1 Panama City Marina City of Panama City, Florida MARINA BULKHEAD ASSESSMENT October 3, 2011 Prepared For: Prepared By: 543 Harbor Boulevard, Suite 204 Destin, Florida DRAFT - 12/19/2011

2 Panama City Marina Marina Bulkhead Assessment 1.0. Introduction Panama City Marina (Figure 1.1) is one of the City of Panama City s (City) greatest assets which provide a mix of economic, recreational, and transportation opportunities and benefits to the community and its users. Located on St. Andrews Bay the Panama City Marina provides boaters with a calm and protected harbor. The upland public access points provide the general public with panoramic views of the scenic waters of St. Andrews Bay. However due to the age of the marina and upland infrastructure, attention is needed to increase the longevity of the facility and create additional opportunities and uses to benefit the City, residents, and businesses. The City is in the planning process to investigate cost-effective renovations and improvements to the existing Panama City Marina. MRD Associates, Inc. (MRD) has been tasked to perform a general Figure 1.1. Project Location assessment of the structural integrity of the existing concrete bulkhead. In addition, as a result of the proposed improvements to the marina uplands, this assessment will provide recommendations for the rehabilitation or replacement of the bulkhead and magnitude of cost Bulkhead Investigations The fundamental purpose of bulkhead investigation is to provide the information necessary to assess the condition (capacity, safety, and rate of deterioration) of the bulkhead, as well as to identify potential impacts to the bulkhead as a result of the proposed upland improvements. The entire length of the bulkhead will be assessed with special focus at the south-west end of T dock and the corner of the bulkhead near the Annex. Recommendations for required rehabilitation or replacement of the bulkhead and magnitude of cost will also be provided Site Overview and Existing Conditions The City owned and operated marina is located on the St. Andrews Bay adjacent to downtown. The marina is bounded to the north-east by the City buildings with adjacent parking. The remaining three sides of the marina are open to St. Andrews Bay. Existing 240-slip marina facility designed for all classes of vessels, from 30 feet to 120 feet October 3, 2011 DRAFT - 12/19/2011

3 Panama City Marina Marina Bulkhead Assessment The marina is open for business 7-days a week and offers full-service fueling. The marina can accommodate vessels with 110/220 power and cable TV service at the slips. The marina s uncovered and covered slips are timber docks supported on timber and precast concrete piles. Timber and concrete mooring piles separate the slips. On the north-west and south-east openings into the marina are protected by vertical concrete breakwaters which provide wave attenuation from minor wave and boat wakes. The bulkhead that forms the 5,635 foot upland marina perimeter was constructed in the late 1950s over 55 years ago. Figure 2-1 provides a general schematic of the bulkhead, anchoring system and immediate upland walkway and parking/driveway, and consists of: a concrete 12-inch to 16-inch thick and 30-inch wide reinforced concrete panels; keyed panels and secured together at the top of the panels by a continuous 24-inch by 18- inch concrete cap; panels with unknown lengths and embedment depths; and, a dead-man anchoring system. Based on limited information provided the City, the bulkhead is supported by in-earth anchors (tie-rods, concrete dead-man and concrete walers). Figure 2.1. Typical Bulkhead Cross-section 2.2. Assessment of Existing Bulkhead Structural Conditions The analysis was performed utilizing information: a) provided by the CITY; b) collected by students from NDSTC Class MEDO/UCTB/2C who performed a preliminary underwater inspections on June 22, 2011; and, c) an above water visual assessment performed by MRD on October 11, 2010 and August 30, 2011 which is the primary source of information. The documented conditions are October 3, 2011 DRAFT - 12/19/2011

4 Panama City Marina Marina Bulkhead Assessment relied solely on visual observations of the bulkhead and did not include detailed testing, capacity analysis, or forensic investigation. This investigation did not include below grade excavation or geotechnical coring; therefore, the conditions of a significant portion of the marina infrastructure remains unknown. This report serves as a preliminary baseline investigation to assist the City in the assessment of potential opportunities and/or impediments. Appendix A summarizes and itemizes original field notes with location identifiers and photographs Recommendations and Opinion of Probable Costs The following section of the report indentifies, summarizes, and provides preliminary opinions of probable costs for the marina bulkhead improvements, maintenance needs and/or replacement Summary of Repair and Replacement The bulkhead repair and replacement recommendations are included in this assessment to provide the CITY with sound engineering options to plan and budget for the future of this structure. A number of maintenance and repair items that may be necessary to sustain and improve the marina facility and upland improvements were identified. Based on this investigation, two types of corrective action is presented to increase the integrity of the parameter retaining (bulkhead) structure. The first would be to repair segments of bulkhead to minimize costs while increasing the longevity and aesthetics of the structure. The second is to replace entire 5,635 linear feet of concrete bulkhead with new parameter wall (bulkhead). The following provides a list of structural improvements for the bulkhead replacement and repairs to meet the project goals. The parenthetical reference point (S) is respective to the Sheet Numbers found in Appendix A, which further depicts the noted condition Repairs to the Existing Bulkhead Periodic maintenance on the existing bulkhead has occurred a number of times over the past 25 years to repair damage and prolong further deterioration of the structure. These efforts have increase the life of structure to over 55 years. Maintenance and repair items were identified during the recent site visits to correct current structural deficiencies and further increase the life of the structure. Based on these field assessments and the desk-top structural analysis of the existing bulkhead and anchoring system, the repairs identified below and the implementation of a maintenance program it is possible that the repairs will increase the life of the structure for another 10 years. However, even with this the structure is approaching the end of its life and will need to be replaced. The repairs to the bulkhead will include: Replace all loose, disconnected, or missing concrete walers Replace all failed anchor ties Replace cracked, damaged bulkhead concrete panels Seal all gaps between bulkhead panels Replace cracked and damaged concrete pile cap In addition, approximately 150 linear feet of bulkhead will need to be replaced due to the extensive deterioration of the structure October 3, 2011 DRAFT - 12/19/2011

5 Panama City Marina Marina Bulkhead Assessment Bulkhead Replacement The existing concrete bulkhead was designed and constructed in mid 1950's making the structure over 55-years old. This structure has exceeded the expected lifespan for a concrete bulkhead located in the saltwater environment. Based on documentation provided by the CITY, segments of the wall have been repaired several times due to damage and deterioration of the steelreinforced concrete structure. A new steel sheet-pile bulkhead will increase the longevity of the parameter retaining structure for another 50+ years. Steel over concrete, aluminum or composite is recommended due to the cost, performance, stability and ability to drive the sheet into the bay bottom. Maintenance of the new bulkhead will still be required, However, maintenance costs will be minimized over the life of the new structure with the implementation of a long-term annual inspection and repair program. The replacement of the bulkhead and tie-back system would include the following sequence: Removal of existing waler system; Removal existing steel-reinforced concrete pile-cap; Placement of clean fill and compaction; Installation of new sheet-pile just waterward (in front) of the existing bulkhead; Installation of tie-back (wall anchoring) system; and, Installation of a steel-reinforced concrete pile-cap Opinion of Probable Costs Preliminary opinion of probable costs are presented to assist the CITY in developing an implementation strategy and budgetary framework for the capital improvements to either continually repair or replace the existing bulkhead. It should be noted that the preliminary opinions of probable cost are based on limited information and the best judgment of MRD as a professional design firm familiar with the types of work proposed. While the Panama City is considering a number of upland site changes which would impact the upland area and the marina facility, the preliminary opinion of probable costs presented in this section are only for the repair or replacement of the parameter bulkhead without making significant changes to the marina configuration or in-water facilities. Appendix C provides a detailed, itemized breakdown of the opinions of probable costs. The reader should note, as an added buffer against price uncertainty at this level of analysis, the "Total Opinion of Probable Cost" in Appendix C include a +/- 15% range. Table 3.1 summarizes the preliminary opinion of probable cost figures and "Annual Cost". Table 3.1. Summary of Opinion of Probable Cost and Annual Cost Alternative Opinion of Probable Cost Annual Cost Repairs to the Existing Bulkhead $2,072,754 (1) $845,000 $19,480,695 Bulkhead Replacement $19,480,695 $795,000 (1) Assumes the replacement of the bulkhead in the 10th year October 3, 2011 DRAFT - 12/19/2011

