6300 Enterprise Ln Madison, WI

Size: px
Start display at page:

Download "6300 Enterprise Ln Madison, WI"

Transcription

1 6300 Enterprise Ln Madison, WI Installation Instructions For Attachment of Exterior Wall Coverings Through GreenGuard Insulation Board (CM, SL) and Insulative Sheathing Products (CM, SLX, PLYGOOD, PLYGOOD Ultra) to Wood or Steel Wall Framing

2 GreenGuard Insulation Boards and Insulated Sheathing Products: Are made of Extruded Polystyrene (XPS) conforming to ASTM C578 Come in many thicknesses to accommodate almost any end use.

3 GreenGuard Insulation Boards and Insulated Sheathing Products: Exterior wall coverings are attached directly through the FPIS into the framing or to furring attached through the FPIS to framing. Shall be installed in accordance with: Code compliance requirements per TER XXXX-XX Jobsite package found at com

4 Step 1: Verify FPIS and Framing FPIS must have min compressive strength of 15 psi Must comply with ANSI/SBCA FS100 where wind pressure resistance is required ASTM D 1621 Note: Wind speeds shown in Table 1 are V ASD. Where V ULT is used, multiply wind speeds by a factor of 1.26 _ + _

5 Step 1: Verify FPIS and Framing Wood framing may be any softwood species with specific gravity 0.42 or higher Steel framing must be: Thickness Minimum F b 33 mil, 43 mil 33 ksi 54 mil 50 ksi

6 Step 2: Verify Fasteners Exterior coverings may be attached by the following methods: (a) Cladding (b) Fasteners (c) Furring (d) FPIS (e) Framing (f) Cavity Insulation (g) Interior wall finish (a) (d) (a) (c) (d) Direct Attachment Attachment through Furring (b) (b) (e) (f) (g) (e) (f) (g)

7 Step 2: Verify Fasteners Fasteners must meet penetration requirements per IRC Table R703.3(1) into: Studs Framing members Where penetration into framing is not required, fasteners must extend ¼ beyond the opposite face of the sheathing per IRC Table R ¼ min or per manuf. instructions 1/4 min

8 Step 3: Place Insulation Boards Ensure wall is square and true Align boards with bottom edge of wall

9 Step 3: Place Insulation Boards Verify stud spacing, blocking, and bracing requirements with manufacturer. Provide framing or blocking for attachment of siding and trim at transitions Seams should not be visible from interior unless allowed by manufacturer.

10 Step 4: Attach Insulation Boards Attach boards with fasteners* at 16 o.c around the perimeter of the wall and along vertical framing members. Min ¾ penetration into sheathing Do not overdrive nails Repair damaged areas with GreenGuard Contractor Sheathing/Housewrap Tape 16 o.c. max * Use 1½ ring shank nails with a 1 diameter plastic cap only

11 Step 4: Attach Insulation Boards Drive nails flush and snug Do not overdrive nails Do not underdrive nails Exception: Leave 1/32 gap to allow for lengthwise thermal expansion of vinyl or aluminum siding

12 Step 5: Trim Boards at Openings Trim boards at all window and door openings Cover all framing with FPIS Fit joints tightly Greenguard Continuous Insulation

13 Step 6: WRB and Flashing Ensure that a codecompliant water resistive barrier (WRB) and required flashing is provided If using FPIS as a WRB: Seal all joints and openings and penetrations GreenGuard Continuous Insulation

14 Step 6: WRB and Flashing Seal all seams with GreenGuard Contractor Sheathing/Housewrap Tape or GreenGuard Flashing (minimum 2 inch wide strips) Alternatively, a Z-furring horizontal seam treatment may be constructed using 16 wide strips of GreenGuard Housewrap sealed to the boards as shown on right Note: If GreenGuard is installed over an existing exterior wall where cladding is not removed, no additional WRB is needed. Omit steps 5-6.

15 Step 6: WRB and Flashing Typical Window Installation: 1. First, install sill flashing 2. Next, install window in accordance with window manufacturer s instructions 3. Then, install jamb flashing overlapping the sill flashing 4. Finally, install head flashing overlapping the jamb flashing. For additional window flashing options, refer to the GreenGuard Residential Installation Guide 1 2 Use one of the following products: GreenGuard Flashing GreenGuard Butyl Flashing GreenGuard SuperStretch (self-adhering) 3 4

16 Step 6: WRB and Flashing Repair damaged areas per manufacturer s instructions

17 Jobsite Safety Information IMPORTANT - PLEASE REVIEW The handling, storing, installing and temporary bracing of walls requires specialized training, clearly implemented procedures, and careful planning and communication among the contractor and installation crew. Handling and installing walls without appropriate training, planning and communication greatly increases the probability of an accident resulting in property damage, serious personal injury and/or death. Prior to wall installation, the documents should be examined and disseminated to all appropriate personnel, in addition to proper training and a clear understanding of the installation plan, any applicable fall protection requirements, and the intended temporary wall bracing requirements. Examine the building s foundation and related installation conditions. Begin wall installation only after any unsatisfactory conditions have been corrected. Do not cut, drill, notch or otherwise alter the walls beyond the limitations specified in the building code. Report any damage before installation. The information below is offered as minimum guidelines only. Nothing contained in this jobsite package should be construed in any manner as expanding the scope of responsibility of, or imposing any additional liabilities on. To print copies of this information, download pdfs at bottom of page.

18 Wall panels are generally not marked in any way to identify the frequency or location of out-ofplane temporary diagonal bracing. Follow the recommendations for handling, installing and temporary bracing provided in this document or by the building designer. All permanent bracing design is the responsibility of the building designer. This document is intended for typical installation conditions. The contractor is responsible for ensuring the appropriateness of any bracing strategy and quality of installation. Disregarding handling, installing and bracing safety recommendations is the major cause of wall panel installation accidents. Ignoring an unsafe condition or action greatly increases the probability of an accident resulting in property damage, serious personal injury and/or death. Wear personal protective equipment for the eyes, feet, hands and head when working with wall panels. walking on stacks. Stacks of wall and building materials may be unstable and/or slippery. Avoid

