Seismic Installation Manual

Size: px
Start display at page:

Download "Seismic Installation Manual"

Transcription

1 Seismic Installation Manual

2 This manual provides the design strength capacities and installation guidelines for the Restraint systems brace components for use in the design of an overall bracing/restraint system for suspended nonstructural components, equipment, and systems. 2

3 Contents / Page Number Section 1: Introduction 1.1 Scope Kit Contents System Strengths Description of Bracing Assemblies Transverse Longitudinal Way Brace Spacing Guidelines Section 2: Seismic Bracing Kit and Components Overview 2.1 Kit Contents Eyelet & Fastener Brackets 15 Section 3: Seismic Brace Installation 3.1 Basic Brace Layout Seismic Fastener Installation Seismic Bracket Installation Retrofi t Bracket Installation Bracket Stacking Installation 19 Section 4: Brace Anchor/Attachment Installation 4.1 Basic Guidelines for Concrete Structures Concrete Wall Concrete Ceiling/Roof Concrete Over Metal Decking Concrete Block Wall Steel Beam Bar Joists Transverse or Longitudinal Way Steel Purlins Timber Members 30 Section 5: Restraint Layout Guide 5.1 Round Ductwork 5.5 Insulated Pipe & Conduit Transverse Transverse Longitudinal Longitudinal Way Way Rectangular Ductwork 5.6 Trapeze Supported Piping or Conduit Transverse Transverse Longitudinal Longitudinal Way Way Flat or Oval Ductwork 5.7 Electrical Cable/Ladder/Basket Tray Transverse Transverse Longitudinal Longitudinal Way Way SIGNATURE REQ D Un-Insulated Pipe & Conduit Transverse Longitudinal 41 Todd R Hawkinson Professional Engineer Way Rectangular Units of Equipment Way Linear 4-Way 53 DATE: XX/XX/2009 3

4 1.1 Introduction / Scope Restraint systems are specifi cally designed and engineered to brace and secure nonstructural equipment and components within a building or structure to minimize earthquake damage to suspended components. Restraint systems are ideal for use on nonstructural components and equipment requiring seismic design, such as in essential facilities that are required for emergency operations in the aftermath of an earthquake. Detailed in this manual are bracing guidelines for a variety of nonstructural components, equipment, and systems. Actual restraint requirements for some sites may vary from these guidelines, and these site-specifi c restraint installations are not limited to the guidelines detailed here. However, ensure that any deviations from the guidelines within this manual are pre-approved by the seismic engineer of record for the particular site. It is the responsibility of the reader and structural engineer for the project/site to ensure that the existing structure is capable of withstanding the full loads that may be induced by the braced equipment or Seismic attachments. The services of a seismic bracing engineer or a professional/structural engineer is required to determine the seismic demand forces, required bracing, spacing, and anchorage of the bracing in accordance with the applicable building code design provisions and conditions for the project. Please note that this manual does not replace code-required industry standard practices. Restraint systems, designed as per the guidelines outlined in this manual, do not guarantee adequacy of the installation, and it is the responsibility of the reader and structural engineer for the site/project to ensure the adequacy of the design and placement of the Seismic bracing kits and their installation to be in compliance with the applicable codes.. Michael J. Griffin Professional Engineer California No DATE 6/7/10 Disclaimer: Neither Michael J. Griffi n nor Gripple are the Structural or Professional Engineers of Record. The stability and adequacy of the structural elements, nonstructural components or seismic sway braces, hangers, brackets, bolting, anchorage and any other required attachments are the responsibility of the Structural or Professional Engineer of Record, or the seismic bracing design engineer for the Facility or Project. Any additional or supplementary members required to ensure the adequacy or stability of the structures the seismic sway bracing attaches to are not within the scope of this manual/document. Gripple warrants that the Restraint systems will achieve the applicable design strengths published if installed in accordance with the guidelines contained in this manual. Gripple disclaims any and all other express or implied warranties of fi tness for any general or particular application. Anyone making use of this manual does so at their own risk, and assumes any and all liability resulting from such use. 4

5 1.2 Kit Contents Gripple Seismic Kit Size Length Seismic Bracket Rod/Structural Attachment Size Product Code GS12 Max Load: 860 lbs 1.5:1 SF 10ft 15ft 20ft Standard Retrofit Standard Retrofit Standard Retrofit 3/8 1/2 3/8 1/2 3/8 1/2 3/8 1/2 3/8 1/2 3/8 1/2 GS12-10E4-S4 GS12-10S5-S5 GS12-10E4-R4 GS12-10S5-R5 GS12-15E4-S4 GS12-15S5-S5 GS12-15E4-R4 GS12-15S5-R5 GS12-20E4-S4 GS12-20S5-S5 GS12-20E4-R4 GS12-20S5-R5 Range of Sizes GS12 Max Load: 860 lbs GS19 Max Load: 2,450 lbs GS25 Max Load: 4,100 lbs GS19 Max Load: 2,450 lbs 1.5:1 SF 10ft 15ft 20ft Standard Retrofit Standard Retrofit Standard Retrofit 3/8 1/2 5/8 3/8 1/2 5/8 3/8 1/2 5/8 3/8 1/2 5/8 3/8 1/2 5/8 3/8 1/2 5/8 GS19-10S4-S4 GS19-10S5-S5 GS19-10S6-S6 GS19-10S4-R4 GS19-10S5-R5 GS19-10S6-R6 GS19-15S4-S4 GS19-15S5-S5 GS19-15S6-S6 GS19-15S4-R4 GS19-15S5-R5 GS19-15S6-R6 GS19-20S4-S4 GS19-20S5-S5 GS19-20S6-S6 GS19-20S4-R4 GS19-20S5-R5 GS19-20S6-R6 Understanding Gripple Seismic Codes Cable Size GS12=1/8 GS19=3/16 GS25=1/4 End Fitting E=45º Eyelet S=Standard Single Bracket DS=Standard Double Bracket Hole Size in Loose Brackets 4=3/8 5=1/2 6=5/8 8=3/4 10=1 GS12-10E4-S4 GS25 Max Load: 4,100 lbs 1.5:1 SF 10ft 15ft 20ft Standard Retrofit Standard Retrofit Standard Retrofit 5/8 3/4 1 5/8 3/4 1 5/8 3/4 1 5/8 3/4 1 5/8 3/4 1 5/8 3/4 1 GS25-10DS6-DS6 GS25-10DS8-DS8 GS25-10DS10-DS10 GS25-10DS6-DR6 GS25-10DS8-DR8 GS25-10DS10-DR10 GS25-15DS6-DS6 GS25-15DS8-DS8 GS25-15DS10-DS10 GS25-15DS6-DR6 GS25-15DS8-DR8 GS25-15DS10-DR10 GS25-20DS6-DS6 GS25-20DS8-DS8 GS25-20DS10-DS10 GS25-20DS6-DR6 GS25-20DS8-DR8 GS25-20DS10-DR10 Cable Length 10, 15 or 20ft Hole Size in End Fitting 4=3/8 5=1/2 6=5/8 8=3/4 10=1 Style of Loose Bracket S=Standard Bracket R=Retrofit Bracket DS=Double Standard Bracket DR=Double Retrofit Bracket (Double Brackets for GS25 only) 5

6 1.3 Introduction / System Strengths Hanger rod with stiffener Break strength certifi ed, pre-stretched Gripple Seismic cable brace Anchorage to structure See Section 4 See Section 3 for end bracket installation Attachment to equipment See Section 5 See Section 3 for end bracket installation A = 30º - 60º F h fastener See Section 3 for installation Brace Size Cable Diameter Max System Design Strength* Max Horizontal Force (F h A = 30º Max Horizontal Force (F h A = 45º Max Horizontal Force (F h A = 60º GS12 1/8 860 lbs 745 lbs 608 lbs 430 lbs GS19 3/16 2,450 lbs 2,122 lbs 1,732 lbs 1,225 lbs GS25 1/4 4,100 lbs 3,551 lbs 2,899 lbs 2,050 lbs * Max design strength (LRFD), based on 1.5:1 Safety Factor as per ASCE and IBC Section Based on the lowest average failure load from tension tests of the Gripple bracing components (cable, brackets, and fasteners)

7 1.4.1 Introduction / Transverse Brace Assembly 30º- 60º 30º- 60º Run direction Anchorage to structure Hanger rod with stiffener Anchorage to structure Break strength certified, pre-stretched Gripple Seismic cable brace 30º- 60º Fastener See Section 3 for Installation F h End View Transverse bracing acts to restrain the seismic forces in a plane perpendicular to the run of braced piping, conduit, ductwork or equipment, as shown above. The seismic forces that a transverse brace resists are illustrated by F h. A vertical force can be generated during a seismic event and as such, rod stiffeners may be required to help prevent the hanger rod from buckling under this upwards force. Ductile Braced Components: For piping, conduit, and equipment connections manufactured from ductile materials, the maximum allowable brace spacing for transverse bracing is typically 40ft; this brace spacing is dependent on pipe size, seismic forces, and brace components selected. Non-ductile Braced Components: For piping, conduit, and equipment connections manufactured from non-ductile materials, the maximum allowable brace spacing for transverse bracing is typically 20ft; this brace spacing is dependent on pipe size, seismic forces, and brace components selected. Refer to Section 1.5 for spacing guidelines. OVAL ENDING

