SECTION 4 - SECONDARY CONSTRUCTION OVERHEAD TABLE OF CONTENTS

Size: px
Start display at page:

Download "SECTION 4 - SECONDARY CONSTRUCTION OVERHEAD TABLE OF CONTENTS"

Transcription

1 4. GENERAL SECONDARIES & SERVICES 4.- INDIVIDUAL PHASE SECONDARY OVERHEAD LINE EXTENSIONS 4.- SECONDARY AND SERVICE CABLE SPLICES 4.- INSULATED SERVICE ENTRANCE COMPRESSION CONNECTORS POLE ATTACHMENTS POLE ATTACHMENT DEVICES 4.- MULTIPLEX SERVICE ATTACHMENTS TO POLES SECONDARIES SECONDARY SPACER INSTALLATIONS OVERHEAD TRIPLEX SECONDARIES SERVICES SERVICE ATTACHMENT METHODS O4.5- OVERHEAD SERVICE POLE TEMPORARY SERVICE POLE BILLBOARD SERVICE ENTRANCE REQUIREMENTS METHOD "A" 4.5- BILLBOARD SERVICE ENTRANCE REQUIREMENTS METHOD "B" 4.5-7/8/ CECCONI GUINN ELKINS SECTION 4 - SECONDARY CONSTRUCTION OVERHEAD TABLE OF CONTENTS 4.-A

2 GENERAL. THE NEUTRAL SHALL BE COMMON TO BOTH PRIMARY AND SECONDARY CIRCUITS ON WYE SYSTEMS. THE NEUTRAL SHALL BE MULTI-GROUNDED.. THE NEUTRAL CONDUCTOR SHALL ALWAYS BE IN THE TOP POSITION ON AN OPEN-WIRE SECONDARY CIRCUIT. SIZING OF SECONDARY CONDUCTORS WILL DEPEND ON THE AMOUNT OF LOAD, THE TYPE OF LOAD (SUCH AS MOTORS, ETC.), AND THE VOLTAGE DROP.. ALL SERVICE CONDUCTORS WILL BE OF COVERED ALUMINUM. THE REQUIRED SIZE, SHALL BE SPECIFIED BY THE ENGINEER. 4. THE SERVICE ENTRANCE LOCATION WILL BE DETERMINED BY THE COMPANY AND MUST BE AGREED TO BY THE CUSTOMER. CUSTOMER'S REQUESTS FOR NON-STANDARD LOCATIONS FREQUENTLY REQUIRE AN ADDITIONAL CHARGE. 5. FOR THREE PHASE FOUR WIRE DELTA SECONDARY CABLE AND SERVICES, THE PHASE CONDUCTOR WITH THE MOST NUMBER OF RAISED RIBS WILL BE THE HIGH (8 VOLT) PHASE. 6. USE INSULINKS OR INSTALL COVERS OVER SECONDARY CABLE OR SERVICE CABLE PHASE CONNECTORS. 7. STREETLIGHT CIRCUITS ARE TO BE CONSIDERED AS SECONDARY. 8. BEFORE CUTTING THE LACING WIRE ON AERIAL SECONDARY CABLE, BIND THE LACING WITH SEVERAL TURNS OF SCRAP LACING WIRE. 9. TO DEADEND THE PHASE CONDUCTORS OF AERIAL SECONDARY CABLE WHILE ALLOWING NEUTRAL TO CONTINUE ON, FIRST TAPE THE ENDS OF THE PHASE CONDUCTOR THEN BEND THEM BACK AND SECURE WITH SEVERAL WRAPS OF THE BINDING WIRE. COVER ENDS IF NOT IN USE. LIMIT FOR ALUMINUM CABLES NOT REQUIRING GUYING WIRE SIZE CODE NAME **SPAN LENGTH #4 DUPLEX SECONDARY #4 TRIPLEX SERVICE # TRIPLEX SERVICE #/ TRIPLEX SERVICE/SECONDARY #4/ TRIPLEX SERVICE 5/5 TRIPLEX SERVICE #/ QUADRUPLEX SECONDARY #4/ QUADRUPLEX SECONDARY 6.4/5 QUADRUPLEX SERVICE WHIPPET CRAB SOLASTER SANDCRAB LEPAS *NO CODE NAME VIATKA WALKING *NO CODE NAME 5' 5' 5' ' 5 QUADRUPLEX SERVICE *NO CODE NAME 4' * WIRE SIZE CUSTOM MADE IN FIELD ** BASED ON 5 LB. CUSTOMER MAST TENSION LIMIT AS INDICATED IN THE REQUIREMENTS FOR ELECTRIC SERVICE AND METER INSTALLATIONS MANUAL. 7' 5' 9' 6' 4' /8/ BURLISON ADCOCK SECONDARIES & SERVICES 4.- R

3 NORMAL POINT OF DELIVERY NORMAL POINT OF DELIVERY 5' 5' 5' NORMAL P.O.D. NO CHARGE NORMAL P.O.D. IS ON THE END OF THE BUILDING NEAREST THE OVERHEAD SOURCE. NO EXTRA POLE CHARGE TO NORMAL P.O.D. USING OH SECONDARY LIFT POLES WIRING BEYOND NORMAL POINT OF DELIVERY 4' NOTE: DIMENSIONS SHOWN ARE FOR ILLUSTRATIVE PURPOSES ONLY. 7' 6' POLE FEE AND PER FOOT CABLE CHARGES APPLY. CONTACT COMPANY REPRESENTATIVE FOR COSTS. 8/8/4 SIMPSON GUINN ADCOCK 5// SIMPSON SIMPSON ADCOCK 4// SIMPSON SIMPSON ELKINS 7/8/ BURLISON GUINN ELKINS INDIVIDUAL PHASE SECONDARY OVERHEAD LINE EXTENSIONS DEC DEM DEP DEF X 4.-

4 SEMI-TENSION SLEEVE INSULATED SERVICE ENTRANCE COMPRESSION CONNECTOR; SEE DWG 4.- FOR INSTALLATION INSTRUCTIONS AND CONNECTOR INFORMATION 6" 6" TRIPLEX CABLE SPLICE SEMI-TENSION SLEEVES FOR SERVICE NEUTRALS CATALOG NUMBER CONDUCTOR SIZE 56 #6 ACSR OR ALLOY 64 #4 ACSR OR ALLOY 64 # ACSR OR ALLOY 656 #4/ ACSR OR ALLOY INSULATED SERVICE ENTRANCE COMPRESSION CONNECTOR; SEE DWG 4.- FOR INSTALLATION INSTRUCTIONS AND CONNECTOR INFORMATION SEMI-TENSION SLEEVE 6" 6" 6" QUADRUPLEX CABLE SPLICE. WHEN SPLICING NEUTRAL, CUT OFF ENOUGH CONDUCTOR TO ASSURE A LOOSE WRAP OF PHASE CONDUCTORS AT SPLICE.. USE "BG" GROOVE OF BURNDY TOOL, OR EQUIVALENT TOOL WITH DIE FOR 5/8" SLEEVES. USE 84 DIE ON 4/ SLEEVE.. CLEAN CONDUCTORS BY WIRE BRUSHING. 4. FOR DETAILS OF INSULATED COMPRESSION CONNECTOR INSTALLATION SEE DWG "NEW" TRIPLEX OR QUADRUPLEX SECONDARIES AND SERVICES MAY CONTAIN A MAXIMUM OF ONE SPLICE PER SPAN. "REPAIR" TRIPLEX OR QUADRUPLEX SECONDARIES AND SERVICES MAY CONTAIN A MAXIMUM OF TWO SPLICES PER SPAN. 6. PHASE CONDUCTORS SHALL BE POSITIONED SUCH THAT CONTACT WITH THE NEUTRAL SLEEVE WILL NOT OCCUR. 7/8/ BURLISON GUINN ELKINS SECONDARY AND SERVICE CABLE SPLICES 4.-

