1 Forterra Building Products Limited 5 Grange Park Court Roman Way Northampton NN4 5EA Tel: Fax: asktechnical@forterra.co.uk website: APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL APPROVALS FOR CONSTRUCTION Agrément Certificate 14/5114 Product Sheet 1 FORTERRA CLADDING SYSTEMS WONDERWALL 1 CLAY BRICK SLIP CLADDING SYSTEM This Agrément Certificate Product Sheet (1) relates to the Wonderwall 1 Clay Brick Slip Cladding System, an insulated backer board and clay brick slip system for use as protective/decorative cladding over external masonry, concrete, timber and steel-frame substrate walls of new and existing domestic and non-domestic buildings. (1) Hereinafter referred to as Certificate. CERTIFICATION INCLUDES: factors relating to compliance with Building Regulations where applicable factors relating to additional non-regulatory information where applicable independently verified technical specification assessment criteria and technical investigations design considerations installation guidance regular surveillance of production formal three-yearly review. KEY FACTORS ASSESSED Strength and stability the system can be designed to transfer the design wind loads to the substrate wall (see section 6). Behaviour in relation to fire the system may be regarded as having a designated A1 surface to in England and Wales and low risk in Scotland in accordance with the national Building Regulations (see section 7). Thermal properties the system can contribute to the overall thermal performance of the wall construction (see section 9). Condensation risk the system can contribute to limiting the risk of interstitial and surface condensation (see section 10). Weathertightness the system resists water penetration and the risk of damage to the inner wall (see section 11). Durability the system has adequate durability and an ultimate service life exceeding 25 years (see section 13). The BBA has awarded this Certificate to the company named above for the system described herein. This system has been assessed by the BBA as being fit for its intended use provided it is installed, used and maintained as set out in this Certificate. On behalf of the British Board of Agrément Date of First issue: 23 April 2014 Brian Chamberlain Claire Curtis-Thomas Head of Approvals Engineering Chief Executive Certificate amended on 30 September 2015 to update front page information. The BBA is a UKAS accredited certification body Number 113. The schedule of the current scope of accreditation for product certification is available in pdf format via the UKAS link on the BBA website at Readers are advised to check the validity and latest issue number of this Agrément Certificate by either referring to the BBA website or contacting the BBA direct. British Board of Agrément tel: Bucknalls Lane fax: Watford mail@bba.star.co.uk Herts WD25 9BA 2014 website: Page 1 of 15

2 Regulations In the opinion of the BBA, the Wonderwall 1 Clay Brick Slip Cladding System, if installed, used and maintained in accordance with this Certificate, will meet or contribute to meeting the relevant requirements of the following Building Regulations (the presence of a UK map indicates that the subject is related to the Building Regulations in the region or regions of the UK depicted): The Building Regulations 2010 (England and Wales) (as amended) Requirement: A1 Loading The system can sustain and transmit wind loads to the substrate. See sections 4.3, 4.4, 4.6 and 6.2 of this Certificate. Requirement: B4(1) External fire spread The system outer surface is designated A1 and, therefore, meets this requirement. See sections 7.1 to 7.4 and 7.6 to 7.8 of this Certificate. Requirement: C2(b) Resistance to moisture The system will resist the passage of rainwater to the supporting structure. See sections 11.1 to 11.8 of this Certificate. Requirement: C2(c) Resistance to moisture The system contributes to minimising the risk of surface and interstitial condensation. See section 10.1 of this Certificate. Requirement: L1(a)(i) Conservation of fuel and power The system can contribute to meeting this Requirement. See sections 9.1 to 9.4 of this Certificate. Regulation 7 Materials and workmanship The system is acceptable. See section 13 and the Installation part of this Certificate. Requirement: 26 CO 2 emission rates for new buildings Requirement 26A Fabric energy efficiency rates for new dwellings (in England only) Walls incorporating the system can contribute to meeting the Target Emission Rate. See sections 9.1 to 9.4 of this Certificate. The Building (Scotland) Regulations 2004 (as amended) Regulation: 8(1)(2) Durability, workmanship and fitness of materials The use of the system satisfies the requirements of this Regulation. See sections 12.1, 13 and the Installation part of this Certificate. Regulation: 9 Building standards applicable to construction Standard: 1.1(b) Structure The system can sustain and transmit wind loads to the substrate. See sections 4.3, 4.4, 4.6 and 6.2 of this Certificate. Standard: 2.6 Spread to neighbouring buildings The system can contribute to satisfying this Standard, with reference to clauses (1)(2), (1)(2), (1)(2), (1) and (2). See sections See sections 7.1 to 7.8 of this Certificate of this Certificate. Standard: 2.7 Spread on external walls The system can contribute to satisfying this Standard, with reference to clause (1)(2) and Annex 2A (1). See sections 7.1 to 7.8 of this Certificate. Standard: 3.10 Precipitation The system will resist the passage of rainwater to the inner face of the wall, with reference to clauses (1)(2), (1)(2) and (1)(2). See sections 11.1 to 11.8 of this Certificate. Standard: 3.15 Condensation The system will satisfy the requirements of clauses (1), (1), (1) and (1) of this Standard. See section 10.1 of this Certificate. Standard: 6.1 Carbon dioxide emissions Standard: 6.2 Building insulation envelope The system can contribute to a building achieving the Target Emissions Rate, with reference to clauses (or parts of) (1)(2), (1), (1)(2), (1), (1)(2), (1)(2), (2) and (2). See sections 9.1 to 9.4 of this Certificate. Standard: 7.1(a)(b) Statement of sustainability The system can contribute to meeting the relevant Requirements of Regulation 9, Standards 1 to 6, and, therefore, will contribute to a construction meeting a bronze level of sustainability as defined in this Standard. In addition, the system can contribute to a construction meeting a higher level of sustainability as defined in this Standard, with reference to clauses (1)(2) [Aspects 1 (1)(2) and 2 (1) ], (1)(2) [Aspects 1 (1)(2) and 2 (1) ] and (1)(2) [Aspect 1 (1)(2) ]. See sections 9.1 to 9.4 of this Certificate. Regulation: 12 Building standards applicable to conversions All comments given for these systems under Regulation 9, also apply to this Regulation, with reference to clause (1)(2) and Schedule 6 (1)(2). (1) Technical Handbook (Domestic). (2) Technical Handbook (Non-Domestic). Page 2 of 15

3 The Building Regulations (Northern Ireland) 2012 Regulation: 23(a)(i)(iii)(b) Fitness of materials and workmanship The system is acceptable. See section 13 and the Installation part of this Certificate. Regulation: 28 Resistance to moisture and weather The system will satisfy this Regulation. See sections 11.1 to 11.8 of this Certificate. Regulation: 29 Condensation The system will satisfy the requirements of this Regulation. See section 10.1 of this Certificate. Regulation: 30 Stability The system is acceptable as set out in sections 4.3, 4.4, 4.6 and 6.2 of this Certificate. Regulation: 36 External fire spread The system is judged to meet this requirement. See sections 7.1 to 7.4 and 7.6 to 7.8 of this Certificate. Regulation: 39(a)(i) Conservation measures Regulation: 40(2) Target carbon dioxide emissions rate The system will contribute to a building satisfying its target emission rate. See sections 9.1 to 9.4 of this Certificate. Construction (Design and Management) Regulations 2007 Construction (Design and Management) Regulations (Northern Ireland) 2007 Information in this Certificate may assist the client, CDM co-ordinator, designer and contractors to address their obligations under these Regulations. See section: Additional Information NHBC Standards Delivery and site handling (3.2 and 3.4) and 15 Installation General (15.2) of this Certificate. NHBC accepts the use of Wonderwall 1 Clay Brick Slip Cladding System, when installed, used and maintained in accordance with this Certificate, in relation to NHBC Standards, Chapter 6.2 External timber framed walls, Chapter 6.9 Curtain walling and cladding and Chapter 6.10 Light steel framed walls and floors. Technical Specification 1 Description 1.1 The Wonderwall 1 Clay Brick Slip Cladding System (see Figure 1) comprises: backerboard 1200 mm wide by 2400 mm in length composite panels consisting of a 0.75 mm thick high impact polystyrene (HIPS) profiled carrier sheet, bonded to a 25 mm or 50 mm thick rigid phenolic foam insulation board (density of 42 kg m 3 ) manufactured in accordance with BS EN : 2012 with a foil covering internal face. The HIPS carrier sheet is formed with horizontal bed joint ribs, at 75 mm centres, to aid application of brick slips brick slip adhesive a one part polyurethane elastic adhesive (Korapur 126 grau) and applied in a 10 mm diameter bead to the backerbord panel to attach the brick slips clay brick slip up to 215 mm in length, 65 mm in height and thicknesses between 18 mm and 30 mm, and available in a range of colours and finishes. Other lengths are available and the Certificate holder s advice must be sought on these. The brick slips are frost resistant, and classified as durability designation F2, in accordance with BS EN : L-shaped bricks are also available for external corners pointing grout/mortar cement based mortar mix to class 12, 6 or 4 in accordance with BS EN : 2010, or site batched mortar of equivalent specification to mortar mix designation (i), (ii) or (iii) in accordance with PD 6697 : 2010 and agreed with the Certificate holder. Page 3 of 15

