MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN
|
|
- Solomon Evelyn Collins
- 6 years ago
- Views:
Transcription
1 Engineering Specification Electrical Networks MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN Version: 1 Issued: November 2014 Owner: Engineering Division Approved By: Pat Kelly Head Engineer (Electrical) PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION
2 Approval Amendment Record Approval Date Version Description 25/10/ New document created PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 2 of 8
3 Table of Contents Purpose... 4 Abbreviations... 4 Definitions... 4 References & Legislation Standards Latest Issues and Amendments... 5 Service Conditions... 5 Cable Details and Ratings... 5 Testing Type Test Factory Tests Certificate of Conformance Tests after Delivery... 6 Warranty... 6 Information to be Supplied by Supplier... 6 Appendix Technical Data Schedule Form... 7 PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 3 of 8
4 1. Purpose This document is the MTM technical specification for a single core, 70mm 2 tinned copper, stranded Conductor, 3.3kV EPR Insulated, CPE Sheathed Electric Cable without a Metallic Screen. This is the standard Cable for Secondary Insulation Bonding use on the MTM 1500 Volt DC Traction System. 2. Abbreviations A CPE DC EPR k mm MTM UV V Amps Black Chlorinated Polythene Direct Current Ethylene Propylene Rubber Kilo Millimetre Metro Trains Melbourne Ultraviolet Volts 3. Definitions For all technical terms refer to AS/NZS Shall Should Is used as the descriptive word to express a requirement that is mandatory to achieve conformance to the standard. Is used as the descriptive word to express a requirement that is recommended in order to achieve compliance to the standard. should can also be used if a requirement is a design goal but not a mandatory requirement. 4. References & Legislation 4.1 Standards AS/NZS Electric Cables Polymeric Insulated, Part 1 - for working voltages 1.9/3.3 (3.6) kv up to and including 19/33kV AS/NZS 1125 Conductors in insulated electric cables and flexible cords, class 5 IEC Conductors of Insulated Cables IEC Tests on electric and optical fibre cables under fire conditions - Part 1 AS/NZS 3808 Insulating and sheathing materials for electric cables PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 4 of 8
5 4.2 Latest Issues and Amendments Reference to all standards shall be read as a reference to the latest edition of that standard and amendments available at the time of tendering. 5. Service Conditions The Cable is to be used on the MTM 1500 Volt DC Electric Traction System. This System consists mainly of an overhead catenary wiring construction that is susceptible to lightning, switching surges and short-circuits. The Cable shall be suitable for use when installed directly under ground, in ducting, conduit, on cable racks or trays either protected or exposed to the weather and ultra-violet radiation. 6. Cable Details and Ratings Rated Voltage 3.3 kv Cores Single-core Conductor Material Copper Tinned Conductor Cross Sectional Area 70mm 2 ± 2mm Nominal outer diameter of cable 16.8mm ±1mm DC 20 C (ohms) Short Circuit Current Rating (20ms) 118.3kA Conductor Stranding Stranded circular compacted, 540/0.4 Conductor Screen Not Required Insulation Material EPR Insulation Colour Neutral Insulation Screen Not Required Metallic Screen Not Required Oversheath Material CPE, UV Stabilised and Fire Retardant Sheath Colour Black Static minimum bending radius 4 times diameter Flexing minimum bending radius 6 times diameter Metre Markings Required *Cable Marking RAILWAY SECONDARY INSULATION BONDING CABLE 70mm² 3.3kV Cable Drum Type Wooden Nominal Length of Cable on Drum To be specified on purchase order * Note: Alternate cable markings cannot be substituted without written approval from MTM Engineering. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 5 of 8
