Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

Size: px
Start display at page:

Download "Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR"

Transcription

1 PART 1 - GENERAL Section SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR 1.1 Cable shall be 15 kv, shielded, three conductor with ground, stranded copper, with continuously welded and corrugated aluminum armor and outer jacket; size and voltage rating shown on the drawings. 1.2 Applicable Documents per latest edition. A. ICEA S /NEMA WC74. Ethylene propylene rubber (EPR) - insulated wire and cable for the transmission and distribution of electrical energy. B. ASTM Designation B-496. C. UL 1072 listed Type MV-105 or MC-HL. D. IEC 502, 540 and 332-3; NEMA and IEEE. PART 2 - PRODUCTS 2.1 Medium voltage cable shall be Type C-X-L MV-105 manufactured by Okonite "Okoguard Shielded Power Cable Welded Aluminum Sheath" or approved equal by, Prysmian, Southwire, General Cable, Kerite or Aetna. 2.2 Power cable with continuously corrugated welded aluminum welded sheath (C-L-X) and outer red Okoseal jacket shall be approved for cable tray or direct burial use, embedded in concrete; sunlight resistant. 2.3 Requirements A. The cable shall meet the requirements of ICEA S and UL Type MV-105, except where it conflicts with the requirements of this specification, in which case this specification shall apply. B. Conductors Class "B" stranded, copper per ASTM B-496. C. Strand Screen: Extruded semiconducting conductor stress relief or non-conducting strand screen in accordance with Section of ICEA S D. Insulation thickness shall be for 133 percent insulation level; ethylene-propylene rubber (EPR). 15 kv cable mils minimum insulation thickness 11/11/ page 1 of 5

2 E. Insulation Screen: For 15 KV only extrude a semiconducting stress relief layer of thermoset material over the insulation to serve as an electrostatic shield. The shield compound shall be compatible with the insulation. F. Provide a phase identification for each conductor (black, red, blue); polyester ribbon laid longitudinally under the copper shield for 15 KV. G. Copper Tape - A layer of spirally wound (5 mil minimum) bare copper tape shall be applied with a minimum 12.5% overlap over the insulation shield. H. Grounding conductor: Uncoated copper Class B stranded per ASTM B-496 and sized in accordance with UL I. Assembly: Cabled with fillers in the interstices, binder tape overall. J. Sheath: Close fitting, impervious, continuous corrugated aluminum C-L-X per UL 1072, UL Listing as a grounding conductor. K. Jacket: A low temperature, sunlight resistant, red (15 kv) PVC jacket in accordance with UL 1072 and CSA C Quality Assurance A. Each length of cable shall be tested in accordance with ICEA; provide certified test report from manufacturer. B. Provide 3 rd party testing of installed cables. C. Manufacturer shall certify that cable has been manufactured within the last 12 months. 2.5 All cable ends shall be sealed to prevent the entrance of moisture into the insulation during shipment, storage and installation. 2.6 Compression type fittings shall be used for all cable terminations and splices. Standard 3M or Plymouth termination or splice kits consisting of tape built up stress relief or premolded splices, connectors and terminations manufactured by Elastimold, RTE, Raychem, or 3M equal to the following 3M types: Splices (15 kv) Series #2 thru 750 MCM Copper Tape 5500 Shielded Terminations (15 kv) Copper Tape Shielded Series Outdoor K Indoor K 2.7 Aluminum armor and grounding conductor terminators shall be approved for the purpose page 2 of 5 11/11/11

3 PART 3 - EXECUTION 3.1 Coordinate power outages and switching with Miami University System Operator. No shutdown will be allowed without written approval of time and date by Miami University. 3.2 Primary cables shall be run continuous without splices, except where indicated or where prior approval is given by the Engineer. 3.3 Provide rain shields on all outdoor cable terminations. 3.4 Install cables, cable and armor terminations, and splices per cable manufacturer's and terminator manufacturer's recommendations. At each splice and at each termination, bond all sheaths, shields, ground conductor, etc. to a ground rod or equipment ground bar. Terminations and splices shall be first-class by men familiar with the trade, per manufacturer's instructions. 3.5 Fireproof cables in manholes and other exposed locations. Each cable shall be arc and fireproofed with one-half lapped layer of Scotch Brand 77 Electric Arc and Fireproofing Tape. Tape shall be secured with a two-layer band of Scotch Brand 69 Glass Electrical Tape over the last wrap. 3.6 Exercise extreme caution when arranging and supporting cables in manholes, to be certain that no underground ducts entering the manholes are made inaccessible for future cable installations. Arrange cables such that removal and/or repair of existing cables shall not require breaking a splice in existing cables, except those that are involved in such repair or removal. Contractor shall supply and install new heavy duty, insulated cable supports in the manholes as required. 3.7 Cable racks shall be furnished and installed by the Contractor; Line Material heavy duty, fiberglass, non-metallic type. 3.8 Exercise extreme care in the installation of the cables in cable trays, underground ducts and conduits. Proper sheaves, hose and lubrication shall be used for the pulling in operation, to ensure that the cables will not be damaged. Ducts to be used shall be thoroughly cleaned by pulling thru a spiral brush prior to cable installation. 3.9 During the entire cable installation procedure, the ends of the cables shall be protected to prevent the entrance of moisture into the insulation and cable assembly. This protection shall be provided until the splicing operation has been completed Bends of the cables in manholes shall be of a radius not less than that recommended by the cable manufacturer Identify each cable by circuit number size, insulated, rating, date and phases A, B or C, at splices, in manholes and at all termination points with corrosion resistant 2" x 6" non-metallic tags and fasteners, (phenolic and nylon) consistent with the new (or existing) marking system The installation of cables in ducts when the temperature is 32 degrees F. or below shall have the approval of the and Associate Engineer before such installation takes place. 11/11/ page 3 of 5

