June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES

Size: px
Start display at page:

Download "June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES"

Transcription

1 June 7, 2012 TO: PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES SUBJECT: Revisions to the Acceptance Criteria for Metallic HVAC Duct Enclosure Assemblies, Subject AC R1 (MB/CA) Dear Colleague: We are enclosing the revised ICC-ES Acceptance Criteria for Metallic HVAC Duct Enclosure Assemblies (AC179), which was approved by the Evaluation Committee during the June 2012 hearings. The criteria was approved with the revisions proposed in our letter dated April 27, 2012 (new Sections 3.7 and 5.6), and with an editorial revision to Section 3.5. The revisions are related to use of the enclosure materials to protect ducts used in pressurization systems in stairways and elevator hoistways under IBC Sections and The changes approved by the committee expand the scope of the criteria. Report applicants with applications currently under review may request an expansion of the scope of their review, and current report holders may apply to revise their existing reports, to include this new recognition. Thank you for your interest. If you have any questions, please contact Michael Beaton, P.E., senior vice president, at (800) , extension 3289, or by at Yours very truly, GGN/md Enclosure cc: Evaluation Committee Gary G. Nichols, P.E., SECB Vice President

2 (800) (562) A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR METALLIC HVAC DUCT ENCLOSURE ASSEMBLIES AC179 Approved June 2012 Previously revised October 2011, April 2008, October 2005, February 2005 PREFACE Evaluation reports issued by ICC Evaluation Service, LLC (ICC-ES), are based upon performance features of the International family of codes. (Some reports may also reference older code families such as the BOCA National Codes, the Standard Codes, and the Uniform Codes.) Section of the International Building Code reads as follows: The provisions of this code are not intended to prevent the installation of any materials or to prohibit any design or method of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternative material, design or method of construction shall be approved where the building official finds that the proposed design is satisfactory and complies with the intent of the provisions of this code, and that the material, method or work offered is, for the purpose intended, at least the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability and safety. This acceptance criteria has been issued to provide interested parties with guidelines for demonstrating compliance with performance features of the codes referenced in the criteria. The criteria was developed through a transparent process involving public hearings of the ICC-ES Evaluation Committee, and/or on-line postings where public comment was solicited. New acceptance criteria will only have an approved date, which is the date the document was approved by the Evaluation Committee. When existing acceptance criteria are revised, the Evaluation Committee will decide whether the revised document should carry only an approved date, or an approved date combined with a compliance date. The compliance date is the date by which relevant evaluation reports must comply with the requirements of the criteria. See the ICC-ES web site for more information on compliance dates. If this criteria is a revised edition, a solid vertical line ( ) in the margin within the criteria indicates a change from the previous edition. A deletion indicator ( ) is provided in the margin where significant wording has been deleted. ICC-ES may consider alternate criteria for report approval, provided the report applicant submits data demonstrating that the alternate criteria are at least equivalent to the criteria set forth in this document, and otherwise demonstrate compliance with the performance features of the codes. ICC-ES retains the right to refuse to issue or renew any evaluation report, if the applicable product, material, or method of construction is such that either unusual care with its installation or use must be exercised for satisfactory performance, or if malfunctioning is apt to cause injury or unreasonable damage. NOTE: The Preface for ICC-ES acceptance criteria was revised in July 2011 to reflect changes in policy. Acceptance criteria are developed for use solely by ICC-ES for purpose of issuing ICC-ES evaluation reports. Copyright 2012

3 ACCEPTANCE CRITERIA FOR METALLIC HVAC DUCT ENCLOSURE ASSEMBLIES (AC179) 1.0 INTRODUCTION 1.1 Purpose: The purpose of this acceptance criteria is to establish requirements for fire protection enclosure systems, applied to metallic HVAC ducts which provide an alternate to required fire-resistance-rated shafts or an alternate to required fire dampers in specific locations, to be recognized in an ICC Evaluation Service, LLC (ICC- ES) evaluation report under the 2012, 2009 and 2006 International Building Code (IBC) and the 2012, 2009 and 2006 International Mechanical Code (IMC). Bases of recognition are 2012 IBC Sections , 713.1, 714, 717, 909 and ; 2009 IBC Sections , 708.2, 713, 716, and ; 2006 IBC Sections , 707.2, 712, 716 and ; and IMC Sections and Scope: This criteria includes requirements for applied, rigid or flexible fire protection enclosure systems (including stability, integrity, and insulation) that are installed on or as part of metallic HVAC ducts, yielding an alternate to required fire-resistance-rated shafts which are required to be protected from both internal and external fire exposure, or required fire dampers. This criteria provides an alternate to shaft enclosures for vertical ducts, and an alternate to fire dampers in horizontal ducts (penetrating fire barriers, fire partitions, and or smoke barriers) and vertical ducts connecting not more than two stories. This criteria is applicable to conventional shaft walls protecting metallic HVAC ducts. This criteria is applicable to ducts that are part of a pressurization system for elevator hoistways and stairways.this criteria is not applicable to commercial kitchen hood ventilation systems (grease ducts), non-metallic ducts, flexible air ducts, or shafts used for egress. The metallic HVAC duct system complying with this criteria may be installed with zero clearance from the insulating materials to combustibles. 1.3 Codes and Reference Standards: Reference Documents: , 2009 and 2006 International Building Code (IBC), International Code Council , 2009 and 2006 International Mechanical Code (IMC), International Code Council ASTM C411-05, Test Method for Hot-surface Performance of High-temperature Thermal Insulation, ASTM ASTM C518-10, Standard Test Method for Steady State Heat Flux Measurements and Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus, ASTM ASTM E84-09, Standard Test Method for Surface Burning Characteristics of Building Materials, ASTM ASTM E Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C, ASTM ASTM E814-08b Standard Test Method for Fire Tests of Through-penetration Fire Stops, ASTM ASTM E , Standard Practice for Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to Assess Surface Burning Characteristics, ASTM ASTM E , Standard Test Methods for Fire Resistive Metallic HVAC Duct Systems, ASTM UL , Standard for Test for Surface Burning Characteristics of Building Materials, Underwriters Laboratories LLC UL , Fire Tests of Through-Penetration Firestops - with revisions through March 2010, Underwriters Laboratories LLC. 1.4 Definitions: HVAC Duct: For the purposes of these criteria, a metallic heating, ventilating, or air-conditioning (HVAC) duct fabricated in accordance with Chapter 6 the IMC, which is often referred to as an air duct Shaft: An enclosed space extending though one or more stories of a building, connecting vertical openings in successive floors, or floors and roof Shaft Enclosure: The walls or construction forming the boundaries of a shaft. For HVAC ducts penetrating more than two floors, 2012 IBC Section 717.6, and 2009 and 2006 IBC Section require shaft enclosure walls to be fire-resistance-rated in accordance with 2012 IBC Section 713.4, 2009 IBC Section and 2006 IBC Section Section of the 2012 IBC, Section of the 2009 IBC and Section of the 2006 IBC require the rating to be one or two hours, depending on the number of floors penetrated by the shaft. Section 713 of the 2012 IBC, Section 708 of the 2009 IBC and Section 707 of the 2006 IBC require the shaft enclosure walls to satisfy the requirements of a fire barrier in accordance with 2012 and 2009 IBC Section 707 and 2006 IBC Section 706, or horizontal assemblies in accordance with 2012 IBC Section 714.4, 2009 IBC Section 712 and 2006 IBC Section 711, or both. Section requires all fire-resistance-rated walls to be assigned a rating based on fire exposure from the side with the least resistance. Fire-resistance-rated shaft enclosures are required for vertical HVAC duct penetrations of fire-resistance-rated floors or floor/ceiling assemblies, with the following exceptions: (1) In occupancies other than groups I-2 and I-3, a fire damper placed at the floor line is allowed when connecting not more than two stories; or (2) a maximum 4-inch-diameter HVAC duct is allowed to connect up to three stories without damper or shaft protection, provided all the exceptions to 2012 IBC Section , and 2009 and 2006 IBC Section , are satisfied. 2.0 BASIC INFORMATION 2.1 General: The following information shall be submitted: Product Description: Information on the manufacturing process of the fire protection enclosure system; method of packaging and product identification; specifications and/or mill order certificates for steel duct material, including gage, thickness and galvanization details. 2

