable alternatives, providing the minimum thickness is not less than 9mm. 5.6 Layer 3 Structural framing systems (SFS) Proposal 1 (with cavity) The systems were each tested with a 150mm-deep SFS insulated with 140mm-thick stone mineral wool insulation. Again, the temperatures at this location in a BS test will be very low and we therefore consider that the SFS can be reduced in depth to 75mm without increasing the likelihood of burn through. Increasing the depth to 200mm is also considered acceptable. As the temperatures at this location would barely be above ambient during the first 15 minutes of a BS test, any insulation material is considered to be suitable, e.g. stone or glass mineral wool, polyurethane insulation, phenolic insulation, expanded polystyrene insulation, etc Proposal 2 (without cavity) With proposal 2 the maximum temperatures measured within the outer layer of sheathing board in the tests suggest that the temperatures within the SFS are likely to be slightly higher but still not much greater than 100 C in the worst case when using the minimum thickness of insulation. We therefore consider that a reduction in the depth of the SFS to 75mm will not increase the likelihood of burn through. Increasing the depth to 200mm is also acceptable as this will have a beneficial effect on the fire performance. The expected temperature within the SFS is well below that required to ignite most flammable insulation materials. It is therefore reasonable to assume that the SFS frame could be filled with any insulation material that will not melt at this temperature, e.g. mineral wool, stone or glass, polyurethane insulation or phenolic insulation. Commercial in Confidence BRE Global Ltd 2016 Page 12 of 19

14 5.7 Layers 1 and 2 Internal plasterboard lining The plasterboard forming the internal lining can be in a single layer with a minimum thickness of 9.5mm without affecting the fire performance in a BS test as break through is very unlikely due to the low temperatures within the SFS framing with either proposal 1 or proposal 2. Commercial in Confidence BRE Global Ltd 2016 Page 13 of 19

15 6 Conclusion Therefore it is our opinion that the Gebrik Insulating Brick Cladding System tested in BRE reports nos Issue: 1 and P Issue: 2, incorporating the variations described in section 4, would satisfy the performance criteria of BR 135, Third Edition, if tested in accordance with BS :2015. Commercial in Confidence BRE Global Ltd 2016 Page 14 of 19

16 7 Figures Figure 1 Horizontal section through typical system with cavity Commercial in Confidence BRE Global Ltd 2016 Page 15 of 19

17 Figure 2 Vertical section through typical system with cavity Commercial in Confidence BRE Global Ltd 2016 Page 16 of 19

18 Figure 3 Horizontal section through typical system without cavity Commercial in Confidence BRE Global Ltd 2016 Page 17 of 19

19 Figure 4 Vertical section through typical system without cavity Commercial in Confidence BRE Global Ltd 2016 Page 18 of 19

20 8 Validity of the assessment 8.1 Declaration by applicant We the undersigned confirm that we have read and complied with the obligations placed on us by the PFPF Guide to Undertaking Assessments in Lieu of Fire Tests. We confirm that the component or element of structure, which is the subject of this assessment, has not to our knowledge been subjected to a fire test to the Standard against which this assessment is being made. We agree to withdraw this assessment from circulation should the component or element of structure be the subject of a fire test to the Standard against which this assessment is being made. We are not aware of any information that could adversely affect the conclusions of this assessment. If we subsequently become aware of any such information we agree to cease using the assessment and ask BRE Global to withdraw the assessment. Signed: For and on behalf of: 8.2 BRE Global declaration This assessment is issued on the basis of test data and information to hand at the time of issue. If contradictory evidence becomes available to BRE Global the assessment will be unconditionally withdrawn and the applicant will be notified in writing. Similarly the assessment is invalidated if the assessed construction is subsequently tested since actual test data is deemed to take precedence over an expressed opinion. The assessment is valid for a period of five years after which it should be returned for review to consider any additional data which has become available or any changes in the fire test procedures. Any changes in the specification of the product will invalidate this assessment. This assessment has been carried out in accordance with Fire Test Study Group Resolution No. 82. It relates to the fire performance of the product and does not cover aspects of quality, durability, maintenance nor service requirements. This assessment relates only to the specimen(s) assessed and does not by itself imply that the product is approved under any Loss Prevention Certification Board approval or certification scheme or any other endorsements, approval or certification scheme. Next review date: 13 April 2021 Commercial in Confidence BRE Global Ltd 2016 Report Ends Page 19 of 19

BRE Global Test Report

BRE Global Test Report BRE Global Test Report BS 8414-2 : 2005 Test on a Gebrik Rainscreen Cladding System Prepared for: Isosystems and Aquarian Cladding Systems Date: 21 September 2015 Report Number: P100838-1000 Issue 2 BRE

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report Classification of fire performance in accordance with BR 135: 2013 Annex B. Prepared for: Date: 02 July 2014 Report Number: 287129 Iso Systems and Aquarian Cladding Systems BRE Global

