1 FINEGAN INSPECTION SERVICES, INC. 27 Laurelwood Drive Milford Ohio, RESIDENCE LOCATION INSPECTION TYPE EIFS system, Visual, Tramex & Delmhorst probe moisture readings OVERVIEW The report is based on visual observations of the exterior façade material on the building envelope of the above residence as well as the use of electronic hand held moisture detector. The inspection was made without removing any existing covering surfaces or materials. There is no warranty implied as to the value, life expectancy, fitness for particular function, usefulness, or merchantability, and therefore, FINEGAN INSPECTION SERVICES, INC. assumes no liability in those areas. There are two types of meters used to determine the presence of moisture in a wall surface. The TRAMEX meter is an impedance measuring type of meter that will read an electronic signal between the wall surface behind the foam board of the EIFS and the meter face. The signal will read on the face of the meter with a 1 to 100 reading. A normal reading is below 40 on the Tramex meter. If that meter shows a reading in the 60 to 100 range, this reading means that that there is a possible wet area behind the EIFS. Because this is a stucco system the Tramex was not used. The Delmhorst meter was only used to probe the stucco surfaces. This meter is orange and it has a digital display that shows the exact percentage of moisture in the wood of the substrate behind the stucco surfaces. A reading of 5 to 14 is normal, 15 to 25 show some elevated moisture, and 25 to 40 is wet with 40 being saturation level.

2 Tramex meter Delmhorst meter The report will discuss the findings of the inspection on the exterior EIFS finishes only that are applied to the wall surfaces of this house. Any wall surfaces not in conformance with accepted workmanlike installation techniques will be also be noted in this report. The moisture analysis survey of this home was conducted by an Exterior Design Institute certified inspector, and following the protocols of the Exterior Design Institute. Right and left will be determined as one faces the front door from the exterior of the house. GENERAL INFORMATION: Time of the Inspection: 12:30 p.m. Weather Conditions- sun 48 degrees Age of home- estimated at 20 years Builder- Zaring Type of home- 2 story Foundation type- Cast in place concrete Framing type- Standard platform Type of windows- wood double hung Persons present at the inspection- Inspector only Type of system- PB- EIFS Manufacturer-unknown Humidity 38% Date of last rain fall- 1/13/15 SUMMARY OF CONDITIONS The home has wood EIFS on all the exterior walls. There is sealant application around the window and door frames on this EIFS system and most appears to be in good condition. Below the front windows, however there is high moisture readings recorded. At some of the window miter points there is moisture access behind the stucco system at the center and far right front wall areas as well as the right wall of the garage side of the home. Repair of the EIFS system is needed in the form of a sill drain systems under those windows that are actively leaking to drain out water that is now leaking behind the EIFS. At the wall surfaces where the substrate has gotten wet, replacement is needed. Each wall surface will be discussed and photos of the moisture readings at the wall surfaces will document the exterior conditions. 2

3 1). Front Left wall surface Window #3 Window #4 Window #1 Window #2 The windows 1 through 4 were noted in good condition with no moisture detected in the walls below Window #1 moisture readings Window #2 Window #3 moisture readings Window #4 The rest of the wall, caulking and EIFS surfaces were in good condition with no other repairs or modifications needed at this time. Because the windows are wood double hung, the warranty requires that all vinyl tracks be lifted at the bases and caulking applied to the wood behind the vinyl tracks 3

4 2). Front Left center wall area In the wall that is above the front entry area there was an elevation in moisture detected in the substrate that is below the window and behind the EIFS. The installation of a sill drain under this window is needed as a requirement for the warranty. There also needs to be installation of a base flashing at the concrete front porch intersection with the EIFS wall. The roof/wall intersections at the wall area above the large front foyer window #5 must be installed where there is now an undersized and leaking kick out flashing. Sill drain needed here Diverter flashing is needed here Window #5 Base flashing needed here What is a sill drain? It is installed by cutting the EIFS directly under the window frame and chiseling out approximately 1 of wood frame. The created opening is then sealed with membrane tape and liquid plastic coating, and then the black drain is inserted under the window frame. The EIFS that was cut is then resurfaces and a vinyl cap is installed over the drain to hide the drainage system and make the window appearance consistent with the rest of the window frame. SILL DRAINS After the notch has been accomplished, the sill drain system is installed After the affected EIFS has been recoated to match the rest of the EIFS finish, the cap is installed and sealed into place with matching colors of the window frame What is base flashing? The manufacturers of all EIFS systems require that the EIFS not be terminated behind concrete slabs. This is because of moisture and termite access issues when the EIFS is installed on the wall and then a concrete slab is poured against the EIFS. To create a break in the wall and to drain all water that may normally bet behind the EIFS given the slab placement, the EIFS should be cut up off the slab, a flashing installed at the intersection of the slab and EIFS so that no water can access behind the EIFS at these locations. BASE FLASHINGS Base flashing installed at the porch floor and at a deck 4

5 DIVERTER FLASHINGS What is a diverter flashing? Diverter flashings are installed at the intersections of roof systems and the walls of the EIFS wall surfaces. The diverter flashing turns the water that travels down the roof, along the wall line away from the wall and into the gutter. These flashings are vital on all walls with EIFS, fiberboard siding and faux stone applications. The diverter is sometimes called a kick out flashing because it kicks the water out and away from the wall where it would access behind the wall if the flashing were not installed. Window #5 moisture readings There were also elevated readings below the diverter flashing that is above and to the right of the window. A replacement of the diverter flashing and repair of the substrate below the diverter is necessary. There is soft substrate detected on the wall. Moisture readings are elevated below this diverter flashing Red box areas have high moisture readings The existing kick out is insufficient and allowing water to leak behind the EIFS below this location 5