4 ACCEPTANCE CRITERIA FOR METALLIC HVAC DUCT ENCLOSURE ASSEMBLIES (AC179) Installation Instructions: Description of fasteners, including manufacturer s type and method of application; details of duct supports; description of any covering or linings for the insulation material Packaging and Identification: A description of the method of packaging and field identification of the fire protection enclosure system. Identification provisions shall include the evaluation report number, the name or logo of the inspection agency, and a description of safety labeling. 2.2 Testing Laboratories: Testing laboratories shall comply with Section 2.0 of the ICC-ES Acceptance Criteria for Test Reports (AC85) and Section 4.2 of the ICC-ES Rules of Procedure for Evaluation Reports. 2.3 Test Reports: Test reports shall comply with AC85. Test reports shall include test specimen description, details of the test method, manner of testing, test results, calculated results, and photographs. The test reports shall also include information required by the applicable standard. 2.4 Product Sampling: Sampling of the duct insulation material for tests under this criteria shall comply with Section 3.1 of AC TEST METHODS AND PERFORMANCE REQUIREMENTS 3.1 General: Fire protection enclosure systems tested under this criteria shall satisfy the requirements of Sections 3.2, 3.3, 3.4, and 3.5 and/or Surface-burning Characteristics: Fire protection enclosure systems, including vapor barriers and adhesives, when used, shall have a flame-spread index of not more than 25 and a smoke-developed index of not more than 50, when tested in accordance with ASTM E84 or UL 723, using the specimen preparation and mounting procedures of ASTM E2231. Duct coverings shall not flame, flow, smolder or smoke when tested in accordance with ASTM C411 at the temperature to which they will be exposed in service. The test temperature shall not fall below 250 F (121 C). 3.3 Non-combustibility Tests: The duct-enclosure material, excluding its duct covering, shall be tested for compliance with ASTM E136, and the material shall be designated as passing the test. 3.4 Durability Tests: The purpose of durability tests is to simulate the effects of long-term exposure to typical in-service conditions on the thermal transmission properties of the duct covering materials A minimum of eight samples of the duct enclosure material is needed, in the thickness intended for use. The length and width of the test specimen shall comply with ASTM C518, and all specimens shall be conditioned for a minimum of 24 hours at 75 F ± 5 F (23.8 C ± 2.7 C) with a relative humidity of 50 ± 5 percent Four samples are exposed to the effects of temperature aging. An additional four samples are reserved as control samples for comparison. The temperature-aging samples are placed on a rack in a vertical position, with a clearance, between samples, of between 3 / 8 and 3 / 4 inch (9.5 to 19.1 mm). The rack is 3 placed into an oven that has been preheated to a temperature of 300 F (149 C). After 12 hours of exposure, the oven is shut off and the specimens are allowed to cool for 12 hours. This cycle is repeated 10 times. On completion of the final cycle, the specimens are removed from the oven and allowed to cool for a period of two hours at standard atmospheric conditions Thermal conductivity properties of temperature-aged samples and control samples are determined in accordance with ASTM C518. The average thermal conductivity of the temperature-aged samples shall be reported as a percentage of the average thermal conductivity of control samples Conditions of Acceptance: When compared to results for control specimens, thermal conductivity shall not increase by more than10 percent as a result of temperature aging. 3.5 Ducts with Fire Protection Enclosure Systems in lieu of Fire-resistance-rated Shaft Walls: To establish equivalence with fire-resistance-rated vertical shaft enclosures and fire dampers, the proprietary enclosure material and duct assembly shall be tested in accordance with ASTM E2816, Condition B Fire exposure from the outside of the vertical HVAC duct system without openings, and Condition D Fire exposure from the outside with hot gases entering the inside of the vertical HVAC duct system. These test methods provide a means for evaluating a vertical HVAC duct system with a horizontal connection, without openings exposed to fire (Condition B) and with unprotected openings exposed to fire (Condition D), passing through a horizontal fireseparating element protected with a through-penetration firestop system. The through-penetration firestop shall comply with the requirements of ASTM E814 or UL 1479 for the same period of time as indicated for the fireengulfment test Conditions B and D. The test specimen shall be representative of its intended construction, application, and installation. The test specimen configuration shall consist of metallic duct material of the thinnest gage, of the maximum cross-sectional area (and maximum duct dimension), with the minimum thickness fire protection enclosure system, for which recognition is sought. 3.6 Fire Protection for Horizontal and Vertical HVAC Ducts with Dedicated Fire Protection Systems in Lieu of Required Fire Dampers: The intent of this section is to establish equivalence of duct fire protection systems to the level of protection provided by required fire dampers, for specific applications as noted herein. The fire protection system, consisting of the proprietary protection materials or assemblies, including supports, shall be tested in accordance with and shall meet the conditions of acceptance of ASTM E Horizontal Ducts: ASTM E2816, Condition A Fire exposure from the outside of the horizontal HVAC duct system without openings, and Condition C Fire exposure from the outside with hot gases entering the inside of the horizontal HVAC duct system with unprotected openings. Recognition under Section is limited to horizontal ducts penetrating fire-resistance-rated fire barriers, fire partitions and/or smoke barriers each with a maximum fire-resistance rating of two hours. The through-penetration firestop shall comply with the requirements of ASTM E814 or UL 1479 for the same

