1 NATATORIUM
2
3 CAMPUS DATA NATATORIUM Hwy 105 West, Montgomery TX Year Built 2009 Approx. Total Square Footage Grades Served 30,420 n/a Current Enrollment n/a Building Levels 1 1
4 MASTER PLAN 2
5 BUILDING CONDITION: EXTERIOR Building Envelope Masonry: Masonry discoloration due to moisture from downspout and weep issues. Most masonry is in good condition. Gutters: There are some leaks in the gutters on the Northwest and Southwest side creating some ponding and masonry discoloration. Also some downspouts around building need to be repainted, color has faded due to sun exposure. Doors: The doors are in good condition. Windows: Windows are in good condition. Site Conditions Pavement Conditions: All paving in good condition, parking asphalt has cosmetic issues that could be refinished. Grade Condition: No major grading issues recorded 3
6 BUILDING CONDITION: EXTERIOR 4
7 BUILDING CONDITION: EXTERIOR View of the front entrance. Drainage issue. Water collection above drain, moisture is causing some paving and masonry discoloration Drainage issue at downspout. Minor expansion joint and sealant separation. Another location where drainage is an issue at downspout locations. Moisture or leak present, source is unknown. 5
8 BUILDING CONDITION: EXTERIOR Moisture runs all along Northwest wall. Security camera not properly installed. Northeast façade. Northeast façade. Southeast façade. Southwest parking lot. 6
9 BUILDING CONDITION: INTERIOR Summary of Conditions Floors: The majority of the flooring is in good condition. There are several minor floor cracks on the flooring in the coaches locker room. Floor inside main pool room should be refinished to avoid permanent staining from water. Several rooms require the base to be replaced. Walls: Walls are in good condition. Walls inside locker rooms and showers should be refinished, starting to show heavy wear and tear in these areas. Ceilings: Suspended acoustic ceilings throughout the facility are in good to fair condition. Doors and Hardware: The majority of the door hardware throughout the facility is not considered handicap accessible and should be replaced, although doors have the right type of handle, they cannot be locked from the interior of the classroom. The entrances currently have a secure vestibule, but lack a buzzer or doorbell system to moderate access to the building. Several hollow metal door frames require new paint. Windows: Windows throughout the facility are in good condition. Casework: Casework throughout the facility is plastic laminate, and in good condition. However, casework inside meeting room needs to be refinished and adjusted. Signage: Signage throughout the facility is in good condition. 7
10 BUILDING CONDITION: INTERIOR 8
11 BUILDING CONDITION: INTERIOR 103 Meeting Sink height not compliant at 35". 103 Meeting Casework needs refinishing and adjustment. 104 Boys Locker Room, all in good condition. 104B RR Urinal height not compliant at 24". 104B RR Damaged base. 104C Showers Drainage issue, puddling slope may need to be increased. Huckabee 9
12 BUILDING CONDITION: INTERIOR 104C Showers Walls are dirty and need refinishing. 105 coaches Floor crack, 15'. 105 RR C Shower seats needs to be remounted. 105 RR C Sink height not compliant at 35". 105 RR D Base is tearing near showers. 106 Lockerroom Boys Athletics Locker Room, all in good condition. Huckabee 10
13 BUILDING CONDITION: INTERIOR 107A Girls Locker Room, all in good condition. 107B Toilet seat height not compliant, only ADA stall compliant. 107B shower ADA shower broken, no hose. 107B shower Shower base needs to be refinished. 108 Girls Athletics Locker Room, all in good condition. 110 Weight room Ceiling leak. Huckabee 11
14 BUILDING CONDITION: INTERIOR 200 Pool Base and floor stained. Concession 101 Typical door handle, cannot lock from the interior. Corridor 1 Girls RR Toilet seat heights not compliant, only ADA stall compliant. Corridor 1 Girls RR No mirrors. Corridor 1 Girls RR Door needs to be refinished. Corridor 1 Girls RR No mirrors. Huckabee 12
15 BUILDING CONDITION: INTERIOR Corridor 1 RR Men No mirrors. Corridor 1 RR Men Toilet seat height not compliant, only ADA stall compliant. Corridor 1 RR Men Urinal height not compliant at 24". Custodian 2 exit 7 Ceiling grid is damaged. Custodian 2 exit 7 Base is peeling off wall and mop sink. Lobby 2 Ceiling leak. Huckabee 13
16 BUILDING CONDITION: INTERIOR Lobby 2 Small wall crack at corner connection. Mechanical 2 No base, not all walls are painted in mechanical room. Mechanical 1 Leak in mechanical room. Mechanical 1 Minor wall crack at corner connection. Room 200 (pool) Main pool. Room 200 (pool) Main pool. Huckabee 14
