Section Sound Control

Size: px
Start display at page:

Download "Section Sound Control"

Transcription

1 Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B Ontario-NBC CODE REFERENCE: Division B / DESCRIPTION OF THE PROPOSED AMENDMENT The proposed change introduces a new sound transmission metric and additional guidance on the new metric. This section has also been restructured. EXISTING 2012 BUILDING CODE PROVISION(S) Section Sound Control Sound Transmission Class Rating (Airborne Sound) Determination of Sound Transmission Class Ratings (1) Sound transmission class ratings shall be determined in accordance with ASTM E413, Classification for Rating Sound Insulation, using results from measurements in accordance with, (a) ASTM E90, Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements, or (b) ASTM E336, Measurement of Airborne Sound Attenuation Between Rooms in Buildings. (See Appendix A.) Required Sound Control Locations (Airborne Sound) Minimum Sound Transmission Class Ratings (1) Except as provided in Sentence (2), every dwelling unit and every suite in hotels shall be separated from every other space in a building in which noise may be generated, by an assembly providing a sound transmission class rating of at least 50, measured in accordance with Subsection or as listed in Tables 1 and 2 of MMAH Supplementary Standard SB-3, Fire and Sound Resistance of Building Assemblies. (2) Where a dwelling unit or suite in a hotel is adjacent to an elevator shaft or a refuse chute, the separating assembly shall have a sound transmission class rating of at least 55, measured in accordance with Subsection or as listed in Tables 1 and 2 of MMAH Supplementary Standard SB-3, Fire and Sound Resistance of Building Assemblies. Page 1 Copyright Queen s Printer for Ontario 2016

2 Building Services in an Assembly (1) Building services located in an assembly required to have a sound transmission class rating shall be installed in a manner that will not decrease the required rating of the assembly. A (1) Sound Transmission Class Ratings. The specified STC rating of 50 is considered the minimum acceptable value, but many builders prefer to design for STC 55 or more in high quality accommodation. Another reason to choose assemblies rated higher than STC 50 is that the STC ratings of assemblies are based on laboratory tests, but the sound transmission of any assembly as constructed in the field may be significantly less than its rating. This can be due to sound leaks, departures from design, poor workmanship or indirect (flanking) transmission paths overlooked in design. To provide a margin of safety to compensate for these, builders often select wall and floor systems that have been rated at least 5 points higher than the design STC rating in laboratory tests. Sound leaks can occur where one wall meets another, the floor, or the ceiling. Leaks may also occur where the wall finish is cut for the installation of equipment or services. Avoid back-to-back electrical outlets or medicine cabinets. Carefully seal cracks or openings so structures are effectively airtight. Apply sealant below the plates in stud walls, between the bottom of drywall sheets and the structure behind, around all penetrations for services and, in general, wherever there is a crack, a hole or the possibility of one developing. Sound-absorbing material inside a well-designed wall decreases sound transmission. It has another advantage; it also helps to reduce the effects of leaks due, perhaps, to poor workmanship. Indirect or flanking transmission arises where the parts of a building are rigidly connected together and where cavities in hollow walls or floors, or continuous lightweight layers connect apartments. Sound travels in cavities, as vibration along surfaces and through walls, ceilings and floors to adjacent rooms. Many paths other than the direct one through the party wall or floor may be involved. To achieve good sound insulation, transmission along flanking paths must be minimized by introducing breaks and resilient connections in the construction. Some examples of bad and good details are shown in Figure (1). Figure A (1) Cross Section Through Wall/floor Junctions Impact Noise Changes to construction should not be made without consultation with someone competent in the field of acoustical design. Adding extra layers of drywall to walls in an attempt to reduce sound transmission, can actually increase it if done incorrectly. For example, attaching drywall on resilient channels directly to an existing wall or ceiling usually increases low frequency sound transmission. Adding an additional layer of drywall inside a double layer wall will also seriously increase sound transmission. Adding blocking inside walls to reduce the risk of fire spread should be done so it does not increase vibration transmission from one part of a wall or floor to the other. To verify that acoustical privacy is being achieved, a field test can be done at an early stage in the construction; ASTM E336, Measurement of Airborne Sound Attenuation Between Rooms in Buildings will give a complete measurement. A simpler and less expensive method is ASTM E597, Determining a Single Number Rating of Airborne Sound Insulation in Multi Unit Building Specifications. The rating provided by this test is usually within 2 points of the STC obtained from

3 ASTM E336. It is useful for verifying performance and finding problems during construction. Alterations can then be made prior to project completion. Impact Noise Section has no requirements for control of impact noise transmission. Footstep and other impacts can cause severe annoyance in multi-family residences. Builders concerned about quality and reducing occupant complaints will ensure that floors are designed to minimize impact transmission. A recommended criterion is that bare floors (tested without a carpet) should achieve an impact insulation class (IIC) of 55. Some lightweight floors that satisfy this requirement may still cause complaints about low frequency impact noise transmission. Adding carpet to a floor will always increase the IIC rating but will not necessarily reduce low frequency noise transmission. Good footstep noise rejection requires fairly heavy floor slabs or floating floors. Most frequently used methods of test for impact noise are ASTM E492, Laboratory Measurement of Impact Sound Transmission Through Floor-Ceiling Assemblies Using The Tapping Machine, or ASTM E1007, Field Measurement of Tapping Machine Impact Sound Transmission Through Floor-Ceiling Assemblies and Associated Support Structures. Machinery Noise Elevators, garbage chutes, plumbing, fans, and heat pumps are common sources of noise in buildings. To reduce annoyance from these, they should be placed as far as possible from sensitive areas. Vibrating parts should be isolated from the building structure using resilient materials such as neoprene or rubber. PROPOSED CODE CHANGE Revise Section 9.11 as follows: Section Sound Transmission Control Sound Transmission Class Rating (Protection from Airborne SoundNoise) Minimum Sound Transmission Class RatingsRequired Protection (1) Except as provided in Sentence (2), and (3), every a dwelling unit and every suite in hotels shall be separated from every other space in a building in which noise may be generated, by an assembly providing a sound transmission class rating of at least 50, measured in accordance with Subsection or as listed in Tables 1 and 2 of MMAH Supplementary Standard SB-3, Fire and Sound Resistance of Building Assemblies. (a) separating assembly and adjoining constructions that, which together provide an apparent sound transmission class rating (ASTC) of not less than 47, or(b) a separating assembly providing a sound transmission class (STC) rating of at least 50 and adjoining constructions that conform to Article (2) In a house, each dwelling unit shall be separated from every other space in the house in which noise may be transmitted by, (a) construction (i) whose joist spaces are filled with sound-absorbing material of not less than 150 mm nominal thickness, (ii) whose stud spaces are filled with sound-absorbing material, (iii) having a resilient channel on one side of the separation spaced 406 or 610 mm o.c., and (iv) having not less than 12.7 mm thick gypsum board on ceilings and on both sised of walls, or Copyright Queen s Printer for Ontario 2015 Page 3

4 (b) (c) construction providing a sound transmission class of not less than 43, or a separating assembly and adjoining constructions, which together provide an apparent sound transmission class (ASTC) rating of not less than 40. (23) Where a dwelling unit or suite in a hotel is adjacent to an elevator shaft or a refuse chute, the Construction separating a dwelling unit or suite in a hotel from an elevator shaft or refuse chute assembly shall have a sound transmission class (STC) rating of at least 55., measured in accordance with Subsection or as listed in Tables 1 and 2 of MMAH Supplementary Standard SB-3, Fire and Sound Resistance of Building Assemblies Determination of Sound Transmission Class Ratings (1) The Ssound transmission class ratings shall be determined in accordance with ASTM E413, Classification for Rating Sound Insulation, using results from measurements carried out in accordance with ASTM E 90, Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements. (a) ASTM E90, Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements, or (b) ASTM E336, Measurement of Airborne Sound Attenuation Between Rooms in Buildings. (See Appendix A.) (2) Apparent sound transmission class (ASTC) ratings of sound transmission between adjoining spaces in a building shall be determined (a) determined in accordance with ASTM E 413, Classification for Rating Sound Insulation, using results from measurements carried out in accordance with ASTM E 336, Measurement of Airborne Sound Attenuation between Rooms in Buildings, or (b) calculated in accordance with Article or Article Compliance with Required Ratings (1) Compliance with STC ratings shall be demonstrated through, (a) measurements carried out in accordance with Sentence (1), or (b) construction of separating assemblies conforming to Tables 1 or 2 of MMAH Supplementary Standard SB-3, Fire and Sound Resistance of Building Assemblies, as applicable. (2) Compliance with ASTC ratings shall be demonstrated by (a) measurement or calculation according to Sentence (2), or (b) construction of separating assemblies conforming to Tables 1 or 2 of MMAH Supplementary Standard SB-3, Fire and Sound Resistance of Building Assemblies, as applicable, that have a sound transmission class rating of not less than 50 in conjunction with flanking assemblies constructed in accordance with Article (see Appendix A) Adjoining Constructions (See Appendix A) (1) This Article applies where the required protection is provided in accordance with Clause (1)(b) and compliance is demonstrated in accordance with Clause (2)(b). (2) Flanking wall assemblies connected to a separating floor or ceiling assembly shall be constructed with (a) concrete or concrete block having a mass per area greater than 200 kg/m 2, or (b) gypsum board finish that (i) is supported on wood or steel framing, and (ii) ends or is interrupted where it meets the structure of the separating floor or ceiling assembly. (3) Flanking wall and ceiling assemblies connected to a separating wall assembly shall be constructed with, (a) concrete or concrete block having a mass per area greater than 300 kg/m 2, or Copyright Queen s Printer for Ontario 2015 Page 4