19 Avoid bending wall out-of-plane. The contractor is responsible for properly receiving, unloading and storing the wall panels at the jobsite. Unload wall panels carefully to smooth surface to prevent damage. Wall panels may be unloaded directly on the ground at the time of delivery or stored temporarily in contact with the ground after delivery. If wall panels are to be stored for more than one week, place blocking of sufficient height beneath the stack at 8 to 10 on center and cover stacks to protect from the environment but allow for ventilation. If bundles of wall panels are stacked, support and separate bundles with wood blocks spaced 8 to 10 apart. Keep wood blocks aligned vertically. Limit stack heights to no more than 10. Wall panels that are delivered with the windows already installed must be stored vertically. Properly brace wall panels to prevent tipping or toppling. Use caution if handling and installing walls and wall panels by hand as panels can be heavy and awkward. If a forklift is used to move walls and wall panels, set forks at wide spacing and use approved extensions to ensure wallk and wall panels are well supported. Always lift walls and wall panels from at least two pick points, spaced far enough apart to ensure panel stability. Reinforce panels in the viccinity of the lifting points, if necessary, to resist hoisting loads. Know the weight of the product being lifted and make sure the capacity of the lifting equipment is adequate to perform the lift. Use special care in windy conditions or near power lines and airports. Use care not to damage walls and wall panels with the forks of the forklift or the

20 rigging/lifting equipment used with cranes. «Previous

21 Temporary bracing and worker safety are the responsibility of the installer. Make sure this information is understood by all persons involved in the installation of walls. Steps to Setting Wall Panels The figures accompanying Steps 1-12 assume that the exterior walls are installed and braced first, followed by the interior walls. Some contractors prefer to install and brace the interior walls before the exterior walls. For wall panels, be sure to coordinate with the wall panel manufacturer which installation sequence is preferred. STEP 1: Start with a foundation that is level and square. If the foundation is not level or square, plan for any adjustments before the wall panels are manufactured, if possible. STEP 2: Be sure the installation crew is familiar with the provisions of: the construction documents (i.e., architectural/structural plans and specifications), this handling, installing and bracing summary sheet, site specific conditions and issues, and OSHA jobsite lifting and fall protection requirements. STEP 3: Verify floor deck or slab dimensions with those provided in the construction documents or on the wall panel placement diagram. Check all floor openings (e.g. stairway, fireplace, etc.). STEP 4: Snap chalk lines at the locations of the walls. STEP 5: For wall panels, write the panel numbers on the floor, in accordance with the wall panel placement diagram, to better identify the location of each wall panel. STEP 6: Set the first two walls and fasten together tightly at the top, middle and bottom of the adjoining studs and attach the bottom plate to the floor per the requirements of the building code or as specified by the building designer. Note: It may be necessary to begin wall placement near the center of a wall line to distribute any dimension discrepancies equally within the wall line.

22 STEP 7: Install temporary bracing as each wall is set but not to exceed the spacing intervals in the table below. Use minimum 2x4 stress graded lumber attached to the wall and floor or ground support with a minimum of 2-16d (0.135x3-1/2 ) nails. Temporary bracing is very important for ensuring stability of the walls as construction proceeds. STEP 8: Continue setting the walls in accordance with the construction documents or wall panel placement diagram. It may be necessary to shim the walls to compensate for deviations in slab or subfloor elevations. If required, be sure to shim for full contact between the wall panel and the slab or subfloor. Adjust fastener size accordingly to ensure adequate attachment of the wall to the floor. If the walls must be racked in order to compensate for a sloping slab or subfloor, the openings will no longer be square. Walls used in long wall lines MUST be butted together tightly to keep the length of the wall line from growing. For wall panels, wall panel manufacturers often compensate for this by undersizing the length of each wall panel by 1/16 to 1/8.

23 STEP 9: Install the upper top plates. STEP 10: Make sure walls are attached to the floor with the required number and type of fasteners and connectors specified in the construction documents. STEP 11: Add bracing (i.e, temporary and permanent) as necessary to maintain wall stability. remove any temporary wall bracing until the building has been closed-in and all permanent bracing has been installed. INSTALLATION TOLERANCES* Wall support conditions (i.e. floor or foundation dimensions) must be accurate to within +/- ½ relative to plan dimensions. Locate walls within +/- ½ of plan dimension. Maximum out-of-plumb of wall is Height/384 (see Table below). *Wall installation tolerances per Model Guidelines for Design, Fabrication and Installation of Engineered Panelized Walls, U.S. Department of Housing and Urban Development, Office of Policy Development and Research. Check with authority having jurisdiction to ensure compliance with the governing building code.

24 Construction loads are those loads imposed on the unfinished building as a result of the construction process. Typical construction loads include the weight of the workers, equipment, and building materials, to name a few. For example, a bundle of plywood sheathing or gypsum board stacked on trusses temporarily creates construction loads. Make sure that the truss assembly is properly restrained and braced according to the guidelines in BCSI-B1*** andbcsi-b2*** before placing any construction loads on them. Construction loads shall only be placed on fully restrained and braced structures. Stacking excessive amounts of construction materials on floor or roof trusses is an unsafe practice. Property damage, personal injury and/or death are possible if this warning is not heeded. Trusses that have been over-stressed due to excessive construction loading will usually show excessive sagging (deflection) and at least a portion of this deflection will remain even after the load has been removed. In more severe cases, broken truss members and/or failed truss joints may result. Construction Loading DO's and DO NOTs exceed stack heights listed in the table.

25 stack materials on unbraced trusses. overload the trusses. distribute loads over as many trusses as possible. Position stacks of materials flat with the longest dimension perpendicular to the trusses, as shown.

26 allow the stack to lean against walls, or stack materials so they overload single or small groups of trusses. stack materials along exterior supports or directly over interior supports of properly restrained and braced structures. stack materials at or near the midspan of the truss. Never exceed stack heights provided in the table above unless alternative information is provided by the Building Designer, Truss Designer or Truss Manufacturer. drop loads on trusses. The impact can damage the trusses even if the load is small. leave construction materials on lifting equipment until installation, if possible.

27 stack materials at locations that will produce instability, such as on cantilevers or near truss-togirder connections. pile cut-off tile and/or other construction waste on trusses. ***Contact the component manufacturer to obtain the referenced document or consult a Registered Design Professional for more information on this subject.

