1 Energy Consumption in Mid- and High-rise Residential Buildings The Myths and Realities of Real Building Energy Performance Warren Knowles P.Eng. January 19, 2011

2 Learning Objectives Understanding of: Energy consumption trends within new and older high-rise buildings (where energy is used / can be conserved). Impacts of design of the building enclosure on energy consumption. Relationship between enclosure air-tightness, suite compartmentalization, and ventilation strategies on energy consumption. How simple calibrated energy modeling can be used to assist with the design. How to comply with current energy code requirements including ASHRAE How to improve performance characteristics of building enclosure assemblies.

3 BC Climate Action Plan By 2020: 33 % reduction in Greenhouse Gas Emissions Energy Efficient Building Strategy -20% energy use per household Clean Energy Act

4 City of Vancouver Greenest City Action Plan 2020 Goals: Carbon Neutral New Buildings 20% Reduction in Energy Consumption and Greenhouse Gas Emissions in Existing Buildings Buildings account for 55% of Greenhouse Gas Emissions How will we get there? Absolute Energy Intensity requirements (kwh/m2/yr) Incentives and other means

5 Multi-Unit High-Rise Residential Building Energy Study Energy consumption of over 60 mid- to highrise Multi-Unit Residential Buildings (MURBs) Constructed between 1974 and 2002 Half of study buildings underwent a full-scale building enclosure rehabilitation Allows for the assessment of actual energy savings from enclosure performance Pre- and post-rehabilitation R-values, airtightness characteristics are compared to energy consumption. Other building performance characteristics as a result of the enclosure improvements are assessed. CMHC SCHL

6 Energy Units Typical energy intensity units - kwh/m 2 /yr or GJ/m 2 /yr in Canada Gas is metered/billed in units of GJ, and electricity in units of kwh Both energy intensities are used in the study 1 kwh = 10 x 100 watt lights bulbs 1 hour 1 kj = Burning a match 1 GJ = kwh (or ekwh)

7 Study Buildings Why High-rise MURBs? 55% of GHGs from Buildings in Vancouver High-rise MURBs largest emitters (COV) Not well understood

8 Study Buildings 39 mid and high rise residential buildings 4,400 residential suites 4,600,000 square feet of floor area $5,000,000 annual energy costs 44,000,000 kwh annual electricity use 173,000 GJ annual gas use

9 Design Characteristics Older Buildings Lower glazing percentage Framed walls Exposed concrete Punched windows

10 Design Characteristics 1990s Buildings Higher glazing percentage Concrete walls Framed wall Window wall and punched windows

11 Design Characteristics - More Recent Buildings High glazing percentage Metal panel cladding Concrete fins Window wall / spandrel panels

12 Top-down vs. Bottom-up Analysis Top down: Annual bulk energy billed known Suggests good overview Problems: Bottom-up: Metering varies (individual for electrical, vs. common for gas) Building features and activities Pools, elevators, fireplaces, lighting, etc. Seasonal conversion efficiencies not known Detailed information available Can identify anomalies or errors in billing data One building at a time Building systems known Modeling software available Occupant Behavior? Better weather data (smart metering data during cold rain events)

13 Monthly Energy Consumption Typical Building kwh Baseline Gas No Space Heat Baseline Suite Electricity No Space Heat

14 Estimated Monthly Heating kwh

15 Energy Intensity kwh/m 2 /yr Average = 213 kwh/m 2 /yr Median = 217 kwh/m 2 /yr Average = 213 kwh/m 2 /yr Std Dev = 42 kwh/m 2 /yr Range = 144 to 299 kwh/m 2 /yr Common Electricity Suite Electricity Gas

16 Distribution of Space Heat Energy % of Total Building Energy Used for Space Heat % Total Energy Which h is Heat 60% 50% 40% 30% 20% 10% Electrical Heat Gas Heat Average of 37% of Energy is used for Space-Heating Average 37% of total building energy is used for heat Of this portion an average of 69% of this energy is from gas 0% Building ID

17 Energy Consumption vs Year of Construction 350 Energy Consumption n - kwh/m 2 /yr Total Energy Space Heat Energy Year of Construction

18 Fuel for Space Heat versus Age of Building kwh/m 2 /yr 160 Gas MAU or Fireplace Space Heat 140 Electric Resistance Space Heat Electric Space Heat Trend 120 Gas Space Heat Trend

19 Space-Heat from Gas Sources % Total Building Heat which is Gas 100% 80% Average of 69%, Majority of Space-Heat Energy from Gas Sources MURBs with fireplaces in majority of suites Hydronic Gas Heat % Space Heat from Gas 60% 40% 20% 0%

20 Current Misconceptions about High-Rise Energy Use 258 kwh/m kwh/m 2 Actual? >213 kwh/m 2 HOUSES HIGHRISES All of Canada BC buildings use approximately 92% of the Canadian average Appears that Common Area Gas Consumption (~50% of total energy use), may not have been included in SHEU data-set

21 Detailed Analysis Heat Transfer

22 Determining Thermals Resistance of Assemblies Model assemblies using THERM 5.2

23 Three-Dimensional Components Isothermal planes modeling technique Cladding (Stucco) Exterior Insulation (Mineral Wool) Steel Stud Interior Gypsum Wall Board Exterior Sheathing Steel Z-girts Stud Sill Track Concrete Floor Slab Stud Head Track 1) A cross-section is created on the horizontal blue plane. 2) Components that vary along the length of the wall are modeled using THERM and equivalent homogeneous materials are created. Horizontal Cross-section Vertical Cross Section 3) A cross-section is created on the vertical green plane. 4) The assembly is modeled on this plane using THERM and the equivlanet homogenous materials created in Step 2 are used in place of inhomogeous components as illustrated at left.

24 Three-Dimensional Components Verify with HEAT 3D and previous Guarded Hot-Box testing results HEAT 3D model of 6 Stainless Steel Clip Temperature Isotherms for 6 Stainless Steel Clip Temperature Isotherms through stainless clip horizontal cut

25 R-Values Down Jacket R 3-5 R 2 Acoustic Ceiling Tile

26 Framed Wall with Batt Insulation 3.5 Fibreglass R 12 or R14 Steel stud wall assembly with concrete slab R 3-4

27 Exterior Insulated Wall 3 XPS Insulation R 15 Exterior insulated wall assembly R 7.5

28 Concrete Wall R5 1 XPS Insulation Concrete wall with steel stud furring R Fibreglass R 7 (R3 without XPS Buildings 39 and 41)

29 U-Values Window U-value = Frame U x % Frame Area + Center of Glass U x % Glass Area + Edge of Glass U x % Edge of Glass Area U-value = 1/R-value

30 Why do We Use U-Values for Windows? Window Frame Material Aluminum Small Thermal Break Typical U-value Aluminum 0.39 Improved Thermal Break Insulated Vinyl or Fiberglass Typical R-value % Heat Flow through Framing % % % Because thermal performance is so poor?

31 Spandrel Panels Spandrels are poor thermal performers Thermal bridging of insulation by frames Effective R-value of spandrel panel assemblies are only slightly better than the windows themselves

32 U-Values What do we need? Current project original window sill detail

33 U-Values What do we need? Glazing = 0.24 Glazing + Frame = 0.37 Glazing + Frame + Flashing = 0.52 BC Energy Efficiency Act Requirement = 0.35 Building Design Requirement = 0.27

34 Shop Drawing Resubmission U value =? Moisture Management? IGU Durability?

35 Determining Thermals Resistance of Assemblies Model building in Google SketchUp Concrete Wall at Outside Corner Wall Full Height at Window Jamb Concrete Wall at Inside Corner Wall Under Window Concrete Wall Full Height Wall Full Height

36 Building 39 Typical Newer High-rise Enclosure Thermal Performance Effective Window R- value Effective Wall Area R- value Effective Roof R-value Enclosure R-value Pre Rehabilitation R- value hr ft 2 F/Btu (m 2 K/W) 1.58 (0.28) 2.95 (0.52) (3.74) 2.06 (0.36) Enclosure R-value from energy consumption data 2.2