5 ACCEPTANCE CRITERIA FOR METALLIC HVAC DUCT ENCLOSURE ASSEMBLIES (AC179) period of time as indicated for the fire-engulfment test Conditions A and C. The test shall be performed for horizontal applications, with metallic duct material of the thinnest gage, of the maximum cross-sectional area (and maximum duct dimension), with the minimum thickness fire protection enclosure system, for which recognition is sought Vertical Ducts: ASTM E2816, Condition B Fire exposure from the outside of the vertical HVAC duct system without openings, and Condition D Fire exposure from the outside with hot gases entering the inside of the vertical HVAC duct system with unprotected openings. Recognition under Section is limited to vertical ducts that connect multiple stories with a maximum fireresistance rating of two hours. The through-penetration firestop shall comply with the requirements of ASTM E814 or UL 1479 for the same period of time as indicated for the fire-engulfment test Conditions B and D. The test shall be performed for vertical applications, with metallic duct material of the thinnest gage, of the maximum crosssectional area (and maximum duct dimension), and with the minimum thickness fire protection enclosure system, for which recognition is sought. 3.7 Fire Protection for Horizontal and Vertical Stair or Elevator Hoistway Pressurization Systems with Dedicated Fire Protection Systems Ducts that are part of elevator hoistway pressurization systems under 2012 IBC Section or stair pressurization systems under 2012 IBC Section , shall meet the conditions of acceptance of ASTM E2816, Condition A Fire exposure from the outside of the horizontal HVAC duct system without openings, or Condition B Fire exposure from the outside of the vertical HVAC duct system without openings, or both orientations (Conditions A and B). The duct enclosure system shall consist of the proprietary protection materials or assemblies, including supports. 4.0 QUALITY CONTROL 4.1 The products shall be manufactured under an approved quality control program with inspections by an inspection agency accredited by the International Accreditation Service (IAS) or otherwise acceptable to ICCES. 4.2 Quality documentation complying with the ICC-ES Acceptance Criteria for Quality Documentation (AC 10) shall be submitted. 4.3 A qualifying inspection shall be conducted at each manufacturing facility when required by the ICC-ES Acceptance Criteria for Inspections and Inspection Agencies (AC304). 5.0 EVALUATION REPORT RECOGNITION The evaluation report shall include the following conditions of use: 5.1 The system shall bear the words Fire-Resistance- Rated Protective Duct Assembly - DO NOT REMOVE. The wording shall be visible after the fire protection system is installed. 5.2 Substitution of fire protection systems for required fire dampers under Section 3.6 is limited to horizontal ducts penetrating fire-resistance-rated fire barriers, fire partitions and/or smoke barriers, shaft enclosures, and to vertical ducts, each with a maximum fire-resistance rating of two hours. 5.3 For fire protection systems qualified under Section 3.6, openings are not permitted for a minimum distance of 6 feet ( mm) from each side of the fire-resistancerated assembly. 5.4 When qualification is under Sections 3.2, 3.3, 3.5 and either Section or Section 3.6.2, or both, the evaluation report shall include one or both of the following conditions of use: When penetrating fire-resistance-rated wall combustibles only when the ASTM E814 or UL 1479 F- rating equals or exceeds the fire-resistance rating of the wall assembly, as required by the applicable code. See 2012 IBC Section , 2009 IBC Section or 2006 IBC Section When penetrating fire-resistance-rated horizontal combustibles only when the ASTM E814 or UL 1479 F- rating and T-rating equal or exceed the fire-resistancerating of the horizontal assembly, as required by the applicable code. For exceptions, see 2012 IBC Section , 2009 IBC Section or 2006 IBC Section Smoke dampers must be installed as required by the applicable code. 5.6 When qualification is under Section 3.7, the evaluation report shall include the following condition of use: When penetrating fire-resistance-rated wall combustibles only when the F-rating and T-rating equal or exceed the fire-resistance-rating of the fire-resistancerated fire barrier, fire partition, or smoke barrier being penetrated. 4

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION July 23, 2010 TO: SUBJECT: PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION Revisions to the Acceptance Criteria for Reflective Foil Insulation, Subject AC02-0610-R1 (LS/RB) Dear Madam or Sir: In June

More information

December 3, 2012 PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS

December 3, 2012 PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS December 3, 2012 TO: PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS SUBJECT: Proposed Acceptance Criteria for Intumescent Fire-resistant Coatings

More information

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION June 1, 2010 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION SUBJECT: Proposed Revisions to the Acceptance Criteria for Reflective Foil Insulation, Subject AC02-0610-R1 (LS/RB)