5 (b) gypsum board finish that (i) is supported on wood or steel framing, and (ii) ends or is interrupted where it meets the structure of the separating wall assembly or, for double-stud walls, where it meets the space between the two lines of studs. (4) Flanking floor assemblies connected to a separating wall assembly shall be, (a) constructed (i) with concrete having a mass per area greater than 300 kg/m 2, or be constructed (ii) in accordance with Section 9.16., or (b) supported on joists or trusses that are not continuous across the junction and are covered with floor treatments in accordance with Table for the applicable wall construction. Table Floor Treatments for Flanking Wood-Framed Floor Assemblies in Horizontally Adjoining Spaces Forming Part of Sentence (4) Type of Separating Wall Assembly with STC 50 from MMAH Supplementary Standard SB-3 Fire and Sound Resistance of Building Assemblies Minimum Requirements for Floor Treatments Applied Over Subfloor of Wood- Framed Flanking Floor Assemblies on Both Sides of Floor/Wall Junction W5, W6, W10, W12 (staggered studs) wood strip flooring not less than 16 mm thick aligned parallel to separating wall, or one layer OSB or plywood not less than 15.5 mm thick plus finished flooring, or one additional material layer plus finished flooring having a combined mass per area not less than 8 kg/m² (1) W4, W11 (staggered studs) one layer of OSB or plywood not less than 12.5 mm thick plus hardwood strip flooring not less than 19 mm thick aligned parallel to separating wall, or one additional material layer plus finished flooring having a combined mass per area 16 kg/m² (1) W8, W9 (staggered studs) concrete or gypsum concrete topping not less than 19 mm thick bonded to the subfloor plus finished flooring, or one additional material layer plus finished flooring having a combined mass per area not less than 32 kg/m² (1) Copyright Queen s Printer for Ontario 2015 Page 5

6 Type of Separating Wall Assembly with STC 50 from MMAH Supplementary Standard SB-3 Fire and Sound Resistance of Building Assemblies Minimum Requirements for Floor Treatments Applied Over Subfloor of Wood- Framed Flanking Floor Assemblies on Both Sides of Floor/Wall Junction W13, W14, W15 (double stud walls) Where a continuous subfloor or other rigid materials at the floor/wall junction provide structural connection between the two rows of studs in the separating wall:, hardwood strip flooring not less than 16 mm thick aligned parallel to separating wall, or one layer OSB or plywood not less than 15.5 mm thick plus finished flooring, or one additional material layer plus finished flooring having a combined mass per area not less than 8 kg/m² (1) B1 to B10 any finished flooring Notes to Table : (1) See Appendix A Minimum Sound Transmission Class Ratings (1) Except as provided in Sentence (2), every dwelling unit and every suite in hotels shall be separated from every other space in a building in which noise may be generated, by an assembly providing a sound transmission class rating of at least 50, measured in accordance with Subsection or as listed in Tables 1 and 2 of MMAH Supplementary Standard SB-3, Fire and Sound Resistance of Building Assemblies. (2) Where a dwelling unit or suite in a hotel is adjacent to an elevator shaft or a refuse chute, the separating assembly shall have a sound transmission class rating of at least 55, measured in accordance with Subsection or as listed in Tables 1 and 2 of MMAH Supplementary Standard SB-3, Fire and Sound Resistance of Building Assemblies Building Services in an Assembly (1) Building services located in an assembly required to have a sound transmission class rating shall be installed in a manner that will not decrease the required rating of the assembly. A (1) Sound Transmission Class Ratings. Airborne Sound Airborne sound is transmitted between adjoining spaces directly through the separating wall, floor and ceiling assemblyies and via the junctions between these separating assemblies and the flanking assemblies. Copyright Queen s Printer for Ontario 2015 Page 6

7 The Sound Transmission Class (STC) rating describes the performance of the separating wall or floor/ceiling assembly, whereas the Apparent Sound Transmission Class (ASTC) takes into consideration the performance of the separating element as well as the flanking transmission paths. Therefore, from the occupants point of view, the best indicator of noise protection between the two spaces is the ASTC rating. As a key principle, it is important to follow a whole system approach when designing or constructing assemblies that separate dwelling units because the overall sound performance of walls and floors is also influenced by fire protection measures and the structural design of the assemblies. Likewise, changes to the construction of assemblies to meet sound transmission requirements may have fire and structural implications. Another key principle is that enhancing the performance of the separating element does not automatically enhance the system s performance. For horizontally adjoining spaces, the separating assembly is the intervening wall and the pertinent flanking surfaces include those of the floor, ceiling, and side wall assemblies that have junctions with the separating wall assembly, normally at its four edges. For each of these junctions, there are a set of sound transmission paths. Figure A A illustrates the horizontal sound transmission paths at the junction of a separating wall with flanking floor assemblies. Figure A A Horizontal Sound Transmission Path IMAGE N/A For vertically adjoining spaces, the separating assembly is the intervening floor/ceiling and the pertinent flanking surfaces include those of the side wall assemblies in the upper and lower rooms that have junctions with the separating floor/ceiling assembly at its edges, of which there are normally four. For each of these junctions, there is a set of sound transmission paths. Figure A B illustrates the vertical sound transmission paths at the junction of a separating floor/ceiling assembly with two flanking wall assemblies. Figure A B Vertical Sound Transmission Path IMAGE N/A Control of sound leaks The specified STC rating of 50 is considered the minimum acceptable value, but many builders prefer to design for STC 55 or more in high quality accommodation. Another reason to choose assemblies rated higher than STC 50 is that the STC ratings of assemblies are based on laboratory tests, but the sound transmission of any assembly as constructed in the field may be significantly less than its rating. This can be due to sound leaks, departures from design, poor workmanship or indirect (flanking) transmission paths overlooked in design. To provide a margin of safety to compensate for these, builders often select wall and floor systems that have been rated at least 5 points higher than the design STC rating in laboratory tests. The metrics used to characterize the sound transmission performance of assemblies separating dwelling units do not account for the adverse effects of air leaks in those assemblies, which can transfer sound. Sound leaks can occur where onea wall meets another wall, the floor, or the ceiling. Leaks may alsothey can also occur where the wall finish is cut for the installation of equipment or services. The following are examples of measures for controlling sound leaks: Avoid back-to-back electrical outlets or medicine cabinets; Carefully seal cracks or openings so structures are effectively airtight; Apply sealant below the plates in stud walls, between the bottom of drywallgypsum board sheets and the structure behind, around all penetrations for services and, in general, wherever there is a crack, a hole or the possibility of one developing; Copyright Queen s Printer for Ontario 2015 Page 7

8 include Ssound-absorbing material inside a well-designedthe wall decreases sound transmissionif not already required. It has another advantage; it also helps to reduce the effects of leaks due, perhaps, to poor workmanship. The reduction of air leakage is also addressed to some extent by the smoke tightness requirements in the Code. The calculation of and laboratory testing for STC and ASTC ratings are performed on intact assemblies having no penetrations or doors. When measuring ASTC ratings in the field, openings can be blocked with insulation and drywall. Indirect or flanking transmission arises where the parts of a building are rigidly connected together and where cavities in hollow walls or floors, or continuous lightweight layers connect apartments. Sound travels in cavities, as vibration along surfaces and through walls, ceilings and floors to adjacent rooms. Many paths other than the direct one through the party wall or floor may be involved. To achieve good sound insulation, transmission along flanking paths must be minimized by introducing breaks and resilient connections in the construction. Some examples of bad and good details are shown in Figure (1). Figure A (1) Cross Section Through Wall/floor Junctions Impact Noise Changes to construction should not be made without consultation with someone competent in the field of acoustical design. Adding extra layers of drywall to walls in an attempt to reduce sound transmission, can actually increase it if done incorrectly. For example, attaching drywall on resilient channels directly to an existing wall or ceiling usually increases low frequency sound transmission. Adding an additional layer of drywall inside a double layer wall will also seriously increase sound transmission. Adding blocking inside walls to reduce the risk of fire spread should be done so it does not increase vibration transmission from one part of a wall or floor to the other. To verify that the required acoustical privacyperformance is being achieved, a field test can be done at an early stage in the construction; ASTM E336, Measurement of Airborne Sound Attenuation Between Rooms in Buildings will gives a complete measurement. A simpler and less expensive method is presented in ASTM E597, Determining a Single Number Rating of Airborne Sound Insulation for Use in Multi-Unit Building Specifications. The rating provided byderived from this test is usually within 2 points of the STC obtained from ASTM E336. It is useful for verifying performance and finding problems during construction. Alterations can then be made prior to project completion. Impact Noise Section has no requirements for the control of impact noise transmission. However, Ffootstep and other impacts can cause severe annoyance in multi-family residences. Builders concerned about quality and reducing occupant complaints will ensure that floors are designed to minimize impact transmission. A recommended criterion is that bare floors (tested without a carpet) should achieve an impact insulation class (IIC) of 55. Some lightweight floors that satisfy this requirement may still causeelicit complaints about low frequency impact noise transmission. Adding carpet to a floor will always increase the IIC rating but will not necessarily reduce low frequency noise transmission. Good footstep noise rejection requires fairly heavy floor slabs or floating floors. Impact noise requirements are being considered for inclusion in future editions of the OBC. Copyright Queen s Printer for Ontario 2015 Page 8

