PHOTO 1: View from Inside the Structure. Note the Rotation of the WSP, Failure at the Lower Leading Edge and Deformation of the Top Plate

Size: px
Start display at page:

Download "PHOTO 1: View from Inside the Structure. Note the Rotation of the WSP, Failure at the Lower Leading Edge and Deformation of the Top Plate"

Transcription

1 2009 International Residential Code (IRC) Braced Wall Panel Design Value Comparative Equivalency Testing Braced Wall Panel Design Values July 15, 2010 Introduction: SBCRI undertook 39 tests resulting in 78 30' braced wall lines being evaluated. For these tests, the SBCRI standard comparative equivalency 12'x30' IRC single-story test structure was used to assess the performance of a 2009 IRC-based structure. PHOTO 1: View from Inside the Structure. Note the Rotation of the WSP, Failure at the Lower Leading Edge and Deformation of the Top Plate PHOTO 2: Fasteners Tear Out at the Top of the Braced Wall Panel View all SBCA Tech Notes at SBCA 6300 Enterprise Lane Madison, WI / / (fax)

2 Full Scale Testing of a Building Constructed as Specified by the IRC: To learn as much as possible about the assumptions made by the ICC Ad-Hoc Wall Bracing (AHWB) Committee in crafting the IRC, SBCRI created a standard 12'x30' single-story building, built precisely as specified in the IRC. The initial testing used IRC Method Wood Structual Panel (WSP) braced wall lines. See the following reports for the testing approach, test details and the building specification used to establish SBCRI's standard comparative equivalency benchmarks: 1. Critical Concepts Surrounding Deployment of ASTM E72, E564 and E2126 to Establish IRC/IBC Braced Wall Panel Design Values 2. Creation of the SBCRI Standard Comparative Equivalency Test Structure A 12'x30' IRC Single- Story Building 3. Specifications for the SBCRI Standard Comparative Equivalency Test Structure A 12'x30' IRC Single-Story Building 4. Background on the Development of the 2009 International Residential Code (IRC) Braced Wall Panel Section 5. Detailed test reports of each test will be placed on the IRC wall panel testing web page. Reports are currently available by contacting SBCRI at testdata@sbcri.info or by calling Emily at FIGURE 1: 3D Representation of Test Setup This setup represents the lower bound of the IRC braced wall panel Method WSP using 3 /8" OSB for the bracing panels located near the maximum allowed distance from the ends of the braced wall line per IRC Section R Testing was performed using ASTM E564 procedures and resulted in a two 30' shear wall/four braced wall panel average ultimate load of 367 PLF 1. 1 IRC Braced Wall Panel Testing in a 12' by 30' Full Scale Building Method WSP Constructed Braced Wall Panel System Performance Under Laterally Applied Monotonic Loading (WSP 3 /8" Test), SBCRI Test Report # SBCRI SBCA Tech Notes Page 2

3 The IRC assumption for Method 3 braced wall panels (without gypsum) is that the braced wall panel has a capacity of 500 PLF (prior to adjustments for partial restraint and/or systems effects). Therefore, to calibrate the SBCRI full scale test of a building constructed as specified by the IRC, an Actual Building Calibration Factor (ABC Factor) was created for each comparative equivalency test undertaken. This ABC Factor is defined as the IRC wall value divided by the tested value. For example, the IRC defines the baseline WSP wall as follows: FIGURE 2: IRC Maximum End Distance for Braced Wall Panels and IRC Table R WSP Application Defined SBCRI testing defines the Actual Building Calibration Factor as: SBCRI Comparative Equivalency Test # SBCRI Description of Wall Tested IRC 3 /8" WSP 6d 6 /12 Restraint IRC anchor bolts, trusses and actual roof dead load (sheathing and ceiling gypsum) Actual Building Test Average Ultimate Load (PLF) TABLE 1: Definition of Actual Building Calibration Factor (ABC Factor) IRC Assumed Load w/ Full Restraint (PLF) Full Scale Building to IRC Design Value Calibration Factor Similarly, the ultimate PLF loads in the table below are used as the basis for comparing the test results that follow: Ultimate Load Summary Basis of Comparison Description Sheathing Type Sheathing Location Sheathing Fastener Type Sheathing Fastener Spacing Restraint Interior Gypsum Ultimate PLF Load Intermittent WSP (Method 3) IRC basis 3 /8" WSP Any permitted 6d (0.113 x 2") 6 /12 Fully Restrained No Wood-Frame Shear Wall SDPWS basis 3 /8" WSP - 6d (0.113 x 2") 6 /12 Fully Restrained No Wood-Frame Shear Wall SDPWS basis 7 /16" WSP - 8d (0.131 x 2-1 /2") 6 Fully /12 Restrained TABLE 2: Ultimate PLF Loads Used as the Basis for Comparing Test Results No Table 1 from The Story Behind the 2009 IRC Wall Bracing Provisions (Part 2, Wind Bracing Requirements), Jay H. Crandell, P.E., ARES Consulting Zeno A. Martin, P.E., WJE Assoc., Wood Design Focus continuation of previous article, Vol. 17, No. 2, Summer SDPWS, Table 4.3A value adjusted for SPF lumber per footnote 3 (table value x 0.92 = adjusted value) 4 SDPWS, Table 4.3A value adjusted for SPF lumber per footnote 3 (table value x 0.92 = adjusted value) SBCA Tech Notes Page 3

4 SBCRI has undertaken the following matrix of IRC/SDPWS benchmark tests: Ultimate Load Summary Table of Wall Types Tested SBCRI Comparative Equivalency Test # Sheathing Type Sheathing Location Sheathing Fastener Type Sheathing Fastener Spacing Restraint Interior Gypsum5 Ultimate PLF Load SBCRI SBCRI a SBCRI b 3 /8" WSP 7 /16" WSP 6' from corners 6 6' from corners 6d (0.113 x 2") 6 /12 8d (0.131 x 2-1 /2") 6 /12 SBCRI /16" WSP At Corners 8d (0.131 x 2-1 /2") 6 /12 Partial - Full Building Dead Load, IRC Anchor Bolts Partial - Full Building Dead Load, IRC Anchor Bolts Partial - Full Building Dead Load, IRC Anchor Bolts No 367 No 412 No 426 SBCRI /16" WSP 6' from corners 8d (0.131 x 2-1 /2") 6 /12 Fully Restrained No 626 TABLE 3: Ultimate Load Summary Table of Wall Types Tested Given the above matrix of ASTM E564 testing where each test was performed on two 30' shear wall/four braced wall panels, the following IRC/SDPWS calibration factors have been developed: Calibration Factors Comparing SBCRI Full Scale Building Tests to IRC/SDPWS Design Values Using 3 /8" OSB as the Basis (IRC value of 500 PLF/SDPWS of 515 PLF) Test Description IRC 3 /8" WSP 6d 6 6' from corner Test # SBCRI IRC 7 /16" WSP 8d 6 6' from corner Test # SBCRI a Test # SBCRI b IRC 7 /16" WSP 8d 6 corner Test # SBCRI IRC 7 /16" WSP 8d 6 6' from corner with hold downs Test # SBCRI Ultimate PLF Load (unrestrained and restrained) Full Scale Building to IRC Design Value (500 PLF) Calibration Factor Full Scale Building to SDPWS Restrained Design Value (515 PLF) Calibration Factor 3 /8" WSP Basis /500 = /515 = /500 = /515 = /500 = /515 = /500 = /515 = 1.2 TABLE 4: Calibration Factors Comparing SBCRI Full Scale Building Tests to IRC/SDPWS Design Values Using 3 /8" OSB as the Basis (IRC value of 500 PLF/SDPWS of 515 PLF) 5 If Interior sheathing was indicated as Yes, ½" gypsum is applied along the entire 30' braced wall lines in accordance with IRC Table R and Section R Sheathing installed 64" from one corner and 72" from opposite end. For all other tests, WSPs were installed symmetrically at 6' from each end. SBCA Tech Notes Page 4

