1 DULLES STATION EST. e a s t Dulles Station Blvd., Herndon, VA BASE BUILDING SPECS Narrative: 2303 Dulles Station Blvd (Dulles Station East) is a modern six story office building located in the multi-use development known as Dulles Station. The building is located at the entry point of the development off of Sunrise Valley Drive and has tremendous exposure to the Dulles Toll Road. The building is approximately 190,869 gross interior square feet with 186,734 rentable square feet. The footprints of floors 2 6 range from 29,544 rentable square feet to 31,380 rentable square feet. There are approximately 800 spaces in the Phase One Parking Deck, which yields 4.3 spaces per 1,000 RSF in Phase One of the development. Structure First Slab on grade. Floors 2-6 Steel frame, metal deck with reinforced concrete topping slab. Column Spacing: 30 x 43 Load: 100 lbs per square foot. Exterior Finishes Precast: Glazing: Main Building Entry: Entrance Systems at Lobby: Architectural precast concrete panels with sandblasted and water washed finishes to simulate Coral Grey granite. Curtainwall & punched window system comprised of horizontal, kynar coated aluminum mullions, vertical silicone butt joints, and floor to floor clear low-e insulated glass. The window systems are thermally broken and fully weeping. The main building entry is accentuated by a two story curtainwall leading into the two story lobby. A dramatic, sloping cantilever overhead canopy further marks the entrance. The entry is glazed with clear windows and glass entry doors. Fully insulated clear tempered glazing system with a highly polished #8 stainless steel vestibule within a two-story lobby curtainwall Dulles Station East BASE BUILDING SPECS - Page 1 of 7

2 Thermal Moisture Protection Exterior Soffits: Interior Partitions: Roof: Semi-rigid mineral fiber insulation at precast panels and curtain walls, spandrels, and fire insulation to comply with local codes. Fiberglass batt insulation Demising walls, elevator shafts, mechanical room or shafts, and other areas requiring sound isolation have acoustical fiberglass or mineral fiber insulation. High performance, fluid applied, hot rubberized asphalt roofing membrane system with rigid insulation and ballast. Interior Finishes Main Lobby An active stone pattern consisting of three Italian marbles that picks up on the grids of the building. Feature wall Back-lit patterned glass wall that is the terminus of a 400-foot vehicular axis between buildings. The glass is set into a sleek framework of highly polished #8 stainless steel. Non-feature walls Two story multi-layered Venetian Plaster walls that create a sculptural effect on these walls. Elevator Signage: Directory: Typical Tenant Elevator Lobbies Floors: Elevator Painted gypsum board ceiling at a height of 24. The curving metal panel system hangs from the ceiling and is patterned with linear lights. Polished # 8 stainless steel doors at Levels One and Two. TBD TBD Sealed concrete, floor covering by tenant. Gypsum board taped and prepared for final finish application by tenant. Exposed beams and deck above-finished ceiling by tenant. #4 stainless steel doors on Levels Three Six Dulles Station East BASE BUILDING SPECS - Page 2 of 7

3 Typical Tenant Areas Floors: Door Hardware: Window Treatment: Restrooms Wet Wall: Other Lavatory Counter: Toilet Accessories: Partitions: Service Areas and Stairs Floors: Ceilings: Door Hardware: Concrete floor covering by tenant. Gypsum board, taped and prepared for final finish application by tenant. Ceiling height at 9-0 above finished floor. Grid and ceiling tiles installed by tenant. Full height, solid core stained wood doors with painted metal frames at core doors and tenant entries at main corridors. Brushed stainless steel levers and latch sets. Standard color 1 Mini blinds. Large 24 x 12 porcelain tiles. Full height tile wet walls. Tile base with vinyl wall covering. Drywall ceilings and bulkheads. Polished granite with full height individual mirrors and sconces framing the mirrors. Fully recessed with satin stainless steel finish. Full height hospitality type drywall partitions with mahogany louvered doors. Partitions are covered with wall covering. Sealed concrete. Painted gypsum board with rubber base. Exposed structure high stained wood doors with painted metal frames. Brushed stainless steel levers and latch sets. Conveying Systems Office Building Passenger Elevators Three traction elevators serving all floors, 3,500 lb capacity and 350 fpm speed. All cabs will be supplied with removable protective padding Dulles Station East BASE BUILDING SPECS - Page 3 of 7

4 Freight Elevator: Elevator Cab Finishes Front Wall: Side & Back Parking Deck Passenger Elevators: Elevator Cab Finishes One swing traction passenger/freight elevator serving all floors, rated to 4,000 lb capacity and 350 fpm speed with removable protective padding. Ceiling height is 9-0 Carpet. Polished stainless steel. Polished stainless steel control panels. Textured metal wall panels with a stainless steel handrail. Stainless steel panels with recessed down lights. Two traction elevators serving all floors. 3,000 lb capacity and 350 fpm speed. Textured rubber tiles. Plastic laminate panels with polished stainless steel handrail. #4 Stainless steel panels and recessed down lights. #4 Stainless steel 2303 Dulles Station East BASE BUILDING SPECS - Page 4 of 7

