1 SECTION SUPPORTS, ANCHORS, AND SEALS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division 1 Specification Sections, and the Mechanical General Requirements Section apply to work of this Section, as if repeated herein REFERENCES A. Pipe Supports: ANSI B 31.1, Power Piping. B. Automatic Sprinkler Pipe Supports: Refer to Section C. Standpipe System Pipe Supports: Refer to Section D. Duct Hangers: SMACNA Standards SUMMARY A. This section includes supporting and anchoring of equipment, piping ductwork and associated accessories specified in subsequent sections as well as sealing of penetrations through building components due to same. B. Related Sections: The following sections contain requirements that relate to this section. 1. Division 15 Mechanical - All sections. PART 2 - PRODUCTS 2.01 ACCEPTABLE MANUFACTURERS A. Hangers:
2 1. Carpenter & Patterson 2. Elcen 3. Grinnell 4. Joslyn 5. Michigan 6. Powerstrut 7. Superior 8. Unistrut B. Seismic Expansion Compensators: 1. Adsco 2. Hyspan Or equal INSERTS, EXPANSION SHIELDS, AND CLAMPS A. Inserts for use in poured-in-place concrete shall have malleable iron cases or galvanized steel shells and expander plugs for threaded connection with lateral adjustment, top slot for reinforcing rods, lugs for attaching to forms. B. Size inserts to fit threaded hanger rods. C. Use drilled insert expansion shields on concrete walls and on sides of concrete beams. Do not use power-driven fasteners, expansion nail type anchors, or friction spring-type clips. D. In areas of metal decking and joists, all pipe and duct shall be hung from joists and intermediate steel with Elcen No. 25 malleable iron "C" clamps. Provide angles and channels to span between joists PIPE HANGERS AND SUPPORTS A. Hangers for Uninsulated Pipe: An adjustable wrought steel clevis, Elcen No. 12. B. Hangers for Cold Insulated Pipe, All Sizes: An adjustable wrought steel clevis, Elcen No. 12, sized to suit 360 degree high-density insulation insert. C. Hangers for Hot Insulated Pipe, Sizes 1/2" to 1-1/2": An adjustable wrought steel clevis, Elcen No. 12, sized to suite a 180 degree, 20 gauge galvanized sheet metal insulation saddle, 12" long.
3 D. Hangers for Hot Insulated Steel Pipe, Sizes 2" and Larger: Adjustable roller hanger with steel yoke and cast iron roller, Elcen No. 14, with Series 250 welded insulation protection saddle, size to accommodate insulation. E. Hangers for Hot Insulated Copper Pipe, Sizes 2" and Larger: Same as for steel except with 360 degree high-density insert. F. Rollers or Sliding-Type Supports: Provide for hangers of all sizes to permit free movement of piping where expansion and contraction will occur. G. High Density Insulation Inserts: 360 degree rigid calcium silicate (waterproofed for chilled water) inserts having 360 degree sheet metal sleeve at all hangers supporting all insulated pipes 2-1/2" and larger. Thickness shall match pipe covering thicknesses. Inserts shall be Pipe Shields, Inc., for chilled water, Model A-2000 and A-4000; for all other insulated lines, Model A-1000 and A-3000; each of which shall be selected predicated upon hanger type or pipe size. H. Multiple or Trapeze Hangers: Steel channels or angles with welded spaces and hanger rods, sized to support load. I. Wall Support for Pipe Sizes to 3": Cast iron hooks. J. Wall Support for Pipe, Sizes 4" and Larger: Welded steel bracket and wrought steel clamp; adjustable steel yoke and cast iron roll for hot pipe, sizes 5" and larger. K. Vertical Support: Steel riser clamp, Elcen No. 39. L. Floor Support for Hot Pipe, Sizes to 4", and All Cold Pipe Sizes: Cast iron adjustable pipe saddle, locknut nipple, floor flange, and concrete pier or steel support. M. Floor Support for Hot Pipe, Sizes 5" and Larger: Adjustable cast iron roll and stand, steel screws, and concrete pier of steel support. N. Design hangers to impede disengagement by movement of supported pipe. O. Provide copper-plated hangers and supports for copper piping or provide isolator between hanger or support and piping. P. Provide angles or channels to span joists and distribute load.
