TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION

Size: px
Start display at page:

Download "TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION"

Transcription

1 GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION GETCO/E/TS C&C057/R0 DT. 10/10/2007 Page 1 of 13

2 SPECIAL INSTRUCTIONS TO BIDDER Please read following instructions carefully before submitting your bid. 1. All the drawings, i.e. elevation, side view, plan, cross sectional view etc., in AutoCAD format and manuals in PDF format, for offered item shall be submitted. Also the hard copies as per specification shall be submitted. 2. The bidder shall submit Quality Assurance Plan for manufacturing process and Field Quality Plan with the technical bid. 3. The bidder shall have to submit all the required type test reports for the offered item. In absence of this, the evaluation shall be carried out accordingly as nonsubmission of type test reports. 4. The bidder must fill up all the point of GTP for offered item/s. Instead of indicating refer drawing, or as per IS/IEC, the exact value/s must be filled in. 5. All the points other than GTP, which are asked to confirm in technical specifications must be submitted separately with the bid. 6. The bidder is required to impart training in view of manufacture, assembly, erection, operation and maintenance for offered item, at his works, to the person/s identified by GETCO, in the event of an order, free of cost. The cost of logistics will be borned by GETCO. 7. Please note that the evaluation will be carried out on the strength of content of bid only. No further correspondence will be made. 8. The bidder shall bring out all the technical deviation/s only at the specified annexure. 9. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE). Page 2 of 13

3 QUALIFYING REQUIREMENT DATA (For Supply) Bidder should satisfy all the following requirements. 1) The bidder shall be Original Equipment Manufacturer (OEM). The offered equipment have to be designed, manufactured and tested as per relevant IS/IEC with latest amendments. 2) The minimum requirement of manufacturing capacity of offered type, size and rating of equipment shall be 7 times tender / bid quantity. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE). 3) Equipment proposed shall be of similar or higher rating and in service for a minimum period of THREE (3) years and satisfactory performance certificate in respect of this is to be available and submitted. 4) The bidder should clearly indicate the quantity and Single Value Contract executed during last FIVE (5) years, for the offered equipment. Bidder should have executed one single contract during last five years for the quantity equivalent to tender / bid. The details are to be submitted in following format, Sr. No ITEMS SUPPLIED TO ORDER REFERENC E No. & DATE ITEM S QUANTI TY ORDER FULLY EXECUTE D. YES/NO STATUS, IF ORDER UNDER EXECUTI ON REMARK 5) Equipment offered shall have Type Test Certificates from accredited laboratory (accredited based on ISO/IEC Guide 25 / or EN by the National accredition body of the country where laboratory is located), as per IEC / IS / technical specification.the Type test reports shall not be older than FIVE years and shall be valid upto the expiry of validity of offer. Page 3 of 13

4 TECHNICAL SPECIFICATIONS FOR CLAMPS & CONNECTORS (FITTINGS) 1.0 SCOPE: This specification covers the design, manufacture, assembly, inspection, testing, packing and delivery of clamps & connectors (fittings), suitable for MOOSE Conductor (54/7/3.53 mm) or Zebra Conductor (54/7/3.18), Panther Conductor -quadruple & Twin formations. The same are required for out door bus of 132/66 KV Sub-stations. The material offered shall be complete with all components that are necessary for efficient operation. Such parts shall be deemed to be within scope of the supply whether specifically mentioned or not. Fittings shall confirm in all respect to the highest standard of engineering, design, and workmanship and shall be capable of performing trouble free continuous operation. 2.0 QUANTITY: The quantities of various clamps/connectors/fittings are to be considered as set. 3.0 CLIMATIC CONDITIONS: The overall climate is moderate hot, humid, tropical, highly polluted and conductive to rust and fungus growth. The clamps/connector shall be given tropical and fungicidal treatment and shall be capable of satisfactory operation under the hot and humid climatic conditions that would prevail at sites. The climatic conditions are prone to wide range of variation in ambient conditions. The materials offered shall be suitable for installation at any of the switchyards in Gujarat State. 4.0 SYSTEM PARTICULARS: 4.1 Nominal System Voltage : 66 KV 132 KV 4.2 Highest System Voltage. : 72.5 KV 145 KV 4.3 Short circuit level for 3 sec : 25 KA 40 KA 4.4 Frequency : 50 Hz. 50 Hz. 4.5 Basic insulation level : 350 KVP 650 KVP (1.2/50 Micro second wave) 4.6 Switching surge withstand : Number of phases : System earthing : Effectively earthed. 4.9 No. of sub-conductor bus : a) Size of sub-conductor bus : 30/7/3.0 54/7/3.18mm. b) Overall diameter of the : mm. conductor. c) Approx. weight of the : Kg/km. conductor. Page 4 of 13

5 4.11 Ultimate tensile strength : Kg. of single conductor Calculated resistance at 20ºC : Ohms/Km. when corrected to standard weight of single conductor Spacing between sub- : conductors of the bus Maximum working tension : Kg.per conductor. of the bus Span of the bus. : 36 meters, & 56 meters Conductor temperature range : Minimum 3.5ºC Maximum- 64.5ºC 5.0 STANDARD: 5.1 Design, manufacture, performance of the clamps/connectors shall comply with all currently applicable standards, regulations and safety codes in the locality where the same will be installed. Unless otherwise specified it should conform to the latest applicable Indian Standards and in particular to the following: IS :2121 : Fittings for aluminum and steel covered aluminum conductors for overhead power lines. IS:5561 : Electrical power connectors. IS: : Method of high voltage testing. IEC: IS 2629 : Methods of galvanizing. IS Materials conforming to any other national standards which ensure equal or better services shall be acceptable. The salient point of this Specification and point of difference between these in the above specification shall be clearly brought in the offer. 5.3 If required, modifications shall have to be incorporated for the items ordered with you without any extra cost to the Board. 6.0 GENERAL TECHNICAL REQUIREMENT OF CLAMP/CONNECTOR: Page 5 of 13