More information

April 2, 2018 PARTIES INTERESTED IN CROSS LAMINATED TIMBER PANELS USED AS COMPONENTS IN FLOOR AND ROOF DECKS

April 2, 2018 PARTIES INTERESTED IN CROSS LAMINATED TIMBER PANELS USED AS COMPONENTS IN FLOOR AND ROOF DECKS April 2, 2018 TO: PARTIES INTERESTED IN CROSS LAMINATED TIMBER PANELS USED AS COMPONENTS IN FLOOR AND ROOF DECKS SUBJECT: Proposed Revisions to the ICC-ES Acceptance Criteria for Cross-laminated Timber

More information

June 9, 2008 PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS

June 9, 2008 PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect June 9, 2008 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS SUBJECT: Acceptance Criteria for Termite-resistant

More information

ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS PREFACE

ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR ROOF UNDERLAYMENT FOR USE IN SEVERE CLIMATE AREAS AC48 Approved January 2000 Effective February 1, 2000 (Editorially revised

More information

June 1, 2017 PARTIES INTERESTED IN POST-TENSIONING ANCHORAGES AND COUPLERS OF PRESTRESSED CONCRETE

June 1, 2017 PARTIES INTERESTED IN POST-TENSIONING ANCHORAGES AND COUPLERS OF PRESTRESSED CONCRETE June 1, 2017 TO: PARTIES INTERESTED IN POST-TENSIONING ANCHORAGES AND COUPLERS OF PRESTRESSED CONCRETE SUBJECT: Proposed Revisions to the Acceptance Criteria for Post-Tensioning Anchorages and Couplers

More information

June 22, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS

June 22, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS June 22, 2009 TO: SUBJECT: PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS Acceptance Criteria for Composite Cold-formed Light Gage Steel

More information

October 3, Section 1.2 Scope and Section 6.6 were revised to clarify interior and exterior construction types allowed.

October 3, Section 1.2 Scope and Section 6.6 were revised to clarify interior and exterior construction types allowed. October 3, 2016 TO: PARTIES INTERESTED IN EVALAUTION REPORTS ON FIBER- REINFORCED POLYMER (FRP) COMPOSITE COLUMNS USED AS AXIAL LOAD-BEARING AND NONLOAD-BEARING ARCHITECTURAL AND DECORATIVE COLUMNS SUBJECT:

More information

August 1, Removed reference to the standard edition from Sections and

August 1, Removed reference to the standard edition from Sections and August 1, 2018 TO: PARTIES INTERESTED IN SPRAYED FIRE-RESISTANT MATERIALS (SFRMs), INTUMESCENT FIRE-RESISTANT COATINGS AND MASTIC FIRE-RESISTANT COATINGS USED TO PROTECT STRUCTURAL STEEL MEMBERS SUBJECT:

More information

February 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Staples, Subject AC R1 (EL/JF)

February 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Staples, Subject AC R1 (EL/JF) February 1, 2018 TO: PARTIES INTERESTED IN STAPLES SUBJECT: Proposed Revisions to the Acceptance Criteria for Staples, Subject AC201-0218-R1 (EL/JF) Dear Colleague: We are seeking your comments on proposed

More information

October 12, Yours very truly, Gary G. Nichols, P.E., SECB Vice President. GGN/md Enclosure Evaluation Committee

October 12, Yours very truly, Gary G. Nichols, P.E., SECB Vice President. GGN/md Enclosure Evaluation Committee October 12, 2010 TO: SUBJECT: PARTIES INTERESTED IN EVALUATION REPORTS ON STAY-IN-PLACE, FOAM PLASTIC INSULATING CONCRETE FORM (ICF) SYSTEMS FOR SOLID CONCRETE WALLS Revisions to the Acceptance Criteria

More information

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) AC191 Approved May 2008 Effective June 1, 2008 Previously approved February 2008, October 2007,

More information

February 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS

February 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS February 1, 2010 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS SUBJECT: Proposed Revisions to the Acceptance Criteria for Roof Underlayments for Use

More information

December 1, 2014 PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS

December 1, 2014 PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS December 1, 2014 TO: PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS SUBJECT: Proposed Revision to the ICC-ES Acceptance Criteria for Structural Wood-Based Products, Subject AC47-1214-R2-2 (JF/PC)

More information

February 1, 2018 PARTIES INTERESTED IN DECK BOARD SPAN RATINGS AND GUARDRAIL SYSTEMS (GUARDS AND HANDRAILS)

February 1, 2018 PARTIES INTERESTED IN DECK BOARD SPAN RATINGS AND GUARDRAIL SYSTEMS (GUARDS AND HANDRAILS) February 1, 2018 TO: SUBJECT: PARTIES INTERESTED IN DECK BOARD SPAN RATINGS AND GUARDRAIL SYSTEMS (GUARDS AND HANDRAILS) Proposed Revisions to the ICC-ES Acceptance Criteria for Deck Board Span Ratings

More information

June 1, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS

June 1, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS June 1, 2009 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS SUBJECT: Proposed Revisions to the Acceptance Criteria for Wood-based Studs, Subject AC202-0609-R1

More information

April 18, 2018 PARTIES INTERESTED IN ADHERED PORCELAIN TILE WALL CLADDING SYSTEM

April 18, 2018 PARTIES INTERESTED IN ADHERED PORCELAIN TILE WALL CLADDING SYSTEM April 18, 2018 TO: SUBJECT: PARTIES INTERESTED IN ADHERED PORCELAIN TILE WALL CLADDING SYSTEM Proposed Acceptance Criteria for Adhered Porcelain Tile Wall Cladding System, Subject (YM/DO) Hearing Information:

More information

ACCEPTANCE CRITERIA FOR THREADED HIGH-STRENGTH STEEL BARS FOR CONCRETE REINFORCEMENT PREFACE

ACCEPTANCE CRITERIA FOR THREADED HIGH-STRENGTH STEEL BARS FOR CONCRETE REINFORCEMENT PREFACE www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR THREADED HIGH-STRENGTH STEEL BARS FOR CONCRETE REINFORCEMENT AC237 Approved June 2009

More information

PMG LISTING CRITERIA FOR PERT-AL-PERT PIPE AND FITTINGS FOR REFRIGERATION APPLICATIONS LC1039. Approved Date: November 2015 PREFACE