4 Figure 1 Typical Wonderwall 1 Brick Slip Cladding System 10 mm diameter continuous brickslip adhesive pointing grout mortar drainage channel brickslip flat profile to rib phenolic insulation curved profile to rib ribbed sheet 1.2 Ancillary components for use with the system, but outside the scope of the Certificate: substrate wall starter rail aluminium L-shape, 2400 mm long, 60 mm by 35 mm silicone sealant in accordance with BS EN ISO : 2003 used as a decorative coat only and applied over Ralliflame Caulk 360 joint sealant or other proprietary mastic brand in accordance with BS 6213 : 2000 adhesive bead 5 mm bead applied along vertical edge between adjacent backerboard panels fixings zinc coated, black phosphorous coated or stainless steel screws with plugs tailored to suit timber or steelframe, masonry, dense and no-fines concrete substrates support timber battens minimum 75 mm wide by 20 mm deep to support the backerboard panels in timber frame construction and to create a minimum 20 mm cavity support steel rails minimum 75 mm wide by 20 mm deep to support the backerboard panels in steel frame construction and to create a minimum 20 mm cavity sheathing minimum 9 mm cement particle board installed behind the backerboard movement joints additional insulation where used between substrate wall and backerboard component. 2 Manufacturing 2.1 The backerboard insulation component is manufactured to BS EN : The clay brick slips are fired, using conventional clay moulding techniques, extruded or cut from standard facing bricks. 2.3 As part of the assessment and ongoing surveillance of product quality, the BBA has: agreed with the manufacturer the quality control procedures and product testing to be undertaken assessed and agreed the quality control operated over batches of incoming materials monitored the production process and verified that it is in accordance with the documented process evaluated the process for management of nonconformities checked that equipment has been properly tested and calibrated undertaken to carry out the above measures on a regular basis through a surveillance process to verify that the specifications and quality control operated by the manufacturer are being maintained. 3 Delivery and site handling 3.1 The backerboard panels are delivered to site on pallets wrapped in polythene. Each pallet bears a ticket number. 3.2 The panels must be stored flat, level, clear of the ground on pallets out of direct sunlight and in dry conditions. Panels should ideally be stored indoors, however, if should short-term storage outdoors be necessary, the backerboard must be covered with tarpaulin. Backerboard panels must not be exposed to sunlight for more than 48 hours and volatile organic solvents. Page 4 of 15

5 3.3 Brick slips are supplied on pallets and wrapped in purpose-made bags. 3.4 Containers of adhesive, mortar, sealants and expanding foam should be stored in dry conditions and protected against frost and excessive heat. Adhesive and mortar must be used within the time span indicated on the packaging or the supplier s guidelines. Assessment and Technical Investigations The following is a summary of the assessment and technical investigations carried out on the Wonderwall 1 Clay Brick Slip Cladding System. Design Considerations 4 General 4.1 The Wonderwall 1 Clay Brick Slip Cladding System, is suitable for use as a durable non-structural weather resistant, thermally insulating external protective and decorative cladding finish for application on external vertical walls of new or refurbished buildings less than 18 m in storey height of solid and cavity masonry, dense or no-fines concrete, timber frame or light gauge steel frame construction. 4.2 The system will improve the weather resistance of a wall and provide a decorative finish. However, it may only be installed where other routes for moisture penetration have been dealt with separately and where dampness, other than that caused solely by condensation, is not evident on the inner surface of the wall. The system can contribute to minimising condensation on internal wall surfaces. 4.3 Existing buildings subject to national Building Regulations should have wall surfaces in accordance with section 4.5 of this Certificate. 4.4 New buildings subject to national Building Regulations should be constructed in accordance with the relevant recommendations of: BS EN : 2005, BS EN : 2005, BS EN : 2006 and BS EN : 2006 BS : Other buildings, not subject to any of the previous requirements should also be built in accordance with requirements given in section The substrate to which the boards are fixed must be structurally sound and constructed in accordance with the requirements of the relevant national Building Regulations and Standards thus: Timber stud walls and timber battens must be structurally sound, designed and constructed in accordance with BS EN : 2004, and preservative treated in accordance with BS EN : 2007 Galvanized steel framework must be structurally sound, designed and constructed in accordance with BS EN : 2005 and BS EN : 2006 New masonry buildings subject to national Building Regulations should be constructed in accordance with the relevant recommendations of BS EN : 2005, BS EN : 2005, BS EN : 2006 and BS EN : The system transfers its self-weight and design wind loads to the backing wall. The substrate and any supporting framework should be capable of resisting the associated loads. Particular care is required around window and door openings to ensure that the structure is capable of sustaining the additional weight of the system. 4.8 The system does not make any contribution to the overall structural performance of the building and must not be used for the support of any temporary structure. 4.9 In severe exposure conditions, application of a high performance breather membrane to the substrate wall should be considered All externally exposed perimeters of, and penetrations through, the composite insulation panel (backerboard) must be protected by non-combustible material The fixing of rainwater goods, satellite dishes, clothes lines, hanging baskets and similar items is outside the scope of this Certificate. 5 Practicability of installation The system is designed to be installed by installers who have been trained, approved and monitored by the Certificate holder. 6 Strength and stability 6.1 A suitably qualified and experienced individual must check the design and installation of the cladding system to provide adequate resistance to design loads applicable in the UK. Page 5 of 15

6 6.2 Design wind actions should be calculated in accordance with BS EN : 2005 and the UK National Annex. Due consideration should be given to the higher-pressure coefficients applicable to corners of the building as recommended in this Standard. 6.3 The contribution of the cladding system on the stability of the substrate is assumed to be negligible. The substrate wall without the Wonderwall 1 Clay Brick Slip Cladding System must be able to take the full wind actions, racking loads and the weight of the cladding system. A typical construction comprising 50 mm thick phenolic foam composite insulation backerboard, adhesive and pointed with 20 mm thick brick slips weighs 53.4 kg m 2. The adequacy of the substrate wall is outside the scope of this Certificate and must be verified by a suitably qualified and experienced individual. 6.4 Positive wind load (pressure) is transferred to the substrate wall directly via bearings and compression of the brick slips and backerboard. 6.5 Negative wind pressure (suction) is resisted by the bond between each component. The backerboard is retained by fixings. 6.6 Fixing type and spacing must be designed on a project specific basis. The maximum distance between fixings is 600 mm horizontally and 225 mm vertically as shown in Figure 2. Figure 2 Fixing layout of backerboard Front elevation Tests carried out confirm that when fixed directly to a solid substrate wall or through vertical support battens at maximum 600 mm centres to framed substrate walls, the system has a characteristic wind load resistance of 2 kn m 2 without damage or permanent deformation, provided the designer ensures: the fixing of the system to the substrate wall has adequate pull-out resistance (not covered by this Certificate) for the calculated loads. The characteristic pull-out resistance of the fixings to be used for securing the system to the substrate wall should be determined in accordance with the guidance given in ETAG 014 : 2002 Annex D. design of the supporting framework is such that the maximum deflection does not exceed 1/350 of its span the vertical support battens are no more than 600 mm centres apart. 6.8 Tests carried out confirm that the bond strength between brick slips and insulated panel is 0.08 N mm 2 in accordance with the requirements of ETAG 004. Page 6 of 15

7 Impact resistance 6.9 When tested for hard and soft body impacts, the cladding system installed on solid and timber-frame substrates, achieved adequate resistance for use in areas classified as E 2, E 3, E 4 and E 5 as defined in Table 3.1 of MOAT 043 : 1987 (an extract of which is reproduced in Table 1). The system when installed on steel frame substrates, with vertical support at no more than 600 mm centre, will have similar impact resistance. Table 1 Classification of opaque vertical components according to the extent of exposure to external impacts Category Description Examples of components (1) E 2 Readily accessible to public and others with little incentive to exercise care. Chance of accident occurring and of misuse E 2 Above zone of normal impacts from people but liable to impacts from thrown or kicked objects E 3 E 4 Accessible primarily to those with some incentive to exercise care. Some chance of accident occurring or of misuse Only accessible, but not near a common route, to those with high incentive to exercise care. Small chance of accident occurring or of misuse Walls adjacent to pedestrian thoroughfares or playing fields, up to 1.5 m above pedestrian level, but not in vandal prone locations 1.5 m to 6 m above pedestrian level at location category E 2 Walls adjacent to private open gardens. Back walls of access galleries or balconies, up to 1.5 m above pedestrian level Walls adjacent to small fenced decorative gardens with no through paths E 5 Above zone of normal impacts from people and not exposed to impact from thrown or kicked objects Locations similar to E 2, but over 6 m above pedestrian level. Locations similar to E 3 and E 4 but over 1.5 m above pedestrian level (1) The height of 1.5 m corresponds to the region where human impacts with the energies established in Table 2.1 are likely to occur in normal buildings. However, for some types of building, such as gymnasia, warehouses, etc, greater heights may have to be considered To avoid damage of the clay brick slips, the use of the system shall be restricted to locations where some incentive to exercise care and little chance of hard body impacts occur. 7 Behaviour in relation to fire 7.1 For reaction to fire, the system incorporating 25 mm thick phenolic foam insulation and 20 mm thick clay brick slips achieved a fire classification of B-s1,d0 when tested in accordance with BS EN : The brick slips and mortar are designated A1 to Table 6, Approved Document B (England and Wales) and low risk in Scotland. 7.3 The systems are restricted for use in buildings less than 18 m in height. 7.4 For houses (1) in Scotland and for all buildings in England and Wales and Northern Ireland, the system is suitable for use on, or at any distance from the boundary. (1) house means a dwelling on one or more storeys either detached or forming part of a building from all other parts of which it is divided on vertically. 7.5 For flats and maisonettes and non-domestic buildings in Scotland, the system is suitable only for use more than 1 m from the boundary. 7.6 The system is not classified as non-combustible therefore, calculations for unprotected areas may apply dependant on the fire resistance characteristics of the wall. 7.7 For application to second storey walls and above, it is recommended that the designer includes at least one stainless steel fixing per square metre and fire barriers in line with compartment walls and floors as advised in BRE Report 135 : To limit the risk of fire spread between floors in buildings subject to the national Building Regulations, fire barriers should be incorporated behind the cladding as required under these Regulations, but should not block essential ventilation pathways (see Figure 3). Care should be taken in the detailing of the system over fire barriers to prevent melting of the insulation board during a fire. Guidance on fire barriers can be found in BRE Report 135 : Page 7 of 15