6 Panama City Marina Repairs to the Existing Bulkhead Marina Bulkhead Assessment The recommended repairs to the existing bulkhead may increase the longevity of the structure by another 10 years or so. The preliminary opinion of probable costs are estimated between $1,761,841 (-15%) and $2,383,667 (+15%), with a mean value of $2,072,754 (Table C.1). However, due to the age of the structure (55 years+) the on-going annual maintenance of the structure will be required. Although these improvements will prolong the need to replace the entire bulkhead for the next 10 years, it is anticipated the 5,485 linear feet (the 150 feet repaired was deleted) bulkhead will eventually need to be replaced at an additional cost of $19,480,695 (in year one cost, see Section 3.2.2). In order to achieve the desired 50 year life for the new bulkhead, a yearly maintenance program should be developed and implemented. The Annual Cost of $845,000 (50 years, 8.0%) includes the initial repairs, construction of the replacement bulkhead and maintenance (assuming $10,000 per year for this assessment) Bulkhead Replacement The preliminary opinion of probable costs for the replacement of the entire 5,635 linear feet of bulkhead with a new steel sheet-pile wall is estimated between $16,558,591 (-15%) and $22,402,800 (+15%), with a mean value of $19,480,695 (Table C.2). As discussed in Section 3.2.1, in order to achieve the desired 50 year life for the new structure, a yearly maintenance program should be developed and implemented. The assessment assumes an annual maintenance budget of $10,000. The Annual Cost of $795,000 (50 years, 8.0%) includes construction of the replacement bulkhead in the first year and maintenance. Although a maintenance program is a capital investment and requires a dedicated funding and implementation strategy, not conducting such a maintenance program would reduce the Annual Cost. However, not maintaining the new bulkhead would require extensive and costly repairs in 20- to 25-years as historically experienced for this structure Conclusions The following provides a brief summary of findings: The concrete bulkhead is currently supporting the marina perimeter; however, some of these key component structures are showing signs of age, deterioration and require repair or replacement. The bulkhead was constructed in the mid 1950's and at this time it exceeds its life expectance which on an average runs approximately 30+ years. The field assessment and the review of the structural conditions of the bulkhead system did not indicate any problems that would require immediate remedial action. The marina facility can continue its current operations; however, the analysis of the site conditions suggest that the bulkhead will continue to deteriorate and may have less than five (5) year of life remaining before significant capital investments will be required. Based on this investigation, two types of corrective action is presented to increase the integrity of the parameter retaining (bulkhead) structure. The first would be to repair segments of bulkhead to minimize costs while increasing the longevity and aesthetics of the structure. The second is to replace entire 5,635 linear feet of concrete bulkhead with new parameter wall (bulkhead) October 3, 2011 DRAFT - 12/19/2011

7 Panama City Marina Marina Bulkhead Assessment The preliminary opinion of probable cost for the partial bulkhead replacement and repair is approximately $2,072,754 and $19,480,695 to replace the entire 5,635 linear foot bulkhead. It is recommended that the CITY replace the existing bulkhead rather than repairing sections. First, the Annual Cost for the replacement bulkhead is less than that for the repair (and eventual replacement) option. Replacing the bulkhead now rather than in the future (within the next 10 years) will minimize the disruption of activities along the new upland improvements, minimize costs associated with restoring the new upland facilities, and reduce further damage to the marina facility. However, a phasing plan can be developed to replace the bulkhead in the immediate area of need where upland improvements will be constructed and to meet any budget constraints October 3, 2011 DRAFT - 12/19/2011

8 Panama City Marina Marina Bulkhead Assessment APPENDIX A Survey of Existing Conditions October 3, 2011 DRAFT - 12/19/2011

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35 Panama City Marina Marina Bulkhead Assessment APPENDIX B NAVY Underwater Inspection Report October 3, 2011 DRAFT - 12/19/2011

36 Panama City Pier Inspection Report of Findings from 20JUN2011 DRAFT - 12/19/2011

37 Inspections focused on locating areas of discoloration, cracking, rusting, detection of any misalignments or movements of the seawall, and undermining at the wall s base. Overview On 20 June 2011, students from NDSTC class MEDO/UCTB/2C conducted Level I and II training inspections at the Panama City Marina. DRAFT - 12/19/2011 As per city s request, certain areas of the structure were keyed in as primary and secondary points of interest. Inspection results of these areas are detailed in the following slides.

38 Inspection Areas

39 General Inspection Results Wharf s depth averaged 15 with sand, mud, and shell bottom. Marine growth covered majority of the wall and was approximately 1-2 inches thick in most areas. The wharf was in overall good condition with some cracks, discoloration markings from rusting rebar, damage to concrete, and detached fender pieces (marked areas to follow). DRAFT - 12/19/2011 Exposed joints along concrete seams were identified in numerous locations In several areas, fenders were broken or hanging off the pier. These locations can be seen from the surface.

40 Damaged Areas Reference Point 11 DRAFT - 12/19/

41 Damaged Areas Problem Description 1 Concrete Jet Out Must confirm Jet out is in as-built; SE wall 2 Crack 2.5" wide crack at 1174' from reference point 3 Exposed Joint Runs 5' below surface at 1153' from reference point 4 Concrete Fender Concrete fender laying on the ground; where it came from not found 5 Crack 3 crack 2' from surface at 747' from reference point 6 Crack 2 wide at 735' from reference point 7 Exposed Joint Waterline to seafloor at 710' from reference point 8 Concrete Wearing Concrete is broken off in areas on NW wall of wharf 9-11 Broken Fenders Fenders are hanging and broken off DRAFT - 12/19/2011 *Note: Once exposed joints were found in several locations it was noted as a problem area in general and not marked as damaged area

42 Crack #2 Exposed Joint #3 DRAFT - 12/19/2011 Concrete Fender #4 Crack #6

43 Concrete Wearing #8 Concrete Wearing #8 Broken Fenders #9 Broken Fenders #9 DRAFT - 12/19/2011

44 Typical exposed joints along concrete seams

45 The student led Level I and II inspection of the City Pier revealed that the structure was in overall good condition. Further investigation is recommended on areas previously noted to determine extent of damage. Conclusion DRAFT - 12/19/2011 Level III or destructive testing is recommended to ensure structural concrete is within design parameters.

