1 SPECIFICATION SHEET JUNCTION BOXES 8484-SS DOCUMENT NO REV SHEET 1 OF 1 CLIENT : HPCL, MUMBAI PROJECT : LPG BOTTLING PLANT, ANANTAPUR PLANT : - LPG BOTTLING PLANT ISSUED FOR : PROPOSAL ENQUIRY ORDER FINAL GENERAL Res. Stds. BIS IEC Encl. Docs. ES 8201 Make Maker s type Sample Required Yes No AMBIENT CONDITIONS Temp. Max. / Min. / Design Ref. 45 / 15 / 45 O C Rel. Humidity 100% Alt. Above Sea Level <1000M ATMOSPHERIC Dusts Dusty POLLUTION Vapours Area Safe Hazardous Hazardous area classification Zone Encl.Gr. Temp. Class Location Indoor Outdoor TESTS Routine Type Others : As per agreement BASIC DATA Item 240V, 1 Ph., 50Hz,HOSE PROOF JUNCTION BOX Quantity 19 Nos. Rated Voltage 240V + 10% Rated Frequency 50HZ + 5% Rated Current 16A No. of Phases & Wires 1 PHASE, 3 WIRE Application INDOOR USE Material of Enclosure CAST ALUMINIUM(LM-6) Shape of Enclosure CIRCULAR Degree of Protection IP-55 Addl. Degree of Protection - Type of Cover SUITABLE FOR ABOVE No. of Outlets 4 PAINTING Type EPOXY ELECTROSTATIC POWDER COATING Shade 631 OF IS:5 SPARE Required REQUIRED Duration 2 YEARS No. of Terminals SUITABLE FOR 3X2.5 SQ.MM (CU) XLPE, FRLS CABLE Cable gland DOUBLE COMPRESSION NI PLATED BRASS CABLE GLAND CABLE Incoming 3X2.5 SQ. MM (cu) XLPE FRLS SIZE Outgoing 3X2.5 SQ. MM (cu) XLPE FRLS NOTES:- Note: 1. 4 Nos. Double compression Ni plated brass cable gland with 2 No. Stopping plug suitable for 3x2.5sq mm(cu), XLPE FRLS cable shall be provided for each junction box ISSUED FOR ENQUIRY MANISH RBM SHREE REV REV DATE EFF DATE PURPOSE PREPD REVWD APPD FORM NO: F3 REV2 SS-8201Z:\8484 Engineering Consultancy Services on structural design etc at HPCL, Mumbai\electrical\rbmeena\8484 PLANT PACKAGE (ENQUIRY)\ SS8201- JB.doc All rights reserved

2

3 ENGINERING STANDARD ES: DOCUMENT NO REV JUNCTION BOX SHEET 2 OF 8 CONTENTS SECTION NUMBER DESCRIPTION SHEET NUMBER 1.0 SCOPE STANDARDS TO BE FOLLOWED SERVICE CONDITIONS GENERAL DESIGN & CONSTRUCTIONAL FEATURES 5.0 SPECIAL FEATURES FOR JUNCTION BOXES FOR HAZARDOUS AREA PAINTING TESTS & INSPECTION PACKING DRAWINGS AND DOCUMENTS SPARES DEVIATIONS 7 ANNEXURE - I DOCUMENTATION FOR JUNCTION BOXES 8 FORM NO: F2 REV1 All rights reserved

4 ENGINERING STANDARD ES: DOCUMENT NO REV JUNCTION BOX SHEET 3 OF SCOPE 1.1 This standard covers the technical requirements of design, manufacture, testing and inspection at works and delivery in well packed condition of junction boxes. 1.2 This standard shall be read in conjunction with relevant specification sheet and other relevant references as specified their in. 2.0 STANDARDS TO BE FOLLOWED 2.1 The design, manufacture and testing of the equipment covered by this standard shall comply with the latest issue of relevant Indian standards unless otherwise specified. Equipment complying with equivalent IEC standards shall also be acceptable. 2.2 Flameproof & increased safety junction boxes shall in addition, comply with the requirement as laid down in IS: 2148 & IS: 6381 respectively. 2.3 The design and constructional features of the junction boxes offered shall also comply with the provision of latest issue of the Indian Electricity Rules and other relevant Statutory Rules & Regulations. The supplier shall, whenever necessary, make suitable modification in the equipment to comply with the above mentioned rules. 2.4 Wherever any requirement laid down in this standard differs from that in Indian Standard specifications, the requirement specified herein shall prevail. 3.0 SERVICE CONDITIONS 3.1 Ambient Conditions These shall be as indicated in specification sheet. 3.2 System Details The details of power supply system shall be as indicated in the specification sheet. 4.0 GENERAL DESIGN & CONSTRUCTIONAL FEATURES 4.1 The junction boxes shall be dust and weather proof and suitable for installation outdoors without extra protection. The degree of protection shall be IP-55 as per IS: The junction boxes shall be of die cast aluminium alloy LM-6 with domed / suspension covers. As an alternative to cast aluminium, fibre glass enclosure is also acceptable if specified in specification sheet. 4.3 The casting of the junction boxes and their cover shall be pressure die cast. The casting shall be uniform and free from blow holes. All mechanical surfaces shall be free from burrs, dents and internal roughness. 4.4 All external hardware of diameter less than 8 mm shall be of stainless steel and those of diameter 8 mm and above shall be of mild steel cadmium plated or zinc FORM NO: F2 REV1 All rights reserved

5 ENGINERING STANDARD ES: DOCUMENT NO JUNCTION BOX SHEET 4 OF 8 passivated. For fibre glass enclosure Nylon PVC bolts of diameter 8 mm may be used. 4.5 The clearances and creepage distances shall be maintained inside the junction boxes as per relevant Indian standard. 4.6 The junction boxes shall be suitable for wall / structure / ceiling mounting and necessary arrangement for mounting the same shall be provided. 4.7 The junction boxes shall be provided with continuous gasket made of neoprene or synthetic rubber to prevent ingress of dust. The gasket shall be held in position in groove provided in the enclosure and shall be pressed all around uniformly by suitably shaped projection of the door. Gaskets simply glued to the surface are not acceptable. 4.8 The junction boxes housing terminal block shall be moulded type made of DMC / Fibre glass. Threaded terminals shall be made of brass (nickel plated or tinned) and provided with two tightening threaded nuts and four washers all made of brass (nickel plated or tinned). The terminals shall have two shorting links each horizontally placed connecting three terminals. 4.9 The terminal block shall be fitted with junction boxes base by means of 2 nos. 1/2 long nickel plated brass screws The junction boxes shall be provided with two nos. external earthing terminals and 1 no. internal earthing terminal All live parts inside the junction boxes shall be insulated and shall withstand a test voltage of 2.5 KV for 1 minute The junction boxes shall be provided with heavy duty double compression type rolled Al cable glands to suit the cable entries Threaded blanking plugs shall be provided for junction boxes to plug out the entries not in use as indicated in bill of quantities enclosed The junction boxes shall be provided with a blank stainless steel tag plate fastened to the junction box top cover with two stainless steel screws. The plate shall be at least 25 mm wide, 100 mm long and 1 mm thick For flameproof / increased safety junction boxes, the manufacturer shall submit copies of test certificates from statutory authorities clearly stating that the junction boxes as well as cable glands / blanking plugs are suitable for hazardous area as indicated in the specification sheet Amp. Junction Box The junction boxes shall be 4 way dome cover type The dimensions of the junction boxes with their cover and accessories shall be generally as per PDS: E-547. REV FORM NO: F2 REV1 All rights reserved