6 The cable shall be delivered into MTM Central Store. The Central Store is located at E- Gate, Footscray Road, West Melbourne, Victoria Delivery shall take place during business hours Monday to Friday (except Public Holidays) from 0800 till Metro Trains Melbourne shall be notified of any delivery 5-working days prior to delivery. The length of cable on drums will be specified separately on the purchase order. The supplier/manufacturer shall notify MTM if there are changes to the manufacturing process or design since the approval date of this specification. 7. Testing 7.1 Type Test Type Test Certificates shall be supplied on request. 7.2 Factory Tests The cable shall be subjected to Routine Tests at the Manufacturer s Works as described in AS MTM reserves the right to appoint a representative to witness these tests. Seven working days notification shall be given to MTM of intention to carry out factory testing. 7.3 Certificate of Conformance The results of all tests shall be recorded on test certificates. The test certificates shall clearly show the performance of the cable and shall be accompanied by tables showing the actually measured values and all calculations The test certificates shall be forwarded to the Head of Engineering (electrical) within MTM and the results approved by the Head of Engineering (electrical) prior to delivery. 7.4 Tests after Delivery After delivery, the cable will be inspected by the MTM Central Store. The cable may be subjected independent testing as may be considered necessary to determine compliance with this Specification. Any non-compliance with this specification will result in MTM rejecting delivery Cable drum shall be clearly marked with the gross weight and batch number 8. Warranty The Cable shall be warranted by the Supplier against faulty design, materials, processing and workmanship for a minimum of two years after delivery. 9. Information to be Supplied by Supplier The supplier shall insert where provided for all of the information required in the Appendix - Technical Data Schedule Form. Failure to do so may render the offer liable to rejection. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 6 of 8
7 10. Appendix Technical Data Schedule Form The Tenderer shall supply the following information and guaranteed performance. Compliance Does the cable fully comply with this Specification? YES / NO Manufacturer Name Address Outside Diameter Of Conductor and insulation Operating Voltage Rated Operating Voltage Conductor (mm) (kv) Nominal Area (mm 2 ) Stranding ( / mm) Material Insulation Material Colour Sheath Material and Type Colour Ultra-Violet Stabilised YES / NO PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 7 of 8
8 Short Circuit Current Rating (20 ms) Conductor Weights Weight of Cable Weight of Drum Dimensions of Drum Outside Diameter Width Diameter of Barrel Nominal Length of Cable on Drum (ka) (kg/m) (kg) (m) (m) (m) (m) PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 8 of 8
Cables for Railway Signalling Applications General Requirements
Discipline: Engineering (Signalling) Category: Procedure Cables for Railway Signalling Applications General Requirements ESA-11-01 Applicability ARTC Network Wide Primary Source ESA-02-01 Document Status
More informationMTSP MANUFACTURE AND SUPPLY OF INSULATED RAIL JOINTS
Engineering Specification Track MANUFACTURE AND SUPPLY OF INSULATED RAIL JOINTS Version: 2 Issued: December 2015 Owner: Engineering Division Approved By: Liam Palmer Cannon A/Head of Engineering Track
More informationP.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT
CEB SPECIFICATION 005-1: 2012 P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS PAGE 1. Scope 03
More information15 kv EPR Insulated, Jacketed, URD Cable
15 kv EPR Insulated, Jacketed, URD Cable 1000 kcm Copper Conductor with Tape Shield Page 1 of 11 Table Of Contents 1 GENERAL... 3 2 STANDARDS... 3 3 APPROVED CABLE MANUFACTURERS... 3 4 REEL SPECIFICATIONS...
More informationTechnical Specification for Single Core 38/66kV TR-XLPE Insulated Underground Cable
Ergon Energy Corporation Limited Technical Specification for Single Core 38/66kV TR-XLPE Insulated Underground Cable ETS04-03-01 Specification ETS04-03-01 Ver 1 Contents 1. Purpose and Scope... 1 1.1 General...
More informationConductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072.