6 6.1 All casting shall be free from shrinking, blow holes, surface blisters,cavities,cracks, other defects and quality of product shall be uniform throughout. All sharp edges and corners shall be blurred and rounded off. 6.2 Assembly shall be designed and manufactured in such a way so as to have minimum contact resistance. 6.3 The fittings offered shall be inherently resistive to atmospheric corrosion or be suitable to protect against corrosion both during storage as well as in service. 6.4 The clamps/connector shall not cause any damage to the conductor in any way. 6.5 All bolts, clamps, etc. shall have suitable locking arrangements to safe guard against vibration and loosening. 6.6 No part of a clamp shall be less than 12 mm thick for fittings suitable upto size of ACSR Panther conductor, No part of a clamp shall be less than 15 mm thick for fittings suitable for ACSR Zebra conductor and ACSR Moose conductor 6.7 All ferrous parts shall be hot dip galvanised confirming to IS: For bimetallic connectors, copper alloy liner of minimum thickness of 2 mm shall be cast integral with aluminium body. 6.9 Flexible connectors shall be made from tinned/copper/aluminium sheets Connectors shall be designed to be corona free in accordance with the requirements stipulated in IS: The terminal connector for equipments shall be suitable for single Panther conductor for 66 KV,twin ACSR Zebra conductor for 145 KV, twin ACSR Moose conductor for 245 KV and Quadra Moose ACSR for 400kV switchyard The terminal connector shall be compression type to jumper side / boltless type The required bolts and nuts for terminal connector must be stainless steel with suitable check nut. 7.0 SPECIFIC REQUIREMENTS: 7.1 Clamps and fittings shall be so designed that the post insulators shall not be subject to any abnormal stress due to thermal changes in conductor. All the clamps and fittings shall enable the connection to be as short as possible. Wherever possible they shall be in two separate halves. No U bolts shall be used. 7, 2 The data in respect of bus bars and equipment for which clamps and connectors are required shall be given to the successful bidder. 7.3 MATERIAL: The clamps and connectors shall be made of materials listed below: Page 6 of 13

7 i) For connecting ACSR conductor aluminum alloy casting conforming to designation A6 of IS: 617. ii) Bolts, nuts, plain washers and spring washers for all items: Hot dip galvanized mild steel/stainless steel as per GETCO approved make. iii) Split pin shall be made of stainless steel. 7.4 The clamps shall be designed to withstand the flow of continuous current as follows: i) 132KV Amp. ii) 66KV(Transformer) Amp. iii) 66KV Amp. The temperature rise when carrying full load current shall not exceed 45ºC above site ambient temperature of 40ºC. The rated current for which the clamp connectors are designed with respect to the specified ambient temperature shall be marked on each component of clamps and connectors. 8.0 DESIGNS: 8.1 Responsibility of satisfactory design of the clamps/connectors to safely withstand the specified mechanical stresses and carry the rated current without exceeding the temperature rise specified, shall solely rest with the bidder. For this purpose, a minimum factor of safety 2 (two) shall be taken into account. 9. TEST: Individual fittings, clamps, connectors shall be subjected to following Type, Acceptance and Routine Tests. 9.1 CLAMPS & CONNECTORS IS:5561 (1970): Type Test: a) Tensile test : b) Resistance test : c) Temperature rise test. : d) Short time current test : e) Dimensional check : f) Galvanizing test : g) Corona test :}For the fittings suitable for twin h) Radio interference test. :} Moose and above size Page 7 of 13

8 9.1.2 Acceptance Test: a) Tensile test : b) Resistance test : c) Dimensional check : d) Galvanizing test : Routine Test: a) Visual inspection : b) Dimensional check : SAMPLES: The bidder shall have to submit copies of type test certificates.type test reports shall not be older than FIVE years and shall be valid up to the expiry of the validity of the offer. of any Govt. Recognized Laboratory for consideration along with the technical bid, otherwise, bidder should confirm to arrange for conducting these tests at their cost before commencement of supply. Each bidder shall supply free of cost one sample of each item covered under this specification at Const.Store Asoj,Under E.E.Const.Jambuva, before opening of the technical bid so as to enable the GETCO to ascertain their quality and workmanship. The samples shall however be submitted positively along with the tender. The GETCO shall be at liberty to subject these samples to any tests which may deem fit. The GETCO shall not be responsible for any damage, which may occur to these free samples during such testing. The samples shall not be returned to the Tenderer EXPERIENCE: 11.1 The Bidders have to clearly state their experience, resources, engineering organization to undertake this work of supply of clamps/connectors. The Bidder shall have minimum experience of 3 years in the manufacture of similar item for 220KV and above. The purchaser reserves the right to waive stipulation in respect of experience in case of new firms DRAWINGS: Immediately on receipt of the order an authorized representative of the Bidder should come with the necessary drawings for approval of the user Department. Page 8 of 13

9 13.0 INTERCHANGEABILITY: All fittings shall be of standard design and made to guage or jig and shall be interchangeable in all respects with similar items The fittings should also have marked upon them the name of the manufacture, the country of original and suitable identification marks INSPECTION & TESTING: 15.1 The GETCO reserves the right to inspect the material at the time of manufacture at various stages. All acceptance tests shall be performed in the presence of the GETCO s inspecting authority and the manufacturer/supplier shall have to give intimation of place, date and time of each test to the inspecting authority sufficiently in advance to enable the later to be present at the test. All test results must be recorded in the presence of the inspecting authority and no material shall be dispatched without having been passed by the GETCO s Representative. Routine/Acceptance tests shall have to be arranged by the Bidder in accordance with the relevant standards free of cost for each lot of supply Inspection by the GETCO s Representative shall not relieve the Bidder of this obligation of furnishing material in accordance with the relevant specifications (a) The Technical Bid should be comprising of all the information as per the format (for GTP) given with this specification. (b) (c) True copies of all the Type Test Certificates of Govt. recognized Laboratory in respect of the offered items only shall be furnished. Descriptive literature, dimensional drawings catalogues, etc. shall be submitted for the offered items. (d) Bids which do not give complete details, or which are vague and Technically not in line with the GETCO s requirements shall be liable for rejection. Telegraphic or short Bids will also be not considered. Offers without samples and type tests reports will be out rightly rejected QUALITY ASSURANCE PLAN Page 9 of 13