6 ENGINERING STANDARD ES: DOCUMENT NO JUNCTION BOX SHEET 5 OF The junction boxes housing terminal block shall be moulded type made of DMC / Fibre glass as per Drg. no. PDS: E Amp. Junction Box The junction boxes shall be 3 / 4 way dome cover type The minimum internal diameter of the box shall be 240 mm. 5.0 SPECIAL FEATURES FOR JUNCTION BOXES FOR HAZARDOUS AREA 5.1 For increased safety junction boxes, the terminals shall be provided with positive locking device against loosening. 5.2 The enclosure shall be in addition, of increased safety execution, Exe, as per relevant standard and shall be suitable for installation specified in specification sheet. 5.3 The junction boxes shall be liberally dimensioned in order to avoid temperature rise inside the enclosure which may damage the insulating materials or gaskets employed therein. 5.4 Cables shall enter the terminal box through increased safety compression type cable glands. From the terminal chamber to the main enclosure, the connections shall be made through proper bushings. 5.5 An additional earthing terminal inside the terminal chamber shall be provided. 5.6 The junction boxes shall be provided with Brass-Nickel plated shorted links. The terminal block shall be made of non-hygroscopic compound. Bakelite / Hylam shall not acceptable. 5.7 All screws / bolts and nuts shall be of stainless steel. 5.8 Junction boxes and cable glands must be certified by Statutory Authorities for use in the specified hazardous area. Equipments certified by overseas authorities shall obtain certificate of compliance / letter of opinion from respective statutory authorities. 5.9 Duly wired prototype samples for junction boxes shall be submitted for scrutiny as and when called for Type Test certificates for increased safety type junction boxes and cable glands along with blanking plugs shall be supplied. 6.0 PAINTING 6.1 Epoxy based electrostatic powder coating paint shall be provided on exterior surface while the interior of junction boxes shall be painted with anti-condensate paint. The painting shall be able to withstand corrosive atmosphere as specified in specification sheet. REV FORM NO: F2 REV1 All rights reserved

7 ENGINERING STANDARD ES: DOCUMENT NO JUNCTION BOX SHEET 6 OF Unless otherwise specified, the finishing shade shall be grey having shade no. 632 as per IS The terminal block of junction boxes shall be painted with Red, Yellow, Blue & Black colour for phase indication. 7.0 TESTS AND INSPECTION 7.1 The junction boxes shall be routine tested as per relevant standards. 7.2 Additional tests, wherever specified, shall be carried out on one unit of each rating. 7.3 The procedure & extent of the physical checks, routine & type test shall be governed by Quality Assurance Plan mutually agreed and approved by Inspection Authority. 7.4 All the above mentioned tests shall be carried out in the presence of purchaser s representative. In addition, the equipment shall be subjected to stage inspection at works and inspection at site for final acceptance. 7.5 These inspections shall, however, not absolve the vendor from their responsibility for making good any defect which may be noticed subsequently. 8.0 PACKING Each junction box and cable gland shall be suitably packed and protected from damage due to transportation, loading and unloading. Threaded fittings shall have plastic caps to protect the threading. 9.0 DRAWINGS AND DOCUMENTS 9.1 Drawings and documents as per Annexure-I shall be supplied, unless otherwise specified. 9.2 All drawings and documents shall have the following descriptions written boldly: - Name of client - Name of consultant - Enquiry / order number with plant / project name - Motor Code No. and Description 10.0 SPARES 10.1 Spares for operation and maintenance Item wise unit prices of spare parts for the following items, as applicable, shall be offered along with the main equipment with recommended quantity for the period as indicated in specification sheet. i) Cable glands ii) Threaded Plug REV FORM NO: F2 REV1 All rights reserved

8 ENGINERING STANDARD ES: DOCUMENT NO REV JUNCTION BOX SHEET 7 OF 8 iii) iv) Terminal blocks Terminal bushings 10.2 Commissioning Spares Commissioning spares, as required, shall be supplied with the main equipment. Item wise list of recommended commissioning spares shall be furnished for approval Any other spare parts not specified, but required, shall also be quoted along with the offer All spare parts shall be identical to the parts used in the equipment DEVIATIONS 11.1 Deviations, if any, from this standard shall be clearly indicated in the offer with reasoning Deviations, if any, from the data furnished in specification sheet shall be indicated therein beside the data by encircling it. FORM NO: F2 REV1 All rights reserved

9 ENGINERING STANDARD ES: DOCUMENT NO REV JUNCTION BOX SHEET 8 OF 8 ANNEXURE - I DOCUMENTATION FOR JUNCTION BOXES Sl. Documents Required (Y / N) Document Description No. With Bid For Approval Final 1. Specification Sheet, duly completed Y Y Y 2. Technical Particulars, duly filled-in Y Y Y 3. Certified dimensional drawing, including mounting details Y Y Y 4. Drawing showing constructional details Y Y Y 5. Illustrative and Descriptive catalogues Y N Y 6. Spare parts list Y N Y 7. FLP/Exe certificates for junction boxes and terminals conforming to IEC/ISS (CMRI, CCE, DGFASLI and BARC for terminals) 8. Certificate for weather proof construction for junction boxes as per IPW-55 Y N Y Y N Y Note: 1. 4 hard copies & 1 soft copy shall be supplied with bid hard copies & 1 soft copy shall be supplied for approval after order within 4 weeks from the date of LOI hard copies & 2 soft copies in CD shall be submitted as final documents prior to despatch of the equipment. These shall be made in sets and supplied in fine plastic coated folder. Y - Yes, N - No FORM NO: F2 REV1 All rights reserved

10 TECHNICAL PARTICULARS JUNCTION BOXES 8484-TP DOCUMENT NO REV SHEET 1 OF 1 CLIENT : HPCL,MUMBAI PROJECT :LPG BOTTLING PLANT,ANANTPUR PLANT :LPG BOTTLING PLANT ISSUED FOR : PROPOSAL ENQUIRY ORDER FINAL GENERAL Item No. Ref. Std. Type of Junction Box Make Maker s type CONSTRUCTIONAL FEATURES Material of Construction Thickness of Enclosure Enclosure Protection Class Mounting Arrangement Cover Fixing Arrangement Gasketing Material External Cable Sizes Dimensions LX B X H / Dimensional Drg. Ref. No. Weight Painting Type Test Certificate No. Type Material of Construction Make Nos. of Terminals Material Type Current Rating Fixing Arrangement Make CABLE GLAND TERMINAL BLOCK ISSUED FOR ENQUIRY MANISH REV REV DATE EFF DATE PURPOSE PREPD REVWD APPD FORM NO: F3 REV2 TP-8201 All rights reserved