5 Calibration Factors Comparing SBCRI Full Scale Building Tests to IRC/SDPWS Design Values Using 7 /16" OSB as the Basis (SDPWS value of 672 PLF) Test Description Ultimate PLF Load (unrestrained and restrained) Full Scale Building to SDPWS Design Value (672 PLF) Calibration Factor 7 /16" WSP Basis IRC 3 /8" WSP 6d 6 6' from corner Test # SBCRI IRC 7 /16" WSP 8d 6 6' from corner Test # SBCRI a Test # SBCRI b IRC 7 /16" WSP 8d 6 corner Test # SBCRI IRC 7 /16" WSP 8d 6 6' from corner with hold downs Test # SBCRI /672 = /672 = /672 = /672 = 0.9 TABLE 5: Calibration Factors Comparing SBCRI Full Scale Building Tests to IRC/SDPWS Design Values Using 7 /16" OSB as the Basis (SDPWS value of 672 PLF) Calibration Factors Comparing SBCRI Full Scale Building Tests Test Description Ultimate PLF Load (unrestrained and restrained) Full Scale Building Partial Restraint to Full Scale Building Full Restraint Factor Full Scale Unrestrained 3 /8" OSB performance to full scale 7 /16" OSB performance built per IRC Full Scale 7 /16" OSB performance to full scale unrestrained 3 /8" OSB performance built per IRC IRC 3 /8" WSP 6d 6 6' from corner Test # SBCRI IRC 7 /16" WSP 8d 6 6' from corner Test # SBCRI a Test # SBCRI b IRC 7 /16" WSP 8d 6 corner Test # SBCRI /626 = /626 = /412 = /367 = /626 = /426 = /367 = 1.2 IRC 7 /16" WSP 8d 6 6' from corner with hold downs Test # SBCRI /626 = /367 = 1.7 TABLE 6: Calibration Factors Comparing SBCRI Full Scale Building Tests The SBCRI testing shows that the AHWB Committee made the best judgments it could given the data at its disposal. The SBCRI full scale building testing a building constructed as prescribed by the IRC having two 30' braced wall lines containing four braced wall panels has created a series of benchmark equivalency factors that could be viewed as a combination of a partial restraint factor and a systems effect factor. SBCA Tech Notes Page 5

6 Given all of this, SBCRI, as an ANSI/ACLASS approved agency as defined in the IRC/IBC, has established an equivalency testing procedure by performing ASTM E564-based whole building testing. The purpose of this testing is to provide data in accordance with the following code language found in both the IRC and IBC: R Alternative materials, design and methods of construction and equipment. The provisions of this code are not intended to prevent the installation of any material or to prohibit any design or method of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternative material, design or method of construction shall be approved where the building official finds that the proposed design is satisfactory and complies with the intent of the provisions of this code, and that the material, method or work offered is, for the purpose intended, at least the equivalent of that prescribed in this code. Compliance with the specific performance-based provisions of the International Codes in lieu of specific requirements of this code shall also be permitted as an alternate. R Tests. Whenever there is insufficient evidence of compliance with the provisions of this code, or evidence that a material or method does not conform to the requirements of this code, or in order to substantiate claims for alternative materials or methods, the building official shall have the authority to require tests as evidence of compliance to be made at no expense to the jurisdiction. Test methods shall be as specified in this code or by other recognized test standards. In the absence of recognized and accepted test methods, the building official shall approve the testing procedures. Tests shall be performed by an approved agency. Reports of such tests shall be retained by the building official for the period required for retention of public records. Therefore, the SBCRI 12'x30' building tests: 1. Establish ASTM E564 ultimate strength values for benchmark IRC braced wall panel systems. a. From these established ultimate strength values, allowable design values can be determined from SDPWS counsel of dividing the ultimate strength test data by a factor of two. 2. Provide a pathway for new product development where comparisons can be made through testing that provides an accurate, and technically sound, level playing field. SBCRI testing provides a benchmark to compare equivalent performance to: a. IRC prescriptive braced wall panel and portal applications found in IRC Section R602.10, as specifically defined in IRC Table R b. SDPWS series of shear wall design values found in Table 4.3A (see Appendix B) c. WSP braced wall panels using hold down connection systems d. Any type of braced wall panel that makes up a shear wall i. It is now easy to compare performance of a wide variety of braced wall panel configurations using the specific construction specifications for the application. 3. Provide the equivalency characteristics/factors found in the previous tables and establish the partial restraint factor in the full scale building as shown in the table below. Test Description Ultimate PLF Load (unrestrained) Full Scale Building Partial Restraint Compared to Full Scale Building Full Restraint (626 PLF) IRC 7 /16" WSP 8d 6 6' from corner Test # SBCRI a Test # SBCRI b IRC 7 /16" WSP 8d 6 corner Test # SBCRI /626 = /626 = 0.7 TABLE 7: Full Scale Building Partial Restraint Compared to Full Scale Building Full Restraint SBCA Tech Notes Page 6

