1 ADDENDUM ADDENDUM # 1 DATE: February 16, 2017 REFERENCE: Invitation for Bid No.: S-LB IFB Issue Date: January 30, 2017 Title: River Oaks Elementary School Renewal Architect/Engineer: Architecture Incorporated. Sealed Bid Due Date: February 21, 2:00 p.m. THE FOLLOWING CHANGES, ADDITIONS, DELETIONS AND CLARIFICATIONS ARE HEREBY MADE PART OF THE BIDDING REQUIREMENTS AND CONTRACT DOCUMENTS FOR THE ABOVE REFERENCED PROJECT AND SHALL BE TAKEN INTO ACCOUNT IN THE PREPARATION OF ALL BIDS AND THE EXECUTION OF ALL WORK. BIDDERS SHALL ACKNOWLEDGE RECEIPT OF THIS ADDENDUM IN THE APPROPRIATE SPACE ON THE BID FORM. A. Specifications: 1. Section , 2.2: Delete line J. 2. Section , 2.1, A, 1, i: Change from Chanburg, Fredericksburg, BA to read Mid- Atlantic Casework, LLC, Fredericksburg, VA 3. Section , 1.3, A,1: Add d. MOEN 4. Section , 1.3, A, 2: Add f. MOEN 5. Section , 1.3, A, 9: Add e. MOEN 6. Section , 2.1, A: Add 4. Trane 7. Section , 2.1, A: Revise to read, The following manufacturers are approved as alternates, which are subject to review and compliance with the requirements of the Specifications, before being able to be utilized on the project. 1. Basis of Design: Daikin Applied 2. Trane 8. Section , 2.1, A: Revise to read, The following manufacturers are approved as alternates, which are subject to review and compliance with the requirements of the Specifications, before being able to be utilized on the project. 1. Basis of Design: Daikin Applied 2. Trane 9. Section , 1.5, A: Revise second sentence to read, Equal products by other manufacturers submitted in accordance with the requirements of Section , 1.9 will be considered for acceptability. 10. Section : Add entire section. PURCHASING OFFICE P.O. BOX 389, MANASSAS, VA , FAX

2 B. Drawings: 1. PH1.1: Add tag to indicate that Work Room 511, Computer Lab 512, Special Ed. 513, Media Center 600, Office 600A and A/V Storage 600B shall be part of Phase 10. Add note indicating that the site lighting indicated on SL1.1 is to be completed in Phase A2.1: Revise the hardware set of doors 600, 600C, 600D, 704C and 704G to be hardware set 130F A5.1: Add Site Plan #2, showing contractor s staging area. See attached sheet A A9.1: Detail 5, add 1 x 3 ledger, with toggle bolts at 16 o.c. below the cabinet. Detail 10, add 1 x 3 ledger, with toggle bolts at 16 o.c. below the cabinet. 5. F1.1: Revise the wall designation finishes for all walls of Multi-Purpose Room 704 to indicate finish 3 / 4, CMU painted epoxy / acoustic wall panels painted flat. 6. M2.1: Added fire dampers, notes on pipe sizes and notes about EA grilles connecting to existing ductwork. See attached sheet M M2.2: Added fire dampers, notes on pipe sizes and notes about EA grilles connecting to existing ductwork. See attached sheet M M2.3: Removed two ductheaters for the large AHU s and added pipe size notes. See attached sheet M M4.1: Removed two duct heaters DH-2 and DH-3 from the equipment schedule. 10. P0.1: Revise sink SK-3. Sink (SK-3): Duratop proxy resin sink model ADA-A-07CR (14 x 14 x 5 ) Provide with EF-PPSW-85 poly drain outlet 3.25 flange x 4 height x 1.5 diam thread, EF-PPWT-158 overflow 1.5 tapered OD x 6 length, EF-PPPG-150 stopper 1.5 diameter, EF-PPBT-158 adjustable riser bottle trap 1.75 ID x 2.00 OD x 7.5 height. Supply with Duratop model L411, deck mounted mixing faucet, forged brass with polished chrome plated finish, forged brass four-arm handles with 6 swing gooseneck. 11. P2.1: Revise Toilet C115. Revise sprinkler note. See attached sheet P P2.2: Revise piping at Girls Toilets B127 and C102, Boys Toilets B128 and C104 and Special Ed. B109. Revise sprinkler note. See attached sheet P P2.3: Revise piping at Girls Toilet A136, Boys Toilet A135, Principal A123, Men s A131, Women s A130, Toilet A106 and Clinic A105. Revise sprinkler note. See attached sheet P E2.1: Added typical tag for light fixture type N1, to right of door 211 on the exterior of Second Grade E3.1: Added power, data and wire mold in various classrooms, offices and computer labs. See attached sheet E E3.2: Added power, data and wire mold in various classrooms, offices and computer labs. See attached sheet E E5.1: Remove duct heater (2-30kw). See attached sheet E5.1. PURCHASING OFFICE P.O. BOX 389, MANASSAS, VA , FAX