37 ASHRAE Compliance Prescriptive Path ASHRAE Compliance - Influence of Window Framing Type & IGU on Overall Enclosure R-value Overall Combined Wall and Win ndow Enclosure R-value Compliant Enclosure Walls effective R-15.6, exterior insulated,clip supports, minimal exposed slab edges Non-Compliant Enclosure <R-3.75 R2.06 < R3.75 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% % Window Area Arranged in order from best to worst U-value Vinyl/Wood/Fiberglass - lowe/argon Triple IGUs, U-0.17 Vinyl/Wood/Fiberglass - lowe/argon Double IGUs, U-0.27 High Perf. Aluminum - lowe/argon Triple IGUs, U-0.29 High Perf. Aluminum - lowe/argon Double IGUs, U-0.39 High Perf. Aluminum - lowe/air Double IGUs, U-0.43 Typical Aluminum - low-e/air Double IGUs, U-0.49 Minimum ASHRAE Compliant, U-0.55 U-values from ASHRAE tables & NFRC published values

38 Building 19 Pre & Post Rehabilitation R-values Building #19 Pre and Post R-value Improvement Pre Rehabilitation Post Rehabilitation Assembly Description R-value Assembly Description R-value Walls (52%( of enclosure): Walls: Steel Stud w/ R-14 fiberglass. Exterior insulated, R-9.5 mineral Slab edges un-insulated, wool between steel z-girts. No 3.9 balconies stud cavity insulation. Slab 5.3 edge insulated, balconies uninsulated. Windows ( 27% of enclosure, Windows: 34% of wall area): High performance thermally Non-thermally broken broken aluminum frames. Soft aluminum frames. Clear glass, coat low-e, air filled IGUs with 2.16 air filled IGUs with aluminum aluminum spacers spacers Roof (21% of enclosure): Inverted assemblies with Roof: Inverted assemblies with extruded polystyrene extruded polystyrene. Overall l Building 2.92 Overall Building 4.26 Rehabilitation improved R-value by 46% (31% reduction in U-value) Rehabilitation Resulted in a Space-Heat Savings of Approximately 10%

39 Detailed R-value Calculations Pre- & Post-Rehabilitation R-values to assess space-heat savings Calculated U-values for every detail of each wall, roof, window assembly Calculated area-weighted U-values using detailed areas from sketch-up PRE R-2.92 POST R-4.26

40 Typical Enclosure R-values Study MURBs Pre-Rehabilitation Post-Rehabilitation Overall Enclosure R-Valu ue - hr ft 2 F/Btu Building ID

41 Typical Building R-value / Glazing Percentages R-16 ASHRAE prescriptive minimum R- value wall 14 Overall Enc clsosure R-value R-10 Exterior insulated wall with no balconies & minimal thermal bridging R-5 Typical practice accounting for thermal bridging Typical MURB Enclosure R-value R-2 to R-5 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% % Window and Door Area R-2.5 High Performance Aluminum Windows R-1.3 Low Performance Aluminum Windows

42 Whole Building Modeling

43 Whole Building Energy Simulation FAST Facility Analysis and Simulation Tool (FAST) Developed by EnerSys Analytics Uses DOE-2 engine (same engine as equest, EE4) Customized for Multi-Unit Residential Buildings

44 Whole Building Energy Simulation FAST Define building through series of inputs Architectural Mechanical Space conditions

45 Whole Building Energy Simulation FAST Program calculates monthly gas and electricity consumption

46 Whole Building Energy Simulation FAST Model calibrations Define set of starting estimates for unknown input parameters Run simulation, compare simulation output to metered energy consumption (from bills) Adjust unknown inputs so that simulation output matches metered consumption

47 Whole Building Energy Simulation FAST Eg. Building 32: Suite Electricity Decreased space heating (lowered baseboard capacity) to calibrate simulation to metered data Uncalibrated Energy in kwh 250, ,000 Difference 20% 15% 10% Avg. Monthly Error: 35.4% 9.7% Ann. Error: 46.2% 150,000 5% 0% 100,000-5% Billed 50,000-10% -15% Simulated Difference 0-20% Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Calibrated Energy in kwh 140, , ,000 80,000 60,000 40,000 20,000 Difference 20% 15% 10% 5% 0% -5% -10% -15% Avg. Monthly Error:.0% 2.7% Ann. Error:.1% Billed Simulated Difference 0-20% Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

48 Whole Building Modeling, Building 33 Energy in kwh 300, , , , ,000 50,000 0 Difference Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec 20% 15% 10% 5% 0% -5% -10% -15% -20% Un-calibrated results (45.1% annual difference) Avg. Monthly Error: 35.5% 8.3% Ann. Error: 45.1% Billed Simulated Difference Energy in kwh 160,000 Difference 20% 140,000 15% 120,000 10% 100,000 5% 80,000 0% 60,000-5% 40,000-10% 20,000-15% 0-20% Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Calibrated results (o.1 % annual difference) Avg. Monthly Error:.1% 2.9% Ann. Error:.1% Billed Simulated Difference

49 Building 33 Modeling, Gas Consumption Natural Gas in GJ Difference Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec 20% 15% 10% 5% 0% -5% -10% -15% -20% Un-calibrated results (24.1% annual difference) Avg. Monthly Error: 24.9%.8% Ann. Error: 24.1% Billed Simulated Difference 700 Natural Gas Difference Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Calibrated results (o.8 % annual difference) 20% 15% 10% 5% 0% -5% -10% -15% -20% Avg. Monthly Error: -.6% 1.2% Ann. Error:.8% Billed Simulated Difference

50 Distribution of Energy Consumption Building 33 Total building energy consumption = kwh/m 2 /yr Equipment and Ammenity (Common), 28.3, 14% Elevators, 4.2, 2% Electric Baseboard Heating, 18.8, 9% Plug and Appliances (Suites), 18.7, 9% Fireplaces, 37.2, 19% Lights - Suite, 15.9, 8% Lights - Common, 3.7, 2% DHW, 32.9, 17% Ventilation Heating, 39.7, 20%

51 Distribution of Energy Consumption - Modern MURB Equipment and Ammenity (Common), 19.9, 9% Elevators, 2.7, 1% Electric Baseboard Heating, 29.1, 13% Plug and Appliances (Suites), 18.7, 9% Fireplaces, 24.1, 11% Lights -Suite, 15.9, 7% Lights -Common, 3.8, 2% Heat DHW, 20.7, 9% Modern MURB - >221.9 kwh/m 2 Ventilation Heating, 86.9, 39%

52 Impact of Nominal R-Values In Modeling Building 11 Annual Space Heat Consu umption, kwh/m Baseline Pre Nominal Assumptions 29 % Difference in Space Heat Energy Consumption

53 Other Building Systems Calibrated models allow the assessment of other building systems Number of Su uites Buildings 7, 11, 32, 33 Building Peak Average Daily Domestic Hot Water Consumption, gpm Domestic Hot Water

54 Other Building Systems Power Density (W/sf) Suite Lighting Suite Plug Loads Building Number Suite Lighting and Plug Loads

55 Typical Building Model Created a typical building model to run simulations Typical Building Model Based on 13 Buildings Average of 39 Study Buildings Total Floor Area 121,922 ft² 118,655 Percent Area for Common Space 13% Number of Suites Number of Storeys (above grade) Height of Average Storey 8.7 ft Orientation from North 0 o Gross Exposed Wall Area, Wall ft² Gross Exposed Wall Area, Wall ft² Gross Exposed Wall Area, Wall ft² Gross Exposed Wall Area, Wall ft² Window Percentage, Wall 1 46% 47% Window Percentage, Wall 2 46% 47% Window Percentage, Wall 3 46% 47% Window Percentage, Wall 4 46% 47% Infiltration Rate (0.15 cfm/sf) ACH Pre Post Overall Roof R-Value o F-ft²-hr/Btu Overall Wall R-Value o F-ft²-hr/Btu Overall Window U-Value Btu/ o F-ft²-hr Window Solar Heat Gain Coefficient Architectural Inputs

56 Distribution of Energy Consumption Typical MURB uses approximately 200 kwh/m 2 /yr Equipment and Ammenity (Common), 28.3, 14% Elevators, 4.2, 2% Electric Baseboard Heating, 18.8, 9% Plug and Appliances (Suites), 18.7, 9% Fireplaces, 37.2, 19% Lights - Suite, 15.9, 8% Lights - Common, 3.7, 2% DHW, 32.9, 17% Ventilation Heating, 39.7, 20%

57 Space Heat Consumption for locations across Canada 180 Annual Space Hea at Consumption, kwh/m Ottawa Vancouver Calgary Edmonton Winnipeg Toronto Ottawa Montreal Halifax Whitehorse