4 3.13 All terminations, potheads, bus, etc. shall be insulated by application of appropriate compounds, fillers and tapes. All cable terminations shall be made consistent with the phase identification and placement in the existing power system When electrical outages are required for splicing to existing cables, such outage shall be as scheduled in advance by the Contractor Before any cable terminating or splicing is started, the Contractor must submit his proposed cable splicers name in writing to the Architect and Engineer for approval. Splicing is not to proceed until this approval has been granted. Submit qualifications and certificates for these individuals for review Splicing of cables shall be accomplished in accordance with the recommendations of the cable manufacturer or termination manufacturer. Splicing materials used shall be the highest quality and shall be of the type compatible with the cable being spliced. Tools used for the splicing operation shall be kept clean and free of moisture at all times The manholes shall be kept pumped dry at all times during the splicing operation. Splicing will not be permitted when the manhole wall and/or ceiling is dripping with moisture. Protection shall be provided at the manhole access opening to prevent the entrance of rain and running water When splicing cable or making cable terminations, it is extremely important that the cable insulation and the conductor connector be free of contamination and moisture before the taping operation is started. A portable hair dryer with a blower (or similar device) should be used for drying before and during the taping operation to prevent moisture being trapped in the splice Proof Testing A. All testing shall be conducted by a 3 rd party testing agency. The electrical contractor shall include the cost for this testing in their base bid pricing. B. Conduct all tests and inspections necessary to determine that all wiring and equipment installed under this specification is in satisfactory condition to be energized. Tests shall be conducted in the presence of, and at a time acceptable to the Engineer. All tests shall meet the applicable standards of IEEE and NEC. A complete accurate record of all tests and inspections shall be made. The furnishing and setting up of any required test equipment and performance of all work incidental to making test, including any necessary professional engineering fees, are a part of the work specified herein. C. The high voltage d-c "Step-Voltage" field acceptance test shall be performed on each cable after installation of cable terminations and before energizing, in accordance with recommendations of the cable manufacturer. Test shall be performed by a testing organization normally engaged in testing of cables; testing organization shall be approved by the Engineer. (Note: Test voltage maximum level 300 volts per mil of insulation thickness. The voltage shall be kept at this level for 15 minutes.) D. Any existing high voltage cable that is spliced or reworked shall be tested as follows: (2 x rated kv +1 kv); e.g. existing 15 kv cable is to be tested at 31 kv; existing 5 kv cable is to be tested at 11 kv. This formula is not to be exceeded. The voltage shall be kept at this level for 5 minutes page 4 of 5 11/11/11

5 E. Ensure that the maximum test voltage does not exceed the limits of the cable and terminator manufacturer recommendations. F. Test each section of cable individually. Individually test each conductor with all other conductors grounded at both ends. Ground all shields. Apply a dc high potential test in at least five equal increments. Record dc leakage current at each step after necessary stabilization time. G. Raise the test conductor to the specified maximum test voltage and hold for the time indicated above or as specified by the manufacturer. Record readings of leakage current at 30 seconds and 1 minute and at 1 minute intervals, thereafter. H. Reduce the conductor test potential to zero and measure residual voltage at discrete intervals. I. When new cables are spliced into existing cables, the high voltage d-c "Step-Voltage" field acceptance test shall be performed on the new cable prior to splicing. After test results are approved for new cable and the splice is complete, an insulation resistance test and a shield continuity test shall be performed on the length of new and existing cable including the splice. After a satisfactory insulation resistance test, a high voltage d-c "Step-Voltage" field acceptance test test shall be performed on the full length of the combined cable. J. Megger test shall be performed before and after each high potential test. K. Record humidity and temperature. L. Furnish six (6) copies of certified graphs showing leakage current on d-c test (current versus time) to the Engineer for review. The graph shall show the leakage current value at five equal steps to the specified test voltage, from 20 percent to 100 percent. The specified test voltage shall be maintained constant and the leakage currents recorded at one minute intervals for ten minutes. If the current has not dropped, or after dropping it starts to rise again, the test shall be continued as long as the current continues to rise, or until failure occurs Any work found defective under the tests shall be replaced. After replacement, the work shall again be tested as specified. Final acceptance of the work depends on successful completion of complete operation tests on all equipment to show that the equipment will perform the functions for which it was designed. END OF SECTION 11/11/ page 5 of 5