46 Panama City Marina Marina Bulkhead Assessment APPENDIX C Opinion of Probable Costs October 3, 2011 DRAFT - 12/19/2011

47 Panama City Marina Marina Bulkhead Assessment Table C-1. Preliminary Opinion of Probable Costs for Bulkhead Repair and Replacement Item Item Item Description Quantity Unit Unit Cost Total Sub-Total 1.0 Mobilization/Demobilization (1) 1 % 10.0% $188, General Conditions Item Sub-Total: $188, Demolition and Site Preparation 1 L.S. $125, $125, Item Sub-Total: $125, Replacement of Bulkhead, Cap, and Tie-Back System 3.1. Steel Sheetpile Bulkhead a) AZ-40 46' x 150' x LBF/FT². 135 T $1, $243, b) Epoxy Coating 25' x 150' x 2 7,500 S.F. $2.00 $15, c) Labor and equipment cost 150 L.F. $ $75, Item Sub-Total: $333, Reinforced Concrete Cap (150') a) Concrete 60"Wx24"D x 150'L 56 C.Y. $ $5, b) #6 Rebar 12 T $1, $21, c) #3 Rebar 2 T $1, $3, d) Labor and equipment cost 150 L.F. $ $18, Item Sub-Total: $48, Tie-Back System a) Con. Deadman 20"Wx6'D x 150'L 375 C.Y. $ $37, b) #5 Rebar 1 T $1, $1, c) 1-3/4" dia. 100ksi All-Thread Bar 1,000 L.F. $1.00 $1, d) 6"x6"x1" Steel Plate 45 EA. $26.00 $1, e) Hex Nut for 1-3/4" Bar 45 EA. $4.85 $ f) Bevel Washer for 1-3/4" Bar 45 EA. $28.00 $1, g) Coupling 24 EA. $26.00 $ h) Labor and equipment 150 L.F. $ $75, Item Sub-Total: $118, Repair of Existing Bulkhead 4.1. Concrete Bulkhead a) Bulkhead Repair with New Waler 600 L.F. $ $174, b) Bulkhead Repair 1,770 T $ $256, Item Sub-Total: $430, Reinforced Concrete Cap (2,545') a) Concrete 60"Wx24"D x 2,545'L 945 C.Y. $ $94, b) #6 Rebar 204 T $1, $367, c) #3 Rebar 34 T $1, $61, d) Labor and equipment cost 2,545 L.F. $ $305, Item Sub-Total: $828, L.S. = Lump Sum; C.Y. = Cubic Yard; L.F. = Linear Foot -15% $1,761,841 S.F. = Square Foot; FT = Foot; EA = Each; % = Percentage Total $2,072,754 W = Width; D = Depth; T = Ton; LBF = Pounds +15% $2,383,667 Table C-2. Preliminary Opinion of Probable Costs for Bulkhead Replacement October 3, 2011 DRAFT - 12/19/2011

48 Panama City Marina Marina Bulkhead Assessment Item Item Item Description Quantity Unit Unit Cost Total Sub-Total 1.0 Mobilization/Demobilization (1) 1 % 10.0% $1,402, General Conditions Item Sub-Total: $1,402, Demolition and Site Preparation 1 L.S. $250, $250, Replacement of Bulkhead, Cap, and Tie-Back System Item Sub-Total: $250, Steel Sheetpile Bulkhead a) AZ-40 46' x 1,394' x LBF/FT². 1,394 T $1, $2,509, b) AZ-25 37' x 4,241' x LBF/FT². 4,241 $1, $7,633, c) Epoxy Coating 7,500 S.F. $2.00 $470, d) Labor and equipment cost 5,635 L.F. $ $2,817, Item Sub-Total: $13,431, Reinforced Concrete Cap a) Concrete 60"Wx24"D x 5,635'L 2,087 C.Y. $ $208, b) #6 Rebar 25 T $1, $44, c) #3 Rebar 4 T $1, $7, d) Labor and equipment cost 5,635 L.F. $ $676, Item Sub-Total: $937, Tie-Back System a) Con. Deadman 20"Wx6'D x 5,375'L 1,991 C.Y. $ $199, b) #5 Rebar 29 T $1, $53, c) 1-3/4" dia. 100ksi All-Thread Bar 35,652 L.F. $1.00 $35, d) 6"x6"x1" Steel Plate 1,618 EA. $26.00 $42, e) Hex Nut for 1-3/4" Bar 1,618 EA. $4.85 $7, f) Bevel Washer for 1-3/4" Bar 1,618 EA. $28.00 $45, g) Coupling 809 EA. $26.00 $21, h) Labor and equipment 5,375 L.F. $ $2,687, Item Sub-Total: $3,091, L.S. = Lump Sum; C.Y. = Cubic Yard; L.F. = Linear Foot -15% $16,558,591 S.F. = Square Foot; FT = Foot; EA = Each; % = Percentage Total $19,480,695 W = Width; D = Depth; T = Ton; LBF = Pounds +15% $22,402,800 Notes: (1) Cost based on 10% of all direct construction costs (Item 1.0) (2) This Preliminary Opinion of Probable Cost is based on the results of the field investigations, and it is for budget purposes only. These estimates may be refined during value engineering and final design. (3) This Preliminary Opinion of Probable Cost does not include associated upland features not listed herein (i.e.. access roadways, parking, upland utility infrastructure, lock boxes, etc.) (4) The estimated materials and unit costs represent MRD Associates, Inc. (MRD) best judgment as a professional design firm familiar with the type of proposed construction. MRD has no control over the availability or cost of labor, equipment or materials, market conditions, or the Contractor s methods of pricing. Accordingly, MRD makes no warranty, express or implied, that the actual bids or negotiated prices will not vary from this Preliminary Opinion of Probable Costs. October 3, 2011 DRAFT - 12/19/2011

Estimating Material Requirements

Estimating Material Requirements A CMI Technical White Paper Ben Brown January 2007 Physical properties are defined by ASTM testing standards, The Aluminum Association Design Manual, and/or standard engineering practice. The values shown

More information

PREPARED FOR: NEW BEDFORD HARBOR DEVELOPMENT COMMISSION FLOATING DOCK CONDITION ASSESSMENT REPORT PORT OF NEW BEDFORD POPE S ISLAND MARINA

PREPARED FOR: NEW BEDFORD HARBOR DEVELOPMENT COMMISSION FLOATING DOCK CONDITION ASSESSMENT REPORT PORT OF NEW BEDFORD POPE S ISLAND MARINA PREPARED FOR: NEW BEDFORD HARBOR DEVELOPMENT COMMISSION FLOATING DOCK CONDITION ASSESSMENT REPORT PORT OF NEW BEDFORD POPE S ISLAND MARINA APRIL 14, 2014 Pope s Island Marina Floating Dock Condition Assessment

More information

The Leader in Underwater Piling Repair Technology

The Leader in Underwater Piling Repair Technology Typical Spalling of square concrete piling on a Mooring Dolphin Completed Mooring Dolphin with Structural Jackets Pilecap offers the strongest structural repair in the industry for application on concrete

More information

SECTION CAST-IN-PLACE CONCRETE

SECTION CAST-IN-PLACE CONCRETE SECTION 03300 CAST-IN-PLACE CONCRETE PART 1 GENERAL 1.01 SECTION INCLUDES A. The Contractor shall furnish all work and materials, including cement, sand and coarse aggregate, water, admixtures, curing

More information

TECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS. Financial Project ID , &

TECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS. Financial Project ID , & TECHNICAL SPECIAL PROVISION FOR CONCRETE REPAIRS Financial Project ID 429140-1-52-01, 429140-2-52-01 & 428267-1-52-01 The official record of this Technical Special Provision is the electronic file signed

More information

EVALUATION REPORT. PFC-5551 Reissued April 1, Filing Category: DESIGN Steel (038)

EVALUATION REPORT. PFC-5551 Reissued April 1, Filing Category: DESIGN Steel (038) ICBO Evaluation Service, Inc. 5360 WORKMAN MILL ROAD WHITTIER, CALIFORNIA 90601-2299 A subsidiary corporation of the International Conference of Building Officials EVALUATION REPORT Copyright 2001 ICBO

More information

These guidelines are to ensure systematic and consistent pier construction throughout the Jonathan s Landing development.