17 BUILDING CODE AND TAS Exterior Conditions Accessible Path: All paths to the building are ADA compliant. Stairs and Ramps: All ramps and curb ramps along accessible routes are ADA compliant. Changes in Level: N/A Door Landings: All landings outside of exterior doors are ADA compliant. Interior Conditions Accessible Paths: All paths inside the building are ADA compliant. Protruding Objects: N/A Door Clearances: All doors meet required clear space. Doors Hardware: Doors throughout the school do not have the manual locking at the handle. Hardware should be replaced. Restrooms/Locker Rooms: Toilets throughout the building do not meet the required seat height, only ADA toilet fixtures meet the required height. Several urinals are mounted higher than allowed by ADA requirements. Multiuser restrooms currently have no mirrors. Girls ADA shower currently is not operable. Drinking Fountains: Drinking fountains throughout the campus are ADA complaint. Counters, Sinks and Work Surfaces: Sink inside the meeting room does not comply with the required ADA height, currently at 35. Clothes/Book bag Hooks: N/A Room Signage: Signage throughout the facility is in good condition. 15
18
19 ENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING The building was reviewed and ranked as follows: 5 Excellent; 4 Good; 3 Fair; 2 Poor; 1 Failure Corrosion control and maintenance on all condensing units recommended - 3 Corrosion control and maintenance on all condensing units recommended - 3 Corrosion control and maintenance on all condensing units recommended - 3 Corrosion control and maintenance on all condensing units recommended
20 ENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING Exhaust and Ventilation required. Current ventilation is not working properly and corrosion of the facility has begun - 1 Exhaust and Ventilation required. Current ventilation is not working properly and corrosion of the facility has begun - 1 Exhaust and Ventilation required. Current ventilation is not working properly and corrosion of the facility has begun 1 Exhaust and Ventilation required. Current ventilation is not working properly and corrosion of the facility has begun - 1 Exhaust and Ventilation required. Current ventilation is not working properly and corrosion of the facility has begun 1 Exhaust and Ventilation required. Current ventilation is not working properly and corrosion of the facility has begun
21 ENGINEERING REPORT - STRUCTURAL No significant structural concerns were noted during our time on the site; however, our observations for this assessment were limited as described in the Preamble. If the District ever has any structural concerns, please let us know and we might amend our report. Further study is recommended to determine if there is sufficient flexural capacity in the cantilevered masonry walls primarily exterior walls for screening walls shown in picture 1. 19
22 ENGINEERING REPORT - STRUCTURAL 20
23 ENGINEERING REPORT - STRUCTURAL Cantilevered screening walls. 21
24
25 ROOFING Montgomery ISD Aquatics Center is a two story structure with a standing seam metal roof system. The standing seam metal roof system is bound by a prefinished perimeter metal. The drainage of the standing seam metal roof system is accomplished by using gutters along all sides of the roof and drains onto the adjoining field. The single ply roof system is bound by a prefinished perimeter metal. The drainage of the single ply roof system is accomplished by using both primary and overflow field drains. Roof Composition: No cores were taken on the metal roof system. No cores were taken on the single ply roof system as it is still under warranty. Deficiencies: The roof systems appeared to be in good condition as few deficiencies were observed. 1. Deteriorated sealant joint./ 1 EA 2. Deteriorated pipe boot sealant./ 7 EA 3. Organic growth within the gutter./ 1 EA 4. Damaged membrane with exposed insulation./ 1 SF Recommendations: Perform remediations to the deficiencies listed above. Performing recommended repairs may extend the roof s estimated remaining service life by slowing the deterioration of the roofing system components. 23
26 ROOFING
27 ROOFING General view of the deteriorated sealant joint. General view of the deteriorated pipe boot sealant. General view of the organic growth within the gutter system. General view of the damaged membrane with exposed insulation. 25
Total Building Area: 1964 Construction 30,140 square feet 1976 Construction 36,787 square feet 66,927 square feet
FLANDERS ELEMENTARY SCHOOL Located at 167 Boston Post Road, East Lyme, Connecticut the school s original structure was built in 1964 and replaced the Central Office Building as the elementary school. Two
More informationBOWIE LEARNING CENTER
BOWIE LEARNING CENTER Bowie Learning Center BUILDING DATA BOWIE LEARNING CENTER 900 North Elm St., Weatherford, TX 76086 Year Built 1936 No. of Buildings No. of Portables 0 Approx. Total Square Footage
More informationThe parking lot is in varying condition depending upon location. The vehicular and pedestrian traffic flow is generally good.