6 3). Front Right Wall The wall substrate is some soft below these windows #6 and #7 and there are high readings all the way down to the floor line on this wall. The area in the red box below the window will need to be torn out, all substrate removed and replaced and new surface coatings installed. In order that the wall finishes match, the wall surface from the cornice line to the floor lines. Window #7 Window # 6 There elevated moisture readings on the center wall where the front porch gutter terminate at the front wall. RED BOX The water from the gutter is accessing the EIFS system at this location. The kick out flashing needs to be replaced with a full sized kickout as shown in the detail below. The repair of the wet substrate that is behind the EIFS below the existing kick out and then the wall will need to be resurfaced as well. Window #6 moisture readings below Add a sill drain here Rot at the base of the window sill Window #7 moisture readings were all good 6

7 Window #8 4). Front Right Wall There are elevated moisture readings below this front window. The installation of a sill drain and repair of the substrate below will be necessary. These repairs will only be needed directly below the window frame. There wall surfaces on this wall section that need some repairs to the loose lamina finish similar to those found on the upper center wall surfaces. Windows #8 and #9 Cut out the EIFS and replace any rotted substrate below the windows Sill drain needed here Moisture readings window #8 Window #9 5). Right house/garage wall The right wall of the home has the garage overhead door and chimney as well as 2 windows. The moisture readings below the windows and at the rear surface of the chimney were elevated. At these locations new sill drains need to be installed and a kick out flashing is needed at the back of the chimney framing. The addition of a flashing at the front of the chimney near the roof line is needed to prevent water access in this area. 7

8 Window #11 Window #10 Sill drains at the window #10 and #11 are needed because the existing sill drain system is allowing some water to access below these windows. The red circle locations shown in the photo are where new flashings are needed at the front upper and rear walls of the chimney. The rear section does have elevated moisture readings below this metal cap. Window #10 Window #11 Rear chimney cap area 8

9 The substrate appears to be solid behind the EIFS in these locations so there should not need to be any wall repair needed. At the rear roof intersection with the right wall, the modification of the end dam flashing is needed. The existing flashing is not installed properly. There is no water access below; this would be an insurance against future moisture access. 7). Rear right Wall Window #15 Window #16 Window #17 Windows #12,13,14 All moisture readings below these windows were noted to be in the normal range. There was no soft substrate or damage to the surfaces. These windows will need to be closely monitored because as they are, moisture access is inevitable. The windows need caulking behind the vinyl tracks, like all other windows, and keep all painted and caulked. Windows #12, 13, 14 9

10 Windows #15 and 16 Window #17 8). Rear wall Left There is only 1 elevated reading at the rear window # 18 of the kitchen. A sill drain below this window is needed but the other windows and walls are in good condition. #19 #21 #18 #20 Window #18 10

11 Window #19 Window#20 Window # 21 9). Left wall There are no elevated moisture readings in any location on the left wall surface. 11

12 Conclusion There are repairs that are needed on this synthetic stucco system. 1). The installation of sill drains under those windows shown in the report 2). The repair of all EIFS walls below the window and diverter flashing will be needed. There will need to be new caulking and a sill drains in these areas to capture the water and drain it away is needed in these locations. 3). At the front house wall, the installation of base flashings is necessary at the front porch slab/house wall intersection. 4).On the right wall windows and chimney there are flashing installations and new sill drains needed. 5). The rear window #18 will need a sill drain. 6). Re-surface the areas where there has been EIFS cut and repair so that they match the rest of the wall surfaces as closely as possible. 7). Have all windows caulked behind the vinyl tracks so that there is a better seal at these vulnerable locations and repair those window sill nosing s and mullion points that have gotten rotted. If Finegan Management and Consulting LLC supervise the EIFS repairs made by approved sub contractors, a 2 year warranty will be issued by Finegan Management and Consulting LLC on all repairs. The warranty includes two inspections over the course of the next 24 months at no costs to the homeowner. More information on this warranty can be obtained on request. SPECIFICATIONS a). There will be new substrate installed in any locations that have rot behind the EIFS as needed. The use of properly sized plywood or DuroRock concrete board is included in this bid. b).the substrate will be secured directly to the wall studs. c). EPS foam mechanically fastened to the substrate. d). Re-surfacing of the affected areas will be accomplished using the same texture as now on the wall surfaces. There will be no seams created by the repair. The entire wall surface re-coating will be accomplished in the wall sections noted in this proposal. The re-coating will stop at the horizontal floor seams and be limited to the wall section at vertical plane changes only. Because the existing wall surfaces have not been painted, the color match will be accomplished as close as possible given computer match techniques. Painting only the affected wall areas included in this bid. No wood trim or any other wall surface painting is a part of this bid. e). There will be caulking applied to the any expansion seams and around the windows that are affected by the repairs. All window exteriors will not be caulked as a part of this bid only those where caulking had to be removed and replaced to install the sill drains. All windows will have caulking applied behind the tracks from the inside of the structure. The cleaning, bonding and installation of new 12

13 silicone based caulking with closed cell backer rod will be accomplished by the contractor on affected windows. f). All blending of new color with old color by re-surfacing affected areas on the EIFS covered walls is included in this bid, the blending of all lamina with that texture that is now in place in the areas that are cut will be attempted to the best of the ability of the contractor. Exact match cannot be achieved unless the entire wall surface is re-coated with base and finish lamina. Paint to be furnished by the owner. g). The caulking use will be Dow 790 series color to match existing and closed cell backer rod will be used as needed. h). At the front wall, the removal of EIFS accent trim and water damaged substrate will be accomplished bvelow the windows and if there is wet insulation, it too, will be removed and replaced. The wall will be cleaned and any surfaces affected by moisture will be sealed with Kilz stain sealer, then new insulation and new plywood or DuroRock concrete board will be installed. The EIFS will be reinstalled and a re-coating of the walls with new lamina on the surfaces will be accomplished in the designated areas. i). Sill flashings will be installed at the wall surfaces under the specific widows shown in this proposal. #5,6,7,8,9,10,11,18 j). The kick out flashing will be replaced at the wall above window #5. A kick out will be added to the wall behind the fireplace chimney where new metal cap has been installed. Repair methods and techniques 1). The work on house will take place between the hours of 8:30 am and 6:00 pm 6 days a week. 2). All walkways and other landscaping materials will be protected to the very best ability of the contractors. 3). The daily cleaning of the site will take place. 4). All trash will be removed from site. 5). Any mold detected on the framing material will be cut out or cleaned. 6). Any structural modifications will be accomplished only by the techniques prescribed and approved by Terry Finegan. 7). The modifications will be completed within 7 business days weather permitting. 8). The repairs are guaranteed for workmanship and materials for 2 years. A cost of repair is estimated at Fee schedule FINEGAN Management and Consulting LLC By Terrence P. Finegan E.D.I. OH17 Phone: (513)