37-105VFD MMV-VFD Power Cable Three : kv - 15kV 133% Level Rated 90 C s (3) Soft annealed flexible stranded tinned copper per IEEE 150 Table 11. Extruded thermosetting 90 C Ethylene Propylene Rubber (EPR),
More informationElectrical Networks Principles and Performance
Engineering Standard Electrical Networks Electrical Networks Principles and Performance Version: 1 Issued: January 2015 Owner: Chief Engineer Approved By: Paul O Halloran Chief Engineer PRINTOUT MAY NOT
More informationTitle: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards
Change History Date Description of Change Pages / Sections Modified Change Approver Initials 6/15/16 Updated division section from 16124 to 2605 - mgl44 13, removed references to other section 10/17/14
More informationSection ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR
PART 1 - GENERAL Section 26 05 15 SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR 1.1 Cable shall be 15 kv, shielded, three conductor with ground, stranded copper, with continuously welded and corrugated
More informationNUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0
REVISION NO. 0 NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 PAGE NO. 1 OF 24 DATE OF ISSUE (MONTH/YEAR) TOTAL NO. OF PAGES (Including cover
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60502-2 Second edition 2005-03 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 2: Cables
More informationDMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)
DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- T/0018/ DMRC-E-TR-CABLE-2 SPECIFICATIONS FOR 33 kv CABLES FOR ELEVATED AND Issued on: Date Stage
More informationPHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-P156-60
Solar Innova uses the latest materials to manufacture photovoltaic modules. Our modules are ideal for any application that uses the photoelectric effect as a clean energy source because of its minimal
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables
More informationPHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-BIPV-SM-P125-36
Solar Innova uses the latest materials to manufacture photovoltaic modules. Our modules are ideal for any application that uses the photoelectric effect as a clean energy source because of its minimal
More information*** Supercedes: BECO E and COM , , & ***
7/27/09 Page 1 of 9 R5 *** Supercedes: BECO E2.9-27.4 and COM 1-0696, 2-0196, & 5-0385 *** 1.0 Scope #2 AWG to 1000 KCMIL CONCENTRIC NEUTRAL JACKETED CABLES RATED 5-35 kv These Specifications cover single
More informationCeramic Ceramic No. of Lead/Wire Lead Allied RS order Dia Ø Length Wires Type Length Code code
Datasheet Platinum Resistance Pt100 Tubular Ceramic Insert Elements with tail wires 2 or 4 wire with choice of Teflon or nickel/glassfibre insulated tail wires up to 450mm long ENGLISH 237-1635 237-1641
More informationSpecifications: Ice point resistance: Fundamental interval (0 C to 100 C): 38.5Ω (nominal)
ENGLISH Datasheet Platinum Resistance Pt100 Wire-Wound Detector Elements Pt100 platinum resistance thermometer elements in a choice of sizes single & dual element Pt100 elements to IEC 60751 Class A or
More informationMineral Insulated Platinum Resistance Thermometer PT100 Sensor - Available in 3mm or 6mm diameter x 150mm or 250mm probe lengths
Datasheet ENGLISH Mineral Insulated Platinum Resistance Thermometer PT100 Sensor - Available in 3mm or 6mm diameter x 150mm or 250mm probe lengths High temperature, rugged, flexible Pt100 probe Suitable
More informationTechnical Specification for LV ABC Fuse Switch Disconnectors
Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and
More informationENGLISH Datasheet Platinum Resistance Pt100 & Pt1000 Thin Film Detectors Platinum Sensing Resistors Thin Film (Pt100 & Pt1000 Ohm)
ENGLISH Datasheet Platinum Resistance Pt100 & Pt1000 Thin Film Detectors Platinum Sensing Resistors Thin Film (Pt100 & Pt1000 Ohm) Pt100 Elements, Thin Film (100 Ohm) Pt100 elements to IEC751 Class A,
More informationTECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT
TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.
More informationStandard of Practice - Campus Electrical Distribution System
A26.3 Standard of Practice - Campus Electrical Distribution System NOTE: Significant revisions or additions to the previous standards are highlighted in italics. GENERAL Designers shall verify that all
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-26 05 19.10 10 (May 2016) ----------------------------------- Preparing Activity: USACE Superseding UFGS-26 05 19.00 10 (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationDatasheet Platinum Resistance Pt100 Dual Element Industrial Sensor Probe 6mm diameter x 150mm or 250mm probe lengths
Datasheet Platinum Resistance Pt100 Dual Element Industrial Sensor Probe 6mm diameter x 150mm or 250mm probe lengths ENGLISH Duplex PRT s with two independent PT100 detectors inside tip of probe. This
More informationThe Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999
CANADIAN ELECTRICAL CODE 1 The Canadian Electrical Code (Saskatchewan Amendments) Regulations, 1999 Repealed by Chapter E-6.3 Reg 8 (effective June 24, 2003). Formerly Chapter E-6.3 Reg 6 (effective March
More informationELECTRICAL CODE TRADE REFERENCE
ELECTRICAL CODE TRADE REFERENCE FIFTH EDITION By Marvin Rosenberg UNIT 2: CODE COMPONENTS General Rule Sections 0 Definitions accurate interpretation 2 General Rules administrative and technical requirements
More informationXLPE CABLE (11KV - Aluminium)
XLPE CABLE (11KV - Aluminium) September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091.