5 Mechanical HVAC system is designed to maintain a summer indoor condition of 76 F db at 38% RH at a coincidental outdoor temperature of 92 F db, 76 F wb, and a winter indoor condition of 72 F at 0 F ambient. Ventilation is provided at the rate of 20CFM/person with an occupant density if 142 square feet per person. Chilled water will be supplied to air handling units throughout the building from the central refrigeration plant. Air handling units will be of the packaged central station type. O.A. will be ducted to each fan room through medium pressure main risers and constant volume air valves from a variable speed outside air fans located in the penthouse. Conditioned air (at 46 degrees db) is supplied to each floor from the air handling units through a medium pressure, medium velocity air distribution system to pressure independent series type fan powered induction units located throughout the floors. Conditioned air will be supplied to the occupied space at a minimum of 55 degrees db from the fan powered induction units. The heating requirements for the building will be handled by electric resistance coils located integral to the powered induction units located in the ceiling return air plenum in the vicinity of the various zones. The refrigeration system consists of two parallel connected driven hermetic rotary screw type compressor water chillers and associated chilled water pumps, condenser water pumps, controls and two cell induced draft cooling tower with variable speed fan drives. Condenser water risers with valved taps at each floor will be provided in each fan room. Cooling tower and condenser water risers will be sized to accommodate the tenant s 24-hour loads, retail loads, elevator equipment room loads, and general tenant loads of 2 watts/sq.ft. Plumbing One sanitary, vent and water line (with valve) riser is provided in the janitor s closet and stubbed into the tenant area on each floor, and for use by tenant. Two sanitary and vent connection points per floor will be provided during base building construction in the lease area outside the base building core, for use by tenant. Fire Protection Base building sprinkler system is a wet pipe system with upright heads. Tenant will modify existing sprinkler system to work with the layout of their space. Tenant contractor shall provide sprinkler heads and hydraulic calculations for system to meet NFPA and local code requirements Dulles Station East BASE BUILDING SPECS - Page 5 of 7

6 Fire Alarm An addressable fire alarm system will be provided for the office tower and parking deck. All alarm initiating devices will be directly connected to and addressed by the main fire alarm panel. The vertical fire alarm riser shall be Style 6 connected. All interconnecting wiring between the central control equipment and all remote panels and equipment shall be buried below the slab on grade, encased in 2 minimum of concrete, routed in a dedicated 2 hour rated enclosure, and will be type MI cable or Fire Alarm Circuit Integrity (CI) Cable. NFPA and ADA compliant audio/strobe visual signals will be provided in each elevator lobby, in each rest room, in corridors and throughout the parking deck. Strobe visual signals shall be rated 110 candela per UL 1971 for interior spaces and 117 candela per UL 1638 for unconditioned spaces. Spare amplifier capacity and power supply capacity shall be provided in the shell office tower to add 30 - one watt speakers and candela strobes on each floor in the unfinished tenant spaces. Electrical Systems General: The project will be served at 277/480 volt, 3 phase, 4 wire from a utility company transformer located in the service area behind the building. One 4,000 amp switchboard will be provided to serve the office tower and one 225 amp panelboard will be provided to serve the parking deck portions of the project. Two 2,000 amp bus risers will extend from the switchboard to serve the office floors, each serves half of the loads of the office tower typical floors. Emergency/standby loads, the central plant, site lighting and lobby lighting are served from the switchboard. The power distribution system will be sized to provide 8.5 Watts/Gross Square Foot for the tenant space power and lighting loads. This tenant power allowance will be provided at 480 volts, in the bus risers serving each office floor, and is exclusive of the power requirements of the shell building. Separate 277/480 volt panel boards will be provided for HVAC equipment and lighting, in accordance with the ASHRAE Energy Code. A 75 KVA, dry type transformer serving 84 pole 120/208 volt panel boards will be provided in each office level electric room (two per floor). This 75 KVA transformer is sized to provide 5 Watts/Useable Square Foot and utilizes a portion of the 8.5 watts/gsf of the tenant power allowance. A copper building ground riser will be provided in the office tower core electric rooms. Cadweld or irreversible compression connectors will be used for all connections Dulles Station East BASE BUILDING SPECS - Page 6 of 7

7 Emergency Power: Light Fixtures: Telephone/Data A diesel fueled, 450KW generator will be provided in a weatherproof enclosure, located in the service area behind the building. The generator will comply with the Level 1, Type 10, Class 8 requirements of NFPA 110. The generator will provide emergency back-up service to the emergency egress lighting in the office building and the parking deck, the fire alarm system, 1 elevator in the office building and 1 elevator in the parking deck. This generator will also serve the panel intended for the telephone system in the main telephone room, the power operated doors and the receptacles at the front desk. The generator will be four cycle, have two-thirds pitch alternator, PMG exciter and output circuit breakers. The generator will have critical grade muffler. Fuel storage shall be a 300-gallon skid mounted base tank. Passenger elevator lobbies and rest rooms will be illuminated with single vertical lamp 26(or18) watt selfflanged reflector fluorescent recessed downright fixtures. Enclosed wall mounted two lamps T8 fluorescent light fixtures will be provided in stairwells, on both the main and intermediate landings. Two lamp T8 fluorescent strip fixtures (with wire guards where required by code) will be provided in all areas without ceilings. All fluorescent lamp ballasts will be electronic type, with 10% maximum Total Harmonic Distortion (THD). The parking deck will be illuminated utilizing 175-watt metal halide direct/indirect fixtures, two per bay and rows thirty feet on center. 25% of the fixtures will contain quartz restrike and will be connected to the emergency generator. Data service, provided by Cox Communications, and telephone service provided by Verizon, will be available to the building. Six 4 sleeves are provided through each floor in each core tel/data room for wiring by others. Six 4 conduits are provided connecting each stacked riser closet to the main telephone network room. Ten 4 conduits are incoming from the building exterior to the main telephone room for telecommunication service. Each telephone riser closet and the main telephone network room contain a 3 / 4 plywood backboard and a copper ground bar with #6 ground wire. In the riser closets, this ground bus is connected to the ground riser. In the main telephone room, the ground bus is connected to the main electric service ground bus Dulles Station East BASE BUILDING SPECS - Page 7 of 7