14 14

Chapter 2 Understanding The Problem

Chapter 2 Understanding The Problem Chapter 2 Understanding The Problem What Causes Most Of The Problems With Stucco? EIFS was originally intended to seal and insulate the exterior of the home from the elements. Problems occur when poorly

More information

Building Moisture Survey

Building Moisture Survey Home Inspections - Thermal Imaging - Building Envelope Forensics Building Moisture Survey Prepared For: Robin 797 Merrimac Ln Kennett Square PA 19348 Table of Contents Cover Page...1 Table of Contents...2

More information

Introduction. Massing and Overall Form. Catalina. Catalina is a 111 lot, single-family home community by Costain Arizona, Inc.

Introduction. Massing and Overall Form. Catalina. Catalina is a 111 lot, single-family home community by Costain Arizona, Inc. Introduction Catalina is a 111 lot, single-family home community by Costain Arizona, Inc. Massing and Overall Form This neighborhood comprises single-story, asymmetrical plan homes with asymmetrical facades.

More information

Differences between EnCon Insulated Precast and EIFS

Differences between EnCon Insulated Precast and EIFS Differences between EnCon Cover Differences between EnCon EnCon produces a number of different insulated precast concrete products. They range from Insulated Wall panels, Styrocore Insulated Wall Panels,

More information

The Inspection Process. Waxhaw N.C.

The Inspection Process. Waxhaw N.C. The Inspection Process In Waxhaw N.C. This information is provided by the Waxhaw Enforcement Division to assist you in the progression of your project. Nothing in this document should be considered "Code"

More information

Senturion TM III Wall System

Senturion TM III Wall System Senturion TM III Wall System TYPICAL DETAILS 1017666 1. Senturion III Wall System Application (Plan VIew) 2. Senturion III Wall System Application (Isometric View) 3. Aesthetic Groove (Plan VIew) 4. Insulation

More information

Siding and Soffit Installation Guidelines

Siding and Soffit Installation Guidelines Siding and Soffit Installation Guidelines email web phone 07 46 16 Longboard Siding & Soffit INTRODUCTION INSTALLATION GUIDELINES NOTE: These instructions are prepared for persons experienced in the field

More information

STORAGE AND TRANSPORTION

STORAGE AND TRANSPORTION Content 1. General & Notes 2. Substrate Processing 3. Panel Layout 4. Tools 5. Screws 6. Installation instructions 7. Cleaning 8. FAQS 8. MSDS General & Notes In comparison to natural or cast stone, Questone

More information

Beginning of the Course

Beginning of the Course Beginning of the Course Topics we will Cover What is Stucco? What does InterNACHI require? How to Identify Stucco Type. Primary Concerns Related to Stucco. How to Inspect during a Home Inspection. What

More information

City of Richmond Zoning Ordinance Page 12-1

City of Richmond Zoning Ordinance Page 12-1 ARTICLE 12 BUILDING DESIGN AND COMPOSITION Section 12.01 Purpose. High quality architectural design and building composition are important elements in reinforcing a comfortable, human-scale environment,

More information

Section COATING RESTORATION

Section COATING RESTORATION Sto Corp. 3800 Camp Creek Parkway Building 1400, Suite 120 Atlanta, GA 30331 Tel: 404-346-3666 Toll Free: 1-800-221-2397 Fax: 404-346-3119 www.stocorp.com 80658R StoColor Texture - Coarse Textured Acrylic-Based,

More information

Construction. Sikaflex 15 LM. Application Instructions. Sika Corporation

Construction. Sikaflex 15 LM. Application Instructions. Sika Corporation Construction Sikaflex 15 LM Application Instructions Sika Corporation Construction Sikaflex 15 LM A high-performance, low-modulus elastomeric sealant. Where to use: Excellent for moving joints in vertical

More information

The Ashland Project. Total Area: 1,778 Sq.Ft. 3 Bedroom, 2 Bath, 2 Car Garage

The Ashland Project. Total Area: 1,778 Sq.Ft. 3 Bedroom, 2 Bath, 2 Car Garage The Ashland Project Total Area: 1,778 Sq.Ft. 3 Bedroom, 2 Bath, 2 Car Garage The garage and bedroom extend from the front of this three bedroom home, drawing you visually into the entryway. Brick and stucco

More information

TEXAS DEPARTMENT OF HOUSING AND COMMUNITY AFFAIRS OFFICE OF COLONIA INITIATIVES TEXAS BOOTSTRAP LOAN PROGRAM. Form 15 Work Write-Up

TEXAS DEPARTMENT OF HOUSING AND COMMUNITY AFFAIRS OFFICE OF COLONIA INITIATIVES TEXAS BOOTSTRAP LOAN PROGRAM. Form 15 Work Write-Up TEXAS DEPARTMENT OF HOUSING AND COMMUNITY AFFAIRS OFFICE OF COLONIA INITIATIVES TEXAS BOOTSTRAP LOAN PROGRAM Form 15 Work Write-Up Owner-Builder Applicant Owner-Builder Co-Applicant Physical Address: City,

More information

Perimeter Relief and Control Joints in Fire-Rated Gypsum Board

Perimeter Relief and Control Joints in Fire-Rated Gypsum Board Perimeter Relief and Control Joints in Fire-Rated Gypsum Board In multi-family residential construction, involving fire-rated assemblies stress relief in the firerated assemblies is important, but often

More information

QUANTITIES: Included Included Included Included Included Included Included Included Included Included Included Included Address Ranking Repair #