8 1.4.2 Introduction / Longitudinal Brace Assembly 30º- 60º 30º- 60º Anchorage to structure Run direction Hanger rod with stiffener (as required by design) Anchorage to structure Break strength certified, pre-stretched Gripple Seismic cable brace 30 O -60 O fastener See Section 3 for Installation F h Side View Longitudinal bracing acts to restrain the seismic forces in a plane parallel to the run of braced piping, conduit, ductwork or equipment, as shown above. The seismic forces that a longitudinal brace resists are illustrated by F h. A vertical force can be generated during a seismic event and as such, rod stiffeners may be required to help prevent the hanger rod from buckling under this upwards force. Ductile Braced Components: For piping, conduit, and equipment connections manufactured from ductile materials, the maximum allowable brace spacing for longitudinal bracing is typically 80ft; this brace spacing is dependent on pipe size, seismic forces, and brace components selected. Non-ductile Braced Components: For piping, conduit, and equipment connections manufactured from non-ductile materials, the maximum allowable brace spacing for longitudinal bracing is typically 40ft; this brace spacing is dependent on pipe size, seismic forces, and brace components selected. Refer to Section 1.5 for spacing guidelines

9 1.4.3 Introduction / 4-Way Bracing Assembly 40º - 50º Hanger rod with stiffener Run direction 30º- 60º Anchorage to structure Anchorage to structure F h Anchorage to structure Top View Anchorage to structure 4-Way bracing acts to restrain the seismic forces of the run of braced piping, conduit, ductwork or equipment, in both the transverse and longitudinal directions, as shown above. The seismic forces that a 4-Way brace resists are illustrated by F h. A vertical force can be generated during a seismic event and as such, rod stiffeners may be required to help prevent the hanger rod from buckling under this upwards force. Ductile Braced Components: For piping, conduit, and equipment connections manufactured from ductile materials, the maximum allowable brace spacing for 4-Way bracing is typically limited to 80ft, so long as transverse bracing is used in addition, every 40ft; this brace spacing is dependent on pipe size, seismic forces, and brace components selected. Non-ductile Braced Components: For piping, conduit, and equipment connections manufactured from non-ductile materials, the maximum allowable brace spacing for 4-Way bracing is typically limited to 40ft, so long as transverse bracing is used in addition, every 20ft; this brace spacing is dependent on pipe size, seismic forces, and brace components selected. Refer to Section 1.5 for spacing guidelines. O AL ENDING

10 1.5 Introduction / Brace Spacing Guidelines Bracing must be installed on the vertical support system comprised of threaded rod (all-thread rod) hanger suspensions, or directly to a suspended individual equipment component. Seismic bracing shall be designed in accordance with: - the applicable building code or local city/county code requirements for seismic design. - the engineering drawings and specifi cations of the specifi c project requirements. Component hanger spacing will typically be less than the required seismic spacing. Typical maximum allowable brace spacing limits The maximum allowable brace spacing for piping/conduit/ductwork constructed of ductile materials (e.g. steel, copper, aluminum) are typically: - 40ft for transverse bracing (piping larger than 2½ dia, general conduit and ductwork) - 80ft for longitudinal bracing (piping larger than 2½, general conduit and ductwork) - 30ft for transverse bracing (piping smaller than 2½ dia) - 60ft for longitudinal bracing (piping smaller than 2½ dia) The maximum allowable brace spacing limits for piping/conduit/ductwork constructed of non-ductile materials (e.g. cast iron, plastic) are: - 20ft for transverse bracing - 40ft for longitudinal bracing The brace spacing could be considerably less than this for a specifi c run, depending on the seismic demand loads, the size and load capacity of the cable brace system used, and the strength of the structural members/components and structural anchors which resist the resulting seismic brace forces. Reduced spacing may also be required to prevent: - collisions between the piping/conduit/ductwork/equipment and other non-structural components. - rupture/shearing/slippage of fl exible joints between piping/conduit/ductwork and fl oor/ceiling mounted equipment. Brace size and spacing should not vary considerably during a run to ensure uniform defl ection of the piping/conduit/ductwork along the run, and uniform loading of the individual braces during a seismic event. 1. Transverse Maximum longitudinal spacing 4-Way Maximum transverse spacing Less than 24 Transverse bracing can be used as longitudinal bracing for an adjacent run (at 90º changes of direction) where the brace is located less than 24 from the change in direction. Longitudinal/Transverse sway bracing shall also be required within 24 of every fl exible coupling due to differential movement of the pipe or conduit. Maximum transverse spacing

11 1.5 Introduction / Brace Spacing Guidelines (continued) 2. Transverse Maximum transverse spacing 4-Way Piping/conduit/duct run may be considered a continuous run if the horizontal offset is less than 24. Otherwise, if the offset is greater than 24, each straight segment shall be treated as an independent run and appropriately braced. Offset less than Transverse Maximum transverse spacing Less than 24 4-Way 1. The minimum bracing required for runs longer than 5ft is a transverse brace at each end, and a longitudinal brace at one of these two positions. This bracing could be sourced using points 1 and 2 above. Less than More than 5ft but less than transverse spacing Maximum transverse spacing P OVAL N I G

12 1.5 Introduction / Brace Spacing Guidelines (continued) 4. Max transverse spacing Less than 24 max Transverse 4-Way 4-Way braces required if vertical run exceeds 3ft Vertical runs must have both transverse and longitudinal bracing, or a 4-Way brace at each end of the vertical run. These bracing points must be located within 24 of the end of the vertical run, away from the change in direction. 4-way braces shall be provided at the top of all pipe risers exceeding 3ft in length. Less than 24 max Max transverse spacing 5. Maximum transverse spacing Maximum transverse spacing 4-Way braced equipment Transverse Less than 24 4-Way Each unit of equipment connected to a run of piping/conduit/ductwork should be individually and independently braced. If rigidly connected to the piping/conduit/ductwork, then the equipment bracing shall also be designed for the tributary piping/ conduit/ductwork seismic forces. If the piping/conduit/ductwork is not rigidly connected, i.e. fl ex joints, then the equipment bracing cannot be used to brace the adjacent piping/conduit/ductwork and shall be independently braced. Suspended rectangular units of equipment shall be provided with a minimum of one sway brace at each corner (4 total braces). See Section 5 for details

13 2.1 Seismic Bracing Kit and Components Overview / Kit Contents Cable Break strength certifi ed, pre-stretched cable. Available in lengths of 10ft, 15ft and 20ft. 2. Color Coded Tags Pre-assembled color coded tags for easy fi eld verifi cation of cable diameter. 3. End Fitting E-45º Eyelet S-Standard Single Bracket* DS-Standard Double Bracket* Eyelet Standard Bracket Double Bracket 4. Fastener GS12 - Max Load 860 lbs GS19 - Max Load 2,450 lbs GS25 - Max Load 4,100 lbs Green Yellow Purple 5. Loose bracket Standard Bracket or Retrofi t Bracket as Single or Double Brackets. Standard Bracket Retrofit Bracket * Zinc plated copper ferrules

14 2.2 Seismic Bracing Kit and Components Overview / Eyelet & Fastener Gripple Eyelet C E 45º A D B Eyelet Size GSE4 A 1 Dimensions B C ø 19/32 53/64 D ø 7/16 E 1/8 Fastener B C A Brace Size A Dimensions B C Cable Construction Lowest System Component Break Strengths Max System Design Strength (Safety factor 1.5:1) GS12 (1/8 cable) 1 9/64 3 1/4 35/64 7 x 7 1,278 lbs 860 lbs GS19 (3/16 cable) 1 11/32 3 3/4 9/16 7 x 19 3,669 lbs 2,450 lbs GS25 (1/4 cable) 1 23/ /32 11/16 7 x 19 6,085 lbs 4,100 lbs

15 2.3 Seismic Bracing Kit and Components Overview / Brackets Standard Bracket E 45º A Code will alter according to size D B C Standard Bracket Size GSS4 GSS5 GSS6 GSS8 GSS10 A 25/32 13/16 13/ /16 B 19/16 1 9/16 19/ / /32 Dimensions C ø 19/ / / / /32 D ø 1/2 19/32 11/16 13/16 1 5/64 E 5/32 5/32 5/32 5/32 5/32 Retrofit Bracket 45º G D A B Code will alter according to size E Retrofit Bracket Size GSR4 GSR5 GSR6 GSR8 GSR10 A 345/64 33/4 33/4 4 9/64 97/16 B 29/16 45/8 45/8 31/16 35/16 C 131/32 131/32 131/32 21/4 27/16 C Dimensions D 1/2 19/32 3/4 53/64 11/16 F E 11/16 15/16 15/ /32 117/32 F 47/64 45/64 45/64 55/64 29/32 G 1/4 1/4 1/4 1/4 1/

16 3.1 Seismic Brace Installation / Basic Brace Layout Attachment to structure Gripple cable end fi tting (GSE or GSS bracket) Break strength certifi ed, pre-stretched Gripple Seismic Cable Fastener (GS12, GS19, GS25) Color tag Hanger rod with stiffener 30º - 60º Attachment to equipment/strut Gripple GSS or GSR Bracket Strut

17 3.2 Seismic Brace Installation / Seismic Fastener Installation Thread the tail end of the cable through the first channel of the Fastener. 2. Thread the cable through the hole of the Bracket X 3. Thread the cable back through the second channel of the Gripple Fastener. A 2 tail is recommended for any future adjustments. Hand-tighten cable to remove all slack. For isolated equipment, leave 1/8 visible sag in the cable. 4. Hand-tighten the locking bolts until tight. Installation of the Brace is complete

18 3.3.1 Seismic Brace Installation / Retrofi t Bracket Installation Retrofit Bracket Installation Loosen nut and washer. 2. Attach Retrofi t Bracket in direction of brace. 3. Tighten down nut on top of the Retrofi t Bracket. Double stacking for GS25 Kit Note: When using GS25 the attachment to the braced equipment must use double stacked Retrofi t Brackets. Hanger rod with stiffener GS25 to structure attachment X To GS25 brace