7 Summary: This test data suggests the following concepts: 1. The restraint-to-partial-restraint factor is The calibration factor to convert 3 / 8 " OSB performance to 7 / 16 " OSB performance is: a. 1.1 for unrestrained applications 7 b. 1.7 for unrestrained to restrained 8 3. For proprietary product development, calibration factors can be used to determine IRC equivalents. a. If the test data finds that the proprietary product is equal to or better than 3 / 8 " OSB installed as specified in the IRC, the IRC design values for that proprietary product installed per its installation instructions follow: Calibration Factors to take SBCRI Full Scale Building Tests to an equivalent IRC/SDPWS Design Value (IRC value of 500 PLF/SDPWS of 515 PLF for 3 /8"and 672 PLF for 7 /16") Test Description Ultimate PLF Load (unrestrained and restrained) Full Scale Building to IRC Design Value (500 PLF) Calibration Factor Full Scale Building to SDPWS Restrained Design Value (515 PLF) Calibration Factor 3 /8" WSP Basis IRC 3 /8" WSP 6d 6 6' from corner Test # SBCRI IRC 7 /16" WSP 8d 6 6' from corner Test # SBCRI a Test # SBCRI b IRC 7 /16" WSP 8d 6 corner Test # SBCRI IRC 7 /16" WSP 8d 6 6' from corner with hold downs Test # SBCRI /367 = /367 = /412 = /426 = /626 = 1.1 TABLE 7: Calibration Factors to take SBCRI Full Scale Building Tests to an equivalent IRC/SDPWS Design Value (IRC value of 500 PLF/SDPWS of 515 PLF for 3 /8"and 672 PLF for 7 /16") PLF / 367 PLF PLF / 367 PLF 1.7 SBCA Tech Notes Page 7

8 Appendix A: SBCRI-Wall 1 Test Setup and Connection Criteria SBCA Tech Notes Page 8

9 Appendix B: SDPWS Table 4.3A Nominal Unit Shear Capacities for Wood-Frame Shear Walls SBCA Tech Notes Page 9

10 Appendix C: Summary of Connections The following table summarizes the requirements for connecting various members of wall assemblies. Connection Location IRC Connection Requirement IRC Code Section Connection Used for Testing Reason for Deviation Notes Roof sheathing to trusses 8d common (2-1 /2 x 6/12 spacing Minimum thickness for 24" oc framing is: 3 PSF live, 7 40 PSF live and 1 70 PSF live. (All assume 10 PSF dead) R803.2, Table R602.3(1), Table R (1) 8d sinker (2-3 /8" x 6/12 spacing Available hand driven nail purchased locally Truss to perpendicular wall very top plate (2) 16d box nails (3-1 /2" x 0.135"). For trusses, approved connections with at least 175 lbs capacity. Table R602.3(1), R , R (3) 16d (3-1 /4" x 0.131") Available hand driven nail purchased locally The 2012 IRC changes this to (3) 16d nails and removes the truss specific requirement in 2009 IRC R Truss to parallel wall very top plate. No provision for general construction. At braced wall 6 in. oc (2-1 /2" x 0.131") Figure R (2) No provision for general construction. At braced wall 6 in. oc (2-1 /2" x 0.131") Where the uplift is greater than 100 PLF, an alternate connection is required per 2009 IRC R Very top plate to top plate Face nail, 10d (3" x 24" oc Table R602.3(1) Face nail, 10d (3" x 24" oc Offset of top plate ends Top plate overlaps at corners and intersections. 48" offset with (8) 16d (3-1 /2" x 0.135") nails in the overlapped area. Face nail, (2) 10d (3" x 0.128") Table R602.3(1) Table R602.3(1) 48" offset with (8) 16d (3-1 /2" x 0.135") nails in the overlapped area. Face nail, (2) 10d (3" x 0.128") WFCM allows a 30" offset (minimum 5' splice plate) Top plate to Studs (2) 16d (3-1 /2" x 0.135") nails Table R602.3(1) (3) 3-1 /4" x 0.131" pneumatic nails. Nails for framing guns are not available in the larger size. Sole plate to Studs (end nailed) Stud to stud connection (built up corners and double studs) Wall Sheathing to framing (2) 16d (3-1 /2" x 0.135") nails Table R602.3(1) 10d (3" x 24" oc 3 /8" WSP fastened with 6d (2" x 0.113") 6' oc at panel edges and 12" oc in the field Table R602.3(1) (3) 3-1 /4" x 0.131" pneumatic nails. 10d (3" x 24" oc. 3 /8" OSB fastened with 6d (2-3 /8" x 0.113") 6' oc at panel edges and 12" oc in the field Nails for framing guns are not available in the larger size. Wood sole plates to foundation 1 /2" anchor bolts with nut and washer (no size given), 6' oc, first bolt no more than 12" or less than 7 dia. (3-1 /2") from end. Extend 7" minimum into concrete. R , SDPWS , C & Appendix A2 5 /8" anchor bolt. Use 3" x 3" x 0.229" plate washer for the unrestrained condition Needed for fixture. May use other anchorage with other spacing s equivalent to the 1 /2" requirement SBCA Tech Notes Page 10

11 Appendix D: 2009 IRC Table R602.3 (1) SBCA Tech Notes Page 11

12 SBCA Tech Notes Page 12

ReWall EssentialBoard, NakedBoard & Ceiling Panels TER No

ReWall EssentialBoard, NakedBoard & Ceiling Panels TER No TER No. 1202-02 ReWall ReWall Company, LLC P.O. Box 1818 Des Moines, IA 50305 515-265-1400 rewallmaterials.com Issue Date: March 6, 2012 Updated: December 18, 2013 Subject to Renewal: April 1, 2014 DIVISION:

More information

Floor Truss Ribbon Board Load Path

Floor Truss Ribbon Board Load Path Floor Truss Ribbon Board Load Path SRR No. 1506-16 Structural Building Components Association (SBCA) July 26, 2016 SBCA is an APPROVED SOURCE This research report is based on practical scientific research

More information

sheathing) fastened between four flatwise SPF stud grade 2x4s.

sheathing) fastened between four flatwise SPF stud grade 2x4s. Continuously Insulated Portal Frame with Hold-Down Evaluation () TER No. 1101-01.SIS Ox Engineered Products, LLC 228 Broadway, Suite 2 Hanover, PA 17331 269-435-2425 164 Eyster Rd. Halltown, WV 25423 269

More information

Floor Truss Ribbon Board Load Path. Overview Revised 3/24/2017

Floor Truss Ribbon Board Load Path. Overview Revised 3/24/2017 Floor Truss Ribbon Board Load Path Overview Revised 3/24/2017 SBCA has been the voice of the structural building components industry since 1983, providing educational programs and technical information,

More information

Wood Shear Wall Design Examples For Wind

Wood Shear Wall Design Examples For Wind Wood Design Examples For Wind EARN 0.1 ICC Continuing Education Unit (CEU) and/or AIA/CES HSW 1 Learning Unit (LU) DES413-A Wood Design Examples for Wind Description: In this article, a wood frame shear

More information

Stanley Fastening Systems, L.P. Stanley BOSTITCH Pneumatic Pins. TER No

Stanley Fastening Systems, L.P. Stanley BOSTITCH Pneumatic Pins. TER No Stanley Fastening Systems, L.P. TER No. 1109-02 StanleyBlack&Decker, Inc. StanleyBlack&Decker, Inc. Stanley Fastening Systems, L.P. 125 Circuit Drive North Kingstown, Rhode Island 02852 888-556-6696 bostitch.com

More information

Individual Truss Marking Is it a Building Code Requirement?