8 Figure 3 Cavity/Fire barriers substrate wall Wonderwall 1 clay brick slip cladding system 9 mm cement particle board timber batten weep holes at 900 mm centres fire-resistant filler with external intumescent seal movement gap cavity barrier 8 Proximity of flues and appliances When the system is installed in close proximity to certain flue pipes the relevant provisions of the national Building Regulations should be met: England and Wales Approved Document J Scotland Mandatory Standard 3.19, clause (1)(2) Northern Ireland Technical Booklet L. (1) Technical Handbook (Domestic). (2) Technical Handbook (Non-Domestic). 9 Thermal properties 9.1 Wonderwall 1 can provide additional thermal resistance to an external wall with extra insulation required to achieve the level of thermal performance required by the regulations. The U value calculations for specific constructions should be carried out in accordance with BS EN ISO 6946 : 2007 and BRE Report 443 : The U value of a completed wall will depend on the selected insulation thickness, the number, type and method of fixing the insulating value of the substrate wall and its internal finish. The phenolic foam insulation has a declared thermal conductivity ( 90/90 value) of W m 2 K 1 for the 50 mm thick board and W m 2 K 1 for the 25 mm thick board. 9.3 When used in conjunction with timber or steel framed substrate walls, the effect of the vented cavity needs to be considered in accordance with Section 5.3 of BS EN ISO 6946 : Junctions with other elements and opening in external walls should be designed to limit heat loss. Guidance on limiting heat loss at junctions can be found in: England and Wales Approved Documents to Part L and, for new thermal elements to existing buildings, Accredited Construction Details (version 1.0) (for new-build, see also SAP 2009, Appendix K, and the isbem User Manual) Scotland Accredited Construction Details (Scotland) Northern Ireland Accredited Construction Details (version 1.0). Page 8 of 15

9 9.5 In conjunction with a substrate wall providing the required airtightness (see section 10), the cladding system can contribute to the requirement for limiting heat loss through the building fabric and achieving the Target Emission Rate. 10 Condensation risk 10.1 Provided the system is properly installed, the risk of surface and interstitial condensation under normal domestic use will be minimal. Any condensate that may occur will dissipate during the summer months Dynamic simulations to BS EN 15026: 2007 indicate that the cladding system is acceptable when installed creating a watertight masonry wall. The simulations were done for a particular location, orientation and vapour resistance of the masonry substrate. The suitability of other constructions/parameters may be assessed by using an appropriate dynamic modelling package When used in conjunction with timber or steel framed substrate walls, Wonderwall 1 cladding system will adequately limit the risk of interstitial condensation when the construction is designed and built in accordance with Annex G.4 of BS 5250 : 2011 and this Certificate. It is essential to maintain a drained and vented cavity behind the system and an internal vapour control layer on the warm side of the construction It is essential that walls incorporating the cladding system are rain resistant and show no sign of water ingress. Careful attention has to be paid to joints and junctions in and between components and elements The risk of interstitial condensation in the external walling is greatest when the building is drying out after construction. Guidance on preventing condensation is given in BRE Digest 369 and BRE Report 262 : Weathertightness 11.1 The system resists the passage of moisture from the ground and from weather. Any water collecting in the cavity due to rain or condensation will be removed by drainage and ventilation The system is classified as Type 4, in accordance with BS 8104 : 1992, and suitable for use in areas subject to severe wind driven rain The system is classified as being F2 for resistance to freeze thaw, in accordance with DD CEN/TS : 2006, and is therefore suitable for conditions of severe exposure When clad to timber- or steel-frame constructions, there must be a minimum 20 mm cavity provided. The cavity must be drained and ventilated, incorporating perpend weep vents at 1.5 m centres, as defined in BS EN ISO 6946 : Ventilation and drainage openings should be suitably protected, or baffled, to prevent the ingress of birds, vermin and rain At the top of walls, the system should be protected by an adequate overhang or other detail designed for use with this type of system (see section 16.9) Designers and installers should take particular care in detailing around openings, penetrations and movement joints to minimise the risk of rain ingress A dpc must be provided through the thickness of Wonderwall 1. In new constructions, the substructure dpc should be carried through, and on existing building, an appropriate dpc is fitted adjoining the building s existing dpc The fixing of external fittings, eg rainwater goods, satellite dishes, clothes lines, hanging baskets and similar items are outside the scope of this Certificate. However, support fixings must pass through the cladding into the substrate wall so as not to exert any loadings on the cladding. Care must be taken not to overtighten the fixings which could cause damage. Guidance must be sought from the Certificate holder. 12 Maintenance 12.1 Regular maintenance inspections should be carried out to ensure that the ingress of water does not occur. Necessary repairs must be effected immediately. Annual inspections should be carried out to ensure the condition of sealants is satisfactory. Sealant should be reapplied where necessary. Damaged brick slips should be replaced in accordance with Certificate holder s installation instructions The brick finish may become soiled over time. For normal soiling, the surface may be cleaned using a hot water/household detergent mix, applied with a suitable cleaning pad or sponge. For more difficult chemical soiling, the advice of the Certificate holder should be sought. 13 Durability The durability and service life of the panels will depend upon the building location and height, façade aspect, intended use of the building and the immediate environmental conditions to which it is exposed. Providing regular maintenance is carried out as described in section 12 and in accordance with the Certificate holder s instructions, the system should have an ultimate service life of over 25 years. Page 9 of 15

10 Installation 14 Approved installers Application of the system, within the context of this Certificate, is carried out by approved installers recommended or recognised by the Certificate holder. Such an installer is a company: employing operatives who have been trained and approved by the Certificate holder to install the system which has undertaken to comply with the Certificate holder s application procedure, containing the requirement for each application team to include at least one member operative trained by the Certificate holder subject to at least one inspection per annum by the Certificate holder to ensure suitable site practices are being employed. This may include unannounced site inspections. 15 General 15.1 The Wonderwall 1 Clay Brick Slip Cladding System must be installed by approved installers, in accordance with the Certificate holder s recommendations, the requirements of this Certificate and the specification laid down by the consulting engineer Backerboard panels can be handled on site and can be cut or trimmed using a sharp knife or fine-toothed saw. Reasonable precautions must be taken to ensure panels are not damaged during and subsequent to installation The panels must not be installed on wet walls, or in temperatures below 5 C. Pointing should take place not more than 72 hours after the installation of the backerboards and not at temperatures below 2 C or above 30 C The profiled carrier sheet surface of the backerboard and brick slip surface must be clean and dry before application of the adhesive. Any dirt/ debris or damp on the surface must be brushed away and the surface wiped with a clean dry cloth When fixed to a framed substrate (see Figure 4), a suitable breather membrane must be applied to the substrate wall sheathing board Horizontal movement joints in accordance with BS EN : 2005 must be provided at every floor to accommodate vertical shrinkage of up to 6 mm in the timber frame and to follow movement joints in the substructure. For steel-frame structures, reference to the Structural Engineer s details for deflection at floor level and movement joints in the substructure should be made Vertical movement joints in accordance with BS EN : 2005 should be provided at a maximum of 15 m intervals. The actual spacing and position of the joints should coincide with movement joints in the structure and allow for the same degree of movement (see Figure 4). The Certificate holder s advice should be sought on movement joints. 16 Procedure 16.1 Typical installation details of the systems are given in Figure 4. Page 10 of 15

11 Figure 4 Typical installation details masonry wall (cross section) 12 masonry wall with additional insulation (plan view) timber frame (cross section) metal frame (cross section) Key 1 Brick slip 2 Pointing mortar 3 Brickslip adhesive 4 Backerboard 5 breather membrane vertical movement joint (plan view) 6 Masonry wall 7 Minimum 9 mm cement particleboard sheathing 8 Minimum 20 mm drained and vented cavity 9 Minimum 75 mm x 20 mm steel rail creating cavity 10 Additional insulation by others 11 Steel frame wall 12 Timber frame wall 13 Timber batten 14 5 mm 10 mm external mastic seal 15 Compressible joint filler 16 dpc 17 sheathing board 18 breather membrane (used with aerated blocks only) Page 11 of 15