58 Impact of Wall Performance on Space Heat Consumption

59 Window Influence on Total Building Energy Comparison of Different Window Performance Criteria on Total Building Energy Consumption Case Baseline Performance Standard (effective values) Average Pre Wall R-3.6 Roof R-12.7 Overall Product Performance Characteristics [W/(m 2 K] Total Heating [kwh/m 2 ] Total Bldg Energy [kwh/m 2 ] % Total Savings U-3.97, SHGC % Window U-3.97 SHGC-0.67 Window ASHRAE U-3.24, SHGC % ASHRAE U-3.1, SHGC % ASHRAE U-2.57, SHGC % BC EEA metal frame U-2.57, SHGC % BC EEA non-metal frame U-2.0, SHGC % Non-metal frame, low-e, U-0.96, SHGC % argon fill, triple glazed Lighting ASHRAE W/m % ASHRAE W/m %

60 Impact of Window Performance on Space Heat 120 Annual Space Heat Consumption, kwh/m Electricity Gas 0 Baseline U = 0.45 SHGC = 0.4 U = 0.45 SHGC = 0.3 U = 0.27 SHGC = 0.4 U = 0.27 SHGC = 0.3 U = 0.17 SHGC = 0.3 U = 0.17 SHGC = 0.2 Post U-Value with Pre SHGC

61 Air Flow

62 Space Heat Loss Distribution Effect of Air Leakage Air Tight Enclosure Natural Air Leakage, 2.9, 3% Air Leaky Enclosure Open Windows Natural Air Leakage, 16.3, 16% Conduction, 47.9, 53% Mechanical Ventilation, 39.7, 44% Conduction, 47.9, 46% Mechanical Ventilation, 39.7, 38% kwh/m 2 /yr, % Total Space Heat Total Space Heat = 90.5 kwh/m 2 /yr kwh/m 2 /yr, % Total Space Heat Total Space Heat = kwh/m 2 /yr

63 What if Good Enclosure & w/heat Recovery Ventilation? Air Tight Enclosure Air Leaky Enclosure Open Windows Conduction 5% Conduction, 2.3, 20% Natural Air Leakage, 2.5, 22% Mechanical Ventilation 24% Mechanical Ventilation, 6.5, 58% Natural Air Leakage 71% kwh/m 2 /yr, % Total Space Heat Total Space Heat = 11.2 kwh/m 2 /yr kwh/m 2 /yr, % Total Space Heat Total Space Heat = 30.3 kwh/m 2 /yr

64 Impact of Different Make-up Air Flow Rates Assumed flow rate of 50 cfm per suite 160 Annual Space Heat Cons sumption, kwh/m Gas 0 100% of Nominal* 95% of Nominal 90% of Nominal 85% of Nominal 80% of Nominal 75% of Nominal 70% of Nominal 65% of Nominal 60% of Nominal Zero Modern

65 Understanding Energy Use in MURBs Domestic Hot Water is heated using Gas Air leakage of heated ventilation air through elevator and stairwell shafts Elevator pumping Ventilation air is heated using gas-fired make-up air unit (MUA) - To heat ventilation air for make-up air supply - To heat domestic hot water - To heat pool/hot-tubs - Suite fireplaces (if equipped) - Pilot lights for above - Interior lighting - Elevators - Ventilation fans and motors - Parking garage exhaust fans - Water distribution pumps - Baseboard heaters - Recreation areas/pool pumps - Exterior lighting - Communication - Controls Heated Ventilation air from corridor Electric Baseboard Heaters in all Suites Gas fireplaces in some Suites Air flow through open windows Air exhausted using bathroom/kitchen fans & windows Enclosure airleakage - Baseboard heaters - Lighting - Appliances - Miscellaneous Electric Loads - Plug loads - Exhaust fans Gas Boiler to heat pool & hot-tubs Rec. Areas Pool Suites Common Areas Parking Garage Typically Unheated Some Gas & Electric Heat at Common Areas Parking Garage Exhaust Fans

66 Air Flow within a Building Building 20

67 Air Pressure Differential in Study Building (43) 22 storey highrise - Pressure Beneath Suite Doors Floor Theoretical 18 Average 17 Maximum 16 Linear (Theoretical) 15 Linear (Average) Linear (Maximum) Pressure Differential (Pa) Measured air pressure across the corridor doors of suites in a 22 storey building

68 Make-Up air Considerations 1. We should be ventilating for health and comfort (not heat) 2. Corridors need a minimal amount of air for smoke/odour control but fresh air is needed in the suites. 3. Reconsider large rooftop MUA units & pressurized corridor supply for ventilation. 4. Provide fresh air-directly to suites 5. Compartmentalization is needed Further research of air flow within buildings required

69 Make-Up Air Investigation Investigation and analysis of condensation related problems at window-wall assemblies. Monitored environmental conditions and mechanical system conditions: Temperatures Relative Humidity CO 2 Operation of mechanical equipment including Heat pump Cloths dryer Exhaust Fans Make-up air at suite door

70 Make-Up Air Investigation

71 Actual Airflow Suite Number N601 N301 Baseline (no fans operational) Master Bathroom Fan Guest Bathroom Fan Common Bathroom Fan Kitchen Fan - Level 1 Kitchen Fan - Level 2 Kitchen Fan - Level 3 Dryer w/ Booster Fan ASHRAE Recommended (based on suite size = 0.3 ACH) % of ASHRAE Baseline % of ASHRAE Recommended with Continuous Master Bath Fan ASHRAE Recommended (based on # of occupants, 15cfm/person) % of ASHRAE Baseline % of ASHRAE Recommended with Continuous Master Bath Fan Control suite Air flow less affected by fan operation, hallway pressurization was not working ASHRAE recommendations based on suite area (accounts for 5-6 occupants) ASHRAE recommendations at 15 cfm per person for actual occupant loads 24 cfm cfm 29% 67% 30 cfm 79% 183% 0 cfm cfm 0% 10% 30 cfm 0% 27%

72 Other Considerations Fireplaces Occupants etc.

73 Other Considerations Impact of Fireplaces Why do we need them? 120 Annual Space Heat Cons nsumption, kwh/m Gas Electricity Baseline Pre With Fireplaces Baseline Pre Without Fireplaces

74 Distribution of Energy Costs in MURBs Plug and Appliances (Suite), 18.7, 31% Electric Baseboard Heating, 24.8, 42% Total Consumed By Strata, 146.9, 71% Total Consumed By Owner, 59.5, 29% Equipment and Ammenity (Common), 28.3, 19% Lights (Suite), 15.9, 27% Elevators, 4.2, 3% Owner Paid Electric Baseboard Heating, 0.3, 0% Fireplaces, 37.7, 26% Lights (Common), 3.7, 3% Strata Paid DHW, 32.9, 22% Ventilation Heating, 39.7, 27%

75 Disconnect Between Consumption and Billing Average MURB Energy Distribution and Associated Cost 28% Suite Electricity = $408/yr (Occupant Paid) 21% Common Area Electricity = $323/yr (Strata Paid) 51% Gas Heat and Hot water = $455/yr (Strata Paid) Only 36% of Total Energy Cost is Directly Paid by Occupant 69% of Building Space Heat is from Gas (Paid by Strata) Occupants are only directly paying for 31% of space heating

76 How Do We Do Better?

77 Where Do We Want To Go? New Buildings to be Carbon Neutral by 2020 Biggest Opportunities in Existing Buildings

78 Getting to Best Performance Space Heating Reduce the loads Recover the heat

79 Impact of Cladding Attachment R-15 of Insulation Current Practice Better Even Better Most Efficient R-7.4 R-10.3 R-11.6 to 14.4 R-15.8

80 Retrofit and New Construction Enclosure Strategies 10 ASHRAE Compliance - Influence of Window Framing Type on Overall Enclosure R-value 9 Overall Combined Wall and Wind dow Enclosure R-value ASHRAE Compliant Buildings Constructed with minimally compliant wall and window R-values Study Buildings - Metro Vancouver Average 50% glazing area Thermally Efficient Building Enclosures Constructed with high performance windows and well insulated walls 0 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% % Window Area

81 Thermal Anatomy of a High Rise MURB R-12 Insulation in walls R-4 accounting for steel studs and slab edges R-1.8 Windows aluminum window wall, low-e, air fill R-20 Roof Insulation 65% Glazing R-Value % of Enclosure % Heat loss Walls Windows Roof Overall R-Value 2.3 Strategy 1 Improve wall R-value to R10 Strategy 2 Improve window R-value to R3.5 Strategy 3 Reduce window area to 30%