10 The bidder shall invariably furnish following information along with his offer, failing which his offer shall be rejected. i) Statement giving list of important raw materials, proposed to be used in the manufacture of the accessories against this specification, names of sub suppliers for the raw materials, list of standards according to which the raw materials are tested, ii) List of tests normally carried out on raw materials in presence of supplier s representative as routine and/or acceptance during production and on finished goods, copies of test certificates. iii) Information and copies of test certificates as in (i) above in respect of bought out accessories. iv) List of manufacturing facilities available. v) Level of automation achieved and list of areas where manual processing exists. vi) List of areas in manufacturing process, where stage inspections are normally carried out for quality control and details of such tests and inspections. vii) List of testing equipment available with the supplier for final testing of conductor specified. In the case if the supplier does not possess all the routine and acceptance testing facilities the tender will be rejected. viii) ix) Special features provided to make it maintenance free. The GETCO reserves the right for factory inspection to verify the facts quoted in the offer. If any of the facts are found to be misleading or incorrect the offer of that supplier will be out rightly rejected and they may be black listed. Page 10 of 13

11 GUARANTEED AND TECHNICAL PARTICUALRS FOR CLAMPS & CONNECTORS. (Completely filled in & submitted in the Technical Bid) 1 Manufacturer s Name and address 2 Standard to which confirming. ISS Application For 400/220KV Sub-station. 4 Type Standard clamps to & visible corona free type 5 For connection to: 1) Conductor size and arrangement. ACSR Moose /4 IPS/2 IPS & as per schedule of requirements. 2) Equipment terminal size. 6 Material (State percentage composition of constituents and impurities present) 1) Clamp body Aluminium 2) Bolt and Nuts M.S. Hot dip galvanized 3) Spring washers Galvanized spring steel 4) Liners if any 1 mm thick Al.Cu. 7 Rated current (Ampere) 8 Maximum temp. rise over ambient temp. when carrying rated current. (ºC) 9 Rated terminal load 10 Factor of safety >2 11 Minimum thickness of any part. mm. 12 Weight of clamp complete with hardware. 13 Machining accuracy for matching surface. 14 Service Indoor/Outdoor. Outdoor 15 Manufacturers Drg. No. 16 Type tests certificates 17 Details of the type tests to be carried out. 18 List of acceptance & routine tests to be carried out. 19 Mechanical Test i) Heat run test ii) Material compositing tests. iii) Tests for checking blow holes cracks etc. 45ºC over an ambient temperature 40ºC mm( AS per I.S) Page 11 of 13

12 20 For above mentioned testing facilities phase indicate the name and address. Signature of the Bidder: Name: Designation: Date: Authorised common rubber Stamp / seal of the bidder: Page 12 of 13

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 66 kv LIGHTNING ARRESTORS GETCO/ENGG/TECH SPECI.- 66 KV LA/R4/Jan11 Sign

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 400 kv, 220 kv & 132 kv LIGHTNING ARRESTORS (SURGE ARRESTORS) GETCO/ENGG/TECH

More information

TECHNICAL SPECIFICATION OF TOWER MATERIAL FOR132KV-PANTHER TRANSMISSION LINE

TECHNICAL SPECIFICATION OF TOWER MATERIAL FOR132KV-PANTHER TRANSMISSION LINE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF TOWER MATERIAL FOR132KV-PANTHER TRANSMISSION LINE GETCO/E/TS TM051/R0

More information

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS Page no. :1 of 11 SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS Prepared by: Eng. T. Lev (-חתום-) Checked by: I. Bester (-חתום (- Approved by: Eng. Y. Samoocha (-חתום (- 1 Page no.

More information

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEB SPECIFICATION 005-1: 2012 P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS PAGE 1. Scope 03

More information

TECHNICAL SPECIFICATIONS OF SUB STATION STRUCTURES

TECHNICAL SPECIFICATIONS OF SUB STATION STRUCTURES GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF SUB STATION STRUCTURES GETCO/E/TS-STR 2301/R8 PROCUREMENT Dtd. 06.02.2013

More information

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - 1. SCOPE: - This specification covers 11KV Disc Type & 11KV/ 22KV Pin Type Insulators for 11/22KV H.T. over head power lines. 2. APPLICABLE

More information

SEAL & SIGNATURE OF THE TENDERER

SEAL & SIGNATURE OF THE TENDERER MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. LTD. SCHEDULE - `A' TECHNICAL SPECIFICATION FOR 11 kv & 22 kv A.B. SWITCH. SPECIFICATION NO:RE/II/A.B.SWITCH/2005 INDEX -----------------------------------------------------------------------------------------------------------------------

More information

TECHNICAL SPECIFICATION FOR MS BEAMS 116X100 11MTR LONG FOR SUB-STATIONS

TECHNICAL SPECIFICATION FOR MS BEAMS 116X100 11MTR LONG FOR SUB-STATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR MS BEAMS 116X100 11MTR LONG FOR SUB-STATIONS GETCO/E/TS-MS024/R0DT01-04-2008

More information

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 REVISION NO. 0 NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 PAGE NO. 1 OF 24 DATE OF ISSUE (MONTH/YEAR) TOTAL NO. OF PAGES (Including cover

More information

Technical Specification for Live Line Tap Connectors

Technical Specification for Live Line Tap Connectors Ergon Energy Corporation Limited Technical Specification for Live Line Tap ETS-06-01-01 Check this is the latest Process Zone version before use. Specification ETS 06-01-01 Ver 1 Contents 1. Purpose and

More information

TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES

TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES GETCO/E/TS

More information

TECHNICAL SPECIFICATION OF MS TOR BARS FOR TRANSMISSION LINES

TECHNICAL SPECIFICATION OF MS TOR BARS FOR TRANSMISSION LINES GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF MS TOR BARS FOR TRANSMISSION LINES GETCO/E/TS-MS024/R2 DT08-02-2012 TECHNICAL

More information

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR 003: 2008 CEB SPECIFICATION SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for Specification For All Aluminium Alloy Stranded Conductor CEB Specification

More information

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008 Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4

More information

General Requirements. Technical Specifications for Insulators of Transmission Lines

General Requirements. Technical Specifications for Insulators of Transmission Lines Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Insulators of Transmission

More information

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.