11

12 TECHNICAL ENQUIRY SPECIFICATION FOR HOSEPROOF ELECTRICAL ITEMS 8484-DS DOCUMENT NO. REV. Page 1 of 3 Documentation schedule for 125Watt HPMV and 160 Watt MLL Blended hose proof well glass lighting Fixture. With bid After Order Sl. (No. of Copies) For Approval For Final Documents No. To To To To (No. of To To PDIL HPCL PDIL HPCL weeks) PDIL HPCL 1. Specification sheet E 2. Technical particular E 3. Illustration & descriptive catalogue indicating general arrangement, light distribution, light absorption & utilisation factors, full load currents, power factors & power requirement for each type of fixture including control gear losses. 4. Sketch showing mounting arrangement with dimensions 5. Type of certificate for : a) Hose proof fixtures b) Flame proof fixtures c) Division 2 area fixtures E E E 6. Spare parts lists E 7. Test certificates E 8. Guarantee certificates E FORM NO: F1 REV2 All rights reserved

13 TECHNICAL ENQUIRY SPECIFICATION FOR HOSEPROOF ELECTRICAL ITEMS 8484-DS DOCUMENT NO. REV Page 2 of 3 Documentation schedule for hose proof Junction Boxes. With bid After Order Sl. (No. of Copies) For Approval For Final Documents No. To To To To (No. of To To PDIL HPCL PDIL HPCL weeks) PDIL HPCL 1. Specification sheet E 2. Technical particular E 3. Certified dimensional drawing, including mounted details E 4. Drawing showing construction details E 5. Illustrative and Descriptive catalogues E 6. Spare parts lists E 7. Certificate for weather proof construction for junction box as per IPW Test certificates E 9. Guarantee certificates E FORM NO: F2 REV1 Z:\8484 Engineering Consultancy Services on structural design etc at HPCL, Mumbai\electrical\rbmeena\8484 PLANT PACKAGE (ENQUIRY)\ DS for HOSE PROOF ITEMS Rev 0.doc(e2)

14 TECHNICAL ENQUIRY SPECIFICATION FOR HOSEPROOF ELECTRICAL ITEMS 8484-DS DOCUMENT NO. REV Page 2 of 3 Documentation schedule for 15 A switch socket Sl. No. Documents 1. Specification sheet, Technical Particulars completely filled in With bid (No. of Copies) To To PDIL HPCL To PDIL After Order For Approval For Final To (No. of To HPCL weeks) PDIL To HPCL E 2. General arrangement (GA) drawings E 3. Illustrative and descriptive literature E 3. Catalogue for bought out accessories E 4. Installation operation and maintenance manual E 5. Descriptive catalogue E 6. Guarantee certificates E 7. Test certificates E Documentation schedule for hose proof Lighting Sub - Dist. Board. With bid After Order Sl. (No. of Copies) For Approval For Final Documents No. To To To To (No. of To To PDIL HPCL PDIL HPCL weeks) PDIL HPCL 1. Specification sheet E 2. Technical particular E 3. General arrangement drg E 4. Schematic diagram E 5. Descriptive Literature of various equipment E 6. Test certificates E 7. Guarantee certificates E FORM NO: F2 REV1 Z:\8484 Engineering Consultancy Services on structural design etc at HPCL, Mumbai\electrical\rbmeena\8484 PLANT PACKAGE (ENQUIRY)\ DS for HOSE PROOF ITEMS Rev 0.doc(e2)

15

16

17

18

19

20

21

22

23

24

31-SDMS-03 REV. 01 SPECIFICATIONS FOR

31-SDMS-03 REV. 01 SPECIFICATIONS FOR 31-SDMS-03 REV. 01 SPECIFICATIONS FOR LOW VOLTAGE CABINET FOR POLE MOUNTED TRANSFORMER This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Description

More information

TENDER NO. PGVCL/PROC/HT SMC Meter Box/872

TENDER NO. PGVCL/PROC/HT SMC Meter Box/872 TECHNICAL SPECIFICATION FOR HT AMR METER BOXES MADE FROM GLASS REINFORCED POLYSTER SHEET MOULDING COMPOUNDS (SMC). 1.0 SCOPE: 1.1 This specification covers the design, manufacturing and testing of anticorrosive,

More information

JUNCTION BOX AND BAYMARSHALLING KIOSK

JUNCTION BOX AND BAYMARSHALLING KIOSK JUNCTION BOX AND BAYMARSHALLING KIOSK September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata

More information

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

37-SDMS-01 REV. 03 SPECIFICATIONS FOR 37-SDMS-01 REV. 03 SPECIFICATIONS FOR LOW VOLTAGE MOLDED CASE CIRCUIT BREAKERS FOR SERVICE CONNECTIONS This specification is property of SEC and subject to change or modification without any notice CLAUSE

More information

56-SDMS-01 REV. 01 SPECIFICATIONS FOR

56-SDMS-01 REV. 01 SPECIFICATIONS FOR 56-SDMS-01 REV. 01 SPECIFICATIONS FOR 13.8KV UNIT SUBSTATIONS This specification is property of SEC and subject to change or modification without any notice CONTENTS PAGE No. 1.0 SCOPE 3 2.0 CROSS REFERENCES

More information

TECHNICAL SPECIFICATION FOR SMC LT AMR METER BOXES MANUFACTURED FROM THERMOSETTING PLASTIC 1.0 SCOPE:

TECHNICAL SPECIFICATION FOR SMC LT AMR METER BOXES MANUFACTURED FROM THERMOSETTING PLASTIC 1.0 SCOPE: TECHNICAL SPECIFICATION FOR SMC LT AMR METER BOXES MANUFACTURED FROM THERMOSETTING PLASTIC 1.0 SCOPE: 1.1 This specification covers the design, manufacturing & testing of anticorrosive, dust proof, rust

More information

TECHNICAL SPECIFICATION FOR OUTDOOR TYPE DISTRIBUTION PLOT & SERVICE JUNCTION BOX

TECHNICAL SPECIFICATION FOR OUTDOOR TYPE DISTRIBUTION PLOT & SERVICE JUNCTION BOX TECHNICAL SPECIFICATION FOR OUTDOOR TYPE DISTRIBUTION PLOT & SERVICE JUNCTION BOX 1. Scope: This specification covers technical requirements of design, manufacture, testing at manufacturer s works, packing,

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA MATERIALS MANAGEMENT TITLE DRAG LINK CHAIN FEEDERS Phone: +91 431 2574091/2574046