These guidelines are to ensure systematic and consistent pier construction throughout the Jonathan s Landing development. PIER GUIDELINES 1 PIER CONSTRUCTION GUIDELINES These guidelines are to ensure systematic and consistent pier construction throughout the Jonathan s Landing development. 1. DEFINITIONS The following definitions

More information

BILL OF QUANTITIES. Construction and Rehabilitation of wadi Gaza Bridges PAL Funded by Government of Brazil

BILL OF QUANTITIES. Construction and Rehabilitation of wadi Gaza Bridges PAL Funded by Government of Brazil United Nations Development Programme Programme of Assistance to the Palestinian People-PAPP Construction and Rehabilitation of wadi Gaza Bridges PAL10-00054031 Funded by Government of Brazil BILL OF QUANTITIES

More information

SECTION A1 EXCAVATION AND BACKFILL GENERAL

SECTION A1 EXCAVATION AND BACKFILL GENERAL SECTION A1 EXCAVATION AND BACKFILL GENERAL The work under this section shall include all excavation to such width and depth as shown on the drawings, specified herein, or ordered by the Engineer. Such

More information

ODOT Design & Construction Requirements for MSE Walls

ODOT Design & Construction Requirements for MSE Walls ODOT Design & Construction Requirements for MSE Walls Peter Narsavage, P.E. Foundation Engineering Coordinator Ohio Department of Transportation Office of Structural Engineering 2006 Ohio Transportation

More information

A Perspective 1. Perspective 2. Perspectives. Kincaid Park Anchorage Alaska. Schematic rendering to represent intent 100% CD.

A Perspective 1. Perspective 2. Perspectives. Kincaid Park Anchorage Alaska. Schematic rendering to represent intent 100% CD. Perspective 1 Schematic rendering to represent intent Perspectives Perspective 2 A.01.1 Over-Under Net Timber! Cave Charlotte's Web Stepping Forms (10) Vertical Net Tree Vine Moose Hollow Log Vine 2 Vine

More information

Marine 15. Planning & Infrastructure for Marina Development

Marine 15. Planning & Infrastructure for Marina Development Marine 15 Planning & Infrastructure for Marina Development Who is this Pompous American? Jesse Ellenz Vice President of Special Projects What Makes Him So Special? Nothing Not a PHD Not a Professor Not

More information

Table of Contents for Guide Specifications

Table of Contents for Guide Specifications Table of Contents for Guide Specifications 01270A Measurement and Payment 01355A Environmental Protection 01356A Storm Water Pollution Prevention Measures 01421 Basic Storm Water Pollution Prevention Plan

More information

Current Trends in Marina Planning and Design

Current Trends in Marina Planning and Design ASSOCIATION OF PACIFIC PORTS 101 st Annual Conference, July 2014 Current Trends in Marina Planning and Design, PE, LEED AP, Reid Middleton Outline Introduction Market & Demand Planning Environmental Design

More information

See the IRC for additional information. See CPD-DS Information Bulletin 100 for Requirements for 1 & 2 Family Dwelling plan submittals.

See the IRC for additional information. See CPD-DS Information Bulletin 100 for Requirements for 1 & 2 Family Dwelling plan submittals. As a customer service initiative, the Kansas City, Missouri, City Planning and Development Department/Development Services, in cooperation with the Greater Kansas City Home Builders Association, has developed

More information

Overturning Forces. 12 times 300 lbs = 3,600 lbs of shear force along top of wall. Shear Wall

Overturning Forces. 12 times 300 lbs = 3,600 lbs of shear force along top of wall. Shear Wall 2,400 lbs of compression Overturning Forces Overturning forces act on all shear walls. However, sometimes a shear wall will be subjected to very strong overturning forces that can damage the shear wall.

More information

Table of Contents. List of Drawings

Table of Contents. List of Drawings SCOPE OF WORK Hastings Stadium Exhibition Park, 81 London Road, Guelph, Ontario Structural and Maintenance Remedial Work Prepared For City of Guelph City Hall, 1 Carden Street, Guelph, ON N1H 3A1 Prepared

More information

ESTIMATE OF QUANTITIES

ESTIMATE OF QUANTITIES ESTIMATE QUANTITIES STATE S.D. SHEET NO. TOTAL SHEETS 2 12 SPECIFICATIONS TEMPORARY PAVEMENT MARKING, Continued STATE S.D. SHEET NO. TOTAL SHEETS 3 12 South Dakota Standard Specifications for Roads and

More information

Introduction Introduction

Introduction Introduction Introduction Maritime International is a leading manufacturer of marine bollards and cleats worldwide. Our range of bollards and cleats is unsurpassed by any other manufacturer or supplier. Maritime can

More information

Chapter A-15. CID-MO Structural Analysis

Chapter A-15. CID-MO Structural Analysis Kansas Citys, Missouri and Kansas Flood Risk Management Feasibility Study Engineering Appendix to the Final Feasibility Study Chapter A-15 CID-MO Structural Analysis Chapter A-15 CID-MO Structural Analysis

More information

MATERIAL ALLOWANCES AND UNIT PRICES

MATERIAL ALLOWANCES AND UNIT PRICES PART 1 - GENERAL 1.1 SECTION INCLUDES ADDITIONS AND RENOVATIONS TO WEST YORK AREA HIGH SCHOOL - #1231 SECTION 012200 MATERIAL ALLOWANCES AND UNIT PRICES A. Measurement and payment criteria applicable to

More information

Bonner Bridge Replacement Update:

Bonner Bridge Replacement Update: Bonner Bridge Replacement Update: Jerry D. Jennings, PE - NCDOT Division 1 Engineer Pablo A. Hernandez, - NCDOT Resident Engineer September 18, 2017 Bonner Bridge Replacement Timeline Refresher Bonner

More information

SPECIAL SPECIFICATION 4900 Sacrificial Cathodic Protection Pile Jacket

SPECIAL SPECIFICATION 4900 Sacrificial Cathodic Protection Pile Jacket 1993 Specifications CSJ 0331-04-045 SPECIAL SPECIFICATION 4900 Sacrificial Cathodic Protection Pile Jacket 1. Description. This Item shall govern for the furnishing, installing and energizing a sacrificial

More information

MOA Project # Golden View Drive Intersection & Safety Upgrades

MOA Project # Golden View Drive Intersection & Safety Upgrades Appropriate transitions can include extending the insulation beyond the roadway improvements, reducing the insulation thickness, or angling the insulation downward. Use of a frost tolerant section, an

More information

SECTION DUCTILE IRON PILES

SECTION DUCTILE IRON PILES SECTION 31 66 13 DUCTILE IRON PILES PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. Work of this Section, as shown or specified, shall be in accordance with the requirements of the Contract Documents. B.