19 3.3.2 Seismic Bracing Installation / Bracket Stacking Installation Typical bracket installation for Transverse bracing Hanger rod with stiffener Note: When using GS25 brackets, they must be double stacked (see Section 3.3.1) To brace Strut Typical stacking for Longitudinal bracing Hanger rod with stiffener To brace Strut To brace Typical stacking for 4-Way bracing To brace Hanger rod with stiffener 40º - 50º 40º - 50º Strut To brace

20 4.1.1 Brace Anchor/Attachment Installation / Concrete Wall 1. Anchor design shall be in accordance with the applicable building code seismic design provisions. Typically this will include compliance with ACI318, Appendix D. 2. Refer to applicable International Code Council evaluation service reports (ICC-ES) for each specifi c anchor. 3. All non-gripple parts, rod hangers, support products and connectors shall be approved for seismic applications where required, and shall be designed by a licensed professional engineer responsible for the design. 4. Use caution when drilling or anchoring into a concrete wall, that the anchor embedment does not exceed the minimum required wall width as established by the anchor manufacturer. 5. When using GS25, two double standard brackets must be used (see Section ). 6. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 1. Concrete wall Expansion anchor as per the design of the seismic bracing system 2. Warning: Locate steel reinforcement/ rebar before drilling. Follow bolt manufacturer s installation guidelines. 3. Break strength certifi ed, pre-stretched cable Standard Bracket End Fitting Double stacked (GS25 system) 2. Standard Bracket End Fitting (GS12 and GS19 systems) 3. Eyelet End Fitting (GS12 system) 4. Cable looped through a loose Standard Bracket, secured with a Fastener Either factory swaged end fi tting or loop through a Gripple Bracket with Fastener (30º - 60º)

21 4.1.2 Brace Anchor/Attachment Installation / Concrete Ceiling/Roof 1. Anchor design shall be in accordance with the applicable building code seismic provisions. Typically this will include compliance with ACI318, Appendix D. 2. Refer to applicable International Code Council evaluation service reports (ICC-ES) for each specifi c anchor. 3. All non-gripple parts, rod hangers, support products and connectors shall be approved for seismic applications where required, and shall be designed by a licensed professional engineer responsible for the design. 4. Use caution when drilling or anchoring into a concrete surface, that the anchor embedment does not exceed the minimum required depth as established by the anchor manufacturer. 5. When using GS25, two double standard brackets must be used (see Section 3.3.1). 6. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. Expansion anchor as per design of the seismic bracing system Concrete slab or roof (30º- 60º) Break strength certifi ed, pre-stretched cable Either factory swaged end fi tting or loop through a Gripple Bracket with Fastener 1. Eyelet End Fitting (GS12 system) 2. Standard Bracket End Fitting (GS12 and GS19 systems) 3. Standard Bracket End Fitting Double stacked (GS25 system) 4. Cable looped through a loose Standard Bracket, secured with a Gripple Seismic Fastener Warning: Locate steel reinforcement/ rebar before drilling. Follow bolt manufacturers installation guidelines

22 4.1.3 Brace Anchor / Attachment Installation / Concrete over Metal Decking 1. Anchor design shall be in accordance with the applicable building code seismic design provisions. Typically this will include compliance with ACI318, Appendix D. 2. Refer to applicable International Code Council evaluation service reports (ICC-ES) for each specifi c anchor. 3. All non-gripple parts, rod hangers, support products and connectors shall be approved for seismic applications where required, and shall be designed by a licensed professional engineer responsible for the design. 4. Use caution when drilling or anchoring into a concrete surface, that the anchor embedment does not exceed the minimum required depth as established by the anchor manufacturer. 5. When using GS25, two double standard brackets must be used (see Section 3.3.1). 6. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. Expansion anchor as per design and orientation at metal decking per manufacturer s instructions Concrete over metal deck Either Gripple Eyelet or Standard Bracket Either factory swaged end fi tting or loop through a Gripple Bracket with Fastener (30º - 60º) Break strength certifi ed, pre-stretched cable 1. Standard Bracket end fi tting (GS12 and GS19 systems) Warning: Locate steel reinforcement/ rebar before drilling. Follow bolt manufacturer s installation guidelines

23 4.1.3 Brace Anchor / Attachment Installation / Concrete over Metal Decking 1. Anchor design shall be in accordance with the applicable building code seismic design provisions. Typically this will include compliance with ACI318, Appendix D. 2. Refer to applicable International Code Council evaluation service reports (ICC-ES) for each specifi c anchor. 3. All non-gripple parts, rod hangers, support products and connectors shall be approved for seismic applications where required, and shall be designed by a licensed professional engineer responsible for the design. 4. Use caution when drilling or anchoring into a concrete surface, that the anchor embedment does not exceed the minimum required depth as established by the anchor manufacturer. 5. When using GS25, two double standard brackets must be used (see Section 3.3.1). 6. Building structure at anchor locations must be point load capable. Verify loading with registered professional engineer for the site/project. Strut, strut anchors, and bracket anchor to strut per design Concrete slab on metal deck. 1. Either swaged end fi tting or loop through a Gripple Bracket with Fastener 1. Note: Position of strut in line with deck ribs. Either Gripple Eyelet, Standard or Double Bracket (30º - 60º) Angle may not vary from parallel to deck ribs no more than ±5 o Break strength certifi ed, pre-stretched cable 1. Standard Bracket End Fitting (GS12 and GS19 systems) Warning: Locate steel reinforcement/ rebar before drilling. Follow bolt manufacturer s installation guidelines

24 4.1.3 Brace Anchor / Attachment Installation / Concrete over Metal Decking 1. Anchor design shall be in accordance with the applicable building code seismic design provisions. Typically this will include compliance with ACI318, Appendix D. 2. Refer to applicable International Code Council evaluation service reports (ICC-ES) for each specifi c anchor. 3. All non-gripple parts, rod hangers, support products and connectors shall be approved for seismic applications where required, and shall be designed by a licensed professional engineer responsible for the design. 4. Use caution when drilling or anchoring into a concrete surface, that the anchor embedment does not exceed the minimum required depth as established by the anchor manufacturer. 5. When using GS25, two double standard brackets must be used (see Section 3.3.1). 6. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. Strut, strut anchors, and bracket anchor to strut per design Concrete slab over metal deck Either Gripple Eyelet, Standard or Double Bracket 1. Either a factory swaged end fi tting or loop through a Gripple Bracket withfastener Break strength certifi ed, pre-stretched cable 1. Note: position of strut perpendicular with deck ribs. Break strength certifi ed, pre-stretched Gripple Seismic cable (30º - 60º) Angle may not vary more than ±5 o from perpendicular to deck ribs 1. Standard Bracket end fi tting (GS12 and GS19 systems) Warning: Locate steel reinforcement/ rebar before drilling. Follow bolt manufacturer s installation guidelines

25 4.1.4 Brace Anchor / Attachment Installation / Concrete Block Wall 1. Anchor design shall be in accordance with the applicable building code seismic design provisions. Typically this will include compliance with ACI318, Appendix D. 2. Refer to applicable International Code Council evaluation service reports (ICC-ES) for each specifi c anchor. 3. All non-gripple parts, rod hangers, support products and connectors shall be approved for seismic applications where required, and shall be designed by a licensed professional engineer responsible for the design. 4. Use caution when drilling or anchoring into a wall, that the anchor embedment does not exceed the minimum required wall width as established by the anchor manufacturer. 5. When using GS25, two double standard brackets must be used (see Section 3.3.1). 6. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. Grouted concrete wall block Hollow concrete block wall Anchor per design of the seismic bracing system and specifi c anchor manufacturer instructions Gripple Eyelet, Standard or Double Bracket end fi ttings Break strength certifi ed, pre-stretched Gripple Seismic cable Either factory swaged end fi tting or loop through a Gripple Bracket wtih Fastener (30º - 60º)

26 4.2 Brace Anchor / Attachment Installation / Steel Beam 1. Anchor design shall be in accordance with the applicable building code seismic design provisions and hardware manufacturer s approved design data. 2. Refer to applicable International Code Council evaluation service reports (ICC-ES) for each specifi c anchor and attaching hardware. 3. All non-gripple parts, rod hangers, support products and connectors shall be approved for seismic applications where required, and shall be designed by a licensed professional engineer responsible for the design. 4. When using GS25, two double standard brackets must be used (see Section 3.3.1). 5. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. Metal deck Steel beam Strut and beam clamps as required by design Either a factory swaged end fi tting or a loop through a Gripple Bracket with Fastener Either Gripple Eyelet or Standard Bracket (30º - 60º) Break strength certifi ed, pre-stretched cable Angle may not vary from parallel to the strut no more than ±5 o Beam End View Beam Side View

27 4.3.1 Brace Anchor / Attachment Installation / Bar Joist - Transverse or Longitudinal 1. Details below indicate how braces may be attached to a bar joist structure. 2. All non-gripple parts, rod hangers, support products and connectors shall be approved for seismic applications where required, and shall be designed by a licensed professional engineer responsible for the design. 3. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 4. The Gripple seismic cable shall only be attached to the top chord of the bar joist member. Loop must be formed around top of bar joist in between web members as shown, then secured with Gripple Seismic Fastener Note: For the bracing arrangements detailed here, two seismic fasteners may be required (one at each end of the cable brace supplied without factory swaged on brackets). Joist web member 12 mininum Fastener (30º-60º) Leave a minimum 2 tail when installing Gripple Fastener Break strength certified, pre-stretched Gripple Seismic cable Looped around bar joist, secured with Fastener, as detailed above Hanger location Connection to equipment Looped around bar joist, secured with Fastener, as detailed above Hanger location Hanger location Connection to equipment Connection to equipment