Individual Truss Marking Is it a Building Code Requirement? Introduction: Individual Truss Marking Is it a Building Code Requirement? Released April 1, 2010 On January 1, 2008, the 2007 edition of the California Building Code (CBC) 1 was adopted for use and replaced

More information

Building Division Informational Handout

Building Division Informational Handout CITY OF SAN JOSÉ, CALIFORNIA Building Division Informational Handout Conventional Light Frame Construction Design Provisions 2007 CBC Handout No. 2-21 Published: 1/1/08 Page 1 of 3 This document summarizes

More information

Frame Wood Systems. Prepared for Forest Product Laboratory, Forest Service, U.S. Department of Agriculture National Association of Home Builders

Frame Wood Systems. Prepared for Forest Product Laboratory, Forest Service, U.S. Department of Agriculture National Association of Home Builders Evaluation of the Lateral Performance of Roof Truss-to-Wall Connections in Light- Frame Wood Systems Prepared for Forest Product Laboratory, Forest Service, U.S. Department of Agriculture National Association

More information

Frame Wood Systems. Prepared for Forest Product Laboratory, Forest Service, U.S. Department of Agriculture National Association of Home Builders

Frame Wood Systems. Prepared for Forest Product Laboratory, Forest Service, U.S. Department of Agriculture National Association of Home Builders Evaluation of the Lateral Performance of Roof Truss-to-Wall Connections in Light- Frame Wood Systems Prepared for Forest Product Laboratory, Forest Service, U.S. Department of Agriculture National Association

More information

Prescriptive Wind Pressure Performance of Foam Plastic Insulation Used as Insulating Sheathing in Exterior Wall Covering Assemblies. TER No.

Prescriptive Wind Pressure Performance of Foam Plastic Insulation Used as Insulating Sheathing in Exterior Wall Covering Assemblies. TER No. Prescriptive Wind Pressure Performance of Foam Plastic Insulation Used as Insulating Sheathing in Exterior Wall Covering Assemblies TER No. 1006-01 Foam Sheathing Committee (FSC) Members Atlas Roofing

More information

Design for Uplift & Lateral Strength Using TimberLOK Screws to Connect Walls to Rim Joists. TER No

Design for Uplift & Lateral Strength Using TimberLOK Screws to Connect Walls to Rim Joists. TER No Using TimberLOK Screws to Connect Walls to Rim Joists TER No. 1306-05 OMG, Inc. d/b/a/ FastenMaster Manufacturing Location: OMG, Inc. 153 Bowles Road Agawam, MA 01001 413-789-0252 fastenmaster.com mguthrie@olyfast.com

More information

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses Released May 20, 2009 Updated March 9, 2011 Introduction: Wood frame structures with attached brick masonry veneer

More information

BASF HP+ Wall XR Series Limit States TER No

BASF HP+ Wall XR Series Limit States TER No BASF HP+ Wall XR Series Limit States TER No. 1506-01 BASF, Inc. 100 Park Ave Florham Park, NJ 07932-1089 973-245-6000 basf.com Issue Date: October 21, 2015 Updated: March 27, 2019 Subject to Renewal :

More information

Heel Blocking Requirements and Capacity Analysis. Overview Revised 3/22/2017

Heel Blocking Requirements and Capacity Analysis. Overview Revised 3/22/2017 Heel Blocking Requirements and Capacity Analysis Overview Revised 3/22/2017 SBCA has been the voice of the structural building components industry since 1983, providing educational programs and technical

More information

Attachment of Residential Deck Ledger to Metal Plate Connected Wood Truss Floor Systems

Attachment of Residential Deck Ledger to Metal Plate Connected Wood Truss Floor Systems to Metal Plate Connected Wood Truss Floor Systems Structural Building Components Association (SBCA) February 17, 2015 Revised August 15, 2017 SBCA is an APPROVED SOURCE This research report is based on

More information

R Code and Commentary for 2012 NC Residential Code final 03/06/13

R Code and Commentary for 2012 NC Residential Code final 03/06/13 R602.10 Code and Commentary for 2012 NC Residential Code final 03/06/13 Commentary italicized and printed in red 1. Section R602.10 -- provides charging language for two simplified bracing approaches (isolated

More information

APPENDIX A1 WIND AND SEISMIC BRACING GUIDELINE FOR ONE AND TWO FAMILY DWELLINGS AND TOWNHOUSES

APPENDIX A1 WIND AND SEISMIC BRACING GUIDELINE FOR ONE AND TWO FAMILY DWELLINGS AND TOWNHOUSES ST. LOUIS COUNTY DEPARTMENT OF PUBLIC WORKS DIVISION OF CODE ENFORCEMENT APPENDIX A1 WIND AND SEISMIC BRACING GUIDELINE FOR ONE AND TWO FAMILY DWELLINGS AND TOWNHOUSES Lateral Loads All buildings are subject

More information

Design for Uplift Using TimberLOK Screws to Connect Gable Trusses to Wall Top Plates. TER No

Design for Uplift Using TimberLOK Screws to Connect Gable Trusses to Wall Top Plates. TER No to Connect Gable Trusses to Wall Top Plates TER No. 1304-02 OMG, Inc. d/b/a/ FastenMaster OMG, Inc. 153 Bowles Road Agawam, MA 01001 413-789-0252 fastenmaster.com mguthrie@olyfast.com Issue Date: April

More information

COMBINED SHEAR AND WIND UPLIFT RESISTANCE OF WOOD STRUCTURAL PANEL SHEARWALLS. B Yeh T G Williamson. APA The Engineered Wood Association USA

COMBINED SHEAR AND WIND UPLIFT RESISTANCE OF WOOD STRUCTURAL PANEL SHEARWALLS. B Yeh T G Williamson. APA The Engineered Wood Association USA CIB-W18/41-15-6 INTERNATIONAL COUNCIL FOR RESEARCH AND INNOVATION IN BUILDING AND CONSTRUCTION WORKING COMMISSION W18 - TIMBER STRUCTURES COMBINED SHEAR AND WIND UPLIFT RESISTANCE OF WOOD STRUCTURAL PANEL

More information

USING WOOD STRUCTURAL PANELS FOR SHEAR AND WIND UPLIFT APPLICATIONS

USING WOOD STRUCTURAL PANELS FOR SHEAR AND WIND UPLIFT APPLICATIONS USING WOOD STRUCTURAL PANELS FOR SHEAR AND WIND UPLIFT APPLICATIONS Borjen Yeh 1 and Ed Keith 2 ABSTRACT: Shearwalls constructed with wood structural panels, such as plywood and oriented strand board (OSB),