82 Strategy 1 Improve wall R-value to R10 R-Value % of Enclosure % Heat loss Walls Windows Roof Overall R-Value Base Strategy 1

83 Strategy 2 Improve Window R-value to R3.5 R-Value % of Enclosure % Heat loss Walls Windows Roof Overall R-Value Base Strategy 1 Strategy 2

84 Strategy 3 Reduce Glazing to 30% R-Value % of Enclosure % Heat loss Walls Windows Roof Overall R-Value Base Strategy 1 Strategy 2 Strategy 3

85 Reduced Glazing Area

86 Improved Ventilation Strategies Corridor pressurized with small fans at each floor level

87 Combination Energy Efficiency Measures Simulated Scenario Model Inputs Baseline Post t Walls effective R-5.5 t Windows double glazed, air fill, low-e, aluminum frame; U = 0.51, SC = 0.45 t Air tightness Tight High Average, 0.15 cfm/ft 2 t Make-up air temperature setpoint 68 F t No heat recovery Good t Walls effective R-10 t Windows double glazed, argon fill, low-e, low conductive frame; U = 0.27, SC = 0.35 t Air tightness Tight Low Average, 0.05 cfm/ft 2 t Make-up air temperature setpoint 64 F t No heat recovery Best t Walls effective R-18.2 t Windows triple glazed, argon fill, low-e, low conductive frame; U = 0.17, SC = 0.23 t Air tightness Very Tight, 0.02 cfm/ft 2 t Make-up air temperature setpoint 60 F t 80% Heat Recovery

88 Simulated Space Heat Consumption Scenarios Annual Space Heat Cons sumption, kwh/m Better windows, walls and air-tightness 67.4 Ventilation Heat-Recovery Baseline Pre Baseline Post Good Best Good, Without Fireplaces Best, Without Fireplaces

89 Total Building Energy Use Can get ~100 kwh/m 2 /yr with ventilation and enclosure upgrades only Further improvements from Domestic Hot Water, Lighting, Appliances, Controls etc. 250 Annual Energy Consumption, kwh/m Gas Electricity 0 Baseline Pre Baseline Post Good Best Good, Without Fireplaces Best, Without Fireplaces

90 How Do We Get To Net Zero? 35 R-Values 30 t Consumption, kwh/m 2 Annual Suite Electric Space Heat U = 0.45, 50% WWR U = 0.45, 40% WWR U = 0.45, 30% WWR U = 0.45, 20% WWR U = 0.27, 50% WWR U = 0.27, 40% WWR U = 0.27, 30% WWR U = 0.27, 20% WWR U = 0.17, 50% WWR U = 0.17, 40% WWR U = 0.17, 30% WWR U = 0.17, 20% WWR Wall Effective R-Value R (hr-ft 2 -F/Btu)

91 Near Net Zero Effective Control of Air Flow 40 Annual Suite Electric Space Heat Consumption, kwh/m Enclosure 1: Windows U-0.17, 30% WWR, Walls R-18.2 Enclosure 2: Windows U-0.45, 40% WWR, Walls R-15.6 Typical Building Simulated Air Leakage Rate Air Leakage Rate, cfm/sf

92 Final Thoughts - Energy Efficiency & Moisture Problems Increased risk of moisture problems in more energy efficient buildings Consider future maintenance and renewal costs Systemic Low-e corrosion within proprietary triple IGUs after 5 years Failure of thermo-cladding

93 Need for a New Approach

94 Integrated Design Process Courtesy of Bunting Coady Architects

95 A New Approach for the Design of Buildings

96 A New Approach for the Design of Buildings

97 A New Approach for the Design of Buildings

98 A New Approach for the Design of Buildings

99 Discussion

100 Further Information / Background Information CMHC Reports / Guides Homeowner Protection Office Bulletins and Guides Builder Insight No. 7 Building Enclosure Design Guide

101 BC Energy Efficiency Act - Windows Low-rise Requirements Product Maximum U-Value W/(m 2 K) BTU/(hr ft 2 K) Effective Date Vinyl and fibreglass windows and sliding doors Tested with CSA A or NFRC Third party testing (SCC or NFRC accredited labs) Permanent certification label, temporary U-value label Exempts heritage buildings March 1, 2009 Wood windows and sliding glass doors January 1, 2011 Metal windows and sliding glass doors June 1, 2009 January 1, 2011 Skylights (for low-rise and high-rise) March 1, 2009

102 BC Energy Efficiency Act - Windows High-rise Requirements Product Maximum U-Value W/(m 2 K) BTU/(hr ft 2 K) Effective Date Metal framed curtain wall, window wall and storefront products Windows with framing materials other than metal, with or without metal reinforcing or cladding January 1, January 1, 2011 Exempts products installed in buildings that are compliant with ASHRAE 90.1 (04 or 07) Option for U-value certificate in lieu of labels Flexibility provided for structural windows

103 Improved Ventilation Strategies Corridor pressurized with small fans at each floor level

104 Questions?

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING Brittany Hanam 1, Lorne Ricketts 2, Andrew Pape-Salmon 3 ABSTRACT The National Institute of Building Sciences estimates that over 70% of the

More information

Deep Energy Retrofit of a HighRise MURB

Deep Energy Retrofit of a HighRise MURB Deep Energy Retrofit of a HighRise MURB COLIN SHANE M.Eng., P.Eng. RDH BUILDING SCIENCES INC. SAN FRANCISCO, CA AIA Credits National Institute of Building Sciences Provider #G168 Credit(s) earned on completion

More information

EVALUATING THE ENERGY SAVINGS OF HIGH PERFORMANCE BUILDING ENCLOSRE RETROFITS Brittany Hanam, MASc, P.Eng. Graham Finch, MASc, P.Eng.

EVALUATING THE ENERGY SAVINGS OF HIGH PERFORMANCE BUILDING ENCLOSRE RETROFITS Brittany Hanam, MASc, P.Eng. Graham Finch, MASc, P.Eng. EVALUATING THE ENERGY SAVINGS OF HIGH PERFORMANCE BUILDING ENCLOSRE RETROFITS Brittany Hanam, MASc, P.Eng. Graham Finch, MASc, P.Eng. ABSTRACT Building enclosure retrofits for multiunit residential buildings

More information

airflow in to, out of, and within buildings. These airflows are resisted by the airtightness of building elements including the exterior enclosure and

airflow in to, out of, and within buildings. These airflows are resisted by the airtightness of building elements including the exterior enclosure and Airflow in to, out of, and within buildings is a fundamental factor of indoor air quality, comfort, durability, and energy consumption. Multi-unit residential buildings are uniquely complex in this respect

More information

Thermal Bridging and Whole Building Energy Performance

Thermal Bridging and Whole Building Energy Performance Thermal Bridging and Whole Building Energy Performance Steve Murray, P.Eng. PMP Morrison Hershfield May 8 & 9, 2013 1 Acknowledgments The real work for ASHRAE 1365 RP was done by others in MH s Vancouver

More information

A New Paradigm for the Design of Sustainable Buildings

A New Paradigm for the Design of Sustainable Buildings BEST2, Energy Efficiency - Invited paper for session EE3-2 A New Paradigm for the Design of Sustainable Buildings Warren Knowles, P.Eng., Brian Hubbs, P.Eng., Paul Kernan, MAIBC, Graham Finch, MASc, 1

More information

Hamilton Way - Case Study of a High Performance Community in a Cold Climate

Hamilton Way - Case Study of a High Performance Community in a Cold Climate March 11, 2010 Northeast Sustainable Energy Association Conference Peter Baker, P.Eng. Building Science Corporation Chris Nelson Nelson Construction Hamilton Way - Case Study of a High Performance Community

More information

Passive House in Canada: Case Studies on a Near EnerPHit Retrofit and Post-Occupancy Research

Passive House in Canada: Case Studies on a Near EnerPHit Retrofit and Post-Occupancy Research Passive House in Canada: Case Studies on a Near EnerPHit Retrofit and Post-Occupancy Research Brittany Coughlin, RDH Building Science Inc. 224 W 8 th Ave, Vancouver, BC Canada Phone: +011 604 873 1181;

More information

PV Generation Potential 17.1 kbtu/ft2/yr 15.4

PV Generation Potential 17.1 kbtu/ft2/yr 15.4 TOWNHOME PROTOTYPE BASELINE 60 kbtu/sf/yr 50 kbtu/sf/yr 40 kbtu/sf/yr 30 kbtu/sf/yr 20 kbtu/sf/yr 10 kbtu/sf/yr 0 kbtu/sf/yr 54.4 Baseline 54.4 kbtu/ 2/yr 21.8 High Performance 18.2 PHIUS - IES 60 MMBtu