EAST LYME HIGH SCHOOL Located at 30 Chester Field Road, East Lyme, Connecticut 06333, the High School s original structure was built in 1967. An addition and alterations occurred in 1973. The building
More informationDivision 09 FINISHES TABLE OF CONTENTS
Division 09 FINISHES TABLE OF CONTENTS 09 1000 GENERAL... 3 A. RELATED SECTIONS... 3 B. MAINTENANCE OF FINISHES... 3 C. PUBLIC AREAS... 3 D. CUTTING AND PATCHING... 3 E. CLEANING... 3 F. RECOMMENDED FLOORING
More information2 Main School Building BLDG-124A Building Purpose Building Area Administrative, Classrooms, Cafeteria and Gymnasium 61,905 SF Inspection Date June 28-
1 Metz Elementary School Site Summary Address 84 Robert Martinez Jr. Austin, TX 78702 Number of Permanent Campus Facilities 1 Original Year of Construction 1993 Total Campus Building Area (combined) 61,905
More informationUSER INSTRUCTIONS The FIT is comprised of three parts as follows:
GENERAL INFORMATION The Facility Inspection Tool (FIT) has been developed by the Office of Public School Construction to determine if a school facility is in good repair as defined by Education Code (EC)
More informationLOGAN SCHOOL SCHOOL WITHOUT WALLS AT LOGAN
INITIAL YEAR BUILT 1935 BUILDING AREA 47,200 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 418 WARD 6 PROPOSED PROGRAM CAPACITY 450 Site Plan LOGAN - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION HS
More informationSPACE TYPE: OUTSIDE PARKING (STRUCTURE)
SPACE TYPE: OUTSIDE PARKING (STRUCTURE) Construction Criteria The unit costs for Outside Parking (Structure) space types are based on the construction quality and design features in the following table.
More informationCODE COMPLIANCE PLAN REVIEW PROCEDURES
CODE COMPLIANCE PLAN REVIEW PROCEDURES 1. All construction for state agencies on state-owned or state leased-purchased properties or facilities are to submit design documents for code compliance plan reviews
More informationPLUMMER ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1959 BUILDING AREA 69,400 SF CURRENT PROGRAM CAPACITY 481 ENROLLMENT 2008 228 WARD 7 PROPOSED PROGRAM CAPACITY 325 Site Plan PLUMMER - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationMt. Jumbo Gymnasium. Facility Condition Survey Report. Prepared August 2014
Mt. Jumbo Gymnasium Facility Condition Survey Report Prepared August 2014 By MRV Architects, R&M Engineering (Structural), Murray & Associates (Mechanical), and Haight & Associates (Electrical), and City
More informationProperty Condition Assessment
Property Condition Assessment Pewaukee, WI 53072 Inspection Date: 1/6/15 Prepared For: Report Number: Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar Dr. Pewaukee, WI 53072
More informationMISSOURI DEPARTMENT OF TRANSPORTATION ATTACHMENT G FACILITIES EXPECTATION FORM
MISSOURI DEPARTMENT OF TRANSPORTATION ATTACHMENT G FACILITIES EXPECTATION FORM Note: This list should be used as a guide and not considered all inclusive. The offeror should use due diligence for any items
More informationFacility Improvements
CA-SI-01 ACCESSIBLE PARKING STALL ADDITIONS CA-SI-07 BASEBALL & SOFTBALL INFIELD IMPROVEMENTS Additional parking stalls and signage needed for disabled individuals and to meet ADA requirements. Installation
More informationMISSOURI DEPARTMENT OF TRANSPORTATION ATTACHMENT G REST AREA/WELCOME CENTER AND TRUCK PARKING FACILITY PERFORMANCE MEASURES
MISSOURI DEPARTMENT OF TRANSPORTATION ATTACHMENT G REST AREA/WELCOME CENTER AND TRUCK PARKING FACILITY RESTROOMS Toilets and urinals Clean and functional All toilets shall be clean and functional at all
More informationBuilding Inspection Report
Building Inspection Report Sample Commercial Inspection Report Inspection Date: Prepared For: Prepared By: Professional Property Inspection Consultants 4857 Winterset Drive Columbus, OH 43220 (614) 459-5941
More informationMadison School District. Strategic Five-Year Facility Maintenance Plan
Madison School District Strategic Five-Year Facility Maintenance Plan 2016 2020 Dear Madison Stakeholder, Throughout the past twenty years, Madison School District has experienced tremendous growth. Since
More informationBRUCE MONROE AT PARK VIEW ELEMENTARY SCHOOL MODERNIZATION PROPOSED MAIN ENTRY - EXTERIOR RENDERING
PROPOSED MAIN ENTRY - EXTERIOR RENDERING EXISTING SITE AERIAL PHOTOGRAPH 6TH STREET NW PEDESTRIAN ACCESS School access to existing alley leads students through vehicular path CHAIN LINK ENCLOSED PARKING
More informationLASALLE - BACKUS EDUCATION CAMPUS
INITIAL YEAR BUILT 1957 BUILDING AREA 63,000 SF CURRENT PROGRAM CAPACITY 406 ENROLLMENT 2008 349 WARD 4 PROPOSED PROGRAM CAPACITY 425 Site Plan LASALLE - BACKUS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationVelma F Thomas Early Childhood Center