4 Q. Do not use wire for either temporary or permanent hanger or support purposes PIPE ISOLATORS A. Provide each hanger or clamp for insulated piping with a metal-backed pipe isolating material to isolate sound vibration and electrolysis. Isolators are not required for fire protection, sprinkler piping, waste, vent, gas, and downspout piping HANGER RODS A. Provide steel hanger rods, appropriately threaded. Provide connection points with jamb nuts or double nuts DUCT HANGERS AND SUPPORTS A. Per SMACNA Standards. B. Provide galvanized steel angles, channels, stays, rods, etc., for duct support and reinforcement. Do not use raw steel FLASHING A. Steel Flashing: 26 gauge galvanized steel. B. Lead Flashing: 4 lb/sq ft sheet lead for waterproofing; 1 lb/sq ft sheet lead for soundproofing. C. Safes: 5 lb/sq ft sheet lead or 8 mil thick neoprene. D. Caps: Steel, 22 gauge minimum, 16 gauge at fire-resistant structures SLEEVES A. Sleeves for Pipes Passing Through Nonrated Walls and Floors: Schedule 40 black steel pipe. For waterproof sleeves, use Thunderline Link-Seal or Calpico Sealing Linx. B. Sleeves for Pipes Passing Through Beams, Walls, and Footings: Schedule 40 black steel pipe or 20 gauge galvanized steel.
5 C. Insulated pipes passing through fire-rated walls and floors shall be provided with insulation through the penetration which shall consist of a 360 degree waterproofed calcium silicate insert sized to extend a minimum of 1" beyond the wall or floor penetration. The insert shall be the same thickness as the pipe covering it adjoins. Sleeves shall be the same thickness as the pipe covering it adjoins. Sleeves shall have the same fire rating as the construction in which they are installed. Sleeves shall be Pipe Shields, Inc. for bare pipe, Model F-3000 for walls, F-6000 for floors, F-2000 and F-5000 for insulated chilled water, and F-1000 and F-4000 for all other insulated lines. D. Open voids and cavities occurring in pipe sleeves passing through rated walls and floors shall be completely sealed with UL classified Dow Corning Fire Stop Sealant #2000 installed in strict accordance with the manufacturer's recommendations. E. Sleeves for Ducts: Form with galvanized steel. F. Size sleeves large enough to allow for movement due to expansion and to provide for continuous insulation SEISMIC EXPANSION COMPENSATORS A. Compensators for Water Piping 3" and Larger: Hyspan Series 1500 Universal with flanged ends, tie rods, and 321 stainless steel laminated bellows. B. Compensators for Piping 2-1/2" and Smaller: Hyspan 321 stainless steel braided hose. Provide Series 4505 with threaded ends for natural gas; Series 4510 with sweat ends for domestic cold, hot, and hot water return. C. Provide units suitable for minimum 150 psi at 400 degrees F. D. Units shall be manufactured and installed in accordance with EJMA recommendations and shall provide for multiple plane movement for seismic isolation ROOF CURBS A. Provide prefabricated curbs for roof mounted equipment specified in subsequent sections of Division 15 and for ductwork penetrating roof. Curbs shall be as specified in Section "Roof Specialties and Accessories."
6 PART 3 - EXECUTION 3.01 INSERTS AND EXPANSION SHIELDS A. Use inserts for suspending hangers from reinforced concrete slabs and sides of reinforced concrete beams wherever practicable. B. Set inserts in position in advance of concrete work. Provide reinforcement rod in concrete for inserts carrying pipe over 4" in diameter or ducts over 60" wide. C. Where concrete slabs form finished ceiling, finish inserts flush with slab surface D. Locate expansion shields in concrete beams with a minimum of 6" above bottom of beam. E. Do not use power-driven fasteners or friction spring-type clips PIPE HANGERS AND SUPPORTS A. Support horizontal steel and copper piping as follows: Hanger Rod Nominal Pipe Support Diameter Size (inches) Spacing (feet) (inches) 1/2 to 1-1/4 6 3/8 1-1/2 to /8 2-1/2 to 3-1/2 12 1/2 4 & /8 6 to /8 B. Install hangers to provide minimum 1/2" clear space between finished covering and adjacent work. C. Support piping at each change in direction, at ends of branches, at base and top of risers, drops, and wherever necessary to prevent sag, bending, or vibration, in addition to the above listed hanger spacing. D. Use hangers which are vertically adjustable 1-1/2" minimum after piping is erected.