More information

STANDARD TECHNICAL SPECIFICATION FOR ROTAMETER VOLUME - IIB. SPECIFICATION No: PE-SS I010

STANDARD TECHNICAL SPECIFICATION FOR ROTAMETER VOLUME - IIB. SPECIFICATION No: PE-SS I010 STANDARD TECHNICAL SPECIFICATION FOR ROTAMETER VOLUME - IIB SPECIFICATION No: PE-SS-999-145-I010 BHARAT HEAVY ELECTRICALS LIMITED POWER SECTOR PROJECT ENGINEERING MANAGEMENT DIVISION NOIDA, INDIA SPECIFICATION

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION 1.0 SPECIFICATION OF FLAMEPROOF DISTRIBUTION BOARD, FIXTURES, POWER DISTRIBUTION SYSTEM INCLUDING CABLE LYING & TERMINATION. 1.0.1 Scope The following Specification flameproof Distribution

More information

TABLE OF CONTENTS. FOREWORD... Error! Bookmark not defined. INTRODUCTION SCOPE NORMATIVE REFERENCES DRAWING...4

TABLE OF CONTENTS. FOREWORD... Error! Bookmark not defined. INTRODUCTION SCOPE NORMATIVE REFERENCES DRAWING...4 TITLE SPECIFICATION FOR FREE- STANDING 11 DATE: AUGUST 2006 PAGE: 1 OF 15 TABLE OF CONTENTS Page FOREWORD... Error! Bookmark not defined. INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DRAWING...4 4

More information

ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200

ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200 ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200 The GRD 4200 is an electronic earthing equipment for tankers during loading and unloading operations of flammable liquids in places with danger of explosion.

More information

Subject: Guidance on Corrosion Assessment of Ex Equipment

Subject: Guidance on Corrosion Assessment of Ex Equipment 1. Introduction Maintaining the integrity of Ex certified electrical equipment is a key barrier against Major Accident Hazards in the oil and gas industry. The integrity must be maintained to ensure that

More information

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 REVISION NO. 0 NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 PAGE NO. 1 OF 24 DATE OF ISSUE (MONTH/YEAR) TOTAL NO. OF PAGES (Including cover

More information

42-SDMS-02 SPECIFICATIONS FOR FIBERGLASS REINFORCED LOW VOLTAGE SERVICE CABINET FOR 800A BULK CUSTOMERS

42-SDMS-02 SPECIFICATIONS FOR FIBERGLASS REINFORCED LOW VOLTAGE SERVICE CABINET FOR 800A BULK CUSTOMERS SPECIFICATIONS FOR FIBERGLASS REINFORCED LOW VOLTAGE SERVICE CABINET FOR 800A BULK CUSTOMERS This specification is property of SEC and subject to change or modification without any notice C O N T E N T

More information

NEW GC-16 IN WEST KUWAIT MATERIAL REQUISITION FOR LEVEL GAUGE TABLE OF CONTENTS

NEW GC-16 IN WEST KUWAIT MATERIAL REQUISITION FOR LEVEL GAUGE TABLE OF CONTENTS TABLE OF CONTENTS Sh. 2 of 16 1 INTRODUCTION 4 1.1 Purpose 4 1.2 Definitions 4 1.3 Acronyms 4 1.4 Codes and Standard 5 1.5 Environmental Condition 6 1.6 Language 6 1.7 Units of Measurement 7 1.8 General

More information

SPECIFICATION FOR FRLS POWER CABLES

SPECIFICATION FOR FRLS POWER CABLES SPECIFICATION FOR FRLS POWER CABLES 1.0 SCOPE This specification cover the technical requirements of design, manufacture, testing and delivery to site of Power Cables of 1100V grade with FRLS PVC Sheathed,

More information

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH SPECIFICATIONS FOR LOAD BREAK SWITCH This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE CODES

More information

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 14 TECHNICAL SPECIFICATION FOR LT XLPE POWER CABLES (SPECIFICATION NO.MM/I/LTXLPE/2006) 1. SCOPE: The specification

More information

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES CEB STANDARD 030-1 : 1996 Specification for RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES CEYLON ELECTRICITY BOARD SRI LANKA Specification for RESIN FILLING TYPE JOINTING KITS FOR

More information

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES 11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE

More information

INTER PLANT STANDARD STEEL INDUSTRY

INTER PLANT STANDARD STEEL INDUSTRY INTER PLANT STANDARD STEEL INDUSTRY IPSS SPECIFICATION FOR PROTECTIVE PANELS FOR dc CRANES (Second Revision) Corresponding IS does not exist IPSS:1-10-013-11 Formerly : IPSS: 1-10-013-03 0. FOREWORD 0.1

More information

42-SDMS-03 SPECIFICATIONS FOR

42-SDMS-03 SPECIFICATIONS FOR SPECIFICATIONS FOR INSIDE ROOM FIBER GLASS REINFORCED POLYESTER METER BOXES This specification is property of SEC and subject to change or modification without any notice CONTENTS Clauses: Page No. 1 SCOPE

More information

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS PART 1: SCOPE AND CONDITIONS 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, off-loading and performance requirements of 33kV, 200 amp, triple pole Gang

More information

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification

More information

Meter Cup Board (MCB) for Single Phase Energy Meters

Meter Cup Board (MCB) for Single Phase Energy Meters DAKSHIN HARYANA BIJLI VITRAN NIGAM LIMITED SPECIFICATION NO.S-61/DD-161 Meter Cup Board (MCB) for Single Phase Energy Meters Issue of month:april,2006 TECHNICAL SPECIFICATION IN RESPECT OF METER CUPBOARD

More information

Maharashtra State Electricity Distribution Company Limited. SPECIFICATION NO. MMC: MSC-II/Multi Meter box/smc/2018/10 TECHNICAL SPECIFICATION FOR

Maharashtra State Electricity Distribution Company Limited. SPECIFICATION NO. MMC: MSC-II/Multi Meter box/smc/2018/10 TECHNICAL SPECIFICATION FOR Maharashtra State Electricity Distribution Company Limited SPECIFICATION NO. MMC: MSC-II/Multi Meter box/smc/2018/10 TECHNICAL SPECIFICATION FOR FOR MULTI-METER BOX SUITABLE FOR HOUSING 4/8/12/18 NOS.OF

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION SECTION -IV TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS LIGHT FITTINGS GROUP D Tender Notice No. NESCO Utility / O&M Materials/09 / 7519, dtd.08.07.16 Page 1 Group-D Sl no. Material Description Unit

More information

42-SDMS-01 REV. 04 SPECIFICATIONS FOR

42-SDMS-01 REV. 04 SPECIFICATIONS FOR 42-SDMS-01 REV. 04 SPECIFICATIONS FOR FIBER GLASS REINFORCED POLYESTER METER BOXES This specification is property of SEC and subject to change or modification without any notice CONTENTS Clauses: Page

More information

Glass Reinforced Polyester Enclosures BPG. Glass Reinforced Polyester Enclosures

Glass Reinforced Polyester Enclosures BPG. Glass Reinforced Polyester Enclosures BPG 42 The BPG range comprises 16 sizes of enclosure manufactured in glass reinforced polyester (GRP). This material is highly resistant to contamination from oils, fats, aliphatic and aromatic carbohydrates,

More information

PART- A ROTARY TABLE : 3000 X 4000 MM

PART- A ROTARY TABLE : 3000 X 4000 MM ROTARY TABLE : SIZE - 3000 X 4000 The BIDDER has to compulsorily meet the following requirements to get qualified for considering the technical offer for the ROTARY TABLE - 3000 X 4000 MM SL NO 1.0 REQUIREMENTS

More information

33-SDMS-02 SPECIFICATIONS FOR

33-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR MV AUTOMATIC LINE SECTIONLIZER UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS SECTION T I T L E PAGE NO.