3 18. E6.1: Remove duct heater (2-30kw) circuits breaker in panel HA. Revise load analysis. See attached sheet E E6.2: Added vending machine circuit in panel LC. See attached sheet E6.2. C. Questions: 1. This building does not have a building wide sprinkler system. There are limited area sprinklers in the following locations: Bookkeeper 110, Janitor 201, 508, 702, Storage 300B, 301B, 302B, 303B, 704A, 704B, 709C, 723, A/V Storage 600B, Stage 710 and Receiving On sheet F1.1, where the finish schedule indicates wall finish 1- Existing to Remain, the existing finishes on the wall are to remain. Do not paint the wall. 12. On sheet F1.1, acoustic walls panels are to be painted flat. 13. Specification section Athletic Equipment allows for other manufacturers, subject to compliance with the specifications and all their requirements. 14. Exterior basketball backstops and backboards are not required for this project. 15. The 6 interior basketball backstops are existing to remain. The backboards and goals are to be replaced. Height adjusters if present are existing to remain. Provide 2 safety straps for the 2 existing forward folding back stops. 16. Provide wall pads as indicated on sheet A The translucent core insulating glass units called for in specification section , 2.3 are not required for this project. 18. The Glass Type #2 called for in specification section , 2.11 is not required for this project. 19. The stage curtains are indicated by note N20 on Stage 710, on sheet A1.3. END OF ADDENDUM #1 PURCHASING OFFICE P.O. BOX 389, MANASSAS, VA , FAX

4 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The drawings and general provisions of the Contract Documents apply to this Section. 1.2 SUMMARY A. This Section includes computer based fault current, overcurrent protective device coordination and studies including the setting of these devices. Confirm fault current rating of equipment and advise PWCS of any deficiencies. B. Fault current study shall be prepared and submitted during the first 90 days of the project. 1.3 SUBMITTALS REQUIRED A. The study shall be submitted during the first 90 days of the project. 1.4 QUALITY ASSURANCE A. Studies shall use computer programs that are distributed nationally and are in wide use. Software algorithms shall comply with requirements of standards and guides specified in this Section. Manual calculations are not acceptable. B. Study shall be prepared by a firm regularly involved in performing coordination studies. 1. Pre-approved firm: a. Power Systems Engineering, Springfield, VA C. Comply with IEEE 399 for general study procedures. D. Comply with IEEE 242 for short circuit currents and coordination time intervals. PART 2 - PRODUCTS 2.1 COMPUTER SOFTWARE PROGRAM REQUIREMENTS A. Comply with IEEE 399. B. Analytical features of fault current study computer software program shall include "mandatory," "very desirable" and "desirable" features as listed in IEEE 399, Table 7-4. C. Computer software program shall be capable of plotting and diagramming time current characteristic curves as part of its output. Computer software program shall report device settings and ratings of all overcurrent protective devices. River Oaks Elementary School Renewal Arc-Flash Study

5 PART 3 - EXECUTION 3.1 EXAMINATION A. Examine project overcurrent protective device submittals for compliance with electrical distribution system coordination requirements and other conditions affecting performance. Power Company transformer(s), switchboard(s), MDP(s), panelboard(s), transformer(s) and feeder(s) shall be included in the coordination study. B. Proceed with coordination study only after relevant equipment submittals have been assembled. Overcurrent protective devices not submitted for approval with coordination study may not be used in study. C. All revisions and corrections made to the study, whether owner or contractor initiated, shall be included in original project costs. No additional compensation will be made to the contractor for revisions and corrections to the study. 3.2 ARC-FLASH STUDY A. ARC-FLASH STUDY REPORT CONTENT 1. Study descriptions, purpose, basis and scope. 2. One-line diagram, showing the following: a. Protective device designations and ampere ratings. b. Cable size and lengths. c. Transformer kilovolt ampere (kva) and voltage ratings. d. Motor and generator designations and kva ratings. e. Switchgear, switchboard, motor-control center and panelboard designations. 3. Arc-Flash Study Output: a. Interrupting Duty Report: Three-phase and unbalanced fault calculations, showing the following for each overcurrent device location: 1) Voltage. 2) Calculated symmetrical fault-current magnitude and angle. 3) Fault-point X/R ratio. 4) No AC Decrement (NACD) ratio. 5) Equivalent impedance. 6) Multiplying factors for 2-, 3-, 5-, and 8-cycle circuit breakers rated on a symmetrical basis. 7) Multiplying factors for 2-, 3-, 5-, and 8-cycle circuit breakers rated on a total basis. 4. Incident Energy and Flash Protection Boundary Calculations: a. Arcing fault magnitude. b. Protective device clearing time. c. Duration of arc. d. Arc-flash boundary. e. Working distance. f. Incident energy. River Oaks Elementary School Renewal Arc-Flash Study

6 g. Hazard risk category. h. Recommendations for arc-flash energy reduction. 5. Fault study input data, case descriptions, and fault-current calculations including a definition of terms and guide for interpretation of the computer printout. B. ARC-FLASH WARNING LABELS 1. The label shall have an orange header with the wording, "WARNING, ARC- FLASH HAZARD," and shall include the following information taken directly from the arc-flash hazard analysis: a. Location designation. b. Nominal voltage. c. Flash protection boundary. d. Hazard risk category. e. Incident energy. f. Working distance. g. Engineering report number, revision number, and issue date. 2. Labels shall be machine printed, with no field-applied markings. C. ARC-FLASH HAZARD ANALYSIS 1. Comply with NFPA 70E and its Annex D for hazard analysis study. 2. Calculate maximum and minimum contributions of fault-current size. a. The minimum calculation shall assume that the utility contribution is at a minimum and shall assume no motor load. b. The maximum calculation shall assume a maximum contribution from the utility and shall assume motors to be operating under full-load conditions. 3. Calculate the arc-flash protection boundary and incident energy at locations in the electrical distribution system where personnel could perform work on energized parts. 4. Include medium- and low-voltage equipment locations, except equipment rated 240-V ac or less fed from transformers less than 125 kva. 5. Safe working distances shall be specified for calculated fault locations based on the calculated arc-flash boundary, considering incident energy of 1.2 cal/sq.cm. 6. Incident energy calculations shall consider the accumulation of energy over time when performing arc-flash calculations on buses with multiple sources. Iterative calculations shall take into account the changing current contributions, as the sources are interrupted or decremented with time. Fault contribution from motors and generators shall be decremented as follows: a. Fault contribution from induction motors should not be considered beyond three to five cycles. b. Fault contribution from synchronous motors and generators should be decayed to match the actual decrement of each as closely as possible (e.g., contributions from permanent magnet generators will typically decay from 10 per unit to three per unit after 10 cycles). 7. Arc-flash computation shall include both line and load side of a circuit breaker as follows: a. When the circuit breaker is in a separate enclosure. b. When the line terminals of the circuit breaker are separate from the work location. River Oaks Elementary School Renewal Arc-Flash Study