More information

1.0 INTRODUCTION EC

1.0 INTRODUCTION EC EVALUATION CRITERIA FOR IN-PLANE SHEAR RESISTANCE AND EQUIVALENCY OF PROPRIETARY SHEATHING AS BRACING FOR WOOD FRAME WALL CONSTRUCTION 1.0 INTRODUCTION EC008-2011 1.1 Purpose: This evaluation criteria

More information

Versetta Stone Panelized Stone Veneer Applications Over Continuous Insulation. TER No Boral Stone Products LLC

Versetta Stone Panelized Stone Veneer Applications Over Continuous Insulation. TER No Boral Stone Products LLC Applications Over Continuous Insulation TER No. 1212-01 Boral Stone Products LLC 200 Mansell Court East, Suite 310 Roswell, GA 30076 419-318-5345 949-341-8890 (fax) chris.hines@boral.com versettastone.com

More information

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued)

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued) 2000 IRC 1997 NEHRP Section Provision Section Provision Comments CHAPTER 3 BUILDING PLANNING R301 DESIGN CRITERIA R301.2.2 Seismic Provisions R301.2.2.1 Determination of Seismic Design Category R301.2.2.1.1

More information

Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses. DD No

Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses. DD No Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses. DD No. 1608-01 Structural Building Components Association (SBCA) Issue Date: August 8, 2016 6300 Enterprise Lane Madison,

More information

Prepared for Forest Product Laboratory, Forest Service, U.S. Department of Agriculture Norbord Inc., Toronto, Ontario, Canada

Prepared for Forest Product Laboratory, Forest Service, U.S. Department of Agriculture Norbord Inc., Toronto, Ontario, Canada High Heel Roof-to-Wall Connection Testing Phase III Evaluation of extended wall OSB sheathing connection under combined uplift and shear loading for 24-inch-heel trusses Prepared for Forest Product Laboratory,

More information

2008 Special Design Provisions for Wind and Seismic

2008 Special Design Provisions for Wind and Seismic 2008 Special Design Provisions for Wind and Seismic Philip Line, P.E., Bradford K. Douglas, P.E., and Peter Mazikins, P.Eng. Introduction The 2008 edition of the Special Design Provisions for Wind and

More information

Live Load Considerations for Truss Bottom Chords

Live Load Considerations for Truss Bottom Chords Live Load Considerations for Truss Bottom Chords Released September 1, 2006 Issue: There is a lack of uniformity in when and where it is appropriate to apply the non-storage live load and the storage live

More information

Version 2.1 IBS 2010 Special Resource Edition

Version 2.1 IBS 2010 Special Resource Edition Copyright 2009 Version 2.0 1 Table of Contents Introduction... 4 List of Figures/Tables... 5 Section 1: Basic Concepts for Code-Compliant Wall Bracing... 6 1.1 Why is Wall Bracing Needed?... 6 1.2 How

More information

TECO Certified Rim Board in Fire-Rated Assemblies TER No

TECO Certified Rim Board in Fire-Rated Assemblies TER No TECO Certified Rim in Fire-Rated Assemblies TER No. 1005-01 TECO 507 Matt Pass, Suite 2 Cottage Grove, WI 53527 608-403-4197 tecotested.com Issue Date: May 28, 2010 Updated: January 3, 2014 Subject to

More information

UDC Wall Bracing Provisions Emergency Rule effective date 4/1/2014. A How To guide for use of the new provisions

UDC Wall Bracing Provisions Emergency Rule effective date 4/1/2014. A How To guide for use of the new provisions UDC Wall Bracing Provisions Emergency Rule effective date 4/1/2014 A How To guide for use of the new provisions Summary: Forget what you knew about the previous wall bracing provisions this method is a

More information

Pulaski County, Virginia Practical Wall Bracing

Pulaski County, Virginia Practical Wall Bracing Pulaski County, Virginia Practical Wall Bracing Based on the 2012 Virginia Residential Code The information herein provides guidelines for complying with the most common Practical Wall Bracing provisions

More information

Lateral load basics Code acceptance of Standard. Standard Overview 2008 Wind & Seismic Standard. Wind. Wind Load Path. IBC Section 1604.

Lateral load basics Code acceptance of Standard. Standard Overview 2008 Wind & Seismic Standard. Wind. Wind Load Path. IBC Section 1604. Outline 2005/2008 Special Design Provisions for Wind & Seismic Standard Lateral load basics Code acceptance of Standard 2005/2008 Wind & Seismic Standard Overview 2008 Wind & Seismic Standard John Buddy

More information

SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION

SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION Section R614 Add new section to read as shown: (RB34-06/07) SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION R614.1 General. Structural insulated panel (SIP) walls shall be designed in accordance

More information

COPYRIGHT MATERIALS. Wind Solutions - Perforated Wood Structural Panel Shear Walls (DES 416)

COPYRIGHT MATERIALS. Wind Solutions - Perforated Wood Structural Panel Shear Walls (DES 416) Wind Solutions - Perforated Wood Structural Panel Shear Walls (DES 416) Lori Koch, M.S., M.F., P.E. Manager, Educational Outreach American Wood Council Adam Robertson, M.A.Sc., P.Eng. Manager, Codes and

More information

130 MPH EXPOSURE B WFCM GUIDE. Guide to Wood Frame Construction in High Wind Areas for One- and Two-Family Dwellings 2015 EDITION

130 MPH EXPOSURE B WFCM GUIDE. Guide to Wood Frame Construction in High Wind Areas for One- and Two-Family Dwellings 2015 EDITION 130 MPH EXPOSURE B WFCM GUIDE Guide to Wood Frame Construction in High Wind Areas for One- and Two-Family Dwellings 2015 EDITION Updates and Errata While every precaution has been taken to ensure the accuracy

More information

WFCM 120 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

WFCM 120 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS 120 MPH EXPOSURE B GUIDE WFCM WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS A F & P A American Forest & Paper Association American Wood

More information

WFCM 130 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

WFCM 130 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS 130 MPH EXPOSURE B GUIDE WFCM WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS A F & P A American Forest & Paper Association American Wood

More information

2015 Special Design Provisions for Wind and Seismic Philip Line, P.E., John Buddy Showalter, P.E., Michelle Kam-Biron, P.E., S.E., Jason Smart, P.E.