More information

BRE Global Classification Report

BRE Global Classification Report BRE Global Classification Report Kingspan Ltd. BENCHMARK Engineered Façade system - Metallic Hook on Cassette. Classification of fire performance in accordance with BR 135: 2013 Annex B Prepared for: Kingspan

More information

BRE Global Classification Report

BRE Global Classification Report BRE Global Classification Report Kingspan Insulation Cladding system with a Terracota tile rainscreen. Classification of fire performance in accordance with BR 135: 2013 Annex B Prepared for: Kingspan

More information

BRE Global Classification Report

BRE Global Classification Report BRE Global Classification Report Classification of fire performance in accordance with BR135:2013 Annex B on a Kingspan BENCHMARK 80mm QuadCore TM Karrier & Dri Design Cassette system. Prepared for: Kingspan

More information

BRE Global Classification Report

BRE Global Classification Report BRE Global Classification Report Classification of fire performance in accordance with BR 135: 2013 Annex A for a ventilated façade system with Kingspan Kooltherm K15 insulation and Alpolic/fr panels.

More information

BRE Global Assessment Report

BRE Global Assessment Report BRE Global Assessment Report An assessment of the fire performance of FireWizard intumescent acrylic sealant/nor-coustic Acoustic Fire Rated Mastic Prepared for: Norseal Limited Date: 10 November 2015

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report BS 8414-2: 2005 Test on a Kingspan BENCHMARK 220mm QuadCore TM Wall liner panel with a Corium brick system. Prepared for: Kingspan Ltd Date: 7 th November 2016 Report Number: P102340-1000

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report BS 8414-1:2015 + A1:2017 test on ventilated façade system with Kingspan (K15) thermal insulation and ACM panels Prepared for: Date: 18 January 2017 Mitsubishi Chemical Corporation

More information

BRE Global Ltd Watford, Herts WD25 9XX. d+b facades (UK) Ltd. The Packway, Larkhill, Salisbury, SP4 8PY. Customer Services

BRE Global Ltd Watford, Herts WD25 9XX. d+b facades (UK) Ltd. The Packway, Larkhill, Salisbury, SP4 8PY. Customer Services BRE Global Test Report BS 8414-1:2015 + A1:2017 test on d+b facades rain screen cladding system with 100mm-thick Rockwool insulation and aluminium cassette panels. Prepared for: d+b facades (UK) Ltd. Date:

More information

BRE Global Assessment Report

BRE Global Assessment Report BRE Global Assessment Report An assessment of the fire performance of Suresnap Fire Collars fitted around plastic pipes penetrating concrete floors against the adopted criteria of BS 476: Part 20: 1987

More information

BS8414 Part 1: 2002 Test on a Phenolic Insulated Rainscreen system. Prepared for: Kingspan Insulation Ltd Pembridge Leominster Herefordshire HR6 9LA

BS8414 Part 1: 2002 Test on a Phenolic Insulated Rainscreen system. Prepared for: Kingspan Insulation Ltd Pembridge Leominster Herefordshire HR6 9LA BS8414 Part 1: 2002 Test on a Phenolic Insulated Rainscreen system Prepared for: Kingspan Insulation Ltd Pembridge Leominster Herefordshire HR6 9LA 8 December 2005 0578 Page 1 of 16 Prepared on behalf

More information

Classification of fire performance in accordance with BR 135: Annex B: Prepared for: Alsecco (U.K) Ltd Whitebridge Way Stone Staffs.

Classification of fire performance in accordance with BR 135: Annex B: Prepared for: Alsecco (U.K) Ltd Whitebridge Way Stone Staffs. Classification of fire performance in accordance with BR 135: Annex B: 2007 Prepared for: Alsecco (U.K) Ltd Whitebridge Way Stone Staffs. ST15 8GH 29 th June 2007 Classification report : 237475-2 Issue

More information

BS :2005 test on a Kingspan Benchmark External Wall Insulation System

BS :2005 test on a Kingspan Benchmark External Wall Insulation System BS 8414-2:2005 test on a Kingspan Benchmark External Wall Insulation Prepared for: Kingspan Ltd. Carrickmacross Road Kingscourt County Cavan Ireland 7 September 2011 0578 Page 1 of 30 Prepared on behalf

More information

Assessment Number BTC 14254FA

Assessment Number BTC 14254FA Assessment Number BTC 14254FA A FIRE TEST ASSESSMENT ON A LOADBEARING WALL CONSISTING OF OSB FACE AND POLYURETHANE CORE, CLAD ON THE EXPOSED FACE WITH 19mm GYPROC PLANK AND 12.5mm GYPROC FIRELINE, CONDUCTED