SPACE TYPE: OUTSIDE PARKING (STRUCTURE)

SPACE TYPE: OUTSIDE PARKING (STRUCTURE) SPACE TYPE: OUTSIDE PARKING (STRUCTURE) Construction Criteria The unit costs for Outside Parking (Structure) space types are based on the construction quality and design features in the following table.

More information

AGILITAS Property Development

AGILITAS Property Development Hartmann Commons offered by For Infomation and Leasing Mr. Seth T. McDowell 1614 16th Avenue South Nashville, Tennessee 37212 Voice 615-327-8788 Fax 615-327-8789 Hartmann Commons Agilitas Property Development

More information

TABLE OF CONTENTS Public Safety Building

TABLE OF CONTENTS Public Safety Building DOCUMENT 00 01 10 - TABLE OF CONTENTS VOLUME I DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 00 31 32 Geotechnical Data DIVISION 01 GENERAL REQUIREMENTS 01 10 00 Summary

More information

ADDENDUM 2 - JULY 14, 2015

ADDENDUM 2 - JULY 14, 2015 7/9/2015 The Professional(s) of Record above has signed for the following specification sections: DIVISION 1 GENERAL REQUIREMENTS Section 01 10 00 Summary of Work Section 01 25 00 Substitution Procedures

More information

Appendix J - Custom Uniformat for EDU Migration

Appendix J - Custom Uniformat for EDU Migration Appendix J - Custom Uniformat for EDU Migration Nr. MTC Uniformat for VFA.facility Life (Years) Weight (1-100) Out of Scope Cost Y/N 1 A Substructure 150 N 2 A10 Foundations 150 N 3 A1010 Standard Foundations

More information

Overall Existing Conditions Summary

Overall Existing Conditions Summary September 12, 2002 Overall Executive Summary: The multi-use project on 250 West Street is a 7-story building with space for offices, retail, storage and parking. The project is a small part of the development

More information

PROGRAM COST MODEL. for. PEER Tall Buildings Study Concrete Structural Option Los Angeles, California

PROGRAM COST MODEL. for. PEER Tall Buildings Study Concrete Structural Option Los Angeles, California PROGRAM COST MODEL for PEER Tall Buildings Study Concrete Structural Option Los Angeles, California March 8, 2010 PEER Tall Buildings Study Concrete Structural Option March 8, 2010 CONTENTS Page Nos. Overall

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM)

SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM) SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM) Construction Criteria The unit costs for the Physical Fitness Center (Exercise Room) space type are based on the construction quality and design features in

More information

OFFICE Space STANDARD SPECS Page 1

OFFICE Space STANDARD SPECS Page 1 OFFICE Space STANDARD SPECS Page 1 Standard features listed are based on manufacturer availability- Substitutions may occur and interchanged with items of similar standard likeness at the discretion of

More information

SANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA

SANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA Atlanta, GA LOCATED AT CAMP CREEK PARKWAY AND CAMPBELLTON ROAD For Sale or Lease Single units start at 1,176sf and can be combined to exact specification Custom Designed Medical and Professional finishes

More information

2800 TRANS-CANADA MONTREAL POINTE-CLAIRE

2800 TRANS-CANADA MONTREAL POINTE-CLAIRE Exceptional Head Office Leasing Opportunity! 2800 TRANS-CANADA COMMISSION BONUS! 65,000 SF and up $25,000 125,000 SF $50,000 Contact Leasing Director for details. Limited time offer. MONTREAL POINTE-CLAIRE

More information

March 2018 Progress. Work Completed, Week Ending 3/23/18:

March 2018 Progress. Work Completed, Week Ending 3/23/18: March 2018 Progress Work Completed, Week Ending 3/23/18: Continued draft curtains and liner panels. Continued running power to hangar doors. Continued installation of bath accessories in the gang bathrooms.

More information

TENANT CRITERIA MANUAL INSERT PHOTO HERE

TENANT CRITERIA MANUAL INSERT PHOTO HERE G TENANT CRITERIA MANUAL GREENWOOD MALL INSERT PHOTO HERE General Growth Properties, Inc. 110 N. Wacker Drive Chicago, IL 60606 (312)-960-5000 Tenant shall supply and install an electrical meter

More information

Whitley Shower Locker Toilet Facilities

Whitley Shower Locker Toilet Facilities Whitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman.com Building Type Building Code Whitley Shower Locker Toilet Facilities

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

CM ASSIGNMENT OF TEMPORARY FACILITIES see included IU Project Site Requirements

CM ASSIGNMENT OF TEMPORARY FACILITIES see included IU Project Site Requirements SECTION A CM INSTRUCTIONS TO BIDDERS SECTION B BID CATEGORY DESCRIPTIONS & BID FORMS BC-07: Building HVAC and Plumbing BC-08: Building Electric BC-09: General Trades BC-10: Masonry BC-11: Precast Structural