28 4.3.2 Brace Anchor / Attachment Installation / Bar Joist - 4-Way Bracing 1. Details below indicate how braces may be attached to a bar joist structure for a 4-Way brace system. 2. All non-gripple parts, rod hangers, seismic support and connectors shall be approved for seismic applications where required, and shall be designed by a licensed professional engineer responsible for the design. 3. Building structure at anchor locations must be point load capable. Verify loading with structural for the site/project. 4. The Gripple seismic cable shall only be attached to the top chord of the bar joist member. Note: For the bracing arrangements detailed here, two seismic fasteners may be required (one at each end of the cable brace supplied without a factory swaged on bracket). Looped around bar joist, secured with Fastener, as detailed in Section Hanger location Connection to equipment Break strength certified pre-stretched Gripple Seismic cable. Cable angles shall be per Section Looped around bar joist, secured with Fastener, as detailed in Section Hanger location Hanger location Connection to equipment Break strength certified pre-stretched Gripple Seismic cable. Cable angles shall be per Section

29 4.4 Brace Anchor / Attachment Installation / Steel Purlins 1. Details below indicate how braces may be attached to steel purlins in a building structure. 2. All non-gripple parts, rod hangers, support products and connectors shall be approved for seismic applications where required, and shall be designed by a licensed professional engineer responsible for the design. 3. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. Purlin Warning: Obtain approval from site structural engineer before attaching or drilling into purlins. Added reinforcement may be required. * Eyelet end fitting shown. Alternatively a Standard Bracket could be used. * (30º-60º) * (30º-60º) Break strength certifi ed pre-stretched cable Transverse or Longitudinal Hanger location Hanger location Hanger location 4-Way bracing Hanger location Hanger location Hanger location Steel purlin or beam Either run direction s shall be per Section

30 4.5 Brace Anchor / Attachment Installation / Timber Members 1. Details below indicate how braces may be attached to timber structural members. 2. All non-gripple parts, rod hangers, support products and connectors shall be approved for seismic applications where required, and shall be designed by a licensed or registered professional engineer responsible for the site/project. 3. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. Warning: Obtain approval from site structural engineer before attaching or drilling into beams. * Break strength certifi ed, pre-stretched cable * Eyelet end fitting shown. Alternatively a Standard Bracket could be used. (30º-60º) 9x bolt dia minimum Design of bolt must be in upper half of beam 3 min * (30º-60º) 9x lag screw dia minimum Lag screw 3 min * Gripple Eyelet or Gripple Standard Bracket Lag Screw as required by design * (30º-60º)

31 5.1.1 Round Ductwork / Transverse 1. Install cable assemblies with a 60º maximum angle from the horizontal plane. 2. Anchor cable assemblies to structure per Section 4, and as required by design. 3. Tighten cables to remove slack (see Section 3.2). 4. Hanger rod and rod stiffeners shall be by design. 5. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 6. For GS25 two brackets must be used at end fi ttings to cable (see Section 3.3.1). 7. Leave a 2 tag extending out of the Fastener for future adjustments. 8. Ensure locking screws are fully installed into the Fastener on completion of installation. Anchorage to structure Hanger rod with stiffener Break strength certified, pre-stretched cable (30º- 60º) Fastener See detail Round ductwork Section View Duct clamp hanger Detail either/or Round ductwork Duct clamp hanger Max deviation ±5 o Looped through a Gripple Seismic Standard or Retrofit Bracket Standard or Retrofit Bracket (with bolt hole as per threaded rod dia) Top View

32 5.1.2 Round Ductwork / Longitudinal 1. Install cable assemblies with a 60º maximum angle from the horizontal plane. 2. Anchor cable assemblies to structure per Section 4, and as required by design. 3. Tighten cables to remove slack (see Section 3.2). 4. Hanger rod and rod stiffeners shall be by design. 5. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 6. For GS25 two brackets must be used at end fi ttings to cable (see Section 3.3.1). 7. Leave a 2 tag extending out of the Fastener for future adjustments. 8. Ensure locking screws are fully installed into the Fastener on completion of installation. Max deviation ±5º Hanger rod with stiffener Max deviation ±5º Break strength certified, pre-stretched Gripple Seismic cable Duct clamp hanger ; Duct shall be tightly clamped Round ductwork Looped through a Standard or Retrofit Bracket Round ductwork Section View Fastener Hanger rod with stiffener Duct clamp hanger Standard or Retrofit Bracket (with bolt hole as per threaded rod dia) Top View (30º- 60º) Round ductwork Detail See detail Standard or Retrofit Bracket Side View Duct clamp hanger either/or

33 5.1.3 Round Ductwork / 4-Way 1. Install cable assemblies with 4-Way brace angles in accordance with section Anchor cable assemblies to structure per Section 4, and as required by design. 3. Tighten cables to remove slack (see Section 3.2). 4. Hanger rod and rod stiffeners shall be by design. 5. Building structure at anchor locations must be point load capable. Verify loading wtih structural engineer for the site/project. 6. For GS25 two brackets must be used at end fi ttings to cable (see Section 3.3.1). 7. Leave a 2 tag extending out of the Fastener for future adjustments. 8. Ensure locking screws are fully installed into the Fastener on completion of installation. Anchorage to structure Hanger rod with stiffener by design Break strength certified, prestretched Gripple Seismic cable (30º- 60º) Fastener Round ductwork Section View Duct clamp hanger ; Duct shall be tightly clamped See detail (30º- 60º) Side View Looped through a Gripple Seismic Standard Bracket Standard or Retrofit Bracket (in bolt hole as per threaded rod dia) Detail (30º- 60º) Top View either/or

34 5.2.1 Rectangular Ductwork / Transverse 1. Install cable assemblies with a 60º maximum angle from the horizontal plane. 2. Anchor cable assemblies to structure per Section 4, and as required by design. 3. Tighten cables to remove slack (see Section 3.2). 4. Hanger rod and rod stiffeners shall be by design. 5. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 6. For GS25 two brackets must be used at end fi ttings to cable (see Section 3.3.1). 7. Leave a 2 tag extending out of the Fastener for future adjustments. 8. Ensure locking screws are fully installed into the Fastener on completion of installation. Hanger rod with stiffener Anchorage to structure Rectangular ductwork Break strength certified, pre-stretched Gripple Seismic cable (30º- 60º) Fastener See detail Attach duct to strut as required by design Section View Strut Detail Rectangular ductwork Standard or Retrofit Bracket with bolt hole as per threaded rod dia) either/or Max deviation ±5 O Looped through a Gripple Seismic Standard or Retrofit Bracket Top View

35 5.2.2 Rectangular Ductwork / Longitudinal 1. Install cable assemblies with a 60º maximum angle from the horizontal plane. 2. Anchor cable assemblies to structure per Section 4, and as required by design. 3. Tighten cables to remove slack (see Section 3.2). 4. Hanger rod and rod stiffeners shall be by design. 5. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 6. For GS25 two brackets must be used at end fi ttings to cable (see Section 3.3.1). 7. Leave a 2 tag extending out of the Fastener for future adjustments. 8. Ensure locking screws are fully installed into the Fastener on completion of installation. Max deviation ±5º Hanger rod with stiffener Rectangular ductwork Max deviation ±5º Break strength certified, pre-stretched cable Fastener Rectangular ductwork Looped through a Standard or Retrofit Bracket Attach duct to strut as required by design Section View Strut Hanger rod with rod stiffener Rectangular ductwork Strut (by others) Standard or Retrofit Bracket (with bolt hole as per threaded rod dia) Top View (30º- 60º) Standard or Retrofit Bracket Duct strut hanger support Detail See detail Side View either/or

36 5.2.3 Rectangular Ductwork / 4-Way 1. Install cable assemblies with 4-Way brace angles in accordance with Section Anchor cable assemblies to structure per Section 4, and as required by design. 3. Tighten cables to remove slack (see Section 3.2). 4. Hanger rod and rod stiffeners shall be by design. 5. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 6. For GS25 two brackets must be used at end fi ttings to cable (see Section 3.3.1). 7. Leave a 2 tag extending out of the Fastener for future adjustments. 8. Ensure locking screws are fully installed into the Fastener on completion of installation. Anchorage to structure Rectangular ductwork Hanger rod with stiffener Break strength certified, pre-stretched Gripple Seismic cable (30º- 60º) Strut Fastener Attach duct to strut support as required by design Section View See detail Rectangular ductwork Standard or Retrofit Bracket (with bolt hole as per threaded rod dia) (30º- 60º) Side View Looped through a Gripple Seismic Standard or Retrofit bracket Detail (40º - 50º) Top View either/or

37 5.3.1 Flat or Oval Ductwork / Transverse 1. Install cable assemblies with a 60º maximum angle from the horizontal plane. 2. Anchor cable assemblies to structure per Section 4, and as required by design. 3. Tighten cables to remove slack (see Section 3.2). 4. Hanger rod and rod stiffeners shall be by design. 5. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 6. For GS25 two brackets must be used at end fi ttings to cable (see Section 3.3.1). 7. Leave a 2 tag extending out of the Fastener for future adjustments. 8. Ensure locking screws are fully installed into the Fastener on completion of installation. 9. Use shortest possible screws when penetrating the ductwork to minimize airfl ow noise inside the duct. Break strength certified, pre-stretched Gripple Seismic cable Flat oval ductwork Attach duct to strut support (see note 9) Hanger rod with stiffener Fastener Anchorage to structure (30º- 60º) Strut support Section View See detail Looped through a Gripple Seismic Standard or Retrofit Bracket Flat oval ductwork Note: Alternative location for bracing Detail Max deviation ±5º Standard or Retrofit Bracket (with bolt hole as per threaded rod dia) Strut Fastener either/or Top View