More information

Fence & Guardrail Block Reference Manual ReCon Series 50

Fence & Guardrail Block Reference Manual ReCon Series 50 Fence & Guardrail Block Reference Manual ReCon Series 50 esthetics You Want Performance You Need! Copyright 2011 ReCon Wall Systems, Inc. www.reconwalls.com Introduction t ReCon, we are proud of our tradition

More information

In Service Replacement of Box Girder Bottom Slab

In Service Replacement of Box Girder Bottom Slab In Service Replacement of Box Girder Bottom Slab WSDOT Bridge No. 5/537S - Span 11 Craig R. Boone, P.E., S.E. Lynn Peterson Secretary of Transportation 2015 Western Bridge Engineers Seminar Reno, Nevada

More information

1. Cast-in-place concrete is specified in Section

1. Cast-in-place concrete is specified in Section SECTION 03 38 00 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for furnishing and installing post-tensioned slabs, jacks, jacking and anchors at Parking Structure, and record

More information

Bridge Manual - Part I - June CHAPTER 5 SPECIAL PROVISIONS AND ESTIMATE

Bridge Manual - Part I - June CHAPTER 5 SPECIAL PROVISIONS AND ESTIMATE Bridge Manual - Part I - June 2007 5-1 CHAPTER 5 SPECIAL PROVISIONS AND ESTIMATE 5.1 GENERAL This chapter is intended to instruct the Designer in the preparation and submission of Special Provisions and

More information

The Northern Waterfront Seawall History and Earthquake Performance Waterfront Plan Working Group Meeting April 13, 2016

The Northern Waterfront Seawall History and Earthquake Performance Waterfront Plan Working Group Meeting April 13, 2016 The Northern Waterfront Seawall History and Earthquake Performance Waterfront Plan Working Group Meeting April 13, 2016 Steven Reel, PE - Project Manager, Engineering Division, Port 1 The Northern Waterfront

More information

STREAMBANK RESTORATION DESIGN

STREAMBANK RESTORATION DESIGN STREAMBANK RESTORATION DESIGN WITH VINYL SHEET PILE GRADE CONTROL STRUCTURES BRUCE M. PHILLIPS, M.S., P.E. ABSTRACT Grade control structures are an effective channel stabilization measure which can eliminate

More information

MARINE SPECIALTY CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION FOR COMPUTER BASED TESTING Revised March 2012

MARINE SPECIALTY CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION FOR COMPUTER BASED TESTING Revised March 2012 MARINE SPECIALTY CONTRACTORS GENERAL TRADE KNOWLEDGE EXAMINATION CONTENT INFORMATION FOR COMPUTER BASED TESTING Revised March 2012 The General Trade Knowledge examination will be administered in one session

More information

Item Name Description Unit of Measure Mobilization Per WSDOT Lump Sum

Item Name Description Unit of Measure Mobilization Per WSDOT Lump Sum Page 1 of 6 DESIGN STANDARDS FOR: MEASUREMENT AND PAYMENT Where bids are utilities for construction, repair or alteration for Public Work park projects, the following bid item descriptions and units of

More information

151 First Side. Technical Assignment 2 November 16 th, William J. Buchko. AE 481w Senior Thesis The Pennsylvania State University

151 First Side. Technical Assignment 2 November 16 th, William J. Buchko. AE 481w Senior Thesis The Pennsylvania State University November 16 th, 2007 William J. Buchko AE 481w Senior Thesis The Pennsylvania State University Thesis Advisor: Kevin Parfitt Table of Contents Executive Summary... 3 Structural System Overview Foundation...

More information

SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL

SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL This section covers the furnishing and installation of ductile iron water pipe, fittings, thrust restraint and pipe disinfection. Ductile Iron Pipe MATERIALS

More information

Evaluation of Rehabilitation Alternatives for the Cedar Avenue Bridge

Evaluation of Rehabilitation Alternatives for the Cedar Avenue Bridge Evaluation of Rehabilitation Alternatives for the Cedar Avenue Bridge Mn/DOT Bridge No. 3145 Prepared for Minnesota Department of Transportation and City of Bloomington, Minnesota Prepared by www.meadhunt.com

More information

INDEX FOR SPECIFICATIONS FOR REMOVING CULVERTS AND PLACING CULVERTS SCOPE... 1

INDEX FOR SPECIFICATIONS FOR REMOVING CULVERTS AND PLACING CULVERTS SCOPE... 1 March 2002 No. 400 INDEX FOR SPECIFICATIONS FOR REMOVING CULVERTS AND PLACING CULVERTS 400. 1 SCOPE... 1 400. 2 REMOVING CULVERTS AND TIMBER STRUCTURES 2.1 Concrete and Metal Pipe Culverts... 1 2.2 Structural

More information

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2328 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 03 00

More information

TOWN OF MOUNT PLEASANT WESTCHESTER COUNTY, NEW YORK

TOWN OF MOUNT PLEASANT WESTCHESTER COUNTY, NEW YORK TOWN OF MOUNT PLEASANT WESTCHESTER COUNTY, NEW YORK COST EVALUATION FOR ROLLING HILLS AREA WATER MAIN EXTENSION PROFESSIONAL CONSULTING, LLC. Octagon 10, Office Center 1719 Route 10, Suite 225 Parsippany,

More information

Performance of Mechanically Stabilized Earth walls over compressible soils

Performance of Mechanically Stabilized Earth walls over compressible soils Performance of Mechanically Stabilized Earth walls over compressible soils R.A. Bloomfield, A.F. Soliman and A. Abraham The Reinforced Earth Company, Vienna, Virginia, USA ABSTRACT: Two projects have recently

More information

OPEN CELL. (800) SWC 120. SWC Weld-on. Charts and Pictures courtesy of: 120 o

OPEN CELL. (800) SWC 120. SWC Weld-on. Charts and Pictures courtesy of: 120 o OPEN CELL The OPEN CELL bulkhead, used primarily on docks and similar structures, is a cellular flat sheet pile structure in which each cell s sheet piles are driven in the shape of a U when viewed from

More information

02800 SHADE STRUCTURES

02800 SHADE STRUCTURES 02800 SHADE STRUCTURES for PLAY AREAS ****************************************** SPECIFIER: The shade structure shall utilize a four point hypar system with four columns located a minimum of 10 feet from

More information

Section 2 Supplemental Specification 2.11 High Tension Cable Barrier

Section 2 Supplemental Specification 2.11 High Tension Cable Barrier 2.11 HIGH TENSION CABLE BARRIER 2.11.1 GENERAL This Work consists of the supply, installation, removal, disposal and reinstallation of High Tension Cable Barrier (HTCB) system. 2.11.2 DEFINITIONS AND INTERPRETATION

More information

BILL SUMMARY. March 15, 2018 BILL No. DESCRIPTION AMOUNT

BILL SUMMARY. March 15, 2018 BILL No. DESCRIPTION AMOUNT PROJECT: CONSTRUCTION OF NEW TIMBER WHARF, SOUTHERN BILL No. DESCRIPTION AMOUNT 1 PRELIMINARIES 2 DEMOLISHION WORKS 3 TIMBER WHARF CONSTRUCTION 4 CATWALK CONSTRUCTION BILL SUMMARY 5 CONCRETE WALKWAY CONSTRUCTION

More information

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7)

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7) Page 1 of 7 STONE STRONG SYSTEMS SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7) PART 1: GENERAL 1.01 Description A. Work includes furnishing and installing precast modular

More information

BACKGROUND: SUBSURFACE CONDITIONS:

BACKGROUND: SUBSURFACE CONDITIONS: 2 BACKGROUND: The planned project consists of a prefabricated modular apartment building with underground parking, located on the site bounded by Dexter Avenue N. to the east, multi-story residential/commercial

More information

SECTION CHAIN LINK FENCES AND GATES (GALVANIZED) A. Fence framework, fabric, gates, and accessories.