QUANTITIES: Included Included Included Included Included Included Included Included Included Included Included Included Address Ranking Repair # First, a brief explanation of how the proposal is designed to read. The quantities section below shows the amount of work required to complete the work as shown in the section below titled "picture that

More information

Weep Valves Stucco Wire Mesh Reinforcement Weather Resistive Barrier Sheathing Insulation Framing

Weep Valves Stucco Wire Mesh Reinforcement Weather Resistive Barrier Sheathing Insulation Framing INSTALLATION INSTRUCTION FOR SINGLE-HUNG AND FIXED WINDOW REPLACEMENT using FLUSH FLANGE Installation Instructions for replacing windows in a Typical Stucco Application. These instructions were developed

More information

Quality Inspection 8618 London Heights San Antonio, TX Phone: (210)

Quality Inspection 8618 London Heights San Antonio, TX Phone: (210) Quality Inspection 8618 London Heights San Antonio, TX 78254 Phone: (210) 240-0476 PRE DRYWALL INSPECTION REPORT Prepared For: DELETED (Name of Client) Concerning: DELETED, San Antonio, TX 78258 (Address

More information

Senergy Platinum CI Stucco Typical details for an impact resistant cement plaster stucco system featuring Neopor GPS Plus Rigid Insulation Board

Senergy Platinum CI Stucco Typical details for an impact resistant cement plaster stucco system featuring Neopor GPS Plus Rigid Insulation Board Senergy Platinum CI Stucco Typical details for an impact resistant cement plaster stucco system featuring Neopor GPS Plus Rigid Insulation Board NOTES Senergy Platinum CI Stucco Typical details for an

More information

LP SmartSide Perfection Shingle

LP SmartSide Perfection Shingle Application Instructions Fiber Substrate Lap Siding A A - Lap Siding ON SITE STORAGE Store off the ground well supported, on a flat well-drained surface. (Diagram 1a) Additional support may be required

More information

Proper Installation of Insulated Metal Wall Panels

Proper Installation of Insulated Metal Wall Panels Proper Installation of Insulated Metal Wall Panels Insulated metal panels (IMPs) are an ideal cladding solution for pre-engineered metal buildings. They are available in lengths up to 50, and may also

More information

Storm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002

Storm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002 Storm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002 Prepared For: Miriam Saliba nspection Date: 9/6/2017 Prepared By: Adam Wells TREC License # 21140 105 E Spreading Oaks Ave, Friendswood,

More information

FMA / AAMA / WDMA Installation Committee Update. Jim Katsaros / DuPont Building Innovations FMA Installation Committee April 24, 2012

FMA / AAMA / WDMA Installation Committee Update. Jim Katsaros / DuPont Building Innovations FMA Installation Committee April 24, 2012 FMA / AAMA / WDMA Installation Committee Update Jim Katsaros / DuPont Building Innovations FMA Installation Committee April 24, 2012 Topics for discussion. Review & Update on FMA/AAMA/WDMA Window & Door

More information

OWNER S REPONSIBILITIES AND PREPARATION INSTRUCTIONS. Schedule "C"

OWNER S REPONSIBILITIES AND PREPARATION INSTRUCTIONS. Schedule C OWNER S REPONSIBILITIES AND PREPARATION INSTRUCTIONS Schedule "C" Building Code All Ready To Move (RTM) Homes are built according to the Alberta Building Code and National Building Code. Please note that

More information

Property Condition Assessment

Property Condition Assessment Property Condition Assessment Pewaukee, WI 53072 Inspection Date: 1/6/15 Prepared For: Report Number: Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar Dr. Pewaukee, WI 53072

More information

General. Moisture. Secondary Water-Resistive Barrier. Storage. Gaps & Sealants. Stud Spacing. Flashing, Windows, Doors & Openings

General. Moisture. Secondary Water-Resistive Barrier. Storage. Gaps & Sealants. Stud Spacing. Flashing, Windows, Doors & Openings application instructions STRAND SUBSTRATE 38, 76 AND 190 SERIES PRIMED PANEL SIDING INCLUDING SILVERTECH & SMARTFINISH General At the time of manufacture, siding meets or exceeds the performance standards

More information

How do you install yours?

How do you install yours? How do you install yours? Darrell Paul Qualistat Building Performance Consultants CSA 440 Just about adding Peel & Stick? 1 Window and door problems Photos / videos Video available for viewing at INSTAGRAM

More information

Water Intrusion Into Buildings Forensic Investigations

Water Intrusion Into Buildings Forensic Investigations Water Intrusion Into Buildings Forensic Investigations How does water flow? Let me count the ways. Major building structural and operational failures are caused by three problems: water, water, and water.

More information

1 BASE HOME CONSTRUCTION SPECIFICATIONS: TOWNHOMES 5-13-2015 Note: Specifications noted below may change based on selected options. Verify upgrades from the base specifications with the option sheets and

More information

Pella 250 Series. Wood Frame Construction with Vinyl Siding... V250-ID-888 Wood Frame Construction with Brick Veneer...

Pella 250 Series. Wood Frame Construction with Vinyl Siding... V250-ID-888 Wood Frame Construction with Brick Veneer... SECTION DIRECTORY General Information Introduction... V250-ID-886 Installation Accessories and Applications... V250-ID-886 Typical Sealant Placement Details... V250-ID-887 Fin Installation Details Wood

More information

The Disclaimer located on the reverse side of the title page of the OAA Rain Penetration Practice Guide applies to each section of the Guide.

The Disclaimer located on the reverse side of the title page of the OAA Rain Penetration Practice Guide applies to each section of the Guide. Note: This document has been divided into several sections in order to suit the limitations of the website. The Disclaimer located on the reverse side of the title page of the OAA Rain Penetration Practice

More information

WARRANTY PROVIDER ACCEPTED A REFERENCE GUIDE OF TYPICAL RAINSCREEN WALL AND WINDOW DETAILS

WARRANTY PROVIDER ACCEPTED A REFERENCE GUIDE OF TYPICAL RAINSCREEN WALL AND WINDOW DETAILS WARRANTY PROVIDER ACCEPTED A REFERENCE GUIDE OF TYPICAL RAINSCREEN WALL AND WINDOW DETAILS Per: 2006 B.C.B.C. Part 9 DISCLAIMER: THE INFORMATION CONTAINED IN THIS DOCUMENT REPRESENTS CURRENT WOOD FRAME

More information

The conditions, recommendations, suggestions contained herein are the result of a visual inspection as of this date.