More information

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION SECTION 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 - GENERAL 1.1 SUMMARY A. This section supplements all sections in this division, including pipe, fittings, valves, and connections for sprinkler

More information

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION GETCO/E/TS-C&C

More information

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS SPEC.NO. MSEDCL/ DIST:MSC-III/SPRING LOADED CONNECTOR BOX/05/10/R0/ 200510 TECHNICAL SPECIFICATIONS FOR TAMPER PROOF SERVICE CONNECTION BOX FOR L.T. LINES / CONSUMER MAINS (20.05.2010) Page 1 of 14 Clause

More information

Lighting Luminairies B-LTG-25 ERTL : CIMFR/TC/P/H702+CIMFR/TC/S/1092. DGMS : 199 (for oil mines)

Lighting Luminairies B-LTG-25 ERTL : CIMFR/TC/P/H702+CIMFR/TC/S/1092. DGMS : 199 (for oil mines) Lighting Luminairies MFW/193/IIC-IEC Ex'd', IIC, IP-66 FLP/WP. Integral / Non-integral Wellglass Luminary TECHNICAL DATA Enclosure Type Ex-'d',' Class-1, Zone/Division-1, Gas Groups IIC, hazardous area

More information

Technical Specification for LV ABC Fuse Switch Disconnectors

Technical Specification for LV ABC Fuse Switch Disconnectors Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

SUPPLY ERECTION TOTAL RATE AMOUNT RATE AMOUNT AMOUNT (Rs.) (Rs.) (Rs.) (Rs.) (Rs.)

SUPPLY ERECTION TOTAL RATE AMOUNT RATE AMOUNT AMOUNT (Rs.) (Rs.) (Rs.) (Rs.) (Rs.) SBI-AO2 Project Residency Rd Br-elect/RBO-4 SCHEDULE OF QUANTITIES FOR ELECTRICAL WORKS. DATE : 24/4/2018 Sl. No. DESCRIPTION OF WORK UNIT QTY 1 READYMADE FINAL DISTRIBUTION BOARDS Supply, Instillation,

More information

ELECTRICAL WORKS RELATED TO AC & UPS OF CMP GOC & IAD, LINGAMPALLY, HYDERABAD IN TWO BID SYSTEM THROUGH E-TENDER PRICE BID

ELECTRICAL WORKS RELATED TO AC & UPS OF CMP GOC & IAD, LINGAMPALLY, HYDERABAD IN TWO BID SYSTEM THROUGH E-TENDER PRICE BID SBI INFRA MANAGEMENT SOLUTIONS PVT.LTD. 3 rd Floor, Local Head Office,Bank Street, Koti, Hyderabad- 500095 On behalf of On behalf of On behalf of Cash Management Product GOC (CMP GOC) & Internal Audit

More information

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1 ANNEXURE TO TENDER NO. PUR42396GM DATED 06 th FEBRUARY 2014 SUPPLY OF 1.1KV GRADE LT POWER CABLES FOR THE PERIOD APRIL 2014 MARCH 2016 TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1 1.1 SCOPE

More information

42-SDMS-01 REV. 05 SPECIFICATIONS FOR

42-SDMS-01 REV. 05 SPECIFICATIONS FOR DATE: April 2017G 42-SDMS-01 REV. 05 SPECIFICATIONS FOR FIBERGLASS REINFORCED POLYESTER METERBOXES This specification is property of SEC and subject to change or modification without any notice C O N T

More information

MATERIAL SPECIFICATION FOR HIGH PRESSURE SODIUM LUMINAIRES FOR UNDERPASS LIGHTING

MATERIAL SPECIFICATION FOR HIGH PRESSURE SODIUM LUMINAIRES FOR UNDERPASS LIGHTING ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS.PROV 2434 November 2016 MATERIAL SPECIFICATION FOR HIGH PRESSURE SODIUM LUMINAIRES FOR UNDERPASS LIGHTING TABLE OF CONTENTS 2434.01 SCOPE 2434.02 REFERENCES

More information

660 Volts 630 & 800AMP

660 Volts 630 & 800AMP Ergon Energy Corporation Limited Technical Specification for Switch- Disconnectors and Fuse-Switch- Disconnectors 660 Volts 630 & 800AMP ETS-06-02-01 Check this is the latest Process Zone version before

More information

TECHNICAL SPECIFICATION FOR 3-PH SMC BOXES MADE FROM THERMOSETTING PLASTIC FOR 3-PH ENERGY METER.

TECHNICAL SPECIFICATION FOR 3-PH SMC BOXES MADE FROM THERMOSETTING PLASTIC FOR 3-PH ENERGY METER. TECHNICAL SPECIFICATION FOR 3-PH SMC BOXES MADE FROM THERMOSETTING PLASTIC FOR 3-PH ENERGY METER. 1.0 SCOPE: This specification covers the design, manufacturing and testing of anticorrosive, dust proof,

More information

STANDARD TECHNICAL SPECIFICATION FOR SIGHT FLOW INDICATOR VOLUME - IIB. SPECIFICATION No: PES

STANDARD TECHNICAL SPECIFICATION FOR SIGHT FLOW INDICATOR VOLUME - IIB. SPECIFICATION No: PES STANDARD TECHNICAL SPECIFICATION FOR SIGHT FLOW INDICATOR VOLUME - IIB SPECIFICATION No: PES-145-029 BHARAT HEAVY ELECTRICALS LIMITED POWER SECTOR PROJECT ENGINEERING MANAGEMENT DIVISION NOIDA, INDIA SPECIFICATION

More information

NPS/001/024 Technical Specification for Low Voltage Aerial Bundled Conductor Fittings

NPS/001/024 Technical Specification for Low Voltage Aerial Bundled Conductor Fittings Version:- 5.0 Date of Issue:- July 2017 Page 1 of 12 NPS/001/024 Technical Specification for Low Voltage Aerial Bundled Conductor Fittings 1. Purpose The purpose of this document is to outline the technical

More information

- Zone 1, 2, 21, 22 - Mechanical strength - Reliability over time - Instant, bright illumination

- Zone 1, 2, 21, 22 - Mechanical strength - Reliability over time - Instant, bright illumination SLED Painted aluminium body and cover - Zone 1, 2, 21, 22 - Mechanical strength - Reliability over time - Instant, bright illumination Tempered glass Ex e terminal board housing for fast connection Mounting