PMG LISTING CRITERIA FOR PERT-AL-PERT PIPE AND FITTINGS FOR REFRIGERATION APPLICATIONS LC1039. Approved Date: November 2015 PREFACE www.icc-es.org/pmg (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR PERT-AL-PERT PIPE AND FITTINGS FOR REFRIGERATION APPLICATIONS Approved Date: November

More information

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS June 1, 2012 TO: PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS SUBJECT: Proposed Revisions to the Acceptance Criteria for Cold-formed Steel Framing Members, Subject AC46-0612-R1 (WM/DM) Dear

More information

ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS PREFACE

ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR WATER-RESISTIVE BARRIERS AC38 Approved June 2004 Effective July 1, 2004 Previously approved July 2000, September 1990 PREFACE

More information

PMG LISTING CRITERIA FOR MULTILAYER PIPE AND FITTINGS ASSEMBLY FOR REFRIGERANT APPLICATIONS LC1036

PMG LISTING CRITERIA FOR MULTILAYER PIPE AND FITTINGS ASSEMBLY FOR REFRIGERANT APPLICATIONS LC1036 www.icc-es-pmg.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR MULTILAYER PIPE AND FITTINGS ASSEMBLY FOR REFRIGERANT APPLICATIONS LC1036 August

More information

ACCEPTANCE CRITERIA FOR METAL COMPOSITE MATERIAL (MCM) PREFACE

ACCEPTANCE CRITERIA FOR METAL COMPOSITE MATERIAL (MCM) PREFACE www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR METAL COMPOSITE MATERIAL (MCM) AC25 Approved October 2010 (Editorially revised August

More information

ICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years.

ICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years. ICC-ES Evaluation Report ESR-1255 Reissued May 1, 2010 This report is subject to re-examination in two years. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information

PMG LISTING CRITERIA FOR STRUCTURAL ADHESIVE JOINING SYSTEMS FOR FITTINGS PREFACE

PMG LISTING CRITERIA FOR STRUCTURAL ADHESIVE JOINING SYSTEMS FOR FITTINGS PREFACE www.icc-es.org/pmg (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR STRUCTURAL ADHESIVE JOINING SYSTEMS FOR FITTINGS Approved March 2009 (Editorially

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MINERAL-FIBER FIREPROOFING REPORT HOLDER: THERMAL CERAMICS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MINERAL-FIBER FIREPROOFING REPORT HOLDER: THERMAL CERAMICS, INC. 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2213 Reissued 04/2018 This report is subject to renewal 04/2019. DIVISION: 07 00

More information

2012 IBC Inspection of Fire-resistance Rated Walls

2012 IBC Inspection of Fire-resistance Rated Walls Accreditation 2012 IBC Inspection of Fire-resistance Rated Walls Based on the 2012 International Building Code (IBC ) The International Code Council has been accredited as an Authorized Provider by the

More information

The purpose of this memo is to respond to the comments received in response to the May 1, 2007, staff letter and the revised criteria.

The purpose of this memo is to respond to the comments received in response to the May 1, 2007, staff letter and the revised criteria. ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect #19 To: From: ICC-ES Evaluation Committee Brian Gerber, S.E., and Irni Yani Date: June 1, 2007 Subject: Revisions to the Proposed Acceptance Criteria

More information

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs Accreditation 2012 IBC Inspection of Fire-resistance-Rated Floors, Ceilings and Roofs Based on 2012 International Building Code The International Code Council has been accredited as an Authorized Provider

More information

The Rehabilitation of Existing Building Drains and Building Sewers by the

The Rehabilitation of Existing Building Drains and Building Sewers by the Inversion or Pulled-in-Place Method and Curing of Resin-impregnated Tube Page 1 of 7 www.icc-es.org/pmg (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council PROPOSED PMG LISTING

More information

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs Class Outline Inspection of Fire-resistance-Rated Floors, Ceilings and Roofs Based on 2012 International Building Code (IBC) Introduction Determining fire resistance Test standards Definitions Alternate

More information

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD.

Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD. Following contains common verbiage found in major model building codes and has been edited for the purpose of inclusion on this CD. Included are selected sections of codes taken directly from: 1997 Uniform

More information

PMG LISTING CRITERIA FOR PUSH-FIT FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS LC1009

PMG LISTING CRITERIA FOR PUSH-FIT FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS LC1009 www.icc-es.org/pmg (800) 42-6587 (562) 699-054 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR PUSH-FIT FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS Approved April

More information

December 1, 2014 PARTIES INTERESTED IN WATER-RESISTIVE BARRIERS

December 1, 2014 PARTIES INTERESTED IN WATER-RESISTIVE BARRIERS December 1, 2014 TO: PARTIES INTERESTED IN WATER-RESISTIVE BARRIERS SUBJECT: Proposed Revisions to the Acceptance Criteria for Water-resistive Barriers, Subject AC38-1214-R1 (ST/GH) Dear Colleague: You

More information

2015 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2015 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs Class Outline Inspection of Fire-Resistance-Rated Floors, Ceilings and Roofs Based on 2015 International Building Code, (IBC ) Introduction Determining fire resistance Test standards Definitions Alternate

More information

ACCEPTANCE CRITERIA FOR POLYMER-BASED AND POLYMER-MODIFIED EXTERIOR AND INTERIOR WALL CLADDING

ACCEPTANCE CRITERIA FOR POLYMER-BASED AND POLYMER-MODIFIED EXTERIOR AND INTERIOR WALL CLADDING www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR POLYMER-BASED AND POLYMER-MODIFIED EXTERIOR AND INTERIOR WALL CLADDING AC92 Approved

More information

December 1, 2011 PARTIES INTERESTED IN ALTERNATE DOWEL-TYPE THREADED FASTENERS

December 1, 2011 PARTIES INTERESTED IN ALTERNATE DOWEL-TYPE THREADED FASTENERS December 1, 2011 TO: PARTIES INTERESTED IN ALTERNATE DOWEL-TYPE THREADED S SUBJECT: Proposed Revisions to the Acceptance Criteria for Alternate Dowel-type Threaded Fasteners, Subject AC233-1211-R1 (EL/JS)

More information

February 1, 2016 PARTIES INTERESTED IN EXTERIOR ULTRA-HIGH PERFORMANCE CONCRETE THIN WALL CLADDING PANELS

February 1, 2016 PARTIES INTERESTED IN EXTERIOR ULTRA-HIGH PERFORMANCE CONCRETE THIN WALL CLADDING PANELS February 1, 2016 TO: PARTIES INTERESTED IN EXTERIOR ULTRA-HIGH PERFORMANCE CONCRETE THIN WALL CLADDING PANELS SUBJECT: Proposed Revisions to the Acceptance Criteria for Exterior Ultra-high Performance

More information

ESR-1061 Reissued May 1, 2011 This report is subject to renewal in two years.