More information

BVSC BVSC. Midwest Technical Inspections Survey Worksheet. Account / Account Code: Insured: Policy #: Building Data - Section 1

BVSC BVSC. Midwest Technical Inspections Survey Worksheet. Account / Account Code: Insured: Policy #: Building Data - Section 1 Midwest Technical Inspections Survey Worksheet BVSC BVSC Account / Account Code: Agency: Insured: Policy #: Telephone: Alt. Phone: Building Data - Section 1 Building Name (Entire Valuation) Section Name

More information

SANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA

SANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA Atlanta, GA LOCATED AT CAMP CREEK PARKWAY AND CAMPBELLTON ROAD For Sale or Lease Single units start at 1,176sf and can be combined to exact specification Custom Designed Medical and Professional finishes

More information

NEWPORT OFFICE CENTER Washington Boulevard, Jersey City, New Jersey

NEWPORT OFFICE CENTER Washington Boulevard, Jersey City, New Jersey 570 Washington Boulevard, Jersey City, New Jersey EXECUTIVE SUMMARY Newport Office Center 6 is a stand alone 340,000 square foot building which was built and delivered as a "state-of-the art" build-to-suit

More information

AIRWAYS CROSSING PHASE II BUILDING INFORMATION 5305 McCall Way N.E. T2E 7N7

AIRWAYS CROSSING PHASE II BUILDING INFORMATION 5305 McCall Way N.E. T2E 7N7 AIRWAYS CROSSING PHASE II BUILDING INFORMATION 5305 McCall Way N.E. T2E 7N7 www.airwayscrossing.ca Excellent access to Barlow Trail/McKnight Blvd. Bays starting at 4,000 sq. ft. Surface loading T5 lighting

More information

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6 PROJECT MANUAL for: FRANKLIN VILLAGE APARTMENTS Building I Morristown, NJ 07960 Block: 3901 Lots: 4,5,6 Owner: Atlantic Health Investment Corp. 200 American Road Morris Plains, NJ 07950 Architect NETTA

More information

TABLE OF CONTENTS. (Δ = Rev 06/08)

TABLE OF CONTENTS. (Δ = Rev 06/08) TABLE OF CONTENTS (Δ = Rev 06/08) INTRODUCTION REQUEST FOR REVISION FORMS TAB A TABLE OF CONTENTS TAB B PROCEDURES B-9 Record Drawings B-10 Variance Procedure B-11 Surface Water Procedures (New Section)

More information

Franklin Hall Renovation TABLE OF Document Indiana University Bloomington

Franklin Hall Renovation TABLE OF Document Indiana University Bloomington VPS Project No. 2013022.00 Page 1 SPECIFICATIONS VOLUME I INTRODUCTORY INFORMATION Document 000010 - Table of Contents... 6 Document 000011 - Certification and Seals... 2 Document 000012 - Project Directory...

More information

TABLE OF CONTENTS. (Δ = Rev 11/15) Update #7

TABLE OF CONTENTS. (Δ = Rev 11/15) Update #7 TABLE OF CONTENTS ( = Rev 11/15) Update #7 INTRODUCTION REQUEST FOR REVISION FORMS TAB A TABLE OF CONTENTS TAB B PROCEDURES B-4 International Suite of Codes (New) B-9 Record Drawings B-10 Variance Procedure

More information

TABLE OF CONTENTS. (Δ = Rev 04/17) Update #8

TABLE OF CONTENTS. (Δ = Rev 04/17) Update #8 TABLE OF CONTENTS ( = Rev 04/17) Update #8 INTRODUCTION REQUEST FOR REVISION FORMS TAB A TABLE OF CONTENTS TAB B PROCEDURES B-4 International Suite of Codes B-9 As-Builts and Record Drawings B-10 Variance

More information

Division 00 Procurement and Contracting Requirements

Division 00 Procurement and Contracting Requirements SECTION 00 01 10 TABLE OF CONTENTS Division SECTION NO. VOLUME ONE Title SECTION TITLE Division 00 Procurement and Contracting Requirements 00 11 00 Invitation to Bidders 00 21 00 Instructions to Bidders

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION Section 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Invitation

More information

SPACE TYPE: ENHANCED OFFICE

SPACE TYPE: ENHANCED OFFICE SPACE TYPE: ENHANCED OFFICE Construction Criteria The unit costs for Enhanced Office space types are based on the construction quality and design features in the following table. This information has been

More information

Property Offering. Cold Storage Warehouse 4501 Hitch Peters Road Evansville, IN 47711

Property Offering. Cold Storage Warehouse 4501 Hitch Peters Road Evansville, IN 47711 Property Offering Cold Storage Warehouse 4501 Hitch Peters Road Evansville, IN 47711 Executive Summary We are pleased to present an outstanding cold storage opportunity in Evansville, Indiana. Built in

More information

CSO / BSU NW2 NORTH RESIDENTIAL NEIGHBORHOOD PHASE #2 VOLUME 1 PROCUREMENT AND CONTRACTING DOCUMENTS GROUP

CSO / BSU NW2 NORTH RESIDENTIAL NEIGHBORHOOD PHASE #2 VOLUME 1 PROCUREMENT AND CONTRACTING DOCUMENTS GROUP VOLUME 1 PROCUREMENT AND CONTRACTING DOCUMENTS GROUP DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 01 Project Title Page 00 01 10 Table of Contents 00 01 15 List of Drawing Sheets 00 21

More information

Seasons Business Center 2 New Construction!