The conditions, recommendations, suggestions contained herein are the result of a visual inspection as of this date. HOME INSPECTION ENGINEERS LICENSED PROFESSIONAL ENGINEERS 926 Haddonfield Road, Suite E PMB 162 Cherry Hill, NJ 08002 800-676-7879 Phone 856-482-6615 Fax 856-667-8401 In accordance with your request, the

More information

Weatherproofing & Sealing Systems

Weatherproofing & Sealing Systems Weatherproofing & Sealing Systems Weather Barrier & Waterproofing Residential & Commercial Structures New Construction, Remodeling & Repair Low Slope Roofing Membranes Roofing Underlayments Window & Door

More information

Margaret Batts Tobin Laboratory

Margaret Batts Tobin Laboratory Roof Evaluation of Margaret Batts Tobin Laboratory The University of Texas At San Antonio Performed for UTSA Zero/Six Consulting, LLC 8423 Stewart Road Galveston, Texas 77554 409 740 0090 voice Table of

More information

Application Instructions for Dryvit Backstop NT For Use Beneath Claddings Other Than Dryvit EIFS

Application Instructions for Dryvit Backstop NT For Use Beneath Claddings Other Than Dryvit EIFS Application Instructions for Dryvit Backstop NT For Use Beneath Claddings Other Than Dryvit EIFS CHECKLIST PRIOR TO THE INSTALLATION OF BACKSTOP NT - SMOOTH AND TEXTURE Project Conditions Maximum storage

More information

Edouard AVANT GROVE U I C U I C. Modern Living Made Easy uichomes.com

Edouard AVANT GROVE U I C U I C. Modern Living Made Easy uichomes.com Edouard Modern Living Made Easy uichomes.com - new construction - 3 stories + full basement - 4 bedrooms - 2.5 baths - 2,380 s.f. call 314.881.2333 or e-mail sales@uicstl.com PLAN NTS DECK 13' 0" X 12'-0"

More information

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 SECTION ONE A. Objective The objective of this guide is to provide Owners and General Contractors/Construction

More information

SECTION SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION

SECTION SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION SECTION 093000 - SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION PART 1 - GENERAL This specification includes the sheet membrane used as waterproofing, vapor retarder, and crack isolation in conjunction

More information

STUCCO FAILURES and REMEDIATION Roger G. Morse AIA

STUCCO FAILURES and REMEDIATION Roger G. Morse AIA STUCCO FAILURES and REMEDIATION Roger G. Morse AIA Morse Zehnter Associates Rensselaer Technology Park 165 Jordan Road Troy, NY 12180 rgmorse@mzaconsulting.com Florida Environment Hot Humid High ground

More information

HPW Protocol Reference Manual

HPW Protocol Reference Manual 1 HPW Protocol Reference Manual Change Log: UPDATED BY DATE UPDATED VERSION UPDATE DETAILS 2 Table of Contents: HIGH PERFORMANCE WALL ASSEMBLY... 4 THERMAL SPECIFICATION... 4 REQUIREMENTS FOR HPW INSULATION...

More information

WOOD DESTROYING PESTS AND ORGANISM INSPECTION REPORT. Building No. Street City ZIP Date of Inspection Number of Pages

WOOD DESTROYING PESTS AND ORGANISM INSPECTION REPORT. Building No. Street City ZIP Date of Inspection Number of Pages WOOD DESTROYING PESTS AND ORGANISM INSPECTION REPORT Building No. Street City ZIP Date of Inspection Number of Pages 1360 Huston Road Walnut Creek 94597 1/15/2008 Page 1 of 4 HomeGuard Incorporated 58

More information

Eclipse Energy Guard. Product Information & Installation Manual General Installation Requirements

Eclipse Energy Guard. Product Information & Installation Manual General Installation Requirements Product Information & Installation Manual 01 Important Notice to Buyers and Users of RoyOMartin wall system These instructions are not intended to cover every installation requirement, application, detail

More information

REPORT HOLDER: COREV AMERICA BRITTMOORE PARK DRIVE HOUSTON, TEXAS EVALUATION SUBJECT:

REPORT HOLDER: COREV AMERICA BRITTMOORE PARK DRIVE HOUSTON, TEXAS EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2000 Reissued 02/2017 This report is subject to renewal 02/2019. DIVISION: 07 00 00 THERMAL

More information

Senershield -R / Senershield -VB

Senershield -R / Senershield -VB Senershield -R / Senershield -VB Air / Water-Resistive Barrier Typical Details 1. Termination at Grade - Sheathing Overlapping Foundation 2. Termination at Grade - Sheathing Overlapping Foundation with

More information

SINGLE FAMILY USER S BULLETIN FOR INSTALLATION OF DUPONT WEATHERIZATION SYSTEMS PRODUCTS

SINGLE FAMILY USER S BULLETIN FOR INSTALLATION OF DUPONT WEATHERIZATION SYSTEMS PRODUCTS USER S BULLETIN SINGLE FAMILY USER S BULLETIN FOR INSTALLATION OF DUPONT WEATHERIZATION SYSTEMS PRODUCTS CONTENTS Introduction...1 Use of This Residential Single Family User s Bulletin...1 DuPont Residential

More information

Home Building Planner

Home Building Planner Home Building Planner Created by PHO For YOU! Please accept this guide with our compliments. We have developed this planner based upon prior projects we have completed. While every situation will have

More information

Corium Brick Rainscreen System Specifications

Corium Brick Rainscreen System Specifications CORIUM BRICK RAINSCREEN SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Work Included: The Work of this Section shall include but not be limited to the following: 1. Corium brick plates 2. Galvanized and coated

More information

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 075423 - THERMOPLASTIC POLYOLEFIN (TPO) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Division 00 Bidding Requirements and other Division