7 E. Support horizontal soil pipe near each joint, with 5'-0" maximum spacing between hangers and with no more than two joints occurring between any two hangers. F. Support vertical piping at every other floor. Support vertical soil pipe at each floor at joint. G. Where several pipes can be installed in parallel and at same elevation, provide multiple or trapeze hangers. H. Where practical, support riser piping independently of connected horizontal piping. I. Support nonmetallic piping with a sufficient number of hangers to prevent sagging and misalignment DUCT HANGERS AND SUPPORTS A. Duct hangers, supports, and installation per SMACNA Standards. B. Specific details shown on Drawings take precedence over SMACNA requirements EQUIPMENT BASES AND SUPPORTS A. Provide 6" minimum thickness reinforced concrete housekeeping bases poured directly on structural floor slab for major equipment including air cooled condensing units. Extend pads a minimum of 6" beyond machinery bedplates. Provide templates, anchor bolts, and related accessories for mounting and anchoring equipment. B. Construct supports of structural steel members or steel pipe and fittings. Brace and fasten with flanges bolted to structure. C. Stiff leg (stanchion) support of piping shall not interfere with the free operation of vibration isolation systems PAINTING A. Paint exposed steel hangers and supports. Hangers and supports located in crawl spaces, pipes shafts and suspended ceiling spaces are not considered exposed. Refer to Section "Painting."
8 3.06 FLASHING A. Flash and counterflash where mechanical equipment passes through weather or waterproofed walls, floors, and roofs. B. Flash vent and soil pipes with 24" by 24" sheet lead, minimum 8" above roof. Counterflash with caulked stack flashing sleeve, Zurn Z-196. C. Flash floor drains over finished areas and roof drains with lead, 10" clear on sides, minimum 36" by 36" sheet size. Fasten flashing to drain with clamping device. D. Provide 8" minimum height curbs for roof mounted mechanical equipment. Flash and counterflash with galvanized steel, soldered and waterproofed SLEEVES A. Set sleeves in position in advance of concrete work. Provide suitable reinforcing around sleeves. B. Where piping or ductwork passes through floor, ceiling, or wall, close off space between pipe or duct and construction with noncombustible insulation. Provide tight-fitting metal caps on both sides and caulk. C. Install chrome-plated escutcheons where piping passes through finished surfaces. D. Provide pipe sleeves for all mechanical piping except rain leaders, sanitary waste, and vents. E. Adequately sleeve pipe passing through concrete or masonry walls or concrete slabs to receive both pipe and insulation pertaining thereto. Linx. F. Waterproof sleeves shall be Thunderline Link-Seal or Calpico Sealing G. Seal pipes passing through walls or slabs. Use mastic or oakum seal in the annular space in non-fire-rated walls. H. Insulated pipe shall be insulated in sleeves, sealed, and pointed as above. I. Install sleeves on pipes as they are being hung, ready for proper placement in wall as wall is being constructed.
9 J. Where sleeves have been inadvertently omitted in concrete floors, provide requisite pipe opening by using properly sized diamond core drills. Areas located below drilling operations shall be protected from possible damage EXPANSION COMPENSATORS A. Provide expansion compensators where piping crosses new construction expansion joints. B. Provide flexible duct connections at the same points of cross-over specified for piping. Refer to Section **END OF SECTION**
E. Manufacturers Standardization Society of the Valve and Fittings Industry:
SECTION 230529 - HANGERS AND SUPPORTS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment curbs. 6. Sleeves. 7. Mechanical
More informationSECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
SECTION 220529 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Steel pipe hangers and supports. 2. Metal framing systems. 3. Thermal-hanger shield inserts. 4. Fastener systems.
More informationSECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT
SECTION 230548 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Elastomeric Isolation pads. 2. Elastomeric Isolation mounts. 3. [Freestanding] [Restrained] [Freestanding and restrained]
More information1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.
SECTION 260529 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases. 1.2
More informationSECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS. 1. Hangers and supports for electrical equipment and systems.
SECTION 26 05 29 HANGERS AND SUPPORTS FOR PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Hangers and supports for electrical equipment and systems. 1.2 DEFINITIONS A. EMT: Electrical
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 22 1319 - SANITARY WASTE PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSmarter. Safer. Leaner.