5 NOTE STRIP LENGTH NOTE NOTE INSULATED COMPRESSION CONNECTOR SIZE TABLE PGN CN CONDUCTOR SIZE END MARKINGS END COLOR CONDUCTOR SIZE END COLOR / / / BLUE ORANGE ORANGE RED RED RED YELLOW YELLOW YELLOW I/ BLUE BLUE ORANGE BLUE ORANGE RED ORANGE RED YELLOW / YELLOW / GRAY /O /O 4/O YELLOW YELLOW PINK / 4/ 4/O BLACK PINK PINK. STRIP INSULATION ON EACH CONDUCTOR FOR LENGTH SHOWN BY ARROWS ON SIDE OF CONNECTOR, CLEAN CONDUCTOR BY WIRE BRUSHING.. INSERT CONDUCTORS THROUGH CAPS ON EACH END UNTIL THEY HIT THE CENTER STOP.. MAKE THREE COMPRESSIONS ON EACH END. ROTATE TOOL SO THAT CRIMPS DO NOT LINE UP. USE "BG" GROOVE OF BURNDY TOOL, OR EQUIVALENT TOOL WITH DIE FOR 5/8" SLEEVES. REMOVE END CAPS WHEN INSTALLED ON BARE NEUTRAL. 4. INSULATED COMPRESSION CONNECTOR IS TO BE USED FOR NON-TENSION JOINTS ONLY. NO TAPING OR ADDITIONAL INHIBITOR IS REQUIRED. SEE 4.- FOR SERVICE DROP CABLE SPLICE. 9/4/ BURLISON ADCOCK INSULATED SERVICE ENTRANCE COMPRESSION CONNECTORS 4.- R

6 INSULATOR, SECONDARY SPOOL FOR TANGENT POLE NEUTRAL SUPPORT AND OPEN-WIRE SECONDARY SUPPORT (ANGLES TO 5 DEGREES) MACRO UNIT - CU ITEM NO. COMPATIBLE UNIT NSSBC QTY REQ'D NSSBC BILL OF MATERIALS QTY CATALOG PER NUMBER CU DESCRIPTION 8 BOLT, SPOOL, 5/8 X, GALV, DUI WASHERS 547 WASHER, SQ, -/4", /6, GALV WASHER, LOCK, 5/8, COIL, DOUBLE, GALV. 8 BOLT, SPOOL, 5/8 X, GALV, DUI WASHERS 547 WASHER, SQ, -/4", /6, GALV WASHER, LOCK, 5/8, COIL, DOUBLE, GALV. ISPLC 5 INSULATOR, SPOOL, INCH INSULATOR, SECONDARY RACK FOR ANGLE POLE NEUTRAL SUPPORT AND OPEN-WIRE SECONDARY DEAD ENDS MACRO UNIT - CU/CN ITEM NO. COMPATIBLE UNIT QTY REQ'D NSSCC BILL OF MATERIALS QTY CATALOG PER NUMBER CU DESCRIPTION BOLT, MACH, SQ, 5/8- X, GALV CLEVIS, INSULATOR SPOOL, GALV, -/8" 547 WASHER, SQ, -/4", /6, GALV. ISPLC 5 INSULATOR, SPOOL, INCH. FOR FACTORY FORMED TIE INFORMATION, SEE.4-9. /8/ BURLISON ADCOCK 4// BURLISON BURLISON ELKINS 7/8/ BURLISON GUINN ELKINS REVISED BY CK'D APPR. POLE ATTACHMENT DEVICES 4.- R

7 CU ISEYENUT58C CN 8 WEDGE GRIP 4" " " DETAIL SHOWN FOR / AND SMALLER TPX AND QPX (SEE NOTE ) ON OPPOSITE SIDE FROM EXISTING SECONDARY DEADEND ON SAME SIDE AS EXISTING SECONDARY CONNECTIONS TO OPEN WIRE SECONDARIES WEDGE GRIP CU SERCLMP4ALC CN 85 CU SERCLMPNALC CN 49 CU ISEYEBOLT58C CN 6 WEDGE GRIP EYENUT DEAD END CLAMP CN " TO SERVICE TO SOURCE LIFT POLE GUYED LIFT POLE USE MINIMUM /4" GUYSTRAND AND 6" SCREW ANCHOR FOR ANGLE POLES AS NEEDED LIFT POLE ATTACHMENTS. FOR 4/ AND LARGER TPX & QPX, SUBSTITUTE STRAIGHT DEAD END CLAMP ( CN 4957) AND SALVAGED 4" STRAIN INSULATORS ( CN 98) FOR LOOP DEAD END CLAMP, AND EYEBOLT ( CN 6) FOR CLEVIS AND SPOOL.. APPLY INHIBITOR AND WIRE BRUSH ALL CONNECTIONS. USE ALUMINUM COMPRESSION CONNECTORS ON COPPER TO ALUMINUM CONNECTIONS. INSTALL CONNECTORS SO THAT ALUMINUM IS ABOVE COPPER.. POLES WITH ONLY SECONDARY CONDUCTORS WILL NOT BE EQUIPPED WITH A POLE GROUND. 4. POLES WITH METERING EQUIPMENT TO BE EQUIPPED WITH A POLE GROUND (EITHER WRAP BUTT OR TWO DRIVEN 5' GROUND RODS). 5 /8/ SIMMONS GUINN ADCOCK 4 /8/ BURLISON ADCOCK 4/7/ GUINN BURLISON ELKINS 7/8/ BURLISON GUINN ELKINS MULTIPLEX SERVICE ATTACHMENTS TO POLES 4.-6 R