More information

Synthetic Stucco Without Failures To avoid a lawsuit, build a drainable assembly

Synthetic Stucco Without Failures To avoid a lawsuit, build a drainable assembly BEST PRACTICES STUCCO Synthetic Stucco Without Failures To avoid a lawsuit, build a drainable assembly BY MARK PARLEE Photos: Mark Parlee I started out 38 years ago as a framing and siding contractor in

More information

Design Guidelines for Construction and Renovation in the Longmeadow Historic District

Design Guidelines for Construction and Renovation in the Longmeadow Historic District Design Guidelines for Construction and Renovation in the Longmeadow Historic District Revision 2008.1 The following list of Guidelines has been compiled to facilitate the homeowner's planning for projects

More information

MCCARTY ARCHITECTS, P.A. POST OFFICE BOX 440 / 533 WEST MAIN STREET TUPELO, MS / FOR ANSWERS TO QUESTIONS CONTACT: JUSTIN HARRINGTON

MCCARTY ARCHITECTS, P.A. POST OFFICE BOX 440 / 533 WEST MAIN STREET TUPELO, MS / FOR ANSWERS TO QUESTIONS CONTACT: JUSTIN HARRINGTON ADDENDUM NUMBER FROM: MCCARTY ARCHITECTS, P.A. POST OFFICE BOX 0 / 533 WEST MAIN STREET TUPELO, MS 3880 / 3880 FOR ANSWERS TO QUESTIONS CONTACT: JUSTIN HARRINGTON PHONE: -8-00 PROJECT: ACADEMIC STUDENT

More information

Wall Panels. Structural wall panel. Architectural wall panel. Cladding wall panel. Sandwich wall panel

Wall Panels. Structural wall panel. Architectural wall panel. Cladding wall panel. Sandwich wall panel Wall Panels Structural wall panel Architectural wall panel Cladding wall panel Sandwich wall panel Wall Panels Assorted styles and colours Reveals and other patterns Painted finish Bolted, welded and knife

More information

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards SECTION 07185 TRAFFIC MEMBRANE PART 1 GENERAL 1.1 SECTION INCLUDES A. Traffic membrane, consisting of welded seam PVC waterproofing, over f following surfaces: 1. Decks, balconies, and sun porches 2. Walkways,

More information

SIDING BUILDING PERMIT APPLICATION

SIDING BUILDING PERMIT APPLICATION Community Development 1050 W Romeo Rd, Romeoville, IL 60446-1530 (815) 886-7200 Fax #: (815) 886-2724 Email: buildinginspections@romeoville.org SIDING BUILDING PERMIT APPLICATION Application Date / / Property

More information

Kelly Village Apartments 3118 Green Houston, Texas 77020

Kelly Village Apartments 3118 Green Houston, Texas 77020 Kelly Village Apartments 3118 Green Houston, Texas 77020 Houston Housing Authority J. Allen Management Managing Agent Scope for Kelly Village Unit #1125 Overall Scope: Demolition, Renovation, and Restoration

More information

Building Inspection Report

Building Inspection Report Building Inspection Report Sample Commercial Inspection Report Inspection Date: Prepared For: Prepared By: Professional Property Inspection Consultants 4857 Winterset Drive Columbus, OH 43220 (614) 459-5941

More information

A. ASTM C190 - Test Method for Tensile Strength of Hydraulic Cement Mortars

A. ASTM C190 - Test Method for Tensile Strength of Hydraulic Cement Mortars SECTION 04850 (04 40 00) MSI PRECAST STONE VENEER SYSTEM PART 1 GENERAL 1.1 SECTION INCLUDES A. MSI Precast Stone Veneer for exterior and interior vertical surfaces. 1.2 RELATED SECTIONS Specifier Notes:

More information

Fast Track Re-Roof Permit Checklist

Fast Track Re-Roof Permit Checklist Fast Track Re-Roof Permit Checklist ADDRESS I will abide by attached City Re-Roofing Building Permit Required Guidelines, including applicable Siding and Roofing Match and Smoke Detector requirements.

More information

NOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION. MASTERFORMAT SECTION (Mortarless Concrete Brick Veneer)

NOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION. MASTERFORMAT SECTION (Mortarless Concrete Brick Veneer) NOVABRIK MORTARLESS CONCRETE BRICK VENEER SPECIFICATION MASTERFORMAT SECTION 04818 (Mortarless Concrete Brick Veneer) Spec_USA_En_18102005.doc 12/1/2005 Novabrik Page 2 Section 04818 NOVABRIK MORTARLESS

More information

CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1%

CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1% CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE EXAM ID: I1 80 multiple-choice questions 3-1/2-hour time limit Open book 01. GENERAL ADMINISTRATION 6% 0101. Project Administration 1% Verify that

More information

for New Construction Applications

for New Construction Applications INSTALLATION GUIDE for New Construction Applications Designing and building instructions for ThermalStar LCi are described in the following manual. General installation, fastening details and instructions

More information

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: EXTERIOR INSULATION AND FINISH SYSTEMS REPORT HOLDER:

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: EXTERIOR INSULATION AND FINISH SYSTEMS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Legacy Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org NER 646 Reissued 07/2017 This report is subject to renewal 07/2018. DIVISION: 07 00 00 THERMAL

More information

PAYING ATTENTION TO DETAIL by Bob Cusumano

PAYING ATTENTION TO DETAIL by Bob Cusumano PAYING ATTENTION TO DETAIL by Bob Cusumano Painting contractors are often required to install caulk or sealant in exterior joints. Too often, the sealant is simply gunned into the joint until it s filled

More information

Commercial Roof Cover Maintenance and Repair Risk Engineering Your Business Insurance Specialists

Commercial Roof Cover Maintenance and Repair Risk Engineering Your Business Insurance Specialists Commercial Roof Cover Maintenance and Repair Risk Engineering Your Business Insurance Specialists With information provided by the Insurance Institute for Business & Home Safety Protection from the top