More informationENGLISH. 1metre 7/.02mm Teflon insulated twin twisted lead
Datasheet Platinum Resistance Pt100 Sheathed Thin Film Strip Sensor 2 wire sensor sheathed in a thin stainless steel shim body ideal for surface measurement ENGLISH Sheathed Pt100 element in a thin, flat
More informationArmoured Instrumentation Cables to BS7917
Armoured Instrumentation Cables to BS1 Fire Resistant, Pairs/Triples - Collectively Screened. Low Smoke Zero Halogen TAC, MGT, EPR, SCRN, ZH, GSWB, SW 0/0V Application Control and instrumentation cable
More informationEngineering Data for Copper and Aluminum Conductor Electrical Cables
2018 Edition Engineering Data for Copper and Aluminum Conductor Electrical Cables THE OKONITE COMPANY Okonite Cables...A higher Standard! The Okonite Company, 2018 Okonite Cables Table of Contents SECTION
More informationWelding Accessories
Welding Accessories www.airliquide.ca 1-800-817-7697 Welding Accessories BLUESHIELD Welding Cables Blueshield Welding Cables: Excellent flexibility (stays flexible at -50 C) Abrasion resistant Oil, solvent
More informationConstruction guideline
1/6 1) SUMMARY OF ABBREVIATIONS FOR CABLE CONSTRUCTION ELEMENTS MSR - : EUPEN code for INSTRUMENTATION CABLES JE - : cable for INDUSTRIAL ELECTRONICS RD - : cable for CONTROL SYSTEMS INSULATION MATERIALS:
More informationSingle core conductor BETAtherm 145
Internet: www.synflex.de Single core conductor BETAtherm 145 Description BETAtherm 145 is a flexible low-voltage cable with UL recognition consisting of a tinned copper stranded wire and insulated with
More informationSPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR
003: 2008 CEB SPECIFICATION SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for Specification For All Aluminium Alloy Stranded Conductor CEB Specification
More informationENERGY PROTOLON(SMK) LWL. (N)TSKCGEWOEU Medium Voltage Reeling Cable with integrated Fibre Optics
ENERGY PROTOLON(SMK) LWL (N)TSKCGEWOEU Medium Voltage Reeling Cable with integrated Fibre Optics Technical Data Type Type designation Approvals/ standards Application PROTOLON (SMK) LWL (N)TSKCGEWÖU DIN
More informationTECHNICAL SPECIFICATION FOR CONDUCTORS
TECHNICAL SPECIFICATION FOR CONDUCTORS SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 9 TECHNICAL SPECIFICATION FOR CONDUCTORS SPECIFYING TECHNICAL PARAMETERS OF THE CONDUCTOR SPECIFICATION NO. RE/ II/ ACSR
More informationSECTION WIRES AND CABLES
SECTION 16120 PART 1 - GENERAL 1.01 DESCRIPTION A. The work to be performed includes, but is not necessarily limited to, all work involved with the supply and installation of wires and cables and the associated
More informationFactors Affecting Current Ratings for Underground and Air Cables
Factors Affecting Current Ratings for Underground and Air Cables S. H. Alwan, J. Jasni, M. Z. A. Ab Kadir, N. Aziz Abstract The aim of this paper is to present a parametric study to determine the major
More informationElectrical Insulating Tapes
Electrical Insulating Tapes Energy, Mining, Industrial and Contractors applications LV and MV electrical jointing and termination applications Adhesive or Self-amalgamating UV resistant Cold and weather
More informationTS 801 ELECTRICAL WORK - GENERAL TABLE OF CONTENTS
TORONTO TRANSPORTATION January 2012 TS 801 ELECTRICAL WORK - GENERAL TABLE OF CONTENTS 1. DRAWINGS TTD 801.001 ELECTRICAL ABBREVIATIONS AND SYMBOLS TTD 801.005 ELECTRICAL LEGEND I TTD 801.006 ELECTRICAL
More informationTECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS PAGODA CABLES PVT. LTD. 1/58, STREET NO: 3, VISHWAS NAGAR, SHAHDARA, DELHI 110 032. (INDIA) TEL/FAX : 91-11-22392801, 22385391. Email : pagoda @del2.vsnl.net.in CONTENTS: 1. 2.