Smarter. Safer. Leaner. Fast Installation and Removal Decrease Leading Edge Exposure by 87% OSHA Compliant Versatile and Reusable Use Perimeter Protection Posts During Construction: At Building Perimeter
More informationSECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-13 48 00.00 10 (October 2007) ---------------------------------- Preparing Activity: USACE Superseding UFGS-13 48 00.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationFig. 1 - Standard Clevis Hanger
Revision 10/24/2007 Fig. 1 - Standard Clevis Hanger Component of State of California OSHPD Approved Seismic Restraints System Size Range Size 1/2" thru 36" pipe. Function Recommended for the suspension
More informationSECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:
SECTION 16130 (Master Template Final-05) ELECTRICAL BOXES PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide boxes for electrical equipment and wiring devices as follows: 1. Wall and ceiling outlet boxes.
More informationSECTION VIBRATION ISOLATION FOR PLUMBING PIPING AND EQUIPMENT
SECTION 220550 - VIBRATION ISOLATION FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL REQUIREMENTS 1.1 SUMMARY A. It is the intent of this specification to provide vibration isolation supports for Plumbing
More informationSECTION SEISMIC CONTROL OSHPD
SECTION 01451 PART 1 - GENERAL 1.01 DESCRIPTION A. Provide all required seismic restraints and calculations in order to insure that the installation of all architectural, mechanical, and electrical equipment/components
More informationThis product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.
Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral
More informationSECTION DRAINAGE AND VENT SYSTEMS CONSTRUCTION STANDARD
PART 1: GENERAL 1.01 The design guidelines contained herein include the requirements for drainage and vent systems utilized at The University of Texas at Austin. It is the intention of this document to
More informationMaterials Carbon Steel and Malleable Iron are used in the manufacture of concrete inserts. Stainless Steel and other materials are available.
Concrete inserts offered in this section are designed to provide a pre-set support point in concrete ceilings, walls, and floors. A range of inserts with varying design loads are available. Materials Carbon
More informationTRADE OF Pipefitting PHASE 2 Module 4 Pipe Installation UNIT: 4 Bracket Fabrication
TRADE OF Pipefitting PHASE 2 Module 4 Pipe Installation UNIT: 4 Produced by In cooperation with subject matter expert: Finbar Smith SOLAS 2014 Table of Contents Unit Objective... 1 Learning Outcome...
More informationSECTION ACOUSTICAL PANEL CEILINGS
SECTION 095113 ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationBEARING METAL STUD FRAMING
L-1 Section 05410 Long Form Specification LOAD BEARING METAL STUD FRAMING This section includes axially loaded steel studs, with unique slotted top channels, usually of 0.91, 1.2 and 1.5 mm (16, 18, or
More informationStructural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)
Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 22 1316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationSECTION PLUMBING PIPING SYSTEMS
SECTION 15300 PLUMBING PIPING SYSTEMS PART 1 - GENERAL 1.01 SPECIAL NOTICE A. Each contractor shall read all relevant documents, become familiar with the job, the scope of work, type of general construction,
More informationSECTION PLATE CONNECTED WOOD TRUSSES
SECTION 06173 PLATE CONNECTED WOOD TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Shop fabricated wood trusses for roof and floor framing. 2. Bridging, bracing, and anchorage. B. Related Sections:
More informationDesign & Construction Standards, Revised January
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationKINETICS Pipe & Duct Seismic Application Manual
QUICK START READ ME FIRST I1.1 Seismic Restraint Categories and Types: Seismic restraints for pipe and duct are generally separated into to two categories. 1. Transverse Seismic Restraints: These act to
More informationMASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING
SECTION 221316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following soil and waste, sanitary drainage and vent piping inside the building: 1. Pipe, tube,
More informationSECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and
More informationSECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS
SECTION 270528 PATHWAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Communications equipment coordination and installation. 2. Sleeves for pathways and cables. 3. Raceway
More informationSECTION I -- IRONWORK
SECTION I -- IRONWORK CONTENTS PAGE 1. GENERAL... I-2 1.1. Introduction... I-2 2. REQUIREMENTS... I-2 2.1. General... I-2 2.2. Auxiliary Framing... I-2 2.3. High Seismic Risk Zone Requirements... I-3 2.4.