More information

ACHIEVING HIGH-PERFORMANCE MULTI-UNIT RESIDENTIAL BUILDINGS: THE OPPORTUNITIES

ACHIEVING HIGH-PERFORMANCE MULTI-UNIT RESIDENTIAL BUILDINGS: THE OPPORTUNITIES ACHIEVING HIGH-PERFORMANCE MULTI-UNIT RESIDENTIAL BUILDINGS: THE OPPORTUNITIES CHALLENGES OF MURB PERFORMANCE Energy intensity of multi-unit residential buildings (MURBs) has been marginally increasing

More information

Fenestration Energy Performance:

Fenestration Energy Performance: number 9 Builder Insight Fenestration Energy Performance: A Roadmap for Understanding Requirements for Residential Buildings in British Columbia Overview Energy performance requirements for windows, doors

More information

PV Generation Potential 17.1 kbtu/ft2/yr 15.4

PV Generation Potential 17.1 kbtu/ft2/yr 15.4 TOWNHOME PROTOTYPE HIGH PERFORMANCE 60 kbtu/sf/yr 50 kbtu/sf/yr 40 kbtu/sf/yr 30 kbtu/sf/yr 20 kbtu/sf/yr 10 kbtu/sf/yr 0 kbtu/sf/yr 54.4 Baseline 21.8 kbtu/ 2/yr 15 MMBtu 12 MMBtu 9 MMBtu 6 MMBtu 3 MMBtu

More information

Break it, or Lose it: Thermal Bridging in Building Envelopes

Break it, or Lose it: Thermal Bridging in Building Envelopes Break it, or Lose it: Thermal Bridging in Building Envelopes NESEA BuildingEnergy 16 March 9, 2016 INTRODUCTION Learning Objectives 1. Learn the significance that thermal bridges can have on decreasing

More information

MID-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 10.8 kbtu/ 2/yr

MID-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 10.8 kbtu/ 2/yr MID-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE 50 kbtu/sf/yr 45.1 PROJECT INFORMATION 40 kbtu/sf/yr 30 kbtu/sf/yr 20 kbtu/sf/yr 10 kbtu/sf/yr 0 kbtu/sf/yr 13.0 kbtu/ft2/yr Baseline 10.8 kbtu/ft2/yr

More information

Choosing Windows for the North

Choosing Windows for the North Choosing Windows for the North MAY 7, 2015 WHITEHORSE, YUKON GRAHAM FINCH, MASC, PENG PRINCIPAL, BUILDING SCIENCE RESEARCH SPECIALIST RDH BUILDING ENGINEERING LTD. VANCOUVER, BC - GFINCH@RDH.COM Afternoon

More information

The Concept of Linear and Point Transmittance and its Value in Dealing with Thermal Bridges in Building Enclosures

The Concept of Linear and Point Transmittance and its Value in Dealing with Thermal Bridges in Building Enclosures The Concept of Linear and Point Transmittance and its Value in Dealing with Thermal Bridges in Building Enclosures BEST3, April 2012 Neil Norris, MaSc Patrick Ropell, B.Eng. Mark Lawton, P.Eng MH Vancouver

More information

LOW-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 17.9 kbtu/ 2/yr

LOW-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 17.9 kbtu/ 2/yr LOW-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE 40 kbtu/sf/yr 35 kbtu/sf/yr 30 kbtu/sf/yr 25 kbtu/sf/yr 20 kbtu/sf/yr 15 kbtu/sf/yr 10 kbtu/sf/yr 5 kbtu/sf/yr 0 kbtu/sf/yr 11.9 kbtu/ft2/yr 36.0

More information

Bridging on Building Envelope Performance. A Whole Building Energy Perspective

Bridging on Building Envelope Performance. A Whole Building Energy Perspective The Effects of Thermal Bridging on Building Envelope Performance A Whole Building Energy Perspective Dave André PEng Dave André, P.Eng. January 2014 1 Thermal Bridging g Impact 2 Thermal Bridging Overview

More information

The Importance of Slab Edge & Balcony Thermal Bridges

The Importance of Slab Edge & Balcony Thermal Bridges Date RDH Building Engineering Ltd. September 24, 2013 The Importance of Edge & Balcony Thermal Bridges Report # 3: Energy Consumption and Cost Savings of Thermal Breaks Prepared by The Importance of Edge

More information

Is Your Envelope Effective? BCBEC Luncheon January 29, 2009

Is Your Envelope Effective? BCBEC Luncheon January 29, 2009 Is Your Envelope Effective? Patrick Roppel P Eng Patrick Roppel P.Eng BCBEC Luncheon January 29, 2009 Goals for this Presentation Why we might be concerned with heat loss through the envelope (U-value

More information

THE IMPORTANCE OF BALCONY AND SLAB EDGE THERMAL BRIDGES IN CONCRETE CONSTRUCTION

THE IMPORTANCE OF BALCONY AND SLAB EDGE THERMAL BRIDGES IN CONCRETE CONSTRUCTION THE IMPORTANCE OF BALCONY AND SLAB EDGE THERMAL BRIDGES IN CONCRETE CONSTRUCTION G. Finch, J. Higgins and B. Hanam ABSTRACT Exposed concrete slab edges, balconies, and eyebrows on multistorey buildings

More information

The Importance of Slab Edge & Balcony Thermal Bridges

The Importance of Slab Edge & Balcony Thermal Bridges Exterior Exterior Thermal Break Prepared by Date RDH Building Engineering Ltd. September 24, 2013 Interior 18.6 C Interior 18.6 C Report # 2: Impact of Slab Thermal Breaks on Thermal Comfort and Condensation

More information

Brussels Window. Good Windows. Windows. Objectives. Why Good Windows? Windows. Need to control. Learn. Functions: Same as wall - plus.

Brussels Window. Good Windows. Windows. Objectives. Why Good Windows? Windows. Need to control. Learn. Functions: Same as wall - plus. Good Windows Brussels Window Dr John Straube Dupont Young Professor Civil Eng Dept and School of Architecture University of Waterloo Waterloo, Ont Canada jfstraube@uwaterloo.ca Windows Objectives Need

More information

Could a European Super Energy Efficient Standard Be Suitable for the U.S.? John Broniek, IBACOS BEST1 CONFERENCE June 12, 2008

Could a European Super Energy Efficient Standard Be Suitable for the U.S.? John Broniek, IBACOS BEST1 CONFERENCE June 12, 2008 Could a European Super Energy Efficient Standard Be Suitable for the U.S.? John Broniek, IBACOS BEST1 CONFERENCE June 12, 2008 Agenda European Passive House Program Creating Passive House Designs in U.S.

More information

PART 2 ENERGY SAVINGS AND COST BENEFIT ANALYSIS

PART 2 ENERGY SAVINGS AND COST BENEFIT ANALYSIS ENERGY SAVINGS AND COST BENEFIT ANALYSIS Table Of Contents 2.1 OVERVIEW... 2-1 2.2 WHOLE BUILDING ENERGY USE... 2-1 2.2.1 Assessing Whole Building Energy Use... 2-1 2.2.2 Building Archetypes and Modeling

More information

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012 2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,

More information

Impact of Insulated Concrete Curb on Concrete Balcony Slab

Impact of Insulated Concrete Curb on Concrete Balcony Slab Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 118 (2015 ) 1030 1037 International Conference on Sustainable Design, Engineering and Construction Impact of Insulated Concrete

More information

HOT2000 Natural Resources CANADA Version v11.3

HOT2000 Natural Resources CANADA Version v11.3 HOT2000 Natural Resources CANADA Version v11.3 File: 1234 Fulton Ave..h2k ERS reference house Weather Library: C:\HOT2000 v11.3\dat\wth110.dir Weather Data for: VANCOUVER, BRITISH COLUMBIA Builder Code:

More information

BC Energy Efficiency Act - Regulatory Proposal for Window and Door Products

BC Energy Efficiency Act - Regulatory Proposal for Window and Door Products BC Energy Efficiency Act - Regulatory Proposal for Window and Door Products A number of regulations for window and door products are currently included in the Energy Efficiency Standards Regulation that

More information

Thermal Performance of Northern Facades ISO Clip System Summary

Thermal Performance of Northern Facades ISO Clip System Summary Thermal Performance of Northern Facades ISO Clip Summary The Northern Facades ISO Thermal Clip is a steel clip system for attaching cladding systems to various types of exterior insulated wall assemblies.