7 8. Base arc-flash calculations on actual overcurrent protective device clearing time. Cap maximum clearing time at two seconds based on IEEE 1584, Section B.1.2. D. POWER SYSTEM DATA 1. Obtain all data necessary for the conduct of the arc-flash hazard analysis. a. Verify completeness of data supplied on the one-line diagram on Drawings. b. For new equipment, use characteristics submitted under the provisions of action submittals and information submittals for this Project. c. For existing equipment, whether or not relocated, obtain required electrical distribution system data by field investigation and surveys, conducted by qualified technicians and engineers. 2. Electrical Survey Data: Gather and tabulate the following input data to support study. Comply with recommendations in IEEE 1584 and NFPA 70E as to the amount of detail that is required to be acquired in the field. Field data gathering shall be under the direct supervision and control of the engineer in charge of performing the study, and shall be by the engineer or its representative who holds NETA ETT Level III certification or NICET Electrical Power Testing Level III certification. a. Product Data for overcurrent protective devices specified in other Sections and involved in overcurrent protective device coordination studies. Use equipment designation tags that are consistent with electrical distribution system diagrams, overcurrent protective device submittals, input and output data, and recommended device settings. b. Obtain electrical power utility impedance at the service. c. Power sources and ties. d. Short-circuit current at each system bus, three phase and line-to-ground. e. Full-load current of all loads. f. Voltage level at each bus. g. For transformers, include kva, primary and secondary voltages, connection type, impedance, X/R ratio, taps measured in per cent, and phase shift. h. For reactors, provide manufacturer and model designation, voltage rating and impedance. i. For circuit breakers and fuses, provide manufacturer and model designation. List type of breaker, type of trip and available range of settings, SCCR, current rating, and breaker settings. j. Generator short-circuit current contribution data, including short-circuit reactance, rated kva, rated voltage, and X/R ratio. k. For relays, provide manufacturer and model designation, current transformer ratios, potential transformer ratios, and relay settings. l. Busway manufacturer and model designation, current rating, impedance, lengths, and conductor material. m. Motor horsepower and NEMA MG 1 code letter designation. n. Low-voltage cable sizes, lengths, number, conductor material and conduit material (magnetic or nonmagnetic). o. Medium-voltage cable sizes, lengths, conductor material, and cable construction and metallic shield performance parameters. River Oaks Elementary School Renewal Arc-Flash Study

8 E. LABELING 1. Apply one arc-flash label for 600-V ac, 480-V ac, and applicable 208-V ac panelboards and disconnects and for each of the following locations: 2. Motor-control center. 3. Low-voltage switchboard. 4. Switchgear. 5. Medium-voltage switch. 6. Control panel. F. APPLICATION OF WARNING LABELS 1. Install the arc-fault warning labels under the direct supervision and control of the Arc-Flash Study Specialist. END OF SECTION River Oaks Elementary School Renewal Arc-Flash Study

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number PART 1 GENERAL 01 02 03 04 SCOPE Furnish and install Manual Transfer Switches (MTS) and

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

B. Provide liquid-filled secondary substation transformers as indicated on drawings.

B. Provide liquid-filled secondary substation transformers as indicated on drawings. SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED

More information

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? How to compare apples-to-apples bids. By R. Dee Jones, P.E., AVO Training Institute Electrical Engineering Division Manager/Principal

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES Guidelines effective March 5, 2007 NES is committed to providing safe, reliable electric service at a reasonable price for all of our customers. These guidelines offer direction for activities relating

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Low Voltage Switchgear Construction Checklist (under 500 kva)

Low Voltage Switchgear Construction Checklist (under 500 kva) Low Voltage Switchgear Checklist (under 500 kva) Project: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

B. Accept materials on site in original factory packaging, labeled with manufacturer s identification.

B. Accept materials on site in original factory packaging, labeled with manufacturer s identification. SECTION 26 05 02 - BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL 1.1 SUMMARY A. Work Included: Furnish all labor, material, services and skilled supervision necessary for the construction, erection, installation,

More information

SMALL GENERATOR INTERCONNECTION REQUEST (Application Form)

SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Attachment 2 Transmission Provider: Bluestem Electric Cooperative, Inc. Designated Contact Person: Kevin Heptig Address: P.O. Box 5, Wamego, Kansas

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

Unit Substation Transformer Construction Checklist (under 500 kva)

Unit Substation Transformer Construction Checklist (under 500 kva) Unit Substation Transformer Checklist (under 500 kva) Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999