2015 Special Design Provisions for Wind and Seismic Philip Line, P.E., John Buddy Showalter, P.E., Michelle Kam-Biron, P.E., S.E., Jason Smart, P.E. 2015 Special Design Provisions for Wind and Seismic Philip Line, P.E., John Buddy Showalter, P.E., Michelle Kam-Biron, P.E., S.E., Jason Smart, P.E. The 2015 Edition of Special Design Provisions for Wind

More information

Changes in the 2007 Supplement to the 2006 International Building Code That Affect Component Manufacturers

Changes in the 2007 Supplement to the 2006 International Building Code That Affect Component Manufacturers Changes in the 2007 Supplement to the 2006 International Building Code That Affect Component Manufacturers Released August 8, 2008 Introduction: Building codes are continually evolving. They are never

More information

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC)

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC) Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC) Plan Check Submittal Date: Plan Check #: Permit App.# Job Address: Applicant: Phone: ( ) P.C. Engineer: Phone:

More information

A Simple Solution for Meeting

A Simple Solution for Meeting A Simple Solution for Meeting Narrow Wall Bracing Requirements AND BUILDING A STRONGER, SAFER HOME. APA s Narrow Wall Bracing Method, combined with walls that are fully sheathed with plywood or OSB, helps

More information

TER No Cultured Stone & ProStone Applications Over Continuous Insulation

TER No Cultured Stone & ProStone Applications Over Continuous Insulation Cultured Stone & ProStone Applications Over Continuous Insulation TER No. 1302-01 Boral Stone Products LLC 200 Mansell Court East, Suite 310 Roswell, GA 30076 419-318-5345 949-341-8890 (fax) chris.hines@boral.com

More information

WFCM 110 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

WFCM 110 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS 110 MPH EXPOSURE B GUIDE WFCM WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS A F & P A American Forest & Paper Association American Wood

More information

WFCM 100 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

WFCM 100 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS 100 MPH EXPOSURE B GUIDE WFCM WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS A F & P A American Forest & Paper Association American Wood

More information

WFCM 90 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

WFCM 90 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS MPH EXPOSURE B GUIDE WFCM WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS A F & P A American Forest & Paper Association American Wood Council

More information

WFCM 130 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS

WFCM 130 MPH GUIDE EXPOSURE B WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS 130 MPH EXPOSURE B GUIDE WFCM WOOD FRAME CONSTRUCTION MANUAL GUIDE TO WOOD CONSTRUCTION IN HIGH WIND AREAS FOR ONE- AND TWO-FAMILY DWELLINGS A F & P A American Forest & Paper Association American Wood

More information

TER No Attachment of Exterior Wall Coverings Through Kingspan GreenGuard Extruded Polystyrene (XPS) Sheathing to Wood or Steel Wall Framing

TER No Attachment of Exterior Wall Coverings Through Kingspan GreenGuard Extruded Polystyrene (XPS) Sheathing to Wood or Steel Wall Framing Attachment of Exterior Wall Coverings Through Kingspan Insulation LLC 2100 RiverEdge Parkway Suite 175 Atlanta, GA 30328 kingspaninsulation.us TER No. 1410-09 Issue Date: January 30, 2015 Updated: March

More information

BASF HP+ Wall XR Series Ontario TER No

BASF HP+ Wall XR Series Ontario TER No TER No. 1706-02 BASF, Inc. 100 Park Ave Florham Park, NJ 07932-1089 973-245-6000 basf.com Issue Date: July 13, 2017 Updated: March 6, 2019 Subject to Renewal: January 1, 2020 DIVISION: 06 00 00 WOOD, PLASTICS,

More information

Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS

Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS This chapter explains the International Residential Code s (IRC s) general earthquake-resistance requirements as well as specific IRC requirements concerning

More information

Wall bracing panel requirements

Wall bracing panel requirements Wall bracing panel requirements Building Inspections Exterior and interior walls must be braced in accordance with Minnesota State Building Code section R602 to resist wind loads and racking. Locations,

More information

TER No Attachment of Exterior Wall Coverings Through Kingspan Kooltherm Insulation Boards to Wood or Steel Wall Framing

TER No Attachment of Exterior Wall Coverings Through Kingspan Kooltherm Insulation Boards to Wood or Steel Wall Framing Attachment of Exterior Wall Coverings Through Kingspan Kooltherm Insulation Boards to Wood or Wall Framing Kingspan Insulation LLC 2100 RiverEdge Parkway Suite 175 Atlanta, GA 30328 kingspaninsulation.us

More information

RB104-09/10 R602.7, R (New), Table R (New), Figures R (1)-(2) (New)

RB104-09/10 R602.7, R (New), Table R (New), Figures R (1)-(2) (New) RB104-09/10 R602.7, R602.7.1 (New), Table R602.7.1 (New), Figures R602.7.1(1)-(2) (New) Proposed Change as Submitted Proponent: Joseph Lstiburek, Building Science Corporation 1. Revise as follows: R602.7

More information

Page 1 of 21

Page 1 of 21 www.garyklinka.com Page 1 of 21 UDC Wall Bracing Provisions quiz Instructions 1. Print these pages. Fee $30 2. Answer the Simple questions that follow mini sections of the code language. 3. Circle the

More information

PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood, Plastics, and Composites (06) SECTION: Structural Panels ( )

PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood, Plastics, and Composites (06) SECTION: Structural Panels ( ) PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood, Plastics, and Composites (06) SECTION: Structural Panels (06 12 00) Report Holder ACME Panel Company 1905 West Main St. Radford, VA 24141 Manufacturing

More information

VERTICAL AND HORIZONTAL LATERAL LOAD SYSTEMS

VERTICAL AND HORIZONTAL LATERAL LOAD SYSTEMS TECHNICAL NOTE On Cold-Formed Steel Construction $5.00 Light Gauge Steel Engineers Association Washington, D.C. Toll-Free: 1 (866) 465-4732 www.lgsea.com DESIGN VALUES FOR VERTICAL AND HORIZONTAL LATERAL

More information

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation 0 ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg Most Widely Accepted and Trusted ESR 3105 Reissued 08/2017 Revised 10/2018 This report is subject to renewal 08/2019.

More information

2012 IRC Wood Wall Bracing

2012 IRC Wood Wall Bracing Description 2012 IRC Wood Wall 2012 International Residential Code (IRC ) This 6-hour seminar provides a comprehensive explanation of the 2012 International Residential Code (IRC ) bracing requirements.