SECTION MEDIUM-VOLTAGE CABLES PART 1 GENERAL

SECTION MEDIUM-VOLTAGE CABLES PART 1 GENERAL SECTION 260513 - MEDIUM-VOLTAGE CABLES PART 1 GENERAL 1.1 SECTION INCLUDES A. Medium voltage cable. B. Cable terminations. C. This specification describes single conductor EPR (Ethylene-propylene-rubber)

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 6/15/16 Updated division section from 16124 to 2605 - mgl44 13, removed references to other section 10/17/14

More information

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

The Contractor shall furnish and install all shielded power cable suitable for use on this project. Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS

More information

SECTION WIRES AND CABLES

SECTION WIRES AND CABLES SECTION 16120 - WIRES AND CABLES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

PV Solar Wiring Solutions

PV Solar Wiring Solutions Priority Solar Projects Across the US 14 DISTRIBUTION CENTERS PV Solar Wiring Solutions ON TIME ACCURATE FLEXIBLE SERVICE CUSTOM SOLUTIONS Priority Capabilities: Premier Supplier of Wire & Cable Cut to

More information

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways.

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways. SECTION 16120 WIRE, CABLE AND BUSWAYS PART 1 - GENERAL 1.01 DESCRIPTION: A. This section specifies providing wire, cable and busways. B. Definitions: 1. Cable: Cable having low smoke generating characteristics.

More information

Standard of Practice - Campus Electrical Distribution System

Standard of Practice - Campus Electrical Distribution System A26.3 Standard of Practice - Campus Electrical Distribution System NOTE: Significant revisions or additions to the previous standards are highlighted in italics. GENERAL Designers shall verify that all

More information

This section applies to the design and installation relating to wire and cable systems and terminations. 16G Figure 1 16G Figure 2

This section applies to the design and installation relating to wire and cable systems and terminations. 16G Figure 1 16G Figure 2 Wire, Cable and Terminations Basis of Design This section applies to the design and installation relating to wire and cable systems and terminations. Design Criteria Medium Voltage Review and modify the

More information

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE ONTARIO PROVINCIAL STANDARD SPECIFICATION OPSS.PROV 604 NOVEMBER 2017 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

15 kv EPR Insulated, Jacketed, URD Cable

15 kv EPR Insulated, Jacketed, URD Cable 15 kv EPR Insulated, Jacketed, URD Cable 1000 kcm Copper Conductor with Tape Shield Page 1 of 11 Table Of Contents 1 GENERAL... 3 2 STANDARDS... 3 3 APPROVED CABLE MANUFACTURERS... 3 4 REEL SPECIFICATIONS...

More information

3 MODIFICATIONS TO EXISTING STANDARDS

3 MODIFICATIONS TO EXISTING STANDARDS 1 SCOPE This specification covers the requirements for 25 kv rated single-phase primary cable with shielded concentric neutral and an insulating jacket. The cable may be used in single or multi-phase application

More information

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION 1.0 SCOPE 1.1 This specification covers the construction, mechanical, and electrical requirements of single conductor,

More information

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072.

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072. 37-105VFD MMV-VFD Power Cable Three : kv - 15kV 133% Level Rated 90 C s (3) Soft annealed flexible stranded tinned copper per IEEE 150 Table 11. Extruded thermosetting 90 C Ethylene Propylene Rubber (EPR),

More information

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 604 NOVEMBER 2004 CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 604 NOVEMBER 2008 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

Clark Public Utilities

Clark Public Utilities Clark Public Utilities TECHNICAL SPECIFICATIONS 15KV MEDIUM VOLTAGE 1000 MCM AL URD CABLE 175 MIL EPR FEBRUARY 1994 REVISED MAY 1996 REVISED JUNE 2001 REVISED MARCH 2002 REVISED MARCH 2005 REVISED MAY

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990) WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990) ABRASION RESISTANT 600V CABLE NOTE: This "Guide" summarizes the opinions, recommendations, and practices of the Western Underground Committee members

More information

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed]

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed] [6.35/11kV Copper XLPE Three-Core HDPE Sheathed] APPLICATION Mostly used as feeder electric cable for power distribution network such as power supply station, substation, switching system etc. They are

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 05 19.10 10 (May 2016) ----------------------------------- Preparing Activity: USACE Superseding UFGS-26 05 19.00 10 (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Engineering Data for Copper and Aluminum Conductor Electrical Cables