8 SERVICE DROP LOCATED TO AVOID OBSTACLES OR TO CLEAR POLE FOR CLIMBING (TO BE USED ONLY WHERE SPECIFIED BY ENGINEER) SERVICE DROP FROM TRANSFORMER POLE (TO BE USED ONLY WHERE SPECIFIED BY ENGINEER) DOUBLE SERVICE DROP (TO BE USED ONLY WHERE SPECIFIED BY ENGINEER) SECONDARY SPACER 8" SPACING (CN ) " SPACING (CN 9) FOR 4/ ACSR MAXIMUM DOUBLE SERVICE BAIL CN 47. SERVICE DROP INSTALLATIONS SHALL BE APPLIED ONLY IN THOSE CASES WHERE THE ALTERNATIVE WOULD BE RELOCATING EXISTING POLES OR INSTALLING ADDITIONAL ONES TO SERVE CUSTOMERS.. SERVICE DROPS SHALL NOT BE SPECIFIED WHEN THE LOCATION IS INACCESSIBLE TO A LADDER.. INSTALLATIONS SHALL BE MADE SO THAT SAGS AND TENSIONS OF THE SECONDARY SERVICE CABLE ARE MAINTAINED FOR PROPER APPEARANCE. 4. MAXIMUM SIZE SERVICES PERMITTED FOR THIS INSTALLATION ARE 8' OF # TRIPLEX OR 6' OF #/ TRIPLEX. 5. MORE THAN ONE SERVICE PULL-OFF IN THE SAME SPAN IS NOT PERMITTED EXCEPT FOR BACK-TO-BACK SERVICES. DOUBLE TAP FOR SINGLE TAP USE SINGLE SERVICE BAIL ( CN 8) 6. SECONDARY SPACERS MAY BE INSTALLED AT APPROXIMATELY 5' INTERVALS TO PREVENT OUTAGES DUE TO SECONDARY CONDUCTORS COMING TOGETHER IN LONG SPANS. 6// BURLISON GUINN ELKINS SECONDARY SPACER INSTALLATIONS 4.4-6

9 PRIMARIES EXISTING PRI.-NEUT. SPACING PRIMARY NEUTRAL SEE DETAIL A 4" CLEAR. MIN. AT POLE TRIPLEX SECONDARY CLEARANCE " MIN. IN SPAN TELEPHONE/CATV MINIMUM CLEARANCE TO GROUND BELOW PER 9.- FINAL GRADE * GUY CLAMP PRIMARY NEUTRAL TPX BARE NEUT. TRIPLEX PHASE WIRES PRIMARY NEUT. SIZE GUY CLAMP CN 4/ AL 4574 #4 - #/ AL 59 DETAIL "A" (SEE CHART FOR SIZE & CN). THE PREFERRED METHOD IS TO INSTALL THE TRIPLEX BENEATH THE PRIMARY NEUTRAL, CLEAR-SPANNING FROM POLE TO POLE.. THE TRIPLEX AT ITS LOWEST POINT MUST BE AT LEAST " ABOVE THE TELEPHONE/CATV LINES BELOW. IF THERE ARE NO TELEPHONE/CATV LINES, THE TRIPLEX AT ITS LOWEST POINT MUST HAVE THE APPROPRIATE MINIMUM GROUND CLEARANCE GIVEN BY.-.. IF THE SAG OF THE TRIPLEX ENCROACHES THE MINIMUM CLEARANCE TO THE TELEPHONE/CATV LINES OR GROUND BELOW, THE TRIPLEX SHOULD BE ATTACHED TO THE PRIMARY NEUTRAL, AS SHOWN IN DETAIL A ABOVE, AS OFTEN AS NECESSARY TO ACHIEVE THE REQUIRED MINIMUM CLEARANCES. 4. ONLY # AND #4 TRIPLEX MAY BE ATTACHED TO THE PRIMARY NEUTRAL FOR ITS SUPPORT. THE LARGER SIZE TRIPLEXES MUST BE CLEAR-SPANNED BETWEEN POLES AND NOT SUPPORTED BY THE PRIMARY NEUTRAL. 8/6/4 EANES EANES ADCOCK 7/8/ BURLISON GUINN ELKINS OVERHEAD TRIPLEX SECONDARIES DEC DEM DEP DEF X 4.4-8

10 HOUSE BRACKETS FASCIA HOUSE BRACKET CN. HOUSE BRACKETS MUST BE INSTALLED IN STUDS (" X 4") OR EQUIVALENT SUPPORT. CUSTOMER'S GUY WIRE OR BRACE SERVICE MAST STEEL CONDUIT ONLY FASCIA MAST BRACKET /4" - /" CU SDEMASTCLMPSMC CN 67 " - 4" CU SDEMASTCLMPLGC CN 58. SERVICE MAST SHALL BE OF ADEQUATE STRENGTH OR BE SUPPORTED BY A GUY OR BRACE TO WITHSTAND A MAXMIUM TENSION FORCE OF 5 LBS. IMPOSED BY SERVICE DROP.. " RIGID STEEL CONDUIT IS REQUIRED FOR MASTS UP TO 4'. LONGER MAST HEIGHTS REQUIRE GUYING, BRACING, LARGER MAST SIZE OR SPECIAL SAG.. DRIP LOOPS SHALL BE FORMED ON SERVICE DROP SERVICE ENTRANCE CONDUCTORS.. THE CONNECTIONS OF THE SERVICE DROP CONDUCTORS TO THE SERVICE ENTRANCE CONDUCTORS SHALL BE MADE BELOW THE LEVEL OF THE SERVICE WEATHERHEAD.. SEE DWGS..- AND.- FOR SERVICE GROUND CLEARANCES AND DWGS..4-9A AND.4-9B FOR SERVICE CLEARANCES AT BUILDINGS. 4. SERVICE ENTRANCE CONNECTORS SHALL BE INSULATED PER NEC RULE THE SERVICE POINT OF ATTACHMENT SHOULD BE LOCATED BELOW THE LEVEL OF THE WEATHERHEAD OR GOOSENECK. IF THIS IS IMPRACTICAL, THE POINT OF ATTACHMENT MUST BE LOCATED WITHIN 4" OF THE WEATHERHEAD OR GOOSENECK (REF. NEC -54C). 6. CUSTOMER IS RESPONSIBLE FOR PROVIDING AN ATTACHMENT POINT FOR MASONRY AND STEEL BUILDINGS. 7. SEE 4.-6 FOR SERVICE CLAMP COMPATIBLE UNITS. 8/6/4 EANES EANES ADCOCK /8/ BURLISON ADCOCK 7/8/ BURLISON GUINN ELKINS REVISED BY CK'D APPR. SERVICE ATTACHMENT METHODS DEC DEM DEP DEF X 4.5-