28 cut, drill, notch or otherwise alter the walls beyond the limitations specified in the building code unless such alterations are approved by the building designer. and void. Walls that have been inappropriately altered may render the limited warranties null

29 NOTE: Product manufacturer relies on the presumption that the contractor and crane operator (if applicable) are professionals with the capability to undertake the work they have agreed to do on any given project. If the contractor believes it needs assistance in some aspect of the construction project, it should seek assistance from a competent party. The methods and procedures outlined in this document are intended to ensure that the overall construction techniques employed will put the wall into place SAFELY. These recommendations for handling, installing and temporary bracing the walls are based upon the collective experience of leading personnel involved with wall manufacture and installation, but must, due to the nature of responsibilities involved, be presented only as a GUIDE for use by a qualified building designer or contractor. It is not intended that these recommendations be interpreted as superior to the building designer s design specification for handling, installing and temporary bracing walls and it does not preclude the use of other equivalent methods for bracing and providing stability for the walls, columns, floors, roofs and all the interrelated structural building components as determined by the contractor. Thus, DrJ expressly disclaims any responsibility for damages arising from the use, application, or reliance on the recommendations and information contained herein. Copyright 2013 Structural Building Components Association (SBCA) and DrJ Engineering, LLC. This information is being provided so that jobsite safety information is consistent with SBCA best practices for installation of structural framing materials. Refer to the manufacturer s installation instructions for specific information about installing this product, as well as the Engineered Product Installation Diagram (EPID), which assists the Installer and Building Inspector in properly applying the product to comply with the code.

30 JOBSITE WARNINGS, HANDLING, INSTALLATION & SAFETY INFORMATION IMPORTANT - PLEASE REVIEW WARNING: The handling, storing, installing and temporary bracing of walls requires specialized training, clearly implemented procedures, and careful planning and communication among the contractor and installation crew. Handling and installing walls without appropriate training, planning and communication greatly increases the probability of an accident resulting in property damage, serious personal injury and/or death. Prior to wall installation, the documents should be examined and disseminated to all appropriate personnel, in addition to proper training and a clear understanding of the installation plan, any applicable fall protection requirements, and the intended temporary wall bracing requirements. Examine the building s foundation and related installation conditions. Begin wall installation only after any unsatisfactory conditions have been corrected. Do not cut, drill, notch or otherwise alter the walls beyond the limitations specified in the building code. Report any damage before installation. This information is offered as minimum guidelines only. Nothing contained in this jobsite document should be construed in any manner as expanding the scope of responsibility of, or imposing any additional liabilities on. Throughout this document, the term wall panel(s) refers to either walls built off-site and delivered to the jobsite or walls that are built on-site.

31 GENERAL Wall panels are generally not marked in any way to identify the frequency or location of out-of-plane temporary diagonal bracing. Follow the recommendations for handling, installing and temporary bracing provided in this document or by the building designer. All permanent bracing design is the responsibility of the building designer. This document is intended for typical installation conditions. The contractor is responsible for ensuring the appropriateness of any bracing strategy and quality of installation. Disregarding handling, installing and bracing safety recommendations is the major cause of wall panel installation accidents. Ignoring an unsafe condition or action greatly increases the probability of an accident resulting in property damage, serious personal injury and/or death. Wear personal protective equipment for the eyes, feet, hands and head when working with wall panels. Stacks of walls and building materials may be unstable and/or slippery. Avoid walking on stacks.

32 STORAGE & HANDLING Avoid bending walls out-of-plane. The contractor is responsible for properly receiving, unloading and storing the wall panels built off-site and delivered to the jobsite. Unload wall panels carefully to smooth surface to prevent damage. Wall panels may be unloaded directly on the ground at the time of delivery or stored temporarily in contact with the ground after delivery. If wall panels are to be stored for more than one week, place blocking of sufficient height beneath the stack at 8' to 10' on center and cover stacks to protect from the environment but allow for ventilation. Wall panels built on-site may be stored in the same manner. If bundles of wall panels are stacked, support and separate bundles with wood blocks spaced 8' to 10' apart. Keep wood blocks aligned vertically. Limit stack heights to no more than 10'.

33 STORAGE & HANDLING Wall panels with the windows already installed must be stored vertically. Properly brace wall panels to prevent tipping or toppling. Use caution if handling and installing wall panels by hand as panels can be heavy and awkward. If a forklift is used to move wall panels, set forks at wide spacing and use approved extensions to ensure and wall panels are well supported.

34 GENERAL Always lift wall panels from at least two pick points, spaced far enough apart to ensure panel stability. Reinforce panels in the vicinity of the lifting points, if necessary, to resist hoisting loads. Know the weight of the product being lifted and make sure the capacity of the lifting equipment is adequate to perform the lift. Use special care in windy conditions or near power lines and airports. Use care not to damage wall panels with the forks of the forklift or the rigging/lifting equipment used with cranes.

35 INSTALLATION & TEMPORARY BRACING Temporary bracing and worker safety are the responsibility of the installer. Make sure this information is understood by all persons involved in the installation of wall panels. Steps to Setting Wall Panels The figures accompanying Steps 1-12 assume that the exterior walls are installed and braced first, followed by the interior walls. Some contractors prefer to install and brace the interior walls before the exterior walls. For wall panels built off-site, be sure to coordinate with the wall panel manufacturer which installation sequence is preferred. STEP 1: Start with a foundation that is level and square. If the foundation is not level or square, plan for any adjustments before the wall panels are built or manufactured, if possible.

36 INSTALLATION & TEMPORARY BRACING STEP 2: Be sure the installation crew is familiar with the provisions of: the construction documents (i.e., architectural/structural plans and specifications), this handling, installing and bracing information, site-specific conditions and issues, and OSHA jobsite lifting and fall protection requirements. STEP 3: Verify floor deck or slab dimensions with those provided in the construction documents or on the wall panel placement diagram. Check all floor openings (e.g., stairway, fireplace).

37 INSTALLATION & TEMPORARY BRACING STEP 4: Snap chalk lines at the locations of the walls. STEP 5: For wall panels built off-site, write the panel numbers on the floor, in accordance with the wall panel placement diagram, to better identify the location of each wall panel. STEP 6: Set the first two walls and fasten together tightly at the top, middle and bottom of the adjoining studs, and attach the bottom plate to the floor per the requirements of the building code or as specified by the building designer. Note: It may be necessary to begin wall placement near the center of a wall line to distribute any dimension discrepancies equally within the wall line.

38 INSTALLATION & TEMPORARY BRACING STEP 7: Install temporary bracing as each wall is set but not to exceed the spacing intervals in the table below. Use minimum 2x4 stress-graded lumber attached to the wall and floor or ground support with a minimum of 2-16d (0.135x3 1 / 2 ") nails. Temporary bracing is very important for ensuring stability of the walls as construction proceeds.

39 INSTALLATION & TEMPORARY BRACING STEP 8: Continue setting the walls in accordance with the construction documents or wall placement diagram. It may be necessary to shim the walls to compensate for deviations in slab or subfloor elevations. If required, be sure to shim for full contact between the wall and the slab or subfloor. Adjust fastener size accordingly to ensure adequate attachment of the wall to the floor. If the walls must be racked in order to compensate for a sloping slab or subfloor, the openings will no longer be square. Wall panels used in long wall lines MUST be butted together tightly to keep the length of the wall line from growing. Wall panel manufacturers often compensate for this by undersizing the length of each wall panel by 1 /16" to 1 /8".