More information

Building Envelopes 101

Building Envelopes 101 Session: Foundation Building Block 1 Building Envelopes 101 Diana Hun, PhD Oak Ridge National Laboratory August 9, 2016 Rhode Island Convention Center Providence, Rhode Island US Primary Energy Consumption

More information

Understanding the National Energy Code of Canada for Buildings, 2011

Understanding the National Energy Code of Canada for Buildings, 2011 Understanding the National Energy Code of Canada for Buildings, 2011 Introduction Manufacturer of fiberglass construction products Fiberglass windows Fiberglass doors Fiberglass cladding support systems

More information

ENCLOSURE SOLUTIONS THERMAL BRIDGING GUIDE FIBERGLAS FOAMULAR THERMAFIBER

ENCLOSURE SOLUTIONS THERMAL BRIDGING GUIDE FIBERGLAS FOAMULAR THERMAFIBER ENCLOSURE SOLUTIONS THERMAL BRIDGING GUIDE FIBERGLAS FOAMULAR THERMAFIBER This publication was prepared by Published by Owens Corning September 2018 DISCLAIMER This publication provides thermal transmittance

More information

SURNA Grow Facility: Systems Comparison - IEA

SURNA Grow Facility: Systems Comparison - IEA SURNA Grow Facility: Systems Comparison - IEA May 2016 SURNA Grow Facility This analysis provides the projected energy and associated cost comparison between the Surna proposed facility in comparison to

More information

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort

Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort Please add relevant logo here Energy Efficiency: Designing Wood-Frame Buildings for Occupant Comfort Presented by: Peter J. Arsenault, FAIA, NCARB, LEED-AP Disclaimer: This presentation was developed by

More information

ENERGY EFFICIENCY STANDARDS REGULATION

ENERGY EFFICIENCY STANDARDS REGULATION Energy Efficiency Act ENERGY EFFICIENCY STANDARDS REGULATION B.C. Reg. 14/2015 Deposited and effective February 4, 2015 Last amended March 6, 2018 by B.C. Reg. 29/2018 Consolidated Regulations of British

More information

Passive House 2.0 LESSONS LEARNED FROM THE FIRST GENERATION OF MULTI-UNIT PASSIVE HOUSE BUILDINGS IN B.C.

Passive House 2.0 LESSONS LEARNED FROM THE FIRST GENERATION OF MULTI-UNIT PASSIVE HOUSE BUILDINGS IN B.C. Passive House 2.0 LESSONS LEARNED FROM THE FIRST GENERATION OF MULTI-UNIT PASSIVE HOUSE BUILDINGS IN B.C. PASSIVE HOUSE NORTHWEST, APRIL 6 2017 MONTE PAULSEN, PHI-ACCREDITED BUILDING CERTIFIER RDH Building

More information

3-Dimensional Thermal Analysis of Lenmak EnvaTherm and SpandrelTherm Backpan Assemblies

3-Dimensional Thermal Analysis of Lenmak EnvaTherm and SpandrelTherm Backpan Assemblies Report Number: 5160440 August 18 th, 2016 3-Dimensional Thermal Analysis of Lenmak EnvaTherm and SpandrelTherm Backpan Assemblies Presented to: Lenmak Exterior Innovations Inc. 10404-176 Street Edmonton,

More information

Building Envelope

Building Envelope 9.36.2. Building Envelope Module 2 BCBC 9.36. 2014 1 Richard Kadulski Architect 9.36.2. Building Envelope Focus is on total building performance, not just thermal insulation Heat transfer and air leakage

More information

RESEARCH HIGHLIGHT. Documentation of Super-Insulated Housing in Yukon

RESEARCH HIGHLIGHT. Documentation of Super-Insulated Housing in Yukon RESEARCH HIGHLIGHT March 2017 Technical Series INTRODUCTION Since 2007, Yukon Housing Corporation (YHC) has built 224 super-insulated public housing units, with approximately 300 market units built across

More information

Thermal Bridging and Energy Standards 2014 BOABC Education Conference. November 27, 2014

Thermal Bridging and Energy Standards 2014 BOABC Education Conference. November 27, 2014 Thermal Bridging and Energy Standards 2014 BOABC Education Conference November 27, 2014 Current Energy Standards vs. Research Insights Building Envelope Thermal Bridging Guide Overview Significance, Insights,

More information

Zero Carbon Building Energy Modelling Guidelines. October 31, 2017

Zero Carbon Building Energy Modelling Guidelines. October 31, 2017 Zero Carbon Building Energy Modelling Guidelines October 31, 2017 Contents 1. INTRODUCTION... 3 1.1 DEFINITIONS... 4 2. CALCULATING TEDI... 5 2.1 INTERNAL HEAT GAINS... 6 2.2 CALCULATING BUILDING ENVELOPE

More information

2010 National Building Code Adoption and Associated Process Changes

2010 National Building Code Adoption and Associated Process Changes Building Inspection City of Moncton 655 Main Street Moncton, NB E1C 1E8 Phone: (506) 856-4375 Fax: (506) 856-4348 Bulletin No. 14 From: Randy Richard Date: February 9, 2015 Subject: 2010 National Building

More information

Net Zero Building Enclosure Retrofits for Houses: An Analysis of Retrofit Strategies

Net Zero Building Enclosure Retrofits for Houses: An Analysis of Retrofit Strategies Net Zero Building Enclosure Retrofits for Houses: An Analysis of Retrofit Strategies Graham Finch, PEng Associate Member ASHRAE Brittany Hanam, PEng, BEMP Associate Member ASHRAE, Building Energy Modeling

More information

Be Aggressive About the Passive Solutions

Be Aggressive About the Passive Solutions Be Aggressive About the Passive Solutions Integrating Building Envelope Design in Whole Building Energy Goals Daniel Luddy, PE BEMP CPHC LEEP AP Senior Energy Engineer 2015 Building Envelope Forum AIA

More information

ENERGY AUDIT. 123 Main Street Mississauga, Ontario. January 1, Report To: Mr. John Smith Smith Printing Company.

ENERGY AUDIT. 123 Main Street Mississauga, Ontario. January 1, Report To: Mr. John Smith Smith Printing Company. Report To: Mr. John Smith Smith Printing Company ENERGY AUDIT 123 Main Street Mississauga, Ontario January 1, 2009 120 Carlton Street, Suite 212 Toronto, Ontario M5A 4K2 Tel 416-964-3246 Toll Free 1-866-964-3246

More information

The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario

The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario Visionwall Technologies Inc. 14904-123 Avenue Edmonton, Alberta, Canada T5V 1B4 Tel: 403 451 4000 Fax:

More information

What s My Baseline? ASHRAE

What s My Baseline? ASHRAE 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116,part 2). For personal use only. Additional reproduction,

More information

Insulation - History. Heat Flow, in 2 and 3 D. Insulation - History. Insulation - History

Insulation - History. Heat Flow, in 2 and 3 D. Insulation - History. Insulation - History Heat Flow, in 2 and 3 D R2 Insulation - History Dr John F Straube, P.Eng. Building Science Corporation & University of Waterloo Department of Civil Engineering & School of Architecture Waterloo, Ontario,

More information

Three-Story Victorian Partial Retrofit. Overview. Case Study

Three-Story Victorian Partial Retrofit. Overview. Case Study Case Study National Grid Deep Energy Retrofit Pilot Program Three-Story Victorian Partial Retrofit Brookline, Massachusetts Overview The owners of this single family Victorian had previously gone through

More information

Sample Reports. for. HAP v4.90 Example Problem

Sample Reports. for. HAP v4.90 Example Problem Sample Reports for HAP v4.90 Example Problem December, 2014 Carrier Software Systems Copyright 2014 Carrier Corporation, All Rights Reserved Introduction This document contains reports generated using

More information

Manitoba Energy Code for Buildings. Part 3 Building Envelope

Manitoba Energy Code for Buildings. Part 3 Building Envelope Manitoba Energy Code for Buildings Part 3 Building Envelope Rick Marshall, P. Eng, LEED AP September 17, 2014 Manitoba Energy Code for Buildings (MECB) Training Day Part 3 - Scope Part 3 is concerned with