More information

GREEN PASTURES - RESIDENTIAL ARCHITECTURAL REVIEW GUIDELINES

GREEN PASTURES - RESIDENTIAL ARCHITECTURAL REVIEW GUIDELINES GREEN PASTURES - RESIDENTIAL ARCHITECTURAL REVIEW GUIDELINES Guideline Areas Traditional Guidelines All homes on Palm Drive, Eagle Court, Emmaus Road, Calvary Road, Wilderness Road, & Sparrow Road. Neighborhood

More information

Exterior Stucco and Siding Installation

Exterior Stucco and Siding Installation Exterior Stucco and Siding Installation CITY OF NEWARK, CALIFORNIA BUILDING INSPECTION DIVISION 37101 Newark Boulevard, Newark, CA 94560-3796 510-578-4261 Fax 510-578-4307 e-mail: building.inspection@newark.org

More information

The NWX Prairie Style

The NWX Prairie Style zontal proportions and a kinship with the earth. All Prairie style homes reflect Wright s obsession with breaking up the box. Historically, single level prairie style homes were uncommon. Single level

More information

ELEVATION FOR DETAIL REFERENCE ONLY

ELEVATION FOR DETAIL REFERENCE ONLY 6 7 8 10 26 19 20 14 15 22 SOFFIT OUTSIDE CORNER INSIDE CORNER 23 25 24 25 5 27 28 29 16 11 OPENING 17 18 END WALL 21 12 13 9 6 7 8 ELEVATION FOR DETAIL REFERENCE ONLY CSH-01 CSH-02 CSH-03 CSH-04 CSH-05

More information

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person

More information

Marbella Isles Homeowners Association, Inc.

Marbella Isles Homeowners Association, Inc. REQUEST FOR ARCHITECTURAL REVIEW Please Note: There is a $25.00 non-refundable processing fee for all requests. The application will not be processed if it is not included with application. Make check

More information

Acceptable Floor Substrates: Concrete, cured mortar bed, plywood, and backer board.

Acceptable Floor Substrates: Concrete, cured mortar bed, plywood, and backer board. SECTION 093000 - SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL This specification includes the sheet membrane used as waterproofing and vapor retarder, in conjunction with tile and dimension stone installations.

More information

THE CONSTRUCTION SUPERVISOR

THE CONSTRUCTION SUPERVISOR City of Aurora Building Inspections 15151 E Alameda Pkwy Aurora, CO 80012 (303) 739-7420 THE CONSTRUCTION SUPERVISOR When a building permit has been issued for any construction within the City, the Supervisor

More information

SECTION MANUFACTURED ROOF EXPANSION JOINTS

SECTION MANUFACTURED ROOF EXPANSION JOINTS SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SPECIFICATIONS FOR AluSystems Aluminum Composite Panels Series 20 Dry Joint 1.00 GENERAL 1.01 RANGE OF WORK Section includes: Laminated panels and attachment systems for use as exterior cladding. A. Provide

More information

SECTION SHEET MEMBRANE SOUND REDUCTION, CRACK ISOLATION / JOINT BRIDGING, AND WATERPROOFING

SECTION SHEET MEMBRANE SOUND REDUCTION, CRACK ISOLATION / JOINT BRIDGING, AND WATERPROOFING SECTION 093000 - SHEET MEMBRANE SOUND REDUCTION, CRACK ISOLATION / JOINT BRIDGING, AND WATERPROOFING PART 1 - GENERAL This specification includes the sheet membrane used for sound reduction, crack isolation

More information

Paint Failure Blues 2017, Jeffrey C. May

Paint Failure Blues 2017, Jeffrey C. May 1 Paint Failure Blues 2017, Jeffrey C. May Indoor air quality (IAQ) problems occur inside a building for a number of reasons that include the presence of mold as well as a food chain, with mites at the

More information

11/1/2016. Smoke detectors will be furnished by MHA and installed by contractor.

11/1/2016. Smoke detectors will be furnished by MHA and installed by contractor. 11/1/2016 Request for Proposal: Make Ready Services McKinney Housing Authority (MHA) requests proposals for vendors to perform make ready services on vacant units within the authority. All bidders must

More information

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960 STUC-O-FLEX PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960 PART 1 - GENERAL 1.01 DESCRIPTION Provide all labor, materials and equipment necessary

More information

NEW CONSTRUCTION ADDENDUM TO COA APPLICATION

NEW CONSTRUCTION ADDENDUM TO COA APPLICATION NEW CONSTRUCTION ADDENDUM TO COA APPLICATION Property Owner Address City, ST Zip Phone Fax Street Address Tax Parcel Historic ID C N P F I HPC HDC Staff Project Description: Check all that apply. Primary

More information

EMERGENCY MANAGEMENT PREPAREDNESS AND ASSISTANCE TRUST FUND ARC 4496 Evaluation Questionnaire

EMERGENCY MANAGEMENT PREPAREDNESS AND ASSISTANCE TRUST FUND ARC 4496 Evaluation Questionnaire EMERGENCY MANAGEMENT PREPAREDNESS AND ASSISTANCE TRUST FUND ARC 4496 Evaluation Questionnaire Additional Instructions and Clarifications 1. Please review ARC 4496 before beginning the project identification

More information

Encapsulated, Sealed & Closed Crawlspace Installation Manual

Encapsulated, Sealed & Closed Crawlspace Installation Manual YourCrawlSpace, Inc. 1007 Johnni4 Dodds Blvd. Mt. Pleasant, SC 29464 Toll Free: 877-44-CRAWL (27295) Local: (843) 593-1115 Encapsulated, Sealed & Closed Crawlspace Installation Manual Copyright 2017 Your

More information

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING P.O. Box 599 - Mars, PA 16046 800-321-3337 SECTION 07555 COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3435 Reissued 07/2017 This report is subject to renewal 07/2018. DIVISION: 07 00

More information

Applying for Permits to build a new house in Linn County

Applying for Permits to build a new house in Linn County Planning & Development Linn County, Iowa Building Division Linn County Building Code Residential Guidelines Single Family Dwellings Page 1 of 4 Applying for Permits to build a new house in Linn County

More information

Letter of Intent 1026 Sherman Ave

Letter of Intent 1026 Sherman Ave Letter of Intent 1026 Sherman Ave Overview We would like to tear down the existing structure which is not fit for occupancy or renovation and build a new home which is appropriate to the feel, class, size

More information

SECTION CONCRETE AND MASONRY COATINGS

SECTION CONCRETE AND MASONRY COATINGS 80658 StoColor Texture - Coarse Textured Acrylic-Based, Vertical Above-Grade Exterior Wall Coating for New Concrete, Stucco, and Masonry Construction SECTION 099723 CONCRETE AND MASONRY COATINGS Sto Corp.