More informationElectricity Safety (Electric Line Clearance) Regulations 2010
Version No. 001 Electricity Safety (Electric Line Clearance) Regulations 2010 Version as at 29 June 2010 TABLE OF PROVISIONS Regulation Page 1 Objectives 1 2 Authorising provisions 1 3 Commencement 2 4
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 5/12/10 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Is it illegal to install a wet-niche luminaire face-up
More informationSECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number
MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number PART 1 GENERAL 01 02 03 04 SCOPE Furnish and install Manual Transfer Switches (MTS) and
More informationTESTING PTE EARTHING
1 SCOPE This section of the Power Systems Live Working Manual details the procedures to be followed to achieve Safety from the System when carrying out examination, testing and remedial work on PTE (Pole
More informationA. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).
16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the
More informationMinistry of Defence Defence Standard 61-12(Part 26)
Ministry of Defence Defence Standard 61-12(Part 26) Issue 3 Publication Date 27 January 2001 Wires, Cords and Cables, Electrical Part 26: Wires, and Cables Electrical, Dual Extruded Insulation Type Olefin/vinylidene-Fluoride
More information3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series
3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series Data Sheet May 2014 Product Description 3M Cold Shrink Connector Insulators 8440 Series are open-ended, silicone rubber, tubular sleeves.
More informationPT. KABELINDO MURNI Tbk SHIPBOARD CABLE WIRE AND CABLE MANUFACTURER. No. EMS No. OSH No. QCS 00152
PT. KABELINDO MURNI Tbk WIRE AND CABLE MANUFACTURER No. QCS 00152 No. OSH 00971 No. EMS 00151 Introduction of company The Company s history was marked by the founding of PT. Kabel Indonesia (Kabelindo)
More informationThe Company by Peter Bröckskes sen. an independent, middle sized company
The Company DIN EN ISO 9001 More than 60 years of experience in temperature measurement and control technique as well as in cable production have made a one man business a company with nearly 500 staff
More informationSECTION GROUNDING AND BONDING
SECTION 16060 PART 1 GENERAL 1.01 DESCRIPTION A. Section includes requirements for an electrical grounding system, including electrodes, grounding rods, connectors, insulators, equipment grounding and
More informationITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION
SECTION 74 AIRPORT OBSTRUCTION LIGHTS (FAA L-119) 74-1 GENERAL The Contractor shall perform all work required by the plans and specifications for construction of obstruction lights in accordance with the
More informationNPS/002/001 Technical Specification for Earthing Materials
Version:- 6.0 Date of Issue:- October 2017 Page 1 of 14 NPS/002/001 Technical Specification for Earthing Materials 1. Purpose The purpose of this document is to detail the requirements of Northern Powergrid
More informationMTM REQUIREMENTS METROPOLITAN TRAIN MAINTENANCE DEPOT
Approval Amendment Records Approval Date Version Description 14/11/2011 1 Initial Version Disclaimer Metro Trains Melbourne makes no warranties, express or implied, that compliance with the contents of
More informationEvaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire
Evaluation of Aluminum Cable Presentation for IEEE OCS September 14, 2011 Breck Booker, Southwire Today s Topics Brief Overview of Southwire In-depth Discussion on Aluminum Characteristics Discussion of
More informationSpecification Technical Requirements for Revenue Electricity Meters
Specification Technical Requirements for Revenue Electricity Meters Standard Number: HPC-8DJ-16-0001-2013 Document Control Author Name: Richard Flett Position: Metering Technician Document Owner (May also
More informationProduct Application. Prestige Power Post in White Epoxy Coated Aluminium Finish
Product Application 83 Prestige Power Post in White Epoxy Coated Aluminium Finish 84 Floor Distribution Technical Floor Distribution Technical 85 Range Technical Data Raised Floor Systems Interact Underfloor
More informationC&G 2382 BS7671: th Edition IEE Wiring Regulations. 25 Questions
C&G 2382 BS7671:2008 17 th Edition IEE Wiring Regulations 25 Questions 1. BS7671 states that installation design must take into account a. current copper prices b. the effects of climate change c. a comparison
More information600 VOLT 600V, 3 CONDUCTOR (WITH GROUND), FR-EPR OR FR-XLPE INSULATION, PVC JACKET SPECIFICATIONS (FLAME RETARDANT POWER CABLE) (UL TYPE TC-ER) TYPE C3 SPEC 70.0100 PROJECT 196116 REFERENCE: LATEST EDITIONS
More informationUna e mpre sa Vi akab l e GLOSSARY.