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationLEWIS ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1962 BUILDING AREA 49,500 SF CURRENT PROGRAM CAPACITY 550 ENROLLMENT 2008 288 WARD 1 PROPOSED PROGRAM CAPACITY 450 Site Plan LEWIS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5
More informationJohn T Pirie Fine Arts & Academic Center ES 650 E 85th St Chicago, IL 60619
E 8th St Chicago, IL 19 Facility Assessment Report This report contains a summary of the results from the facility assessment completed on the date noted in the document footer below. This report will
More informationLECKIE ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1970 BUILDING AREA 65,000 SF CURRENT PROGRAM CAPACITY 471 ENROLLMENT 2008 321 WARD 8 PROPOSED PROGRAM CAPACITY 400 Site Plan LECKIE - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5
More informationCARL E. SCHLUTER ELEMENTARY SCHOOL
CARL E. SCHLUTER ELEMENTARY SCHOOL Carl E. Schluter Elementary School Campus Data CARL E. SCHLUTER ELEMENTARY SCHOOL 1220 Mesa Crest Drive, Haslet, Texas 76052 Year Built 2011 Approx. Total Square Footage
More informationDesign Advisory Committee Meeting #1. December 6, 2016
Design Advisory Committee Meeting #1 December 6, 2016 1 Meeting Agenda 1. Agenda / Attendance Sheet 5 minutes 2. Introductions - 10 minutes 3. Meeting Norms 5 minutes 4. Project Schedule 5 minutes 5. Buildings
More informationClassroom Facilities Assessment Program. Building Phone: Enrollment Date is the date in which the current enrollment was taken.
Building Information - Columbus City SD (43802) - Alum Crest Special School (513) Program Type: Setting: Assessment Name: Classroom Facilities Assessment Program Urban Alum Crest Special School Assessment
More informationSchool Without Walls
INITIAL YEAR BUILT 1938 BUILDING AREA 59,400 SF CURRENT PROGRAM CAPACITY 304 ENROLLMENT 2008 276 WARD 1 PROPOSED PROGRAM CAPACITY 400 SCHOOL WITHOUT WALLS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationHISTORIC PLAN, FLOOR PLANS, AERIAL PHOTOS
1 Page 1 of 28 HISTORIC PLAN, FLOOR PLANS, AERIAL PHOTOS HISTORIC PLAN NOT TO SCALE NORTH 2 Page 2 of 28 SITE PLAN NOT TO SCALE NORTH 3 Page 3 of 28 BUILDING INSPECTION REPORT The assessment of site and
More informationTERMINAL BUILDING EVALUATION
TERMINAL BUILDING EVALUATION 1.0 INTRODUCTION This report evaluates the existing Terminal Building at Frederick Municipal Airport (FDK) to determine the suitability of the building for continued use as
More informationDRAFT. Baker Center Special Campus Site Summary 64,153 SF. Introduction
1 Baker Center Special Campus Site Summary Address 3908 Avenue B Austin, TX 78751 Number of Permanent Campus Facilities 3 Original Year of Construction 1911 Total Campus Building Area (combined) 64,153
More informationCITY OF NOVI. Police Department
CITY OF NOVI Police Department Indoor Gun Range and Training Facility Assessment Analysis with Master Plan for Novi Police Department at Community Build Out Field Services Complex Facility Needs Master
More informationCheldelin Middle School
Facility Information Address: 987 NE Conifer Blvd Corvallis Site Size: Building Area: Construction Date: Improved Parking: Grade Levels Served: Regular Classrooms: Portable Classrooms: Sept. 2007 Enrollment:
More informationHERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW
HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW 27 September 2007 prepared by: J. CHRIS EVANS ARCHITECT 3220 E. Terra Alta Blvd. No. 9 Tucson, Arizona 85716 520.319.8835 evansarch@hotmail.com
More informationSIDEWALK & RAILING REPLACEMENT BOARD OF ED BUILDING
PROJECT: 25 E 5 S SALT LAKE CITY, UTAH 84111 CODE ANALYSIS APPLICABLE CODES 675 E. 5 S. Suite 4 DFCM PROJECT NUMBER: 182782 DFCM CONTRACT NUMBER: 18793 STRUCTURAL ENGINEER: REAVELEY ENGINEERS + ASSOCIATES
More informationProperty Condition Assessment (PCA) Checklist c:\users\joseph\documents\hhc\blog\pca cklist template.doc Friday, August 11, 2006
FORUM for Historic Harvard Property Assessment (PCA) Checklist c:\users\joseph\documents\hhc\blog\pca cklist template.doc Friday, August 11, 2006 The purpose of this document is to identify in checklist
More informationSPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM)
SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM) Construction Criteria The unit costs for the Physical Fitness Center (Exercise Room) space type are based on the construction quality and design features in
More informationClassroom Facilities Assessment Program. Building Phone: Enrollment Date is the date in which the current enrollment was taken.