More information

Originally Issued: 03/31/2017 Valid Through: 04/30/2018

Originally Issued: 03/31/2017 Valid Through: 04/30/2018 ALLEGHENY STRUCTURAL COMPONENTS, INC. OPEN JOIST 2000 WOOD TRUSSES CSI Sections: 06 11 00 Wood Framing 06 11 13 Engineered Wood Products 06 17 00 Shop Fabricated Structural Wood 06 17 53 Shop-Fabricated

More information

Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Design Guide Revised 11/17/2016

Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Design Guide Revised 11/17/2016 Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Design Guide Revised 11/17/2016 SBCA has been the voice of the structural building components industry since 1983,

More information

FastenMaster FlatLOK Fasteners TER No

FastenMaster FlatLOK Fasteners TER No FastenMaster FlatLOK s TER No. 1501-08 OMG, Inc d/b/a FastenMaster 153 Bowles Road Agawam, Massachusetts 01001 413-789-0252 fastenmaster.com Issue Date: May 14, 2015 Updated: June 1, 2018 Subject to Renewal:

More information

TER No Attachment of Exterior Wall Coverings Through Kingspan GreenGuard Extruded Polystyrene (XPS) Sheathing to Wood or Steel Wall Framing

TER No Attachment of Exterior Wall Coverings Through Kingspan GreenGuard Extruded Polystyrene (XPS) Sheathing to Wood or Steel Wall Framing Attachment of Exterior Wall Coverings Through Kingspan Insulation LLC 2100 RiverEdge Parkway Suite 175 Atlanta, GA 30328 kingspaninsulation.us TER No. 1410-09 Issue Date: January 30, 2015 Updated: August

More information

Building Guide. olorado Chapter of the International Conference of Building Officials. Lancaster County Building Department

Building Guide. olorado Chapter of the International Conference of Building Officials. Lancaster County Building Department olorado Chapter of the International Conference of Building Officials Lancaster County Building Department Single Family Residential One Story Detached Garage How to Use this Guide Provide two sets of

More information

Originally Issued: 11/04/2016 Revised: 11/28/2017 Valid Through: 11/30/2018

Originally Issued: 11/04/2016 Revised: 11/28/2017 Valid Through: 11/30/2018 HUBER ENGINEERED WOODS ZIP SYSTEM R-SHEATHING CSI Section: 06 12 00 Structural Panels 06 16 00 Sheathing 1.0 RECOGNITION ZIP System R-Sheathing panels, manufactured by Huber Engineered Woods, LLC, were

More information

Long Span Truss Installation

Long Span Truss Installation Long Span Truss Installation SRR No. 1506-08 Structural Building Components Association (SBCA) May 31, 2017 SBCA is an APPROVED SOURCE This research report is based on practical scientific research (literature

More information

Earthquake Resistant Residential Design and Construction, Part 2

Earthquake Resistant Residential Design and Construction, Part 2 Earthquake Resistant Residential Design and Construction, Part 2 Course No: S05-007 Credit: 5 PDH John L. Galinski, PE Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY

More information

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS WOOD CHAPTER 3 301 SCOPE This chapter prescribes construction requirements for buildings where all exterior walls above the foundation are wood framed

More information

TER No Use of FastenMaster HeadLOK Fasteners to Attach Cladding and/or Furring to Wood Framing through Foam Sheathing

TER No Use of FastenMaster HeadLOK Fasteners to Attach Cladding and/or Furring to Wood Framing through Foam Sheathing Use of FastenMaster HeadLOK Fasteners to through Foam Sheathing OMG, Inc. d/b/a/ FastenMaster 153 Bowles Road Agawam, Massachusetts, 01001 413-789-0252 fastenmaster.com mguthrie@olyfast.com TER No. 1009-01

More information

Special Inspections for Wood Construction BCD710 Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council

Special Inspections for Wood Construction BCD710 Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council Special Inspections for Wood Construction BCD710 Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council Copyright Materials This presentation is protected by US and International

More information

PRODUCT: Structural Insulated Panels (SIP) DIVISION: Wood and Plastics (06) SECTION: Structural Panels ( )

PRODUCT: Structural Insulated Panels (SIP) DIVISION: Wood and Plastics (06) SECTION: Structural Panels ( ) PRODUCT: Structural Insulated Panels (SIP) DIVISION: Wood and Plastics (06) SECTION: Structural Panels (06 12 16) Report Holder General Panel Corporation PO Box 279 2604 Sunset Drive Grenada, Mississippi

More information

RB213-06/07 Table R

RB213-06/07 Table R RB213-06/07 Table R602.10.5 Proposed Change as Submitted: Proponent: Scott Beard, SE, City of Tacoma, WA Revise as follows: TABLE R602.10.5 a, b, c LENGTH REQUIREMENTS FOR BRACED WALL PANELS IN A CONTINUOUSLY

More information

Colorado Chapter of the International Conference of Building Officials. Building Guide. The Colorado Chapter of the International

Colorado Chapter of the International Conference of Building Officials. Building Guide. The Colorado Chapter of the International Building Guide Colorado Chapter of the International Conference of Building Officials Colorado Building Chapter of the International Guide Code Council Single Family Residential One Story Detached Garage

More information

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC)

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC) Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC) Plan Check Submittal Date: Plan Check #: Permit App.# Job Address: Applicant: Phone: ( ) Plan Check Engineer:

More information

Mid-Rise Engineering Considerations for Engineered Wood Products

Mid-Rise Engineering Considerations for Engineered Wood Products Mid-Rise Engineering Considerations for Engineered Wood Products Presented by Frank Powell, P.E. Presented by [ Presenter s Name ] Please add relevant logo here Disclaimer: This presentation was developed

More information

Minimum required percentage of length of braced wall band on each storey 4

Minimum required percentage of length of braced wall band on each storey 4 C-10 Supplementary Guidelines on Applicability and Scope Table C1 b (continued) Braced Wall Panels for High Wind or High Seismic Loads Building with normal weight construction: 0.8 kpa q 1/50 wind load

More information

Listing Report: MUR Reissue Date: 12/07/17 This report is subject to annual review

Listing Report: MUR Reissue Date: 12/07/17 This report is subject to annual review CSI 06 12 16 PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood and Plastics SECTION: Structural Panels Report Holder The Murus Company PO Box 220 Mansfield, PA 16933 Manufacturing Locations The

More information

Norbord TallWall/Windstorm/QuakeZone Rated Sheathing for Use with IRC Energy-Heel Trusses Revised February 20, 2018

Norbord TallWall/Windstorm/QuakeZone Rated Sheathing for Use with IRC Energy-Heel Trusses Revised February 20, 2018 Norbord TallWall/Windstorm/QuakeZone Rated PR-N133 Sheathing for Use with IRC Energy-Heel Trusses Revised February 20, 2018 Products: Norbord TallWall/Windstorm/QuakeZone Rated Sheathing for Use with IRC

More information

Thermo-Ply Red & Thermo-Ply Red AMG Structural Sheathing Canada Limit States Design. TER No

Thermo-Ply Red & Thermo-Ply Red AMG Structural Sheathing Canada Limit States Design. TER No Structural Sheathing Canada Limit States Design TER No. 1808-03 Ox Engineered Products, LLC 22260 Haggerty Road #365 700 Centreville Rd Northville, MI 48167 Constantine, MI 49042 989-798-5923 269-435-2425

More information

STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E.

STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E. STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION Presented by: Susan L. Lasecki P.E., S.E. Presentation Outline Gravity Design Load Paths from Roof to Foundation Roof Framing Floor Framing Wall Framing Lateral

More information

Garage/Accessory Structures

Garage/Accessory Structures Garage/Accessory Structures City of New Prague Building Inspections Department 118 Central Ave N New Prague, MN 56071 (952) 758-4401 Fax (952) 758-1149 Requirements for submitted Building Plans Signed

More information

Recent Research to Expand the Engineering Knowledge Base for SIPs

Recent Research to Expand the Engineering Knowledge Base for SIPs Recent Research to Expand the Engineering Knowledge Base for SIPs 2017 TFEC Symposium Madison, WI Tom Williamson, P.E.,Timber Engineering, LLC Chair, SIPA Technical Activities Committee SIP Construction

More information

Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Overview Revised 11/17/2016

Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Overview Revised 11/17/2016 Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses (MPCWT) Overview Revised 11/17/2016 SBCA has been the voice of the structural building components industry since 1983, providing

More information

TER No Use of FastenMaster HeadLOK TM Fasteners to Attach Cladding and/or Furring to Wood Framing through Foam Sheathing

TER No Use of FastenMaster HeadLOK TM Fasteners to Attach Cladding and/or Furring to Wood Framing through Foam Sheathing OMG, Inc. d/b/a/ FastenMaster 153 Bowles Road Agawam, Massachusetts, 01001 413/789-0252 fastenmaster.com mguthrie@olyfast.com TER No. 1009-01 Issue Date: March, 27 2011 Updated: December 18, 2013 DIVISION:

More information

Introduction: Issue: Analysis/Conclusion:

Introduction: Issue: Analysis/Conclusion: Special Inspection Requirements for Buildings Falling under the Jurisdiction of the California Division of the State Architect and the 2007 California Building Code Released May 7, 2008 Introduction: WTCA

More information

GARAGES/ONE-STORY City of Grand Rapids Building Safety Division

GARAGES/ONE-STORY City of Grand Rapids Building Safety Division GARAGES/ONE-STORY City of Grand Rapids Building Safety Division 218-326-7601 www.cityofgrandrapidsmn.com This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building

More information

PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood and Plastics (06) SECTION: Structural Panels ( )

PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood and Plastics (06) SECTION: Structural Panels ( ) PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood and Plastics (06) SECTION: Structural Panels (06 12 16) Report Holder Thermocore Panel Systems, Inc. 1801 Hancel Parkway Mooresville, Indiana

More information

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016.

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016. ICC-ES Evaluation Report ESR-894 Reissued April 04 This report is subject to renewal April, 0. www.icc-es.org (800) 4-87 () 99-04 A Subsidiary of the International Code Council DIVISION: 07 00 00 THERMAL

More information

Evaluation of Full-Scale House Testing Under Lateral Loading

Evaluation of Full-Scale House Testing Under Lateral Loading Evaluation of Full-Scale House Testing Under Lateral Loading Prepared for National Association of Home Builders Prepared by NAHB Research Center 400 Prince Georges Boulevard Upper Marlboro, MD 20774-8731

More information

WTCA 6300 Enterprise Lane Madison, WI / / (fax)

WTCA 6300 Enterprise Lane Madison, WI / / (fax) Introduction: Released May 15, 2008 Building Designers need to account for the weight of Fire Sprinkler Systems in addition to the load requirements imposed under the model building codes. Truss Designers

More information

Prescriptive and Engineered Design Provisions of the Massachusetts One- and Two-Family Dwelling Code

Prescriptive and Engineered Design Provisions of the Massachusetts One- and Two-Family Dwelling Code Prescriptive and Engineered Design Provisions of the Massachusetts One- and Two-Family Dwelling Code Released July 27, 2009 Introduction: Buildings in the United States are designed to withstand the loads

More information

Stark Truss Company, Inc. Revised December 14, 2018

Stark Truss Company, Inc. Revised December 14, 2018 Fire-Rated Assemblies PR-S223 Stark Truss Company, Inc. Revised December 14, 2018 Products: SI-40, SI-60, and SI-80 Prefabricated Wood I-Joists Stark Truss Company, Inc. 8655 Chestnut Ridge Road, N.W.

More information

High Performance Walls:

High Performance Walls: High Performance Walls: Advanced Framing Walls Systems and Insulated Headers Karyn Beebe, PE, LEED AP APA The Engineered Wood Association Quality Services Division Technical Services Division Field Services

More information

High Performance Walls:

High Performance Walls: High Performance Walls: Advanced Framing Walls Systems and Insulated Headers Karyn Beebe, PE, LEED AP APA The Engineered Wood Association Quality Services Division Technical Services Division Field Services

More information

June 1, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS

June 1, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS June 1, 2009 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS SUBJECT: Proposed Revisions to the Acceptance Criteria for Wood-based Studs, Subject AC202-0609-R1

More information

Structural Design for Wind Loads: An Overview of Engineering Considerations for Wood

Structural Design for Wind Loads: An Overview of Engineering Considerations for Wood Structural Design for Wind Loads: An Overview of Engineering Considerations for Wood Lori Koch, PE Manager, Educational Outreach American Wood Council Buildings Copyright Materials This presentation is

More information

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings Building Safety Department 400-2 nd Street South St. Cloud, MN 56301 (320) 255-7239 A building permit is required for any accessory

More information

MBOIA IRC Wall Bracing. Mark Halverson. Maine Building Officials and Inspectors Association. First Last

MBOIA IRC Wall Bracing. Mark Halverson. Maine Building Officials and Inspectors Association. First Last Wall Bracing This document was prepared for the MBOIA and based on the wind speeds and Seismic Design Categories for Maine and shall only be used as a reference since the Wind Speeds and the Seismic Design

More information

Stora Enso S-LVL Laminated Veneer Lumber (LVL) TER No

Stora Enso S-LVL Laminated Veneer Lumber (LVL) TER No (LVL) TER No. 1507-01 Stora Enso Wood Products Oy Ltd. Kanavaranta 1 PO Box 309 Helsinki Finland FL-00101 buildingandliving.storaenso.com Issue Date: February 7, 2017 Updated: May 1, 2018 Subject to Renewal:

More information

Requirements and Solutions for Sunroom Lateral Design

Requirements and Solutions for Sunroom Lateral Design Requirements and Solutions for Sunroom Lateral Design Jay H. Crandell, P.E. ARES Consulting October 6, 2010 Technical Committee Meeting National Sunroom Association Outline Background on Sunroom Lateral

More information

Strong-Drive SDWS TIMBER Screw

Strong-Drive SDWS TIMBER Screw Simpson Strong-Tie Fastening Systems Structural Wood-to-Wood Connections including Ledgers Designed to provide an easy-to-install, high-strength alternative to through-bolting and traditional lag screws.

More information