9 The Mmost frequently used test methods of test for impact noise are ASTM E492, Laboratory Measurement of Impact Sound Transmission Through Floor-Ceiling Assemblies Using The Tapping Machine, or ASTM E1007, Field Measurement of Tapping Machine Impact Sound Transmission Through Floor-Ceiling Assemblies and Associated Support Structures. Machinery Noise Elevators, garbage chutes, plumbing, fans, and heat pumps are common sources of noise in buildings. To reduce annoyance from these, they should be placed as far as possible from sensitive areas. Vibrating parts should be isolated from the building structure using resilient materials such as neoprene or rubber. A Control of Airborne Noise in Buildings. Tables 1 and 2 of MMAH SB-3 Fire and Sound Resistance of Building Assemblies present separating assemblies that comply with Subsection However, selecting an appropriate separating assembly is only one part of the solution for reducing airborne sound transmission between adjoining spaces: to fully address the sound performance of the whole system, flanking assemblies must be connected to the separating assembly in accordance with Article A Adjoining Constructions. Tables A A to A D present generic options for the design and construction of junctions between separating and flanking assemblies. Constructing according to these options is likely to meet or exceed an ASTC rating of 47. Other designs may be equally acceptable if their sound resistance can be demonstrated to meet the minimum ASTC rating or better on the basis of tests referred to in Article , or if they comply with Subsection However, some caution should be applied when designing solutions that go beyond the options provided in these Tables: for example, adding more material to a wall could negatively impact its sound performance or have no effect at all. Table A A presents compliance options for the construction of separating wall assemblies with flanking floor, ceiling and wall assemblies in horizontally adjoining spaces. Copyright Queen s Printer for Ontario 2015 Page 9

10 Table A A Options for the Design and Construction of Junctions and Flanking Surfaces Between Separating Wall Assemblies in Horizontally Adjoining Spaces for Compliance with Clause (1)(b) Type of Separating Wall Assembly with STC 50 from Table 1 of MMAH SB-3 Fire and Sound Resistance of Building Assemblies Options for Design and Construction of Junctions and Flanking Surfaces (1) to Address Horizontal Sound Transmission Paths Bottom Junction (between separating wall and flanking floors) Top Junction (between separating wall and flanking ceiling) Side Junctions (between separating wall and flanking walls) W4, W5, W6 (single stud) W8, W9, W10, W11, W12 (staggered studs) for additional material layer and finished flooring, see Table subfloor on both sides of wall is plywood, OSB, waferboard (15.5 mm thick) or tongue and groove lumber ( 17 mm thick) floor is framed with wood joists, wood I-joists or wood trusses spaced 400 mm o.c., with or without absorptive material (2) in cavities floor joists or trusses are oriented parallel to separating wall (non-loadbearing case) or perpendicular to separating wall but are not continuous across junction (loadbearing case) ceiling is framed with wood joists, wood I-joists, or wood trusses, with or without absorptive material (2) in cavities ceiling joists or trusses are oriented perpendicular to separating wall but are not continuous across junction (loadbearing case) or parallel to junction (non-loadbearing case) gypsum board ceiling is fastened directly to bottom of ceiling framing or on resilient metal channels (3) Example Showing Side View of Bottom and Top Junctions gypsum board on flanking walls ends or is cut at separating wall and is fastened directly to framing or on resilient metal channels (3) flanking wall is framed with single row of wood studs, staggered studs on a single 38 mm x 140 mm plate, or 2 rows of 38 mm x 89 mm wood studs on separate 38 mm x 89 mm plates, with or without absorptive material (2) in cavities flanking wall framing is structurally connected to separating wall and terminates where it butts against framing of separating wall or is continuous across junction Example Showing Plan View of Side Junctions Copyright Queen s Printer for Ontario 2015 Page 10

11 Type of Separating Wall Assembly with STC 50 from Table 1 of MMAH SB-3 Fire and Sound Resistance of Building Assemblies Options for Design and Construction of Junctions and Flanking Surfaces (1) to Address Horizontal Sound Transmission Paths Bottom Junction (between separating wall and flanking floors) Top Junction (between separating wall and flanking ceiling) Side Junctions (between separating wall and flanking walls) W13, W14, W15 for additional material layer and finished flooring, see Table subfloor on both sides of wall is plywood, OSB, waferboard (15.5 mm thick) or tongue and groove lumber ( 17 mm thick) floor is framed with wood joists, wood I-joists or wood trusses spaced 400 mm o.c., with or without absorptive material (2) in cavities floor joists or trusses are oriented parallel to separating wall (non-loadbearing case) or perpendicular to separating wall but are not continuous across junction (loadbearing case) near leaf of separating wall is supported on designated joist wood joists, wood I-joists or wood trusses are oriented perpendicular or parallel to separating wall, with or without absorptive material (2) in cavities joist framing at junction is supported on near leaf of separating wall gypsum board ceiling panels end at wall framing and are fastened directly to bottom of ceiling framing or on resilient metal channels (3) Example Showing Side View of Bottom and Top Junctions flanking wall framing is fastened to adjacent leaf of separating wall flanking wall is framed with single row of wood studs, staggered studs on a single 38 mm x 140 mm plate, or 2 rows of 38 mm x 89 mm wood studs on separate 38 mm x 89 mm plates, with or without absorptive material (2) in cavities gypsum board panels on flanking walls ends or is cut at framing of separating wall and is fastened on resilient metal channels (3) or directly to framing of flanking wall if that framing and any sheathing are not continuous across the junction Example Showing Plan View of Side Junctions Copyright Queen s Printer for Ontario 2015 Page 11

12 Type of Separating Wall Assembly with STC 50 from Table 1 of MMAH SB-3 Fire and Sound Resistance of Building Assemblies Options for Design and Construction of Junctions and Flanking Surfaces (1) to Address Horizontal Sound Transmission Paths Bottom Junction (between separating wall and flanking floors) Top Junction (between separating wall and flanking ceiling) Side Junctions (between separating wall and flanking walls) S1 to S15 F1 concrete floor assembly from Table B with mass per area not less than 300 kg/m 2 (e.g. normal-weight concrete with average thickness of 130 mm) with or without an additional material layer or finished flooring F1 concrete floor assembly from Table B with mass per area not less than 300 kg/m 2 (e.g. normal-weight concrete with average thickness of 130 mm) with or without gypsum board ceiling suspended below concrete floor Example Showing Side View of Bottom and Top Junctions flanking wall framing is structurally connected to separating wall and terminates where it butts against framing of separating wall or is continuous across junction gypsum board on flanking walls ends or is cut at separating wall and is fastened directly to framing or on resilient metal channels (3) flanking wall consists of steel framing (loadbearing or non-loadbearing steel studs) or concrete blocks with mass per area not less than 200 kg/m 2 (e.g. normal-weight hollow core concrete block units (4) with a gypsum board lining supported on framing providing a cavity not less than 50 mm deep) with or without absorptive material (2) in cavities behind gypsum board of flanking walls Example Showing Plan View of Side Junctions B1 to B10 same options as stated above for walls S1 to S15 same options as stated above for walls S1 to S15 junction at top of concrete block assembly is loadbearing or non-loadbearing resilient joint same options as stated above for walls S1 to S15 Example Showing Side View of Bottom and Top Junctions Examples Showing Plan View of Side Junctions Copyright Queen s Printer for Ontario 2015 Page 12