Seasons Business Center 2 New Construction! Seasons Business Center 2 New Construction!...542 Seasons Rd. Stow, Ohio 114,188 SF of High Bay Space 32 Clear Height 80 480 ESFR Sprinklers 8 Reinforced Concrete Floor Abundant Parking Floor Plans to

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION Section 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Invitation

More information

The building on 250 West Street is a 7-story multi-use that provides space for parking,

The building on 250 West Street is a 7-story multi-use that provides space for parking, December 5, 2002 Thesis Executive Summary The proposal for the investigation of the building on 250 West Street will include an in depth look at the floor and lateral systems. A continuation of the Pro-Con

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP PROCUREMENT AND CONTRACTING DOCUMENTS GROUP DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS 00 11 00 Notice To Bidders 00 21 00 Instructions To Bidders 00 22 00 Supplementary Instructions To Bidders

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 16060 Grounding and Bonding This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or

More information

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)

More information

Division 09 FINISHES TABLE OF CONTENTS

Division 09 FINISHES TABLE OF CONTENTS Division 09 FINISHES TABLE OF CONTENTS 09 1000 GENERAL... 3 A. RELATED SECTIONS... 3 B. MAINTENANCE OF FINISHES... 3 C. PUBLIC AREAS... 3 D. CUTTING AND PATCHING... 3 E. CLEANING... 3 F. RECOMMENDED FLOORING

More information

flexible spaces all the right places... fogg.com Resource Business Centre I, II, III & IV 5399 Lancaster Dr. & Resource Dr.

flexible spaces all the right places... fogg.com Resource Business Centre I, II, III & IV 5399 Lancaster Dr. & Resource Dr. flexible spaces all the right places......resource Business Centre I, II, III & IV 5399 Lancaster Dr. & 800-900 Resource Dr. Flexible Spaces in All the Right Places is what Fogg had in mind when designing

More information

How to Prepare Your LSE Report

How to Prepare Your LSE Report LSE Rule Category Required Documentation Information Comments / Applicable Code Sections/ 10.1 Building Height Provide the Building height in Feet Provide the number of stories above grade Helpful Hints

More information

CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST

CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST Check off each item that is included within the submitted Contract Documents Review Package. Provide a written explanation for any omissions. The following items,

More information

Watercrest - Sand Hill - Columbia, SC TABLE OF CONTENTS PROCUREMENT AND CONTRACTING REQUIREMENTS

Watercrest - Sand Hill - Columbia, SC TABLE OF CONTENTS PROCUREMENT AND CONTRACTING REQUIREMENTS Watercrest - Sand Hill - Columbia, SC 00 0110-1 TABLE OF CONTENTS DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS INTRODUCTORY INFORMATION Document 00 0101 Document 00 0110 Project Title Page CONTRACTING

More information

Seasons Business Center New Construction!

Seasons Business Center New Construction! Seasons Business Center New Construction!...Seasons Business Center Stow, Ohio 114,188 SF of High Bay Space 32 Clear Height 80 480 ESFR Sprinklers Tax Abatement Available 8 Reinforced Concrete Floor 271

More information

INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT

INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT 7100 147 th Street West Telephone (952) 953-2588 Apple Valley, MN 55124-9016 Fax (952) 953-2515 www.cityofapplevalley.org INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT 1. Submit plan showing the proposed

More information

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS INDIANA UNIVERSITY BIDDING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 (REVISED 2005) MINORITY,

More information

Building Inspection Report

Building Inspection Report Building Inspection Report Sample Commercial Inspection Report Inspection Date: Prepared For: Prepared By: Professional Property Inspection Consultants 4857 Winterset Drive Columbus, OH 43220 (614) 459-5941

More information

Lake Highlands North Recreation Center Summary

Lake Highlands North Recreation Center Summary Lake Highlands North Recreation Center Summary Address Building Purpose 9940 White Rock Trail Dallas, TX 75238 Recreation Center Original Year of Construction 1971 Building Area 33,036 SF Inspection Date

More information

Beckley-Saner Recreation Center Summary

Beckley-Saner Recreation Center Summary Beckley-Saner Recreation Center Summary Address Building Purpose 114 West Hobson Avenue, Dallas, TX 75224 Recreation Center Original Year of Construction 1949 Building Area 34,510 SF Inspection Date July

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

Timberglen Recreation Center Summary

Timberglen Recreation Center Summary Timberglen Recreation Center Summary Address Building Purpose 3810 Timberglen Road Dallas, TX 75287 Recreation Center Original Year of Construction 2003 Building Area 15,000 SF Inspection Date August 2,

More information

ST. CLOUD, MN 316,000 Square Feet Situated on Acres

ST. CLOUD, MN 316,000 Square Feet Situated on Acres ST. CLOUD, MN 316,000 Square Feet Situated on 49.56 Acres For additional information contact: Gerald P. Norton Tel: 952.831.1993 E mail: gnorton@binswanger.com B. Andrew Lubinski Tel: 952.831.1931 E mail:

More information

FACILITY COMPONENTS - MIDDLE SCHOOL

FACILITY COMPONENTS - MIDDLE SCHOOL SITE AREAS Parking and Access - Buses 2.0 2.0 0.30 Parking and Access - Serv. / Delivery 3.0 1.0 0.22 Parking and Access - Staff 4.0 3.0 0.89 Parking and Access - Visitors 1.0 3.0 0.22 Four fewer stalls

More information

1200 Oakman Blvd INDUSTRIAL INVESTMENT/ USER OPPORTUNITY. Building A 85,999 SF. Building D. Building C 11,495 SF 15,046 SF.