More informationSECTION SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS REVISED PART 1 GENERAL 1.1 DESCRIPTION:
SECTION 13 05 41 SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS REVISED 1-25-13 PART 1 GENERAL 1.1 DESCRIPTION: A. Provide seismic restraint in accordance with the requirements of this section
More informationNorthpointe Renovation EPN #1701 F/A Project #17027 September 8, 2017
SECTION 055213 - PIPE AND TUBE RAILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationAnchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi
STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel
More informationTOLCO Fire Protection Support Systems. Pipe Hangers Supports Seismic Bracing. UL Listed FM Approved for Fire Sprinkler Installations
TOLCO Fire Protection Support Systems Pipe Hangers Supports Seismic Bracing UL Listed FM Approved for Fire Sprinkler Installations Revision 12/06/2007 Catalog Forward This catalog has been created with
More informationSECTION FACILITY STORM DRAINAGE
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 22 14 00 Storm drainage systems, including piping and all necessary accessories as designated in this section. 1.2 RELATED WORK A. Penetrations in rated enclosures:
More informationDaytona Beach Pier Building Renovation Jun 2010
SECTION 15150 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationMaterials Carbon Steel is used in the manufacturing of riser and pipe clamps. Stainless Steel and other materials are available.
Pipe clamps offered in this section are designed for support and attachment of pipe to structural members. wide range of pipe clamps are available for various applications. Materials arbon Steel is used
More informationA. Coordinate concrete unit masonry (also termed CMU and block ) work with work before and after, especially:
04222 CONCRETE UNIT MASONRY (UNREINFORCED ONLY) SPECIFIER: Use this section only for UNREINFORCED concrete masonry. Its only reinforcement is in the horizontal joints. It covers ONLY plain blockwork (no
More informationA. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect.
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationFig Beam Clamp Retaining Strap (B-Line B3367)
Fig. 69 - Beam Clamp Retaining Strap (B-Line B3367) Size Range: 3 /8"-16 thru 3 /4"-10 rod 4 (101.6mm) thru 16 (406.4mm) lengths Note: longer lengths are available consult factory Material: Pre-Galvanized
More informationAmerican Metal Specialties, Inc.
American Metal Specialties, Inc. www.cablerailings.com (253) 272-9344 (253) 627-3843 Fax PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 05 73 00 STAINLESS STEEL ORNAMENTAL HANDRAILS AND RAILINGS For best
More informationSECTION CHAIN-LINK FENCES AND GATES 02821/1
SECTION 02821 - CHAIN-LINK FENCES AND GATES 02821/1 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Chain-Link Fences: 2. Gates: horizontal slide or swing. 3. Fences installed where
More informationFACT SHEET #2 DECK INFORMATION
Borough of Doylestown Building and Zoning Department 57 West Court Street, Doylestown, PA 18901 215.345.4140 FACT SHEET #2 DECK INFORMATION BACKGROUND The provisions of the PAUCC. ICC Property Maintenance
More informationSECTION PIPE AND TUBE RAILINGS PART 1- GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY 1.3 PERFORMANCE REQUIREMENTS
SECTION 055213- PIPE AND TUBE RAILINGS PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSeismic Installation Manual
Seismic Installation Manual This manual provides the design strength capacities and installation guidelines for the Restraint systems brace components for use in the design of an overall bracing/restraint
More informationAnvil CSI 3 Part MasterFormat Specifications:
November 2009 Anvil CSI 3 Part MasterFormat Specifications: 23 05 00 Basic Mechanical Methods and Materials 23 05 29 Hangers and Supports 21 11 00 for Fire Protection Systems 22 30 00 for Plumbing Systems
More informationRoof Replacement. Notes: T-1 (Title Sheet) Roof Key Plan Russell House Student Union 1400 Greene Street Columbia, South Carolina 29208
Notes: Drawing Index T-1 Title R-1 Roof Plan - Existing Conditions R-2 Roof Plan - New D-1 Roof Details D-2 Roof Details D-3 Roof Details M-1 Mechanical - Roof Plan M-2 Mechanical - Details Roof Key Plan
More information5. AMCA 301 Method of Publishing Sound Ratings for Air Moving Devices. 6. AMCA 500 Test Methods for Louver, Dampers, and Shutters
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationSECTION GYPSUM BOARD ASSEMBLIES
SECTION 09 21 16 GYPSUM BOARD ASSEMBLIES PART 1 GENERAL 1.1 SECTION INCLUDES A. Metal stud wall and ceiling framing, 20 gauge. B. Metal channel suspended ceiling framing. C. Gypsum board. D. Gypsum sheathing.