Engineering Data for Copper and Aluminum Conductor Electrical Cables 2018 Edition Engineering Data for Copper and Aluminum Conductor Electrical Cables THE OKONITE COMPANY Okonite Cables...A higher Standard! The Okonite Company, 2018 Okonite Cables Table of Contents SECTION

More information

STANDARD SPECIFICATION FOR SIGNAL CABLE. A. This Specification provides for single and multi-conductor insulated and jacketed cable for

STANDARD SPECIFICATION FOR SIGNAL CABLE. A. This Specification provides for single and multi-conductor insulated and jacketed cable for STANDARD SPECIFICATION FOR SIGNAL CABLE 1.01 SCOPE A. This Specification provides for single and multi-conductor insulated and jacketed cable for installation in direct contact with the earth, in ducts,

More information

1. Section COVER PAGE: remove and replace with new Cover Page, Attached.

1. Section COVER PAGE: remove and replace with new Cover Page, Attached. BID ADDENDUM #04 (BID # 940-13) Greenwich Public Schools District Wide Renovations Electric Generator 290 Greenwich Avenue Greenwich, CT 06830 Date: June 11th, 2013 KSQ Project #: 1317905.00 This Addendum

More information

SECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013.

SECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013. PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 26 0519 A. Single conductor building wire. B. Metal-clad cable. C. Wiring connectors. D. Electrical tape. E. Wire pulling lubricant. F. Cable ties. 1.2 RELATED

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less) SECTION 260523 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less) PART 1 - GENERAL 1.1 SUMMARY A. Related Documents: 1. Drawings and general provisions of the Subcontract apply

More information

600 VOLT 600V, 3 CONDUCTOR (WITH GROUND), FR-EPR OR FR-XLPE INSULATION, PVC JACKET SPECIFICATIONS (FLAME RETARDANT POWER CABLE) (UL TYPE TC-ER) TYPE C3 SPEC 70.0100 PROJECT 196116 REFERENCE: LATEST EDITIONS

More information

Tele-Fonika Cable Americas

Tele-Fonika Cable Americas PUMP Cables Tele-Fonika Kable 2 TELE-FONIKA Kable S A, a privately held wire and cable manufacturer headquartered in Krakow, Poland, is one of the largest wire and cable companies in the world. TF operates

More information

NEMA Standards Publication No. WC ICEA Publication No. S

NEMA Standards Publication No. WC ICEA Publication No. S NEMA Standards Publication No. WC 71-1999 ICEA Publication No. S-96-659-1999 Standard for Nonshielded Cables Rated 2001-5000 Volts for use in the Distribution of Electric Energy Published by National Electrical

More information

1.2 REFERENCES.1 CSA C22.2 No.0.3, Test Methods for Electrical Wires and Cables.

1.2 REFERENCES.1 CSA C22.2 No.0.3, Test Methods for Electrical Wires and Cables. Issued 2005/06/01 Section 16122 Wire and Cables (0 1000V) Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 16151 Wire and Box Connectors 0 1000 1.2 REFERENCES.1 CSA C22.2 No.0.3, Test Methods

More information

NORMAS DE REFERENCIA AEIC CS 1: ASTM B

NORMAS DE REFERENCIA AEIC CS 1: ASTM B AEIC CS 1: Especificación para Solid-Type Impregnated-Paper-Insulated Metallic Sheathed AEIC CS2: Especificación para Impregnated-Paper and Laminated Paper- Polypropylene Insulated, High- Pressure Pipe-Type

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract apply to this Section. 1.2 SUMMARY A. This Section

More information

ANSI/NEMA WC ICEA S Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy

ANSI/NEMA WC ICEA S Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy Approved as an American National Standard ANSI Approval Date: February 23, 2009 ANSI/NEMA WC 70-2009 ICEA S-95-658-2009 Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy Published

More information

SECTION LIGHTNING PROTECTION SYSTEM

SECTION LIGHTNING PROTECTION SYSTEM SECTION 16670 - LIGHTNING PROTECTION SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SPECIFICATION FOR FRLS POWER CABLES

SPECIFICATION FOR FRLS POWER CABLES SPECIFICATION FOR FRLS POWER CABLES 1.0 SCOPE This specification cover the technical requirements of design, manufacture, testing and delivery to site of Power Cables of 1100V grade with FRLS PVC Sheathed,

More information

*** Supercedes: BECO E and COM , , & ***

*** Supercedes: BECO E and COM , , & *** 7/27/09 Page 1 of 9 R5 *** Supercedes: BECO E2.9-27.4 and COM 1-0696, 2-0196, & 5-0385 *** 1.0 Scope #2 AWG to 1000 KCMIL CONCENTRIC NEUTRAL JACKETED CABLES RATED 5-35 kv These Specifications cover single

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. AFC Cable Systems, Inc. Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519.13 METAL CLAD CABLE-MC

More information

16300 HIGH VOLTAGE DISTRIBUTION

16300 HIGH VOLTAGE DISTRIBUTION 16300 HIGH VOLTAGE DISTRIBUTION PART 1: GENERAL 1.01 WORK INCLUDED A. Most new loads will be served from the underground electric distribution system. This system is a primary open loop configuration served