11 4" MIN. SECURE TO POLE USING HOUSE BRACKET SCREW OR DRIVE HOOK SCREW MOUNTED IN THE SIDE OF POLE. DO NOT ATTACH TO TOP OF POLE. POLE OPTION A NOT TO SCALE BACKFILL WITH SOIL AND TAMP IN 6" LAYERS. HOLE DIAMETER SHALL BE JUST WIDE ENOUGH TO ALLOW TAMPING. 4'-7" POINT OF DELIVERY 5'-5" OPTION B NOT TO SCALE METER SOCKET (SEE NOTE ) POLE CONCRETE 6' BACKFILL WITH CONCRETE IN A 5" (MIN.) DIAMETER HOLE. '-" TO 5'-6" CUSTOMER'S EQUIPMENT (SEE NOTE B) CUSTOMER'S POLE (SEE NOTE A) '-6" MIN. ANYWHERE IN THE SPAN (8' MIN. IF OVER ROADS OR AREAS SUBJECT TO VEHICULAR TRAFFIC) POLE /4", 7-STRAND GUY (MIN.) 4' DEPTH 6' OPTION C NOT TO SCALE 4' DEPTH BACKFILL WITH SOIL AND TAMP IN 6" LAYERS. HOLE DIAMETER SHALL BE JUST WIDE ENOUGH TO ALLOW TAMPING. GUY AND ANCHOR INSTALLATION MUST BE APPROVED BY LOCAL ENGINEER. 4" SCREW ANCHOR MINIMUM GROUNDING ELECTRODE PER N.E.C.. OWNER PROVIDE AND INSTALL A. A ' CLASS 9 SOUTHERN YELLOW PINE (SYP) POLE OR A 6" X 6" SYP POST THAT IS PROPERLY TREATED WITH A WOOD PRESERVATIVE FOR EARTH CONTACT. SET POLE IN ACCORDANCE WITH OPTION A, B OR C. B. SERVICE ENTRANCE TO BE GROUNDED IN ACCORDANCE WITH N.E.C.. OWNER WILL INSTALL A. METER SOCKET IN ACCORDANCE WITH N.E.C.. SETTING DEPTHS FOR THE THREE OPTIONS ARE FOR 5 LB. ICE TENSIONS. 4. THIS DRAWING MAY BE USED FOR VARIOUS TYPES OF OVERHEAD SERVICES: A. OVERHEAD MOBILE HOME SERVICES B. NON-RESIDENTIAL SERVICES 8// SIMPSON SIMPSON ADCOCK /8/ SIMPSON SIMPSON ELKINS 7/8/ BURLISON GUINN ELKINS OVERHEAD SERVICE POLE 4.5-6

12 . ALL DIMENSIONS SHOWN ARE MINIMUM.. MINIMUM ' POLE REQUIRED. TALLER MAY BE NEEDED TO MEET SERVICE SAG REQUIREMENTS. MINIMUM 6' POLE ALLOWED IF SET WITHIN ' OF SOURCE COMPANY POLE.. ONE BRACE TO BE IN DIRECTION OF SERVICE. AT LEAST ONE ADDITIONAL BRACE TO BE LOCATED AT 9 TO DIRECTION OF SERVICE. 4. SOIL TO BE FIRMLY TAMPED AROUND POLE AND STAKES DRIVEN INTO FIRM EARTH. 5. CUSTOMER FURNISHES ALL ITEMS EXCEPT METER. THE METER BASE, WIRING, EQUIPMENT SERVICE EQUIPMENT GROUND ON THE POLE ARE TO BE INSTALLED BY THE CUSTOMER'S ELECTRICIAN IN ACCORDANCE WITH THE N.E.C AND LOCAL ORDINANCES. 6. SOLID, ONE PIECE, 4" X 4" WOOD POST MAY BE SUBSTITUTED WITH ENGINEER'S APPROVAL. 7. SERVICES SHALL NOT BE RUN TO TEMPORARY POLES NOT MEETING THE REQUIREMENTS SET FORTH HEREIN WITHOUT APPROVAL OF THE LOCAL ENGINEER ON SPECIFIC CASES. 8. HOUSE BRACKET MOUNTING LOCATION SHALL BE IN THE SIDE OF THE SERVICE POLE NOT IN THE TOP. 9. IF THE 4 FOOT MINIMUM DEPTH CANNOT BE OBTAINED DUE TO ROCK, TWO ADDITIONAL BRACES 9 DEGREES TO THE BRACES SHOWN MUST BE INSTALLED (FOUR BRACES TOTAL). IN NO CIRCUMSTANCES SHOULD THE EMBEDMENT DEPTH BE LESS THAN FEET. 8' '-" TO 5'-6" TREATED WOOD POLE WITH MIN. DIAMETER OF 4" '-6" MINIMUM ANYWHERE IN SPAN (8'-" MINIMUM IF OVER ROADS OR AREAS SUBJECT TO VEHICULAR TRAFFIC) WEATHERPROOF SWITCH BOX " X 4" BRACE GROUND WIRE 9 ALTERNATE BRACE LOCATION 9 FROM DIRECTION OF SERVICE 9 SEE NOTE PLAN VIEW DIRECTION OF SERVICE " X 4" BRACE GROUNDING ELECTRODE PER N.E.C. 6' 4' MIN. ' MIN. 6' ' MIN. SEE NOTE 9 " X 4" STAKES //4 SIMPSON GUINN ADCOCK 8// SIMPSON SIMPSON ADCOCK 4// SIMPSON SIMPSON ELKINS 6// BURLISON GUINN ELKINS TEMPORARY SERVICE POLE DEC DEM DEP DEF X 4.5-8

13 CATWALKS BILLBOARDS LADDER LOCATION LADDER LOCATION NO COMPANY SERVICE SHALL BE ATTACHED TO ANY PART OF THE CATWALKS SERVICE MASTHEAD AND RISER ' EXTENSION BRACKET (SUPPLIED BY CUSTOMER) ' MAX. COMPANY SERVICE WIRE ENTRANCE TO BE SPOTTED BY COMPANY ENGINEER PLAN VIEW BILLBOARD MASTHEAD COMPANY SERVICE WIRE ' EXTENSION BRACKET MUST PROVIDE REQUIRED SERVICE DROP CLEARANCES LADDER LOCATION SERVICE RISER SEE.- AND.- METER AND BASE FINAL GRADE '-" TO 5'-6" MT.HT. ELEVATION NOTE:. DO NOT PROVIDE SERVICE TO SIGN WHICH DOES NOT HAVE CLEARANCES FROM ADJACENT OVERHEAD CONDUCTORS AS REQUIRED BY N.E.S.C. AND ANY ADDITIONAL COMPANY SPECIFICATIONS. 8/6/4 EANES EANES ADCOCK 4// SIMPSON SIMPSON ELKINS 7/8/ BURLISON GUINN ELKINS BILLBOARD SERVICE ENTRANCE REQUIREMENTS METHOD "A" DEC DEM DEP DEF X 4.5-

14 BILLBOARD ' MIN. COMPANY SERVICE WIRE LADDER LOCATION SEE DWGS..- AND.- SERVICE RISER '-" TO 5'-6" MT. HT. METER AND BASE FINAL GRADE ELEVATION COMPANY SERVICE WIRE ' MIN. SERVICE RISER AND MASTHEAD STEEL POLE NO PART OF COMPANY SERVICE WIRE WILL BE RUN WITHIN ' OF LADDER OVERHEAD SERVICE WIRE MAY BE LOCATED ANYWHERE IN THIS AREA. CALL LOCAL COMPANY OFFICE FOR SERVICE ENTRANCE SPOTTING. ' MIN. PLAN VIEW 8/6/4 EANES EANES ADCOCK BILLBOARD SERVICE ENTRANCE REQUIREMENTS METHOD "B" DEC DEM DEP DEF X O 7/8/ BURLISON GUINN ELKINS 4.5-

04.00 GENERAL SECONDARIES & SERVICES SECONDARY AND SERVICE CABLE SPLICES INSULATED SERVICE ENTRANCE COMPRESSION CONNECTORS 04.