More informationSECTION GYPSUM BOARD
SECTION 09250 GYPSUM BOARD PART 1GENERAL 1.1 SUMMARY A. Related Documents: General and Supplementary Conditions of the Contract, Division 1 - General Requirements, and Drawings are collectively applicable
More informationAdministrative Changes
Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings
More informationSECTION ALUMINUM GATES
P.O. Box 1058 370 South Athol Rd. Athol, Massachusetts 01331 Phone: (978) 249-7924 Fax: (978) 249-3072 SECTION ALUMINUM GATES PART 1 GENERAL 1.01 SCOPE OF WORK A. The CONTRACTOR shall furnish all labor,
More informationIndustry Standard Terms & Definitions Of The Steel Deck Institute
Industry Standard Terms & Definitions Of The Steel Deck Institute A specialized set of jargon to describe common terms used by manufacturers and other professionals associated with the usage of Steel Deck
More informationGUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION REROOFING ADJUSTABLE FRAMING SYSTEM
- --- -- ----..-------~------------------------------------ GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION 07415 REROOFING ADJUSTABLE FRAMING SYSTEM PART 1 - GENERAL 1.01 SCOPE A.
More informationSECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS
SECTION 08 32 20 CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,
More informationEXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board. 1.2 RELATED WORK A. Installation of steel framing members for walls, partitions,
More informationDARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES
SECTION 15420 DRAINAGE AND VENT SYSTEMS PART 1 DESIGN DIRECTIVES 1.1 DESIGN CRITERIA A. All cleanouts above finished (accessible and non-accessible) ceilings shall be extended to the floor above. B. Do
More informationSECTION BASIC ELECTRICAL MATERIALS AND METHODS
SECTION 26 05 05 BASIC ELECTRICAL MATERIALS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the limited scope construction materials and methods for application with electrical installations as follows:
More informationDivision 11 - Equipment Section 11401
PART 1 - GENERAL 1.1 GENERAL A. Division 1 General Requirements applies and becomes a part of this Section of the Specification as fully as if repeated herein. B. Items of equipment which are included
More informationCITY OF BRISTOL DECK CONSTRUCTION GUIDE ACCORDING TO THE 2012 IRC WITH THE 2016 CT AMMENDMENTS
CITY OF BRISTOL DECK CONSTRUCTION GUIDE ACCORDING TO THE 2012 IRC WITH THE 2016 CT AMMENDMENTS To construct an attached deck in to a residential home in the City of Bristol, you must provide the following:
More informationThe better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs
The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs November 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements....................................
More informationSECTION VIBRATION ISOLATION AND SEISMIC RESTRAINT
SECTION 15200 VIBRATION ISOLATION AND SEISMIC RESTRAINT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division
More informationFEDERAL EMERGENCY MANAGEMENT AGENCY FEMA 414/January 2004 INSTALLING SEISMIC RESTRAINTS FOR DUCT AND PIPE
FEDERAL EMERGENCY MANAGEMENT AGENCY FEMA 414/January 2004 INSTALLING SEISMIC RESTRAINTS FOR DUCT AND PIPE Notice: This guide was prepared by the Vibration Isolation and Seismic Control Manufacturers Association
More informationPIPE AND TUBE RAILINGS
SECTION 05521 - PIPE AND TUBE RAILINGS PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationAND ACCESSORIES FOR DRYWALL CONSTRUCTION
STEEL TRIMS AND ACCESSORIES FOR DRYWALL CONSTRUCTION Quality in your corner. THE STRENGTH WITHIN MONTREAL TORONTO CALGARY EDMONTON VANCOUVER STEEL TRIMS AND ACCESSORIES for Construction BAILEY HAS YOUR
More informationSECTION HVAC DUCTS AND CASINGS
SECTION 23 31 00 HVAC DUCTS AND CASINGS PART 1 -GENERAL 1.1 SUMMARY A. Section includes metal ductwork, nonmetallic ductwork, casing and plenums, buried ductwork, kitchen hood ductwork, duct cleaning.