ESR-1061 Reissued May 1, 2011 This report is subject to renewal in two years. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION Section: 07 21 00 Thermal Insulation Section: 07 25 00 Water-Resistive Barriers/Weather

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIRESTOPPING REPORT HOLDER: PASSIVE FIRE PROTECTION PARTNERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIRESTOPPING REPORT HOLDER: PASSIVE FIRE PROTECTION PARTNERS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2996 Reissued 12/2017 This report is subject to renewal 12/2019. DIVISION: 07 00

More information

ACCEPTANCE CRITERIA FOR EXPANSION BOLTS IN STRUCTURAL STEEL CONNECTIONS (BLIND-BOLTS) PREFACE

ACCEPTANCE CRITERIA FOR EXPANSION BOLTS IN STRUCTURAL STEEL CONNECTIONS (BLIND-BOLTS) PREFACE www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR EXPANSION BOLTS IN STRUCTURAL STEEL CONNECTIONS (BLIND-BOLTS) AC437 Approved October

More information

EVALUATION SUBJECT: THE UNICO SYSTEM SMALL- DUCT, HIGH-VELOCITY HEATING AND COOLING SYSTEMS

EVALUATION SUBJECT: THE UNICO SYSTEM SMALL- DUCT, HIGH-VELOCITY HEATING AND COOLING SYSTEMS ICC-ES Report PMG-1002 Reissued 08/2018 This report is subject to renewal 08/2019 EVALUATION SUBJECT: THE UNICO SYSTEM SMALL- DUCT, HIGH-VELOCITY HEATING AND COOLING SYSTEMS DIVISION: 23 00 00 HEATING,

More information

August 31, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ACCESS FLOORS

August 31, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ACCESS FLOORS August 31, 2010 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON ACCESS FLOORS SUBJECT: Proposed Revisions to the Acceptance Criteria for Access Floors, Subject AC300-1010-R1 (EL/BG) Dear Madam or Sir:

More information

Code Change No: FS43-06/07

Code Change No: FS43-06/07 CODE CHANGES RESOURCE COLLECTION INTERNATIONAL MECHANICAL CODE PART III IBC MEANS OF EGRESS Approved as Submitted Committee Reason: The revised language in Sections 1021.3 and 1022.2. would provide consistency

More information

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER AC51 Approved February 2008 Effective March 1, 2008 (Editorially

More information

Originally Issued: 08/03/2017 Revised: 02/01/2019 Valid Through: 08/31/2019

Originally Issued: 08/03/2017 Revised: 02/01/2019 Valid Through: 08/31/2019 ACCELLA POLYURETHANE SYSTEMS, LLC. 100 Enterprise Drive Cartersville, GA 30120 Phone: (770) 607-0755 www.accellapolyurethane.com BAYSEAL CC X AND BAYSEAL CC XP SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 6587 (562) 699 0543 www.icc es.org ESR 3152 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MINERAL FIBER FIREPROOFING REPORT HOLDER: UNIFRAX I LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MINERAL FIBER FIREPROOFING REPORT HOLDER: UNIFRAX I LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2224 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00

More information

Originally Issued: 11/06/2017 Valid Through: 11/30/2018

Originally Issued: 11/06/2017 Valid Through: 11/30/2018 ACCELLA POLYURETHANE SYSTEMS, LLC. SEALTITE CC+ SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION CSI Section: 07 21 00 Thermal Insulation 1.0 RECOGNITION insulations described in this report have been

More information

2009 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)

2009 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata) TWELFTH PRINTING (Updated December 6, 2016) Note for 706.5.1: This is an erratum in the 8 th, 9 th, 10 th and 11 th printing only. The reference is correct in other editions. 706.5.1 Exterior walls. Where

More information

PMG LISTING CRITERIA FOR PRESS-CONNECTION FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS PREFACE

PMG LISTING CRITERIA FOR PRESS-CONNECTION FITTINGS FOR POTABLE WATER TUBE AND RADIANT HEATING SYSTEMS PREFACE Title???? Page 1 of 1 www.icc-es.org/pmg (800) 42-6587 (562) 699-054 A Subsidiary of the International Code Council PMG LISTING CRITERIA FOR PRESS-CONNECTION FITTINGS FOR POTABLE WATER TUBE AND RADIANT

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-07 84 00 (May 2010) Change 1-08/13 ------------------------ Preparing Activity: USACE Superseding UFGS-07 84 00 (October 2007) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

FS , 712, 713, 714

FS , 712, 713, 714 VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL JUNE 28-29, 2012 PUBLIC COMMENTS CTC Code Change Proposal FS50-12 was Approved as Modified as shown below - No public comments for the Group

More information

June 25, 2012 PARTIES INTERESTED IN SPRAY-APPLIED FOAM PLASTIC INSULATION

June 25, 2012 PARTIES INTERESTED IN SPRAY-APPLIED FOAM PLASTIC INSULATION June 25, 2012 TO: PARTIES INTERESTED IN SPRAY-APPLIED FOAM PLASTIC INSULATION SUBJECT: Revisions to the Acceptance Criteria for Spray-applied Foam Plastic Insulation, Subject AC377-0612-R1 (SF/MB) Dear

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION DIVISION: AIR BARRIERS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION DIVISION: AIR BARRIERS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2717 Reissued 07/2017 This report is subject to renewal 07/2019. DIVISION: 07 00

More information

VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES

VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES The following is the Study Group report that was considered by the CTC at its October 13-14, 2011 meeting.