More information

SECTION MEDIUM VOLTAGE ELECTRICAL DISTRUBUTION (ABOVE 600 VOLTS)

SECTION MEDIUM VOLTAGE ELECTRICAL DISTRUBUTION (ABOVE 600 VOLTS) SECTION 26 10 00 MEDIUM VOLTAGE ELECTRICAL DISTRUBUTION (ABOVE 600 VOLTS) UNIVERSITY OF SOUTH ALABAMA REFERENCE INFORMATION University s Design and Construction Standards, one line diagrams, campus power

More information

POLYMERIC ARMOR DESIGN OF AN IMPROVED PROTECTION TO MECHANICAL STRESSES AND FLUIDS FOR OIL GAS AND PETROCHEM (OGP) APPLICATIONS

POLYMERIC ARMOR DESIGN OF AN IMPROVED PROTECTION TO MECHANICAL STRESSES AND FLUIDS FOR OIL GAS AND PETROCHEM (OGP) APPLICATIONS POLYMERIC ARMOR DESIGN OF AN IMPROVED PROTECTION TO MECHANICAL STRESSES AND FLUIDS FOR OIL GAS AND PETROCHEM (OGP) APPLICATIONS Paul CINQUEMANI, Prysmian Cables & Systems USA, LLC, paul.cinquemani@prysmian.com

More information

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE. ANSI/ICEA S-108-720-2012 STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV Approved by AMERICAN NATIONAL STANDARDS INSTITUTE November 27, 2012 Publication # ANSI/ICEA S-108-720-2012

More information

QUALIFICATION UPDATE. Eric Rasmussen. Quality Cables Since 1854

QUALIFICATION UPDATE. Eric Rasmussen. Quality Cables Since 1854 QUALIFICATION UPDATE Eric Rasmussen Quality Cables Since 1854 90 C 60 year Four successful qualifications to date: QR-1305: Kerite Shielded MV Power Cables for 60 Year Life at 90 C (LOCA) QR-1403: Kerite

More information

SECTION INSULATED WIRE AND CABLE

SECTION INSULATED WIRE AND CABLE SECTION 16120 INSULATED WIRE AND CABLE PART 1 GENERAL 1.01 DESCRIPTION A. This section covers the contract item Insulated Wire and Cable, which includes the following items with accessories, and appurtenances:

More information

SECTION ELECTRICAL UTILITY SERVICES

SECTION ELECTRICAL UTILITY SERVICES SECTION 33 71 73 ELECTRICAL UTILITY SERVICES PART 1 GENERAL 1.1 REFERENCES A. American Association of State Highway Officials (AASHO): 1. Standard Specifications B. California Administrative Code (CAC):

More information

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE METAL-ENCLOSED BUS MEDIUM VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. The medium

More information

PILC Replacement: Getting the Lead Out

PILC Replacement: Getting the Lead Out PILC Replacement: Getting the Lead Out Spring Cincinnati, OH April 30, 2003 Page 1 PILC IS GREAT! Low Profile High Fault Current Capability on Shield High Degree of Water Blocking So why shouldn t you

More information

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV)

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV) EDC3 (5239) P3 Mini-Grid Systems DRAFT TANZANIA STANDARD Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV) TANZANIA BUREAU OF STANDARDS TBS 2017 First Edition 2017 Table of Contents

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal.

1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal. PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University for for Electrical System. B. Texas State University recognizes

More information

Kaf-Tech Product Specification

Kaf-Tech Product Specification Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519.13 METAL CLAD CABLE-LUMINARY CABLE

More information

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor TABLE OF CONTENTS SECTION SUBJECT PAGE I. SCOPE...1 II. APPLICABLE DOCUMENTS...1 III. CONDUCTOR...2 IV. SEPARATOR...2 V. INSULATION...2 A. Physical Properties...2 B. Electrical Properties...3 C. Qualification

More information

SECTION HEAT TRACING FOR PLUMBING PIPING

SECTION HEAT TRACING FOR PLUMBING PIPING SECTION 22 05 33 HEAT TRACING FOR PLUMBING PIPING PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not

More information

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study

A. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study PART 1: GENERAL 1.01 Underground Ducts and Manholes A. The work included in this section of the construction standards consists of the design requirements for the complete layout and installation of a

More information

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW THHN/THWN-2/THW/THWN/TW Listed E-492385 / E-472248 APPLICATIONS THHN/THWN-2 building wire is primarily used for general purpose applications in conduit and cable

More information

SECTION ELECTRICAL CABLE. 1. Trench excavation, backfill, and compaction; Section

SECTION ELECTRICAL CABLE. 1. Trench excavation, backfill, and compaction; Section 02735-1 of 5 SECTION 02735 ELECTRICAL CABLE 02735.01 GENERAL A. Description Electrical cable installation shall include, but not necessarily be limited to, furnishing and placing electrical cable as shown