The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 CANADIAN ELECTRICAL CODE 1 The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 Repealed by Chapter E-6.3 Reg 8 (effective June 24, 2003). Formerly Chapter E-6.3 Reg 6 (effective March

More information

Temporary Wiring Practices And Guidelines For NECA. National Electrical Contractors Association Omaha, Nebraska

Temporary Wiring Practices And Guidelines For NECA. National Electrical Contractors Association Omaha, Nebraska Temporary Wiring Practices And Guidelines For NECA National Electrical Contractors Association Omaha, Nebraska Table of Contents I. Planning II. Lighting and Power III. Maintenance IV. Inspections V. Routing

More information

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION

ITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION SECTION 74 AIRPORT OBSTRUCTION LIGHTS (FAA L-119) 74-1 GENERAL The Contractor shall perform all work required by the plans and specifications for construction of obstruction lights in accordance with the

More information

Proposals and Process 2017 National Electrical Code

Proposals and Process 2017 National Electrical Code Proposals and Process 2017 National Electrical Code for Solar America Board for Codes and Standards Stakeholder Meeting; October 23, 2014 Ward Bower Ward Bower Innovations LLC Introduction The New NFPA

More information

For the 2008 Code, the minimum clear distances were revised to reflect an accurate metric conversion (also known as a soft conversion).

For the 2008 Code, the minimum clear distances were revised to reflect an accurate metric conversion (also known as a soft conversion). II. 600 Volts, Nominal, or Less 110.26 Spaces About Electrical Equipment. Sufficient access and working space shall be provided and maintained about all electrical equipment to permit ready and safe operation

More information

UNDERGROUND SERVICES SECONDARY

UNDERGROUND SERVICES SECONDARY Reference UNDERGROUND SERVICES SECONDARY Underground services secondary... U- 1 General requirements for underground service... U- 2 Name of parts for underground service... U- 3 Conduit layouts... U-

More information

General Electrical Safety Awareness Course: E100

General Electrical Safety Awareness Course: E100 General Electrical Safety Awareness Course: E100 30 minutes No No All "non-qualified" or "unqualified" employees Facility or Plant Management All production personnel Office staff and personnel Any general

More information

Electric Service Standards

Electric Service Standards V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are

More information

2017 NEC Changes for Renewable Energy Systems Session one by Christopher LaForge

2017 NEC Changes for Renewable Energy Systems Session one by Christopher LaForge 2017 NEC Changes for Renewable Energy Systems Session one 2017 by Christopher LaForge Christopher LaForge IREC Certified Master Trainer NABCEP Certified Photovoltaic Installation Professional 30 years

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

CITY OF GRANDE PRAIRIE

CITY OF GRANDE PRAIRIE Inspection Services CITY OF GRANDE PRAIRIE HOMEOWNER S PERMIITS AND WIRING GUIDE FOR ELECTRICAL INSTALLATIONS 2016 INDEX Page Applying for an Electrical Permit 3 Permit Application Requirements 3 Permit

More information

GENERAL PLAN REVIEW REQUIREMENTS

GENERAL PLAN REVIEW REQUIREMENTS GENERAL PLAN REVIEW REQUIREMENTS Cover Letter A letter (or an authorized pre-printed form) authorizing CCIS to perform the Plan Review is required. CCIS performs plan reviews for the ICC International

More information

REQUEST FOR QUOTATION (RFQ)

REQUEST FOR QUOTATION (RFQ) Engineering Support Program (ESP) USAID Contract No. AID-306-C-16-00010 REQUEST FOR QUOTATION (RFQ) To: From: Offerors Tetra Tech ESP Issuance Date: November 22, 2017 Closing Date: Subject: Reference:

More information

BUREAU Joe Iuviene, AIA January 20, 2017

BUREAU Joe Iuviene, AIA January 20, 2017 architectural BUREAU Joe Iuviene, AIA January 20, 2017 Alterations & Additions NEW TOWN HALL for TOWN OF AUSTERLITZ 816 State Route 203, Spencertown, New York 12165 ADDENDUM NO. 1 This addendum amends

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 PART 1 GENERAL 1.01 DESCRIPTION A. Section includes requirements for an electrical grounding system, including electrodes, grounding rods, connectors, insulators, equipment grounding and

More information

ELECTRICAL SAFETY FOLLOW UP INSPECTION REPORT (4th)

ELECTRICAL SAFETY FOLLOW UP INSPECTION REPORT (4th) Factory Name Address Joyna Bazer Road, Jamirdia, Valuka Factory ID 9504 Electrical Safety dates Initial Date 06/07/2014 Date of 5 th Follow Up Report Received Date 07/27/2015 Date of 6 th Follow Up Date

More information

Emergency, Legally Required, and Optional Standby Power Systems

Emergency, Legally Required, and Optional Standby Power Systems Mike Holt s Illustrated Guide to Emergency, Legally Required, and Optional Standby Power Systems Rule 220.87, Articles 445, 700, 701, and 702 Based on the 2011 NEC Extracted from Mike Holt s Illustrated

More information

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows: SECTION 16130 (Master Template Final-05) ELECTRICAL BOXES PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide boxes for electrical equipment and wiring devices as follows: 1. Wall and ceiling outlet boxes.