More information

Technical Specification for LV ABC Fuse Switch Disconnectors

Technical Specification for LV ABC Fuse Switch Disconnectors Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

TECHNICAL SPECIFICATION FOR 11mtr. LONG STEEL TUBULAR POLE

TECHNICAL SPECIFICATION FOR 11mtr. LONG STEEL TUBULAR POLE Annexure-A TECHNICAL SPECIFICATION FOR 11mtr. LONG STEEL TUBULAR POLE 1.0 SCOPE 1.1 This specification covers the design, manufacture, testing at works, supply / delivery & transportation of 11 mtr long

More information

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols Ergon Energy Corporation Limited Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols ETS-01-05-01 Check this is the latest Process Zone version before use. Specification ETS 01-05-01

More information

SPECIFICATION SHEET JUNCTION BOXES

SPECIFICATION SHEET JUNCTION BOXES SPECIFICATION SHEET JUNCTION BOXES 8484-SS8201-8010 0 DOCUMENT NO REV SHEET 1 OF 1 CLIENT : HPCL, MUMBAI PROJECT : LPG BOTTLING PLANT, ANANTAPUR PLANT : - LPG BOTTLING PLANT ISSUED FOR : PROPOSAL ENQUIRY

More information

An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application

An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application Introduction Designed for Indoor and outdoor applications Non-tension tap and splice applications Used

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

SECTION CHAIN-LINK FENCES AND GATES 02821/1

SECTION CHAIN-LINK FENCES AND GATES 02821/1 SECTION 02821 - CHAIN-LINK FENCES AND GATES 02821/1 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Chain-Link Fences: 2. Gates: horizontal slide or swing. 3. Fences installed where

More information

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number PART 1 GENERAL 01 02 03 04 SCOPE Furnish and install Manual Transfer Switches (MTS) and

More information

SCHEDULE-III TECHNICAL SPECIFICATION OF 11 KV CTPT METERING SETS AGAINST TN-2134

SCHEDULE-III TECHNICAL SPECIFICATION OF 11 KV CTPT METERING SETS AGAINST TN-2134 Common Spec-2134.doc - 1-3.01 SCOPE: SCHEDULE-III TECHNICAL SPECIFICATION OF 11 KV CTPT METERING SETS AGAINST TN-2134 This specification covers the design, manufacture, assembly, testing and delivery of

More information

Shackles. Applications. Range. Design. CAD drawings. Finish

Shackles. Applications. Range. Design. CAD drawings. Finish Applications Shackles are used in lifting and static systems as removable links to connect (steel) wire rope, chain and other fittings. Screw pin shackles are used mainly for non-permanent applications.

More information

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D Document type Page Verksamhetsstyrande 1 (5) Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D17-0008968 1.0 Organisation Valid from Valid until Regionnätsaffärer

More information

MIL-L-26764B 4 March 1970 SUPERSEDING MIL-L-26764(ASG) 12 December 1963 MILITARY SPECIFICATION

MIL-L-26764B 4 March 1970 SUPERSEDING MIL-L-26764(ASG) 12 December 1963 MILITARY SPECIFICATION 4 March 1970 SUPERSEDING MIL-L-26764(ASG) 12 December 1963 MILITARY SPECIFICATION LIGHT, MARKER, AIRPORT APPROACH, HIGH INTENSITY, TYPE MB-2 This specification has been approved by the Department of the

More information

SECTION MECHANICAL EQUIPMENT - GENERAL REQUIREMENTS

SECTION MECHANICAL EQUIPMENT - GENERAL REQUIREMENTS SECTION 11000 MECHANICAL EQUIPMENT - GENERAL REQUIREMENTS PART 1 - GENERAL 1.1 DESCRIPTION A. This section contains general information required to install mechanical equipment as shown on the plans and

More information

BUREAU OF INDIAN STANDARDS

BUREAU OF INDIAN STANDARDS POSTED UNDER POSTAL CERTIFICATE BUREAU OF INDIAN STANDARDS Phone : 23721442, 28394955, 28394956, 28396324 FAX : 28398841 BIS BANGALORE LABORATORY Peenya Industrial Area 1 st Stage, Tumkur Road Bangalore

More information

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained.

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained. DOC: STI//1 SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF ACCORDING TO IS/IEC:2003 1. LABORATORY A laboratory shall be maintained which shall be suitably equipped and staffed, where different tests

More information

PS-31 (SUS304, 300 mm) PS-31 (SUS304, 1,000 mm)

PS-31 (SUS304, 300 mm) PS-31 (SUS304, 1,000 mm) CSM_PS-_S(R)_-31_DS_E_7_1 Separate s for Water Supply and Drainage Control in Buildings. Small, Lightweight s for Use as Built-in Components. The PS-@S(R) are separate s that allow the s to be withdrawn

More information

CHECK LIST SCHEDULE OF INFORMATION TO BE FURNISHED WITH THE OFFER

CHECK LIST SCHEDULE OF INFORMATION TO BE FURNISHED WITH THE OFFER Project : 400/220 Kv SWITCHYARD AT TALAGUPPA & GUTTUR TB 342 552 002 CHECK LIST SCHEDULE OF INFORMATION TO BE FURNISHED WITH THE OFFER BIDDER SHALL PUT A TICK IF THE INFORMATION IS ENCLOSED WITH THE OFFER,

More information

B. Polyethylene samples shall be submitted for Owner approval of color and quality.

B. Polyethylene samples shall be submitted for Owner approval of color and quality. Glass Rail ENGINEERED DASHERBOARD SPECIFICATIONS PART 1 - GENERAL 1.01 PROJECT SCOPE A. Contractor shall furnish and install one complete set of steel framed dasherboards as indicated on the drawings and

More information

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)

SECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) SECTION 13125 ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

A. Product Data shall be provided for each type of product indicated.

A. Product Data shall be provided for each type of product indicated. 32 31 13 CHAIN LINK FENCES AND GATES SECTION 1 GENERAL 1.1 SUMMARY This Section includes the following: 1. Chain Link Fences 2. Gates for Chain Link Fences. See electrical specifications for electrical