More information

Section 70 Airport Transformer Vault and Vault Equipment (FAA L-109)

Section 70 Airport Transformer Vault and Vault Equipment (FAA L-109) Black text from standard FAA spec Strikeout text deletions from FAA standard spec Blue text additions to FAA standard spec Red text notes to the Engineer/won t appear in spec I. DESCRIPTION 1. This item

More information

SECTION GROUNDING

SECTION GROUNDING SECTION 16450 GROUNDING PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies general grounding and bonding requirements of electrical and telecommunication installations for personnel safety, equipment

More information

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION

SECTION UNDERGROUND ELECTRICAL CONSTRUCTION PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 41 UNDERGROUND ELECTRICAL CONSTRUCTION A. This section specifies the furnishing, installation, and connection of precast manholes and pullboxes with ducts

More information

1.05 Power System Fault and Coordination Study with Arc Flash Calculations

1.05 Power System Fault and Coordination Study with Arc Flash Calculations PART 1: GENERAL 1.01 Underground Ducts and Manholes A. The work included in this section of the construction standards consists of the design requirements for the complete layout and installation of a

More information

SECTION HEAT TRACING FOR PLUMBING PIPING

SECTION HEAT TRACING FOR PLUMBING PIPING SECTION 22 05 33 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable in the section

More information

Glossary Of Terms M-1

Glossary Of Terms M-1 Glossary Of Terms ANSI - American National Standards Institute. Armor - A sheath, serving, braid or other layer of metal applied over a cable to increase its mechanical protection. ARR - Association of

More information

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7

DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification

More information

Installation of CSST Gas Piping Systems

Installation of CSST Gas Piping Systems (What Inspectors Need To Know) May 2016 Conventional Arc-Resistant CSST Product Standard National Standard ANSI LC-1 Performance-based standard Listed system installed in accordance with manufacturer s

More information

Cables ELE E L CT E C R T R IC I C A A L L

Cables ELE E L CT E C R T R IC I C A A L L E LECTRICAL ELECTRICAL Cables July 28, 2009 CONDUMEX INCORPORATED WIRE & CABLE PRODUCT INDEX BUILDING WIRE MTW/THHN/THWN 600 VOLTS COPPER 14 AWG SOLID 750 MCM STRANDED UL 83 XHHW-2 600 VOLTS COPPER 14

More information

26/35kV Copper XLPE Insulation Electric Cable

26/35kV Copper XLPE Insulation Electric Cable 26/35kV Copper XLPE Insulation Electric Cable Specifications 1.1~35kv XLPE insulated power cable 2.Standard: IEC,VDE,BS,UL,AS/NZS Black PVC sheath XLPE insulated armored copper power cable YJV22 YJV32

More information

MATERIAL STANDARD FOR CABLES AND WIRES

MATERIAL STANDARD FOR CABLES AND WIRES MATERIAL STANDARD FOR CABLES AND WIRES CONTENTS : PAGE No. 1. SCOPE... 2 2. SERVICE CONDITIONS... 2 3. REFERENCES AND STANDARDS... 2 4. UNITS... 3 5. CABLE DESIGN AND CONSTRUCTION... 3 5.1 Applicable Cable

More information

A&E Standards Electrical Cables, Conduits, and Supports Division 26 Electrical

A&E Standards Electrical Cables, Conduits, and Supports Division 26 Electrical A&E Standards Electrical Cables, Conduits, and Supports Division 26 Electrical Version 3.0 SEP Subgroup 4.4 December 2017 PREFACE PURPOSE OF THIS DOCUMENT The intent of this document is to disseminate

More information

PVC Insulating Tape. Electrical Tapes

PVC Insulating Tape. Electrical Tapes Electrical Tapes 7 Electrical Tapes Electrical Tapes 3M offer a range of over 30 electrical tapes and mastics for insulation, jointing, corrosion protection, all weather protection and environmental sealing.

More information

SPECIAL SPECIFICATION 6664 Level (3) Communications System

SPECIAL SPECIFICATION 6664 Level (3) Communications System 2004 Specifications CSJ 1200-05-014 SPECIAL SPECIFICATION 6664 Level (3) Communications System 1. Description. A. This Item will govern the installation of all facilities belonging to Level (3) Communications,

More information

SPECIAL SPECIFICATION 6658 Time Warner Communications System

SPECIAL SPECIFICATION 6658 Time Warner Communications System 2004 Specifications CSJ 1200-05-014 1. Description. SPECIAL SPECIFICATION 6658 Time Warner Communications System A. This Item will govern the installation of all facilities belonging to Time Warner Cable

More information

A. Section includes busway and fittings including plug-in units.

A. Section includes busway and fittings including plug-in units. SECTION 26 25 00 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes busway and fittings including plug-in units. 1.2 REFERENCES A. Institute of Electrical and Electronics Engineers:

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

SPECIFICATION FOR 600 VOLT CONTROL AND POWER CABLE SPECIFICATION NO. 557

SPECIFICATION FOR 600 VOLT CONTROL AND POWER CABLE SPECIFICATION NO. 557 EXHIBIT A - TECHNICAL SPECIFICATION SPECIFICATION FOR 600 VOLT CONTROL AND POWER CABLE SPECIFICATION NO. 557 DATE: March 31, 2000 (REVISED: October 13, 2006) (REVISED: February 14, 2012) (REVISED: January

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 280.21-300.50 CHANGES FROM 2011 TO 2014 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1000 volts II. Instillation III. Connecting Surge

More information

3M Heavy Wall Heat Shrink Tubing ITCSN

3M Heavy Wall Heat Shrink Tubing ITCSN 3M Heavy Wall Heat Shrink Tubing ITCSN Data Sheet September 2013 Description 3M Heavy Wall Heat Shrink Tubing ITCSN is designed to provide reliable performance for electrical splices, connections, and

More information

The Medical Center Company Electrical System Installation Requirements

The Medical Center Company Electrical System Installation Requirements The Medical Center Company Electrical System Installation Requirements Introduction System Description Approvals Scheduling of Power Shutdowns and Power Transfers 5. Service Entrance 6. Feeder Systems

More information

12-SDMS-01 Rev.02 SPECIFICATIONS FOR

12-SDMS-01 Rev.02 SPECIFICATIONS FOR 12-SDMS-01 Rev.02 SPECIFICATIONS FOR CABLE JOINTS, TERMINATIONS, AND ACCESSORIES UP TO 36 KV This specification is property of SEC and is subject to change or modification without any notice. TABLE OF

More information

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES ANSI/ICEA S-05-692 STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES Approved as an American National Standard ANSI Approval Date: 9/29/ ANSI/ICEA Publication

More information

ANSI/NEMA WC ICEA S Standard for Control, Thermocouple Extension, and Instrumentation Cables

ANSI/NEMA WC ICEA S Standard for Control, Thermocouple Extension, and Instrumentation Cables Approved as an American National Standard ANSI Approval Date: October 31, 2014 ANSI/NEMA WC 57-2014 ICEA S-73-532-2014 Standard for Control, Thermocouple Extension, and Instrumentation Cables Prepared

More information

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR 458 7.3.1 11 KV Cables 7.3.1.1 General Where a Manufacturer s Standard or a national Standard equal to or better than the appropriate specified

More information

SECTION PARK NON-SEGREGATED BUS SPECIFICATION

SECTION PARK NON-SEGREGATED BUS SPECIFICATION Page 1 of 5 SECTION ------- PARK NON-SEGREGATED BUS SPECIFICATION 1.0 SCOPE 1.1. This specification describes assemblies of 600V, 5Kv and 15Kv non-segregated bus duct, which will be installed indoors and

More information

Article-No. Type. All dimensions in mm. Subject to technical changes. Other dimensions, reel lengths or colours available on request.

Article-No. Type. All dimensions in mm. Subject to technical changes. Other dimensions, reel lengths or colours available on request. 4.4 Installation Devices HelaTape HellermannTyton offers a wide range of PVC and rubber tapes for sealing, insulation and bundling of cable and conduits. PVC based tapes are designed for low voltage applications

More information

ADDENDUM NO. 1 Date of Issue: 9/8/2010 CONSTRUCTION PROPOSAL LAKE CHARLES HARBOR AND TERMINAL DISTRICT. for PLC PROJECT NO.

ADDENDUM NO. 1 Date of Issue: 9/8/2010 CONSTRUCTION PROPOSAL LAKE CHARLES HARBOR AND TERMINAL DISTRICT. for PLC PROJECT NO. ADDENDUM NO. 1 Date of Issue: 9/8/2010 to CONSTRUCTION PROPOSAL LAKE CHARLES HARBOR AND TERMINAL DISTRICT for PLC PROJECT NO. CP7004B ELECTRICAL MODIFICATIONS FOR THE NEW SHIP UNLOADER AT BT-1 PREPARED

More information

Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire

Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire Today s Topics Brief Overview of Southwire In-depth Discussion on Aluminum Characteristics Discussion of

More information

0.6/1 kv LOW VOLTAGE CONTROL CABLES. Conductors. Insulation. Assembly. Standard Colour Code. Armour (Optional) Screening (Optional) Outer Sheath

0.6/1 kv LOW VOLTAGE CONTROL CABLES. Conductors. Insulation. Assembly. Standard Colour Code. Armour (Optional) Screening (Optional) Outer Sheath 0.6/1 kv LOW VOLTAGE CONTROL CABLES PVC OR XLPE INSULATED, PVC SHEATHED AS PER IEC 60502-1 Conductors Conductors shall be Circular Stranded, Class 2 as per IEC 60228, BS EN 60228. Upon request, Solid Circular