40 INSTALLATION & TEMPORARY BRACING STEP 9: Install the upper top plates. STEP 10: Make sure walls are attached to the floor with the required number and type of fasteners and connectors specified in the construction documents. STEP 11: Add bracing (i.e., temporary and permanent) as necessary to maintain wall stability. remove any temporary wall bracing until the building has been closed in and all permanent bracing has been installed.

41 INSTALLATION & TEMPORARY BRACING INSTALLATION TOLERANCES* Wall support conditions (i.e., floor or foundation dimensions) must be accurate to within +/- ½" relative to plan dimensions. Locate walls within +/- ½" of plan dimension. Maximum out-of-plumb of wall is Height/384 (see table below). *Wall installation tolerances per Model Guidelines for Design, Fabrication and Installation of Engineered Panelized Walls, U.S. Department of Housing and Urban Development, Office of Policy Development and Research. Check with authority having jurisdiction to ensure compliance with the governing building code.

42 CONSTRUCTION LOADING Construction loads are those loads imposed on the unfinished building as a result of the construction process. Typical construction loads include the weight of the workers, equipment, and building materials, to name a few. For example, a bundle of plywood sheathing or gypsum board stacked on trusses temporarily creates construction loads. Make sure that the floor assembly is properly restrained and braced according to the building code, building designer s plans and specs and/or the guidelines in BCSI-B1***, BCSI-B2***, and Guide for Handling, Installing, Restraining & Bracing of Engineered Wood Products before placing any construction loads on any floor system. Construction loads shall only be placed on sheathed or fully restrained and braced structures. Stacking excessive amounts of construction materials on any floor or roof structural elements (e.g., trusses) is an unsafe practice. Property damage, personal injury and/ or death are possible if this warning is not heeded. Floor or roof structural elements (e.g., trusses, joists or rafters) that have been over-stressed due to excessive construction loading will usually show excessive sagging (deflection), and at least a portion of this deflection will remain even after the load has been removed. In more severe cases, broken members and/or failed connections may result.

43 CONSTRUCTION LOADING Construction Loading DOs and DO NOTs exceed stack heights listed in the table.

44 CONSTRUCTION LOADING stack materials on unbraced structural elements (e.g., trusses, joists or rafters). overload the structural elements (e.g., trusses, joists or rafters). distribute loads over as many structural elements as possible. Position stacks of materials flat with the longest dimension perpendicular to the structural elements, as shown. allow the stack to lean against walls, or stack materials so they overload single or small groups of structural elements.

45 CONSTRUCTION LOADING stack materials along exterior supports or directly over interior supports of properly restrained and braced structures. stack materials at or near the midspan of the structural element. Never exceed stack heights provided in the table unless alternative information is provided by the Building Designer, Truss Designer or Truss Manufacturer. drop loads on structural elements. The impact can damage the structural elements even if the load is small.

46 CONSTRUCTION LOADING leave construction materials on lifting equipment until installation, if possible. stack materials at locations that will produce instability, such as on cantilevers or near girder, beam and header connections. pile cut-off tile and/or other construction waste on trusses. ***Contact the component manufacturer to obtain the referenced document or consult a Registered Design Professional for more information on this subject.

47 ALTERATIONS cut, drill, notch or otherwise alter the walls beyond the limitations specified in the building code unless such alterations are approved by the building designer. Walls that have been inappropriately altered may render the limited warranties null and void.

48 NOTE Product manufacturers rely on the presumption that the contractor and crane operator (if applicable) are professionals with the capability to undertake the work they have agreed to do on any given project. If the contractor believes it needs assistance in some aspect of the construction project, it should seek assistance from a competent party. The methods and procedures outlined in this document are intended to ensure that the overall construction techniques employed will put the wall into place SAFELY. These recommendations for handling, installing and temporary bracing the walls are based upon the collective experience of leading personnel involved with wall manufacture and installation, but must, due to the nature of responsibilities involved, be presented only as a GUIDE for use by a qualified building designer or contractor. It is not intended that these recommendations be interpreted as superior to the building designer s design specification for handling, installing and temporary bracing walls and it does not preclude the use of other equivalent methods for bracing and providing stability for the walls, columns, floors, roofs and all the interrelated structural building components as determined by the contractor. Thus, DrJ expressly disclaims any responsibility for damages arising from the use, application, or reliance on the recommendations and information contained herein Structural Building Components Association (SBCA) and DrJ Engineering, LLC. This information is being provided so that jobsite safety information is consistent with SBCA best practices for installation of structural framing materials. Refer to the manufacturer s installation instructions for specific information about installing this product, as well as the Installation Guide, which assists the Installer and Building Inspector in properly applying the product to comply with the code.

TER No Cultured Stone & ProStone Applications Over Continuous Insulation

TER No Cultured Stone & ProStone Applications Over Continuous Insulation Cultured Stone & ProStone Applications Over Continuous Insulation TER No. 1302-01 Boral Stone Products LLC 200 Mansell Court East, Suite 310 Roswell, GA 30076 419-318-5345 949-341-8890 (fax) chris.hines@boral.com

More information

Temporary Construction Loads Over I-Joist Roofs And Floors

Temporary Construction Loads Over I-Joist Roofs And Floors T E C H N I C A L N O T E Temporary Construction Loads Over I-Joist Roofs And Floors Number J735C July 2012 During construction of light-frame structures it is common to see relatively heavy loads placed

More information

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel

More information

HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT

HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT SAMPLE GUIDE FOR RESIDENTIAL DECKS revised 7 16 Call before you dig! 1 800 272 1000 New Jersey One Call. Utility Mark Out. THIS GENERIC GUIDE IS NOT ALL INCLUSIVE

More information

Guide to Attaching Exterior Wall Coverings through Foam Sheathing to Wood or Steel Wall Framing

Guide to Attaching Exterior Wall Coverings through Foam Sheathing to Wood or Steel Wall Framing Guide to Attaching Exterior Wall Coverings through Foam Sheathing to Wood or Wall Framing Released September 20, 2010 Updated December 4, 2012 Note: Tables for cladding attachments to wood framing have

More information

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs November 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements....................................