More informationMETAL HANDRAILS AND RAILINGS. A. Properly identified manufacturer's literature, including shop and erection drawings before starting work.
SECTION 05520 METAL HANDRAILS AND RAILINGS PART 1 GENERAL 1.01 SUBMITTALS A. Properly identified manufacturer's literature, including shop and erection drawings before starting work. B. Railing Assemblies
More informationDIVISION 03 CONCRETE SPECIFICATION : FORMS AND FORMWORK
DIVISION 03 CONCRETE SPECIFICATION 031000: FORMS AND FORMWORK PART 1.0 GENERAL 1.1 DESCRIPTION The work of this specification includes furnishing of all labor, materials, equipment and incidentals to install,
More informationSECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)
SECTION 13125 ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationA. Codes and Standards that are Standards at the University. A. Provide floor drains in all toilet rooms, janitor closets, and mechanical rooms.
PART 1: GENERAL 1.01 Purpose A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationSECTION CHAIN LINK FENCES AND GATES (GALVANIZED) A. Fence framework, fabric, gates, and accessories.
SECTION 02830 CHAIN LINK FENCES AND GATES (GALVANIZED) 1.0 GENERAL 1.1 Section Includes A. Fence framework, fabric, gates, and accessories. B. Excavation for post bases; concrete footing for posts. C.
More informationA. Access doors and frames are part of an access door and frame allowance.
SECTION 08 31 13 ACCESS DOORS AND FRAMES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationPATHWAYS FOR COMMUNICATIONS SYSTEMS
270528 PATHWAYS FOR PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment for the complete installation of work called for in the Contract Documents. 1.2 SCOPE OF WORK A. This
More informationPOST FRAME BUILDING STANDARDS
CASS COUNTY, MISSOURI BUILDING CODES, ENVIRONMENTAL HEALTH AND ZONING DEPARTMENT 30508 S. West Outer Road, Harrisonville, MO 64701 P- (816) 380-8134 F- (816) 380-8130 POST FRAME BUILDING STANDARDS 201.3
More informationShaftwall and Area Separation Wall Systems.
Shaftwall and Area Separation Wall Systems www.marinoware.com Marino\WARE S Fire Rated Wall Systems Quality that takes you to the top. Marino\WARE created its CT Shaftwall System, to be a flexible shaftwall
More informationSECTION VALVES, HANGERS, AND SPECIALTIES
SECTION 15515 VALVES, HANGERS, AND SPECIALTIES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15090 - Supports, Anchors, and Seals. 2. 15410 - Piping (Plumbing). 3. 15510 - Piping (HVAC). 4. 15540
More informationAluminum Component Pipe Railings
1 SECTION 05 7360 ALUMINUM COMPONENT PIPE RAILINGS PART 1 GENERAL 1.01 SECTION INCLUDES A. Aluminum component pipe handrails and railings. 1.02 RELATED REQUIREMENTS A. Section 02 9000: Landscaping: Installation
More information2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING
2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING E3305.3: now reads The space equal to the width and depth of the panelboard and extending
More informationDocument number CURTAIN FIRE DAMPERS
Document number 481324 CURTAIN FIRE DAMPERS DFD, DFD-150X, FD, FD-150X, SSDFD, SSFD, AND KFD Series 1 1 2 and 3 Hour Curtain Fire s Vertical and Horizontal Mount Installation, Operation and Maintenance
More informationSECTION MANUFACTURED ROOF EXPANSION JOINTS
SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.