More information

QUOTATION ENQUIRY. Frequency Range Output AC Voltage Regulation (Batt. Mode) ±10% Frequency Range (Batt. Mode)

QUOTATION ENQUIRY. Frequency Range Output AC Voltage Regulation (Batt. Mode) ±10% Frequency Range (Batt. Mode) ANNEXURE-I-A QUOTATION ENQUIRY Ref: IIT (BHU)/IPCell/2017-18/UPS/1 KVA/574 Due Date: 26.09.2017 Date:16.09.2017 Upto 1:00 pm (Last date of quotation receiving) (Date of tender enquiry) To. Dear Sir, Please

More information

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. SECTION 260529 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. 1.2

More information

A Study on Analysis of Transmission Line Tower and Design of Foundation

A Study on Analysis of Transmission Line Tower and Design of Foundation A Study on Analysis of Transmission Line Tower and Design of Foundation 1 B. Bharath Kumar Reddy, 2 K. Rasagnya, 3 V. Sanjay Gokul 1,2 Under Graduates, 3 Assistant Professor Abstract - The Transmission

More information

ITEM 686 TRAFFIC SIGNAL POLE ASSEMBLIES (STEEL)

ITEM 686 TRAFFIC SIGNAL POLE ASSEMBLIES (STEEL) ITEM 686 TRAFFIC SIGNAL POLE ASSEMBLIES (STEEL) 686.1. Description. This Item shall govern for designing, fabricating, furnishing and erecting steel traffic signal pole assemblies of the various types

More information

Section 906. STRUCTURAL STEEL

Section 906. STRUCTURAL STEEL 906.01 Section 906. STRUCTURAL STEEL 906.01. General Requirements. Finished rolled shapes must be free from imperfections that affect strength and durability in accordance with ASTM A 6. Rolled shapes

More information

Data Bus Connector and Terminator Requirements Document DB-1001-A. Revision C

Data Bus Connector and Terminator Requirements Document DB-1001-A. Revision C Data Bus Connector and Terminator Requirements Document DB-1001-A Revision C 2507 W. Geneva Dr. Tempe, Arizona 85282 Phone [602] 231-8616 FAX [602] 273-9135 www.phxlogistics.com TABLE OF CONTENTS 1. Introduction

More information

Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg.

Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg. DAKSHIN HARYANA BIJLI VITRAN NIGAM LIMITED Specification No. S-95/DD-177 Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg. Chief Engineer/P&D, DHBVN, Hisar. Issue

More information

TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED)

TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED) TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED) Regd. & Corporate Office: Visnagar Road, MEHSANA 384 001 (North Gujarat) Telephone: (02762) 222880, 222080-81 Fax: (02762)

More information

SECTION 1 - INTENT, SYSTEM REQUIREMENT, DESIGN CRITERIA AND SCOPE

SECTION 1 - INTENT, SYSTEM REQUIREMENT, DESIGN CRITERIA AND SCOPE Customer : Tamil Nadu Transmission Corporation Limited. Section 1 SECTION 1 - INTENT, SYSTEM REQUIREMENT, DESIGN CRITERIA AND SCOPE 1.0.0 INTENT OF SPECIFICATION 1.1.0 This specification covers the design,

More information

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)

SECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE) SECTION 02623 HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE) PART 1 - GENERAL 1.1 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals required and install high density

More information

DOMESTIC GAS REGULATORS

DOMESTIC GAS REGULATORS CNG & CITY GAS DISTRIBUTION PROJECT FOR BID DOCUMENT FOR DOMESTIC GAS REGULATORS UNDER DOMESTIC COMPETITIVE BIDDING Bid Document No.: TNGCL/C&P/P(101)/PRV/2013-14 Dated 06/06/2013 VOLUME II OF II PREPARED

More information

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS FOR FRAMES & COVERS OF JOINTING CHAMBERS SPECIFICATIONS NO. Access Networks Division Qatar Telecom (Qtel) P.O. Box 217, Doha, State of Qatar Revision No.: 1, June 2006 CONTENTS

More information

CERTIFICATION SCHEME FOR TYPE APPROVAL OF PRODUCTS

CERTIFICATION SCHEME FOR TYPE APPROVAL OF PRODUCTS CERTIFICATION SCHEME FOR TYPE APPROVAL OF PRODUCTS 1. Introduction 1.1 Scheme for type approval of products of Indian Register of Shipping (IRS) is an impartial certification system based on a design review

More information

UNITED NATIONS DEVELOPMENT PROGRAMME ITB

UNITED NATIONS DEVELOPMENT PROGRAMME ITB UNITED NATIONS DEVELOPMENT PROGRAMME ITB 2017-078 Bill of Quantities Project name: Package 2: External Lighting PAL10-00099398 / Rehabilitate GIE Infrastructure General *All installation works must be

More information

SARDAR VALLABHBHAI NATIONAL INSTITUTE OF TECHNOLOGY,SURAT

SARDAR VALLABHBHAI NATIONAL INSTITUTE OF TECHNOLOGY,SURAT SARDAR VALLABHBHAI NATIONAL INSTITUTE OF TECHNOLOGY,SURAT TENDER NOTICE Sealed tenders are invited in duplicate from the supplier/manufacturer/distributor/vendor for the supply of the following items.

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION 1.0 SPECIFICATION OF FLAMEPROOF DISTRIBUTION BOARD, FIXTURES, POWER DISTRIBUTION SYSTEM INCLUDING CABLE LYING & TERMINATION. 1.0.1 Scope The following Specification flameproof Distribution

More information

City of Ottawa Street Lighting. Streetlight Brackets and Adapters

City of Ottawa Street Lighting. Streetlight Brackets and Adapters TITLE: Engineering Specification RECOMMENDED: S. Edey, NO: 1 REV: APPROVED: D. O Keefe LBS0001 OF REV. DATE: 2010-01-07 6 5 City of Ottawa Street Lighting Streetlight Brackets and Adapters For City of

More information

GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM

GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM 1 GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM 1.01 WORK INCLUDED PART 1: GENERAL A. Provide for all labor, equipment, materials, and services to furnish and install VERSA SHIELD Window

More information

TEESTAVALLEY POWER TRANSMISSION LTD.