12 Figure 4 Typical installation details (continued) Page 12 of 15

13 Figure 4 Typical installation details (continued) Key 1 Window frame 2 Wonderwall 1 adhesive bead 3 Backerboard 4 Brickslip jamb detail timber frame (plan view) 5 Compressible sealing tape 7 Movement gap 8 External mastic seal 9 VCL Backerboard 16.2 The starter rail is horizontally aligned with a spirit level and fixed to the base of the substrate wall or vertical steel rails/ timber battens. The backerboard panel is positioned against the starter rail and fixing positions marked as stipulated in section 6.6 (see Figure 2) The panel is fixed to the masonry substrate with mechanical fixings. For timber/steel frame substrate walls, the panels are fixed through vertical timber/ steel rails at maximum 600 mm centres. Care must be taken to ensure the fixing holes are drilled perpendicular to the surface of the panel Prior to the next panel being installed, a 5 mm adhesive bead is applied along the full height of the vertical edge. Brick slips 16.5 The brick slip adhesive is applied between the ribs of the carrier sheet in accordance with the Certificate holder s instructions. A single continuous 10 mm diameter bead is applied between the carrier sheet ribs approximately two-thirds towards the top. Care must be taken to ensure that the drainage channels located within the ribs of the carrier sheet are not obstructed by ending and starting the line of adhesive bead at the corresponding gaps The clay brick slips are placed on horizontal bed joint ribs of the carrier sheet and must be placed within 10 minutes of the adhesive being applied. The ribs are 75 mm centres and the brick slips sit directly on top of the flat face and must be pressed firmly against the carrier. Alignment should be checked as work proceeds ensuring a typical 10 mm joint between adjacent brick slips is maintained Joints are filled with cement based pointing grout/ mortar mix to class 12, 6 or 4 in accordance with BS EN : Pointing should not take place at temperatures below 2 C and above 30 C. When pointing is completed, tooling of the mortar joints is done to the desired effect and all the excess mortar is brushed off with a soft brush. Finishing 16.8 All window and door openings are sealed strictly in accordance with the Certificate holder s installation instructions to ensure that they are weathertight At the top of walls, the system must be protected by an adequate overhang or by an adequately sealed, purpose-made flashing Care must be taken in the detailing of the system around openings and projections to ensure adequate protection against water ingress and to limit the risk of water penetrating the system All movement joints are sealed using mastic sealant after brick application. Page 13 of 15

14 Technical Investigations 17 Investigations An investigation was made of data relating to: strength and stability fire resistance reaction to fire resistance to weathering freeze/ thaw resistance thermal properties condensation risk durability. Bibliography BRE Digest 369 Interstitial condensation and fabric degradation BRE Report 135 : 2013 Fire Performance of External Insulation for Walls of Multi-storey Buildings BRE Report 262 : 2002 Thermal insulation: avoiding risks BRE Report 443 : 2006 Conventions for U-value calculations, BS 5250 : 2011 Code of practice for control of condensation in buildings BS 6213 : 2000 Guide to selection of constructional sealants BS : 2001 Workmanship on building sites Code of practice for masonry BS 8104 : 1992 Code of practice for assessing exposure of walls to wind-driven rain BS EN : 2007 Durability of wood and wood-based products Preservative-treated solid wood Classification of preservative penetration and retention BS EN : 2011 Specification for masonry units Clay masonry units BS EN : 2010 Specification for mortar for masonry Masonry mortar BS EN : 2005 Eurocode 1 : Actions on structures General actions Wind actions BS EN : 2005 Eurocode 3 : Design of steel structures General rules and rules for buildings BS EN : 2006 UK National Annex to Eurocode 3 : Design of steel structures General rules Supplementary rules for cold-formed members and sheeting BS EN : 2004 Eurocode 5 : Design of timber structures General Common rules and rules for buildings BS EN : 2005 Eurocode 6 : Design of masonry structures General rules for reinforced and unreinforced masonry structures BS EN : 2005 Eurocode 6 : Design of masonry structures General rules Structural fire design BS EN : 2006 Eurocode 6 : Design of masonry structures Design considerations, selection of materials and execution of masonry BS EN : 2006 Eurocode 6 : Design of masonry structures : Simplified calculation methods for unreinforced masonry structures BS EN : 2012 Thermal insulation products for buildings Factory made phenolic foam (PF) products Specification BS EN : A1 : 2009 Fire classification of construction products and building elements Classification using data from reaction to fire tests BS EN : 2005 Design, preparation and application of external rendering and internal plastering External rendering BS EN : 2007 Hygrothermal performance of building components and building elements Assessment of moisture transfer by numerical simulation BS EN ISO 6946 : 2007 Building components and building elements Thermal resistance and thermal transmittance Calculation method BS EN ISO : A1 : 2011 Building construction Jointing products Classification and requirements for sealants DD CEN/TS : 2006 Methods of test for masonry units Determination of freeze/thaw resistance of clay masonry units ETAG 004 : 2000 Guideline for European Technical Approval of External Thermal Insulation Composite Systems with Rendering ETAG 014 : 2002 Guideline for European Technical Approval of Plastic Anchors For Fixing Of External Thermal Insulation Composite Systems With Rendering Page 14 of 15

15 MOAT No 43 : 1987 UEAtc Directives for Impact Testing Opaque Vertical Building Components PD 6697 : 2010 Recommendations for the design of masonry structures to BS EN and BS EN Conditions of Certification 18 Conditions 18.1 This Certificate: relates only to the product/system that is named and described on the front page is issued only to the company, firm, organisation or person named on the front page no other company, firm, organisation or person may hold or claim that this Certificate has been issued to them is valid only within the UK has to be read, considered and used as a whole document it may be misleading and will be incomplete to be selective is copyright of the BBA is subject to English Law Publications, documents, specifications, legislation, regulations, standards and the like referenced in this Certificate are those that were current and/or deemed relevant by the BBA at the date of issue or reissue of this Certificate This Certificate will remain valid for an unlimited period provided that the product/system and its manufacture and/or fabrication, including all related and relevant parts and processes thereof: are maintained at or above the levels which have been assessed and found to be satisfactory by the BBA continue to be checked as and when deemed appropriate by the BBA under arrangements that it will determine are reviewed by the BBA as and when it considers appropriate The BBA has used due skill, care and diligence in preparing this Certificate, but no warranty is provided In issuing this Certificate, the BBA is not responsible and is excluded from any liability to any company, firm, organisation or person, for any matters arising directly or indirectly from: the presence or absence of any patent, intellectual property or similar rights subsisting in the product/system or any other product/system the right of the Certificate holder to manufacture, supply, install, maintain or market the product/system actual installations of the product/system, including their nature, design, methods, performance, workmanship and maintenance any works and constructions in which the product/system is installed, including their nature, design, methods, performance, workmanship and maintenance any loss or damage, including personal injury, howsoever caused by the product/system, including its manufacture, supply, installation, use, maintenance and removal any claims by the manufacturer relating to CE marking Any information relating to the manufacture, supply, installation, use, maintenance and removal of this product/ system which is contained or referred to in this Certificate is the minimum required to be met when the product/system is manufactured, supplied, installed, used, maintained and removed. It does not purport in any way to restate the requirements of the Health and Safety at Work etc. Act 1974, or of any other statutory, common law or other duty which may exist at the date of issue or reissue of this Certificate; nor is conformity with such information to be taken as satisfying the requirements of the 1974 Act or of any statutory, common law or other duty of care. British Board of Agrément tel: Bucknalls Lane fax: Watford mail@bba.star.co.uk Herts WD25 9BA 2014 website: Page 15 of 15

Agrément Certificate 17/5466 website: Product Sheet 1 LEADAX FLASHINGS LEADAX

Agrément Certificate   17/5466 website:   Product Sheet 1 LEADAX FLASHINGS LEADAX Leadax BV Vlijtweg 4 8191 JP Wapenveld The Netherlands Tel: +31 085 065 37 46 Agrément Certificate e-mail: info@leadax.com 17/5466 website: www.leadax.com Product Sheet 1 This Agrément Certificate Product

More information

BUILDBASE SUPPLIED BY IKO BREATHER MEMBRANE FOR USE IN TIMBER FRAME CONSTRUCTIONS

BUILDBASE SUPPLIED BY IKO BREATHER MEMBRANE FOR USE IN TIMBER FRAME CONSTRUCTIONS IKO PLC Appley Lane North Appley Bridge Wigan Lancashire WN6 9AB Tel: 01257 255771 Fax: 01257 252514 Agrément Certificate e-mail: technical.uk@ikogroup.com 15/5190 website: www.ikogroup.co.uk Product Sheet