38 5.3.2 Flat or Oval Ductwork / Longitudinal 1. Install cable assemblies with a 60º maximum angle from the horizontal plane. 2. Anchor cable assemblies to structure per Section 4, and as required by design. 3. Tighten cables to remove slack (see Section 3.2). 4. Hanger rod and rod stiffeners shall be by design. 5. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 6. For GS25 two brackets must be used at end fi ttings to cable (see Section 3.3.1). 7. Leave a 2 tag extending out of the Fastener for future adjustments. 8. Ensure locking screws are fully installed into the Fastener on completion of installation. 9. Use shortest possible screws when penetrating the ductwork to minimize airfl ow noise inside the duct. Break strength certified, prestretched Gripple Seismic cable Attach duct to strut support (see note 9) Hanger rod with stiffener (as required by design) Max deviation ±5º Break strength certified, pre-stretched Gripple Seismic cable Flat oval ductwork Strut Fastener Flat oval ductwork Section View Hanger rod with stiffener (as required by design) Standard or Retrofit Bracket (with bolt hole as per threaded rod dia) Looped through a Standard or Retrofit Bracket (30º- 60º) Top View Strut support See detail Side View Detail either/or Note: Alternative location for bracing

39 5.3.3 Flat or Oval Ductwork / 4-Way 1. Install cable assemblies with 4-Way brace angles in accordance with Section Anchor cable assemblies to structure per Section 4, and as required by design. 3. Tighten cables to remove slack (see Section 3.2). 4. Hanger rod and rod stiffeners shall be by design. 5. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 6. For GS25 two brackets must be used at end fi ttings to cable (see Section 3.3.1). 7. Leave a 2 tag extending out of the Fastener for future adjustments. 8. Ensure locking screws are fully installed into the Fastener on completion of installation. 9. Use shortest possible screws when penetrating the ductwork to minimize airfl ow noise inside the duct. Hanger rod with stiffener Detail Anchorage to structure Attach to strut support (see note 9) (30º- 60º) Flat Oval Ductwork Break strength certified, pre-stretched Gripple Seismic cable either/or Fastener Strut/trapeze Section View See detail Looped through a Gripple Seismic Standard or Retrofit Bracket Flat oval ductwork Standard or Retrofit Bracket (with bolt hole as per threaded rod dia) (40º - 50º) Top View Note: Alternative location for bracing

40 5.4.1 Un-Insulated Pipe & Conduit / Transverse 1. Install cable assemblies with a 60º maximum angle from the horizontal plane. 2. Anchor cable assemblies to structure per Section 4, and as required by design. 3. Tighten cables to remove slack (see Section 3.2). 4. Hanger rod and rod stiffeners shall be by design. 5. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 6. For GS25 two brackets must be used at end fi ttings to cable (see Section 3.3.1). 7. Leave a 2 tag extending out of the Fastener for future adjustments. 8. Ensure locking screws are fully installed into the Fastener on completion of installation. Note: Install clevis hanger/pipe clamp and torque bolts as per manufacturers installation guidelines. Break strength certified, pre-stretched cable Hanger rod or stiffener Anchorage to structure (30º- 60º) Fastener Un-insulated pipe or conduit Pipe clevis hanger may require longer bolt to fit retrofit brackets Detail Section Max deviation ±5º Hanger rod or stiffener Fastener Pipe clevis hanger Fastener Un-insulated pipe or conduit Top View Side View

41 5.4.2 Un-Insulated Pipe & Conduit / Longitudinal 1. Install cable assemblies with a 60º maximum angle from the horizontal plane. 2. Anchor cable assemblies to structure per Section 4, and as required by design 3. Tighten cables to remove slack (see Section 3.2). 4. Hanger rod and rod stiffeners shall be by design. 5. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 6. For GS25 two brackets must be used at end fi ttings to cable (see Section 3.3.1). 7. Leave a 2 tag extending out of the Fastener for future adjustments. 8. Ensure locking screws are fully installed into the Fastener on completion of installation. Note: Install clevis hanger/pipe clamp and torque bolts as per manufacturers installation guidelines. Anchorage to structure Hanger rod or stiffener Break strength certified, pre-stretched Gripple Seismic cable Max deviation ±5º (30º-60º) 6 max. Un-insulated pipe or conduit Pipe clamp Clevis hanger Side View Un-insulated pipe or conduit Clevis hanger Loop cable around clamp bolt, secure with a Fastener Pipe clamp 6 max. Un-insulated pipe or conduit Section View Top View

42 5.4.3 Un-Insulated Pipe & Conduit / 4-Way 1. Install cable assemblies with 4-Way brace angles in accordance with Section Anchor cable assemblies to structure per Section 4, and as required by design. 3. Tighten cables to remove slack (see Section 3.2). 4. Hanger rod and rod stiffeners shall be by design. 5. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 6. For GS25 two brackets must be used at end fi ttings to cable (see Section 3.3.1). 7. Leave a 2 tag extending out of the Fastener for future adjustments. 8. Ensure locking screws are fully installed into the Fastener on completion of installation. Note: Install clevis hanger/pipe clamp and torque bolts as per manufacturers installation guidelines. Break strength certified, pre-stretched cable Looped through a Gripple Seismic Standard bracket (30º- 60º) Fastener Un-insulated pipe or conduit Un-insulated pipe or conduit Section View Standard Bracket (with bolt hole as per threaded rod dia) Hanger rod with stiffener 6 Max. (40º- 50º) Top View (30º- 60º) Clevis hanger Un-insulated pipe or conduit Pipe clamp Side View

43 5.5.1 Insulated Pipe & Conduit / Transverse 1. Install cable assemblies with a 60º maximum angle from the horizontal plane. 2. Anchor cable assemblies to structure per Section 4, and as required by design. 3. Tighten cables to remove slack (see Section 3.2). 4. Hanger rod and rod stiffeners shall be by design. 5. Building structure at anchor locations must be point load capable. Verify loading with structural engineer for the site/project. 6. For GS25 two brackets must be used at end fi ttings to cable (see Section 3.3.1). 7. Leave a 2 tag extending out of the Fastener for future adjustments. 8. Ensure locking screws are fully installed into the Fastener on completion of installation. Note: Install clevis hanger/pipe clamp and torque bolts as per manufacturers installation guidelines. Hanger rod with stiffener (as required by (design) Gripple Seismic Fastener Anchorage to structure (30º- 60º) Looped through a Standard or Retrofit Bracket Clevis Bolt may need to be longer to fit Brackets Standard or Retrofit Bracket (with hole as per rod dia) Pipe Section View Clevis hanger Insulation Max deviation ±5 o Bracket Looped through a Bracket Bracket Insulation Top View Clevis hanger Side View Pipe

Seismic Installation Manual

Seismic Installation Manual Seismic Installation Manual California Office of Statewide Health Planning & Development OPA-2123-10 This manual provides the design strength capacities and installation guidelines for the Bracing System

More information

Large cable sizes stronger than pipe/strut

Large cable sizes stronger than pipe/strut Legrand Seismic Wire Rope/Cable Bracing is the recommended seismic bracing for Legrand wire mesh and ladder tray systems. It is UL Listed, complies with all building codes and standards, and offers significant

More information

KINETICS Pipe & Duct Seismic Application Manual

KINETICS Pipe & Duct Seismic Application Manual QUICK START READ ME FIRST I1.1 Seismic Restraint Categories and Types: Seismic restraints for pipe and duct are generally separated into to two categories. 1. Transverse Seismic Restraints: These act to

More information

KINETICS Pipe & Duct Seismic Application Manual

KINETICS Pipe & Duct Seismic Application Manual KINETICS ipe & Duct Seismic Application Manual FIRE ROTECTION IING SYSTEMS S13.1 Introduction: Historically the ICC (2000, 2003, 2006, and 2009 IBC) and the NFA (NFA 5000) have been competing code writing

More information

Fig Beam Clamp Retaining Strap (B-Line B3367)

Fig Beam Clamp Retaining Strap (B-Line B3367) Fig. 69 - Beam Clamp Retaining Strap (B-Line B3367) Size Range: 3 /8"-16 thru 3 /4"-10 rod 4 (101.6mm) thru 16 (406.4mm) lengths Note: longer lengths are available consult factory Material: Pre-Galvanized

More information

SECTION SEISMIC CONTROL OSHPD

SECTION SEISMIC CONTROL OSHPD SECTION 01451 PART 1 - GENERAL 1.01 DESCRIPTION A. Provide all required seismic restraints and calculations in order to insure that the installation of all architectural, mechanical, and electrical equipment/components

More information

FEDERAL EMERGENCY MANAGEMENT AGENCY FEMA 414/January 2004 INSTALLING SEISMIC RESTRAINTS FOR DUCT AND PIPE

FEDERAL EMERGENCY MANAGEMENT AGENCY FEMA 414/January 2004 INSTALLING SEISMIC RESTRAINTS FOR DUCT AND PIPE FEDERAL EMERGENCY MANAGEMENT AGENCY FEMA 414/January 2004 INSTALLING SEISMIC RESTRAINTS FOR DUCT AND PIPE Notice: This guide was prepared by the Vibration Isolation and Seismic Control Manufacturers Association

More information

Fig. 1 - Standard Clevis Hanger

Fig. 1 - Standard Clevis Hanger Revision 10/24/2007 Fig. 1 - Standard Clevis Hanger Component of State of California OSHPD Approved Seismic Restraints System Size Range Size 1/2" thru 36" pipe. Function Recommended for the suspension

More information

TOLCO Fire Protection Support Systems. Pipe Hangers Supports Seismic Bracing. UL Listed FM Approved for Fire Sprinkler Installations

TOLCO Fire Protection Support Systems. Pipe Hangers Supports Seismic Bracing. UL Listed FM Approved for Fire Sprinkler Installations TOLCO Fire Protection Support Systems Pipe Hangers Supports Seismic Bracing UL Listed FM Approved for Fire Sprinkler Installations Revision 12/06/2007 Catalog Forward This catalog has been created with

More information

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT SECTION 230548 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Elastomeric Isolation pads. 2. Elastomeric Isolation mounts. 3. [Freestanding] [Restrained] [Freestanding and restrained]

More information

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

Materials Carbon Steel is used in the manufacturing of riser and pipe clamps. Stainless Steel and other materials are available.