GLOSSARY www.centelsa.com.co CONDUCTORS Cu Copper conductors. CuSn Tinned copper conductor. ACDSR Rectangular soft bare copper wire. ACDSRP Paper insulated rectangular soft bare copper wire. ACDD Bare
More informationDOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES
Guidelines effective March 5, 2007 NES is committed to providing safe, reliable electric service at a reasonable price for all of our customers. These guidelines offer direction for activities relating
More informationUNDERFLOOR HEATING SYSTEM INSTALLATION MANUAL LIFETIME WARRANTY INSTALLATION MANUAL. Ideal for large areas. Easy to install
LIFETIME WARRANTY INSTALLATION MANUAL Ideal for large areas Easy to install Fully compliant to latest regulations CE approved Suitable for most floor coverings (always check with floor manufacturer) UNDERFLOOR
More informationCHAPTER 5 METERING REQUIREMENTS
CHAPTER 5 METERING REQUIREMENTS CHAPTER 5 METERING REQUIREMENTS 5.1 General 1. All installations connected to, or intended to be connected to HK Electric s supply of electricity must comply with HK Electric
More informationBILLION POWER. Your one stop Supplier for all kinds of Solar Modules and BOS. Scan this quickmark,to visit our website.
BILLION POWER Your one stop Supplier for all kinds of Solar Modules and BOS. BAODI NG BILLION POWER TECHNOLOGY CO.,LTD Website:www.billionpower.cn Email: info@billionpower.cn Scan this quickmark,to visit
More informationO Coaxial/Fiber/Microduct Hybrid Buried Cable. Serves businesses in a new commercial serving area. Mitigates future cost of fiber installation
Product Classification E 2 O E2O540JCASS-24CT 24CT MICFIBR-12.7MB DUCT E 2 O Coaxial/Fiber/Microduct Hybrid Buried Cable E 2 O is a solution that enables service providers the ability to bridge HFC networks
More informationU.V resistance UL Sunlight Resistance. Flame retardant IEC
Cable for underground power distribution and subtransmission. Description Application Underground power distribution and subtransmission. As transformer feeders in substations. In power plants, industrial
More informationANSI/NEMA WC 71 ICEA S Nonshielded Cables Rated V for Use in the Distribution of Electric Energy
Approved as an American National Standard ANSI Approval Date: June 10, 2014 ANSI/NEMA WC 71 ICEA S-96-659-2014 Nonshielded Cables Rated 2001-5000 V for Use in the Distribution of Electric Energy Prepared
More informationB. Accept materials on site in original factory packaging, labeled with manufacturer s identification.
SECTION 26 05 02 - BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL 1.1 SUMMARY A. Work Included: Furnish all labor, material, services and skilled supervision necessary for the construction, erection, installation,
More information1. Approved Manufacturers: Carlon Electrical Products, Cantex, or approved equal.
PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University for for Electrical System. B. Texas State University recognizes
More informationThis product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.
Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral
More informationMETROPOLITAN RAILWAY NETWORK TRACK OCCUPATION PROTOCOL
Approval Name Position Signature/Date Document Author Adam Graves Network Program Planning Manager Document Endorsers Approving Manager Scott Short Karen Wilson Robb van Toledo Manager, Network Scheduling
More informationAmerica s Wire Company
America s Wire Company Dear Customer, We re pleased to provide you with our latest product catalog featuring many cables stocked in our warehouse located in Austin, Texas plus a backup inventory of products
More informationDATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0
DATA SHEET EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0 Unit 21 Priory Industrial Park Airspeed Road Christchurch Dorset BH23 4HD Tel: 01425 278011 Fax: 01425 278012 www.deltarubber.co.uk
More informationInstallation Address. Postcode. Purpose of the report This form to be used only for reporting on the condition of an existing installation.
A B C Details of the installation Owner*/Occupier*/Customer*/ (*Delete as necessary) Only for the reporting on the condition of an existing installation Purpose for which this report is required Installation
More informationA. This section includes building wire and cable rated 600V and less Full Short Circuit Device, Coordination and Arc Fault Study
PART 1: GENERAL 1.01 Underground Ducts and Manholes A. The work included in this section of the construction standards consists of the design requirements for the complete layout and installation of a
More informationMANUFACTURER'S RESPONSIBILITIES AND REQUIREMENTS FOR FACTORY TESTS
MANUFACTURER'S RESPONSIBILITIES AND REQUIREMENTS FOR FACTORY TESTS 1.0 MANUFACTURER'S RESPONSIBILITIES: The manufacturer's responsibilities include, but are not limited to: 1.1 Control of UL Mark - Restrict
More informationHEKAPLAST. PE-HD twin wall cable ducts and cable protection pipes for underground installation. Corrugated and Twin Wall Pipes of Plastics
HEKAPLAST PE-HD twin wall cable ducts and cable protection pipes for underground installation HEGLER HEKAPLAST III/ HEKAPLAST: Twin wall cable ducts or cable protection pipes to DIN 696, manufactured from
More informationTitle: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards
Date Description of Change Pages / Sections Modified ID 6/15/16 Updated format, division title, and removed references to other sections. - mgl44 A. Summary This section contains design criteria for the
More informationPLEASE READ INSTRUCTIONS IN CONJUNCTION WITH THE ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS
VAUFHM Underfloor Heating Mat Range Installation and Wiring Instructions Stock Ref. N 446175 446192 446176 446193 446177 446194 446178 446195 446179 446196 446180 446197 446181 446198 446182 446199 446183
More informationTechnical Specification for Live Line Tap Connectors
Ergon Energy Corporation Limited Technical Specification for Live Line Tap ETS-06-01-01 Check this is the latest Process Zone version before use. Specification ETS 06-01-01 Ver 1 Contents 1. Purpose and
More informationSmall Wind Turbine Electrical System Considerations
Small Wind Turbine Electrical System Considerations Presented by: Tom Buchal Senior Staff Engineer Intertek Renewables International Small Wind Association of Testers Conference Ithaca, NY April 25, 2012
More informationSECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less)
SECTION 260523 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less) PART 1 - GENERAL 1.1 SUMMARY A. Related Documents: 1. Drawings and general provisions of the Subcontract apply
More information(Condensed from National Electric Code)
WIRING, SPECIFICATIONS, INSPECTION, AND METER INSTALLATION PROCEDURES FOR RESIDENTIAL CUSTOMERS SERVED BY SOUTHWEST ARKANSAS ELECTRIC COOPERATIVE CORPORATION Effective April 1, 1974 Revised February 3,
More information3.0) TRANSMISSION LINES MINIMUM REQUIRED STANDARDS LINES
3.0) TRANSMISSION LINES MINIMUM REQUIRED STANDARDS LINES 3.2 Underground Lines [below sections will be renumbered at a later date] 5.0 GENERAL REQUIREMENTS 5.1 Underground transmission lines 69 kv and