More information

TRESPA WALL CLADDING SYSTEMS SYSTEM 700 ALUMINIUM SUB-FRAME SYSTEM

TRESPA WALL CLADDING SYSTEMS SYSTEM 700 ALUMINIUM SUB-FRAME SYSTEM Trespa International B.V. P O Box 110 6000 AC Weert The Netherlands Tel: 00 31 0495 458358 Fax: 00 31 0495 458570 e-mail: infonederland@trespa.com website: www.trespa.com APPROVAL INSPECTION TESTING CERTIFICATION

More information

KINGSPAN FRAME SYSTEMS KINGSPAN STEEL FRAMING SYSTEM

KINGSPAN FRAME SYSTEMS KINGSPAN STEEL FRAMING SYSTEM Kingspan Steel Building Solutions Manor Works Pleck Road Walsall WS2 9ES Tel: 01944712000 Fax: 01922644460 e-mail: enquiries@kingspansbs.com website: www.kingspanpanels.co.uk/kip/steel-building-solutions

More information

WYKAMOL CHEMICAL DAMP-PROOFING SYSTEMS HYDRADRY

WYKAMOL CHEMICAL DAMP-PROOFING SYSTEMS HYDRADRY Wykamol Group Unit 3, Boran Court Network 65 Business Park Hapton, Burnley Lancashire BB11 5TH Tel: 0845 400 6666 Fax: 0845 400 3333 e-mail: info@wykamol.com website: www.wykamol.com APPROVAL INSPECTION

More information

EUROBRICK CLADDING SYSTEMS X-CLAD EXTERNAL CLADDING SYSTEM

EUROBRICK CLADDING SYSTEMS X-CLAD EXTERNAL CLADDING SYSTEM APPROVAL INSPECTION TESTING CERTIFICATION Eurobrick Systems Limited Unit 5, Newbridge Trading Estate Newbridge Close Bristol BS4 4AX Tel: +44 (0)117 971 7117 Fax: +44 (0)117 971 7217 TECHNICAL APPROVALS

More information

DAVID BALL HYDROPHILIC WATERSTOPS HDBR WATERBAR

DAVID BALL HYDROPHILIC WATERSTOPS HDBR WATERBAR David Ball Group Ltd Wellington Way Bourn Airfield Cambridge CB23 2TQ Tel: 01954 780687 Fax: 01954 782912 e-mail: sales@pudlo.com website: www.davidballgroup.com APPROVAL INSPECTION TESTING CERTIFICATION

More information

ADVANCED CONSTRUCTION SYSTEMS LTD CLADDING PRODUCTS FASTCLAD

ADVANCED CONSTRUCTION SYSTEMS LTD CLADDING PRODUCTS FASTCLAD Advanced Construction Systems Ltd Fastclad Building Granite Close Enderby Leicestershire LE19 4AE Tel: 0116 272 5133 Fax: 0116 272 5131 e-mail: info@advancedconstructionsystems.co.uk website: www.advancedconstructionsystems.co.uk

More information

RONACRETE RENDER PRODUCTS RONAFIX CONCRETE RENDER ADMIXTURE

RONACRETE RENDER PRODUCTS RONAFIX CONCRETE RENDER ADMIXTURE Ronacrete Ltd Ronac House Flex Meadow Merring Way Harlow Essex CM19 5TD Tel: 01279 638700 Fax: 01279 638701 e-mail: techweb@ronacrete.co.uk website: www.ronacrete.co.uk APPROVAL INSPECTION TESTING CERTIFICATION

More information

FENTRIM SEALING TAPES

FENTRIM SEALING TAPES SIGA Cover AG Rütmattstrasse 7 Ruswil 6017 Switzerland Tel: 00 41 41 499 69 69 Agrément Certificate e-mail: siga@siga.swiss 16/5378 website: www.siga.swiss Product Sheet 1 SIGA AIR AND WEATHERTIGHTNESS

More information

FILON GRP VALLEY TROUGH AND FLASHINGS RANGE FILON GRP SECRET JOINING STRIP (GJS 1)

FILON GRP VALLEY TROUGH AND FLASHINGS RANGE FILON GRP SECRET JOINING STRIP (GJS 1) Filon Products Limited APPROVAL INSPECTION TESTING CERTIFICATION Unit 3 Ring Road, Zone 2 Burntwood Business Park Burntwood Staffordshire WS7 2JQ Tel: 01543 687300 Fax: 01543 687303 TECHNICAL APPROVALS

More information

Agrément Certificate 05/4201 website: Product Sheet 2 PLYLOAD HIGH PERFORMANCE DAMP-PROOF COURSES

Agrément Certificate   05/4201 website:   Product Sheet 2 PLYLOAD HIGH PERFORMANCE DAMP-PROOF COURSES Plysolene Limited 21 Star Industrial Estate Partridge Green West Sussex RH13 8RA Tel: 01403 713555 Fax: 01403 713666 Page 1 of 9 Agrément Certificate e-mail: sales@plysolene.co.uk 05/4201 website: www.plysolene.co.uk

More information

NOVABRIK Parement extérieur Verkleidung Bedachung. Regulations

NOVABRIK Parement extérieur Verkleidung Bedachung. Regulations Designated by Government to issue European Technical Approvals Product Novabrik Ireland Limited Templemichael Caherconlish Co Limerick Ireland Tel: 00 353 6135 1400 Fax: 00 353 6135 1690 e-mail: info@novabrik.ie

More information

HARCON GRP VALLEY TROUGH AND FLASHING RANGE HARCON GRP DRY VALLEY TROUGHS

HARCON GRP VALLEY TROUGH AND FLASHING RANGE HARCON GRP DRY VALLEY TROUGHS Ariel Plastics Limited Speedwell Industrial Estate Staveley Derbyshire S43 3JP Tel: 01246 280000 Fax: 01246 561111 e-mail: info@harcon.co.uk website: www.harcon.co.uk APPROVAL INSPECTION TESTING CERTIFICATION

More information

FILON GRP VALLEY TROUGH AND FLASHINGS RANGE FILON GRP DRY FIX BONDING STRIP (GDFBS 70 AND GDFBS 110)

FILON GRP VALLEY TROUGH AND FLASHINGS RANGE FILON GRP DRY FIX BONDING STRIP (GDFBS 70 AND GDFBS 110) Filon Products Limited Unit 3 Ring Road, Zone 2 Burntwood Business Park Burntwood Staffordshire WS7 2JQ Tel: 01543 687300 Fax: 01543 687303 e-mail: sales@filon.co.uk website: www.filon.co.uk APPROVAL INSPECTION

More information

NVELOPE RAINSCREEN SYSTEMS NVELOPE RAINSCREEN CLADDING SUPPORT SYSTEMS

NVELOPE RAINSCREEN SYSTEMS NVELOPE RAINSCREEN CLADDING SUPPORT SYSTEMS Nvelope Rainscreen Systems Ltd Unit 10 Blenheim Court Brownfields Welwyn Garden City Hertfordshire AL7 1AD Tel: 01707 333396 Fax: 01707 333343 e-mail: info@nvelope.com website: www.nvelope.com APPROVAL

More information

ARGETON CLADDING SYSTEMS ARGETON TERRACOTTA RAINSCREEN CLADDING SYSTEM

ARGETON CLADDING SYSTEMS ARGETON TERRACOTTA RAINSCREEN CLADDING SYSTEM Telling Architectural Limited 7 The Dell Enterprise Drive Four Ashes Wolverhampton West Midlands WV10 7DF Tel: 01902 797700 Fax: 01902 797720 e-mail: info@telling.co.uk website: www.telling.co.uk APPROVAL

More information

THE A PROCTOR GROUP VAPOUR AND LOW AIR PERMEABLE MEMBRANE FRAMETITE FOR USE IN WALLS

THE A PROCTOR GROUP VAPOUR AND LOW AIR PERMEABLE MEMBRANE FRAMETITE FOR USE IN WALLS The A Proctor Group Ltd The Haugh Blairgowrie Perthshire PH10 7ER Tel: 01250 872261 e-mail: contact@proctorgroup.com website: www.proctorgroup.com APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL APPROVALS

More information

CAPITAL VALLEY PLASTICS MEMBRANES CAPITAL VALLEY PLASTICS DAMP-PROOF MEMBRANE

CAPITAL VALLEY PLASTICS MEMBRANES CAPITAL VALLEY PLASTICS DAMP-PROOF MEMBRANE Capital Valley Plastics Ltd Cwmavon Works Cwmavon Nr. Pontypool Gwent NP4 8UW Tel: 01495 772255 Fax: 01495 772251 e-mail: sales@capitalvalleyplastics.com website: www.capitalvalleyplastics.com APPROVAL

More information

Agrément Certificate 95/3210 website: Product Sheet 5 TRITON CHEMICAL DAMP-PROOFING SYSTEMS

Agrément Certificate   95/3210 website:   Product Sheet 5 TRITON CHEMICAL DAMP-PROOFING SYSTEMS Triton Chemical Manufacturing Co Ltd Unit 3-5 Crayford Commercial Centre Greyhound Way Crayford Kent DA1 4HF Tel: 01322 318830 Fax: 01322 524017 Agrément Certificate e-mail: info@tritonsystems.co.uk 95/3210