13 Notes to Table A A: (1) See also Table A B. (2) Sound absorptive material is porous (closed-cell foam was not tested) and includes fibre processed from rock, slag, glass or cellulose fibre with a maximum density of 32 kg/m3. See Notes (3) and (6) of Table 1 and Note (4) of Table 2 of MMAH SB- 3 Fire and Sound Resistance of Building assemblies for additional information. (3) Resilient metal channels are formed from steel having a maximum thickness of 0.46 mm (25 gauge) with slits or holes in the single leg between the faces fastened to the framing and to the gypsum board (see Figure A D). ASTM C 754, Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products, describes the installation of resilient metal channels. (4) Normal-weight concrete block units conforming to CSA A165.1, Concrete Block Masonry Units, have aggregate with a density not less than kg/m3; 190 mm hollow core units are 53% solid, providing a wall mass per area over 200 kg/m2; 140 mm hollow core units are 75% solid, providing a wall mass per area over 200 kg/m2. Table A B presents options for improving the sound performance of separating wall systems beyond that achieved by implementing the options presented in Table A A. The suggested performance improvement options are listed in order of approximate acoustic priority and are interdependent, i.e., if options at the top of the list are not implemented, then options at the bottom of the list will have much lesser effect. Table A B Options for the Construction of a Separating Wall System to Further Improve the Sound Insulation Performance Achieved with the Options in Table A A Type of Separating Wall Assembly with STC 50 from Table 1 of MMAH SB-3 Fire and Sound Resistance of Building Assemblies W4, W5, W6, W8, W9, W10, W11, W12 W13, W14, W15 Performance Improvement Options for Junctions Between Separating Walls and Flanking Floor/Ceiling Assemblies Increase mass per area of additional material layer and finished flooring over subfloor (e.g. concrete or gypsum concrete topping) Choose separating wall assembly with higher STC rating Orient floor and ceiling joists parallel to separating wall (non-loadbearing case) Add resilient layer under additional material layer over subfloor or between additional material layer and finished flooring Support gypsum board panels of ceiling on resilient metal channels (1) Support gypsum board panels of flanking walls on resilient metal channels (1) If seismic or other structural requirements permit, choose a fire block detail at floor/wall junction in accordance with Subsection that does not provide a rigid connection between the two rows of framing of the separating wall (e.g. subfloor not continuous across junction and semi-rigid fibre insulation board filling the gap in accordance with Article ). In this case, an additional material layer would not be necessary. Also, choose separating wall assembly with higher STC rating (e.g. more absorptive material (2) in cavities and/or more gypsum board). If having a rigid structural connection at the floor/wall junction (such as subfloor continuous across the junction) is required for seismic or other structural reasons, obtain a higher ASTC rating as follows: Increase combined mass per area of additional material layer over subfloor and finished flooring (e.g. concrete or gypsum concrete topping) Choose separating wall assembly with higher STC rating (e.g. more absorptive material (2) and/or more gypsum board) Support gypsum board panels of ceiling on resilient metal channels (1) Support gypsum board panels of flanking walls on resilient metal channels (1) Add resilient layer under additional material layer over subfloor or between additional material layer and finished flooring Copyright Queen s Printer for Ontario 2015 Page 13

14 Type of Separating Wall Assembly with STC 50 from Table 1 of MMAH SB-3 Fire and Sound Resistance of Building Assemblies S1 to S15 B1 to B10 Performance Improvement Options for Junctions Between Separating Walls and Flanking Floor/Ceiling Assemblies Choose separating wall assembly with higher STC rating Increase thickness of concrete floor slab and/or add material layer and finished flooring over subfloor Add gypsum board ceiling on framing supported under the floor above, with cavity not less than 100 mm deep Add resilient layer under additional material layer over subfloor or between additional material layer and finished flooring Support gypsum board panels of flanking walls on resilient metal channels (1) if steel studs are loadbearing type Choose separating wall assembly with higher STC rating Add gypsum board ceiling supported below concrete floor with cavity not less than 100 mm deep and sound absorptive material (2) in cavity Increase thickness of concrete floor slab and/or add material layer and finished flooring over subfloor Add resilient layer under additional material layer over subfloor or between additional material layer and finished flooring and increase mass per area of additional material layer and finished flooring (e.g. floating concrete or gypsum concrete topping) Support gypsum board panels of flanking walls on resilient metal channels (1) if steel studs are loadbearing type Notes to Table A B: (1) Resilient metal channels are formed from steel having a maximum thickness of 0.46 mm (25 gauge) with slits or holes in the single leg between the faces fastened to the framing and to the gypsum board (see Figure A D). ASTM C 754, Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products, describes the installation of resilient metal channels. (2) Sound absorptive material is porous (closed-cell foam was not tested) and includes fibre processed from rock, slag, glass or cellulose fibre with a maximum density of 32 kg/m 3. See Notes (3) and (6) of Table 1 and Note (4) of Table 2 of MMAH SB-3 Fire and Sound Resistance for Existing Buildings for additional information. Table A C presents compliance options for the construction of separating floor/ceiling assemblies with flanking wall assemblies in vertically adjoining spaces. Copyright Queen s Printer for Ontario 2015 Page 14

15 Table A C Options for the Design and Construction of Junctions and Flanking Surfaces Between Separating Floor/Ceiling Assemblies in Vertically Adjoining Spaces for Compliance with Clause (1)(b) Type of Separating Floor/Ceiling Assembly with STC 50 from Table 2 of MMAH SB-3 Fire and Sound Resistance of Building Assemblies F1 (with or without gypsum board ceiling) Options for Design and Construction of Junctions and Flanking Surfaces (1) to Address Vertical Sound Transmission Paths Junctions with Flanking Steel-Framed Walls floor ends at flanking wall assembly (T-junction) or extends beyond it (cross-junction) steel framing of flanking walls is loadbearing or non-loadbearing, with a single row of steel studs, staggered studs, or 2 rows of studs, with studs spaced not less than 400 mm o.c., with or without absorptive material (2) in cavities flanking wall structure is fastened to separating concrete floor but is not continuous across junction gypsum board on flanking walls is not continuous across junction and is fastened directly to wall framing or on resilient metal channels (3) Junctions with Flanking Concrete Walls floor ends at flanking wall assembly (T-junction) or extends beyond it (cross-junction) one wythe of concrete blocks with mass per area not less than 200 kg/m 2 (e.g. normal-weight hollow core concrete block units (4) ) loadbearing (solid) or non-loadbearing (resilient) junction between top of flanking concrete block wall and floor structure gypsum board lining is supported on wood or steel framing providing a cavity not less than 50 mm deep, with or without absorptive material (2) in cavities gypsum board on flanking walls is not continuous across junction and is fastened directly to wall framing or on resilient metal channels (3) F8 to F38 Junctions with Flanking Loadbearing or Non-Loadbearing Walls wood studs of flanking wall are 38 mm x 89 mm or 38 mm x 140 mm and spaced 400 mm or 600 mm o.c. flanking wall framing consists of single row of wood studs, staggered studs on a single 38 mm x 140 mm plate, or 2 rows of 38 mm x 89 mm wood studs on separate 38 mm x 89 mm plates, with or without absorptive material (2) in wall cavities gypsum board on flanking walls ends or is cut near floor framing and is fastened directly to wall framing or supported on resilient metal channels (3) Example Showing Side View of Junctions in Flanking Loadbearing Wall Example Showing Side View of Junctions in Flanking Non-Loadbearing Wall Notes to Table A C: (1) See also Table A D. (2) Sound absorptive material is porous (closed-cell foam was not tested) and includes fibre processed from rock, slag, glass or cellulose fibre with a maximum density of 32 kg/m 3. See Notes (3) and (6) of Table 1 and Note (4) of Table 2 of MMAH SB-3 Fire and Sound Resistance of Building assemblies for additional information. Copyright Queen s Printer for Ontario 2015 Page 15

16 (3) Resilient metal channels are formed from steel having a maximum thickness of 0.46 mm (25 gauge) with slits or holes in the single leg between the faces fastened to the framing and to the gypsum board (see Figure A D). ASTM C 754, Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products, describes the installation of resilient metal channels. (4) Normal-weight concrete block units conforming to CSA A165.1, Concrete Block Masonry Units, have aggregate with a density not less than kg/m 3 ; 190 mm hollow core units are 53% solid, providing a wall mass per area over 200 kg/m 2 ; 140 mm hollow core units are 75% solid, providing a wall mass per area over 200 kg/m 2. Table A D presents options for improving the sound performance of separating floor/ceiling assemblies beyond that achieved by implementing the options presented in Table A C. The suggested performance improvement options are listed in order of approximate acoustic priority and are interdependent, i.e., if options at the top of the list are not implemented, then options at the bottom of the list will have much lesser effect. Table A D Options for the Construction of a Separating Floor System to Further Improve the Sound Insulation Performance Achieved with the Options in Table A C. Type of Separating Floor Assembly with STC 50 from Table 2 of MMAH SB-3 Fire and Sound Resistance of Building Assemblies F1 (with or without gypsum board ceiling) F8 to F38 Performance Improvement Options for Junctions Between Separating Floors and Flanking Wall Assemblies Add heavier additional material layer over subfloor and/or resilient layer under additional material layer or between additional material layer and finished flooring Add gypsum board ceiling supported at least 100 mm below concrete floor with minimal structural connection (e.g. ceiling framing supported resiliently) and sound absorptive material (1) in cavity Support gypsum board of flanking walls of lower room on resilient metal channels (2) (if framed with loadbearing studs) Add heavier additional material layer over subfloor and/or resilient layer under additional material layer or between additional material layer and finished flooring Add more/heavier gypsum board to ceiling and increase spacing of resilient metal channels (2) to 600 mm o.c. Support gypsum board of flanking loadbearing walls of lower room on resilient metal channels (2) Support gypsum board on flanking non-loadbearing walls of lower room on resilient metal channels (2) Notes to Table A D: (1) Sound absorptive material is porous (closed-cell foam was not tested) and includes fibre processed from rock, slag, glass or cellulose fibre with a maximum density of 32 kg/m 3. See Notes (53) and (86) of Table A1 and Note (54) of Table B2 of MMAH SB-3 Fire and Sound Resistance of Building Assemblies for additional information. (2) Resilient metal channels are formed from steel having a maximum thickness of 0.46 mm (25 gauge) with slits or holes in the single leg between the faces fastened to the framing and to the gypsum board (see Figure A D). ASTM C 754, Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products, describes the installation of resilient metal channels. Copyright Queen s Printer for Ontario 2015 Page 16