More information

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 48-05 Van Dam Street Long Island City, NY 11101 ELECTRIC METER SHOP DEPARTMENT METER ENGINEERING SPECIFICATION MES-350 REVISION 3 June 2016 EFFECTIVE DATE

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Updated format, division title, and removed references to other sections. - mgl44 A. Summary This section contains design criteria for the

More information

ADDENDUM NO. TWO TO THE REQUEST FOR PROPOSAL (RFP) DOCUMENTS April 25, 2016

ADDENDUM NO. TWO TO THE REQUEST FOR PROPOSAL (RFP) DOCUMENTS April 25, 2016 ADDENDUM NO. TWO TO THE REQUEST FOR PROPOSAL (RFP) DOCUMENTS April 25, 2016 General: The following changes, additions, or deletions shall be made to the following documents; all other conditions shall

More information

Building Codes in Effect: 2010 California Building, Residential, Fire, Energy and Electrical Codes, including Article 690.

Building Codes in Effect: 2010 California Building, Residential, Fire, Energy and Electrical Codes, including Article 690. AGUA CALIENTE BAND OF CAHUILLA INDIANS A SOVEREIGN TRIBAL GOVERNMENT Planning & Development Department Building and Safety Division 5401 Dinah Shore Drive Palm Springs, CA 92264 (760) 669-6800 RESIDENTIAL

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement Draft 11/17/08 Utility transformer issues began surfacing last year with questions of enforcement responsibilities due to utility

More information

(Condensed from National Electric Code)

(Condensed from National Electric Code) WIRING, SPECIFICATIONS, INSPECTION, AND METER INSTALLATION PROCEDURES FOR RESIDENTIAL CUSTOMERS SERVED BY SOUTHWEST ARKANSAS ELECTRIC COOPERATIVE CORPORATION Effective April 1, 1974 Revised February 3,

More information

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

DESIGN DEVELOPMENT PHASE

DESIGN DEVELOPMENT PHASE UNIVERSITY OF MICHIGAN DESIGN DELIVERABLES FEBRUARY 2012 As part of the deliverables for formal UM review at each of the major phases of design listed below, the Design Professional shall submit this "Design

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS SECTION 26 05 05 BASIC ELECTRICAL MATERIALS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the limited scope construction materials and methods for application with electrical installations as follows:

More information

Telecommunication Spaces

Telecommunication Spaces Telecommunication Spaces October 19, 2016 Page 1 Revision History Telecommunication Spaces Standard Effective Date Email Version Contact Phone OIT-TS strevena@csustan.edu 1.0 Stan Trevena 209.667.3137

More information

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION

More information

ELECTRICAL SAFE WORK PRACTICES

ELECTRICAL SAFE WORK PRACTICES ELECTRICAL SAFE WORK PRACTICES I. PURPOSE To establish minimum acceptable standards for AC and DC electrical safe work practices. The program includes requirements for the training of qualified and unqualified

More information

Fairfax County, Virginia

Fairfax County, Virginia Fairfax County, Virginia Typical Finished Basement Details Based on the 2009 International Residential Code CONTENTS General Requirements... 2 Emergency Escape and Rescue... 2 Wall Construction... 3 Floor/ceiling

More information

FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR

FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR FOUR FOLD DOORS-WITH SINGLE OVERHEAD MTD OPERATOR Section 083713- Four Fold Doors- With Single Overhead Mounted Operator Part 1-General 1.1 Related Document: A. Drawing and general provisions of contract,

More information

Electrical Protection Methods and Devices SAMPLE. Learner Workbook Version 1. Training and Education Support Industry Skills Unit Meadowbank

Electrical Protection Methods and Devices SAMPLE. Learner Workbook Version 1. Training and Education Support Industry Skills Unit Meadowbank Electrical Protection Methods and Devices Learner Workbook Version 1 Training and Education Support Industry Skills Unit Meadowbank Product Code: 5635 Table of Contents Introduction... 5 1. Protection

More information

Implementing and Managing Electrical Safety Programs

Implementing and Managing Electrical Safety Programs Implementing and Managing Electrical Safety Programs Donny Snyder Vice President Martin Technical, Inc donnys@martechnical.com 866-234-6890 Ext. #2 1. Audits 70E, NEC, 70B 2. Written Policy 3. Arc Flash

More information

Electrical Safety ESWP and NFPA 70E Electrical Safe Work Practice

Electrical Safety ESWP and NFPA 70E Electrical Safe Work Practice Electrical Safety ESWP and NFPA 70E Electrical Safe Work Practice 1 Contact Info: Jon Clark, CESCP Faith Technologies, Inc. 2662 American Drive Appleton, WI 54944 920-450-2126 www.faithtechnologies.com

More information

CHAPTER 5 METERING REQUIREMENTS

CHAPTER 5 METERING REQUIREMENTS CHAPTER 5 METERING REQUIREMENTS CHAPTER 5 METERING REQUIREMENTS 5.1 General 1. All installations connected to, or intended to be connected to HK Electric s supply of electricity must comply with HK Electric

More information

NOTICE OF ADDENDUM ADDENDUM 2 CONTRACT NO PROJECT NO UNIT WELL 31 WATER TREATMENT PLANT

NOTICE OF ADDENDUM ADDENDUM 2 CONTRACT NO PROJECT NO UNIT WELL 31 WATER TREATMENT PLANT February 20, 2017 NOTICE OF ADDENDUM ADDENDUM 2 CONTRACT NO. 7500 PROJECT NO. 10434 UNIT WELL 31 WATER TREATMENT PLANT Revise and amend the contract document(s) for the above project as stated in this

More information

Service plans enhance the benefits of preventive maintenance programs

Service plans enhance the benefits of preventive maintenance programs Service plans enhance the benefits of preventive maintenance programs White Paper Document 1910DB1612 by Charles Alvis Executive summary Companies are continually being tasked by management to increase