More information

SAFEGUARD MASONRY PROTECTION SYSTEMS STORMDRY MASONRY PROTECTION CREAM

SAFEGUARD MASONRY PROTECTION SYSTEMS STORMDRY MASONRY PROTECTION CREAM Safeguard Europe Limited Redkiln Close Horsham West Sussex RH13 5QL Tel: 01403 210204 Fax: 01403 217529 e-mail: info@safeguardeurope.com website: www.safeguardeurope.com APPROVAL INSPECTION TESTING CERTIFICATION

More information

EUROBRICK CLADDING SYSTEMS P-CLAD EXTERNAL CLADDING SYSTEM

EUROBRICK CLADDING SYSTEMS P-CLAD EXTERNAL CLADDING SYSTEM Eurobrick Building Systems Ltd Unit 7 Wilverley Trading Estate Bath Road Brislington Bristol BS4 5NL Tel: +44 (0)117 971 7117 Fax: +44 (0)117 971 7217 e-mail: info@eurobrick.co.uk website: www.eurobrick.co.uk

More information

Agrément Certificate 08/4577 website: Product Sheet 2 UBBINK FLASHINGS UBIFLEX EXTREME WATERPROOF FLASHING

Agrément Certificate   08/4577 website:   Product Sheet 2 UBBINK FLASHINGS UBIFLEX EXTREME WATERPROOF FLASHING Ubbink (UK) Ltd Unit 2, Redbourne Park 33 Liliput Road Brackmills Industrial Estate Northampton NN4 7DT Tel: 01604 433000 Fax: 01604 433001 Agrément Certificate e-mail: info@ubbink.co.uk 08/4577 website:

More information

LIMELITE PLASTER PRODUCTS LIMELITE RENOVATING PLASTER

LIMELITE PLASTER PRODUCTS LIMELITE RENOVATING PLASTER Tarmac Building Products Limited Swains Park Industrial Estate Park Road Overseal Swadlincote DE12 6JT Tel: 08444 630046 e-mail: stuart.allerton@tarmacbp.co.uk website: www.tarmacbuildingproducts.co.uk

More information

RIW HIGH PERFORMANCE DAMP-PROOFING SYSTEM

RIW HIGH PERFORMANCE DAMP-PROOFING SYSTEM RIW Ltd Arc House Terrace Road South Binfield Bracknell Berkshire RG42 4PZ Tel: 01344 397777 Fax: 01344 862010 e-mail: enquiries@riw.co.uk website: www.riw.co.uk APPROVAL INSPECTION TESTING CERTIFICATION

More information

Agrément Certificate 17/5474 website: Product Sheet 1

Agrément Certificate   17/5474 website:  Product Sheet 1 Ibstock Brick Ltd Leicester Road Ibstock Leicestershire LE67 6HS Tel: 01530 261999 Fax: 01530 257457 Agrément Certificate e-mail: enquiries@ibstockbrick.co.uk 17/5474 website: www.ibstockbrick.co.uk Product

More information

XTRATHERM XTROLINER (XO) XTRATHERM XTROLINER RAINSCREEN BOARD (XO/RS)

XTRATHERM XTROLINER (XO) XTRATHERM XTROLINER RAINSCREEN BOARD (XO/RS) Xtratherm Ltd Liscarton Industrial Estate Kells Road Navan Co Meath Ireland Tel: 00 353 46 906 6000 Fax: 00 353 46 906 6090 e-mail: info@xtratherm.com website: www.xtratherm.com APPROVAL INSPECTION TESTING

More information

LISNASTRAIN CAVITY TRAYS LISNASTRAIN CATCHMENT TRAYS, STEPPED CAVITY TRAYS AND RIDGE TRAYS

LISNASTRAIN CAVITY TRAYS LISNASTRAIN CATCHMENT TRAYS, STEPPED CAVITY TRAYS AND RIDGE TRAYS Lisnastrain Cavity Trays Ltd Unit 16C Derryloran Industrial Estate Cookstown Co Tyrone BT80 9LU Northern Ireland Tel: 028 8676 4433 Fax: 028 8676 1117 e-mail: info@cavitytrays.ie website: www.cavitytrays.ie

More information

DRYFIX DAMP-PROOF SYSTEMS DRYFIX INJECTION CREAM

DRYFIX DAMP-PROOF SYSTEMS DRYFIX INJECTION CREAM Alliance Remedial Supplies Ltd Units 11 & 12 Regents Trade Park Barwell Lane Gosport Hampshire PO13 0EQ Tel: 01329 235252 e-mail: info@allianceremedialsupplies.co.uk website: www.allianceremedialsupplies.co.uk

More information

TYVEK CONSTRUCTION MEMBRANES TYVEK UV FACADE

TYVEK CONSTRUCTION MEMBRANES TYVEK UV FACADE DuPont de Nemours (Luxembourg) S.à r.l. Rue General Patton L-2984 Luxembourg Tel: 01275 337660 Fax: 01275 879773 e-mail: tyvek.construction@lux.dupont.com website: www.tyvekhome.com APPROVAL INSPECTION

More information

SOLCO DAMP-PROOF COURSES SOLCOURSE HIGH PERFORMANCE DAMP PROOF COURSE

SOLCO DAMP-PROOF COURSES SOLCOURSE HIGH PERFORMANCE DAMP PROOF COURSE Solco Building Products Unit 51 52 Portmanmoor Road Industrial Estate Ocean Park Cardiff CF24 5HB Tel: 0808 168 6927 e-mail: enquiries@solco.co.uk website: www.solco.co.uk APPROVAL INSPECTION TESTING CERTIFICATION

More information

RENDERPLAS RENDER BEADS RENDERPLAS PVC BEADS

RENDERPLAS RENDER BEADS RENDERPLAS PVC BEADS Renderplas Ltd PPROVL INSPECTION TESTING CERTIFICTION Number 2 70 72 High Street ewdley Worcestershire DY12 2DJ Tel: 01299 888333 TECHNICL PPROVLS FOR CONSTRUCTION grément Certificate 11/4823 e-mail: info@renderplas.co.uk

More information

RONACRETE BEDDING MORTARS RONABOND BEDDING MORTAR

RONACRETE BEDDING MORTARS RONABOND BEDDING MORTAR Ronacrete Ltd Ronac House Flex Meadow Merring Way Harlow Essex CM19 5TD Tel: 01279 638700 Fax: 01279 638701 e-mail: techweb@ronacrete.co.uk website: www.ronacrete.co.uk APPROVAL INSPECTION TESTING CERTIFICATION

More information

WALLREFORM. Date of First issue: 5 February 2014 Simon Wroe Claire Curtis-Thomas

WALLREFORM. Date of First issue: 5 February 2014 Simon Wroe Claire Curtis-Thomas Walltransform Unit 4, Rosedale Court Ellerbeck Way Industrial Estate Stokesley North Yorkshire TS9 5GB Tel: 01642 272848 Fax: 01642 503666 e-mail: glen.melvin@ntlworld.com website: www.walltransform.co.uk

More information

GRACE CONSTRUCTION PRODUCTS HYDROPHILIC WATERSTOPS ADCOR 500S

GRACE CONSTRUCTION PRODUCTS HYDROPHILIC WATERSTOPS ADCOR 500S APPROVAL INSPECTION TESTING CERTIFICATION Grace Construction Products Ltd 580/581 Ipswich Road Slough Berks SL1 4EQ Tel: 01753 490000 Fax: 01753 490001 TECHNICAL APPROVALS FOR CONSTRUCTION Agrément Certificate

More information

Agrément Certificate 17/5429 website: Product Sheet 1 MONIER JACKETING MATERIAL WRAPTEC

Agrément Certificate   17/5429 website:   Product Sheet 1 MONIER JACKETING MATERIAL WRAPTEC Monier Roofing Components GmbH Frankfurter Landstrasse 2-4 Oberursel Hessen 61440 Germany Tel: 00 49 3043 559122 Agrément Certificate e-mail: wraptec@monier.com 17/5429 website: www.braas-monier.com Product

More information

MARLEY ETERNIT FAÇADE PANELS EQUITONE [NATURA]

MARLEY ETERNIT FAÇADE PANELS EQUITONE [NATURA] Marley Eternit Ltd Lichfield Road Branston Burton-on-Trent DE14 3HD Tel: 01283 722588 Fax: 01283 722219 e-mail: info@marleyeternit.co.uk website: www.marleyeternit.co.uk APPROVAL INSPECTION TESTING CERTIFICATION

More information

SAFEGUARD DAMP-PROOF SYSTEMS DRYROD DAMP-PROOFING RODS

SAFEGUARD DAMP-PROOF SYSTEMS DRYROD DAMP-PROOFING RODS Safeguard Europe Ltd 6 Redkiln Close Horsham West Sussex RH13 5QL Tel: 01403 210204 Fax: 01403 217529 e-mail: info@safeguardeurope.com website: www.safeguardeurope.com APPROVAL INSPECTION TESTING CERTIFICATION

More information

Agrément Certificate 97/3310 website: Product Sheet 1

Agrément Certificate   97/3310 website:   Product Sheet 1 IKO PLC Appley Lane North Appley Bridge Wigan Lancashire WN6 9AB Tel: 0844 412 7228 Fax: 0844 412 7229 Page 1 of 10 Agrément Certificate e-mail: technical@ikogroup.co.uk 97/3310 website: www.ikogroup.co.uk