More informationCOMPILED BY APPROVED BY FUNCTIONAL RESP AUTHORISED BY V SINGH. Date: 16/03/2009. Date: 16/03/2009. Date: 19/03/2009 Date: 26/03/2009
SPECIFICATION Document Classification: Controlled Disclosure Title: Distribution Specification: Part 8 Unique Identifier: 34-434 COMMON BASE AND STANDARD Document Type: PASSIVE UNITS FOR SINGLE- PHASE
More informationAS/NZS 1477:2017. Australian/New Zealand Standard. PVC pipes and fittings for pressure applications. Superseding AS/NZS 1477:2006 AS/NZS 1477:2017
AS/NZS 1477:2017 Australian/New Zealand Standard PVC pipes and fittings for pressure applications Superseding AS/NZS 1477:2006 AS/NZS 1477:2017 AS/NZS 1477:2017 This joint Australian/New Zealand standard
More informationPenn State Forestland Management Office Multi-Strand High-Tensile Wire Fence Specifications
Penn State Forestland Management Office Multi-Strand High-Tensile Wire Fence Specifications 1. FENCE REQUIREMENTS Hazard Trees All hazard trees, which are within tree length of the fence, must be felled
More informationMCST METROPOLITAN RAILWAY STATIONS
Engineering Standard Structures and Facilities Version: 3 Issued: December 2016 Owner: Chief Engineer Approved By: Phil Ellingworth Chief Engineer PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET
More informationGUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 66 kv LIGHTNING ARRESTORS GETCO/ENGG/TECH SPECI.- 66 KV LA/R4/Jan11 Sign
More informationCable kit (TPP) Installation Instructions
Cable kit (TPP) Installation Instructions Cables (BLUE) ambi-heat brand manufactured by Thermopads Before you begin installing please read through these instructions carefully & check that you have all
More informationFlat polyvinyl chloride sheathed flexible cables
BRITISH STANDARD BS EN 50214:2006 Flat polyvinyl chloride sheathed flexible cables The European Standard EN 50214:2006 has the status of a British Standard ICS 29.060.20 BS EN 50214:2006 National foreword
More informationIEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor
TABLE OF CONTENTS SECTION SUBJECT PAGE I. SCOPE...1 II. APPLICABLE DOCUMENTS...1 III. CONDUCTOR...2 IV. SEPARATOR...2 V. INSULATION...2 A. Physical Properties...2 B. Electrical Properties...3 C. Qualification
More informationúê üßµö ÖãÆü ü ¾Ö³ÖÖÖ - III
Subject: Implementation of IS/IEC 60947-2:2003 due to revision of IS 13947 series of specifications as IS/IEC 60947 series 1. ETD has informed regarding the publication of the series of specifications
More informationGENERAL PROVISIONS: Furnish and install one steel deck platform motor truck scale and associated electronic controls.
GENERAL PROVISIONS: Furnish and install one steel deck platform motor truck scale and associated electronic controls. The scale shall have a clear and unobstructed weighing surface of not less than 70
More informationRIS RIS-1800-ENE. Rail Industry Standard for Network and Depot Interface Management Isolation Documentation. Rail Industry Standard
RIS This document is a voluntary standard, produced by at the request of the industry. Duty holders may choose to mandate it through internal instructions/procedures or contract conditions. Published by
More informationDocument No Amendment No Approved By Approval Date Review Date NS222 MAJOR SUBSTATION EARTHING LAYOUT DESIGN
Network Standard NETWORK Document No Amendment No Approved By Approval Date Review Date : : : : : NW000-S0002 0 Chief Engineer 26/02/2015 31/12/2018 Review Amended Date 22/12/2017 NW000-S0002 NS222 MAJOR
More informationBuilding Regulations
Product 1.1 Technobond is a range of polyester fibre insulation used as thermal and acoustic insulating material in ceilings, roofs and walls of buildings. Appraisal No.69 [010] BRANZ Appraisals Technical
More informationPHOTOVOLTAIC CABLES. Energy and Fiber Optical Cables for Solar Energy Systems.
PHOTOVOLTAIC CABLES Energy and Fiber Optical Cables for Solar Energy Systems. As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient and sustainable supply of
More informationSurge arrester 3EB4. with polymeric composite housing for operating aboard traction units
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders
More information