More information

BRE Global Client Report

BRE Global Client Report BRE Global Client Report BS 8414-1:2015 + A1:2017 test referred to as DCLG test 1. Prepared for: DCLG Date: 27th July 2017 Report Number: B137611-1037 (DCLG test 1) Issue: 1.0 BRE Global Ltd Watford, Herts

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report CEN/TS 1187: 2012 Test 4 External fire exposure to roofs test on Sarnafil G410-12 EL membrane over SarnaTherm G/TR27 on a Plywood deck Prepared for: Sika Limited Date: 05 January

More information

8414-1: A1:2017

8414-1: A1:2017 www..co.uk RE Global Client Report BS 8414-1:2015 + A1:2017 Test referred to as DCLG test 7. Prepared for: Date: Report Number: DCLG 18th August 2017 B137611-1037 (DCLG test 7) Issue: 2.0 BRE Global Ltd

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report BS 476: Part 3: 2004 + A1: 2006 + A2: 2007 External fire exposure to roofs test on Sarnafil G410-12 EL membrane over SarnaTherm G/TR27 on a Plywood deck Prepared for: Sika Limited

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report BS 476-7: 1997 Surface spread of flame test on K-Flex ST, 50mm Prepared for: L Isolante K-Flex S.p.A. Date: 26 May 2015 Report Number: P100094-1003- BRE Global Ltd Watford, Herts

More information

BRE Global Classification Report

BRE Global Classification Report BRE Global Classification Report Classification of reaction to fire performance in accordance with EN 13501-1: 2007 + A1: 2009 on Vitracore G2 Prepared for: Valcan Limited Date: 12 December 2016 Report

More information

An assessment of the fire performance of Sanders Fire-Rated Mortar penetration seal systems

An assessment of the fire performance of Sanders Fire-Rated Mortar penetration seal systems An assessment of the fire performance of Sanders Fire-Rated Mortar penetration seal systems Prepared for: Sandersfire International Limited Hamlyn House 4 Beadles Lane Old Oxted Surrey RH8 9JJ 16 July

More information

K15 Rainscreen Board. Insulation INSULATION FOR USE BEHIND RAINSCREEN CLADDING SYSTEMS

K15 Rainscreen Board. Insulation INSULATION FOR USE BEHIND RAINSCREEN CLADDING SYSTEMS Insulation A4/6 K15 AW2161 Issue 3 Dec 2016 INSULATION FOR USE BEHIND RAINSCREEN CLADDING SYSTEMS Super high performance rigid thermoset phenolic insulation Fibre-free, closed cell insulation core Suitable

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report Ad-hoc fire resistance test on a galvanised steel Tunnel Ventilation Damper employing procedures and criteria from BS 476: Part 20 : 1987. Prepared for: Betec Cad Industries Date:

More information

Rainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres

Rainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres 01473 820850 celotex.co.uk Rainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres 1 Rainscreen Cladding Compliance Guide Compliance Guide This document provides

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report BS 476-6: 1989 + A1: 2009 Fire propagation test on K-Flex ST, 19mm Prepared for: L'Isolante K-Flex Srl Date: 26 November 2015 Report Number: 266234 Issue: 2 BRE Global Ltd Watford,

More information

Copyright 2018 Underwriters Laboratories LLC. UL International (UK) Ltd. 220, Cygnet Court, Centre Park, Warrington. WA1 1PP

Copyright 2018 Underwriters Laboratories LLC. UL International (UK) Ltd. 220, Cygnet Court, Centre Park, Warrington. WA1 1PP Project number: 4788656094-A 10 th October 2018 ASSESSMENT REPORT On IPASSIVE FR ASF sealant Title The Performance of IPASSIVE FR ASF sealant in Accordance with AS 4072.1: 2005 & AS 1530.4 2005/14 ipassive

More information

Assessment Number BTC 16422FA

Assessment Number BTC 16422FA Assessment Number BTC 16422FA A FIRE TEST ASSESSMENT TO BS EN 1364-1:1999 ON A 5M GYPWALL CLASSIC PARTITION OF 92 S 50 STUDS INCORPORATING A DOUBLE LAYER 15mm GYPROC SOUNDBLOC AND ISOVER APR 1200 IN THE

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report BS 476: Part 3: 2004 + A1: 2006 + A2: 2007 External fire exposure to roofs test on SolFit Top Loader. Prepared for: SolFiT Ltd Date: 19 November 2016 Report Number: P105772-1000

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report BS 476-7: 1997 Surface spread of flame test on K-Flex ECO + ALU Prepared for: L'Isolante K-Flex S.p.A. Date: 24 April 2015 Report Number: 261123 BRE Global Ltd Watford, Herts WD25

More information

BRE Global Assessment Report

BRE Global Assessment Report RE Global Assessment Report An assessment of the fire performance of the IDE servery rolling shutter doorset, for opening sizes Prepared for: Date: 07 July 2014 Industrial Door Engineering Limited RE Global

More information

PRODUCT SUSPENDED. Rainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres

PRODUCT SUSPENDED. Rainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres 01473 820850 celotex.co.uk Update - IMPORTANT: On 23 June 2017, in view of the focus on components of rainscreen cladding systems, Celotex stopped the supply of Celotex RS5000, pending further clarity.