04.00 GENERAL SECONDARIES & SERVICES SECONDARY AND SERVICE CABLE SPLICES INSULATED SERVICE ENTRANCE COMPRESSION CONNECTORS 04. 4. GENERAL SECONDARIES & SERVICES 4.- TIE COLOR CODING 4.-6 SECONDARY AND SERVICE CABLE SPLICES 4.- INSULATED SERVICE ENTRANCE COMPRESSION CONNECTORS 4.- 4. POLE ATTACHMENTS POLE ATTACHMENT DEVICES NEUTRAL

More information

RESIDENTIAL QUICK REFERENCE

RESIDENTIAL QUICK REFERENCE RESIDENTIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information

OVERHEAD SERVICES - SECONDARY

OVERHEAD SERVICES - SECONDARY OVERHEAD SERVICES - SECONDARY Contents - Overhead Services... O-1 General Requirements for Overhead Service... O-2 Names of Parts for Overhead Service... O-3 Service Attachment on an Unguyed Service Mast...

More information

OVERHEAD SERVICE. Table of Contents - Section 400

OVERHEAD SERVICE. Table of Contents - Section 400 OVERHEAD SERVICE Table of Contents - Section 400 PARAGRAPH 400.0 OVERHEAD SERVICES (0-600 VOLTS)... 1 400.1 GENERAL 1 400.2 IDENTIFICATION OF CONDUCTORS. 1 400.3 MAXIMUM SERVICE ENTRANCE CONDUCTOR SIZE

More information

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).

OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE). 6.01 GENERAL OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE See Chapter 3, Section 3.01 for more information about point of entrance (POE). In all cases, the customer installs, owns, and maintains the

More information

Specifications for Residential Overhead Electric Service Installation

Specifications for Residential Overhead Electric Service Installation Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be

More information

Electric Service Handbook

Electric Service Handbook Electric Service Handbook Revised August 2017 Contact Information Telephone (253): Electrical Inspection Office 502-8277 7:30 am - 4:30 pm Electrical Inspectors Area Map on Website 7:30 am - 8:30 am Automated

More information

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL WARNING Before digging or trenching... Call 811 Indiana Underground Protection Service 1-800-382-5544 AVOID BURIED POWER CABLES 4901 East Park 30 Drive P.O.

More information

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O.

Effective June, Eaton-Durham Model # UTRS223ACH. Siemens, Model # SUAS877-PG. (or Landis & Gyr # UAS877-PG) Milbank. Model # U1980-O. Siemens, Model # SUAS877-PG (or Landis & Gyr # UAS877-PG) Eaton-Durham Model # UTRS223ACH Milbank Midwest Model # U980-O UTRS223AMEP These are some examples of the single meter sockets we require for underground

More information

TEMPORARY FACILITIES

TEMPORARY FACILITIES MUNICIPAL LIGHT & POWER & CHUGACH ELECTRIC ASSOCIATION ELECTRIC SERVICE REQUIREMENTS EXCERPT TEMPORARY FACILITIES 2015 EDITION Effective August 3, 2015 This is an EXCERPT; the complete book is available

More information

ELECTRICAL SERVICE UPGRADE RESIDENTIAL AND COMMERCIAL QUICK INFORMATION REFERENCE

ELECTRICAL SERVICE UPGRADE RESIDENTIAL AND COMMERCIAL QUICK INFORMATION REFERENCE ELECTRICAL SERVICE UPGRADE RESIDENTIAL AND COMMERCIAL QUICK INFORMATION REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2015 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION.

More information

Specifications for Residential Overhead Electric Service Installation

Specifications for Residential Overhead Electric Service Installation Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be

More information

Building Attachments and Services

Building Attachments and Services Part Four. Other Electrical Procedures CHAPTER 11 Building Attachments and Services All electrical energy supplied to power-consuming devices and appliances within a building must pass through the electrical

More information

GENERAL NOTES PEDERNALES ELECTRIC COOPERATIVE, INC. RESIDENTIAL AND COMMERCIAL AMP METER LOOP SPECIFICATIONS

GENERAL NOTES PEDERNALES ELECTRIC COOPERATIVE, INC. RESIDENTIAL AND COMMERCIAL AMP METER LOOP SPECIFICATIONS GENERAL NOTES 1. Residential and commercial meter loops are typically used when constructing facilities for permanent service. It is important that all guidelines outlined in this document be followed

More information

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6.2 OVERHEAD SERVICES Wiring of any premises for connection

More information

Grant PUD. Joint Use Standards. For Pole Attachments including: Cable Television Fiber Optics Telecommunications

Grant PUD. Joint Use Standards. For Pole Attachments including: Cable Television Fiber Optics Telecommunications Grant PUD Joint Use Standards For Pole Attachments including: Cable Television Fiber Optics Telecommunications REVISED: July 25, 2018 INTRODUCTION AND OVERVIEW The information contained in these Joint

More information

(Condensed from National Electric Code)

(Condensed from National Electric Code) WIRING, SPECIFICATIONS, INSPECTION, AND METER INSTALLATION PROCEDURES FOR RESIDENTIAL CUSTOMERS SERVED BY SOUTHWEST ARKANSAS ELECTRIC COOPERATIVE CORPORATION Effective April 1, 1974 Revised February 3,

More information

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS Greenbook Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 08-15-17 Rev. #06:

More information

ANY SPECIFICATION DRAWINGS OR DATED PRIOR TO SEPTEMBER 2015 WILL NOT BE HONORED.

ANY SPECIFICATION DRAWINGS OR DATED PRIOR TO SEPTEMBER 2015 WILL NOT BE HONORED. November 30, 2015 Dear STEMC Member and Contractors, Over the years, STEMC has made many changes to its member requirements for new services and specifications associated with those requirements. As a

More information

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance.

SERVICE ENTRANCES. OPPD S Electrical Service Designer (ESD) shall designate the Point Of Entrance. SERVICE ENTRANCES 3.01 POINT OF ENTRANCE General Service The customer, or the customer s electrician, should provide OPPD with a site plan, load schedule, and voltage requirements when requesting service.

More information

New Construction Units. a. Includes the furnishing of all labor and equipment for the installation of new construction units.

New Construction Units. a. Includes the furnishing of all labor and equipment for the installation of new construction units. 1 All construction is to follow design and construction documents approved by the Engineer and marked approved for construction. All construction shall also follow the National Electrical Safety Code,

More information

ORDINANCE NO NOW, THEREFORE, BE IT ENACTED BY THE CITY COUNCIL OF THE CITY OF FAIRBANKS, ALASKA, as follows:

ORDINANCE NO NOW, THEREFORE, BE IT ENACTED BY THE CITY COUNCIL OF THE CITY OF FAIRBANKS, ALASKA, as follows: Introduced by: Mayor Eberhart Date: May 23, 2016 ORDINANCE NO. 6013 AN ORDINANCE TO AMEND FGC CHAPTER 10, ARTICLE IX NATIONAL ELECTRICAL CODE, BY ADOPTING THE 2014 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS

More information

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.

6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6.2 OVERHEAD SERVICES Wiring of any premises for connection

More information

UNITED COOPERATIVE SERVICES. SPECIFICATIONS FOR SELF-CONTAINED METER INSTALLATIONS August 2014

UNITED COOPERATIVE SERVICES. SPECIFICATIONS FOR SELF-CONTAINED METER INSTALLATIONS August 2014 UNITED COOPERATIVE SERVICES SPECIFICATIONS FOR SELF-CONTAINED METER INSTALLATIONS August 2014 A member may obtain a new, single phase service from the Cooperative by providing or purchasing a meter loop.