More information

Product Datasheet. Fire Hose Reel (Page 3)

Product Datasheet. Fire Hose Reel (Page 3) Product Datasheet Fire (Page 2) Fire Hose Reel (Page 3) Flush Type Hose Reel Cabinet (Page 4) GRP Fire cabinets are used for indoor and outdoor application with weatherproof and antistatic properties,

More information

SECTION PARK NON-SEGREGATED BUS SPECIFICATION

SECTION PARK NON-SEGREGATED BUS SPECIFICATION Page 1 of 5 SECTION ------- PARK NON-SEGREGATED BUS SPECIFICATION 1.0 SCOPE 1.1. This specification describes assemblies of 600V, 5Kv and 15Kv non-segregated bus duct, which will be installed indoors and

More information

MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. Ltd. (MUMBAI) SCHEDULE 'A' TECHNICAL SPECIFICATION FOR. 11 kv, 22 kv & 33 kv HORN GAP FUSES FOR

MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. Ltd. (MUMBAI) SCHEDULE 'A' TECHNICAL SPECIFICATION FOR. 11 kv, 22 kv & 33 kv HORN GAP FUSES FOR MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. Ltd. (MUMBAI) SCHEDULE 'A' TECHNICAL SPECIFICATION FOR 11 kv, 22 kv & 33 kv HORN GAP FUSES FOR DISTRIBUTION NETWORK IN MAHARASHTRA SPECIFICATION NO:DIST/MM/I/HGF2006

More information

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA 094: 2000 CEB STANDARD MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEB Standard

More information

SECTION 13. A. Extent of Work: The requirements of this section apply to the piping systems specified elsewhere in these specifications.

SECTION 13. A. Extent of Work: The requirements of this section apply to the piping systems specified elsewhere in these specifications. SECTION 13 PIPE, TUBE AND PART 1 - GENERAL 1.01 DESCRIPTION A. Extent of Work: The requirements of this section apply to the piping systems specified elsewhere in these specifications. 1.02 QUALITY ASSURANCE

More information

FIBRE GLASS CROSS ARMS FOR 33 KV LINES

FIBRE GLASS CROSS ARMS FOR 33 KV LINES REC Specification No Page 1 of 5 REC Specification No. 42/1987 (Revised 1997) FIBRE GLASS CROSS ARMS FOR 33 KV LINES FOREWORD Many countries are now extensively using line cross arms and other hardwares

More information

PART 7 Technical Specification for Overhead and Underground Service Connection works for the Year

PART 7 Technical Specification for Overhead and Underground Service Connection works for the Year PART 7 Technical Specification for Overhead and Underground Service Connection works for the Year 2016-17 Technical Specification for Overhead and Underground Service Connection works for the Year 2016-17

More information

All definitions are defined according to ANSI/AWWA C b. Flanged Joint: The flanged and bolted joint as described in ANSI/AWWA C110/A21.10.

All definitions are defined according to ANSI/AWWA C b. Flanged Joint: The flanged and bolted joint as described in ANSI/AWWA C110/A21.10. 21-02 SAN ANTONIO WATER SYSTEM SPECIFICATIONS FOR RESILIENT-SEATED GATE AND TAPPING VALVES FOR WATER SUPPLY SERVICE ANSI/AWWA C509-01 3 IN., 4 IN., 6 IN., 8 IN., 10 IN., 12 IN., 16 IN., & 20 IN. Revised

More information

T. SUNDUPALLI BRANCH (04427)

T. SUNDUPALLI BRANCH (04427) STATE BANK OF INDIA T. SUNDUPALLI BRANCH (04427) REGION 2, KADAPA RURAL TIRUPATI (A.O) ELECTRICAL WORK BILL OF QUANTITIES SL. NO. DESCRIPTION QTY. UNIT RATE AMOUNT Rs. Rs. 1 Supply, installation, testing

More information

STANDARD TECHNICAL SPECIFICATION FOR FLOW ORIFICE ASSEMBLY with ACCESSORIES

STANDARD TECHNICAL SPECIFICATION FOR FLOW ORIFICE ASSEMBLY with ACCESSORIES STANDARD TECHNICAL SPECIFICATION FOR FLOW ORIFICE ASSEMBLY with ACCESSORIES VOLUME - IIB SECTIONS-C & D SPECIFICATION No: PE-TS-XXX-145-I105A BHARAT HEAVY ELECTRICALS LIMITED POWER SECTOR PROJECT ENGINEERING

More information

Not Applicable DD/MM/YY Completed Forms to be submitted by 30/08/2013 : Hrs IST. Date of Opening for Technical Bids 30/08/2013 : 14.

Not Applicable DD/MM/YY Completed Forms to be submitted by 30/08/2013 : Hrs IST. Date of Opening for Technical Bids 30/08/2013 : 14. DETAIL INFORMATION Contact Person and Address M.NALLATHAMBI SENIOR MANAGER / CCDP PURCHASE DEPARTMENT/R&D and CR UNIT HPBP BHEL, TIRUCHY, INDIA PIN : 620 014 Email mnthambi@bheltry.co.in Telephone 0091

More information

NATIONAL CENTER FOR COMBUSTION RESEARCH AND DEVELOPMENT (NCCRD) INDIAN INSTITUTE OF TECHNOLOGY MADRAS CHENNAI , INDIA

NATIONAL CENTER FOR COMBUSTION RESEARCH AND DEVELOPMENT (NCCRD) INDIAN INSTITUTE OF TECHNOLOGY MADRAS CHENNAI , INDIA NATIONAL CENTER FOR COMBUSTION RESEARCH AND DEVELOPMENT (NCCRD) INDIAN INSTITUTE OF TECHNOLOGY MADRAS CHENNAI 600036, INDIA Ref. No. ICS/11-12/013/DSTX/TSUN Date: 24 Aug. 2016 Due date: 14 Sep. 2016 Item

More information

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION GETCO/E/TS C&C057/R0 DT.

More information

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS

DIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS PART 1 - GENERAL 01.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification sections, apply to work of this Section.