More information

JRS ENGINEERING. Continuous Insulation Overall Effective. Presented by: Marty Deemter, P.Eng. Scott Croasdale, M.Eng, P.Eng, PE

JRS ENGINEERING. Continuous Insulation Overall Effective. Presented by: Marty Deemter, P.Eng. Scott Croasdale, M.Eng, P.Eng, PE JRS ENGINEERING Building Envelope Consultants Continuous Insulation Overall Effective R-Value of Exterior Walls Presented by: Marty Deemter, P.Eng. Developed by: Scott Croasdale, M.Eng, P.Eng, PE Topics

More information

SUSTAINABILITY MEASURES

SUSTAINABILITY MEASURES The following items summarize our strategies to outperform the City of Vancouver s sustainability requirements with focus on reducing the thermal energy demand, total energy use, and greenhouse gas emissions

More information

Thermal Bridging From Cladding Attachment Strategies Through Exterior Insulation

Thermal Bridging From Cladding Attachment Strategies Through Exterior Insulation Thermal Bridging From Cladding Attachment Strategies Through Exterior Insulation PHIUS 9 TH ANNUAL NAPHC, SAN FRANCISCO BAY AREA COLIN SHANE M.ENG, P.ENG 12 SEPTEMBER 2014 Learning Objectives / Overview

More information

Corridor Pressurization System Performance in Multi-Unit Residential Buildings

Corridor Pressurization System Performance in Multi-Unit Residential Buildings Corridor Pressurization System Performance in Multi-Unit Residential Buildings Lorne Ricketts Student Member ASHRAE John Straube, PhD, P.Eng. Associate Member ASHRAE ABSTRACT Corridor pressurization based

More information

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING ABSTRACT F. Bagheri 1, M. Fakoor 1, B. Young 1, C. Cranswick 1 1 BC Building Science Ltd. 611 Bent

More information

OUTLINE. Building Envelope Thermal Bridging Guide. High Level Overview and Themes. The Code Context. The Energy Context. Where do we go from here?

OUTLINE. Building Envelope Thermal Bridging Guide. High Level Overview and Themes. The Code Context. The Energy Context. Where do we go from here? Building Envelope Thermal Bridging Guide September 24, 2015 Christian Cianfrone Principal, Morrison Hershfield OUTLINE High Level Overview and Themes The Code Context The Energy Context Where do we go

More information

Supplementary Standard SB-12. Energy Efficiency For Housing

Supplementary Standard SB-12. Energy Efficiency For Housing Ministry of Municipal Affairs and Housing Building and Development Branch 2006 Building Code - Supplementary Standards Supplementary Standard SB-12 Energy Efficiency For Housing January 1, 2012 update

More information

Future tree planting on the two acre lot will offset remaining lifetime carbon emissions.

Future tree planting on the two acre lot will offset remaining lifetime carbon emissions. Luxury Net-Zero Home by Rockwood Custom Homes 47 Grandview Place, Calgary AB T3Z A8 by Grant Bremner A Net-Zero Emissions (NZE) home is carbon neutral where carbon credits fully offset emissions. An NZE

More information

Professional Educational Series BSP716 USGBC # Commercial Building Science Thermal Control in Building Envelopes

Professional Educational Series BSP716 USGBC # Commercial Building Science Thermal Control in Building Envelopes Professional Educational Series BSP716 USGBC # 90006736 Commercial Building Science Thermal Control in Building Envelopes CertainTeed Building Solutions 1.5 CertainTeed is a Registered Provider with the

More information

IMPACT OF CLIMATE CHANGE

IMPACT OF CLIMATE CHANGE October 10 11, 2016. Over 90 blind-reviewed papers. Register today. http://facadetectonics.org/save-the-date-2016-facade-tectonics-world-congress/ IMPACT OF CLIMATE CHANGE Thermal and energy performance

More information

Sample Reports. for. HAP v4.80 Example Problem

Sample Reports. for. HAP v4.80 Example Problem Sample Reports for HAP v4.80 Example Problem October, 2013 Carrier Software Systems Copyright 2013 Carrier Corporation, All Rights Reserved Introduction This document contains reports generated using the

More information

FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION. Florida Department of Business and Professional Regulation - Residential Performance Method

FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION. Florida Department of Business and Professional Regulation - Residential Performance Method FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Merryplace Homes Type II Builder Name:

More information

FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION. Florida Department of Business and Professional Regulation - Residential Performance Method

FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION. Florida Department of Business and Professional Regulation - Residential Performance Method FORM R405-204 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Merryplace Homes Type III

More information

COST AND BENEFIT ANALYSIS OF PROPOSED CHANGES FOR ENERGY EFFICIENCY IN HOUSING AND SMALL BUILDING IN THE NATIONAL BUILDING CODE

COST AND BENEFIT ANALYSIS OF PROPOSED CHANGES FOR ENERGY EFFICIENCY IN HOUSING AND SMALL BUILDING IN THE NATIONAL BUILDING CODE COST AND BENEFIT ANALYSIS OF PROPOSED CHANGES FOR ENERGY EFFICIENCY IN HOUSING AND SMALL BUILDING IN THE NATIONAL BUILDING CODE REPORT PREPARED FOR FRANK LOHMANN, SENIOR TECHNICAL ADVISOR CANADIAN CODES

More information

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal

More information

Case study of an ECBC Compliant, Energy Efficient Building: Aranya Bhawan, Jaipur

Case study of an ECBC Compliant, Energy Efficient Building: Aranya Bhawan, Jaipur Case study of an ECBC Compliant, Energy Efficient Building: Aranya Bhawan, Jaipur Prashant Bhanware (BEEP) 2 nd REGIONAL WORKSHOP ON ECBC IMPLEMENTATION IN STATES March 15 & 16, 2017 Hyatt, Ahmedabad Outline

More information

Technical Report Two: Building and Plant Energy Analysis Report

Technical Report Two: Building and Plant Energy Analysis Report The American Swedish Institute Minneapolis, MN Technical Report Two: Building and Plant Energy Analysis Report Name: Option: Mechanical Advisor: Stephen Treado Date: 10.19.11 Table of Contents Executive

More information

BUILDING ENCLOSURE AIR TIGHTNESS TESTING Course Number: BCLUNA018-01P

BUILDING ENCLOSURE AIR TIGHTNESS TESTING Course Number: BCLUNA018-01P BUILDING ENCLOSURE AIR TIGHTNESS TESTING Course Number: BCLUNA018-01P Provider Number:404108121 Darek Brandt, PE Chief Engineer, Building Science Solutions AIA CES DISCLAIMER Credit(s) earned on completion

More information

2009 IECC Chapter 1 Additions, alterations, renovations or repairs.

2009 IECC Chapter 1 Additions, alterations, renovations or repairs. 2009 IECC Chapter 1 Additions, alterations, renovations or repairs. Additions, alterations, renovations or repairs to an existing building, building system or portion thereof shall conform to the provisions

More information

CENTRA WINDOWS. Manufacturer for Centra Construction Group of Companies

CENTRA WINDOWS. Manufacturer for Centra Construction Group of Companies CENTRA WINDOWS Manufacturer for Centra Construction Group of Companies Windows and Doors What to look for By Anton Van Dyk What does the Building Code Cover: Thermal Performance December, 2014 Air, Water

More information

Thermal Performance of Nvelope NV1 Clip System

Thermal Performance of Nvelope NV1 Clip System Report Number: 5140108.00 December 18, 2014 Thermal Performance of Nvelope NV1 Clip System Presented to: Nvelope USA, LLC 16904 164 th Way S.E. Renton, WA 98058 Morrison Hershfield Suite 310, 4321 Still

More information

National Building Code Part 9 Energy Efficiency: Focus Paper to Assist in the Review of Proposed Changes

National Building Code Part 9 Energy Efficiency: Focus Paper to Assist in the Review of Proposed Changes National Building Code Part 9 Energy Efficiency: Focus Paper to Assist in the Review of Proposed Changes February 2012 Contents 0. Background and Purpose of the Paper 1. Development of NBC Part 9 Energy

More information

High Performance, Energy Efficient Design for Wood Frame Buildings

High Performance, Energy Efficient Design for Wood Frame Buildings Disclaimer: This presentation was developed by a third party and is not funded by WoodWorks or the Softwood Lumber Board. Please add relevant logo here High Performance, Energy Efficient Design for Wood

More information

Date Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection

Date Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection Slab on Grade & Basements: A capillary break is installed on top of all footings Slab / Pre-Drywall / Thermal Inspection A minimum of 4" of clean or washed gravel (0.5" diameter or greater) is placed over