More information

VENTILATED FIRE BARRIERS

VENTILATED FIRE BARRIERS TENMAT VENTILATED FIRE BARRIERS TENMAT VFB Plus fitted behind cladding Many rainscreen and cladding systems are designed with an open cavity to provide back ventilation. The cavity acts like an open chimney

More information

VENTILATED FIRE BARRIERS

VENTILATED FIRE BARRIERS TENMAT VENTILATED FIRE BARRIERS TENMAT VFB Plus fitted behind cladding Many rainscreen and cladding systems are designed with an open cavity to provide back ventilation. The cavity acts like an open chimney

More information

April Section Cladded Walls

April Section Cladded Walls April 2012 Section Cladded Walls Cladded Walls Cladded walls Rainscreen cladding and curtain wall systems Rainscreen cladding systems There are a wide variety of proprietary rainscreen cladding systems

More information

BRE Global Classification Report

BRE Global Classification Report BRE Global ification Report ification report for roofs/roof coverings exposed to external fire in accordance with EN 13501-5: 2005 + A1:2009 on Sarnafil G410-12 EL membrane over SarnaTherm G/TR27 on a

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report BS 476: Part 3: 2004 External fire exposure to roofs test on Flexitec 2020 on 9mm Masterboard calcium silicate base Prepared for: Res-Tec Ltd Date: 03 November 2017 Report Number:

More information

Certificate No: EWWS165

Certificate No: EWWS165 Certificate No: EWWS165 Kingspan Kooltherm K15 Rainscreen Board Description of Product Kooltherm K15 Rainscreen Board is a rigid phenolic insulation board incorporating foil composite facings. It is intended

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report Classification of reaction to fire performance in accordance with EN 13501-1: 2007 + A1: 2009 on Multi-Pro, Multi-Pro XS and Render Pro Prepared for: Resistant Building Products

More information

Light steel frame walls

Light steel frame walls Light Steel Frame Walls Light steel frame walls Solution optimiser and pathfinder Overview Light steel framing is extensively used due to its good thermal and structural behaviour. Heat loss reduction

More information

Title: The Fire Resistance Performance of Modified Timber Based Doorsets. WF Assessment Report No: Issue 2. Prepared for:

Title: The Fire Resistance Performance of Modified Timber Based Doorsets. WF Assessment Report No: Issue 2. Prepared for: assessment report Title: The Fire Resistance Performance of Modified Timber Based Doorsets WF Assessment Report No: 163997 Issue 2 Prepared for: Sauerlander Spanplatten GmbH Postfach 5553 59805 Arnsberg

More information

21 st November Title:

21 st November Title: assessment report Title: The Fire Resistance Performance Of Previously Fire Tested Insulated Timber/ Composite Doorsets Incorporating Simonswerk TE525 Hinges WF Assessment Report No: 178450 Prepared for:

More information

ASSESSMENT REPORT. The fire resistance performance of UltraMgO - Partition 20 Party Wall System if tested in accordance with AS1530.

ASSESSMENT REPORT. The fire resistance performance of UltraMgO - Partition 20 Party Wall System if tested in accordance with AS1530. ASSESSMENT REPORT The fire resistance performance of UltraMgO - Partition 20 Party Wall System if tested in accordance with AS1530.4-2014 EWFA Report No: RIR 46975500.2 Report Sponsor: Fireproof Cladding

More information

APPROVALS. Jabwall has been approved for this application since 1979, and was the first partial-fill insulation product to gain BBA approval.

APPROVALS. Jabwall has been approved for this application since 1979, and was the first partial-fill insulation product to gain BBA approval. Cavity-Wall Insulation: Partial-Fill is a partial-fill cavity-wall insulation system designed to be incorporated into new masonry walls during construction to satisfy the Building Regulations U-value requirements.

More information

Fire Rated Cladding Seals

Fire Rated Cladding Seals Trade Name: Astro Clad Ventilated Fire Barriers Fire Rated Cladding Seals Creates a fire barrier within rainscreen cladding Suitable for ventilated cavities from 15mm Tested to BS 476Part 20 : BS EN 1363-1

More information

Suspended timber upper floors

Suspended timber upper floors Exposed Soffit Floors Exposed soffit Exposed soffit design Many clients perceive that rooms above exposed upper floors will be cold. However, it is possible to achieve very high levels of thermal insulation