More information

PRIMARY LINE EXTENSION

PRIMARY LINE EXTENSION PRIMARY LINE EXTENSION Installation of new electric service to an empty parcel/lot or extending a transformer to within 150' of proposed meter location. This includes installing a permanent branch, addition,

More information

TEMPORARY METER POLE INSTALLATION

TEMPORARY METER POLE INSTALLATION TEMPARY METER POLE INSTALLATION MEMBER PROVIDED Location to be made by REMC within 50' of our transformer or existing service Temporary pole to be properly braced 24" 3 wire weatherhead (located 24" from

More information

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL

UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL 8.01 GENERAL This material is not intended to cover service from OPPD s network in the downtown Omaha area. See Chapter 12 for details

More information

An altered service that is moved, upgraded (ex., 200 to 400 amp) or changed to meet today's standards for electric service.

An altered service that is moved, upgraded (ex., 200 to 400 amp) or changed to meet today's standards for electric service. ALTERED SERVICE An altered service that is moved, upgraded (ex., 200 to 400 amp) or changed to meet today's standards for electric service. Customer Responsibilities Provide, install and maintain all required

More information

[Type text] Heber Light & Power. Developers & Excavators. Electrical Service Requirements Manual

[Type text] Heber Light & Power. Developers & Excavators. Electrical Service Requirements Manual [Type text] Heber Light & Power Developers & Excavators Electrical Service Requirements Manual May 2017 E.1.1 - GENERAL REQUIREMENTS PURPOSE This section was prepared to aid developers, contractors, engineers

More information

Unit Price Labor. INSTALL 138KV DISCONNECT SWITCH WITH MOTOR OPERATOR AND AUXILIARY SWITCHES ON EXISTING STRUCTURE 1 ea.

Unit Price Labor. INSTALL 138KV DISCONNECT SWITCH WITH MOTOR OPERATOR AND AUXILIARY SWITCHES ON EXISTING STRUCTURE 1 ea. SUBSTATION B UPGRADE CONSTRUCTION MAJOR MATERIAL NOTES: Contractor to fill in line item column "Est. Qty." for items left blank. Construction Unit No. Description Est. Qty. Unit Labor 100 INSTALL 138KV

More information

Section 7: Specifications

Section 7: Specifications Section 7: Specifications 29 31 Building Boundary of Clear Area See Note # 1 8' Shrubs 8' Concrete Pad Equipment 8' TRAVELED WAY M Meter Pedestal 8' Curb Protective Vehicle Posts (Bollards) If Required

More information

Metering Installations for Mobile Homes or Mobile Home Parks:

Metering Installations for Mobile Homes or Mobile Home Parks: Metering Installations for Mobile Homes or Mobile Home Parks: Overhead Installations The metering pole must be a minimum of 17 ft, Class 5 pole set at least 4 ft deep so that it will be of sufficient height

More information

GUY-GRIP Dead-end NOMENCLATURE GENERAL INFORMATION SAFETY CONSIDERATIONS

GUY-GRIP Dead-end NOMENCLATURE GENERAL INFORMATION SAFETY CONSIDERATIONS GUY-GRIP Dead-end NOMENCLATURE Please visit our web site at www.preformed.com for additional literature.guy-grip Dead-end Application Procedure - SP2045 Cross-over Marks: (A) Indicate starting point for

More information

Duke Energy Carolinas Distribution Construction Standards Reference Guide

Duke Energy Carolinas Distribution Construction Standards Reference Guide Duke Energy Carolinas Distribution Construction Standards Reference Guide The Duke Energy Carolinas (DEC) Distribution Construction Standards are available on the My Duke Energy Contractor Portal. Access

More information

GUY-GRIP Dead-end NOMENCLATURE GENERAL INFORMATION SAFETY CONSIDERATIONS

GUY-GRIP Dead-end NOMENCLATURE GENERAL INFORMATION SAFETY CONSIDERATIONS GUY-GRIP Dead-end NOMENCLATURE Tower Products, Dead-end and Dead-end Accessories: Section 1 Please visit our web site at www.preformed.com for additional literature.guy-grip Dead-end Application Procedure

More information

STANDARD TECHNIQUE: OH4K/1

STANDARD TECHNIQUE: OH4K/1 Company Directive STANDARD TECHNIQUE: OH4K/1 Relating to the Design of Insulated Aerial Bundle Conductor For LV Overhead Distribution Systems ST:OH4K/1 13 September 2007-1 of 35 - Document Revision & Review

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

Please check with your local inspection authority for any additional requirements before installation.

Please check with your local inspection authority for any additional requirements before installation. Specifications for Residential Underground Electric Service Installation This brochure addresses most typical residential underground service installations. Variances for the following specifications must

More information

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL

NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL NORTHEASTERN REMC ELECTRIC STANDARDS MANUAL WARNING Before digging or trenching... Call Indiana Underground Protection Service 1-800-382-5544 AVOID BURIED POWER CABLES CONTENTS Page # 100-200 OR 400 AMP

More information

CHAPTER 13 GROUNDING AND BONDING

CHAPTER 13 GROUNDING AND BONDING GROUNDING AND BONDING CHAPTER 13 GROUNDING AND BONDING Grounding and bonding must be in accordance with Article 250 of the National Electrical Code (NEC). Bonding is defined in the NEC as the permanent

More information

Basic Service. This Section provides information regarding a. Introduction

Basic Service. This Section provides information regarding a. Introduction Basic Service Introduction This Section provides information regarding a new electric Basic Service for a single phase service less than or equal to 400 amps, and a three phase service less than 50kW.

More information

SECTION GROUNDING

SECTION GROUNDING SECTION 16450 GROUNDING PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies general grounding and bonding requirements of electrical and telecommunication installations for personnel safety, equipment

More information

Central Lincoln PUD Single-Family Residential Guidelines & Standards April 21, 2017

Central Lincoln PUD Single-Family Residential Guidelines & Standards April 21, 2017 Central Lincoln PUD Single-Family Residential Guidelines & Standards April 21, 2017 Overview of Hook-Up Procedures: The following is a general outline of how you get a new electrical service for a single-family

More information

Cutouts and Fuse Links Equipment to protect against faults and over-current conditions on power distribution systems. Open-Type Cutouts Linkbreak Cutouts Loadbreak Cutouts Cutout-Arrester Combinations

More information

WIRING RULES AND REGULATIONS OF TOMBIGBEE ELECTRIC POWER ASSOCIATION

WIRING RULES AND REGULATIONS OF TOMBIGBEE ELECTRIC POWER ASSOCIATION WIRING RULES AND REGULATIONS OF TOMBIGBEE ELECTRIC POWER ASSOCIATION The following rules and information are issued to make it possible for anyone engaged in electrical wiring or installation of electrical

More information

SECTION 410 FENCES All materials shall be new and without flaws or defects of any type GENERAL

SECTION 410 FENCES All materials shall be new and without flaws or defects of any type GENERAL SECTION 410 FENCES 410.1 GENERAL This work shall consist of the construction of fences and gates in substantial compliance with the specifications, lines, and grades shown on the plans or established by