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 6587 (562) 699 0543 www.icc es.org ESR 3152 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00

More information

REPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION

REPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3914 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 07 00

More information

Open-Web Truss Long Span Installation Guidelines

Open-Web Truss Long Span Installation Guidelines TECHNICAL BULLETIN #301 Open-Web Truss Long Span Installation Guidelines RedBuilt has maintained a policy of manufacturing and marketing products of the highest quality to our customers. We guarantee the

More information

One and Two Family Additions

One and Two Family Additions One and Two Family Additions An addition to a house, duplex, garage, or an accessory structure requires a building permit prior to performing any construction. Building Department & Permit Office Mon-Fri

More information

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses Released May 20, 2009 Updated March 9, 2011 Introduction: Wood frame structures with attached brick masonry veneer

More information

Gold Bond BRAND Gypsum Sheathing

Gold Bond BRAND Gypsum Sheathing BRAND 09 06 29 16 00/NGC 43/NGC brand is a moisture-resistant sheathing installed on the outside of exterior framing as a substrate for exterior claddings. It is manufactured with a treated water-resistant

More information

INSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT

INSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT INSULATION RETROFIT DESIGN ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT MAY 2009 prepared by N. A. JACOBSEN, P.Eng. CIVIL ENGINEERING CONSULTANT Whitehorse, Yukon ENERGY SOLUTIONS CENTRE YUKON GOVERNMENT MAY

More information

NOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION. MASTERFORMAT SECTION (Mortarless Concrete Brick Veneer)

NOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION. MASTERFORMAT SECTION (Mortarless Concrete Brick Veneer) NOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION MASTERFORMAT SECTION 04818 (Mortarless Concrete Brick Veneer) Spec_USA_En_18102005.doc 12/1/2005 Novabrik Page 2 Section 04818 NOVABRIK MORTARLESS

More information

YOUR LITE-DECK SECTIONS

YOUR LITE-DECK SECTIONS General Information Warning - Serious injury or death may result from safety hazards caused by improper use or installation. When in doubt about proper use or installation of Lite-Deck, immediately contact

More information

General. Moisture. Secondary Water-Resistive Barrier. Storage. Gaps & Sealants. Stud Spacing. Flashing, Windows, Doors & Openings

General. Moisture. Secondary Water-Resistive Barrier. Storage. Gaps & Sealants. Stud Spacing. Flashing, Windows, Doors & Openings application instructions STRAND SUBSTRATE 38, 76 AND 190 SERIES PRIMED PANEL SIDING INCLUDING SILVERTECH & SMARTFINISH General At the time of manufacture, siding meets or exceeds the performance standards

More information

Administrative Changes

Administrative Changes Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings

More information

SECTION PLATE CONNECTED WOOD TRUSSES

SECTION PLATE CONNECTED WOOD TRUSSES SECTION 06173 PLATE CONNECTED WOOD TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Shop fabricated wood trusses for roof and floor framing. 2. Bridging, bracing, and anchorage. B. Related Sections:

More information

4 EXTREME FOUNDATION PANELS

4 EXTREME FOUNDATION PANELS 4 EXTREME FOUNDATION PANELS For House Crawl Space On Concrete Footings 1. The type of soil is a factor in determining foundation construction details such as footing design, backfill, and drainage provisions.

More information

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)

On Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866) TECHNICAL NOTE On Cold-Formed Steel Construction $5.00 Light Gauge Steel Engineers Association Washington, D.C. 20005 Toll Free (866) 465-4732 www.lgsea.com DESIGN OF BY-PASS SLIP CONNECTORS IN COLD-FORMED

More information

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PARKLEX USA

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PARKLEX USA 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3462 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 07 00

More information

Chapter 7. Roof Framing

Chapter 7. Roof Framing Chapter 7. Roof Framing 7.1 ROOFING PREP WORK 7.2 INSTALLING ROOF TRUSSES 7.3 INSTALLING PORCH TRUSSES 7.4 SHEATHING ROOF 7.5 INSTALLING SUB-FASCIA 7.6 BUILDING AND INSTALLING SCUTTLE BOX 7.7 INSTALLING

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1780 Reissued 11/2017 This report is subject to renewal 11/2019. DIVISION: 06 00

More information

BEARING METAL STUD FRAMING

BEARING METAL STUD FRAMING L-1 Section 05410 Long Form Specification LOAD BEARING METAL STUD FRAMING This section includes axially loaded steel studs, with unique slotted top channels, usually of 0.91, 1.2 and 1.5 mm (16, 18, or

More information

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3089 Reissued 07/2016 This report is subject to renewal 07/2018. DIVISION: 07 00

More information

2003 International Residential Building Code

2003 International Residential Building Code 2003 International Residential Building Code Section R305 Ceiling Height Habitable rooms, hallways, corridors, bathrooms, toilet rooms, laundry rooms and basements shall have a ceiling height of not less

More information

LP SmartSide Perfection Shingle

LP SmartSide Perfection Shingle Application Instructions Fiber Substrate Lap Siding A A - Lap Siding ON SITE STORAGE Store off the ground well supported, on a flat well-drained surface. (Diagram 1a) Additional support may be required

More information

R Code and Commentary for 2012 NC Residential Code final 03/06/13

R Code and Commentary for 2012 NC Residential Code final 03/06/13 R602.10 Code and Commentary for 2012 NC Residential Code final 03/06/13 Commentary italicized and printed in red 1. Section R602.10 -- provides charging language for two simplified bracing approaches (isolated

More information

ICC-ES Evaluation Report Reissued March 2014 This report is subject to renewal March 1, 2015

ICC-ES Evaluation Report Reissued March 2014 This report is subject to renewal March 1, 2015 ICC-ES Evaluation Report ESR-1694 Reissued March 2014 This report is subject to renewal March 1, 201 www.icc-es.org (800) 423-687 (62) 699-043 A Subsidiary of the International Code Council DIVISION: 07

More information

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016.