Building Information - Cincinnati City SD (43752) - Jacobs Center Middle (81778) Program Type: Setting: Assessment Name: Classroom Facilities Assessment Program Urban Jacobs Center Middle School Assessment
More informationEXAMPLE REPORT OF PROPERTY CONDITION ASSESSMENT. <Address> <CITY, STATE> <Report Date> HCI Project Number <ProjNo> Prepared for <Property Name>
EAMPLE REPORT OF PROPERTY CONDITION ASSESSMENT HCI Project Number Prepared for 1114 Grindstone, Union, Kentucky 41091 (859) 657-6677
More informationTOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX
TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ 08014 856-467-3626--- FAX 856-467-9260 Application for Certificate of Occupancy for Change of Occupancy Pursuant to Chapter 119 of the Township
More informationAppendix A. Facilities Condition Assessment
Appendix A Facilities Assessment Facilities Assessment Facilities Assessment s on the Harford Community College campus have been well-maintained and are in excellent condition. Recent renovations to Havre
More informationTable of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities
Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)
More informationElement Z General Design Requirements Room Standards
Toilet Room Guidelines PART 1 - GENERAL 1.01 OVERVIEW A. This document provides design and construction criteria for public/patient, and staff toilet rooms at (Owner). PART 2 - DESIGN CRITERIA 2.01 GENERAL
More informationPaul Laurence Dunbar Career Academy High School 3000 S King Dr Chicago, IL 60616
Facility Assessment Report This report contains the detailed findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility item by visual observation
More informationLANSDOWNE HIGH SCHOOL RENOVATION PRELIMINARY DESIGN PRESENTATION. The Board of Education of Baltimore County Verletta White, Interim Superintendent
RENOVATION PRELIMINARY DESIGN PRESENTATION The Board of Education of Baltimore County Verletta White, Interim Superintendent AGENDA 2 Project Location General Information Existing Conditions Structural
More informationSECTION ALTERNATES
SECTION 01 23 00 - ALTERNATES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationCity of Des Moines. Permit and Development Center 602 Robert D Ray Drive Des Moines, IA Phone: Fax:
City of Des Moines Permit and Development Center 602 Robert D Ray Drive Des Moines, IA 50309 Phone: 515-283-4200 Fax: 515-283-4270 This Code Analysis Form must be completed and returned with the Building
More informationFairfax Elementary School 3150 Fairfax Rd, Cleveland Heights, Ohio
District Wide Facilities Evaluation Building Assessment Report Fairfax Elementary School 3150 Fairfax Rd, Cleveland Heights, Ohio prepared for: Cleveland Heights University Heights City School District
More informationMargaret Batts Tobin Laboratory
Roof Evaluation of Margaret Batts Tobin Laboratory The University of Texas At San Antonio Performed for UTSA Zero/Six Consulting, LLC 8423 Stewart Road Galveston, Texas 77554 409 740 0090 voice Table of
More informationInspection Report Summary
Inspection Report Summary Prepared for: Property Location: XXXXXXXXXXXXXXXX XXXXXXXXXXXXX Dallas, Texas 75XXX Contact Info: Home Phone: XXXXXXXXXXXX E-mail: XXXXXXXXXXXXXXXX Date of Inspection: October
More informationOFFICE OF EDUCATIONAL FACILITIES FLORIDA BUILDING CODE SECTION 423 APPLICATION MATRIX
423.1 Scope: Public educational facilities 423.2 Public schools and community colleges general requirements 423.2.1 Owner 423.2.2 Exemption from local requirements 423.2 Code enforcement 423.3.1 School
More informationEdouard AVANT GROVE U I C U I C. Modern Living Made Easy uichomes.com
Edouard Modern Living Made Easy uichomes.com - new construction - 3 stories + full basement - 4 bedrooms - 2.5 baths - 2,380 s.f. call 314.881.2333 or e-mail sales@uicstl.com PLAN NTS DECK 13' 0" X 12'-0"
More informationSubject: Lucretia Mott School No. 3 Rehabilitation. Figure 1 Figure 2 Figure 3
MEMORANDUM To: Ashley Rosenthal Payne, Indianapolis Historic Preservation Commission Adrienne Schmetzer, Indiana Housing and Community Development Authority Architecture Preservation Interior Design Landscape
More informationClassroom Facilities Assessment Program. Building Phone: Enrollment Date is the date in which the current enrollment was taken.