More information

KINGSPAN INSULATION KOOLTHERM K15 RAINSCREEN INSULATION BOARD

KINGSPAN INSULATION KOOLTHERM K15 RAINSCREEN INSULATION BOARD Kingspan Insulation Ltd Pembridge Leominster Herefordshire HR6 9LA Tel: 0870 850 8555 Fax: 0870 850 8666 e-mail: info.uk@insulation.kingspan.com website: www.insulation.kingspan.com APPROVAL INSPECTION

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report BS 6853: 1999 Incorporating Amendment No. 1 tests to specific requirements of Table 5 on Controltac 180 on 3mm Aluminium coated with EP300/Hydro Topcoat (Axalta, dft 100µm) Prepared

More information

HILTI CP 674 Cavity Closure For Rainscreen / Cladding Systems

HILTI CP 674 Cavity Closure For Rainscreen / Cladding Systems Data Sheet HILTI CP 674 Cavity Closure For Rainscreen / Cladding Systems The enclosed pages are taken from the Hilti Firestop Systems Manual Edition April 2011 Supported by additional standard details

More information

Title: The Fire Resistance Performance of PRT and PRC, Side and Centre-Opening, Vandal Resistant, Lift Landing Doorsets. WF Assessment Report No:

Title: The Fire Resistance Performance of PRT and PRC, Side and Centre-Opening, Vandal Resistant, Lift Landing Doorsets. WF Assessment Report No: assessment report Title: The Fire Resistance Performance of PRT and PRC, Side and Centre-Opening, Vandal Resistant, Lift Landing Doorsets WF Assessment Report No: 183968A Prepared for: Klefer SA Kilkis

More information

Fire performance of curtain walls and rainscreens

Fire performance of curtain walls and rainscreens Technical Note No. 73 Fire performance of curtain walls and rainscreens Curtain walls are normally used for areas of the building envelope that are not required to be fire resisting but they still require

More information

Impact of NFPA 285 on Air Barrier Specification and Design

Impact of NFPA 285 on Air Barrier Specification and Design Impact of NFPA 285 on Air Barrier Specification and Design Charlotte Metzler Amanda Stacy, LEED Green Associate WSP Building Enclosures Air Barrier Association of America (ABAA) is a Registered Provider

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard LPS 1208: Issue 2.2 This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information purposes only. Its use for testing, assessment,

More information

Xtratherm Thin-R Thermal Liner (XT/TL Grade)

Xtratherm Thin-R Thermal Liner (XT/TL Grade) CERTIFICATE NO. 03/0183 DETAIL SHEET 4 Xtratherm Thin-R Thermal Liner (XT/TL Grade) PRODUCT DESCRIPTION: This Detail Sheet relates to Xtratherm Thin-R Thermal Liner, as defined in NSAI Agrément Certificate

More information

Xtratherm Thin-R Thermal Liner (XT/TL Grade)

Xtratherm Thin-R Thermal Liner (XT/TL Grade) CERTIFICATE NO. 03/0183 DETAIL SHEET 4 Xtratherm Thin-R Thermal Liner (XT/TL Grade) PRODUCT DESCRIPTION: This Detail Sheet relates to Xtratherm Thin-R Thermal Liner, as defined in NSAI Agrément Certificate

More information

CALL TO TALK TO THE SAS TEAM

CALL TO TALK TO THE SAS TEAM CALL 01647 24620 TO TALK TO THE SAS TEAM new EIFS.indd 1 1 8/29/2013 11:21:00 AM Contents Insulation overview Page 4 ProRend EIFS Adhesive System Installation Page 6 ProRend EIFS Rail System Installation

More information

Title: The Fire Resistance Performance of Modified Timber Based Panelled Doorsets. WF Assessment Report No: Issue 8.

Title: The Fire Resistance Performance of Modified Timber Based Panelled Doorsets. WF Assessment Report No: Issue 8. Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance

More information

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade)

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade) CERTIFICATE NO. 03/0183 DETAIL SHEET 1 Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade) PRODUCT DESCRIPTION This Detail Sheet relates to Xtratherm Thin-R Partial Fill Cavity Wall Board, as

More information

Title: The Fire Resistance Performance of PRT and PRC, Side and Centre-Opening Lift Landing Doorsets. WF Assessment Report No: Prepared for: Klefer SA

Title: The Fire Resistance Performance of PRT and PRC, Side and Centre-Opening Lift Landing Doorsets. WF Assessment Report No: Prepared for: Klefer SA Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance

More information

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade)

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade) CERTIFICATE NO. 03/0183 DETAIL SHEET 1 Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade) PRODUCT DESCRIPTION This Detail Sheet relates to Xtratherm Thin-R Partial Fill Cavity Wall Board, as

More information

RH & RV CAVITY BARRIERS

RH & RV CAVITY BARRIERS RH & RV CAVITY For use in external envelope or fabric of buildings SIDERISE RH OPEN STATE HORIZONTAL AND RV VERTICAL CAVITY BARRIER RANGE REPRESENT THE DEFAULT CHOICE FOR MARKET-LEADING, HIGH-PERFORMANCE