More information

ZEDEX HIGH PERFORMANCE DAMP-PROOFING SYSTEM ZEDEX CPT HIGH PERFORMANCE DAMP-PROOF COURSE

ZEDEX HIGH PERFORMANCE DAMP-PROOFING SYSTEM ZEDEX CPT HIGH PERFORMANCE DAMP-PROOF COURSE Visqueen Building Products Heanor Gate Heanor Derbyshire DE75 7RG Tel: 0845 302 4758 Fax: 0845 017 8663 e-mail: enquiries@visqueenbuilding.co.uk website: www.visqueenbuilding.co.uk APPROVAL INSPECTION

More information

Agrément Certificate 17/5462 website: Product Sheet 1

Agrément Certificate   17/5462 website:   Product Sheet 1 Vista Engineering Ltd Carr Brook Works Shallcross Mill Road Whaley Bridge High Peak Derbyshire SK23 7JL Tel: 01663 736700 Fax: 01663 736710 Page 1 of 10 Agrément Certificate e-mail: sales@vistaeng.co.uk

More information

FILON GRP VALLEY TROUGH AND FLASHINGS RANGE FILON GRP ABUTMENT SECRET GUTTER/SOAKER (GAS 1)

FILON GRP VALLEY TROUGH AND FLASHINGS RANGE FILON GRP ABUTMENT SECRET GUTTER/SOAKER (GAS 1) Filon Products Ltd Unit 3 Ring Road, Zone 2 Burntwood Business Park Burntwood Staffordshire WS7 3JQ Agrément Certificate Tel: 01543 687300 Fax: 01543 687303 e-mail: sales@filon.co.uk 07/4492 website: www.filon.co.uk

More information

LOW-E FOIL INSULATION FOR PITCHED ROOFS, DRY LININGS AND FLOORS LOW-E FOIL INSULATION FOR USE IN PITCHED ROOF APPLICATIONS

LOW-E FOIL INSULATION FOR PITCHED ROOFS, DRY LININGS AND FLOORS LOW-E FOIL INSULATION FOR USE IN PITCHED ROOF APPLICATIONS Low-E UK Ltd Unit 48 Weaver Industrial Estate Blackburn Street Liverpool Merseyside L19 8JA Tel: 0151 494 9994 Fax: 0560 310 7699 e-mail: info@low-e.co.uk website: www.low-e.co.uk APPROVAL INSPECTION TESTING

More information

NDC POLIPAK MEMBRANES

NDC POLIPAK MEMBRANES NDC Polipak Ltd 1 Garratts Lane Old Hill Cradley Heath West Midlands B64 5RE Tel: 0121 561 6700 Fax: 0121 559 0230 e-mail: sales@ndcpolipak.co.uk website: www.ndcpolipak.com APPROVAL INSPECTION TESTING

More information

SOLCO MEMBRANES SOLCOURSE DAMP-PROOF MEMBRANE

SOLCO MEMBRANES SOLCOURSE DAMP-PROOF MEMBRANE Solco Building Products Units 51 52 Portmanmoor Road Industrial Estate Ocean Park Cardiff CF24 5HB Tel: 0808 168 6927 Fax: 02920 491700 e-mail: enquiries@solco.co.uk website: www.solco.co.uk APPROVAL INSPECTION

More information

ONDULINE BITUMINOUS CORRUGATED ROOFING MATERIALS ONDULINE CLASSIC ROOFING AND CLADDING SHEETS

ONDULINE BITUMINOUS CORRUGATED ROOFING MATERIALS ONDULINE CLASSIC ROOFING AND CLADDING SHEETS Onduline Building Products Ltd Eardley House 182 184 Campden Hill Road Kensington London W8 7AS Tel: 020 7727 0533 Fax: 020 7792 1390 e-mail: enquiries@onduline.net website: www.onduline.co.uk APPROVAL

More information

SURECAV CAVITY WALL SYSTEM SURECAV CAVITY WALL SPACER SYSTEM

SURECAV CAVITY WALL SYSTEM SURECAV CAVITY WALL SPACER SYSTEM SureCav Ltd Holbrook Lodge Holbrook Wincanton Somerset BA9 8BT Tel: 01963 34660 Fax: 01963 32441 e-mail: info@surecav.co.uk website: www.surecav.co.uk APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL

More information

TYVEK ROOF LINING SYSTEMS PRODUCT SHEET 3 TYVEK SD2 AIR LEAKAGE BARRIER/VAPOUR CONTROL LAYER

TYVEK ROOF LINING SYSTEMS PRODUCT SHEET 3 TYVEK SD2 AIR LEAKAGE BARRIER/VAPOUR CONTROL LAYER DuPont de Nemours (Luxembourg) S.à r.l. Rue General Patton L-2984 Luxembourg Tel: 01275 879770 Fax: 01275 879773 e-mail: tyvek.construction@lux.dupont.com website: www.tyvekhome.com Agrément Certificate

More information

NDC POLIPAK DAMP-PROOF COURSES DAMPLAS CPT PLUS

NDC POLIPAK DAMP-PROOF COURSES DAMPLAS CPT PLUS NDC Polipak Ltd 1 Garratts Lane Cradley Heath West Midlands B64 5RE Tel: 0121 561 6700 Fax: 0121 559 0230 e-mail: enquiries@ndcpolipak.com website: www.ndcpolipak.com APPROVAL INSPECTION TESTING CERTIFICATION

More information

POLYPIPE DUCTING SYSTEMS COMTITE DUCTING PLUG

POLYPIPE DUCTING SYSTEMS COMTITE DUCTING PLUG HAPAS Polypipe Civils Charnwood Business Park North Road Loughborough Leicestershire LE11 1LE Tel: 01509 6151001 Fax: 01509 265945 e-mail: civilssales@polypipe.com website: www.polypipe.com POLYPIPE DUCTING

More information

BIOKIL CROWN MASONRY PROTECTION SYSTEMS AQUADRY MASONRY PROTECTION CREAM

BIOKIL CROWN MASONRY PROTECTION SYSTEMS AQUADRY MASONRY PROTECTION CREAM Biokil Crown Ltd Unit 31, Hilton Industrial Estate Sutton Lane Hilton Derbyshire DE65 5FE Tel: 0115 946 0060 Fax: 0115 946 9767 e-mail: info@biokilcrown.co.uk website: www.aqua-dry.co.uk APPROVAL INSPECTION

More information

PRODUCT SHEET 1 ARGETON TERRACOTTA RAINSCREEN CLADDING SYSTEM

PRODUCT SHEET 1 ARGETON TERRACOTTA RAINSCREEN CLADDING SYSTEM CI/SfB (27.9) Ln6 Telling Architectural Ltd Primrose Avenue Fordhouses Wolverhampton West Midlands WV10 8AW Tel: 01902 789777 Fax: 01902 398777 e-mail: info@telling.co.uk website: www.telling.co.uk Agrément

More information

VITRABOND RAINSCREEN CLADDING SYSTEMS VITRABOND FR ALUMINIUM COMPOSITE RAINSCREEN CLADDING PANELS

VITRABOND RAINSCREEN CLADDING SYSTEMS VITRABOND FR ALUMINIUM COMPOSITE RAINSCREEN CLADDING PANELS Valcan Ltd APPROVAL INSPECTION TESTING CERTIFICATION Unit 7 Robins Drive Castlefields Industrial Estate Bridgwater Somerset TA6 4DL Tel: 01278 428 245 Fax: 01278 425 662 TECHNICAL APPROVALS FOR CONSTRUCTION

More information

TYVEK ROOF LINING SYSTEMS PRODUCT SHEET 3 DUPONT AIRGUARD CONTROL AIR LEAKAGE BARRIER/ VAPOUR CONTROL LAYER

TYVEK ROOF LINING SYSTEMS PRODUCT SHEET 3 DUPONT AIRGUARD CONTROL AIR LEAKAGE BARRIER/ VAPOUR CONTROL LAYER DuPont de Nemours (Luxembourg) S.à r.l. Rue General Patton L-2984 Luxembourg Tel: 01275 879770 Fax: 01275 879773 e-mail: tyvek.construction@lux.dupont.com website: www.tyvekhome.com Agrément Certificate

More information

Agrément Certificate 17/5450 website: Product Sheet 1 FOSROC HYDRO-EXPANSIVE WATERSTOPS SUPERCAST SW

Agrément Certificate   17/5450 website:  Product Sheet 1 FOSROC HYDRO-EXPANSIVE WATERSTOPS SUPERCAST SW Fosroc Limited Drayton Manor Business Park Coleshill Road Tamworth Staffordshire B78 3XN Tel: 01827 262222 Fax: 01827 262444 Agrément Certificate e-mail: enquiryuk@fosroc.com 17/5450 website: www.fosroc.com

More information

PITTSBURGH CORNING (UK) PERINSUL HL PERINSUL HL

PITTSBURGH CORNING (UK) PERINSUL HL PERINSUL HL Pittsburgh Corning (UK) Ltd 31-35 Kirby Street Hatton Garden London EC1N 8TE Tel: 020 7492 1731 Fax: 020 7492 1730 e-mail: info@foamglas.co.uk website: www.foamglas.co.uk APPROVAL INSPECTION TESTING CERTIFICATION