SECTION CHAIN LINK FENCES AND GATES (GALVANIZED) A. Fence framework, fabric, gates, and accessories. SECTION 02830 CHAIN LINK FENCES AND GATES (GALVANIZED) 1.0 GENERAL 1.1 Section Includes A. Fence framework, fabric, gates, and accessories. B. Excavation for post bases; concrete footing for posts. C.

More information

Implementation of this Special Provision requires a complete understanding of the following documents:

Implementation of this Special Provision requires a complete understanding of the following documents: VIRGINIA DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR Quality Assurance/Quality Control (QA/QC) for the Construction of Deep Foundation Systems for Design-Build and PPTA Contracts November 10, 2009

More information

STANDARD SPECIFICATIONS SECTION TUNNELING. A. Section includes requirements for constructing tunnels 48-inch and larger diameter.

STANDARD SPECIFICATIONS SECTION TUNNELING. A. Section includes requirements for constructing tunnels 48-inch and larger diameter. STANDARD SPECIFICATIONS SECTION 02420 TUNNELING PART 1 GENERAL 1.1 DESCRIPTION A. Section includes requirements for constructing tunnels 48-inch and larger diameter. 1.2 DEFINITIONS A. Carrier Pipe: Sewer

More information

DRAFT TECHNICAL SPECIFICATIONS FOR

DRAFT TECHNICAL SPECIFICATIONS FOR DRAFT TECHNICAL SPECIFICATIONS FOR DETROIT RIVER AOC STONY ISLAND HABITAT RESTORATION PROJECT THE DETROIT RIVER, WAYNE COUNTY, MICHIGAN FOR INFORMATION JANUARY, 2016 Prepared for: FRIENDS OF THE DETROIT

More information

Structural Design of Dam Sluice Gate Walkway Slabs: Retrofit and Replacement Options

Structural Design of Dam Sluice Gate Walkway Slabs: Retrofit and Replacement Options Structural Design of Dam Sluice Gate Walkway Slabs: Retrofit and Replacement Options A local utility company issued a Request for Proposal to our university s capstone design class for structural improvements

More information

Stainless Steel Aeration Equipment Specification

Stainless Steel Aeration Equipment Specification Section 15 Stainless Steel Aeration Equipment Specification Part 1 - General 1.01 Description A. Scope of Work 1. Furnish, install and test aeration system including air mains, drop pipes, valves, expansion

More information

PUBLIC WORKS SKAGIT COUNTY SAMISH ISLAND ROAD SAMISH ISLAND ROAD SLIDE REPAIR

PUBLIC WORKS SKAGIT COUNTY SAMISH ISLAND ROAD SAMISH ISLAND ROAD SLIDE REPAIR EASEMENT NOTES:. EASEMENT LIMIT SHOWN AS PROVIDED BY. TESC NOTES:. CONTRACTOR SHALL DEVELOP TEMPORARY EROSION AND SEDIMENT CONTROL PLAN AND PROVIDE ONSITE CERTIFIED EROSION AND SEDIMENT CONTROL LEAD (CESCL)

More information

ADDENDUM No. 6. ITB No. 4424: W.R. Wheeler (Swift Run) Service Center PUD Non-motorized Improvements Phase 1

ADDENDUM No. 6. ITB No. 4424: W.R. Wheeler (Swift Run) Service Center PUD Non-motorized Improvements Phase 1 ADDENDUM No. 6 ITB No. 4424: W.R. Wheeler (Swift Run) Service Center PUD Non-motorized Improvements Phase 1 Due: June 9, 2016 at 2:00 p.m. (local time) The following changes, additions, and/or deletions

More information

DIVISION 03 CONCRETE SPECIFICATION : FORMS AND FORMWORK

DIVISION 03 CONCRETE SPECIFICATION : FORMS AND FORMWORK DIVISION 03 CONCRETE SPECIFICATION 031000: FORMS AND FORMWORK PART 1.0 GENERAL 1.1 DESCRIPTION The work of this specification includes furnishing of all labor, materials, equipment and incidentals to install,

More information

Smarter. Safer. Leaner.

Smarter. Safer. Leaner. Smarter. Safer. Leaner. Fast Installation and Removal Decrease Leading Edge Exposure by 87% OSHA Compliant Versatile and Reusable Use Perimeter Protection Posts During Construction: At Building Perimeter

More information

CHAIN LINK FENCES AND GATES

CHAIN LINK FENCES AND GATES SECTION 02831 CHAIN LINK FENCES AND GATES PART 1 GENERAL 1.01 SUMMARY A. Alternate Material for Fence Post and Framing Material: Where schedule 40 galvanized steel is specified, the following will be accepted:

More information

Media Release # 4. Melville Bay East Arnhem Land Mud Wharf Community Project Stages 7c & 7d

Media Release # 4. Melville Bay East Arnhem Land Mud Wharf Community Project Stages 7c & 7d Media Release # 4. Melville Bay East Arnhem Land Mud Wharf Community Project Stages 7c & 7d. 10.07.2016 Work is now underway on the next Stage of the Community Boat Ramp works as part of the $500,000 commitment

More information

CHAPTER 5 - RUBBLE-MOUND STRUCTURES SECTION 1. STRUCTURAL COMPONENTS

CHAPTER 5 - RUBBLE-MOUND STRUCTURES SECTION 1. STRUCTURAL COMPONENTS CHAPTER 5 - RUBBLE-MOUND STRUCTURES SECTION 1. STRUCTURAL COMPONENTS 5.1.1 MOUND. A mound is an artificial embankment or ridge composed of sand, gravel, and cobbles, constructed on the oceanic floor by

More information

PAUL ZICK, PE NORTH SHORE CONSTRUCTORS JV

PAUL ZICK, PE NORTH SHORE CONSTRUCTORS JV NORTH SHORE CONNECTOR TUNNELS AND STATION SHELL LIGHT RAIL PROJECT PAUL ZICK, PE NORTH SHORE CONSTRUCTORS JV North Shore Connector Alignment 7300 lf Extension to existing 25 mile system 18 Contracts $435

More information

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING P.O. Box 599 - Mars, PA 16046 800-321-3337 SECTION 07555 COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

ASPA Pier C North Rehabilitation Phase 2 DOCK UPGRADE ADDENDUM # 4

ASPA Pier C North Rehabilitation Phase 2 DOCK UPGRADE ADDENDUM # 4 ASPA Pier C North Rehabilitation Phase 2 DOCK UPGRADE ADDENDUM # 4 Bid Opening Date is changed from September 28, 2012 at 2:00 PM to October 5, 2012 at 2:00 PM. Revise the first and last paragraphs of

More information

TECHNICAL SESSION 3. Strengthening, Repair & Rehabilitation

TECHNICAL SESSION 3. Strengthening, Repair & Rehabilitation TECHNICAL SESSION 3 Strengthening, Repair & Rehabilitation 2004 PTI Technical Session 3 T. Theryo, P. Garcia - Repair of Sunshine Skyway Bridge The Post-Tensioning Column Repair of High Level Approaches

More information

We have engaged Beacon Construction Consultants to act as the price estimate reviewer.