More information

European Technical Approval ETA-03/0014

European Technical Approval ETA-03/0014 British Board of Agrément Bucknalls Lane Garston Watford Herts WD25 9BA Tel: + 44 (0) 1923 665300 Fax: + 44 (0) 1923 665301 e-mail: mail@bba.star.co.uk Authorised and notified according to Article 10 of

More information

FOCAL POINT RENDAPANEL TM CLADDING SYSTEM

FOCAL POINT RENDAPANEL TM CLADDING SYSTEM FOCAL POINT RENDAPANEL TM CLADDING SYSTEM strength and durability SYSTEM INFORMATION & TECHNICAL SPECIFICATION V4 2002 Page 1 of 7 INTRODUCTION Monolithic Light Weight Cement Render Cladding RendaPanel

More information

Title: The Fire Resistance Performance of Modified Timber Based Panelled Doorsets. WF Assessment Report No: Issue 6.

Title: The Fire Resistance Performance of Modified Timber Based Panelled Doorsets. WF Assessment Report No: Issue 6. Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance

More information

Solutions. Main Headings Third Issue July Insulation DON T COMPROMISE ON THERMAL PERFORMANCE, FIRE PERFORMANCE AND ENVIRONMENTAL RESPONSIBILITY

Solutions. Main Headings Third Issue July Insulation DON T COMPROMISE ON THERMAL PERFORMANCE, FIRE PERFORMANCE AND ENVIRONMENTAL RESPONSIBILITY Insulation Main Headings Third Issue July 2017 See rear cover for applicable countries Kingspan Solutions Wall Insulation DON T COMPROMISE ON THERMAL PERFORMANCE, FIRE PERFORMANCE AND ENVIRONMENTAL RESPONSIBILITY

More information

Henry NFPA 285 Air Barrier Assemblies

Henry NFPA 285 Air Barrier Assemblies Henry NFPA 285 Air Barrier Assemblies Effective 09/27/2018 Supersedes all previous versions The following Henry air barrier assemblies meet the performance requirements of NFPA 285 as required by the International

More information

Deer Ridge Consulting, Inc.

Deer Ridge Consulting, Inc. Deer Ridge Consulting, Inc. Code Compliance Research Report 505 Deer Ridge Lane Ararat, VA 24053 Office: 276-755-9162 Fax: 866-441-1054 www.deer-ridge-consulting.com Subject: NCFI 12-008 Spray Polyurethane

More information

An introduction to Part L U-values

An introduction to Part L U-values December 2010 An introduction to Part L This document provides a wide selection of building fabric constructions with their associated. It has been produced a support to our publication An introduction

More information

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016.

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg ESR 2562 Reissued 08/206 This report is subject to renewal 08/208. DIVISION: 07 00 00

More information

APPLICATION: Floor insulation precast suspended concrete floor. Products: Jabfloor 70, 100, 150, 200, 250

APPLICATION: Floor insulation precast suspended concrete floor. Products: Jabfloor 70, 100, 150, 200, 250 46 APPLICATION: Products:,,, 200, 250 insulation can be used over all types of precast suspended concrete floor systems including beam and block and hollow core plank. It is available in a range of grades

More information

TRESPA WALL CLADDING SYSTEMS SYSTEM 700 ALUMINIUM SUB-FRAME SYSTEM

TRESPA WALL CLADDING SYSTEMS SYSTEM 700 ALUMINIUM SUB-FRAME SYSTEM Trespa International B.V. P O Box 110 6000 AC Weert The Netherlands Tel: 00 31 0495 458358 Fax: 00 31 0495 458570 e-mail: infonederland@trespa.com website: www.trespa.com APPROVAL INSPECTION TESTING CERTIFICATION

More information

XTRATHERM XTROLINER (XO) XTRATHERM XTROLINER RAINSCREEN BOARD (XO/RS)

XTRATHERM XTROLINER (XO) XTRATHERM XTROLINER RAINSCREEN BOARD (XO/RS) Xtratherm Ltd Liscarton Industrial Estate Kells Road Navan Co Meath Ireland Tel: 00 353 46 906 6000 Fax: 00 353 46 906 6090 e-mail: info@xtratherm.com website: www.xtratherm.com APPROVAL INSPECTION TESTING

More information

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1

Design No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1 FIRESTOP JOINT SPRAY CFS-SP WB SILICONE JOINT SPRAY CFS-SP SIL F-RATING 2-HR. 2-HR. T-RATING -HR. -HR. APPLICATION THICKNESS PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table /8" WET FILM (/6"

More information

Regulations Detail Sheet 1

Regulations Detail Sheet 1 Ancon Building Products President Way President Park Sheffield S4 7UR Tel: 0114 275 5224 Fax: 0114 276 8543 e-mail: info@ancon.co.uk website: www.ancon.co.uk Agrément Certificate No 99/3659 Fourth issue*