More information

PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION

PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION Permit No. 175 Beaver Drive, P.O. Box 486 DuBois, PA 15801 Phone: 814-375-1111 Fax: 814-375-1117 Toll Free: 855-PENNSAF LOCATION OF PROPOSED

More information

In the neighborhoods of coastal California where I. A Close Look at Stucco. A Close Look at Stucco

In the neighborhoods of coastal California where I. A Close Look at Stucco. A Close Look at Stucco A Close Look at Stucco A Close Look at Stucco Problems with stucco persist, yet properly installed standard details are still the cure by Dennis McCoy In the neighborhoods of coastal California where I

More information

FACADES - ACM BASE AT OVERHANG (WITH BASE FLASHING) INDEX SHEET

FACADES - ACM BASE AT OVERHANG (WITH BASE FLASHING) INDEX SHEET KPH-DS-01-MTLV KPH-PJ-01-MTLV KPH-PJ-02-MTLV KPH-PJ-03-MTLV KPH-PJ-04-MTLV KPH-PJ-05-MTLV KPH-BS-01-MTLV KPH-BS-02-MTLV KPH-BS-03-MTLV KPH-BS-04-MTLV KPH-OC-01-MTLV KPH-IC-01-MTLV KPH-SF-01-MTLV KPH-SF-02-MTLV

More information

Lithia Dodge East 5500 L St. Omaha, NE

Lithia Dodge East 5500 L St. Omaha, NE Lithia Dodge East 5500 L St. Omaha, NE Perimeter Photos Failed Joints at North Rear Wall Control Joints Look Good Inadequate Downspout Elbows Erosion Along Wall Minor Efflorescence Roof Section Photos

More information

Finestone Stucco System

Finestone Stucco System Typical Details Finestone Stucco System Cement Plaster Stucco 1. Typical Finestone Stucco System with Steel Framing 2. Typical Finestone Stucco System with Wood Framing 3. Typical Finestone Stucco System

More information

Carpenter Level 2 Rev. September 2017

Carpenter Level 2 Rev. September 2017 Level 2 A5 Site Layout II Duration: 14 hours 7 hours 7 hours Upon completion of this unit the apprentice will demonstrate knowledge of site layout tools and equipment and their applications and procedures

More information

MULTI-FAMILY USER S BULLETIN FOR INSTALLATION OF DUPONT WEATHERIZATION SYSTEMS PRODUCTS

MULTI-FAMILY USER S BULLETIN FOR INSTALLATION OF DUPONT WEATHERIZATION SYSTEMS PRODUCTS USER S BULLETIN MULTI-FAMILY USER S BULLETIN FOR INSTALLATION OF DUPONT WEATHERIZATION SYSTEMS PRODUCTS CONTENTS Introduction...1 Use of this Residential Multi-Family User s Bulletin...1 DuPont Multi-Family

More information

ROOF BALLAST MATERIALS ARCHITECTURAL CONCRETE PAVING SLABS SRS LEVELING BLOCK SYSTEM INSTALLATION PART GENERAL 1.

ROOF BALLAST MATERIALS ARCHITECTURAL CONCRETE PAVING SLABS SRS LEVELING BLOCK SYSTEM INSTALLATION PART GENERAL 1. 07555 - ROOF BALLAST MATERIALS ARCHITECTURAL CONCRETE PAVING SLABS SRS LEVELING BLOCK SYSTEM INSTALLATION PART 1.00 - GENERAL 1.01 SUMMARY: A. The work of this section consists of furnishing and installing

More information

Waterproofing MAINTAINING YOUR BOUNDARIES

Waterproofing MAINTAINING YOUR BOUNDARIES Waterproofing MAINTAINING YOUR BOUNDARIES BY KATHY DANFORTH L ocation, location, location isn t just a real estate issue. Water and dirt are essential to life, but entire industries are devoted to preventing

More information

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS St. Louis County Department of Public Works Division of Code Enforcement HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS This guide is intended to provide the homeowner or contractor with the

More information

Colphene BSW Training and Application Guide. Colphene BSW Waterproofing Membrane. 1. Prepare substrate

Colphene BSW Training and Application Guide. Colphene BSW Waterproofing Membrane. 1. Prepare substrate Colphene BSW Training and Application Guide Colphene BSW Waterproofing Membrane. 1. Prepare substrate Substrate must be structurally sound. Surface must be free of voids, spalled areas, loose aggregate,

More information

Infrared Inspection Report

Infrared Inspection Report Infrared Inspection Report 1234 Sample St, Anywhere Inspection Date/Time: 3/12/2007-11:00 AM Prepared For: Dave Smith Prepared By: Norton Inspection Co. 6632 Telegraph Rd, #346 Bloomfield Hills, MI 48301

More information

SAM HOUSTON STATE UNIVERSITY DIVISION 07 THERMAL & MOISTURE PROTECTION SECTION ROOFING SYSTEMS DESIGN AND CONSTRUCTION STANDARDS February 2016

SAM HOUSTON STATE UNIVERSITY DIVISION 07 THERMAL & MOISTURE PROTECTION SECTION ROOFING SYSTEMS DESIGN AND CONSTRUCTION STANDARDS February 2016 PART 1: GENERAL 1.01 Scope Of Standard 1.02 Reference Standards 1.03 Quality Control A. This standard provides general guidance concerning the specific preferences of the Sam Houston State University for

More information