1200 Oakman Blvd INDUSTRIAL INVESTMENT/ USER OPPORTUNITY. Building A 85,999 SF. Building D. Building C 11,495 SF 15,046 SF. 1200 Oakman Blvd A 85,999 SF Detroit, MI 48238 C D 15,046 SF A C Below (4) Grade Level Replacement Cost Doors Shop Floor Height: Zoning M4-Intensive 18 3 Industrial District Immediate HVAC - 6 Ton Unit

More information

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents DIVISION 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN Contents 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION 13 00 60 LIST OF FIGURES... 6 Page 1 of 6 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN 1. General

More information

ST. CLOUD, MN. 316,000 Square Feet Situated on Acres. For additional information contact:

ST. CLOUD, MN. 316,000 Square Feet Situated on Acres. For additional information contact: ST. CLOUD, MN 316,000 Square Feet Situated on 49.56 Acres For additional information contact: Gerald P. Norton Tel: 952.831.1993 E-mail: gnorton@binswanger.com B. Andrew Lubinski Tel: 952.831.1931 E-mail:

More information

CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist

CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist This checklist is a convenient reference to the 2012 Michigan Building Code. The checklist

More information

Northwestern Facilities

Northwestern Facilities Northwestern Facilities NU Master Specification - Issuances Record & Summary of Changes Only the most current version of an NU Master Specification is included as a PDF for download on this website. The

More information

Telecommunication Spaces

Telecommunication Spaces Telecommunication Spaces October 19, 2016 Page 1 Revision History Telecommunication Spaces Standard Effective Date Email Version Contact Phone OIT-TS strevena@csustan.edu 1.0 Stan Trevena 209.667.3137

More information

Building Architecture

Building Architecture The front of the building consists of the three story town homes with facades to remain, as well as one leg of the condominium tower that reaches the street. The main condo portion of the building is L

More information

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES...

DIVISION MEDIUM VOLTAGE VAULT DESIGN Contents MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION LIST OF FIGURES... DIVISION 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN Contents 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN... 2 DIVISION 13 00 60 LIST OF FIGURES... 6 13 00 60 - MEDIUM VOLTAGE VAULT DESIGN 1. General Requirements

More information

Exhibit A Library Shell Construction

Exhibit A Library Shell Construction Exhibit A Library Shell Construction Library Component Building Requirements Approximately 15,000-17,000 square feet plus 900 square feet for mechanical room and additional space on roof for installation

More information

260,000 SF Building Profile

260,000 SF Building Profile Expanding Your Development & Investment Perspectives 260,000 SF Building Profile Precast & Brick Exterior Finish 245,000 SF Production/Warehouse 7,500 SF Office & 7,500 SF Mezzanine 50 x 50 Bays, 24 Clear

More information

1301 PENNSYLVANIA AVENUE, NW

1301 PENNSYLVANIA AVENUE, NW 1301 PENNSYLVANIA AVENUE, NW Table of Contents 1. Project Description 2. Base Building Design Specification 3. Renderings a. Exterior Day b. Exterior Night c. Office d. Terrace 4. Sustainable Design a.

More information

Minneapolis Community and Technical College T-Building Floor 2 Student Affairs Cost Estimating Form Templates - Exhibit C

Minneapolis Community and Technical College T-Building Floor 2 Student Affairs Cost Estimating Form Templates - Exhibit C 2 3 4 5 6 7 8 9 0 2 3 4 5 6 7 8 9 20 2 22 23 24 25 26 27 28 29 30 3 32 33 34 35 36 37 38 39 40 4 42 43 44 45 46 DIVISION 02 EXISTING CONDITIONS Demolition; Removal & Disposal: CMU Partitions AD Quan UM

More information

INNOVATIVE OFFICE SPACE AT A PREMIER LOCATION.

INNOVATIVE OFFICE SPACE AT A PREMIER LOCATION. 500 North Hurstbourne, Louisville, Kentucky 40222 INNOVATIVE OFFICE SPACE AT A PREMIER LOCATION. 4 Floors 120,000 Square Feet Class AA+ Office Building A Paramount And Landmark Location On Hurstbourne

More information

Galleria North Tower II Noel Road Dallas, TX 75240

Galleria North Tower II Noel Road Dallas, TX 75240 Galleria North Tower II FOR MORE LEASING INFORMATION, CONTACT: CHRIS TAYLOR TREY SMITH LAUREN NAPPER +1 972 692 1752 +1 972 692 1755 +1 972 232 8512 chris.taylor@cushwake.com trey.smith@cushwake.com lauren.napper@cushwake.com

More information

HERITAGE MIDDLE SCHOOL. Overview: Livingston School District Heritage Middle School

HERITAGE MIDDLE SCHOOL. Overview: Livingston School District Heritage Middle School HERITAGE MIDDLE SCHOOL Overview: The is located at 20 Foxcroft Drive and consists of a three-story building with Three-Story Classroom and Multi-Purpose Room Additions completed in 2002. The building has