More information

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018)

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) PERMIT SUBMITTAL CHECKLIST: Signed and completed Building Permit application form. A separate Electrical permit is required from

More information

Basic Requirements for Residential Electrical Installations

Basic Requirements for Residential Electrical Installations Basic Requirements for Residential Electrical Installations Wayne County Building Department 428 West Liberty Street Wooster, Ohio 44691 Phone: 330-287-5525 Fax: 330-287-5649 This brochure is intended

More information

DIVISION 26 ELECTRICAL 2006 Edition, Published January 1, 2006; Division Revision Date: October 16, 2017

DIVISION 26 ELECTRICAL 2006 Edition, Published January 1, 2006; Division Revision Date: October 16, 2017 2006 Edition, Published January 1, 2006; Division Revision Date: October 16, 2017 26 00 00. ELECTRICAL 26 00 03. GENERAL PROVISION.1 QUALIFICATIONS OF CABLE SPLICERS: Refer to Division 33..2 INFORMATION

More information

THIS ADDENDUM MUST BE ACKNOWLEDGED. THIS ADDENDUM SHALL BECOME A PART OF THIS SOLICITATION. Amend Invitation to Bid 15-BS-2353 as follows:

THIS ADDENDUM MUST BE ACKNOWLEDGED. THIS ADDENDUM SHALL BECOME A PART OF THIS SOLICITATION. Amend Invitation to Bid 15-BS-2353 as follows: Denver Public Schools Purchasing Department 1617 S. Acoma St. Denver, Colorado 80223 INVITATION TO BID 15-BS-2353 ADDENDUM NUMBER TWO March 12, 2015 THIS ADDENDUM MUST BE ACKNOWLEDGED. THIS ADDENDUM SHALL

More information

Customer Requirements Customer-owned Transformer Vault Room

Customer Requirements Customer-owned Transformer Vault Room Scope This standard documents the requirements for customer-owned vault rooms containing transformers and switches that are owned, operated, and maintained by Tacoma Power. It does not address transformer

More information

UFGS (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 35 33.00 40 (August 2013) --------------------------------- Preparing Activity: NASA Superseding UFGS-26 35 33.00 40 (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

TYPICAL INSTALLATION INSTRUCTIONS

TYPICAL INSTALLATION INSTRUCTIONS TYPICAL INSTALLATION INSTRUCTIONS Environment One Grinder Pump Feature Identification 1. Grinder Pump Basin High density polyethylene (HDPE) 2. Accessway Cover Painted Steel 3. Electrical Quick Disconnect

More information

SECTION COOLING TOWER

SECTION COOLING TOWER PART 1 GENERAL 1.1 SECTION INCLUDES A. Mechanical induced draft Cooling Tower B. Controls C. Ladder and handrails 1.2 REFERENCES SECTION 23 65 00 COOLING TOWER A. ANSI/AFBMA 9 - Load Rating and Fatigue

More information

Solar PV System Code Compliance Best Practices, 2017 NEC Updates, and Opportunities for Improvement

Solar PV System Code Compliance Best Practices, 2017 NEC Updates, and Opportunities for Improvement Solar PV System Code Compliance Best Practices, 2017 NEC Updates, and Opportunities for Improvement MassCEC Webinar April 2017 Presented by: Matt Piantedosi Manager of Solar Field Operations The Cadmus

More information

Installation, Inspection and Maintenance of Dry Type Transformers

Installation, Inspection and Maintenance of Dry Type Transformers Dry Type TX 1 of 8 Installation, Inspection and Maintenance of Dry Type Page 1 of 8 Dry Type TX 2 of 8 Table Of Contents Page Number 1. General... 3 2. Installation... 3 3. Safety Inspections... 4 4. Safety

More information

INSTALLATION INSTRUCTIONS FOR ELECTRICAL CONTRACTORS

INSTALLATION INSTRUCTIONS FOR ELECTRICAL CONTRACTORS INSTALLATION INSTRUCTIONS FOR ELECTRICAL CONTRACTORS Rev. 1.5 1.10.13 Toll free (800) 288-6000 or www.hubbell-wiring.com P a g e 0 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS WARNING- When using

More information

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 14 - CONVEYING EQUIPMENT DESIGN STANDARDS SECTION

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 14 - CONVEYING EQUIPMENT DESIGN STANDARDS SECTION PART 1 - GENERAL 1.01 Elevator manufacturer to provide equipment and installation warranty and maintenance services for at least one year after acceptance. This requires routine monthly inspection, emergency

More information

Fixed Electrical Testing

Fixed Electrical Testing Fixed Electrical Testing Essential Facts for Business Owners January 2017 Fixed Electrical Testing Employers must comply with the Electricity at Work Regulations 1989, made under the Health and Safety

More information

Typical Finished Basement Details

Typical Finished Basement Details Albemarle County, Virginia Typical Finished Basement Details Based on the 2012 Virginia Residential Code Finished basements must be constructed in conformance with these details. For requirements, details

More information

PIP PCEPA003 Process Analyzer System Field Installation Guidelines

PIP PCEPA003 Process Analyzer System Field Installation Guidelines January 2016 Process Control PIP PCEPA003 Process Analyzer System Field Installation Guidelines PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities,

More information

BRADDOCK ROAD YOUTH CLUB

BRADDOCK ROAD YOUTH CLUB BRADDOCK ROAD YOUTH CLUB P.O. Box 2084 Fairfax Virginia 22031 July 25. 2015 Re: Request for Proposals for Kings Park Shopping Center Community Center Dear Prospective Contractor: Braddock Road Youth Club