More information

Part E robustdetails. robustdetails. January 2018 Update Pack

Part E robustdetails. robustdetails. January 2018 Update Pack Part E Pack Dear Colleague, The first Update Pack of the year, and the first welcome from me as Chief Executive. Although new to the role, I have been with the company for nine years with responsibility

More information

BS EN :2006 +A1:2010

BS EN :2006 +A1:2010 BRE Test Report Weathertightness test to BS EN 14351-1:2006 +A1:2010 clauses 4.2, 4.5 and 4.14 on an LR4 Conservation rooflight for Lumen Rooflights Ltd Prepared for: Paul Trace Date: 14 March 2016 Report

More information

APPLICATION: Floor insulation precast suspended concrete floor. Products: Jabfloor Premium 70 and 100

APPLICATION: Floor insulation precast suspended concrete floor. Products: Jabfloor Premium 70 and 100 38 APPLICATION: Products: 70 and 100 insulation can be used over all types of precast suspended concrete floor systems including beam and block and hollow core plank. It is available in a range of grades

More information

Insulation for Ventilated Rainscreen Cladding Systems

Insulation for Ventilated Rainscreen Cladding Systems I n s u l a t i o n Third Issue September 2010 Insulation for Ventilated Rainscreen Cladding Systems COMPLIANCE WITH APPROVED DOCUMENT B2 Low Energy - Low Carbon Buildings Insulation for Ventilated Rainscreen

More information

EasylationWall. External Wall Insulation System. bringing european innovation

EasylationWall. External Wall Insulation System. bringing european innovation EasylationWall External Wall Insulation System bringing european innovation EasylationWall... the new External Wall Insulation System using brick slips for stunning façades. EXTERNAL WALL INSULATION (EWI)

More information

External Steel Stud and Top Hat Walls. Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185

External Steel Stud and Top Hat Walls. Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185 Details SYSTEMS 176 NON-FIRE RATED SYSTEMS 176 FIRE RATED SYSTEMS 178 BRICK VENEER SYSTEMS 183 INSTALLATION 185 GENERAL REQUIREMENTS 185 FRAMING 185 PLASTERBOARD LAYOUT 189 PLASTERBOARD FIXING 190 EXTERIOR

More information

Jabfill High Performance (HP)

Jabfill High Performance (HP) Jabfill High Performance (HP) Wall insulation full-fill cavity wall insulation Jabfill High Performance (HP) is a BBA-certified cavity-wall insulation system. It is designed to be installed into new masonry

More information

Certificate of Assessment

Certificate of Assessment Certificate of Assessment Certificate Number: 159/13 Revision: 03 Kemsley Fields Business Park Sittingbourne Kent ME9 8SR is authorised to use the BRE Global Certification Mark in association with the

More information

Title: The Fire Resistance Performance of EI60, Side and Centre-Opening Lift Landing Doorsets. WF Assessment Report No: /A.

Title: The Fire Resistance Performance of EI60, Side and Centre-Opening Lift Landing Doorsets. WF Assessment Report No: /A. Title: The Fire Resistance Performance of EI60, Side and Centre-Opening Lift Landing Doorsets WF Assessment Report No: 167510/A Prepared for: Klefer A.E. Kilkis Industrial Area 61100 Stavroxori. Grecia

More information

BRE Test Report. Load and Slip Testing of 4 types of Paving Light and 1 Smoke Outlet Panels. Prepared for: Marc Parkinson. BRE Watford, Herts WD25 9XX

BRE Test Report. Load and Slip Testing of 4 types of Paving Light and 1 Smoke Outlet Panels. Prepared for: Marc Parkinson. BRE Watford, Herts WD25 9XX BRE Test Report Load and Slip Testing of 4 types of Paving Light and 1 Smoke Outlet Panels Prepared for: Marc Parkinson Date: 14 March 2018 Report Number: P111484-1000 Issue: 1 BRE Watford, Herts WD25

More information

June Residential New Build Render and cladding walls

June Residential New Build Render and cladding walls June 2010 Residential New Build 2.5.4 Render and cladding walls Residential new build 2.0 Residential New Build Render and Clad Contents Introduction find online page Solution optimiser and pathfinder

More information

Multi-layer Insulation Blanket for

Multi-layer Insulation Blanket for Multi-layer Insulation Blanket for Walls Thermal Insulation in a thin, flexible, multi-layer membrane High performance wall insulation Fully certificated Thermally tested in accordance with EN12667 High

More information

URSA MINERAL WOOL URSA Façade N32 & Façade N35

URSA MINERAL WOOL URSA Façade N32 & Façade N35 RAINSCREEN CLADDING 074_Layout 1 09/10/2017 09:32 Page 1 URSA UK LTD Crest House 102-104 Church Road Teddington, Middlesex TW11 8PY United Kingdom Tel : 020 8977 96 97 Fax : 020 8977 94 56 Web : www.ursa-uk.co.uk