Building Information - Cincinnati City SD (43752) - Whittier Elem (41152) Program Type: Setting: Assessment Name: Classroom Facilities Assessment Program Urban Whittier Elem Assessment Date: 2001-04-11
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS ************************************************************************** SECTION TABLE OF CONTENTS
USACE / NAVFAC / AFCEC / NASA UFGS-09 06 00 (May 2009) Change 1-11/13 ----------------------------- Preparing Activity: USACE Superseding UFGS-09 06 90 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More information3D Home Improvement and Inspection Services, Inc
Property Inspection Report Cover Page ABC Disney Lane, Winter Garden FL, 34787 Inspection prepared for: John Doe Inspection Date: 7/15/2010 Time: 11:00 am Age: 6 Years Size: 3,378 LSF / 4,427 TSF Weather:
More informationINSPIRE each student to develop a strong
DEL PASO MANOR ELEMENTARY SCHOOL Valuing a culturally and academically DIVERSE COMMUNITY, Del Paso Manor Elementary School s Mission is to EDUCATE and INSPIRE each student to develop a strong A C A D E
More information1. Unified Facilities Criteria - Design: General Building Requirements (UFC ).
1. GENERAL GUIDANCE REGARDING DESIGN A. Commissary facilities are Department of Defense (DoD) projects, and as such must be constructed in accordance with the following criteria, codes, and standards.
More informationA Design-Build Project: Repairing the Courthouse Square Complex
A Design-Build Project: Repairing the Courthouse Square Complex Cracked drywall in office building Cracked basement walls Separated columns at expansion joint Source: http://djcoregon.com/news/2010/07/22/salem-government-building-unsound-being-vacated/
More informationU.S. Department of Housing and Urban Development Community Planning and Development
U.S. Department of Housing and Urban Development Community Planning and Development Special Attention of: Notice: CPD-16-02 Regional Directors Field Office Directors Issued: February 8, 2016 CPD Division
More informationJames B Farnsworth Elementary School 5414 N Linder Ave Chicago, IL 60630
Linder Ave Chicago, IL 030 Facility Assessment Report This report contains a summary of the results from the facility assessment completed on the date noted in the document footer below. This report will
More informationUAA Science Renovation Phase 2 Narrative EXISTING BUILDING SITE
UAA Science Renovation Phase 2 Narrative A EXISTING BUILDING SITE The existing building is situated along the campus spine and connected by elevated walkways to the engineering building toward the west
More informationClassroom Facilities Assessment Program. Building Phone: Enrollment Date is the date in which the current enrollment was taken.
Building Information - Cincinnati City SD (43752) - Parham Elem (61606) Program Type: Setting: Assessment Name: Classroom Facilities Assessment Program Urban Parham Elementary Assessment Date: 2001-05-25
More informationStructural Inspection
General: Background: An inspection and structural analysis have been performed for the purpose of evaluating the buildings structural systems and components. A full set of structural drawings was utilized
More informationHealthy Homes Provisions of Lansing, Michigan Ordinances Extracted from by National Center for Healthy Housing
TITLE 6. HOUSING CHAPTER 1460. HOUSING AND PREMISES CODE Selected Provisions Related to Healthy Homes 1460.02. Applicability. (h) Historic Buildings. The provisions of this Code shall not be mandatory
More informationFlorida Accessibility Code for Building Construction
Florida Accessibility Code for Building Construction Accessibility Training Course Florida Building Commission 1 Introduction Course will review the Florida Accessibility Code for Building Construction
More informationHome Inspection Report Report Number: For The Property Located On:
Home Inspection Report Report Number: 416-129 For The Property Located On: Some Place Dr Prepared For Exclusive Use By: John and Jane Doe Report Prepared By: Adam Duncan; License No.: 3533 Inspector Signature:
More informationJane Addams Elementary School S Avenue H Chicago, IL 60617
00 S Avenue H Chicago, IL 0 Facility Assessment Report This report contains a summary of the results from the facility assessment completed on the date noted in the document footer below. This report will
More informationINTERIOR ENVIRONMENT