We have engaged Beacon Construction Consultants to act as the price estimate reviewer. Stantec Consulting Ltd. 400-655 Tyee Road Victoria BC V9A 6X5 Tel: (250) 388-9161 Fax: (250) 382-0514 June 10, 2010 File: 1123-10987 (rev) City of Victoria #1 Centennial Square Victoria, BC V8W 1P6 Attention:

More information

Alternative No. 1 Total Cost DRAFT

Alternative No. 1 Total Cost DRAFT OPINION OF PROBABLE PROJECT COSTS SUMMARY OF ALL THREE ALTERNATIVE ALIGNMENTS Item Description Alternative No. 1 Total Cost Alternative No. 2 Total Cost Alternative No. 3 Total Cost Design Phase 1. Preliminary

More information

GARAGES/ONE-STORY City of Grand Rapids Building Safety Division

GARAGES/ONE-STORY City of Grand Rapids Building Safety Division GARAGES/ONE-STORY City of Grand Rapids Building Safety Division 218-326-7601 www.cityofgrandrapidsmn.com This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building

More information

BILL OF QUANTITY ENGINEERING & MANAGEMENT CONSULTING CENTRE. "Beit Hanoun Emergency Water Supply Project"

BILL OF QUANTITY ENGINEERING & MANAGEMENT CONSULTING CENTRE. Beit Hanoun Emergency Water Supply Project "Beit Hanoun Emergency Water Supply Project" " Rehabilitation and Construction of Beit Hanoun Water Network " BILL OF QUANTITY ENGINEERING & MANAGEMENT CONSULTING CENTRE Bill of Quantities PREAMBLE TO

More information

DIVISION 04 MASONRY CAST STONE. A. Design Considerations. 1. Cast stone shall comply with ASTM C1364, Standard Specification for Cast Stone.

DIVISION 04 MASONRY CAST STONE. A. Design Considerations. 1. Cast stone shall comply with ASTM C1364, Standard Specification for Cast Stone. DIVISION 04 MASONRY 04720 CAST STONE A. Design Considerations 1. Cast stone shall comply with ASTM C1364, Standard Specification for Cast Stone. 2. Care must be taken in the design of individual units

More information

STANDARD SPECIFICATION FOR CRIBLOCK CONCRETE CRIBWALL

STANDARD SPECIFICATION FOR CRIBLOCK CONCRETE CRIBWALL STANDARD SPECIFICATION FOR CRIBLOCK CONCRETE CRIBWALL 1. SCOPE 2. DESIGN 3. MATERIALS 4. CONSTRUCTION 5. METHOD OF MEASUREMENT AND PAYMENT SCOPE This Specification sets out requirements for the design,

More information

SECTION XXXXX AGGREGATE PIERS PART 1 - GENERAL

SECTION XXXXX AGGREGATE PIERS PART 1 - GENERAL SECTION XXXXX AGGREGATE PIERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 00 and Division

More information

SECTION 26 - COLD PLANE ASPHALT CONCRETE PAVEMENT TABLE OF CONTENTS

SECTION 26 - COLD PLANE ASPHALT CONCRETE PAVEMENT TABLE OF CONTENTS SECTION 26 - COLD PLANE ASPHALT CONCRETE PAVEMENT TABLE OF CONTENTS Section Page 26-1 GENERAL... 26.1 26-2 PAVEMENT KEYCUTTING... 26.1 26-3 PAVEMENT PLANING... 26.2 26-4 PLANED PAVEMENT CONFORMS... 26.3

More information

SECTION UNIT PRICES. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION UNIT PRICES. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 012200 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

Evaluation of New Concrete Shrinkage Reducing Additive for Glen Elder Dam Spillway Inlet Slab Repair

Evaluation of New Concrete Shrinkage Reducing Additive for Glen Elder Dam Spillway Inlet Slab Repair Memorandum Number MERL 2011-34 Evaluation of New Concrete Shrinkage Reducing Additive for Glen Elder Dam Spillway Inlet Slab Repair Missouri River Basin Project Solomon Division Glen Elder Unit - Kansas

More information

PUBLIC NOTICE LOS ANGELES DISTRICT. APPLICATION FOR PERMIT Port of Los Angeles Berths : Wilmington Waterfront Promenade

PUBLIC NOTICE LOS ANGELES DISTRICT. APPLICATION FOR PERMIT Port of Los Angeles Berths : Wilmington Waterfront Promenade PUBLIC NOTICE U.S. ARMY CORPS OF ENGINEERS LOS ANGELES DISTRICT BUILDING STRONG APPLICATION FOR PERMIT Port of Los Angeles Berths 182-186: Wilmington Waterfront Promenade Public Notice/Application No.:

More information

County of Orange. Dana Point Marinas Workshop No. 5. Marina Planning. Meeting No. 6. January 30, 2007 CASH &

County of Orange. Dana Point Marinas Workshop No. 5. Marina Planning. Meeting No. 6. January 30, 2007 CASH & County of Orange Dana Point Marinas Workshop No. 5 Marina Planning Meeting No. 6 January 30, 2007 CASH & Dana Point Marinas Project Considerations Age & Dock Condition Existing Boater Feedback Design Criteria

More information

Site Investigation Report

Site Investigation Report Client Name : Mr Client Address : 20 Sample Street in 6026 Kingsley, WA Our Reference : 01548 Site Investigation Report Property : 20 Sample Street in 6026 Kingsley, WA Inspection Date : 27.04.2011 Weather

More information

SPECIAL CONDITIONS FOR PIPE JACKING (PJ) October, 2006

SPECIAL CONDITIONS FOR PIPE JACKING (PJ) October, 2006 Michigan Department Of Transportation 3703C (11/06) 1 Materials 1.1 Pipe SPECIAL CONDITIONS FOR PIPE JACKING (PJ) October, 2006 Page 1 of 5 The type of pipe used for the pipe jacking method shall be capable

More information

03 CONCRETE TAKEOFF SUMMARY REPORT Takeoff and Items Cost Summary. Ryan Manocchio

03 CONCRETE TAKEOFF SUMMARY REPORT Takeoff and Items Cost Summary. Ryan Manocchio 03 CONCRETE TAKEOFF SUMMARY REPORT Takeoff and Items Cost Summary Ryan Manocchio rmanocchio@stackct.com Concrete Takeoff Summary Report The STACK To Go Team is capable of performing takeoff for concrete