More information

Exterior Wall Solutions Building Shell

Exterior Wall Solutions Building Shell A strong, water tight and thermally insulated building shell will ensure the buildings sustainability of usage over time. The Exterior Shell is the most important factor of protection to ensure that the

More information

June Residential New Build Timber Frame Walls

June Residential New Build Timber Frame Walls June 2010 Residential New Build 2.5.2 Timber Frame Walls Residential new build 2.0 Residential New Build Timber Frame Walls Contents Introduction find online page Solution optimiser and pathfinder 186

More information

EUROPEAN ORGANISATION FOR TECHNICAL APPROVALS

EUROPEAN ORGANISATION FOR TECHNICAL APPROVALS E TA TECHNICAL REPORT Fire Resistance Tests for Cavity Barriers TR 31 Edition October 2008 EUROPEAN ORGANISATION FOR TECHNICAL APPROVALS EOTA TECHNICAL REPORT TR 031 Fire Resistance Tests for Cavity Barriers

More information

TR26 LPC/FM / TR27 LPC/FM

TR26 LPC/FM / TR27 LPC/FM Insulation A4/8 TR26/27 AW1955 Issue 2 May 2015 TR26 LPC/FM / INSULATION FOR WATERPROOFED FLAT ROOFS Super high performance rigid thermoset insulation LPCB approved to LPS 1181: Part 1 FM approved for

More information

TR26 LPC/FM / TR27 LPC/FM

TR26 LPC/FM / TR27 LPC/FM Insulation A4/8 TR26/27 AW2163 Issue 2 Jan 2017 TR26 LPC/FM / TR27 LPC/FM INSULATION FOR WATERPROOFED FLAT ROOFS Super high performance rigid thermoset insulation LPCB approved to LPS 1181: Part 1 FM approved

More information

April Section 4.3. Separating Floors

April Section 4.3. Separating Floors April 2012 Section Separating Floors Separating Floors Separating floors Separating floor design Mineral wool products offer substantial advantages when used as both sound absorbent and resilient layers

More information

Use of Coatings to Improve Fire Resistance of Wood

Use of Coatings to Improve Fire Resistance of Wood Reprint from Standard Technical Publication 826 Robert H. White 1 American Society for Testing and Materials 1916 Race Street, Philadelphia, PA 19103 1984 Use of Coatings to Improve Fire Resistance of

More information

June Non - Residential Refurbishment Separating floors

June Non - Residential Refurbishment Separating floors June 2010 Non - Residential Refurbishment 5.6.2 Separating floors Non-residential refurbishment 5.0 Non-residential Refurbishment Separating Floors Contents Introduction find online page Solution optimiser

More information

Wind uplift testing on the Click Fit PV mounting system to MCS012. Prepared for: Gary Bowden Cleaner Air Solutions UK Ltd.

Wind uplift testing on the Click Fit PV mounting system to MCS012. Prepared for: Gary Bowden Cleaner Air Solutions UK Ltd. Wind uplift testing on the Click Fit PV mounting system to MCS012 Prepared for: Gary Bowden Cleaner Air Solutions UK Ltd 4 th October 2010 Prepared by Name Dr P Blackmore Position Associate Director, Building

More information

June Non - Residential New Build Partition walls

June Non - Residential New Build Partition walls June 2010 Non - Residential New Build 4.6.3 Partition walls Non-residential new build 4.0 Non-residential New Build Partition Walls Contents Introduction find online page Solution optimiser and pathfinder

More information

KOOLTHERM K8 CAVITY BOARD Isolant pour murs creux Kerndämmung

KOOLTHERM K8 CAVITY BOARD Isolant pour murs creux Kerndämmung CI/SfB Designated by Government to issue European Technical Approvals Product Kingspan Insulation Limited Pembridge Leominster Herefordshire HR6 9LA Tel: 01544 388601 Fax: 01544 388888 e-mail: info@insulation.kingspan.com

More information

This was followed by a Part 2 experimental scoping study focusing on the issue of external fire spread, to be covered in next month s issue.

This was followed by a Part 2 experimental scoping study focusing on the issue of external fire spread, to be covered in next month s issue. 1 External fire spread: new research In a two-part feature, BRE Global reports on the latest findings to come out of its work on the Investigation of Real Fires for the Department for Communities and Local

More information

Agrément Certificate 16/5352 website: Product Sheet 2

Agrément Certificate   16/5352 website:  Product Sheet 2 Saint-Gobain Construction Products UK Limited trading as Celotex Lady Lane Industrial Estate Hadleigh Ipswich Suffolk IP7 6BA Tel: 01473 822 093 Fax: 01473 820880 Page 1 of 15 Agrément Certificate e-mail:

More information