More information

REPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION

REPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3914 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) LLC 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3210 Valid: 03/15 to 03/16 DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21

More information

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3089 Reissued 07/2016 This report is subject to renewal 07/2018. DIVISION: 07 00

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES 1.0 INTRODUCTION INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR COMPOSITE STEEL SHEET AND NONCOMBUSTIBLE SHEATHING PANELS EC 012-2016

More information

Common Firestop Issues in Wood Framed Commercial Construction

Common Firestop Issues in Wood Framed Commercial Construction Common Firestop Issues in Wood Framed Commercial Construction October 2014 At the July 24, 2014 Metro KC ICC Fire and Life Safety Training all day seminar, there were multiple questions pertaining to issues

More information

FCIA Webinar Gypsum Wall Patching

FCIA Webinar Gypsum Wall Patching FCIA Webinar Gypsum Wall Patching Firestop Contractors International Association Hillside, IL +1-708-202-1108 - office Bill McHugh bill @ fcia.org Nestor Sanchez, USG Corp. nsanchez@usg.com DIIM Firestopping

More information

Originally Issued: 04/17/2015 Valid Through: 04/30/2016

Originally Issued: 04/17/2015 Valid Through: 04/30/2016 EVALUATION SUBJECT: Foamsulate 50-NIB Spray-Applied Polyurethane Foam Plastic Insulation REPORT HOLDER: Premium Spray Products 1255 Kennestone Circle, Suite 200 Marietta, Georgia 30066 www.premiumspray.com

More information

ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015.

ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015. A Subsidiary of the International Code Council

More information

Excerpts from the Uniform Building Code. (UBC) For The US

Excerpts from the Uniform Building Code. (UBC) For The US Excerpts from the Uniform Building Code (UBC) For The US Index 4301 FIRE-RESISTIVE STANDARDS 1. Section 4301(a) Standards of Quality 2. Section 4301(b) Definitions 4304 WALLS AND PARTITIONS 1. Sec.4304(a)

More information

Originally Issued: 2/12/2016 Revised: 07/28/2017 Valid Through: 2/28/2018

Originally Issued: 2/12/2016 Revised: 07/28/2017 Valid Through: 2/28/2018 EVALUATION SUBJECT: FOAMSULATE 50 AND FOAMSULATE 210 SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION REPORT HOLDER: Accella Polyurethane Systems 100 Enterprise Drive Cartersville, GA 30120 (770) 607-0755

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER: 0 ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org Most Widely Accepted and Trusted ESR-4099 Reissued 07/2018 Revised 08/2018 This report is subject to renewal 07/2019.

More information

Protecting Penetrations in Fire Rated Construction

Protecting Penetrations in Fire Rated Construction Protecting Penetrations in Fire Rated Construction NY State Fire Marshals and Inspectors Conference September 7 th Bruce E. Johnson UL Codes and Advisory Services UL and the UL logo are Trademarks of UL

More information

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER PREFACE

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER AC51 Approved February 2008 Effective March 1, 2008 Previously approved October 2007, January 2001,

More information

April 1, 2015 PARTIES INTERESTED IN FLEXIBLE FLASHING MATERIALS

April 1, 2015 PARTIES INTERESTED IN FLEXIBLE FLASHING MATERIALS April 1, 2015 TO: PARTIES INTERESTED IN FLEXIBLE FLASHING MATERIALS SUBJECT: Proposed Revisions to the Acceptance Criteria for Flexible Flashing Materials, Subject AC148-0415-R1 (ST/YM) Dear Colleague:

More information

March 6, 2012 PARTIES INTERESTED IN THE DETERMINATION OF FORMALDEHYDE EMISSIONS OF COMPOSITE WOOD PRODUCTS

March 6, 2012 PARTIES INTERESTED IN THE DETERMINATION OF FORMALDEHYDE EMISSIONS OF COMPOSITE WOOD PRODUCTS March 6, 2012 TO: SUBJECT: PARTIES INTERESTED IN THE DETERMINATION OF FORMALDEHYDE EMISSIONS OF COMPOSITE WOOD PRODUCTS Revisions to the Environmental Criteria for Determination of Formaldehyde Emissions

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: THE DOW CHEMICAL COMPANY

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: THE DOW CHEMICAL COMPANY 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2670 Reissued 07/2017 This report is subject to renewal 07/2019. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1504 Reissued 03/2017 This report is subject to renewal 03/2018. DIVISION: 07 00

More information

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council Copyright This presentation is protected

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER: 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 2717 Reissued 07/2015 This report is subject to renewal 07/2017. DIVISION: 07 00 00 THERMAL

More information

EVALUATION SUBJECT: VIEGA LLC S PUREFLOW PLUMBING SYSTEM

EVALUATION SUBJECT: VIEGA LLC S PUREFLOW PLUMBING SYSTEM ICC-ES Report PMG-1038 Reissued 11/2018 This report is subject to renewal 11/2019 EVALUATION SUBJECT: VIEGA LLC S PUREFLOW PLUMBING SYSTEM DIVISION: 22 00 00 PLUMBING SECTION: 22 11 16 DOMESTIC WATER PIPING

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: BASF CORPORATION (RIGID PU SYSTEMS)

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: BASF CORPORATION (RIGID PU SYSTEMS) 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3662 Reissued 05/2017 This report is subject to renewal 02/2019. DIVISION: 07 00

More information

Originally Issued: 03/31/2017 Revised: 03/15/2018 Valid Through: 03/31/2018

Originally Issued: 03/31/2017 Revised: 03/15/2018 Valid Through: 03/31/2018 OLDCASTLE ARCHITECTURAL INSULTECH CSI Sections: 04 22 00 Concrete Unit Masonry 04 22 00.13 Concrete Unit Veneer Masonry 1.0 RECOGNITION Oldcastle Architectural Insultech insulated concrete masonry unit

More information

April 18, 2018 PARTIES INTERESTED IN RAISED-DECK SYSTEMS INSTALLED OVER ROOF ASSEMBLIES OR EXTERIOR SUPPORTING STRUCTURES