17 A-Table Floor Treatments. The sound insulation performance of lightweight framed floors can be improved by adding floor treatments, i.e., additional layers of material over the subfloor (e.g. concrete topping, OSB or plywood) and finished flooring or coverings (e.g., carpet, engineered wood). Table A-Table presents the mass per area values based on thickness and density of a number of generic floor treatment materials (the values for proprietary products may be different; consult the manufacturer s current data sheets for their products values). Table A-Table Mass per Area of Floor Treatment Materials Floor Treatment Material Thickness, mm Density, kg/m³ Mass per Area, kg/m 2 Materials Typically Having a Mass per Area Less Than 8 kg/m² Medium-density fibreboard (MDF) Plywood generic softwood Ceramic tile Materials Typically Having a Mass per Area Greater Than 8 kg/m² but Less Than 16 kg/m² Particleboard Medium-density fibreboard (MDF) Oriented strandboard (OSB) Plywood generic softwood Materials Typically Having a Mass per Area Greater Than 16 kg/m² but Less Than 32 kg/m² Medium-density fibreboard (MDF) Materials Typically Having a Mass per Area Greater Than 32 kg/m² Concrete Gypsum concrete RATIONALE FOR CHANGE Problem/General Background The requirements in the Building Code with regard to sound transmission are based on the best available information at the time they were introduced. The requirements focus on the laboratory rating of the separating assembly, rather than performance of the system. Advances in the field of acoustical research now make it clear that this falls well short of achieving a level of performance consistent with the objectives of the Code. The current provisions encourage an over-simplified design approach that results in frequent investment in the wrong elements and most importantly fail to provide a functional requirement that establishes a minimum acceptable performance necessary to satisfy the Objective OH3 Noise Protection. Copyright Queen s Printer for Ontario 2015 Page 17

18 Justification/Explanation This proposed change would harmonize requirements with the model National Building Code of Canada. Switching from the current STC rating to the Apparent Sound Transmission Class (ASTC) rating would address the minimum performance of the complete system without over-design and with minimal implication to the scope of the OBC and enforcement. Specifically: This Article was brought to the beginning of the Section because it contains the actual required ratings and deemed-to-comply constructions and clarifies the application for each required rating. An ASTC rating has been added as an option to the requirements for secondary suites in Sentence (2) because this will allow the use of the simplified and detailed calculation methods in Part 5. A rating of STC 43 and ASTC 40 can be considered as roughly equivalent because it is unlikely that the current performance (STC 43) would be further compromised through flanking contributions through commonly constructed walls- floorand ceiling assemblies. The STC rating required between elevator shafts and dwelling units in Sentence (3) will remain unchanged because there are currently no metrics that address noise generated by elevators. Increasing the criteria for a required (airborne) STC rating as is currently done in the Building Code was considered better than no requirement at all. Addressing the protection of occupants from elevator noise through ASTC would therefore also not be an improvement over requiring an STC rating This Article describes acceptable measurement and calculation methods for the ratings used in this Section. The field measurement standard has been deleted as an option to determine the STC because it is virtually impossible to isolate the direct sound transmission of the separating assembly from the overall sound experienced in the receiving room. Sentence (2) introduces two acceptable ways to determine an ASTC rating either by an in-situ test or by calculating This new Article specifies all available and acceptable compliance methods including deemed-tocomply methods involving the looking up of ratings for assemblies constructed according to generic specifications. While the lookup method for an STC (Sentence 1) results in an actual single number rating, the lookup method for an ASTC (Sentence 2) results in specifications for acceptable construction of direct and flanking assemblies without a single number rating This Article allows the use of the STC metric to comply with the requirements for dwelling units. The requirements address three deemed- to-comply scenarios: Flanking walls attached to a separating floor or ceiling Flanking walls or ceilings attached to a separating wall, and Flanking floor assemblies attached to a separating wall The article also addresses the fact that flanking contributions through concrete assemblies are negligible in most cases. Problems could arise where concrete block is too light or in some cases for concrete basement slabs. Copyright Queen s Printer for Ontario 2015 Page 18

Guide for Sound Insulation in Wood Frame Construction

Guide for Sound Insulation in Wood Frame Construction National Research Council Canada Conseil national de recherches Canada Guide for Sound Insulation in Wood Frame Construction Research Report 219, March 2006 J.D. Quirt, T.R.T. Nightingale, F. King Preamble

More information

ARCHITECTURAL AND STRUCTURAL NOISE CONTROL SOLUTIONS

ARCHITECTURAL AND STRUCTURAL NOISE CONTROL SOLUTIONS 13080/KIN BuyLine 1062 Providing solutions to common noise and vibration problems since 1958. ARCHITECTURAL AND STRUCTURAL NOISE CONTROL SOLUTIONS IIC 51 STC 72 FLOOR/CEILING STC 84 IIC 70 FLOOR/CEILING

More information

RESILIENT SOUND ISOLATION CLIPS

RESILIENT SOUND ISOLATION CLIPS RESILIENT SOUND ISOLATION CLIPS For Wall & Floor Ceiling Assemblies RSIC-1 Resilient Sound Isolation Clip Isolation Clip RSIC-1 Isolation Clip Soundproofing Products SonexTM Ceiling & Wall Panels Sound

More information

Part E robustdetails. robustdetails. January 2017 Update Pack. Dear Colleague,

Part E robustdetails. robustdetails. January 2017 Update Pack. Dear Colleague, Part E Pack Dear Colleague, This is the first 2017 update to the Part E Robust Details Handbook. In this update pack, we have focussed on clarifying the situation on incorporating underfloor heating (UFH)

More information

June Residential Refurbishment Separating walls

June Residential Refurbishment Separating walls June 2010 Residential Refurbishment 3.6.1 Separating walls Residential refurbishment 3.0 Residential Refurbishment Separating Walls Contents Introduction find online page Solution optimiser and pathfinder

More information

Appendix D. -Weyerhaeuser Fire Rated Assembly Listings-

Appendix D. -Weyerhaeuser Fire Rated Assembly Listings- Appendix D -Weyerhaeuser Fire Rated Assembly Listings- Table of Contents Assembly Description Reference Standard/Criteria FJ-1 TJI Joist 1 hour fire resistance rated floor and roof assembly. ASTM-E119

More information

This page was. intentionally. left blank

This page was. intentionally. left blank CONSTRUCTION Measurement of Airborne Sound Insulation of 8 Wall Assemblies Measurement of Airborne and Impact Sound Insulation of 29 Floor Assemblies Nordic Engineered Wood Report No. A1-006070.10 July

More information

SECTION GYPSUM BOARD

SECTION GYPSUM BOARD SECTION 09250 GYPSUM BOARD PART 1GENERAL 1.1 SUMMARY A. Related Documents: General and Supplementary Conditions of the Contract, Division 1 - General Requirements, and Drawings are collectively applicable

More information

Presented By: Jim O Neill. Acoustics

Presented By: Jim O Neill. Acoustics Presented By: Jim O Neill Acoustics Topics STC and IIC 101 Sound in floors Sound in walls Noise In Multifamily Measurements of Noise Two ASTM Standards STC Sound Transmission Classification Measurement

More information

Wall and Floor/Ceiling Assemblies

Wall and Floor/Ceiling Assemblies Introduction Catalog of STC and IIC Ratings for Wall and Floor/Ceiling Assemblies Russell B. DuPree Office of Noise Control, California Department of Health Services Berkeley, California 94704 building

More information

RSIC-1. RSIC-1, the Low Cost, High Performance, Noise control Solution. RSIC-1 specifications:

RSIC-1. RSIC-1, the Low Cost, High Performance, Noise control Solution. RSIC-1 specifications: RSIC-1 The RSIC-1 is designed for use with any wood framed, steel framed, CMU, or concrete wall and ceiling system where noise control is needed. The RSIC-1 assembly decouples and isolates the gypsum board

More information

SOUND INSULATION TESTING IN DWELLINGS

SOUND INSULATION TESTING IN DWELLINGS SOUND INSULATION TESTING IN DWELLINGS Chris Dilworth, AWN Consulting This Presentation Discusses the standards by which we judge sound insulation performance. Presents the results of sound insulation tests

More information

DIVISION: FINISHES SECTION: ACOUSTIC TREATMENT REPORT HOLDER: HOMASOTE COMPANY

DIVISION: FINISHES SECTION: ACOUSTIC TREATMENT REPORT HOLDER: HOMASOTE COMPANY 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1374 Reissued 06/2017 This report is subject to renewal 06/2018. DIVISION: 09 00

More information

The GlasRoc Shaftliner Type X advantage...

The GlasRoc Shaftliner Type X advantage... C e r t a i n T e e d SHAFTLINER F o r A r e a S e p a r a t i o n F i r e w a l l s Shaftliner S Type X for Area Separation GlasRoc Shaftliner is a specially formulated product for applications where

More information

DIVISION: FINISHES SECTION: ACOUSTIC TREATMENT REPORT HOLDER: ECORE INTERNATIONAL, INC.