More information

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM Page 1 of 6 SECTION 08 32 20 LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS SLIDING DOORS. SECTION INCLUDES OVERHEAD SLIDING TUBE ASSEMBLY, MOUNTING

More information

BRIDGEHAVEN MARINA CONDITION ASSESSMENT

BRIDGEHAVEN MARINA CONDITION ASSESSMENT BRIDGEHAVEN MARINA CONDITION ASSESSMENT April 14, 2017 Draft Technical Memorandum Bridgehaven Marina Condition Assessment 1. Introduction This technical memorandum outlines the results of a reconnaissance

More information

Instructions for 12 IGT system

Instructions for 12 IGT system Instructions for 12 IGT system Step 1: IGT Site Preparation Site Location Several factors must be considered when choosing the site for your new In-Ground Trampoline (IGT) system. Since local soil and

More information

STRUCTURAL CONDITION ASSESSMENT

STRUCTURAL CONDITION ASSESSMENT STRUCTURAL CONDITION ASSESSMENT ALLEN JAY ROCK GYM 1201 FAIRFIELD ROAD HIGH POINT, NC Prepared for: Prepared by: Guilford County Schools 617 West Market Street Greensboro, NC Adrian S. Durham, PE, SE,

More information

Copyright. magazine. CFS Load Bearing Construction

Copyright. magazine. CFS Load Bearing Construction Progressive Collapse Requirements Cold-Formed Steel Load Bearing Construction By Nabil A. Rahman, Ph.D., P.E., Michael Booth and Gary Bennett Figure 1: Cold formed steel load bearing mid-rise construction.

More information

US 278 East Bound and West Bound. MacKay Creek and Skull Creek. Cursory Above Water and Underwater Investigation Of. Over

US 278 East Bound and West Bound. MacKay Creek and Skull Creek. Cursory Above Water and Underwater Investigation Of. Over Cursory Above Water and Underwater Investigation Of US 278 East Bound and West Bound Over MacKay Creek and Skull Creek In Hilton Head, South Carolina Bridges over MacKay Creek Bridges over Skull Creek

More information

Structural Assessment Live Fire Training Building. FSCJ South Campus Jacksonville, Florida. Florida State College at Jacksonville

Structural Assessment Live Fire Training Building. FSCJ South Campus Jacksonville, Florida. Florida State College at Jacksonville Structural Assessment Live Fire Training Building FSCJ South Campus Jacksonville, Florida Florida State College at Jacksonville November 21, 2011 Report of a Structural Assessment of Live Fire Training

More information

Redi Rock Specification and Installation Manual

Redi Rock Specification and Installation Manual Redi Rock Specification and Installation Manual 1.0 General Scope This Specification covers the Design, Materials and Installation of Redi Rock modular block Retaining and Freestanding Wall systems as

More information

Lesner Bridge Replacement

Lesner Bridge Replacement Lesner Bridge Replacement Rendering of the Completed Lesner Bridge Structure Construction Camera A Construction Camera has been installed to view images of the bridge construction. Images are updated on

More information

Cantilevered Rail System

Cantilevered Rail System Knight Global's Cantilevered Rail Systems are designed to eliminate the need for a four post floor structure system. It provides an alternative to workstations with minimal floor space. A wide range of

More information

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards SECTION 07185 TRAFFIC MEMBRANE PART 1 GENERAL 1.1 SECTION INCLUDES A. Traffic membrane, consisting of welded seam PVC waterproofing, over f following surfaces: 1. Decks, balconies, and sun porches 2. Walkways,

More information

Stay-Cable Replacement Design

Stay-Cable Replacement Design Stay-Cable Replacement Design Mississippi River Bridge Luling, Louisiana Christopher Ligozio CTLGroup Copyright Post-Tensioning Institute all rights reserved. Page 1 of 35 Luling Bridge Copyright Post-Tensioning

More information

MMM Group Limited. Eagle Island Pier Inspection Report. Prepared for: District of West Vancouver. July

MMM Group Limited. Eagle Island Pier Inspection Report. Prepared for: District of West Vancouver. July MMM Group Limited Eagle Island Pier Inspection Report Prepared for: District of West Vancouver July 2013 5013307-001 STANDARD LIMITATIONS This report was prepared by MMM Group (MMM) for the account of

More information

DIVISION: EARTHWORK SECTION: BORED PILES REPORT HOLDER: CANTSINK MANUFACTURING, INC. 71 FIRST AVENUE LILBURN, GEORGIA 30047

DIVISION: EARTHWORK SECTION: BORED PILES REPORT HOLDER: CANTSINK MANUFACTURING, INC. 71 FIRST AVENUE LILBURN, GEORGIA 30047 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1559 Reissued 12/2016 This report is subject to renewal 12/2018. DIVISION: 31 00

More information

SECTION REINFORCING STEEL

SECTION REINFORCING STEEL SECTION REINFORCING STEEL 1. DESCRIPTION This specification shall govern the furnishing and placing of reinforcing steel, deformed and smooth, of the size and quantity designated on the plans and in accordance

More information

Atlantic Coast of New York East Rockaway Inlet to Rockaway Inlet and Jamaica Bay, NY

Atlantic Coast of New York East Rockaway Inlet to Rockaway Inlet and Jamaica Bay, NY Atlantic Coast of New York East Rockaway Inlet to Rockaway Inlet and Jamaica Bay, NY Draft Reformulation Public Information October 2016 US Army Corps of Engineers Presentation Outline Project Overview

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person

More information

DESIGN CONSIDERATIONS FOR NSWS NATURAL STONE RETAINING AND FREE-STANDING WALL SYSTEMS

DESIGN CONSIDERATIONS FOR NSWS NATURAL STONE RETAINING AND FREE-STANDING WALL SYSTEMS DESIGN CONSIDERATIONS FOR NSWS NATURAL STONE RETAINING AND FREE-STANDING WALL SYSTEMS Natural Stone Wall Solutions, Inc (NSWS ) 2352 Main Street, Suite 103 Concord, MA 01742 (978) 461-1777 Concept and

More information

TECHNOLOGY. Graphic Provided by L.B. Foster Company. All Rights Reserved.

TECHNOLOGY. Graphic Provided by L.B. Foster Company. All Rights Reserved. OPEN CELL SHEET PILE TM TECHNOLOGY Graphic Provided by L.B. Foster Company. All Rights Reserved. PND ENGINEERS, INC. OPEN CELL TM STRUCTURE LOCATIONS OPEN CELL structures can be found throughout the world,

More information

DIVISION: EARTHWORK SECTION: BORED PILES REPORT HOLDER: HELICAL ANCHORS, INC BOONE AVENUE, NORTH MINNEAPOLIS, MINNESOTA 55428

DIVISION: EARTHWORK SECTION: BORED PILES REPORT HOLDER: HELICAL ANCHORS, INC BOONE AVENUE, NORTH MINNEAPOLIS, MINNESOTA 55428 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3982 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 31 00

More information

ITEM D-701 PIPE FOR STORM DRAINS AND CULVERTS

ITEM D-701 PIPE FOR STORM DRAINS AND CULVERTS ITEM D-701 PIPE FOR STORM DRAINS AND CULVERTS 701-1 DESCRIPTION 701-1.1 This item shall consist of the construction of pipe culverts, and storm drains, removal of existing storm pipes, connections to existing

More information