More information

Architectural Services

Architectural Services Architectural Services 2016 Capital Improvement Program Request for Proposal Number: 18-20 Title of the Projects: Renovations to Weaver Middle School Procurement Department Bibb County School District

More information

LOGAN SCHOOL SCHOOL WITHOUT WALLS AT LOGAN

LOGAN SCHOOL SCHOOL WITHOUT WALLS AT LOGAN INITIAL YEAR BUILT 1935 BUILDING AREA 47,200 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 418 WARD 6 PROPOSED PROGRAM CAPACITY 450 Site Plan LOGAN - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION HS

More information

ELECTRIC METERING GENERAL

ELECTRIC METERING GENERAL 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 EQUIPMENT 5.0 METER REQUIREMENTS 6.0 METER FACILITIES 7.0 ELECTRICAL CONNECTIONS 2.0 SCOPE This guide covers general requirements and codes for

More information

1.16. Sound Attenuated Enclosure

1.16. Sound Attenuated Enclosure 1.15 UL 891 Generator Main Circuit Breaker Switchboard An insulated case, 4000 amp circuit breaker shall be provided on each genset. It shall be 100% rated and UL approved. Provide the circuit breaker

More information

PORT OF SAN FRANCISCO ELECTRICAL CODE. Based on the 2016 California Electrical Code

PORT OF SAN FRANCISCO ELECTRICAL CODE. Based on the 2016 California Electrical Code 2016 PORT OF SAN FRANCISCO ELECTRICAL CODE Based on the 2016 California Electrical Code The complete 2016 Port of San Francisco Electrical Code adopts and amends the 2013 edition of the California Electrical

More information

Facility Interconnection Requirements

Facility Interconnection Requirements Facility Interconnection Effective 1/1/2016 1. Purpose Facility Interconnection Facility Interconnection (FAC-001-2) To avoid adverse impacts on the reliability of the Bulk Electric System (BES), RPU documents

More information

SECTION ALTERNATES

SECTION ALTERNATES SECTION 01 23 00 - ALTERNATES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

Electrical Panel Boards (Be sure to attach make, model, specifications, technical data and warranty information with the bid response)

Electrical Panel Boards (Be sure to attach make, model, specifications, technical data and warranty information with the bid response) UNIVERSITY OF MASSACHUSETTS-AMHERST Procurement Department 407 Goodell Bldg., 140 Hicks Way Amherst, MA 01003-9334 Voice: 413-545-0361 Fax: 413-545-1643 Email: procurement@admin.umass.edu Web Page: www.umass.edu/procurement

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

Communications Page 1 of 9

Communications Page 1 of 9 Page 1 of 9 Last Update: April 23 rd, 2014 Introduction Design In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a

More information

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.

This guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project. SECTION 14651 FREE STANDING JIB CRANE ***** Gorbel, Inc. manufacturers a broad range of material handling cranes including monorail, bridge, gantry, and jib cranes. Numerous work station and industrial

More information

Attachment 3 Statement of Work Statement PROJECT NUMBER MA DIRECTORATE OF PUBLIC WORKS FORT BRAGG, NORTH CAROLINA

Attachment 3 Statement of Work Statement PROJECT NUMBER MA DIRECTORATE OF PUBLIC WORKS FORT BRAGG, NORTH CAROLINA Request for Task Order Proposal Number: Attachment 3 Statement of Work Statement PROJECT NUMBER MA-00006-15 DIRECTORATE OF PUBLIC WORKS FORT BRAGG, NORTH CAROLINA PROJECT TITLE: Restore one Men s and one

More information

ROOFTOP EQUIPMENT Guide

ROOFTOP EQUIPMENT Guide ROOFTOP EQUIPMENT Guide VERSION 1.0 REVISED 09/24/15 GENERAL The purpose of this inspection checklist is to clarify the minimum building code requirements when installing rooftop equipment and preparing

More information

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS

PHYSICAL FACILITIES Consultant s Handbook Division 27 COMMUNICATIONS 0000 COMMUNICATIONS 1 Introduction 1.1 In the design of Telecommunications systems in Purdue facilities, the overall consideration should be to understand and treat telecom as a utility. It should be assumed that all new

More information

Power Zone Center. Your solution for power distribution and control systems

Power Zone Center. Your solution for power distribution and control systems Power Zone Center Your solution for power distribution and control systems The Strength of One Powerful When you need to install a new power distribution center in your facility, you need it done in fastest

More information

TYP. SINGLE PLY ROOFING ROOF SHEETING BROAN VENT CAP #10 x 1" GASKETED SMS TYP. 4 SIDES 8" FRAMED CURB HVAC SYSTEMS "BASIS OF DESIGN" ROOF INSULATION R-19 WALL INSULATION R-13 LIGHTING EFFIECNCY PER STANDARDS

More information

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO

CITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO SECTION 01010 - SCOPE OF WORK PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General provisions of Contract, General Conditions and Technical Specification Sections, apply to this Section. 1.02 PROJECT DESCRIPTION

More information

Building Regulations; Construction 11

Building Regulations; Construction 11 Building Regulations; Construction 11 b. Ceilings or roofs shall have a minimum of an "R" factor of 12; and c. Where the roof serves also as the finished ceiling a vent space of two inches shall be required

More information

Why Do I Need a Permit? D ID Y OU K N OW? Protects property values. Makes Selling Property Easier. Site Plan Page 2. Plan Requirements Page 2