More information

The Compass ( 270 Lisgar Street, Brighton ) Features General Site Work 1. Construction Drawings 2. Building, Plumbing Electrical and Entrance Permits

The Compass ( 270 Lisgar Street, Brighton ) Features General Site Work 1. Construction Drawings 2. Building, Plumbing Electrical and Entrance Permits The Compass ( 270 Lisgar Street, Brighton ) Features General Site Work 1. Construction Drawings 2. Building, Plumbing Electrical and Entrance Permits 3. Development and Septic Fees 4. Tarion New Home Warranty

More information

4.1.3 Project Manual

4.1.3 Project Manual 4.1.3 Project Manual (*Section requires Filed Sub-Bid) PROCUREMENT AND CONTRACTING REQUIREMENTS GROUP Division 00 Procurement and Contracting Requirements Section 00 01 03 Project Directory Section 01

More information

Existing Site Aerial Frederick High School Feasibility Study September 5, 2012

Existing Site Aerial Frederick High School Feasibility Study September 5, 2012 Existing Site Aerial Building Developmental History 1981 1966 1939 1977 1978 1955 1966 Exterior Roof: Most of existing roof has multi ply built up roofing. Some areas have gravel ballast, others have cap

More information

Expanding Your Development & Investment Perspectives 159,000 SF Building Profile

Expanding Your Development & Investment Perspectives 159,000 SF Building Profile Expanding Your Development & Investment Perspectives 159,000 SF Building Profile Metal & EIFS Exterior Finish 150,000 SF Production/Warehouse 4,500 SF Office & 4,500 SF Mezzanine 50 x 50 Bays, 24 Clear

More information

FACILITY COMPONENTS - ELEMENTARY SCHOOL

FACILITY COMPONENTS - ELEMENTARY SCHOOL SITE AREAS Parking and Access - Buses 1.0 2.0 0.16 Five fewer bus stalls than minimum standard. Parking and Access - Service / Delivery 1.0 1.0 0.08 No delivery parking adjacent to delivery entrance. Parking

More information

Residential Outline Specifications

Residential Outline Specifications Residential Outline Specifications September 2014 1. General a. Site i. Direct elevator access from parkade to residential floors ii. Separate commercial elevator access from parkade to 10th Street NW

More information

Schedule C STANDARD Specifications

Schedule C STANDARD Specifications Schedule C STANDARD Specifications RTM Finished Home Specifications Name: Job #: Address: Phone: Standard Specifications FRAMING 2x6 exterior wall construction 3/8 OSB sheeting 2x4 interior wall construction

More information

Carter's Oshkosh (SIS) # The Center at Pearland Parkway - Pearland, TX Scope Of Work / Bid Qualifications

Carter's Oshkosh (SIS) # The Center at Pearland Parkway - Pearland, TX Scope Of Work / Bid Qualifications Carter's Oshkosh (SIS) #1185 - The Center at Pearland Parkway - Pearland, TX 77581 - Scope Of Work / Bid Qualifications Please fill out the blanks associated with your trade scope or work with the words

More information

TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS

TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS AIA General Conditions... GC-1 to GC-44 Amendments to General Conditions... AM-1 to AM-2 Supplements to General Conditions... SU-1 to SU-7 00200 Instructions To Bidders... 1 3 00201 Contractor s Bidding

More information

Facility Condition Assessment

Facility Condition Assessment Citywide Facility Condition Assessment Report of Facility Condition Assessment For City of Manhattan Beach 1600 Marine Avenue, Manhattan Beach, CA September 4, 2013 (Rev A) Provided By: Faithful+Gould,

More information

PLANNING FOUNDATION FRAMING

PLANNING FOUNDATION FRAMING TRITON MODEL 3208 Chiquita Blvd. S. #208 Cape Coral, FL 33914 (239) 549-5554 CBC 1259879 What s Included in a Poseidon Home PLANNING Provide all permits necessary to comply with local codes Provide all

More information

1733 TW ALEXANDER DRIVE

1733 TW ALEXANDER DRIVE DURHAM, NC R&D PRODUCTION FACILITY ADJACENT TO RESEARCH TRIANGLE PARK ±97,875 SF FOR SALE OR LEASE 85 PROPERTY OVERVIEW 86 Falls Lake Foundry Commercial is pleased to offer the 1733 TW Alexander Drive

More information

Demolition Plan A1 A3. Scale: 3/32" = 1'-0" Arch. Men N.I.C. Elev. Lobby. Stairs N.I.C. N.I.C. Women N.I.C. Issued for Tender.