More information

SPECIFICATION CUM COMPLIANCE CERTIFICATION FOR PRESSURE TESTING PUMP

SPECIFICATION CUM COMPLIANCE CERTIFICATION FOR PRESSURE TESTING PUMP BHARAT HEAVY ELECTRICAL LIMITED Enquiry No. : UNIT'S ADDRESS Due Date : UNIT'S PHONE NOS. Supplier Qtn. No.: CONTACT PERSON'S NAME/DESIGN./PHONE NO. Date : E-MAIL (FROM PURCHASE DEPTT.) NOTE:- SPECIFICATION

More information

All definitions are defined according to ANSI/AWWA C

All definitions are defined according to ANSI/AWWA C SAN ANTONIO WATER SYSTEM SPECIFICATIONS FOR REDUCED-WALL, RESILIENT-SEATED GATE AND TAPPING VALVES FOR WATER SUPPLY SERVICE 4 IN. THROUGH 48 IN. ANSI/AWWA C515-01 July 2017 1. SCOPE This product specification

More information

TECHNICAL SPECIFICATION FOR CONDUCTOR HARDWARE FITTING FOR 11/22/33 kv OVERHEAD POWER LINES

TECHNICAL SPECIFICATION FOR CONDUCTOR HARDWARE FITTING FOR 11/22/33 kv OVERHEAD POWER LINES ANNEXURE - D SCHEDULE - `A' TECHNICAL SPECIFICATION FOR CONDUCTOR HARDWARE FITTING FOR 11/22/33 kv OVERHEAD POWER LINES SPECIFICATION NO:DIST/MM/I/CONDHARD-2006) INDEX -----------------------------------------------------------------------------------------------------------------------

More information

Maharashtra State Electricity Distribution Co. Ltd.

Maharashtra State Electricity Distribution Co. Ltd. Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO. MSEDCL/ DIST:MM-III/06/2006 SPECIFICATION FOR H.T.DISC INSULATORS 1 TECHNICAL SPECIFICATION FOR 11 KV 45 KN / 70 KN DISC. INSULATORS

More information

MATERIAL STANDARD FOR CABLES AND WIRES

MATERIAL STANDARD FOR CABLES AND WIRES MATERIAL STANDARD FOR CABLES AND WIRES CONTENTS : PAGE No. 1. SCOPE... 2 2. SERVICE CONDITIONS... 2 3. REFERENCES AND STANDARDS... 2 4. UNITS... 3 5. CABLE DESIGN AND CONSTRUCTION... 3 5.1 Applicable Cable

More information

L-SERIES: LTH3900 SPECIFICATIONS Stainless Steel Hollow Metal Sliding Fire Door System

L-SERIES: LTH3900 SPECIFICATIONS Stainless Steel Hollow Metal Sliding Fire Door System Version 5.22.13 L-SERIES: LTH3900 SPECIFICATIONS Stainless Steel Hollow Metal Sliding Fire Door System OPTIONS ARE LISTED IN BOLD, PLEASE MODIFY THESE AREAS AS NEEDED BASED ON YOUR PROJECT CONSULT MANUFACTURER

More information

TABLE OF CONTENTS FOREWORD... 3 INTRODUCTION SCOPE NORMATIVE REFERENCES DRAWING... 5

TABLE OF CONTENTS FOREWORD... 3 INTRODUCTION SCOPE NORMATIVE REFERENCES DRAWING... 5 TITLE SPECIFICATION FOR FREE- STANDING 11 DATE: NOVEMBER 2016 PAGE: 1 OF 16 COMPILED BY FUNCTIONAL RESP APPROVED BY AUTHORIZED BY... Z NGQWALA TECHNICIAN: TECHNOLOGY SERVICES... V. RAMPERSAD SENIOR ENGINEER:

More information

Mars. Pendant & Surface

Mars. Pendant & Surface Mars Pendant & Surface IK 10 85 45 C 119540 119550 1195 40W 50W W 3300lm 4125lm 5363lm 1123 x 94 1123 x 94 1423 x 94 * Accessories to be ordered separately. Weather proof metallic body linear ED fixture.

More information

Technical Specification for Outdoor Porcelain Station Post Insulators

Technical Specification for Outdoor Porcelain Station Post Insulators Ergon Energy Corporation Limited Technical Specification for Outdoor Porcelain ETS10-01-02 Specification ETS10-01-02 Ver 2 Contents 1. Purpose and Scope... 1 2. References... 1 2.1 Applicable Standards...

More information

11KV PORCELAIN INSULATORS AND FITTINGS

11KV PORCELAIN INSULATORS AND FITTINGS REC Specification 3/1971 (Revised 1993) 11KV PORCELAIN INSULATORS AND FITTINGS FOREWORD This specification was originally issued in 1971 on the basis of the decisions taken in the First and Second Standardisation

More information

TECHNICAL SPECIFICATIONS ELECTRICAL WORKS

TECHNICAL SPECIFICATIONS ELECTRICAL WORKS ELECTRICAL & ALLIED REPAIR WORK FOR STAFF HOSTEL AT IIT BOMBAY TECHNICAL SPECIFICATIONS ELECTRICAL WORKS Sheet 1 of 18 SECTION 1 INTRODUCTION: 1.0 GENERAL 1.1 This specification covers in brief the technical

More information

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION GETCO/E/TS C&C057/R0 DT.

More information

SPECIFICATIONS FOR Gas-to-Cable termination

SPECIFICATIONS FOR Gas-to-Cable termination Product GSM-145 1.0 APPLICATION: Gas-to-cable termination is a part of high voltage gas insulated indoor switchgear equipment. The component is intended for a high voltage system of 132 kv (AC), 50 Hz.

More information

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA 9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA Technical specification for 9KV/18KV 5KA Metal oxide Lightning Arrestors without Gap. ----------------------------------------------------------------------------------------------------------------

More information

QUOTATION REQUEST (QR) Quotation Request #: SI OA BILL OF QUANTITIES & PRICING

QUOTATION REQUEST (QR) Quotation Request #: SI OA BILL OF QUANTITIES & PRICING Invited Suppliers: QUOTATION REQUEST (QR) Quotation Request #: SI-0282018 OA BILL OF QUANTITIES & PRICING QR cover page 1 Signature Department Head: Date: 04 May '18 Date of submittal: May 11, 2018 before

More information

Maharashtra State Electricity Distribution Co. Ltd.

Maharashtra State Electricity Distribution Co. Ltd. Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO. MSEDCL/ DIST:MM-III/06/2006 SPECIFICATION FOR H.T.DISC INSULATORS 1 TECHNICAL SPECIFICATION FOR 11 KV 45 KN / 70 KN DISC INSULATORS

More information

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE METAL-ENCLOSED BUS MEDIUM VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. The medium

More information

Installation Manual. Retractable Ceiling Column Models 8301 & 8301PC

Installation Manual. Retractable Ceiling Column Models 8301 & 8301PC Retractable ceiling column Installation Manual Retractable Ceiling Column Models 8301 & 8301PC Overview The Retractable Ceiling Column is a convenient and cost-effective way of supplying medical gas and

More information

DUCTILE IRON PIPES AND FITTINGS DETAILED PRODUCTS SPECIFICATIONS

DUCTILE IRON PIPES AND FITTINGS DETAILED PRODUCTS SPECIFICATIONS DUCTILE IRON PIPES AND FITTINGS DETAILED PRODUCTS SPECIFICATIONS General All Materials shall be EN, ISO or equivalent standard and shall be supplied from approved manufacturers. According to the International

More information

GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM

GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM 1 GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM 1.01 WORK INCLUDED PART 1: GENERAL A. Provide for all labor, equipment, materials, and services to furnish and install VERSA SHIELD Window

More information

CONDUIT ACCESSORIES AND FIXINGS

CONDUIT ACCESSORIES AND FIXINGS CONDUIT ACCESSORIES AND FIXINGS L1 : EExd IIB CONNECTION FITTINGS B.. L2 : EExd IIC CONNECTION FITTINGS BMFA L3 : EExd IIC ELBOWS 90 ELF L4 : EExd IIC NIPPLES AND COUPLINGS NP - EM L5 : EExd IIC PLUGS

More information

POLYMER HOUSED SURGE ARRESTORS

POLYMER HOUSED SURGE ARRESTORS POLYMER HOUSED SURGE ARRESTORS March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091.