CHAPTER 12 INTERIOR ENVIRONMENT > SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter shall govern ventilation, temperature control, lighting, yards and courts, sound transmission, room dimensions,
More informationReport to. Winnetka Library District 768 Oak Street, Winnetka, Illinois 60093
Report to Winnetka Library District 768 Oak Street, Winnetka, Illinois 60093 Capital Asset Study, Winnetka Library District 768 Oak Street Winnetka, Illinois 60093 BTC Project No. 11-777 June 21, 2011
More informationINTERIOR ENVIRONMENT
CHAPTER 12 INTERIOR ENVIRONMENT SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter shall govern ventilation, temperature control, lighting, yards and courts, sound transmission, room dimensions,
More informationUniversal Design Standards
Universal Design Standards For applications submitted and approved after April 16, 2007 Introduction to Universal Design Universal design is a building concept that incorporates products, general design
More informationRIVERS EDGE CONDOMINIUM ASSOCIATION MAINTENANCE RESPONSIBILITIES
RIVERS EDGE CONDOMINIUM ASSOCIATION MAINTENANCE RESPONSIBILITIES This Policy Document outlines the separation of responsibilities between the Rivers Edge Condominium Association (RECA) and the Unit Owners
More informationCHECKLIST Inspecting a Garage
CHECKLIST Inspecting a Garage By Ben Gromicko This section deals with the details of the garage or carport inspection that may be performed. At the end of this section, you shall be able to: describe the
More informationMOLD INSPECTION REPORT Block Home Inspections LLC
Block Home Inspections LLC David Block - 913-220-7762 MOLD INSPECTION REPORT Block Home Inspections LLC David M. Block Certified Mold Inspector #CMI-06-2024 INSPECTION AGREEMENT Mold screening is intended
More informationExpedited Local Partnership Program (ELPP)
Building Information - Fairview Park City (43976) - Gilles-Sweet Elementary Program Type Setting Assessment Name Expedited Local Partnership Program (ELPP) Suburban Gilles-Sweet Elementary Assessment Date
More informationOctober 26, 2017 Ref.: Newfoundland & Labrador English School District 95 Elizabeth Avenue St. John s, NL A1B 1R6
October 26, 2017 Ref.: 351-1 Newfoundland & Labrador English School District 95 Elizabeth Avenue St. John s, NL A1B 1R6 Attention: Mr. Jim Sinnott Director of Facilities & Custodial Management Dear Sir:
More informationCENTENNIAL SCHOOL DISTRICT
CENTENNIAL SCHOOL DISTRICT Middle School Feasibility Study Project PLANNING STUDY PRESENTATION 24 May 2016 Middle School Master Planning Process 1. Familiarized team with existing middle schools and sites
More informationGUIDELINES FOR SANITARY DESIGN AND CONSTRUCTION OF MILK PRODUCTS PLANTS (rev )
Milk and Dairy Food Safety Branch 1220 N Street, Sacramento, CA 95814 GUIDELINES FOR SANITARY DESIGN AND CONSTRUCTION OF MILK PRODUCTS PLANTS (rev. 10-20-2011) The outline below lists sanitary requirements
More informationClassroom Facilities Assessment Program. Crest Hills Year Round and Project Succeed. Building Phone:
Building Information - Cincinnati City SD (43752) - Crest Hills Year Round and Project Succeed (62414) Program Type: Setting: Assessment Name: Classroom Facilities Assessment Program Urban Crest Hills
More informationDIVISION 9 FINISHES. This Article on Codes, Regulation and Standards shall apply to all Divisions of the Building Standards
DIVISION 9 FINISHES This Article on Codes, Regulation and Standards shall apply to all Divisions of the Building Standards 1 Table of Contents SECTION 09 05 13 COMMON FINISHES 2 SECTION 09 51 23 ACOUSTICAL
More informationFacilities Condition Assessment Qualcomm Stadium
Qualcomm Stadium Facilities Condition Assessment Qualcomm Stadium Facilities Condition Assessment AECOM San Diego, California April 2011 Qualcomm Stadium Qualcomm Stadium Facilities Condition Assessment
More informationSTRUCTURAL CONDITION ASSESSMENT
STRUCTURAL CONDITION ASSESSMENT ALLEN JAY ROCK GYM 1201 FAIRFIELD ROAD HIGH POINT, NC Prepared for: Prepared by: Guilford County Schools 617 West Market Street Greensboro, NC Adrian S. Durham, PE, SE,
More informationChild Friendly Schools in Rwanda
Child Friendly Schools in Rwanda Typical drawings of school building and toilet block Approved by MINEDUC/UCEFS Eng. Warren Habimana UNICEF Rwanda PO Box 381, Kigali Education section: tel. +250 592750-55
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Calgary Health Region Carewest Cross Bow Auxiliary Hospital B1073A Calgary Report run on: March 3, 9:44 AM Building Name: Address: Location: Building Id: Gross Area (sq.