More information

Chapter ELECTRICAL CODE*

Chapter ELECTRICAL CODE* Chapter 19.08 ELECTRICAL CODE* 19.08.010 National Electrical Code (NEC) adopted. 19.08.100(1) Definitions, general. 19.08.210.5 Identification for branch circuits. 19.08.210.11(C) Branch circuits required;

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract apply to this Section. 1.2 SUMMARY A. This Section

More information

Chapter ELECTRICAL CODE

Chapter ELECTRICAL CODE Chapter 19.08 ELECTRICAL CODE 19.08.010 National Electrical Code (NEC) adopted. 19.08.100(1) Definitions, general. 19.08.210.5 Identification of branch circuits. 19.08.210.11(C) Branch circuits required;

More information

Central Lincoln PUD Commercial Service Guidelines & Standards

Central Lincoln PUD Commercial Service Guidelines & Standards Central Lincoln PUD Commercial Service Guidelines & Standards Overview of Hook-Up Procedures: The following is a general outline of how you get a new electrical service for commercial and other non-residential

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 PART 1 GENERAL 1.01 DESCRIPTION A. Section includes requirements for an electrical grounding system, including electrodes, grounding rods, connectors, insulators, equipment grounding and

More information

600 GROUNDING 9/12/2018

600 GROUNDING 9/12/2018 00 GOUNDING //0 C N C N,N C N,N N TN0 C TN C TN C TN Installation of Grounding Assemblies Basic Units - Grounding Basic Units - Copperweld Grounding - Pole Ground epair Static Wire History/Policy Static

More information

Revisions for the 2015 Edition of the "Specifications and Requirements for Electric Installations (Bluebook)"

Revisions for the 2015 Edition of the Specifications and Requirements for Electric Installations (Bluebook) Revisions for the 2015 Edition of the "Specifications and for Electric Installations (Bluebook)" PAGE NUMBER OF 2015 EDITION Front Cover Front Cover i i PAGE NUMBER OF 2007 EDITION Front Cover Front Cover

More information

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11

Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (URD) Index General Discussion... 1-2 Description... 3-7 Drawings (Available

More information

UNDERGROUND SERVICES SECONDARY

UNDERGROUND SERVICES SECONDARY Reference UNDERGROUND SERVICES SECONDARY Underground services secondary... U- 1 General requirements for underground service... U- 2 Name of parts for underground service... U- 3 Conduit layouts... U-

More information

Transmission Line General Requirements Including Typical Overhead Line Structures. Document Number: 1-03-FR-09

Transmission Line General Requirements Including Typical Overhead Line Structures. Document Number: 1-03-FR-09 Transmission Line General Requirements Including Typical Overhead Line Structures Document Number: 1-03-FR-09 VERSION 1.0 June 2018 This functional requirements document is in line with the organisation's

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 16060 Grounding and Bonding This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or

More information

Manufactured decking (composite) may be used when approved by the building department

Manufactured decking (composite) may be used when approved by the building department DO YOU THINK YOU MIGHT ENCLOSE YOUR DECK IN THE FUTURE? Deck plans are approved based on the assumption that the deck will be used only as a deck for the life of the structure. Because there are so many

More information

6. Temporary Construction Service

6. Temporary Construction Service T e mp o ra ry Co n s tru c tio n Se rv ic e Section 6 Section 6 Temporary Construction Service Directory Page 6.1 General 40 6.2 Construction Criteria For Temporary Service 40 6.3 Meter Socket Requirements

More information

Kaf-Tech Product Specification

Kaf-Tech Product Specification Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519.13 METAL CLAD CABLE-LUMINARY CABLE

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. AFC Cable Systems, Inc. Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519.13 METAL CLAD CABLE-MC

More information

Electric Service Standards

Electric Service Standards V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are

More information

UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES

UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES 7.01 GENERAL UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES Also refer to Chapter 3 (Service Entrances), and Chapter 4 (Metering Installation). OPPD will install,

More information

SECTION CHAIN-LINK FENCES AND GATES 02821/1

SECTION CHAIN-LINK FENCES AND GATES 02821/1 SECTION 02821 - CHAIN-LINK FENCES AND GATES 02821/1 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Chain-Link Fences: 2. Gates: horizontal slide or swing. 3. Fences installed where

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB #

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # SECTION 26 0529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Specifications for Residential Underground Electric Service Installation

Specifications for Residential Underground Electric Service Installation Specifications for Residential Underground Electric Service Installation This brochure addresses most typical residential underground service installations. Variances for the following specifications must

More information

CONSTRUCTION SPECIFICATION FOR POLE ERECTION

CONSTRUCTION SPECIFICATION FOR POLE ERECTION ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 615 SEPTEMBER 1993 CONSTRUCTION SPECIFICATION FOR POLE ERECTION 615.01 SCOPE 615.02 REFERENCES 615.05 MATERIALS TABLE OF CONTENTS 615.05.01 Concrete.02

More information

SECTION ELECTRICAL UTILITY SERVICES

SECTION ELECTRICAL UTILITY SERVICES SECTION 33 71 73 ELECTRICAL UTILITY SERVICES PART 1 GENERAL 1.1 REFERENCES A. American Association of State Highway Officials (AASHO): 1. Standard Specifications B. California Administrative Code (CAC):

More information

Electric Service Requirements (Service Assembly Guide)

Electric Service Requirements (Service Assembly Guide) 20 Electric Service Requirements (Service Assembly Guide) TABLE OF CONTENTS INTRODUCTION... 3 ONECALL LOCATE NUMBERS... 4 SECTION 1 GENERAL INFORMATION... 5 101 PURPOSE... 5 SECTION 2 -- SERVICE... 6 201

More information

Index GROUNDING CONNECTORS. TYPE WB Ground Rod Clamps. TYPE G/SRC Ground Rod Clamps. Heavy-Duty Clamps. Standard-Duty Clamps (Universal)

Index GROUNDING CONNECTORS. TYPE WB Ground Rod Clamps. TYPE G/SRC Ground Rod Clamps. Heavy-Duty Clamps. Standard-Duty Clamps (Universal) TYPE B Ground Rod Clamps Heavy-Duty Clamps GROUNDING CONNECTORS R30117 For direct burial. For connecting ground wire to driven rod. Designed to maintain proper alignment between ground wire and rod. Cast

More information

ENGINEERS ESTIMATE MARYLAND STATE HIGHWAY ADMINISTRATION

ENGINEERS ESTIMATE MARYLAND STATE HIGHWAY ADMINISTRATION ENGINEERS ESTIMATE The Engineer s Estimate is an important part of the overall design process. It is a determination of the construction costs for any given project. The estimate is then used for programming

More information

Residential Electric Policy

Residential Electric Policy Residential Electric Policy 7/19/16 1 Table of Contents General Information..3 Construction.3 Ownership....3 Underground Service...3 Apartments/Multi-Unit Dwellings..3 Modular and Manufactured Homes...3

More information

WOOD POLE SPAN WIRE SIGNAL SYSTEMS

WOOD POLE SPAN WIRE SIGNAL SYSTEMS 7 A wood pole span wire traffic control signal system differs from a mast arm steel pole traffic control signal system in that it uses wood poles and span wires to place the signal indications in the driver

More information

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION

SECTION 1101 TRAFFIC SIGNALS AND APPURTENANCES END OF SECTION SECTION 1101 SIGNALS AND APPURTENANCES PART 1 GENERAL 1.4 SUBMITTALS E. Submit warranty for all supplied material and workmanship for a period of two years from final acceptance. The warranty must state

More information

The Official Meter Manual of JCREMC. Created by the Engineering Dept.