Why Do I Need a Permit? D ID Y OU K N OW? Protects property values. Makes Selling Property Easier. Site Plan Page 2. Plan Requirements Page 2 Swimming Pools Building Guide for Homeowners Why Do I Need a Permit? D ID Y OU K N OW? There are many important reasons to obtain building permits and to have inspections performed for your construction

More information

Seal Harbor Development 1 Nagog Park Acton, MA 01720

Seal Harbor Development 1 Nagog Park Acton, MA 01720 Seal Harbor Development 1 Nagog Park Acton, MA 01720 Specifications for Ocean Mist Villages Foundation and Concrete Floors Footings All footings are constructed and poured with 3000 lb mix, continuous

More information

TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX

TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ 08014 856-467-3626--- FAX 856-467-9260 Application for Certificate of Occupancy for Change of Occupancy Pursuant to Chapter 119 of the Township

More information

CONSULTATION MEETING: Adoption of the 2015 edition of the Canadian Electrical Code

CONSULTATION MEETING: Adoption of the 2015 edition of the Canadian Electrical Code CONSULTATION MEETING: Adoption of the 2015 edition of the Canadian Electrical Code April 29, 2015 (10:00am-11:30am) Safe technical systems. Everywhere. Teleconference: 1-866-643-2939 4442830# Welcome!

More information

CONTACT LIST DOORS IN THE PATH OF EGRESS TRAVEL SHALL MEET THE REQUIREMENTS OF ICC / ANSI A117.1 : SECTION MANEUVERING CLEARANCES AT DOORS

CONTACT LIST DOORS IN THE PATH OF EGRESS TRAVEL SHALL MEET THE REQUIREMENTS OF ICC / ANSI A117.1 : SECTION MANEUVERING CLEARANCES AT DOORS DOORS TO EXTERIOR HAVE CLOSURES & LATCHES AND MEET THE REQUIREMENTS OF ICC / ANSI A7. : SECTION 404.2.7 DOOR HARDWARE SECTION 404.2.8 CLOSING SPEED SECTION 404.2.9 DOOR OPENING FORCE SECTION 404.2.5 TRESHOLDS

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less) SECTION 260523 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less) PART 1 - GENERAL 1.1 SUMMARY A. Related Documents: 1. Drawings and general provisions of the Subcontract apply

More information

ALBUQUERQUE PUBLIC SCHOOLS for MONTESSORI OF THE RIO GRANDE CHARTER SCHOOL

ALBUQUERQUE PUBLIC SCHOOLS for MONTESSORI OF THE RIO GRANDE CHARTER SCHOOL ADDENDUM NO. 2 To all holders of Contract Documents for the construction of: ALBUQUERQUE PUBLIC SCHOOLS for MONTESSORI OF THE RIO GRANDE CHARTER SCHOOL Please note this Addendum forms a part of the Contract

More information

START RIGHT A G U I D E T O L + I S E R V I C E S

START RIGHT A G U I D E T O L + I S E R V I C E S START RIGHT A G U I D E T O L + I S E R V I C E S BUSINESS OWNERS Protect your project with L+I The Department of Licenses and Inspections (L+I) is the most indispensable resource for developers, contractors,

More information

STREET LIGHTING. Springville City Power standard street lights will be installed in accordance with Springville City Power's Line Extension Policy.

STREET LIGHTING. Springville City Power standard street lights will be installed in accordance with Springville City Power's Line Extension Policy. General The following general requirements shall apply to street lights installed in new underground residential subdivisions or developments located within the service area of Springville City Power (within

More information

Article 300: Wiring Methods And Materials

Article 300: Wiring Methods And Materials Part E: Code Book Questions Article 300: Wiring Methods And Materials 1.! Conductors of A.C. or D.C. circuits rated 600 volt or less, shall be permitted to occupy the same! conduit if.! (a)!conductors

More information

Section BUILDINGS, SHELTERS, ENCLOSURES

Section BUILDINGS, SHELTERS, ENCLOSURES Section 13121 BUILDINGS, SHELTERS, ENCLOSURES Part 1 GENERAL 1.1 SECTION INCLUDES 1.2 A. Pre-engineered buildings. B. Pre-engineered shelters. C. Pre-engineered enclosures. D. Electrical wiring and devices

More information

PLANS REVIEW CRITERIA - COMMERCIAL BUILDINGS

PLANS REVIEW CRITERIA - COMMERCIAL BUILDINGS PLANS REVIEW CRITERIA - COMMERCIAL BUILDINGS NOTE: Building Code compliance is the obligation of design professionals and/or contractors. Plan review and inspection guidelines are to be used to ensure

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 27 29 (April 2006) Change 1-08/13 -------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-16407 (August 2004) UNIFIED FACILITIES GUIDE

More information

NEMA Standards Publication ANSI/NEMA PB

NEMA Standards Publication ANSI/NEMA PB ANSI Approval Date October 14, 2003 NEMA Standards Publication ANSI/NEMA PB 1.1-2002 General Instructions for Proper Installation, Operation, and Maintenance of Panelboards Rated 600 Volts or Less Published

More information

ComEd Customer Requirements for Proper Installation of Metering Equipment Residential and Commercial Customers

ComEd Customer Requirements for Proper Installation of Metering Equipment Residential and Commercial Customers 1 st Edition ComEd Customer Requirements for Proper Installation of Metering Equipment Residential and Commercial Customers Dear customer, This booklet contains some of the most common metering equipment

More information