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016. ICC-ES Evaluation Report ESR-894 Reissued April 04 This report is subject to renewal April, 0. www.icc-es.org (800) 4-87 () 99-04 A Subsidiary of the International Code Council DIVISION: 07 00 00 THERMAL

More information

DuPont RainVent Batten Installation Guidelines

DuPont RainVent Batten Installation Guidelines DuPont RainVent Batten Installation Guidelines Purpose: To improve the ventilation and draining space behind a cladding system or 3-coat stucco system in residential construction. The DuPont RainVent Batten

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1993 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00

More information

NEXT GENERATION HIGH PERFORMANCE WALLS

NEXT GENERATION HIGH PERFORMANCE WALLS CONSTRUCTION GUIDE NEXT GENERATION HIGH PERFORMANCE WALLS CLIMATE ZONES 3-5 PART 2: 2X4 Walls with 1" 1.5" Exterior Insulative Sheathing V. Kochkin and J. Wiehagen Home Innovation Research Labs June 2017

More information

Maximum thermal performance ISOLEREN INSULATED METAL PANELS INSTALLATION GUIDE

Maximum thermal performance ISOLEREN INSULATED METAL PANELS INSTALLATION GUIDE Maximum thermal performance ISOLEREN INSULATED METAL PANELS INSTALLATION GUIDE Isoleren Installation Guide ALL INFORMATION CONTAINED IN THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE Table of Contents

More information

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3145 Reissued 02/2017 This report is subject to renewal 02/2018. DIVISION: 05 00 00 METALS SECTION:

More information

KNIGHT WALL SYSTEMS GUIDE DETAILS:

KNIGHT WALL SYSTEMS GUIDE DETAILS: KNIGHT WALL SYSTEMS GUIDE DETAILS: MFI System - S-Series (HORIZONTAL) for CLADDING PANELS HORIZONTAL ORIENTED SYSTEM WITH OPTIONAL VERTICAL PanelRails (EXTERIOR INSULATION OMITTED FOR CLARITY) MINIMUM

More information

Proper Installation of Insulated Metal Wall Panels

Proper Installation of Insulated Metal Wall Panels Proper Installation of Insulated Metal Wall Panels Insulated metal panels (IMPs) are an ideal cladding solution for pre-engineered metal buildings. They are available in lengths up to 50, and may also

More information

Container Installation Guide

Container Installation Guide Continuous Insulation Container Installation Guide Panels and InSerts The InSoFast CX Container panel and the InSerts are designed to fit most shipping containers. Containers have three types of corrugations:

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: ASSOCIATED MATERIALS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: ASSOCIATED MATERIALS, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1258 Reissued 03/2017 This report is subject to renewal 03/2019. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2375 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 07 00

More information

Project Address: Name of Person Completing Form:

Project Address: Name of Person Completing Form: Statement of Inspections This form is provided as a way to list aspects of the project that require special inspection and testing in accordance with IBC Sections 107.1, 1704, and 1705 and define duties

More information

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY

Thermasheath -3. Insulation for the Building Envelope ROOF WALL SPECIALTY Insulation for the Building Envelope ROOF WALL SPECIALTY PRODUCT DESCRIPTION Rmax Thermasheath-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3340 Reissued 05/2017 This report is subject to renewal 05/2018. DIVISION: 07 00 00 THERMAL

More information

Container Installation Guide

Container Installation Guide Container Insulation Container Installation Guide Panels and Inserts The InSoFast CX Container panel and the Inserts are designed to fit most shipping containers. Containers have three types of corrugations:

More information

2012 Wood Frame Construction Manual: Wind Load Distribution on Buildings Load Paths

2012 Wood Frame Construction Manual: Wind Load Distribution on Buildings Load Paths 2012 Wood Frame Construction Manual: Wind Load Distribution on Buildings Load Paths Presented by: William L. Coulbourne, PE Copyright Materials This presentation is protected by US and International Copyright

More information

KNIGHT WALL SYSTEMS GUIDE DETAILS:

KNIGHT WALL SYSTEMS GUIDE DETAILS: KNIGHT WALL SYSTEMS GUIDE DETAILS: MFI System - S-Series (VERTICAL) for CLADDING PANELS VERTICAL ORIENTED SYSTEM WITH OPTIONAL HORIZONTAL PanelRails (EXTERIOR INSULATION OMITTED FOR CLARITY) MINIMUM DEPTH:

More information

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015.

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015. A Subsidiary of the International Code Council DIVISION:

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: GENTEK BUILDING PRODUCTS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: GENTEK BUILDING PRODUCTS, INC. 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (00) 423-657 (562) 699-0543 www.icc-es.org ESR-1133 Reissued 11/2017 This report is subject to renewal 11/201. DIVISION: 07 00 00

More information

Minimum Guidelines for the Design and Use of Underpins When Performing Foundation Stabilization and/or Supplementation UP-08

Minimum Guidelines for the Design and Use of Underpins When Performing Foundation Stabilization and/or Supplementation UP-08 Minimum Guidelines for the Design and Use of Underpins When Performing Foundation Stabilization and/or Supplementation UP-08 Table of Contents 1. Title 2. Designation 3. List of Figures 4. Scope 5. Referenced

More information

POST FRAME BUILDING STANDARDS

POST FRAME BUILDING STANDARDS CASS COUNTY, MISSOURI BUILDING CODES, ENVIRONMENTAL HEALTH AND ZONING DEPARTMENT 30508 S. West Outer Road, Harrisonville, MO 64701 P- (816) 380-8134 F- (816) 380-8130 POST FRAME BUILDING STANDARDS 201.3

More information

Common Errors in Truss Design

Common Errors in Truss Design In today s competitive world of trusses, component manufacturers are always looking for ways to generate more efficient truss designs. Occasionally, truss designs need to be changed in order to be sealed

More information

Inspection of New One- and Two- Family Dwellings

Inspection of New One- and Two- Family Dwellings Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Inspection of New One- and Two- Family Dwellings Planning and Development

More information

Heel Blocking Requirements and Capacity Analysis. Overview Revised 3/22/2017

Heel Blocking Requirements and Capacity Analysis. Overview Revised 3/22/2017 Heel Blocking Requirements and Capacity Analysis Overview Revised 3/22/2017 SBCA has been the voice of the structural building components industry since 1983, providing educational programs and technical

More information

Concrete weighs about 150 pounds per cubic foot

Concrete weighs about 150 pounds per cubic foot At Bassora, where they have no timber, they make arches without any frame. The mason, with a nail and a bit of string, marks a semicircle on the ground, lays his bricks, fastened together with a gypsum

More information

Quality Inspection 8618 London Heights San Antonio, TX Phone: (210)

Quality Inspection 8618 London Heights San Antonio, TX Phone: (210) Quality Inspection 8618 London Heights San Antonio, TX 78254 Phone: (210) 240-0476 PRE DRYWALL INSPECTION REPORT Prepared For: DELETED (Name of Client) Concerning: DELETED, San Antonio, TX 78258 (Address

More information

City of Hughson Building Safety Division 7018 Pine Street Hughson, CA (209)

City of Hughson Building Safety Division 7018 Pine Street Hughson, CA (209) City of Hughson Building Safety Division 7018 Pine Street Hughson, CA 95326 (209) 883-4054 RESIDENTIAL ATTACHED PATIO COVERS Patio covers are one story roofed structures not more than 12 feet above grade,