Materials Carbon Steel is used in the manufacturing of riser and pipe clamps. Stainless Steel and other materials are available. Pipe clamps offered in this section are designed for support and attachment of pipe to structural members. wide range of pipe clamps are available for various applications. Materials arbon Steel is used

More information

KINETICS Pipe & Duct Seismic Application Manual

KINETICS Pipe & Duct Seismic Application Manual S8.1 Introduction: During an earthquake, the hanger rods are not passive components that just simply support the dead load of the pipe or duct. They must also resist the reaction forces generated by the

More information

DDI + (DECK INSERT) Threaded Insert for Metal Deck

DDI + (DECK INSERT) Threaded Insert for Metal Deck GENERAL INFORMATION GENERAL INFORMATION DDI + (DECK INSERT) Threaded Insert for Metal Deck PRODUCT DESCRIPTION The DDI+ (Deck Insert) is a concrete insert designed for installation in concrete-illed metal

More information

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. SECTION 260529 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. 1.2

More information

hors Anc Eaton's B-Line series fasteners 183

hors Anc Eaton's B-Line series fasteners 183 183 Glossary Prefix - Description Screw Dia. Length Suffix ACB - Concrete Anchor Bolt 4 - #4 75-3 /4" AN - Acorn Nut ACPD - Bang-IT 6 - #6 81-13 /16" CH - Combo Head ACPW - Wood-Knocker 8 - #8 87-7 /8"

More information

Suspension Systems for Acoustical Lay-in Ceilings Seismic Design Categories D, E & F

Suspension Systems for Acoustical Lay-in Ceilings Seismic Design Categories D, E & F NWCB Technical Document SUSPENDED CEILINGS 401 Suspension Systems for Acoustical Lay-in Ceilings Seismic Design Categories D, E & F 10/09 This document has been revised based on current Building Code standards.

More information

Materials Carbon Steel is used in the manufacturing of riser and pipe clamps. Stainless Steel and other materials are available.

Materials Carbon Steel is used in the manufacturing of riser and pipe clamps. Stainless Steel and other materials are available. Pipe clamps offered in this section are designed for support and attachment of pipe to structural members. wide range of pipe clamps are available for various applications. Materials arbon Steel is used

More information

Materials Carbon Steel and Malleable Iron are used in the manufacture of concrete inserts. Stainless Steel and other materials are available.

Materials Carbon Steel and Malleable Iron are used in the manufacture of concrete inserts. Stainless Steel and other materials are available. Concrete inserts offered in this section are designed to provide a pre-set support point in concrete ceilings, walls, and floors. A range of inserts with varying design loads are available. Materials Carbon

More information

Smarter. Safer. Leaner.

Smarter. Safer. Leaner. Smarter. Safer. Leaner. Fast Installation and Removal Decrease Leading Edge Exposure by 87% OSHA Compliant Versatile and Reusable Use Perimeter Protection Posts During Construction: At Building Perimeter

More information

MECHANICAL AND PLUMBING SUPPORTS. To order online vist us at.

MECHANICAL AND PLUMBING SUPPORTS. To order online vist us at. MECHANICAL AND PLUMBING SUPPORTS To order online vist us at www.ceasattachments.com Corporate Headquarters Construction Engineered Attachment Solutions 14848 Northam St., La Mirada, CA 90635 Tel: 877-GOO-CEAS

More information

DURA-BLOK Rooftop Supports

DURA-BLOK Rooftop Supports Cooper B-Line s new line of DURA-BLOK products gives you a versatile and long-term solution for all your roof top support needs. Designed with flexibility in mind, Dura-Blok is ideal for roof top support

More information

Suspension System Data Center Ceiling Solutions

Suspension System Data Center Ceiling Solutions Hardware That Needs to be Purchased Separately Screws are fine listed as shown: Min 1-1/4" or longer #8 Truss head self-tapping screws for attaching structural wall angle, lateral support bar 16" or 4"

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT SECTION 220529 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Steel pipe hangers and supports. 2. Metal framing systems. 3. Thermal-hanger shield inserts. 4. Fastener systems.

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS. 1. Hangers and supports for electrical equipment and systems.

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS. 1. Hangers and supports for electrical equipment and systems. SECTION 26 05 29 HANGERS AND SUPPORTS FOR PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Hangers and supports for electrical equipment and systems. 1.2 DEFINITIONS A. EMT: Electrical

More information

Cantilevered Rail System

Cantilevered Rail System Knight Global's Cantilevered Rail Systems are designed to eliminate the need for a four post floor structure system. It provides an alternative to workstations with minimal floor space. A wide range of

More information

Technical Services Information Bureau

Technical Services Information Bureau Technical Services Information Bureau INSTALLING ACOUSTICAL LAY-IN TYPE CEILINGS IN SEISMIC REGIONS AUGUST 2009 UPDATED MAY 2017 TECHNICAL BULLETIN This document covers the installation practices recognized

More information

DURA-BLOK is made from 100% recycled rubber and qualifies for LEED credits. Reflective strips on both sides allow for easy product visibility.

DURA-BLOK is made from 100% recycled rubber and qualifies for LEED credits. Reflective strips on both sides allow for easy product visibility. is made from 100% recycled rubber and qualifies for LEED credits. Reflective strips on both sides allow for easy product visibility. Channels are through bolted on all sizes for added strength and a 1

More information

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2328 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 03 00

More information

REV. 9/08. Mounting Structure PRE-INSTALLATION GUIDE for Ergon Skybooms

REV. 9/08. Mounting Structure PRE-INSTALLATION GUIDE for Ergon Skybooms REV. 9/08 Mounting Structure PRE-INSTALLATION GUIDE for Ergon Skybooms SKYTRON MOUNTING STRUCTURES for Ceiling Mounted Equipment Foreword Skytron s objective is to provide a program and guideline to assist

More information

HANDSET WALL FORM. Handset Wall Form. Quick Assembly - can be built using only a hammer. Reduced weight increases productivity

HANDSET WALL FORM. Handset Wall Form. Quick Assembly - can be built using only a hammer. Reduced weight increases productivity HANDSET WALL FORM Quick Assembly - can be built using only a hammer Reduced weight increases productivity Unsurpassed flexibility in design and availability of panels for a wide variety of applications

More information

HVAC Ductwork and Strut Channels Suspended Ceilings

HVAC Ductwork and Strut Channels Suspended Ceilings General Information General Information Vertigo + Rod Hanger PRODUCT DESCRIPTION Vertigo+ is a one piece, all steel threaded fastening system for suspending threaded rod in applications such as pipe hanging,

More information

SECTION PLATE CONNECTED WOOD TRUSSES

SECTION PLATE CONNECTED WOOD TRUSSES SECTION 06173 PLATE CONNECTED WOOD TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Shop fabricated wood trusses for roof and floor framing. 2. Bridging, bracing, and anchorage. B. Related Sections:

More information

SECTION CLIMBING WALLS

SECTION CLIMBING WALLS SECTION 13120-1 PART 1 - GENERAL 1.1 SUMMARY A. This section includes the following: 1. Custom Climbing Wall. B. Related Sections 1. Section Structural Steel 2. Section Rough Carpentry 3. Finishes 1.2

More information

Nabil A. Rahman, Ph.D., P.E.

Nabil A. Rahman, Ph.D., P.E. STIFFWALL STRAP BRACING SHEAR WALL SYSTEM Nabil A. Rahman, Ph.D., P.E. Introduction Buildings require a vertical load resisting system to provide lateral stiffness and to transfer acting lateral loads

More information

HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT

HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT SAMPLE GUIDE FOR RESIDENTIAL DECKS revised 7 16 Call before you dig! 1 800 272 1000 New Jersey One Call. Utility Mark Out. THIS GENERIC GUIDE IS NOT ALL INCLUSIVE

More information

Field Connector for simple installation. Floating Perimeter detail. Field Connector. Perimeter & XL Connector

Field Connector for simple installation. Floating Perimeter detail. Field Connector. Perimeter & XL Connector mm M0-.5 Turnbuckle connections to structural steel 30mm Perimeter Extrusion Simple supported 4 screw assembly and vertically supported flanged grid 750 Montevideo Road Tel (40)799-4200 Main Runner with

More information

SECTION I -- IRONWORK

SECTION I -- IRONWORK SECTION I -- IRONWORK CONTENTS PAGE 1. GENERAL... I-2 1.1. Introduction... I-2 2. REQUIREMENTS... I-2 2.1. General... I-2 2.2. Auxiliary Framing... I-2 2.3. High Seismic Risk Zone Requirements... I-3 2.4.