TEESTAVALLEY POWER TRANSMISSION LTD. TEESTAVALLEY POWER TRANSMISSION LTD. TECHNICAL SPECIFICATION FOR TRANSMISSION LINE TOWER PACKAGES A1 & A2 VOLUME-II SPECIFICATION NO.: TOWER PACKAGE- A1 & A2 (This document is meant for the exclusive purpose

More information

SECTION 1043 FENCE MATERIAL

SECTION 1043 FENCE MATERIAL SECTION 1043 FENCE MATERIAL 1043.1 Scope. This specification covers the material required in the construction of chainlink fence and woven wire fence. 1043.2 Basis of Acceptance. The basis of acceptance

More information

Specification Lightning Protection Systems

Specification Lightning Protection Systems Specification Lightning Protection Systems General: Summary A) This Section specifies the lightning protection system for the building(s) or structure(s). This system provides safety for the building and

More information

MATERIAL AND EQUIPMENT STANDARD FOR PIG LAUNCHING AND RECEIVING TRAPS

MATERIAL AND EQUIPMENT STANDARD FOR PIG LAUNCHING AND RECEIVING TRAPS MATERIAL AND EQUIPMENT STANDARD FOR PIG LAUNCHING AND RECEIVING TRAPS CONTENTS : PAGE No. 1. SCOPE... 3 2. SOURCES AND REFERENCES... 3 2.1 Sources... 3 2.2 References... 4 3. UNITS... 5 4. SERVICE CONDITIONS...

More information

DETAIL SPECIFICATION. MICROPHONE, CARBON (MICROPHONE M-29( )/U and M-52( )/U) INACTIVE FOR NEW DESIGN AS OF 30 MARCH 1999

DETAIL SPECIFICATION. MICROPHONE, CARBON (MICROPHONE M-29( )/U and M-52( )/U) INACTIVE FOR NEW DESIGN AS OF 30 MARCH 1999 INCH-POUND MIL-DTL-11193E 20 August 2009 SUPERSEDING MIL-M-11193D(SigC) 31 July 1960 DETAIL SPECIFICATION MICROPHONE, CARBON (MICROPHONE M-29( )/U and M-52( )/U) INACTIVE FOR NEW DESIGN AS OF 30 MARCH

More information

SECTION FIBERGLASS REINFORCED POLYMER (FRP) PANELS

SECTION FIBERGLASS REINFORCED POLYMER (FRP) PANELS SECTION 07 44 50 FIBERGLASS REINFORCED POLYMER (FRP) PANELS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Design, Engineering, manufacturing and erection of fiberglass reinforced panels. Delegated Design of

More information

Not Applicable DD/MM/YY Completed Forms to be submitted by 30/08/2013 : Hrs IST. Date of Opening for Technical Bids 30/08/2013 : 14.

Not Applicable DD/MM/YY Completed Forms to be submitted by 30/08/2013 : Hrs IST. Date of Opening for Technical Bids 30/08/2013 : 14. DETAIL INFORMATION Contact Person and Address M.NALLATHAMBI SENIOR MANAGER / CCDP PURCHASE DEPARTMENT/R&D and CR UNIT HPBP BHEL, TIRUCHY, INDIA PIN : 620 014 Email mnthambi@bheltry.co.in Telephone 0091

More information

1. Cast-in-place concrete is specified in Section

1. Cast-in-place concrete is specified in Section SECTION 03 38 00 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for furnishing and installing post-tensioned slabs, jacks, jacking and anchors at Parking Structure, and record

More information

ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200

ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200 ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200 The GRD 4200 is an electronic earthing equipment for tankers during loading and unloading operations of flammable liquids in places with danger of explosion.

More information

HIGH MAST CAMERA POLE ASSEMBLY GENERAL

HIGH MAST CAMERA POLE ASSEMBLY GENERAL 10-3.24 HIGH MAST CAMERA POLE ASSEMBLY GENERAL The Contractor must furnish and install the following equipment for high mast camera pole assembly as described herein and as shown on the plans: 1. Camera

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 9974-4 Minor Revision Draft 2016-04-12 Connections for general use and fluid power Ports and stud ends with ISO 261 threads with elastomeric or metal-to-metal sealing Part 4:

More information

Penn State Forestland Management Office Multi-Strand High-Tensile Wire Fence Specifications

Penn State Forestland Management Office Multi-Strand High-Tensile Wire Fence Specifications Penn State Forestland Management Office Multi-Strand High-Tensile Wire Fence Specifications 1. FENCE REQUIREMENTS Hazard Trees All hazard trees, which are within tree length of the fence, must be felled

More information

List of Enquiry Items for Enquiry BAP/PUR/FGD/EQS/2014/ E dt

List of Enquiry Items for Enquiry BAP/PUR/FGD/EQS/2014/ E dt List of Enquiry Items for Enquiry BAP/PUR/FGD/EQS/2014/4231581E dt 13.03.2014 Sl.No Material Code Description Unit Qty Destination 1. RFW301290000 EMERGENCY QUENCHING SYSTEM AT GGH INLET AS PER TECHNICAL

More information

Welding Accessories

Welding Accessories Welding Accessories www.airliquide.ca 1-800-817-7697 Welding Accessories BLUESHIELD Welding Cables Blueshield Welding Cables: Excellent flexibility (stays flexible at -50 C) Abrasion resistant Oil, solvent

More information

BANK REFERENCE LETTER/SOLVENCY CERTIFICATE (On Bank s Letter Head) Certified that M/s at (address) is having an account in our bank

BANK REFERENCE LETTER/SOLVENCY CERTIFICATE (On Bank s Letter Head) Certified that M/s at (address) is having an account in our bank Annexure -I BANK REFERENCE LETTER/SOLVENCY CERTIFICATE (On Bank s Letter Head) Certified that M/s at (address) is having an account in our bank as per following particulars:- 1. Type of Account : Cash-Credit/Current/Savings

More information

TECHNICAL SPECIFICATIONS for 100Ci Ir-192 source projector(exposure device /Camera )

TECHNICAL SPECIFICATIONS for 100Ci Ir-192 source projector(exposure device /Camera ) S-104-Q-ISTOPE CAMERA-PtB TECHNICAL SPECIFICATIONS for 100Ci Ir-192 source projector(exposure device /Camera ) S. No. PARTICULARS BHEL SPECIFICATIONS 1.0 Area of Application For Gamma Radiography of materials

More information

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM PART 1- GENERAL 1.1 SUMMARY A. Section Includes: SECTION 084523 - SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 1. Flat factory prefabricated structural insulated translucent sandwich panels; with glazed endwalls.