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I-JOISTS REPORT HOLDER: PACIFIC WOODTECH CORPORATION

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD I-JOISTS REPORT HOLDER: PACIFIC WOODTECH CORPORATION 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1225 Reissued 10/2017 This report is subject to renewal 10/2019. DIVISION: 06 00

More information

FrameSAFE Site-Specific Fall Protection Plan Template. Instructions for Use DO NOT INCLUDE THIS PAGE IN YOUR MANUAL SAMPLE

FrameSAFE Site-Specific Fall Protection Plan Template. Instructions for Use DO NOT INCLUDE THIS PAGE IN YOUR MANUAL SAMPLE FrameSAFE Site-Specific Fall Protection Plan Template Instructions for Use DO NOT INCLUDE THIS PAGE IN YOUR MANUAL Step 1: Complete Site-Specific Form Enter the site-specific information in the form on

More information

Standards for Testing and Rating Shoring Equipment

Standards for Testing and Rating Shoring Equipment ANSI/SSFI SH300-2007 American National Standard Standards for Testing and Rating Shoring Equipment Scaffolding, Shoring & Forming Institute, Inc. Sponsor: Scaffolding, Shoring & Forming Institute, Inc.

More information

TRUSS INDUSTRY STANDARD OF CARE ISSUES

TRUSS INDUSTRY STANDARD OF CARE ISSUES TRUSS INDUSTRY STANDARD OF CARE ISSUES by Scott D. Coffman, P.E., SECB & Jim Vogt, P.E. PART 2 Editor s Note: The purpose of this article series is to identify truss-related structural issues sometimes

More information

REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC CALIFORNIA AVENUE CORONA, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC CALIFORNIA AVENUE CORONA, CALIFORNIA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (00) 423-657 (562) 699-0543 www.icc-es.org ESR-2064 Reissued 11/2017 This report is subject to renewal 11/201. DIVISION: 07 00 00

More information

SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC Permit Requirements

SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC Permit Requirements SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC. 320-226.5189 www.101developmentresources.com While every attempt has been made to insure the correctness of this handout, no guarantees are made to its accuracy

More information

LP OSB Sheathing & Structural 1 Sheathing

LP OSB Sheathing & Structural 1 Sheathing Rated OSB Sheathing Roof Panels Span Ratings Max. Live Load Thickness Span Rating for Roofs (lbs)** 3/8" 24/0 30 7/16" 24/16 40 15/32" 32/16 70 1/2" 32/16 70 19/32" 40/20 130 23/32" 48/24 175 1-1/8" 48

More information

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: SUPERWALL MANUFACTURING, INC.

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: SUPERWALL MANUFACTURING, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2214 Reissued 08/2017 This report is subject to renewal 07/2019. DIVISION: 09 00

More information

Truss Repair and Modifications. Overview Revised 4/7/2017

Truss Repair and Modifications. Overview Revised 4/7/2017 Truss Repair and Modifications Overview Revised 4/7/2017 SBCA has been the voice of the structural building components industry since 1983, providing educational programs and technical information, disseminating

More information

DIVISION: FINISHES SECTION: GYPSUM BOARD ACCESSORIES REPORT HOLDER: CONLAB, INC. dba PREST ON CO.

DIVISION: FINISHES SECTION: GYPSUM BOARD ACCESSORIES REPORT HOLDER: CONLAB, INC. dba PREST ON CO. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1812 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 09 00

More information

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS WOOD CHAPTER 3 301 SCOPE This chapter prescribes construction requirements for buildings where all exterior walls above the foundation are wood framed

More information

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A.

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3831 Reissued 12/2017 This report is subject to renewal 12/2018. SECTION: 09 29 00

More information

INSPECTION GUIDELINES: JOIST AND UNDERFLOOR COMBO

INSPECTION GUIDELINES: JOIST AND UNDERFLOOR COMBO Joist and Underfloor Combo Page 1 of 7 Revision Date: 10/02/2017 DEVELOPMENT SERVICES BUILDING INSPECTION INSPECTION GUIDELINES: JOIST AND UNDERFLOOR COMBO INSPECTION CODE: 212, 213 SCOPE: RESIDENTIAL

More information

RESIDENTIAL CONSTRUCTION New Dwellings and Additions

RESIDENTIAL CONSTRUCTION New Dwellings and Additions How to Obtain a Building Permit For RESIDENTIAL CONSTRUCTION New Dwellings and Additions MIAMI COUNTY, KANSAS CODE SERVICES DEPARTMENT 201 South Pearl Street, Suite 201 Paola, Kansas 66071-1777 Phone:

More information

Lintel Tables Design Notes and Limitations

Lintel Tables Design Notes and Limitations LINTEL TABLES Lintel Tables Design Notes and Limitations 1. These tables apply to one and two family residential structures only that conform to the requirements of the 2006, 2009 or 2012 International

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1504 Reissued 03/2017 This report is subject to renewal 03/2018. DIVISION: 07 00

More information

ELEVATION FOR DETAIL REFERENCE ONLY

ELEVATION FOR DETAIL REFERENCE ONLY 6 7 8 10 26 19 20 14 15 22 SOFFIT OUTSIDE CORNER INSIDE CORNER 23 25 24 25 5 27 28 29 16 11 OPENING 17 18 END WALL 21 12 13 9 6 7 8 ELEVATION FOR DETAIL REFERENCE ONLY CSH-01 CSH-02 CSH-03 CSH-04 CSH-05

More information

GARAGES/ONE-STORY City of Grand Rapids Building Safety Division

GARAGES/ONE-STORY City of Grand Rapids Building Safety Division GARAGES/ONE-STORY City of Grand Rapids Building Safety Division 218-326-7601 www.cityofgrandrapidsmn.com This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3435 Reissued 07/2017 This report is subject to renewal 07/2018. DIVISION: 07 00

More information

Perimeter Relief and Control Joints in Fire-Rated Gypsum Board

Perimeter Relief and Control Joints in Fire-Rated Gypsum Board Perimeter Relief and Control Joints in Fire-Rated Gypsum Board In multi-family residential construction, involving fire-rated assemblies stress relief in the firerated assemblies is important, but often

More information

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2) Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction

More information

NATIONAL GYPSUM COMPANY Wood Frame Walls And Ceilings Single- And Double-Layer Construction

NATIONAL GYPSUM COMPANY Wood Frame Walls And Ceilings Single- And Double-Layer Construction Walls And Ceilings Single- And Double-Layer Construction 09 9 00/NGC Single-Layer Construction The single-layer construction system consists of a single layer of Gold Bond brand Gypsum Board applied to