More informationLEVEL TWO NUMBERS AND TITLES. Introductory Information. Bidding Requirements. Contracting Requirements. Facilities and Spaces. Systems and Assemblies
MasterFormat LEVEL TWO NUMBERS AND TITLES Introductory Information 00001 Project Title Page 00005 Certifications Page 00007 Seals Page 00010 Table of Contents 00015 List of Drawings 00020 List of Schedules
More informationDeKalb County School District/Stadiums Avondale Stadium Final School Assessment Report May 20, 2016
DeKalb County School District/Stadiums Avondale Stadium Final School Assessment Report May 20, 2016 PARSONS School Assessment Report Table of Contents School Executive Summary 4 School Condition Summary
More informationEncapsulated, Sealed & Closed Crawlspace Installation Manual
YourCrawlSpace, Inc. 1007 Johnni4 Dodds Blvd. Mt. Pleasant, SC 29464 Toll Free: 877-44-CRAWL (27295) Local: (843) 593-1115 Encapsulated, Sealed & Closed Crawlspace Installation Manual Copyright 2017 Your
More informationNorth Haven Police Department Berniere Memorial Building
North Haven Police Department Berniere Memorial Building Existing Building Conditions February 2016 EXISTING BUILDING CONDITIONS 1 Contents Foreword... 3 Introduction... 4 Current Status of Building...
More informationCode Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617)
Code Requirements for Existing Buildings R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS) was established in 1945 and currently
More informationThe conditions, recommendations, suggestions contained herein are the result of a visual inspection as of this date.
HOME INSPECTION ENGINEERS LICENSED PROFESSIONAL ENGINEERS 926 Haddonfield Road, Suite E PMB 162 Cherry Hill, NJ 08002 800-676-7879 Phone 856-482-6615 Fax 856-667-8401 In accordance with your request, the
More informationUniversity of Texas. Austin, TX. TAS Variance Application Guidelines For Qualifying Historic Structures
University of Texas Austin, TX TAS Variance Application Guidelines For Qualifying Historic Structures Architecture, Planning and Historic Preservation, Inc. 2900 S. Congress Ste 200 Austin, TX 78704 512.444.4220
More informationDESIGN AND CONSTRUCTION STANDARDS. Section 2: Standards for Specific Categories of Work. Laboratory Standards
Laboratory Standards These criteria include general planning guidelines. They are intended for use of Designers during the design phases of the project. Planning Assumptions Overview In order to maximize
More informationHOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS This guide is intended to provide the homeowner or contractor with the
More informationCITY OF CALABASAS RESIDENTIAL PLAN REQUIREMENTS 1 OF 5 8/2017 PLAN INFORMATION
1 PLAN INFORMATION Residential plans must be legible and capable of digital scanning. All sheets shall be the same size and distinctly labeled with a sheet title and number. The minimum dimension of the
More informationSuccessful Restaurant. Accessibility. Accessibility. Did you sign in? Best Practices. Copyright Materials. Course Description
Successful Restaurant Accessibility Successful Restaurant Accessibility TDLR Provider #1521 AIA/CES Provider #G583 Michael Love APA ICC IIDA Best Practices Did you sign in? Accessibility Professionals
More informationDUKE UNIVERSITY CONSTRUCTION STANDARDS
1 07 40 00 Roofing 1. General Several factors repeatedly show up during the inspection of roofs that have failed prematurely. They include inappropriate use of materials, poor drainage systems, poor details
More informationUniversity of Toronto Cleaning Specifications
Revised/Updated February 1-2013 University of Toronto Cleaning Specifications AREA TYPE Task To Be Completed Frequency Main Entrance 1 Clean both sides of door glass including side lights. Daily & 2 Clean
More informationAcoustic Design Criteria
Apartment Acoustics Apartment Buildings Acoustic Design Criteria Building Code of Australia: - Intertenancy walls and floors - Corridor walls and doors - Floor impact isolation - Lift, stair and core walls
More informationDate Rater Verified. Rater Verified. Slab / Pre-Drywall / Thermal Inspection
Slab on Grade & Basements: A capillary break is installed on top of all footings Slab / Pre-Drywall / Thermal Inspection A minimum of 4" of clean or washed gravel (0.5" diameter or greater) is placed over
More informationAuditor Checklist. Age: Height: (ft) (inches)
Assignment Overview: You will visit your assigned Kmart location to evaluate exterior and interior facility features, focusing on cleanliness, condition, and access for disabled customers. You will also
More information