More information

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, TYPE LS3SWU (INCLUDING VARIATION LS3SWUS)

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, TYPE LS3SWU (INCLUDING VARIATION LS3SWUS) INCH-POUND 11 July 2011 USED IN LIEU OF MIL-DTL-24643/36F 01 October 2009 DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, TYPE LS3SWU (INCLUDING VARIATION LS3SWUS) This specification is approved

More information

Building Wire CARRYING YOUR ELECTRICITY

Building Wire CARRYING YOUR ELECTRICITY Building Wire CARRYING YOUR ELECTRICITY Our Commitment Our commitment to our customers is simple - we deliver even when others can t. As one of Canada s largest wire, cable and data communication distributors

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 26 05 26 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide labor, materials, equipment, and incidentals as shown, specified, and

More information

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable.

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable. Spec. No. GO 5821-4361Rev.2 Issued date : July 13, 2005 Revised 1 date : April 29, 2015 Revised 2 date : February 19, 2016 Specification FOR 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 GROUNDING AND BONDING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 26 05 26 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Specification Lightning Protection Systems

Specification Lightning Protection Systems Specification Lightning Protection Systems General: Summary A) This Section specifies the lightning protection system for the building(s) or structure(s). This system provides safety for the building and

More information

PRY-MOULD. High Voltage Accessories for Extruded Cables

PRY-MOULD. High Voltage Accessories for Extruded Cables PRY-MOULD High Voltage Accessories for Extruded Cables Linking the future As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient and sustainable supply of energy

More information

3.0) TRANSMISSION LINES MINIMUM REQUIRED STANDARDS LINES

3.0) TRANSMISSION LINES MINIMUM REQUIRED STANDARDS LINES 3.0) TRANSMISSION LINES MINIMUM REQUIRED STANDARDS LINES 3.2 Underground Lines [below sections will be renumbered at a later date] 5.0 GENERAL REQUIREMENTS 5.1 Underground transmission lines 69 kv and

More information

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).

A. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). 16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the

More information

History of Cable Systems HISTORICAL OVERVIEW OF MEDIUM & HIGH VOLTAGE CABLES. Nigel Hampton

History of Cable Systems HISTORICAL OVERVIEW OF MEDIUM & HIGH VOLTAGE CABLES. Nigel Hampton HISTORICAL OVERVIEW OF MEDIUM & HIGH VOLTAGE CABLES Nigel Hampton Copyright GTRC 2012 Objective To present the evolution of cables in time to understand the lessons from the past: the legacy problems and

More information

Selection of the Correct Optical Cable Outer Jacket for the Application

Selection of the Correct Optical Cable Outer Jacket for the Application Application Notes Selection of the Correct Optical Cable Outer Jacket for the Application Issued December 2012 Abstract The cable jacket provides the first line of defense against the surrounding environment.

More information

Mining Products. Jacketing and Insulating Tapes Trailing Cable Splice Kits High Voltage Splice and Termination Kits Cable Repair Tape Special Items

Mining Products. Jacketing and Insulating Tapes Trailing Cable Splice Kits High Voltage Splice and Termination Kits Cable Repair Tape Special Items Jacketing and Insulating Tapes Trailing Cable Splice Kits High Voltage Splice and Termination Kits Cable Repair Tape Special Items Jacketing and Insulating Tapes Mining Products NEW PLYTUFF - F/R PVC Jacketing

More information

Mining Products Jacketing and Insulating Tapes Trailing Cable Splice Kits High Voltage Splice and Termination Kits Cable Repair Tape Special Items Fon

Mining Products Jacketing and Insulating Tapes Trailing Cable Splice Kits High Voltage Splice and Termination Kits Cable Repair Tape Special Items Fon Jacketing and Insulating Tapes Trailing Cable Splice Kits High Voltage Splice and Termination Kits Cable Repair Tape Special Items Jacketing and Insulating Tapes NEW PLYTUFF - F/R PVC Jacketing Tape PVC

More information

WHAT MAKES ENCORE S XHHW-2 UNIQUE? Our SuperSlick Elite technology may be installed without additonal lubricant

WHAT MAKES ENCORE S XHHW-2 UNIQUE? Our SuperSlick Elite technology may be installed without additonal lubricant SSE XHHW-2/RW90 600V WHAT MAKES ENCORE S XHHW-2 UNIQUE? Our SuperSlick Elite technology may be installed without additonal lubricant and is available in all COLORS in sizes 14 AWG-1000 KCMIL for copper

More information

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +105 C, 1000 VOLTS, TYPE LSFSGU

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +105 C, 1000 VOLTS, TYPE LSFSGU INCH-POUND MIL-DTL-24643/17F 1 October 2009 SUPERSEDING MIL-DTL-24643/17E 22 August 2002 DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +105 C, 1000 VOLTS, TYPE LSFSGU This specification is approved

More information