More information

Structural vs Nonstructural Members. Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures

Structural vs Nonstructural Members. Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures Structural vs Nonstructural Members Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures Behavior of Cold-Formed Steel Members STEEL DESIGN SPECIFICATIONS Type of steel Specification

More information

Lateral Design of Mid- Rise Wood Structures

Lateral Design of Mid- Rise Wood Structures Lateral Design of Mid- Rise Wood Structures Presented by Ricky McLain, MS, PE, SE Technical Director WoodWorks Texas Workshops December, 2016 Insert picture of me graduating college Follow the load Following

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 4042 Issued 07/2017 This report is subject to renewal 07/2018. DIVISION: 04 00 00

More information

B-LINE SERIES. DURA-BLOK rooftop supports BRTS-17 DURA-BLOK. A complete rooftop support solution

B-LINE SERIES. DURA-BLOK rooftop supports BRTS-17 DURA-BLOK. A complete rooftop support solution DURA-BLOK rooftop supports BRTS-17 B-LINE SERIES DURA-BLOK A complete rooftop support solution DURA-BLOK rooftop solutions support DURA-BLOK supports are made of 100% recycled rubber and are designed to

More information

Industrial Product Guide. For suspending Mechanical & Electrical services, HVAC and Signage

Industrial Product Guide. For suspending Mechanical & Electrical services, HVAC and Signage Industrial Product Guide For suspending Mechanical & Electrical services, HVC and Signage Spiral, Oval and Rectangular Ductwork, Plenum oxes, Destratifier Units, Roof Stacks, Fan Coil Units, Chilled eams,

More information

E. Manufacturers Standardization Society of the Valve and Fittings Industry:

E. Manufacturers Standardization Society of the Valve and Fittings Industry: SECTION 230529 - HANGERS AND SUPPORTS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment curbs. 6. Sleeves. 7. Mechanical

More information

Easy to Use A7 Saves You Time and Money

Easy to Use A7 Saves You Time and Money ADHESIVE ANCHORING SPECIALISTS Easy to Use Saves You Time and Money DESCRIPTION/SUGGESTED SPECIFICATIONS* Fast Dispensing, Fast Curing The acrylic resin and hardening agent are completely mixed as they

More information

Code Compliance Research Report CCRR-0194

Code Compliance Research Report CCRR-0194 Code Compliance Research Report CCRR-0194 Issued: 09-16-2013 Renewal Due: 09-16-2018 Revised: 10-12-2017 DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES Section: 06 05 23 Wood, Plastic, and Composite

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-13 48 00.00 10 (October 2007) ---------------------------------- Preparing Activity: USACE Superseding UFGS-13 48 00.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

SECTION VIBRATION ISOLATION FOR PLUMBING PIPING AND EQUIPMENT

SECTION VIBRATION ISOLATION FOR PLUMBING PIPING AND EQUIPMENT SECTION 220550 - VIBRATION ISOLATION FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL REQUIREMENTS 1.1 SUMMARY A. It is the intent of this specification to provide vibration isolation supports for Plumbing

More information

KS SERIES - VERTICAL INSTALLATION

KS SERIES - VERTICAL INSTALLATION CS-DS-01-KSV CS DISCLAIMER CS-PP-01-KSV PANEL PROFILES CS-PP-02-KSV PANEL PROFILES CS-PP-03-KSV PANEL PROFILES CS-PJ-01-KSV KS SERIES EXPANDED PANEL JOINT CS-PJ-02-KSV KS SERIES ENGAGED PANEL JOINT CS-PJ-03-KSV

More information

Fire Barrier Duct Wrap 615+

Fire Barrier Duct Wrap 615+ Fire Barrier Duct Wrap 615+ Duct Wrap Fire Protection System for Commercial Kitchen Grease and Ventilation Air Ducts Product Data Batts and blankets for use in fire resistive duct assemblies see UL fire

More information

EVALUATION REPORT. PFC-5551 Reissued April 1, Filing Category: DESIGN Steel (038)

EVALUATION REPORT. PFC-5551 Reissued April 1, Filing Category: DESIGN Steel (038) ICBO Evaluation Service, Inc. 5360 WORKMAN MILL ROAD WHITTIER, CALIFORNIA 90601-2299 A subsidiary corporation of the International Conference of Building Officials EVALUATION REPORT Copyright 2001 ICBO

More information

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.

This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 4105 Issued 08/2017 This report is subject to renewal 08/2018. DIVISION: 04 00 00

More information

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: MASON WEST, INC.

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS SECTION: CONCRETE ANCHORS REPORT HOLDER: MASON WEST, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3443 Issued 04/2017 This report is subject to renewal 04/2018. DIVISION: 03 00 00

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 687 (6) 699 0 www.icc es.org ESR 8 Reissued 0/08 This report is subject to renewal 0/09. DIVISION: 0 00 00 MASONRY SECTION:

More information

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel

More information

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS SECTION 08 32 20 CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

Superstrut. Metal Framing. Pipe Straps, Pipe Clamps and Hangers

Superstrut. Metal Framing. Pipe Straps, Pipe Clamps and Hangers Design Loads Where design loads are indicated, they provide for a safety factor of 3 in conformance with the American Standard Code for Pressure Piping. Hanger Design Pipe hangers are of advanced design

More information

Modular CABANA Kit 16 x 16 (6x6) Lumber: Western Red CEDAR #1 (Cabinet) Shingles: 5X / 16" long / 1/2" thick or 16 oz. copper

Modular CABANA Kit 16 x 16 (6x6) Lumber: Western Red CEDAR #1 (Cabinet) Shingles: 5X / 16 long / 1/2 thick or 16 oz. copper Lumber: Western Red CEDAR #1 (Cabinet) Shingles: 5X / 16" long / 1/2" thick or 16 oz. copper Modular CABANA Kit 16 x 16 (6x6) Hipped Roof & Build-in Transoms Entry Key Lock Set (bright brass or dark bronze)

More information

CANTILEVER RACK SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE

CANTILEVER RACK SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE CANTILEVER RACK SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE This specification is intended to describe the general requirements applicable to a proper structural cantilever rack design. In addition, it is

More information

Canopies & Exposed Structure Areas Commercial Ceilings and Walls Solutions Guide

Canopies & Exposed Structure Areas Commercial Ceilings and Walls Solutions Guide CEILING & WALL SYSTEMS Canopies & Exposed Structure Areas Commercial Ceilings and Walls Solutions Guide Canopies & Exposed Structures SOUNDSCAPES Acoustical Canopies Product Description SoundScapes are

More information

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 43 6587 (56) 699 0543 www.icc es.org ESR 3754 Reissued 09/07 This report is subject to renewal 09/09. DIVISION: 03 00 00 CONCRETE

More information

Strength Design of Reinforced Concrete Structures

Strength Design of Reinforced Concrete Structures Chapter 6 Strength Design of Reinforced Concrete Structures 6.1 Analysis and Design General Considerations 6.1.1 Convention and Notation Unless otherwise explicitly stated, the following units shall be

More information

QuakeLoc. Seismic Cable Restraint Connector for piping, duct, electrical cable trays, and suspended equipment. MADE IN THE USA MADE IN THE USA

QuakeLoc. Seismic Cable Restraint Connector for piping, duct, electrical cable trays, and suspended equipment. MADE IN THE USA MADE IN THE USA MADE IN THE USA MADE IN THE USA MADE IN THE USA MADE IN THE USA QuakeLoc Seismic Cable Restraint Connector for piping, duct, electrical cable trays, and suspended equipment. MADE IN THE USA QuakeKit-P

More information

TERWA REBAR CONNECTION COUPLERS

TERWA REBAR CONNECTION COUPLERS TERWA REBAR CONNECTION COUPLERS CARES Technical Approval 5058 TA1B Introduction The Terwa Parallel Threaded Coupler is a full bar strength system (the coupling is stronger than the associated rebar, sometimes

More information

Copyright. magazine. CFS Load Bearing Construction

Copyright. magazine. CFS Load Bearing Construction Progressive Collapse Requirements Cold-Formed Steel Load Bearing Construction By Nabil A. Rahman, Ph.D., P.E., Michael Booth and Gary Bennett Figure 1: Cold formed steel load bearing mid-rise construction.

More information

Installing Seismic Restraints for Electrical Equipment

Installing Seismic Restraints for Electrical Equipment Installing Seismic Restraints for Electrical Equipment Course No: S05-009 Credit: 5 PDH Elie Tawil, P.E., LEED AP Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

HIGH PERFORMANCE REINFORCEMENT PRODUCTS. Product Catalogue.

HIGH PERFORMANCE REINFORCEMENT PRODUCTS. Product Catalogue. HIGH PERFORMANCE REINFORCEMENT PRODUCTS Product Catalogue www.hrc-europe.com HRC and its product philosophy The use of T-headed bars in concrete structures has some remarkable benefits compared to the

More information

ASSEMBLY INSTRUCTIONS RESIDENTIAL SOLUTION CROSSRAIL GROUND MOUNT SYSTEM USA

ASSEMBLY INSTRUCTIONS RESIDENTIAL SOLUTION CROSSRAIL GROUND MOUNT SYSTEM USA ASSEMBLY INSTRUCTIONS RESIDENTIAL SOLUTION CROSSRAIL GROUND MOUNT SYSTEM USA TABLE OF CONTENTS TABLE OF CONTENTS SAFETY REGULATIONS MATERIALS REQUIRED ASSEMBLY ENGINEERING DRAWINGS TERMS AND CONDITIONS

More information

SYSTEM S7-RHOMBOS INSTALLATION MANUAL

SYSTEM S7-RHOMBOS INSTALLATION MANUAL SYSTEM S7-RHOMBOS INSTALLATION MANUAL GENERAL INFORMATION GENERAL INFORMATION This assembly manual addresses all metal ceilings manufactured by durlum. The different sections describe the related/relevant

More information

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015 0 ICC ES Report ICC ES (800) 42 6587 (562) 699 054 www.icc es.orgg 000 Most Widely Accepted and Trusted ESR 2269 Reissued 02/205 This report is subject to renewal 02/207. DIVISION: 0 00 00 CONCRETE SECTION:

More information

American Metal Specialties, Inc.