SECTION 05720 ORNAMENTAL ALUMINUM RAILING ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products. This section is based on the products of Superior Aluminum Products,
More informationJC Code & Construction Consultants, Inc. Advanced Training: The FBC & ASTM C 1063
JC Code & Construction Consultants, Inc. Advanced Training: The FBC & ASTM C 1063 1 Welcome! This course was developed by : JC Code & Construction Consultants, Inc. DBPR Provider Number 0003379 www.jccode.com
More informationRISER DETAIL NTS SHANNON FIRE PROTECTION, LLC SCALE: 3/32" = 1'-0"
MAXIMUM DISTANCE BETWEEN HANGERS NOMINAL PIPE SIZE (in.) 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 3-1/2" 4" 5" 6" 8" STEEL PIPE EXCEPT THREADED LIGHTWALL THREADED LIGHTWALL STEEL PIPE COPPER TUBE 10-0 10-0 CPVC
More informationWall Panels. Structural wall panel. Architectural wall panel. Cladding wall panel. Sandwich wall panel
Wall Panels Structural wall panel Architectural wall panel Cladding wall panel Sandwich wall panel Wall Panels Assorted styles and colours Reveals and other patterns Painted finish Bolted, welded and knife
More informationZS880 Linear Shower Drain Installation Instructions
Introduction PATENT PENDING The Zurn ZS880 Stainless Steel Linear Shower Drain incorporates a simple approach to bathroom shower design, when compared to traditional point-drain applications. The linear
More informationLouis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1
Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions
More informationFLUID APPLIED WATERPROOFING
SECTION 07120 FLUID APPLIED WATERPROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 03300 - Cast-In-Place Concrete. 2. 09200 - Metal Studs, Metal Lath, Suspension Ceilings, Plaster, and Stucco.
More informationCHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION
CHAPTER 26 PLASTIC SECTION BC 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic
More informationMaterials Carbon Steel is used in the manufacturing of riser and pipe clamps. Stainless Steel and other materials are available.
Pipe clamps offered in this section are designed for support and attachment of pipe to structural members. wide range of pipe clamps are available for various applications. Materials arbon Steel is used
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationSection SECTIONAL INSULATED STEEL DOORS
1 GENERAL 1.1 GENERAL REQUIREMENTS General Conditions and Division 01 apply to this section. 1.2 RELATED WORK Section 05500: Miscellaneous Metal Fabrication Section 07900: Joint Sealers Section 09900:
More informationRIGID LIFELINES PRODUCT SPECIFICATIONS 1
RIGID LIFELINES PRODUCT SPECIFICATIONS 1 This guide can be used to prepare a bid specification for the incorporation of a Ceiling-Mounted Monorail Anchor Track System into a competitive bid project or
More information. 1.2 APPLICABLE PUBLICATIONS
SECTION 237000 - PART 1 - GENERAL 1.1 PIPING SYSTEM STANDARDS OF MATERIALS A. Piping and fitting materials shall conform to the specification standards of the recognized authorities listed below. References
More information151 First Side. Technical Assignment 2 November 16 th, William J. Buchko. AE 481w Senior Thesis The Pennsylvania State University
November 16 th, 2007 William J. Buchko AE 481w Senior Thesis The Pennsylvania State University Thesis Advisor: Kevin Parfitt Table of Contents Executive Summary... 3 Structural System Overview Foundation...
More informationInspection of New One- and Two- Family Dwellings
Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Inspection of New One- and Two- Family Dwellings Planning and Development
More informationDRAINS AND CLEANOUTS. 1. Division 7 - Thermal and Moisture Protection Piping (Plumbing).
SECTION 15421 DRAINS AND CLEANOUTS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. Division 7 - Thermal and Moisture Protection. 2. 15410 - Piping (Plumbing). 1.02 SUBMITTALS A. Product Data: Submit
More informationProject Address: Name of Person Completing Form:
Statement of Inspections This form is provided as a way to list aspects of the project that require special inspection and testing in accordance with IBC Sections 107.1, 1704, and 1705 and define duties
More informationSCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC Permit Requirements
SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC. 320-226.5189 www.101developmentresources.com While every attempt has been made to insure the correctness of this handout, no guarantees are made to its accuracy
More informationPASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017
SECTION 10505 - METAL STUDENT LOCKERS PART 1 - GENERAL 1.01 SCOPE OF WORK A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationTHE WORLD LOOKS UP TO COMPOSITE ELEVATED TANK
THE WORLD LOOKS UP TO COMPOSITE ELEVATED TANK or our breadth of capability. Of all the storage tank manufacturers doing business today, no other offers Caldwell s range of capability. We are the only manufacturer
More informationSuspension Systems for Acoustical Lay-in Ceilings Seismic Design Categories D, E & F
NWCB Technical Document SUSPENDED CEILINGS 401 Suspension Systems for Acoustical Lay-in Ceilings Seismic Design Categories D, E & F 10/09 This document has been revised based on current Building Code standards.
More information