April 18, 2018 PARTIES INTERESTED IN RAISED-DECK SYSTEMS INSTALLED OVER ROOF ASSEMBLIES OR EXTERIOR SUPPORTING STRUCTURES April 18, 2018 TO: PARTIES INTERESTED IN RAISED-DECK SYSTEMS INSTALLED OVER ROOF ASSEMBLIES OR EXTERIOR SUPPORTING STRUCTURES SUBJECT: Proposed Acceptance Criteria for Raised-deck Systems Installed Over

More information

June 19, 2012 PARTIES INTERESTED IN SCREW FOUNDATION SYSTEMS

June 19, 2012 PARTIES INTERESTED IN SCREW FOUNDATION SYSTEMS June 19, 2012 TO: PARTIES INTERESTED IN SCREW FOUNDATION SYSTEMS SUBJECT: Acceptance Criteria for Screw Foundation Systems (SFSs), Subject AC443-0612-R1 (DZ/KS)] Dear Colleague: We are enclosing the new

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 07 Thermal and Moisture Protection 8400 Firestopping

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 07 Thermal and Moisture Protection 8400 Firestopping 1 General 1.1 The bidding requirements, contracting requirements, and applicable parts of Division 1 - General Requirements, as listed in the Table of Contents, shall be included in and made a part of

More information

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council Copyright This presentation is protected

More information

DIVISION: THERMAL AND MOISTURE SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2668 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: APPLIED FIREPROOFING REPORT HOLDER: CARBOLINE COMPANY

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: APPLIED FIREPROOFING REPORT HOLDER: CARBOLINE COMPANY 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 973 Reissued /207 This report is subject to renewal /208. DIVISION: 07 00 00 THERMAL

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: FOUR SEASONS BUILDING PRODUCTS, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: FOUR SEASONS BUILDING PRODUCTS, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2229 Reissued 05/2018 This report is subject to renewal 05/2019. DIVISION: 07 00

More information

Combustible Exterior Wall Cladding Systems: An ICC Perspective

Combustible Exterior Wall Cladding Systems: An ICC Perspective Combustible Exterior Wall Cladding Systems: An ICC Perspective The tragic Grenfell Tower fire in London brought extensive public focus on combustible exterior wall systems, often called cladding, prompting

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2668 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 07 00

More information

Building Codes and Ordinances ARC 227

Building Codes and Ordinances ARC 227 Building Codes and Ordinances ARC 227 Week 6 Fire Resistive Construction 03.02.10 Instructor: Rick Staub, AIA Email: staub@pointonearchitects.com Phone: 860-434-7707 Fire Resistive Construction Passive

More information

April 18, 2018 PARTIES INTERESTED IN FIBER REINFORCED PLASTIC (FRP) MODULAR WALL SYSTEMS

April 18, 2018 PARTIES INTERESTED IN FIBER REINFORCED PLASTIC (FRP) MODULAR WALL SYSTEMS April 18, 2018 TO: PARTIES INTERESTED IN FIBER REINFORCED PLASTIC (FRP) MODULAR WALL SYSTEMS SUBJECT: Proposed Revisions to the Acceptance Criteria for Fiber Reinforced Plastic (FRP) Modular Wall Systems,

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC. 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1143 Reissued 04/2017 This report is subject to renewal 04/2018. DIVISION: 07 00 00 THERMAL

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2600 Reissued 02/2017 This report is subject to renewal 02/2018. DIVISION: 07 00

More information

DIVISION: SPECIALTIES SECTION: MANUFACTURED FIREPLACES REPORT HOLDER: FIRE ROCK PRODUCTS LLC

DIVISION: SPECIALTIES SECTION: MANUFACTURED FIREPLACES REPORT HOLDER: FIRE ROCK PRODUCTS LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2599 Reissued 04/2018 This report is subject to renewal 04/2020. DIVISION: 10 00

More information

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016.

ICC ES SYSTEM SYSTEM. Trusted DIVISION: 07 SECTION: AND FINISH REPORT HOLDER: ICC-ES Evaluation. Reissued 08/2016. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg ESR 2562 Reissued 08/206 This report is subject to renewal 08/208. DIVISION: 07 00 00

More information

MSC Guidelines for Review of Ventilation System Plans

MSC Guidelines for Review of Ventilation System Plans K. B. FERRIE, CDR, Chief, Hull Division Purpose: This Plan Review Guideline (PRG) explains the requirements for seeking plan approval of ventilation systems from the Marine Safety Center (MSC) for most

More information

Originally Issued: 05/20/2013 Revised: 07/07/2017 Valid Through: 05/31/ Design

Originally Issued: 05/20/2013 Revised: 07/07/2017 Valid Through: 05/31/ Design BRADY INNOVATIONS, LLC. PROX HEADER SYSTEM CSI Section: 05 05 23 Metal Fastenings 05 40 00 Cold-formed Metal Framing 1.0 RECOGNITION Brady Innovations, LLC s ProX Header System recognized in this report

More information

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: DIVERSIFOAM PRODUCTS EVALUATION SUBJECT:

DIVISION: CONCRETE SECTION: INSULATING CONCRETE FORMING REPORT HOLDER: DIVERSIFOAM PRODUCTS EVALUATION SUBJECT: 0 ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org Most Widely Accepted and Trusted ESR 1815 Reissued 10/2018 Revised 11/2018 This report is subject to renewal 10/2020.

More information

EVALUATION SUBJECT: UPONOR/WIRSBO hepex TUBING, UPONOR AQUAPEX TUBING AND FITTINGS

EVALUATION SUBJECT: UPONOR/WIRSBO hepex TUBING, UPONOR AQUAPEX TUBING AND FITTINGS ICC-ES Report PMG-1012 Reissued 08/2017 This report is subject to renewal 08/2018 EVALUATION SUBJECT: UPONOR/WIRSBO hepex TUBING, UPONOR AQUAPEX TUBING AND FITTINGS DIVISION: 23 00 00 HEATING, VENTILATING

More information

Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION

Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION Sections: 4-16-01 PURPOSE 4-16-02 APPLICABLE AREA 4-16-03 CONSTRUCTION AND OCCUPANCY 4-16-04 UPPER BUILDING AREA, HEIGHT, NUMBER OF STORIES

More information

FIRE-RESISTANCE-RATED CONSTRUCTION

FIRE-RESISTANCE-RATED CONSTRUCTION CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION BC 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated

More information