More information

JAMISON SOUND DOOR SPECIFICATIONS VERTICAL SLIDING SOUND REDUCTION DOOR - STC 53 POWERED OPERATION

JAMISON SOUND DOOR SPECIFICATIONS VERTICAL SLIDING SOUND REDUCTION DOOR - STC 53 POWERED OPERATION JAMISON SOUND DOOR SPECIFICATIONS VERTICAL SLIDING SOUND REDUCTION DOOR - STC 53 POWERED OPERATION PART 1 - GENERAL 1.1 APPLICABLE PUBLICATIONS: The publications listed below form a part of this specification

More information

TECHNICAL SPECIFICATION FOR SUPPLY OF WEDGE CONNECTOR TO BE USED IN POWER DISTRIBUTION SYSTEM

TECHNICAL SPECIFICATION FOR SUPPLY OF WEDGE CONNECTOR TO BE USED IN POWER DISTRIBUTION SYSTEM TECHNICAL SPECIFICATION FOR SUPPLY OF WEDGE CONNECTOR TO BE USED IN POWER DISTRIBUTION SYSTEM :: TECHNICAL SPECIFICATIONS:: Sr. No Technical Specification No./Revision Date of revision 1. GUVNL/CPRND/TS/P-018/Wedge

More information

10-SDMS-02 SPECIFICATIONS FOR BARE COPPER CONDUCTORS

10-SDMS-02 SPECIFICATIONS FOR BARE COPPER CONDUCTORS SPECIFICATIONS FOR BARE COPPER CONDUCTORS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

Technical Specification for. Insulators. Part 1. Insulators for High and Extra-High Voltage Overhead Lines

Technical Specification for. Insulators. Part 1. Insulators for High and Extra-High Voltage Overhead Lines Page: 1 / 18 for Insulators Part 1 Insulators for High and Extra-High Voltage Overhead Lines 1.2 Cap-and-pin insulators made of pre-stressed glass This technical specification is valid for the business

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

Design, Fabrication, Supply, Installation & Commissioning of Scissor Lift for ITMT Building at. CREST, Hosakote. Indian Institute of Astrophysics

Design, Fabrication, Supply, Installation & Commissioning of Scissor Lift for ITMT Building at. CREST, Hosakote. Indian Institute of Astrophysics Design, Fabrication, Supply, Installation & Commissioning of Scissor Lift for ITMT Building at CREST, Hosakote Indian Institute of Astrophysics Bangalore October 2017 1. Introduction The required scissor

More information

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/LTPVC & CONTROL/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION

More information

SPECIAL SPECIFICATION 6499 Environmentally controlled Communications Building

SPECIAL SPECIFICATION 6499 Environmentally controlled Communications Building 2004 Specifications CSJ 0720-03-095 SPECIAL SPECIFICATION 6499 Environmentally controlled Communications Building 1. Description. Furnish and install Environmentally Controlled Communications Building

More information

Technical Specifications and General Guidelines for Mass Flow Meters at Petroleum Oil Installations. Note:

Technical Specifications and General Guidelines for Mass Flow Meters at Petroleum Oil Installations. Note: Technical Specifications and General Guidelines for Mass Flow Meters at Petroleum Oil Installations Note: These are general specifications and guidelines for Mass Flow Meters for Petroleum Oil Installations.

More information

Special Specification 6292 Radar Vehicle Detection System for Signalized Intersection Control

Special Specification 6292 Radar Vehicle Detection System for Signalized Intersection Control Special Specification 6292 Radar Vehicle Detection System for Signalized Intersection Control 1. DESCRIPTION 2. MATERIALS Furnish, install, relocate, or remove radar vehicle detection systems (RVDS) of

More information

TECHNICAL SPECIFICATION FOR RATE CONTRACT OF INSULATING MATS

TECHNICAL SPECIFICATION FOR RATE CONTRACT OF INSULATING MATS TECHNICAL SPECIFICATION FOR INSULATING MAT 1.0 SCOPE 1.1 The scope includes design, manufacturing, inspection, testing, packing and delivery to site of protective mats for placing in front of HT (11kV,

More information

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR 458 7.3.1 11 KV Cables 7.3.1.1 General Where a Manufacturer s Standard or a national Standard equal to or better than the appropriate specified

More information

MATERIAL SPECIFICATION FOR SIGNAL HEADS

MATERIAL SPECIFICATION FOR SIGNAL HEADS ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 2461 DECEMBER 1988 MATERIAL SPECIFICATION FOR SIGNAL HEADS 2461.01 SCOPE 2461.02 REFERENCES 2461.03 DEFINITIONS INDEX 2461.04 SUBMISSION AND DESIGN

More information

SPECIAL SPECIFICATION 8810 Communication Hub Enclosure

SPECIAL SPECIFICATION 8810 Communication Hub Enclosure 2004 Specifications CSJ 0914-00-301 & 0914-00-314 SPECIAL SPECIFICATION 8810 Communication Hub Enclosure 1. Description. Provide Communication Hub Enclosures of various types and sizes, as shown on the

More information

Supporting bracket. Cooling fins. Internal reflector. Shock-resistant tempered glass. Ex e terminal housing for a quick connection

Supporting bracket. Cooling fins. Internal reflector. Shock-resistant tempered glass. Ex e terminal housing for a quick connection EVL - Zone 1, 2, 21, 22 - Replaces traditional discharge lamps of up to 400W - Saves in energy, maintenance and installation costs - Instant, bright illumination - Suitable for GAS category IIC Supporting

More information

TECHNICAL SPECIFICATION FOR 11KV INDOOR/OUTDOOR & 22KV/33KV OUTDOOR METERING CUBICLE SPEC NO.CE (DIST)/MM-IV/09/ INDEX

TECHNICAL SPECIFICATION FOR 11KV INDOOR/OUTDOOR & 22KV/33KV OUTDOOR METERING CUBICLE SPEC NO.CE (DIST)/MM-IV/09/ INDEX TECHNICAL SPECIFICATION FOR 11KV INDOOR/OUTDOOR & 22KV/33KV OUTDOOR METERING CUBICLE SPEC NO.CE (DIST)/MM-IV/09/ 23.10.2007 INDEX CLAUSE NO. CONTENTS PAGE NO. 1. SCOPE 2 2. SPARES 2 3. SERVICE CONDITIONS

More information