More information

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 43 6587 (56) 699 0543 www.icc es.org ESR 3754 Reissued 09/07 This report is subject to renewal 09/09. DIVISION: 03 00 00 CONCRETE

More information

TSX Insulation for Exposed Use ROOF WALL SPECIALTY

TSX Insulation for Exposed Use ROOF WALL SPECIALTY Insulation for Exposed Use ROOF WALL SPECIALTY PRODUCT DESCRIPTION Rmax TSX-8500 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (Polyiso) foam core bonded to

More information

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) AC191 Approved May 2008 Effective June 1, 2008 Previously approved February 2008, October 2007,

More information

for New Construction Applications

for New Construction Applications INSTALLATION GUIDE for New Construction Applications Designing and building instructions for ThermalStar LCi are described in the following manual. General installation, fastening details and instructions

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: DERBY BUILDING PRODUCTS INCORPORATED

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: DERBY BUILDING PRODUCTS INCORPORATED 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2888 Reissued 07/2017 This report is subject to renewal 07/2018. DIVISION: 07 00 00 THERMAL

More information

ALLMET CONTINENTAL INSTALLATION GUIDE

ALLMET CONTINENTAL INSTALLATION GUIDE ALLMET CONTINENTAL INSTALLATION GUIDE www.allmet.com INSTALLATION NOTIFICATION The installation procedures demonstrated in this manual are recommended methods for the installation of the Allmet Continental

More information

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: SOMAR INDUSTRIES LTD LUCKETT COURT EL PASO, TEXAS 79932

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: SOMAR INDUSTRIES LTD LUCKETT COURT EL PASO, TEXAS 79932 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2732 Reissued 11/2017 This report is subject to renewal 11/2019. DIVISION: 09 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most idely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-687 (62) 699-043 www.icc-es.org ESR-199 Reissued 0/2017 This report is subject to renewal 0/2019. DIVISION: 07 00 00 THERMAL AND MOISTURE

More information

WARRANTY PROVIDER ACCEPTED A REFERENCE GUIDE OF TYPICAL RAINSCREEN WALL AND WINDOW DETAILS

WARRANTY PROVIDER ACCEPTED A REFERENCE GUIDE OF TYPICAL RAINSCREEN WALL AND WINDOW DETAILS WARRANTY PROVIDER ACCEPTED A REFERENCE GUIDE OF TYPICAL RAINSCREEN WALL AND WINDOW DETAILS Per: 2006 B.C.B.C. Part 9 DISCLAIMER: THE INFORMATION CONTAINED IN THIS DOCUMENT REPRESENTS CURRENT WOOD FRAME

More information

1.2 Reference Standard: NOFMA - National Oak Flooring Manufacturers Association Grading Standards.

1.2 Reference Standard: NOFMA - National Oak Flooring Manufacturers Association Grading Standards. WOOD FLOORING GENERAL INFORMATION 1.1 This section applies to factory finished wood strip flooring. 1.2 Reference Standard: NOFMA - National Oak Flooring Manufacturers Association Grading Standards. 1.3

More information

ALL-ALUMINUM DOOR & WINDOW FRAMING

ALL-ALUMINUM DOOR & WINDOW FRAMING ALL-ALUMINUM DOOR & WINDOW FRAMING WITH INTEGRATED ALUMINUM DOOR STOP SECTION 08 41 13 ALUMINUM FRAMED ENTRANCES AND STOREFRONTS SPECIFICATION PART 1 GENERAL 1.1 SECTION INCLUDES: A. Prefinished aluminum

More information

SPECIFICATIONS: Architectural Aluminum Railings

SPECIFICATIONS: Architectural Aluminum Railings PART ONE: GENERAL 1.1 SUMMARY SPECIFICATIONS: Architectural Aluminum Railings A. Work in this section includes custom and standard Interior and Exterior aluminum railings and guardrails. 1.2 PERFORMANCE

More information

Shaftwall and Area Separation Wall Systems.

Shaftwall and Area Separation Wall Systems. Shaftwall and Area Separation Wall Systems www.marinoware.com Marino\WARE S Fire Rated Wall Systems Quality that takes you to the top. Marino\WARE created its CT Shaftwall System, to be a flexible shaftwall

More information

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1530 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 03 00

More information

Joint Evaluation Report ICC-ES (800) (562)

Joint Evaluation Report ICC-ES (800) (562) 0 Joint Evaluation Report ICC-ES (800) -658 (56) 699-05 www.icc-es.org 000 ESR-0 Reissued 0/0 This report is subject to renewal 0/08. DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION: 06 6 00 SHEATHING

More information

MASTERFORMAT SPECIFICATION

MASTERFORMAT SPECIFICATION Contact: PFB Manufacturing, LLC Insulspan SIP Plant 9012 East US 223 Blissfield, MI, USA 49228-0026 Phone: 800.726.3510 Plasti-Fab Ltd. Head Office 100, 2886 Sunridge Way N.E. Calgary, AB Canada, T1Y 7H9

More information

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board. 1.2 RELATED WORK A. Installation of steel framing members for walls, partitions,

More information

Standard Duty Cantilever Rack Installation and Assembly Guide

Standard Duty Cantilever Rack Installation and Assembly Guide Standard Duty Cantilever Rack Installation and Assembly Guide Steel King Industries, Inc. 2700 Chamber St Stevens Pont, WI 54481 (800) 826 0203 www.steelking.com info@steelking.com ASSEMBLY INSTRUCTIONS:

More information

Exterior Stucco and Siding Installation

Exterior Stucco and Siding Installation Exterior Stucco and Siding Installation CITY OF NEWARK, CALIFORNIA BUILDING INSPECTION DIVISION 37101 Newark Boulevard, Newark, CA 94560-3796 510-578-4261 Fax 510-578-4307 e-mail: building.inspection@newark.org

More information

EcoTouch Insulation with PureFiber Technology

EcoTouch Insulation with PureFiber Technology PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

TER No Use of FastenMaster HeadLOK TM Fasteners to Attach Cladding and/or Furring to Wood Framing through Foam Sheathing

TER No Use of FastenMaster HeadLOK TM Fasteners to Attach Cladding and/or Furring to Wood Framing through Foam Sheathing OMG, Inc. d/b/a/ FastenMaster 153 Bowles Road Agawam, Massachusetts, 01001 413/789-0252 fastenmaster.com mguthrie@olyfast.com TER No. 1009-01 Issue Date: March, 27 2011 Updated: December 18, 2013 DIVISION:

More information