More information

Certified that we agree to all the aforesaid technical specification except at S.No. for which our technical specification shall be as under:-

Certified that we agree to all the aforesaid technical specification except at S.No. for which our technical specification shall be as under:- Schedule III JAIPUR VIDYUT VITRAN NIGAM LIMITED Prescribed technical specification for supply of (Name of Material/Equipment/Machinery/T&P etc.) S.No. Technical specification Name of IS/other Other particulars

More information

HOT ROLLED STEEL FLAT PRODUCTS FOR STRUCTURAL FORMING AND FLANGING PURPOSES SPECIFICATION (Third Revision of IS 5986)

HOT ROLLED STEEL FLAT PRODUCTS FOR STRUCTURAL FORMING AND FLANGING PURPOSES SPECIFICATION (Third Revision of IS 5986) For Comments Only Draft Indian Standard Doc: MTD 4(4939) HOT ROLLED STEEL FLAT PRODUCTS FOR STRUCTURAL FORMING AND FLANGING PURPOSES SPECIFICATION (Third Revision of IS 5986) ICS 77.140.50 Not to be reproduced

More information

PTFE BELLOWS POLY FLUORO LTD. POLY FLUORO LTD.260A. Bommasandra Industrial Area, Hosur Road, Bangalore TECHNICAL SPECIFICATION

PTFE BELLOWS POLY FLUORO LTD. POLY FLUORO LTD.260A. Bommasandra Industrial Area, Hosur Road, Bangalore TECHNICAL SPECIFICATION PTFE BELLOWS TECHNICAL SPECIFICATION 1. MATERIALS 1.1 PTFE Only virgin (not reprocessed) PTFE conforming to ASTM D 1457, type III, IV or V shall be used for the production of bellows; the PTFE raw material

More information

Specification for 11 KV outdoor GOD Air Break Isolator along with earth switch,post insulators, CT, PT and the Double pole Structure.

Specification for 11 KV outdoor GOD Air Break Isolator along with earth switch,post insulators, CT, PT and the Double pole Structure. Page 1 of Specification for 11 KV outdoor GOD Air Break Isolator along with earth switch,post insulators, CT, PT and the Double pole Structure. Hindustan Petroleum Corporation Ltd 8 S.V. Marg, Ballard

More information

NORSOK STANDARD COMMON REQUIREMENTS CATHODIC PROTECTION M-503. Rev. 2, September 1997

NORSOK STANDARD COMMON REQUIREMENTS CATHODIC PROTECTION M-503. Rev. 2, September 1997 NORSOK STANDARD COMMON REQUIREMENTS CATHODIC PROTECTION M-503 Rev. 2, September 1997 Please note that whilst every effort has been made to ensure the accuracy of the NORSOK standards neither OLF nor TBL

More information

REQUEST FOR PROPOSAL

REQUEST FOR PROPOSAL BPACKAGE NO. K.G.B.V. TEACHER'S GUIDELINE ( GUJARATI)/ 2014-15 Gujarat Council of Elementary Education Sarva Shiksha Abhiyan REQUEST FOR PROPOSAL REGARDING PRINTING OF "K.G.B.V. TEACHER'S GUIDELINE ( GUJARATI)

More information

PART MATERIAL REMARK Metal Case with Pig-tail. Brass (Metal Case) Copper (Pig-tail) Star Contact Copper Silver Plated

PART MATERIAL REMARK Metal Case with Pig-tail. Brass (Metal Case) Copper (Pig-tail) Star Contact Copper Silver Plated 1. SCOPE This specification defines the technical requirements of TZ-D series thermal-link with PROFFUSE brand that are produced according to IEC 60691, UL 60691,GB 9816. 2. APPLICABLE STANDARDS IEC 60691,

More information

TESTING PTE EARTHING

TESTING PTE EARTHING 1 SCOPE This section of the Power Systems Live Working Manual details the procedures to be followed to achieve Safety from the System when carrying out examination, testing and remedial work on PTE (Pole

More information

KENDRIYA BHANDAR GROCERY DIVISION NEW DELHI. Registration of Suppliers of Pulses & Rice Terms & Conditions

KENDRIYA BHANDAR GROCERY DIVISION NEW DELHI. Registration of Suppliers of Pulses & Rice Terms & Conditions KENDRIYA BHANDAR GROCERY DIVISION NEW DELHI Registration of Suppliers of Pulses & Rice Terms & Conditions Reference Kendriya Bhandar s advertisement appeared in the Times of India dt. 9 th June, 2015 inviting

More information

B-LINE SERIES. DURA-BLOK rooftop supports BRTS-17 DURA-BLOK. A complete rooftop support solution

B-LINE SERIES. DURA-BLOK rooftop supports BRTS-17 DURA-BLOK. A complete rooftop support solution DURA-BLOK rooftop supports BRTS-17 B-LINE SERIES DURA-BLOK A complete rooftop support solution DURA-BLOK rooftop solutions support DURA-BLOK supports are made of 100% recycled rubber and are designed to

More information

Thermal Diffusion Galvanizing

Thermal Diffusion Galvanizing Engineering Test Report M-571 Thermal Diffusion Galvanizing For Pole Line Hardware Revision D 11.17.2017 Added further Corrosion Test results and Abrasion Test results Prepared by 1. Introduction to Thermal

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 62561-2 Edition 1.0 2012-02 Lightning protection system components (LPSC) Part 2: Requirements for conductors and earth electrodes IEC 62561-2:2012(E) THIS PUBLICATION IS COPYRIGHT