American Metal Specialties, Inc. American Metal Specialties, Inc. www.cablerailings.com (253) 272-9344 (253) 627-3843 Fax PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 05 73 00 STAINLESS STEEL ORNAMENTAL HANDRAILS AND RAILINGS For best

More information

WIND SPEED AND DESIGN CRITERIA FOR FLEXIBLE FACE SIGNS CONSTRUCTED OF ABC EXTRUSIONS

WIND SPEED AND DESIGN CRITERIA FOR FLEXIBLE FACE SIGNS CONSTRUCTED OF ABC EXTRUSIONS WIND SPEED AND DESIGN CRITERIA FOR FLEXIBLE FACE SIGNS CONSTRUCTED OF ABC EXTRUSIONS 2005 EDITION This edition is based upon ASCE 7-98 recommendations for wind speed and wind loads. These have changed

More information

DIVISION: EARTHWORK SECTION: BORED PILES REPORT HOLDER: CANTSINK MANUFACTURING, INC. 71 FIRST AVENUE LILBURN, GEORGIA 30047

DIVISION: EARTHWORK SECTION: BORED PILES REPORT HOLDER: CANTSINK MANUFACTURING, INC. 71 FIRST AVENUE LILBURN, GEORGIA 30047 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1559 Reissued 12/2016 This report is subject to renewal 12/2018. DIVISION: 31 00

More information

High Strength Epoxy Tested in Accordance with ICC-ES AC308

High Strength Epoxy Tested in Accordance with ICC-ES AC308 ADHESIVE ANCHORING SPECIALISTS High Strength Epoxy Tested in Accordance with ICC-ES AC308 DESCRIPTION/SUGGESTED SPECIFICATIONS* The epoxy resin and hardener are completely mixed as they are dispensed from

More information

R-Group Finland Oy. RTA, RWTL and RWTS Lifting anchors Design instructions

R-Group Finland Oy. RTA, RWTL and RWTS Lifting anchors Design instructions R-Group Finland Oy RTA, RWTL and RWTS Lifting anchors Design instructions According to Eurocodes, EU Machinery directive 2006/42/EC and VDI/BV-BS 6205 CE Approved 28.12.2016 2 Table of contents 1 DESCRIPTION

More information

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses Released May 20, 2009 Updated March 9, 2011 Introduction: Wood frame structures with attached brick masonry veneer

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-13 48 00 (August 2008) --------------------------- Preparing Activity: USACE Superseding UFGS-13 48 00 (October 2007) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

PATHWAYS FOR COMMUNICATIONS SYSTEMS

PATHWAYS FOR COMMUNICATIONS SYSTEMS 270528 PATHWAYS FOR PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment for the complete installation of work called for in the Contract Documents. 1.2 SCOPE OF WORK A. This

More information

SHEAR BRACE. Featuring ilevel Shear Braces for Engineered and Prescriptive Applications iLevel8 (

SHEAR BRACE. Featuring ilevel Shear Braces for Engineered and Prescriptive Applications iLevel8 ( WALL SOLUTIONS SHEAR BRACE 2006 IBC/IRC Code Accepted* *Achieved code evaluation report recognition (ICC ES ESR-2652) for compliance with the 2006 IBC/IRC Featuring ilevel Braces for Engineered and Prescriptive

More information

High Strength Epoxy Tested in Accordance with ICC-ES AC308

High Strength Epoxy Tested in Accordance with ICC-ES AC308 ADHESIVE ANCHORING SPECIALISTS DESCRIPTION/SUGGESTED SPECIFICATIONS* The 100% epoxy resin and hardener are completely mixed as they are dispensed from the dual cartridge through a static mixing nozzle,

More information

Wall Panels. Structural wall panel. Architectural wall panel. Cladding wall panel. Sandwich wall panel

Wall Panels. Structural wall panel. Architectural wall panel. Cladding wall panel. Sandwich wall panel Wall Panels Structural wall panel Architectural wall panel Cladding wall panel Sandwich wall panel Wall Panels Assorted styles and colours Reveals and other patterns Painted finish Bolted, welded and knife

More information

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017

Northpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017 SECTION 055213 - PIPE AND TUBE RAILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS DIVISION: CONCRETE ANCHORS REPORT HOLDER: DEWALT

DIVISION: CONCRETE SECTION: CAST IN CONCRETE ANCHORS DIVISION: CONCRETE ANCHORS REPORT HOLDER: DEWALT 0 Most Widely Accepted and Trusted ICC ES Listing Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ELC 3657 Issued 05/2017 This listing is subject to renewal 05/2018. DIVISION: 03 00 00 CONCRETE

More information

SJI Code of Standard Practice

SJI Code of Standard Practice Standard Practice CODE OF STANDARD PRACTICE FOR STEEL JOISTS AND JOIST GIRDERS SECTION 1 GENERAL 1.1 SCOPE Adopted by the Steel Joist Institute April 7, 1931 Revised to May 18, 2010 - Effective December

More information

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: SAS STRESSTEEL INC. 100 NEW DUTCH LANE FAIRFIELD, NEW JERSEY 07004

DIVISION: CONCRETE SECTION: REINFORCING STEEL REPORT HOLDER: SAS STRESSTEEL INC. 100 NEW DUTCH LANE FAIRFIELD, NEW JERSEY 07004 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1163 Reissued 12/2016 This report is subject to renewal 12/2017. DIVISION: 03 00

More information

SECTION DECORATIVE METAL AND GLASS RAILING

SECTION DECORATIVE METAL AND GLASS RAILING SECTION 05 73 00 DECORATIVE METAL AND GLASS RAILING PART 1 GENERAL 1.1 SUMMARY A) This section includes both standard and custom handrails as shown in the contract drawings. B) These include aluminum,

More information

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3931 Reissued 07/2017 This report is subject to renewal 07/2019. DIVISION: 03 00

More information

FEATURES APPLICATIONS. Technical data sheet SSW - STEEL STRONG-WALL FOR TIMBER FRAME RACKING RESISTANCE.

FEATURES APPLICATIONS. Technical data sheet SSW - STEEL STRONG-WALL FOR TIMBER FRAME RACKING RESISTANCE. The Steel Strong-Wall is a corrugated steel panel which is designed to be fixed directly to the concrete foundations of a building, within the external or internal wall, via a bolted connection. FEATURES

More information

DIVISION: EARTHWORK SECTION: BORED PILES REPORT HOLDER: HELICAL ANCHORS, INC BOONE AVENUE, NORTH MINNEAPOLIS, MINNESOTA 55428

DIVISION: EARTHWORK SECTION: BORED PILES REPORT HOLDER: HELICAL ANCHORS, INC BOONE AVENUE, NORTH MINNEAPOLIS, MINNESOTA 55428 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3982 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 31 00

More information

PERI PD 8 The cost-effective shoring for slab tables and high loads

PERI PD 8 The cost-effective shoring for slab tables and high loads PERI PD 8 The cost-effective shoring for slab tables and high loads Edition 06/2010 PERI GmbH Formwork Scaffolding Engineering P.O. Box 1264 89259 Weissenhorn Germany Tel +49 (0)7309.950-0 Fax +49 (0)7309.951-0

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2269 Reissued 02/2017 This report is subject to renewal 02/2019. DIVISION: 03 00

More information

Raised Basement. Mechanical Installation Guide

Raised Basement. Mechanical Installation Guide R Raised Basement Mechanical Installation Guide Ensure masonry work is correct. If recessed, the depth must be 14 inches deep unless otherwise specified for a custom application. Width and length may vary

More information

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance

Open-Web Trusses. Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses. Design Flexibility. Outstanding Strength-to-Weight Performance Open-Web Trusses Including Red-L, Red-W, Red-S, Red-M and Red-H Trusses Download your free copy at RedBuilt.com. Specify Open-Web trusses for your next project using RedSpec single-member sizing software.

More information

ALLOWABLE STRESS DESIGN OF CONCRETE MASONRY LINTELS. TEK 17-1C Structural (2009) Related TEK: Uniform load. Triangular load. Concentrated loads

ALLOWABLE STRESS DESIGN OF CONCRETE MASONRY LINTELS. TEK 17-1C Structural (2009) Related TEK: Uniform load. Triangular load. Concentrated loads An information series from the national authority on concrete masonry technology ALLOWABLE STRESS DESIGN OF CONCRETE MASONRY LINTELS TEK 17-1C Structural (2009) INTRODUCTION Lintels and beams are horizontal

More information

DIVISION: EARTHWORK SECTION: BORED PILES REPORT HOLDER: GOLIATHTECH INCORPORATED 175B RUE PELADEAU MAGOG, QUEBEC J1X 5G9 CANADA

DIVISION: EARTHWORK SECTION: BORED PILES REPORT HOLDER: GOLIATHTECH INCORPORATED 175B RUE PELADEAU MAGOG, QUEBEC J1X 5G9 CANADA 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3726 Issued 10/2017 This report is subject to renewal 10/2018. DIVISION: 31 00 00

More information

200 / 300 SERIES PANELS COLD STORAGE

200 / 300 SERIES PANELS COLD STORAGE CS-DS-01-200/300 DISCLAIMER CS-CD-01-200/300 KINGSPAN CEILING DESIGN POLICY AND PROCEDURES CS-CD-02-200/300 KINGSPAN CEILING DESIGN POLICY AND PROCEDURES CONTINUED CI-PP-01-200 PANEL PROFILES 200 SERIES

More information

DESIGN CRITERIA. Allowable Stress Design (ASD) AISC-1999.

DESIGN CRITERIA. Allowable Stress Design (ASD) AISC-1999. DESIGN CRITERIA 1. INTRODUCTION This appendix summarizes the codes, standards, criteria, and practices that are generally used in the design and construction structural engineering system for the Sarker

More information