DIVISION: FINISHES SECTION: ACOUSTIC TREATMENT REPORT HOLDER: ECORE INTERNATIONAL, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1522 Reissued 09/2016 This report is subject to renewal 09/2018. DIVISION: 09 00

More information

Sound Control Manual Sound Construction Details, Specifications, and Construction

Sound Control Manual Sound Construction Details, Specifications, and Construction Sound Control Manual Sound Construction Details, Specifications, and Construction Second in importance only to selecting the right system, are measures to ensure that the installation is performed in such

More information

SECTION GYPSUM BOARD ASSEMBLIES

SECTION GYPSUM BOARD ASSEMBLIES SECTION 09 21 16 GYPSUM BOARD ASSEMBLIES PART 1 GENERAL 1.1 SECTION INCLUDES A. Metal stud wall and ceiling framing, 20 gauge. B. Metal channel suspended ceiling framing. C. Gypsum board. D. Gypsum sheathing.

More information

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board. 1.2 RELATED WORK A. Installation of steel framing members for walls, partitions,

More information

GIB Quiet Clip GIB CBI March Features and Benefits

GIB Quiet Clip GIB CBI March Features and Benefits CBI - 5113 March 2002 GIB Quiet Clip Features and Benefits No special flooring systems required Easy fit Installation Significantly improves low frequency sound transmission Significantly improves low

More information

Cold-Formed Steel Framing: Engineering the Details of Your Next Project BUILDSTEEL.ORG

Cold-Formed Steel Framing: Engineering the Details of Your Next Project BUILDSTEEL.ORG Cold-Formed Steel Framing: Engineering the Details of Your Next Project Cold-Formed Steel Framing Resource Center for Building Professionals Table of Contents INTRODUCTION 1 How to Engineer Cold-Formed

More information

ILLUSTRATED GUIDE. For Seismic Design of Houses. Lateral Bracing Requirements Part 9 BC Building Code 2012

ILLUSTRATED GUIDE. For Seismic Design of Houses. Lateral Bracing Requirements Part 9 BC Building Code 2012 ILLUSTRATED GUIDE For Seismic Design of Houses Lateral Bracing Requirements Part 9 BC Building Code 2012 This guide has been developed to assist house designers and builders in understanding and complying

More information

COOK COUNTY ILLINOIS CONTRACT FOR WORK DOCUMENT NO Countywide Warehouse and Records Storage Center Hawthorne Project TKB No.

COOK COUNTY ILLINOIS CONTRACT FOR WORK DOCUMENT NO Countywide Warehouse and Records Storage Center Hawthorne Project TKB No. SECTION 092900 GYPSUM BOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

PinkWood Ltd. Revised September 29, 2017

PinkWood Ltd. Revised September 29, 2017 Fire-Rated Assemblies PR-S315 PinkWood Ltd. Revised September 29, 2017 Products: Series I-Joists PinkWood Ltd., 5929 6 th St. NE, Calgary, Alberta, Canada T2K 5R5 (403) 279-3700 www.pinkwood.ca 1. Basis

More information

Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B POTENTIAL CHANGE TO ONTARIO S BUILDING CODE:

Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B POTENTIAL CHANGE TO ONTARIO S BUILDING CODE: Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B-12-02-05 POTENTIAL CHANGE TO ONTARIO S BUILDING CODE: SUMMER AND FALL 2017 CONSULTATION Ministry of Municipal Affairs PROPOSED

More information

WHY I SHOULD SPECIFY AND USE FAS TRACK 1000?

WHY I SHOULD SPECIFY AND USE FAS TRACK 1000? TRACK 1000 FIRE MANAGEMENT PRODUCTS TECHNICAL PRODUCT GUIDE www.cemcosteel.com WHY I SHOULD SPECIFY AND USE FAS TRACK 1000? SOUND BENEFITS: Whether the protection you need is Fire, Air (Smoke), or Sound

More information

GenieMat FF. Floating Floor Systems for Airborne & Impact Sound and Vibration Isolation. It s not magic, it s engineering. Impact Sound Control

GenieMat FF. Floating Floor Systems for Airborne & Impact Sound and Vibration Isolation. It s not magic, it s engineering. Impact Sound Control It s not magic, it s engineering. Impact Sound Control GenieMat FF Floating Floor Systems for Airborne & Impact Sound and Vibration Isolation Patents: US 8240430, US8556029, CA 2500956, CA 2503420 GenieMat

More information

WoodWorks. Learning Objective. Presentation Overview. Fire Protection II Requirements for rated assemblies and common detailing

WoodWorks. Learning Objective. Presentation Overview. Fire Protection II Requirements for rated assemblies and common detailing WoodWorks Fire Protection II Requirements for rated assemblies and common detailing Scott Lockyear, PE Learning Objective Discuss the type of rated assembly requirements in the International Building Code.

More information

2018 British Columbia Building Code Public Review of Proposed Changes

2018 British Columbia Building Code Public Review of Proposed Changes 2018 British Columbia Building Code Public Review of Proposed Changes PROPOSED CHANGE: Asbestos CHANGE NUMBER: 2018-BCBC-03-Asbestos CODE REFERENCE: 2015 National Building Code Division B Various Articles

More information

138 H-STUD AREA SEPARATION WALL SYSTEM

138 H-STUD AREA SEPARATION WALL SYSTEM H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic fashion by the results of this actual townhouse fire in which the two-hour fire-rated

More information

Design. Boral CinemaZone Fact Sheet. Windows. Acoustic sealants. Sound absorptive panels. Ventilation. Floor coverings. The vision.

Design. Boral CinemaZone Fact Sheet. Windows. Acoustic sealants. Sound absorptive panels. Ventilation. Floor coverings. The vision. Windows Like doorways, windows can be a significant source of sound leakage. For maximum isolation, windows should either be removed or built over internally - leaving the house facade unaffected. If natural

More information

CONTRACT NUMBER: W912DQ-08-C % CORRECTED DESIGN 28 JULY 2008

CONTRACT NUMBER: W912DQ-08-C % CORRECTED DESIGN 28 JULY 2008 SECTION 092900 - GYPSUM BOARD 1.1 SUMMARY A. This Section includes the following: 1. Interior gypsum board. 2. Tile backing panels. B. Related Sections include the following: 1. Division 06 Section "Rough

More information

Acoustic Design Criteria

Acoustic Design Criteria Apartment Acoustics Apartment Buildings Acoustic Design Criteria Building Code of Australia: - Intertenancy walls and floors - Corridor walls and doors - Floor impact isolation - Lift, stair and core walls

More information

NATIONAL GYPSUM COMPANY Wood Frame Walls And Ceilings Single- And Double-Layer Construction

NATIONAL GYPSUM COMPANY Wood Frame Walls And Ceilings Single- And Double-Layer Construction Walls And Ceilings Single- And Double-Layer Construction 09 9 00/NGC Single-Layer Construction The single-layer construction system consists of a single layer of Gold Bond brand Gypsum Board applied to

More information

Chevy Chase Club June 30, 2008 Bowie Gridley Architects SECTION GYPSUM BOARD SHAFT WALL ASSEMBLIES

Chevy Chase Club June 30, 2008 Bowie Gridley Architects SECTION GYPSUM BOARD SHAFT WALL ASSEMBLIES SECTION 092116.23 - GYPSUM BOARD SHAFT WALL ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Administrative Changes

Administrative Changes Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings

More information

Basement Renovation Guide For Residential Dwellings

Basement Renovation Guide For Residential Dwellings 1 Development Services Department Building Permit & Inspection Services Basement Renovation Guide For Residential Dwellings This document is a guide for home owners and does not cover all possible conditions.

More information

URSA MINERAL WOOL URSA Acoustic Roll

URSA MINERAL WOOL URSA Acoustic Roll - 073_Layout 1 02/10/2017 10:19 Page 1 URSA UK LTD Crest House 102-104 Church Road Teddington, Middlesex TW11 8PY United Kingdom Tel : 020 8977 96 97 Fax : 020 8977 94 56 Web : www.ursa-uk.co.uk E-mail

More information

AND ACCESSORIES FOR DRYWALL CONSTRUCTION

AND ACCESSORIES FOR DRYWALL CONSTRUCTION STEEL TRIMS AND ACCESSORIES FOR DRYWALL CONSTRUCTION Quality in your corner. THE STRENGTH WITHIN MONTREAL TORONTO CALGARY EDMONTON VANCOUVER STEEL TRIMS AND ACCESSORIES for Construction BAILEY HAS YOUR

More information

Table R (1) Allowable Spans and Loads for Wood Structural Panels for Roof and Subfloor. Sheathing and Combination Subfloor Underlayment

Table R (1) Allowable Spans and Loads for Wood Structural Panels for Roof and Subfloor. Sheathing and Combination Subfloor Underlayment City of Republic - Community Development Department Roof and Subfloor Sheathing Spans Revision Date: January 2017 Table R503.2.1.1(1) Allowable Spans and Loads for Wood Structural Panels for Roof and Subfloor

More information

Installation Guide and Safety Manual

Installation Guide and Safety Manual Installation Guide and Safety Manual Resilmount A237R (Resilient Sound Isolation Clips) REQUIRED FURRING CHANNEL REQUIRED FURRING CHANNEL* 1 4" 2 2" Minimum f" Gauge:...25 Gauge With Hemmed Edge (Do Not

More information

SECTION D Masonry Wall Systems. Contents. Introduction. Design Considerations. Installation. Components. System Specifications.