More information

BIDDING DOCUMENT. Tavua 33 kv Substation Extension. Supply of 36kV Single Break Disconnectors, Structures and Accessories TENDER NO: MR 170/2015

BIDDING DOCUMENT. Tavua 33 kv Substation Extension. Supply of 36kV Single Break Disconnectors, Structures and Accessories TENDER NO: MR 170/2015 Tavua Substation 33 kv Extension Project Bidding Document: Revision 1 FIJI ELECTRICITY AUTHORITY BIDDING DOCUMENT Tavua 33 kv Substation Extension Supply of 36kV Single Break Disconnectors, Structures

More information

INVITATION OF TENDER FOR TERMINAL AUTOMATION SYSTEM (TLF + TFMS) & SAFETY PLC RELATED AUTOMATION JOB AT SEVEN LOCATIONS (BATHINDA, MUGHALSARAI,

INVITATION OF TENDER FOR TERMINAL AUTOMATION SYSTEM (TLF + TFMS) & SAFETY PLC RELATED AUTOMATION JOB AT SEVEN LOCATIONS (BATHINDA, MUGHALSARAI, 1 INVITATION OF TENDER FOR TERMINAL AUTOMATION SYSTEM (TLF + TFMS) & SAFETY PLC RELATED AUTOMATION JOB AT SEVEN LOCATIONS (BATHINDA, MUGHALSARAI, PANIPAT, JALLANDHAR, KANPUR, BATHINDA & REWARI) Bharat

More information

HIGH SEAL ULF Live Loaded Packing System

HIGH SEAL ULF Live Loaded Packing System Instruction Manual HIGH-SEAL Live-Loaded Packing HIGH SEAL ULF Live Loaded Packing System Contents Introduction... 1 Scope of Manual... 1 Description... 2 Spring Selection... 3 Installation... 3 Parts

More information

PHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-P156-60

PHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-P156-60 Solar Innova uses the latest materials to manufacture photovoltaic modules. Our modules are ideal for any application that uses the photoelectric effect as a clean energy source because of its minimal

More information

Hydrodynamic Separation Product Calculator

Hydrodynamic Separation Product Calculator Hydrodynamic Separation Product Calculator Example Project BMP #1 CDS 2015-4 Project Information Project Name Example Project Option # A Country US State Kentucky City Covington Contact Information First

More information

SECTION-I TECHNICAL SPECIFICATIONS

SECTION-I TECHNICAL SPECIFICATIONS SECTION-I TECHNICAL SPECIFICATIONS 1. General Information and Scope 1.1 Scope 1.1.1 The following 400 kv double circuit transmission lines are included in the scope of the Contractor for various packages.

More information

Polymer Suspension Insulators 69kV to 765kV

Polymer Suspension Insulators 69kV to 765kV CATALOG Polymer Suspension Insulators 69kV to 765kV NGK Locke Polymer Insulators, Inc. Virginia Beach, Virginia, U.S.A. TABLE of CONTENTS Table of Contents... 1 Design Features... 2 Material... 2 Definition

More information

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 CANADIAN ELECTRICAL CODE 1 The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 Repealed by Chapter E-6.3 Reg 8 (effective June 24, 2003). Formerly Chapter E-6.3 Reg 6 (effective March

More information

Jhabua Power Ltd. NOTICE INVITING BIDS

Jhabua Power Ltd. NOTICE INVITING BIDS Jhabua Power Ltd. 2nd Floor, Centrum plaza, Golf Course Road, Sector- 53, Gurgaon-122002 Ph.: +91-124-4392000 Fax: +91-124-4376496 NOTICE INVITING BIDS BY JHABUA POWER LIMITED (JPL) 2nd Floor, Centrum

More information

D1 4426, Approved Process Sources. Purchase Order Flow Down Requirements

D1 4426, Approved Process Sources. Purchase Order Flow Down Requirements D1 4426, Approved Process Sources Purchase Order Flow Down Requirements Common Commodity Requirements Unique Commodity Additional Requirements Chemical Processes Heat Treat Materials Testing Laboratories

More information

No.: MTL/PUR/13/06/Pt.XVI/(J)/10 DATE :

No.: MTL/PUR/13/06/Pt.XVI/(J)/10 DATE : No.: MTL/PUR/13/06/Pt.XVI/(J)/10 DATE : 24.05.2006 ASSAM GAS COMPANY LIMITED AN ISO 9001;2000 COMPANY ( A GOVT. OF ASSAM UNDERTAKING ) P.O. DULIAJAN, PIN 786 602 DIST. DIBRUGARH (ASSAM) Sealed tenders

More information

EVALUATION REPORT. PFC-5551 Reissued April 1, Filing Category: DESIGN Steel (038)

EVALUATION REPORT. PFC-5551 Reissued April 1, Filing Category: DESIGN Steel (038) ICBO Evaluation Service, Inc. 5360 WORKMAN MILL ROAD WHITTIER, CALIFORNIA 90601-2299 A subsidiary corporation of the International Conference of Building Officials EVALUATION REPORT Copyright 2001 ICBO

More information

Dr. Deb Kumar Panja Registrar

Dr. Deb Kumar Panja Registrar Notice Inviting Tender Tender Ref. No: PHYS/SERB/AD/Tend/001 Date: 17.01.2018 E-tenders are hereby invited for the item as per detailed specifications from the Original Equipment Manufacturer (OEM) or

More information

I N V I T A T I O N T O B I D City and Borough of Wrangell Premanufactured Restroom

I N V I T A T I O N T O B I D City and Borough of Wrangell Premanufactured Restroom Overview The (CBW) requests sealed bids from interested and qualified firms to provide a, on a one-time basis. Supplier shall furnish all labor, materials, tools, and equipment necessary for supplying

More information

1.1 All testing apparatus shall be periodically checked and calibrated. Records of such checks/calibration shall be maintained.

1.1 All testing apparatus shall be periodically checked and calibrated. Records of such checks/calibration shall be maintained. SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF SINGLE PHASE a.c. INDUCTION MOTORS FOR GENERAL PURPOSE ACCORDING TO IS 996:2009 (Including Amendment No.1) 1. LABORATORY A laboratory shall be maintained

More information