Demolition Plan A1 A3. Scale: 3/32 = 1'-0 Arch. Men N.I.C. Elev. Lobby. Stairs N.I.C. N.I.C. Women N.I.C. Issued for Tender. inc. 400-7 avenue edmonton, alberta, canada tr y t: (780) 48 47 f: (780) 48 00 e: lesnider@shaw.ca 4 door to North Common Corridor doors to door to F. H. C. Men Women ELEC/TEL UP Stairs DN F. H. C. DN

More information

TABLE OF CONTENTS Updated 1/2014 SECTION TITLE DATE

TABLE OF CONTENTS Updated 1/2014 SECTION TITLE DATE TABLE OF CONTENTS SECTION TITLE DATE Division 00 Procurement and Contracting Requirements 000101... Project Title Page 000116... CAD Standards 001116... Invitation to Bid 002113... Instructions to Bidders

More information

HILLSIDE ELEMENTARY SCHOOL. Overview: Livingston School District Hillside Elementary School

HILLSIDE ELEMENTARY SCHOOL. Overview: Livingston School District Hillside Elementary School HILLSIDE ELEMENTARY SCHOOL Overview: The is located at 98 Belmont Drive and consists of a two-story building which has had a number of additions added to it over the years, the latest of which was a two-story

More information

Welcome Center, New Student Services, and Career and Employment Services

Welcome Center, New Student Services, and Career and Employment Services Architectural Program Welcome Center, New Student Services, and Career and Employment Services East Memorial Stadium Renovation May 2014 Prepared By Table of Contents Introduction.... 1 Competitive Market....

More information

24,650 RSF IMMEDIATELY AVAILABLE!

24,650 RSF IMMEDIATELY AVAILABLE! 24,650 RSF IMMEDIATELY AVAILABLE! 700 North Hurstbourne, Louisville, Kentucky 40222 MOVE-IN READY 24,650 RSF SUITE IMMEDIATELY AVAILABLE. 700 North at ShelbyHurst Suite Constructed Brand New From Shell

More information

2016 CDM Smith All Rights Reserved July 2016 SECTION MULTIPLE CONTRACT SUMMARY

2016 CDM Smith All Rights Reserved July 2016 SECTION MULTIPLE CONTRACT SUMMARY PART 1 - GENERAL SECTION 01 01 11 MULTIPLE CONTRACT SUMMARY 1.01 SCOPE OF WORK A. This Section includes a summary of each Contract, including responsibilities for coordination and temporary facilities

More information

VOLUME 4 DIVISION SPECIFICATIONS

VOLUME 4 DIVISION SPECIFICATIONS Page 1 Section Title Consultant Pages VOLUME 4 DIVISION 00-01 SPECIFICATIONS Division 00 - Procurement and Contracting Requirements 00 01 07 SEALS PAGE All 5 00 01 11r6 TABLE OF CONTENTS All 7 00 21 13r1

More information

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY

SECTION PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY SECTION 280528 - PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Metal conduits, tubing, and fittings. 2. Nonmetallic conduits, tubing, and fittings. 3.

More information

Building Permit Application

Building Permit Application Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: ARCHITECT/ENGINEER ADDRESS:

More information

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information Anderson Central 100B, PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G

More information

IECC 2006 with Hawaii Amendments

IECC 2006 with Hawaii Amendments IECC 2006 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other notes to the reviewer.

More information

DESIGN & CONSTRUCTION GUIDELINES

DESIGN & CONSTRUCTION GUIDELINES DESIGN & CONSTRUCTION GUIDELINES EDITION: USF FACILITIES MANAGEMENT - DC 5 DCG FACILITIES MANAGEMENT DESIGN & CONSTRUCTION PHONE: (813) 974-2845 4202 E. FOWLER AVENUE, OPM 1000 TAMPA, FLORIDA 33620-7550

More information

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Project: Date: Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other

More information

Schedule D. RTM Finished Home Specifications

Schedule D. RTM Finished Home Specifications Schedule D RTM Finished Home Specifications RTM Finished Home Specifications Name: Job #: Address: Phone: Executive Specifications Executive Spec-Line Features upgraded finishes not offered in the Standard

More information

FACILITY COMPONENTS - ELEMENTARY SCHOOL

FACILITY COMPONENTS - ELEMENTARY SCHOOL SITE AREAS Parking and Access - Buses 1.0 2.0 0.16 Two stalls fewer than minimum standard. Parking and Access - Service / Delivery 2.0 1.0 0.16 Parking and Access - Staff 1.0 3.0 0.24 Thirty-seven stalls

More information

Simcoe County District School Board. 5yr Condition Assessment 2006/07 to 2010/11. Hillcrest PS (Barrie), 9205

Simcoe County District School Board. 5yr Condition Assessment 2006/07 to 2010/11. Hillcrest PS (Barrie), 9205 5yr Condition Assessment 2006/07 to 2010/11 Construction Year Area 1951 3,813 Page 1 of 25 1. Architectural / Structural & Site Exec Summary Hillcrest Public School is a two storey structure of masonry

More information

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS November 2018 Contents 1. Introduction... 1 2. Ontario Building Code and Second Dwelling Units... 1 3. How Do I Make My Secondary Dwelling Unit

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Foothills School Div #38 Sheep River School B3839A Okotoks Report run on: February 27, 29 2:28 PM Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement

More information

Gerald Desmond Bridge Replacement

Gerald Desmond Bridge Replacement Item # Room # icip. # of Occupants 101 12 Conference / Crew Room 1 400 400 Supervisor Offices Conference and secondary training room for up to 12 people Flooring: VCT Electrical Type: rmal (utility power)

More information

TRANSLINK LOGISTICS CENTRE

TRANSLINK LOGISTICS CENTRE TENANT SPECIFICATIONS IN TRANSLINK LOGISTICS CENTRE AT THE GLOBAL TRANSPORTATION HUB WAREHOUSE BUILDING 2A REGINA, SASKATCHEWAN October 30, 2013 SITE Municipal Address Site Area 12202 Ewing Avenue, Regina,

More information