SECTION D Masonry Wall Systems. Contents. Introduction. Design Considerations. Installation. Components. System Specifications. SECTION D Wall Systems. Contents. SUBJECT Introduction Design Considerations Installation Components PAGE D2 D2 D4 D5 System Specifications Stud One Side Stud Both Sides Stud and Furring Channel Resilient

More information

RSIC-1 ACOUSTIC ASSEMBLY

RSIC-1 ACOUSTIC ASSEMBLY RSIC-1 ACOUSTIC ASSEMBLY FLOOR/CEILING ASSEMBLY DIRECT FIX TO CONCRETE SLAB FCS3 DSWA FIIC 69 PAC INTERNATIONAL Inc. Toll Free 866-774-2100 Telephone 503-649-7700 CONSTRUCTION * Ceramic Tile * 1/4" James

More information

1. Interior gypsum wallboard. 2. Exterior gypsum board panels for ceilings and soffits. 3. Tile backing panels.

1. Interior gypsum wallboard. 2. Exterior gypsum board panels for ceilings and soffits. 3. Tile backing panels. SECTION 09260 - GYPSUM BOARD ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

REPORT HOLDER: KINETICS NOISE CONTROL 6300 IRELAN PLACE DUBLIN, OHIO EVALUATION SUBJECT: KINETICS NOISE CONTROL WAVE HANGER

REPORT HOLDER: KINETICS NOISE CONTROL 6300 IRELAN PLACE DUBLIN, OHIO EVALUATION SUBJECT: KINETICS NOISE CONTROL WAVE HANGER 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3207 Reissued 10/2016 This report is subject to renewal 10/2018. DIVISION: 09 00 00 FINISHES

More information

Floor Insulation Underlayment Section Sound Control Matting

Floor Insulation Underlayment Section Sound Control Matting Floor Insulation Underlayment Section 09618 Sound Control Matting Part I General 1.1 Summary A. Section includes a sound control material for achieving an STC and IIC rating in excess of 50 to meet building

More information

STEEL STUD, TRIMS AND ACCESSORIES FOR DRYWALL CONSTRUCTION MONTREAL TORONTO CALGARY EDMONTON VANCOUVER THE STRENGTH WITHIN

STEEL STUD, TRIMS AND ACCESSORIES FOR DRYWALL CONSTRUCTION MONTREAL TORONTO CALGARY EDMONTON VANCOUVER THE STRENGTH WITHIN STEEL STUD, TRIMS AND ACCESSORIES FOR DRYWALL CONSTRUCTION MONTREAL TORONTO CALGARY EDMONTON VANCOUVER THE STRENGTH WITHIN STEEL STUD AND TRACK FOR DRYWALL PARTITIONS TAKE ADVANTAGE OF THE SAVINGS IN TIME

More information

Specialists in Acoustic Flooring and House to Flat Conversions

Specialists in Acoustic Flooring and House to Flat Conversions Sound Solution Consultants Ltd Po Box 755 Capel St Mary Ipswich Suffolk IP9 2WF Tel No: 0845 5212096 Fax No: 0845 5212097 Email: mpconsultservice@aol.com Specialists in Acoustic Flooring and House to Flat

More information

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows: SECTION 16130 (Master Template Final-05) ELECTRICAL BOXES PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide boxes for electrical equipment and wiring devices as follows: 1. Wall and ceiling outlet boxes.

More information

WOOD USE IN NONCOMBUSTIBLE BUILDINGS

WOOD USE IN NONCOMBUSTIBLE BUILDINGS INTRODUCTION The National Building Code of Canada (NBCC) 1 requires that some buildings be of noncombustible construction under its prescriptive requirements. Its use in certain types of buildings such

More information

ESR-1826 Reissued February 1, 2013 This report is subject to renewal February 1, 2015.

ESR-1826 Reissued February 1, 2013 This report is subject to renewal February 1, 2015. * ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-1826 Reissued February 1, 2013 This report is subject to renewal February 1, 2015. A Subsidiary of the International Code Council

More information

HACKER SOUND MAT II, to create a quieter living environment while meeting demanding project specifications in multi-family construction.

HACKER SOUND MAT II, to create a quieter living environment while meeting demanding project specifications in multi-family construction. HACKER SOUND MAT II HACKER SOUND MAT II, to create a quieter living environment while meeting demanding project specifications in multi-family construction. HACKER SOUND MAT II, a recycled rubber sound

More information

SINTEF Building and Infrastructure confirms that. Separating floors with Hunton Silencio 36 / Hunton Silencio Thermo

SINTEF Building and Infrastructure confirms that. Separating floors with Hunton Silencio 36 / Hunton Silencio Thermo SINTEF Certification No. 2330 Issued t: 18.02.2002 Revised: 17.06.2013 Valid until: 01.07.2018 Page: 1 of 5 SINTEF Building and Infrastructure confirms that Separating floors with Hunton Silencio 36 /

More information

Shaftwall and Area Separation Wall Systems.

Shaftwall and Area Separation Wall Systems. Shaftwall and Area Separation Wall Systems www.marinoware.com Marino\WARE S Fire Rated Wall Systems Quality that takes you to the top. Marino\WARE created its CT Shaftwall System, to be a flexible shaftwall

More information

Acoustic Testing of CLT and Glulam Floor Assemblies Nordic Engineered Wood Report No. A August 2016 CONSTRUCTION

Acoustic Testing of CLT and Glulam Floor Assemblies Nordic Engineered Wood Report No. A August 2016 CONSTRUCTION CONSTRUCTION Acoustic Testing of CLT and Glulam Floor Assemblies Nordic Engineered Wood Report No. A1-008253.1 19 August 2016 The results in this report only apply to the specimen that was tested Page

More information

FIRE PROTECTION. GTEC Shaftwall systems 244 GTEC Shaftwall Stairwell systems 248 GTEC Horizontal Shaftwall systems 249 GTEC Encasement systems 250

FIRE PROTECTION. GTEC Shaftwall systems 244 GTEC Shaftwall Stairwell systems 248 GTEC Horizontal Shaftwall systems 249 GTEC Encasement systems 250 FIRE PROTECTION GTEC Shaftwall range uses a specially designed system to protect voids and shafts in buildings. It resists pressure changes and enables installation from one side of the shaft only. GTEC

More information

I-STUD Shaftwall System

I-STUD Shaftwall System I-STUD Shaftwall System Summit Tower I-Stud and CertainTeed Shaftliner TM MILL CERTIFIED Steel-Con 00% GALVANIZED Steel Construction Systems UL Evaluation Report No. ER3660-02 Intertek The I-Stud is approved

More information

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure

More information

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA

Important Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure

More information

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016.

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016. ICC-ES Evaluation Report ESR-894 Reissued April 04 This report is subject to renewal April, 0. www.icc-es.org (800) 4-87 () 99-04 A Subsidiary of the International Code Council DIVISION: 07 00 00 THERMAL

More information

AIR BARRIER DESIGN PRINCIPLES AN OVERVIEW.

AIR BARRIER DESIGN PRINCIPLES AN OVERVIEW. AIR BARRIER DESIGN PRINCIPLES AN OVERVIEW www.stromatech.com AIR BARRIER DESIGN PRINCIPLES Building Regulations Approved Document Parts L1A & L2A currently requires that new buildings have to achieve a

More information

Structural Technical Report #2 By Robert Whitaker

Structural Technical Report #2 By Robert Whitaker Structural Technical Report #2 By Robert Whitaker Robert Whitaker Structural ~ Parfitt Parkview at Bloomfield Station Bloomfield, NJ 10-31-05 Executive Summary This report covers the comparative redesign

More information

ONE SCHOOL STREET SEPTEMBER 18, 2008 GOWANDA, NEW YORK ARCH PROJECT NO

ONE SCHOOL STREET SEPTEMBER 18, 2008 GOWANDA, NEW YORK ARCH PROJECT NO SECTION 09265 - GYPSUM BOARD SHAFT-WALL ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

KINETICS NOISE CONTROL TEST REPORT #AT001035

KINETICS NOISE CONTROL TEST REPORT #AT001035 KINETICS NOISE CONTROL TEST REPORT #AT001035 KINETICS NOISE CONTROL PRODUCTS: o RIM I-2-16 ACOUSTICAL RATINGS: o STC 66 o IIC 63 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3140.1 KINETICS DRAWING

More information

ENKASONIC FLOOR UNDERLAYMENT 9110

ENKASONIC FLOOR UNDERLAYMENT 9110 ENKASONIC FLOOR UNDERLAYMENT 9110 GS1197 Section 13080 SECTION 09618 SOUND CONTROL MATTING Part I General 1.1 Summary A. Section includes a sound control material for achieving an STC and IIC rating in

More information

Acoustics 08 Paris 3059

Acoustics 08 Paris 3059 Innovative building systems to improve the acoustical quality in lightweight masonry constructions: Application of resilient joints at junctions - PART 2: Study cases modelled according to the standard

More information

Container Installation Guide

Container Installation Guide Container Insulation Container Installation Guide Panels and Inserts The InSoFast CX Container panel and the Inserts are designed to fit most shipping containers. Containers have three types of corrugations:

More information

INSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT

INSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT INSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT MAY 2009 prepared by N. A. JACOBSEN, P.Eng. CIVIL ENGINEERING CONSULTANT Whitehorse, Yukon ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT MAY

More information

The Perfect Choice for Mezzanines in Custom Metal Buildings

The Perfect Choice for Mezzanines in Custom Metal Buildings The Perfect Choice for Mezzanines in Custom Metal Buildings Ecospan composite floor system. The Ecospan Composite Floor System is an innovative, simple, effective and economical method of providing all

More information

Modular Wood Framing Goes Vertical

Modular Wood Framing Goes Vertical Modular Wood Framing Goes Vertical By: Troy Bean, P.E., S.E. DCI Engineers January 2013 The Wood Products Council is a Registered Provider with. Credit(s) earned on completion of this program will be reported

More information

SECTION GYPSUM BOARD

SECTION GYPSUM BOARD Manufacturer: American Gypsum 3811 Turtle Creek Blvd., Suite 1200 Dallas, Texas 75219 (800) 545-6302 (214) 530-5634 fax www.americangypsum.com GUIDE SPECIFICATION SECTION 09 29 00 This guide specification

More information

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS

DIVISION 10 SPECIALTIES SECTION OPERABLE PARTITIONS DIVISION 10 SPECIALTIES SECTION 10 22 26 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

ShaftWall. Shaft and duct encasement system. ShaftWall.