The Official Meter Manual of JCREMC. Created by the Engineering Dept. The Official Meter Manual of JCREMC Created by the Engineering Dept. 1 This copy of the revised Electric Service and Meter Manual is provided to you for your use in the layout and installation of electrical

More information

SECTION OUTLET, PULL, AND JUNCTION BOXES

SECTION OUTLET, PULL, AND JUNCTION BOXES SECTION 16131 OUTLET, PULL, AND JUNCTION BOXES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16112 - Raceways and Conduits. 1.02 SYSTEM DESCRIPTION A. Performance Requirements:

More information

A. Product Data shall be provided for each type of product indicated.

A. Product Data shall be provided for each type of product indicated. 32 31 13 CHAIN LINK FENCES AND GATES SECTION 1 GENERAL 1.1 SUMMARY This Section includes the following: 1. Chain Link Fences 2. Gates for Chain Link Fences. See electrical specifications for electrical

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Commercial Electric Policy

Commercial Electric Policy Commercial Electric Policy 7/19/16 1 Table of Contents General Information..3 Construction.3 Ownership.3 Underground Primary/Service....3 Multi-Unit/Multi-Service Buildings....3 Secondary Termination Enclosures.4

More information

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION SECTION 74 AIRPORT OBSTRUCTION LIGHTS (FAA L-119) 74-1 GENERAL The Contractor shall perform all work required by the plans and specifications for construction of obstruction lights in accordance with the

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Updated format, division title, and removed references to other sections. - mgl44 A. Summary This section contains design criteria for the

More information

Post Office Box 500 Carson, WA Phone (509) Fax (509) Toll Free (800)

Post Office Box 500 Carson, WA Phone (509) Fax (509) Toll Free (800) Public Utility District No. 1 of Skamania County Post Office Box 500 Carson, WA 98610 Phone (509) 427-5126 Fax (509) 427-8416 Toll Free (800) 922-5329 ELECTRIC LINE EXTENSION If you are purchasing property

More information

REA LISTED. Throughout the catalog you will notice blue highlighted items. These are the most frequently ordered BURNDY Products.

REA LISTED. Throughout the catalog you will notice blue highlighted items. These are the most frequently ordered BURNDY Products. Grounding BURNDY Products E-44 TYPE GRC HIGH STRENGTH GROUND ROD CLAMP For Copper Cable to Rod High copper alloy ground connector for joining a range of cable to copper clad, galvanized steel, and stainless

More information

TOWER & ANTENNA Product Catalog

TOWER & ANTENNA Product Catalog TOWER & ANTENNA Product Looking for Reliable Solutions to your Communications Network Needs? COMMUNICATIONS Product Fiber Optic, Copper, Demarcation, Bonding, Strand and Cable Solutions for the Communications

More information

TS 804 CABLES TABLE OF CONTENTS TRAFFIC SIGNAL EQUIPMENT POLE WIRING DIAGRAM LOCATIONS WITH CENTRE MEDIANS

TS 804 CABLES TABLE OF CONTENTS TRAFFIC SIGNAL EQUIPMENT POLE WIRING DIAGRAM LOCATIONS WITH CENTRE MEDIANS TORONTO TRANSPORTATION January 2012 TS 804 CABLES TABLE OF CONTENTS 1. DRAWINGS TTD 804.001 TTD 804.002 TTD 804.003 TTD 804.005 TTD 804.006 TTD 804.007 TTD 804.010 TTD 804.015 TTD 804.020 TTD 804.025 TTD

More information

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE ONTARIO PROVINCIAL STANDARD SPECIFICATION OPSS.PROV 604 NOVEMBER 2017 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

SECTION FACILITY LIGHTNING PROTECTION

SECTION FACILITY LIGHTNING PROTECTION PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 41 00 FACILITY LIGHTNING PROTECTION SPEC WRITER NOTE: Delete between //----//if not applicable to project. Also delete any other item or paragraph not applicable

More information

STREET LIGHTING GENERAL INFORMATION

STREET LIGHTING GENERAL INFORMATION SECTION 1102 STREET LIGHTING GENERAL INFORMATION These specifications are for street lighting that is to be dedicated to the public and maintained by the City of Meridian. Such installations require a

More information

Serv. Low-Voltage Cable Insulated Conductors for Overhead and Underground Distribution

Serv. Low-Voltage Cable Insulated Conductors for Overhead and Underground Distribution Serv Low-Voltage Cable Insulated Conductors for Overhead and Underground Distribution General Cable offers a complete line of insulated cable designs and sizes to meet utility requirements for exceptional

More information

A. Section includes busway and fittings including plug-in units.

A. Section includes busway and fittings including plug-in units. SECTION 26 25 00 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes busway and fittings including plug-in units. 1.2 REFERENCES A. Institute of Electrical and Electronics Engineers:

More information

SERVICES CHAPTER 35. wire. For all other installations, the rating of the ungrounded conductors shall be not less than 60 amperes.

SERVICES CHAPTER 35. wire. For all other installations, the rating of the ungrounded conductors shall be not less than 60 amperes. CHAPTER 35 SERVICES SECTION E3501 GENERAL SERVICES E3501.1 Scope. This chapter covers service conductors and equipment for the control and protection of services and their installation requirements. E3501.2

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 604 NOVEMBER 2004 CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

Section 4 Underground Service

Section 4 Underground Service Table of Contents Section 4 Underground Service A. GENERAL... 4-7 B. PRIMARY SERVICE - RESIDENTIAL SYSTEMS ON PRIVATE PROPERTY... 4-7 C PRIMARY SERVICE - COMMERCIAL SYSTEMS ON PRIVATE PROPERTY... 4-7 D.

More information

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. SECTION 260529 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. 1.2

More information

SECTION SECONDARY UNIT SUBSTATIONS

SECTION SECONDARY UNIT SUBSTATIONS SECTION 26 12 16 SECONDARY UNIT SUBSTATIONS PART 1 GENERAL 1.1 SUMMARY This section describes metal-clad, indoor or outdoor, secondary unit substations with integral primary fused disconnect switches,

More information

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES

PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

This guide can be used to prepare a specification for incorporating wall bracket jib cranes into a competitively bid construction project.

This guide can be used to prepare a specification for incorporating wall bracket jib cranes into a competitively bid construction project. SECTION 14654 WALL BRACKET JIB CRANE ***** Gorbel, Inc. manufacturers a broad range of material handling cranes including monorail, bridge, gantry, and jib cranes. Numerous work station and industrial

More information

Large cable sizes stronger than pipe/strut

Large cable sizes stronger than pipe/strut Legrand Seismic Wire Rope/Cable Bracing is the recommended seismic bracing for Legrand wire mesh and ladder tray systems. It is UL Listed, complies with all building codes and standards, and offers significant

More information