More information

Energy Efficiency For Housing

Energy Efficiency For Housing Ministry of Municipal Affairs and Housing Building and Development Branch MMAH Supplementary Standard SB-12 MMAH Supplementary Standard SB-12 Energy Efficiency For Housing 2016 update Draft for stakeholder

More information

Supplementary Standard SB-12. Energy Efficiency For Housing

Supplementary Standard SB-12. Energy Efficiency For Housing OBC Excerpt: SB 12 Ministry of Municipal Affairs and Housing Building and Development Branch 2006 Building Code - Supplementary Standards Supplementary Standard SB-12 Energy Efficiency For Housing November

More information

Thermal Performance of Nvelope NV1 Clip System

Thermal Performance of Nvelope NV1 Clip System Report Number: 5140108.00 April 30, 2015 Thermal Performance of Nvelope NV1 Clip System Presented to: Nvelope USA, LLC 16904 164 th Way S.E. Renton, WA 98058 Morrison Hershfield Suite 310, 4321 Still Creek

More information

IECC Residential Significant Changes Summary. Tier I

IECC Residential Significant Changes Summary. Tier I 2009-2015 IECC Residential Significant Changes Summary Tier I R401.2 Compliance options for compliance are now prescriptive path, Total UA (which is part of prescriptive), Performance and the new Energy

More information

Welcome to this con-nuing educa-on seminar. This is the second of two parts of the High-Performance Building series.

Welcome to this con-nuing educa-on seminar. This is the second of two parts of the High-Performance Building series. Welcome to this con-nuing educa-on seminar. This is the second of two parts of the High-Performance Building series. 1 3 6 7 8 A building enclosure s basic function is to separate the outside from the

More information

780 CMR: 9 th Edition Massachusetts State Building Code. Presented to: BSA Codes Committee. DATE: January 20, 2016

780 CMR: 9 th Edition Massachusetts State Building Code. Presented to: BSA Codes Committee. DATE: January 20, 2016 780 CMR: 9 th Edition Massachusetts State Building Code Presented to: BSA Codes Committee DATE: January 20, 2016 This course is registered with AIA CES for continuing professional education. Credit(s)

More information

Optimizing Energy Efficiency During Integrated Design: A Whitehorse Case Study

Optimizing Energy Efficiency During Integrated Design: A Whitehorse Case Study Optimizing Energy Efficiency During Integrated Design: A Whitehorse Case Study Northern Energy Solutions Conference 17 February 2010 Curt Hepting, P.Eng., P.E. EnerSys Analytics Inc. 1 Introduction Cost-effective

More information

Window Standards Compared:

Window Standards Compared: Window Standards Compared: NFRC, ISO and Passive House Ratings Brittany Hanam M.A.Sc., P.Eng. September 27, 2013 Outline North American and Passive House window rating systems Example simulation results

More information

2/17/2017. Energy Accounting & Education. Topics (Electricity) Creating Electricity

2/17/2017. Energy Accounting & Education. Topics (Electricity) Creating Electricity Energy Accounting & Education Energy Managers Kermit King School District of La Crosse John Daily School District of Holmen 1 Topics (Electricity) Creating electricity Defining degree days Customer charges

More information

PART 1 BUILDING ENVELOPE THERMAL ANALYSIS (BETA) GUIDE

PART 1 BUILDING ENVELOPE THERMAL ANALYSIS (BETA) GUIDE BUILDING ENVELOPE THERMAL ANALYSIS (BETA) GUIDE Table of Contents 1.1 OVERVIEW... 1-1 1.2 METHODOLOGY FOR DETERMINING THERMAL PERFORMANCE OF BUILDING ENVELOPE ASSEMBLIES... 1-1 1.2.1 Methodology Summary...

More information

Passive Design Solutions. Passive House The Road to Net-Zero

Passive Design Solutions. Passive House The Road to Net-Zero Passive House The Road to Net-Zero Net-Zero into the Future Net-Zero defined as producing as much energy onsite as the building uses annually. Using net-metering with the grid, so grid is acting as 100%

More information

Project Description. Projected build start date 01 Mar 2010 Projected date of occupation 01 Aug Energy target.

Project Description. Projected build start date 01 Mar 2010 Projected date of occupation 01 Aug Energy target. http://lowenergybuildings.org.uk Project name Larch House, Ebbw Vale, Wales Project summary The Larch House, designed by bere:architects, is the UKs first zero carbon (code 6), low cost, Certified Passivhaus,

More information

New energy efficiency requirements for Part 3 buildings in British Columbia

New energy efficiency requirements for Part 3 buildings in British Columbia March 2015 New energy efficiency requirements for Part 3 buildings in British Columbia Part 2: Key differences between ASHRAE 90.1-2010 and NECB 2011 by Tom-Pierre Frappé-Sénéclauze Pembina Institute tompierrefs@pembina.org

More information

Great Ocean Rd Ice Creamery

Great Ocean Rd Ice Creamery Great Ocean Rd Ice Creamery BCA Section J - JV3 Compliance Report Revision: 01 Job No: 2171 Date: 7 July 2015 ADP Consulting Pty Ltd Level 10, 10 Queens Rd, Melbourne Vic 3004 www.adpconsulting.com.au

More information

NYSERDA High Performance Development Challenge Energy Monitoring Report Hudson Passive Project

NYSERDA High Performance Development Challenge Energy Monitoring Report Hudson Passive Project NYSERDA High Performance Development Challenge Energy Monitoring Report Hudson Passive Project The participating home is a single family detached home in Hudson, NY. The house was completed and occupied

More information

THE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012

THE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012 THE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012 Compliance with the code for new residential construction, additions, and substantial remodels will

More information

Thermal Analysis of CL-TALON Cladding Support System

Thermal Analysis of CL-TALON Cladding Support System Report Number: 180181400 February 16, 2018 Thermal Analysis of CL-TALON Cladding Support System Presented to: CL-TALON 3223 Dell Ave. North Bergen, NJ 07047 Morrison Hershfield Suite 310, 4321 Still Creek

More information

Residential Energy Code Update

Residential Energy Code Update Residential Energy Code Update www.phrc.psu.edu August 28 th, 2018 Brian Wolfgang Provider # 60114115 PPP ID: 1562 Description On May 1, 2018, the PA Uniform Construction Code (PA UCC) Review and Advisory

More information

Airflow in Mid to High-rise Multi-Unit Residential Buildings

Airflow in Mid to High-rise Multi-Unit Residential Buildings Airflow in Mid to High-rise Multi-Unit Residential Buildings LORNE RICKETTS, MASC RDH BUILDING ENGINEERING LTD. VANCOUVER, BC CO-AUTHORS: GRAHAM FINCH, MASC, P.ENG. RDH BUILDING ENGINEERING LTD. DR. JOHN

More information

Step Code for Part 9 Buildings: Process and Case Studies

Step Code for Part 9 Buildings: Process and Case Studies Step Code for Part 9 Buildings: Process and Case Studies Conclusion Agenda: 1) Step Code review 2) Understanding the Step Code metrics 3) Who are/working with an Energy Advisor 4) Case study- getting a

More information

Italcementi Center for Research and Innovation

Italcementi Center for Research and Innovation Italcementi Center for Research and Innovation Bergamo, Italy LEED-NC v2.1 EAc1 A. Project Narrative (Viridian) analyzed the energy use of the proposed Italcementi Center for Research and Innovation located

More information

A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings

A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings Lorne Ricketts, MASc, EIT John Straube, PhD, P.Eng. ABSTRACT Airflow into, out of, and within buildings is a fundamental factor

More information

Energy Efficiency For Housing

Energy Efficiency For Housing Ministry of Municipal Affairs Building and Development Branch MMA Supplementary Standard SB-12 MMA Supplementary Standard SB-12 Energy Efficiency For Housing July 7, 2016 update Effective Date: July 7,

More information

PASSIVE HOUSE IN STUDENT HOUSING

PASSIVE HOUSE IN STUDENT HOUSING PASSIVE HOUSE IN STUDENT HOUSING WILLIAMS + WHEATON COLLEGE PHIUS NAPHC 2018 ARCHITECTURE PLANNING INTERIOR DESIGN VDC BRANDED ENVIRONMENTS ARCHITECTURE PLANNING INTERIOR DESIGN VDC BRANDED ENVIRONMENTS

More information