ShaftWall. Shaft and duct encasement system. ShaftWall. ShaftWall ShaftWall Shaft and duct encasement system ShaftWall provides a lightweight, non-loadbearing fire-resistant structure to protect elements within the service cores of modern fast-track developments.

More information

Xtratherm Thin-R Thermal Liner (XT/TL Grade)

Xtratherm Thin-R Thermal Liner (XT/TL Grade) CERTIFICATE NO. 03/0183 DETAIL SHEET 4 Xtratherm Thin-R Thermal Liner (XT/TL Grade) PRODUCT DESCRIPTION: This Detail Sheet relates to Xtratherm Thin-R Thermal Liner, as defined in NSAI Agrément Certificate

More information

SOUND SOLUTIONS TO MEET THE APPROVED DOCUMENT E (2003 EDITION) August 2008

SOUND SOLUTIONS TO MEET THE APPROVED DOCUMENT E (2003 EDITION) August 2008 SOUND SOLUTIONS TO MEET THE APPROVED DOCUMENT E (2003 EDITION) August 2008 PART E AT A GLANCE The New Approved Document E, (2003 Edition) was implemented on 1st July 2003. This applies to houses, flats,

More information

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued January 1, Legacy report on the 1997 Uniform Building Code

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued January 1, Legacy report on the 1997 Uniform Building Code LEGACY REPORT Reissued January 1, 2000 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office # 900 Montclair

More information

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California *Revised April 2003

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California *Revised April 2003 PFC-5804* Reissued February 1, 2003 ICBO Evaluation Service, Inc. 5360 Workman Mill Road, Whittier, California 90601 www.icboes.org Filing Category: DESIGN Wood PACIFIC WOODTECH CORPORATION PWI JOISTS

More information

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIRESTOPPING REPORT HOLDER: PASSIVE FIRE PROTECTION PARTNERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIRESTOPPING REPORT HOLDER: PASSIVE FIRE PROTECTION PARTNERS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2996 Reissued 12/2017 This report is subject to renewal 12/2019. DIVISION: 07 00

More information

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued October 1, Legacy report on the 1997 Uniform Building Code

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued October 1, Legacy report on the 1997 Uniform Building Code LEGACY REPORT Reissued October 1, 2007 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office # 900 Montclair

More information

SECTION GYPSUM WALLBOARD. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION GYPSUM WALLBOARD. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 092116 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866) TECHNICAL NOTE On Cold-Formed Steel Construction $5.00 Light Gauge Steel Engineers Association Washington, D.C. 20005 Toll Free (866) 465-4732 www.lgsea.com DESIGN OF BY-PASS SLIP CONNECTORS IN COLD-FORMED

More information

JUST THE FACTS! EcoTouch PINK FIBERGLAS Insulation The best choice for home energy savings

JUST THE FACTS! EcoTouch PINK FIBERGLAS Insulation The best choice for home energy savings JUST THE FACTS! EcoTouch PINK FIBERGLAS Insulation The best choice for home energy savings ATTIC BASEMENT WALLS CEILINGS FLOORS NOISE CONTROL Residential and Commercial Products & Solutions Recycled Content,

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I-JOISTS REPORT HOLDER: PACIFIC WOODTECH CORPORATION

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I-JOISTS REPORT HOLDER: PACIFIC WOODTECH CORPORATION 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1225 Reissued 10/2017 This report is subject to renewal 10/2019. DIVISION: 06 00

More information

Shaftwall & Stairwell Systems Fire protection & sound isolation for shafts & stairwells

Shaftwall & Stairwell Systems Fire protection & sound isolation for shafts & stairwells Shaftwall & Stairwell Systems Fire protection & sound isolation f shafts & stairwells what the job demands Shaftwall & Stairwell Systems Fire protection & sound isolation systems f elevat shafts, stairwells

More information

Edition October May (always refer to the latest manual as set out on

Edition October May (always refer to the latest manual as set out on LOXO PANEL INTER AND BLOCK TENANCY SYSTEMS WALLS TECHNICAL FIRE AND ACOUSTIC MANUAL REPORT PRODUCT DESCRIPTION AND BUILDING SYSTEM DETAILS Edition October May 2015 2014 (always refer to the latest manual

More information

Questions and Answers about Madison Crescent and Noise Issues

Questions and Answers about Madison Crescent and Noise Issues Questions and Answers about Madison Crescent and Noise Issues Question: What codes were applicable to our condos when they were built? Answer: The Virginia Uniform Statewide Building Code (VUSBC) - The

More information

Staggered stud acoustic partition system

Staggered stud acoustic partition system C0 Partitions Staggered stud acoustic partition system All our systems are covered by SpecSure when using genuine Gyproc and Isover products is a non-loadbearing stud partition incorporating a single framework

More information

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person

More information

Product Selection Guide and Architectural Assemblies

Product Selection Guide and Architectural Assemblies Product Selection Guide and Architectural Assemblies Mold and Moisture Resistant PAPERLESS SOLUTIONS Product Selection Guide The G-P Gypsum Product Line G-P Gypsum constantly monitors and controls the

More information

Gold Bond BRAND Gypsum Sheathing

Gold Bond BRAND Gypsum Sheathing BRAND 09 06 29 16 00/NGC 43/NGC brand is a moisture-resistant sheathing installed on the outside of exterior framing as a substrate for exterior claddings. It is manufactured with a treated water-resistant

More information

Section II Subfloor Guidelines & Specifications Page Chapter 4 Wood Subfloor Guidelines 23 Chapter 5 Concrete Subfloor Guidelines 26 Chapter 6

Section II Subfloor Guidelines & Specifications Page Chapter 4 Wood Subfloor Guidelines 23 Chapter 5 Concrete Subfloor Guidelines 26 Chapter 6 Section II Subfloor Guidelines & Specifications Page Chapter 4 Wood Subfloor Guidelines 23 Chapter 5 Concrete Subfloor Guidelines 26 Chapter 6 Installing a Subfloor Over Concrete 27 24 National Wood Flooring

More information

2000 POCKET DOOR TECHNICAL DATA

2000 POCKET DOOR TECHNICAL DATA 2000 POCKET DOOR TECHNICAL DATA KWIK-WALL... One Source for Wall Systems. KWIK-WALL s s for the 2000 Series - Steel Panel operable wall systems answer the challenge for space division needs posed by multi-purpose

More information

Container Installation Guide

Container Installation Guide Continuous Insulation Container Installation Guide Panels and InSerts The InSoFast CX Container panel and the InSerts are designed to fit most shipping containers. Containers have three types of corrugations:

More information

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 092500 - GYPSUM BOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

BENEFITS OF GREEN GLUE IN STANDARD WALL CONSTRUCTION

BENEFITS OF GREEN GLUE IN STANDARD WALL CONSTRUCTION WALL TYPES BENEFITS OF GREEN GLUE IN STANDARD WALL CONSTRUCTION STC 39 STC 42 STC 44 Single layer drywall both sides. Double layer drywall one side. Double layer drywall both side STC 46 STC 52 STC 55

More information

PROMATECT -H Timber Floor Protection Type 1

PROMATECT -H Timber Floor Protection Type 1 PROMATECT -H Timber Floor Protection Type 1 Ceilings & Floors General Information Introduction Promat carries a wide range of fire rated ceiling and floor systems with fire resistance of up to 240 minutes.

More information

Section HIGH-TENSION Stretched-Fabric Wall Systems SoftWalls, Inc.

Section HIGH-TENSION Stretched-Fabric Wall Systems SoftWalls, Inc. P a g e 1 PART I. GENERAL 1.01 Scope A. Furnish and install SoftWalls HIGH-TENSION Acoustical & Tackable Stretch Fabric Systems B. Related Work Specified Elsewhere: 1.Preparation of a smooth, flat and

More information

Sound control begins with plumbing and HVAC layout. BY MYRON R. FERGUSON In my experience, residential sound control goes something

Sound control begins with plumbing and HVAC layout. BY MYRON R. FERGUSON In my experience, residential sound control goes something The Quest for a Quiet Room Successful sound control requires a basic understanding of acoustics, the right choice of materials, and meticulous attention to detail BY MYRON R. FERGUSON In my experience,

More information

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs November 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements....................................

More information