More information

TERREAL CLADDING SYSTEMS ZEPHIR CLADDING SYSTEM

TERREAL CLADDING SYSTEMS ZEPHIR CLADDING SYSTEM Terreal UK Pinewood Chineham Business Park Crockford Lane Basingstoke Hampshire RG4 8AL Tel: 0845 60 9830 Fax: 0845 60 9873 e-mail: facade@terreal.com website: www.terrealfacade.com APPROVAL INSPECTION

More information

HILTI EUROFOX RAINSCREEN SYSTEMS HILTI EUROFOX RAINSCEEEN CLADDING SUPPORT SYSTEMS

HILTI EUROFOX RAINSCREEN SYSTEMS HILTI EUROFOX RAINSCEEEN CLADDING SUPPORT SYSTEMS EUROFOX GmbH Gewerbepark 10 A 2821 Lanzenkirchen Austria Tel: +43-2627 42400 Fax: +43 2627 4240040 website: www.eurofox.com www.hilti.com APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL APPROVALS FOR

More information

PRODUCT SHEET 1 PARKLEX FACADE WALL CLADDING PANEL

PRODUCT SHEET 1 PARKLEX FACADE WALL CLADDING PANEL Composites Gurea S.A. P.I. Alkaiaga C/Baldrun s/n 31.780 Vera de Bidasoa Navarra Spain Tel: 00 34 948 625 045 Fax: 00 34 948 625 420 e-mail: parklex@parklex.com website: www.parklex.com Agrément Certificate

More information

THERMALITE AIRCRETE BLOCKS AND THIN-JOINT SYSTEM TURBO

THERMALITE AIRCRETE BLOCKS AND THIN-JOINT SYSTEM TURBO Forterra Building Products Limited 5 Grange Park Court Roman Way Northampton NN4 5EA Tel: 0330 123 1018 Fax: 01530 273183 e-mail: asktechnical@forterra.co.uk website: www.forterra.co.uk THERMALITE AIRCRETE

More information

Agrément Certificate 17/5453 website: Product Sheet 1

Agrément Certificate   17/5453 website:   Product Sheet 1 Saint-Gobain Construction Products UK Ltd t/a British Gypsum East Leake Loughborough LE12 6HX Tel: 0115 945 6123 Page 1 of 11 Agrément Certificate e-mail: bgtechnical.enquiries@bpb.com 17/5453 website:

More information

KINGSPAN INSULATION KOOLTHERM K10 SOFFIT INSULATION

KINGSPAN INSULATION KOOLTHERM K10 SOFFIT INSULATION Kingspan Insulation Ltd Pembridge Leominster Herefordshire HR6 9LA Tel: 0870 8508555 Fax: 0870 8508666 e-mail: info.uk@insulation.kingspan.com website: www.insulation.kingspan.com APPROVAL INSPECTION TESTING

More information

TYVEK CONSTRUCTION MEMBRANES TYVEK SOFT WALL BREATHER MEMBRANE

TYVEK CONSTRUCTION MEMBRANES TYVEK SOFT WALL BREATHER MEMBRANE DuPont de Nemours (Luxembourg) S.à r.l. Rue General Patton L-2984 Luxembourg Tel: 01275 337660 Fax: 01275 879773 e-mail: tyvek.construction@lux.dupont.com website: www.tyvekhome.com APPROVAL INSPECTION

More information

Agrément Certificate 17/5435 website: Product Sheet 1

Agrément Certificate   17/5435 website:   Product Sheet 1 Farrat Isolevel Ltd Balmoral Road Altrincham Cheshire WA15 8HJ Tel: +44 (0)161 924 1600 Fax: +44 (0)161 924 1616 Page 1 of 10 Agrément Certificate e-mail: sales@farrat.com 17/5435 website: www.farrat.com

More information

SANDTOFT FLASHINGS KORAFLEX FLASHING SYSTEM

SANDTOFT FLASHINGS KORAFLEX FLASHING SYSTEM Sandtoft Roof Tiles Ltd Belton Road Sandtoft Doncaster South Yorkshire DN8 5SY Tel: 0844 9395 999 Fax: 0844 9359 950 e-mail: info@sandtoft.co.uk website: www.sandtoft.com APPROVAL INSPECTION TESTING CERTIFICATION

More information

Agrément Certificate 12/4956 website: Product Sheet 3 XTRATHERM XTROLINER (XO) XTROLINER SOFFIT PLUS

Agrément Certificate   12/4956 website:   Product Sheet 3 XTRATHERM XTROLINER (XO) XTROLINER SOFFIT PLUS Xtratherm Ltd Liscarton Industrial Estate Kells Road Navan Co Meath Ireland Tel: 00 353 46 906 6000 Fax: 00 353 46 805 6090 Page 1 of 10 Agrément Certificate e-mail: info@xtratherm.com 12/4956 website:

More information

SIKA ADHESIVE SYSTEM

SIKA ADHESIVE SYSTEM Sika Ltd Watchmead Welwyn Garden City Hertfordshire AL7 1BQ Tel: 01707 394444 Fax: 01707 329129 e-mail: technical@uk.sika.com website: www.sika.com APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL APPROVALS

More information

TRITON CHEMICAL DAMP-PROOFING SYSTEMS TRI-CREAM

TRITON CHEMICAL DAMP-PROOFING SYSTEMS TRI-CREAM Triton Chemical Manufacturing Co Ltd Unit 3-5 Crayford Commercial Centre Greyhound Way Crayford Kent DA1 4HF Tel: 01322 318830 Fax: 01322 524017 e-mail: info@tritonsystems.co.uk website: www.tritonsystems.co.uk

More information

OSMADRAIN UNDERGROUND DRAINAGE SYSTEM OSMADRAIN UNIVERSAL GULLY SYSTEM

OSMADRAIN UNDERGROUND DRAINAGE SYSTEM OSMADRAIN UNIVERSAL GULLY SYSTEM Wavin UK (Holdings) Ltd Parsonage Way Chippenham Wiltshire SN15 5PN Tel: 01249 654121 Fax: 01249 443286 e-mail: info@wavin.co.uk website: www.wavin.co.uk APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL

More information

Agrément Certificate website: 02/3883 Product Sheet 1 SIMPSON STRONG-TIE WALL EXTENSION PROFILES

Agrément Certificate website:   02/3883 Product Sheet 1 SIMPSON STRONG-TIE WALL EXTENSION PROFILES Simpson Strong-Tie Winchester Road Cardinal Point Tamworth Staffordshire B78 3HG Tel: 01827 255600 Fax: 01827 255616 Agrément Certificate website: www.strongtie.co.uk 02/3883 Product Sheet 1 SIMPSON STRONG-TIE

More information

Agrément Certificate 90/2548 website: Product Sheet 1

Agrément Certificate   90/2548 website:   Product Sheet 1 DuPont de Nemours (Luxembourg) S.à r.l Rue General Patton L-2984 Luxembourg Tel: 08444 068 722 British Board of Agrément Bucknalls Lane Watford Herts WD25 9BA 2018 Page 1 of 10 Agrément Certificate e-mail:

More information

Agrément Certificate 08/4551 website: Product Sheet 1

Agrément Certificate   08/4551 website:  Product Sheet 1 Alucoil SA Pol Ind Bayas C/Ircio, parc R72-R77 09200 Miranda de Ebro (Burgos) Spain Tel: 00 34 947 33 33 20 Fax: 00 34 947 33 12 24 Page 1 of 10 Agrément Certificate e-mail: info@alucoil.com 08/4551 website:

More information

OLDROYD MEMBRANE SYSTEMS OLDROYD XS

OLDROYD MEMBRANE SYSTEMS OLDROYD XS Oldroyd AS Kragerø Næringspark 3766 Sannidal Norway Tel: 00 47 35 98 75 50 Fax: 00 47 35 98 75 51 e-mail: oldroyd@oldroyd.com website: www.fixoldroyd.com APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL

More information

TCB ANTI-CORROSION PROTECTIVE COATING GREENKOTE

TCB ANTI-CORROSION PROTECTIVE COATING GREENKOTE H A P A S Tension Control Bolts Ltd TCB House Clywedog Road South Wrexham Industrial Estate Wrexham LL13 9XS Tel: +44 (0) 1978 661122 Fax: +44 (0) 1978 661177 e-mail: info@tcbolts.com website: www.tcbolts.com

More information

CLAYMASTER COMPRESSIBLE FILL CLAYMASTER COMPRESSIBLE FILL LOW DENSITY EXPANDED POLYSTYRENE BOARDS

CLAYMASTER COMPRESSIBLE FILL CLAYMASTER COMPRESSIBLE FILL LOW DENSITY EXPANDED POLYSTYRENE BOARDS Jablite Limited Infinity House Anderson Way Belvedere Kent DA17 6BG Tel: 020 8320 9100 Fax: 020 8320 9110 website: www.jablite.co.uk APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL APPROVALS FOR CONSTRUCTION

More information

Building Regulations

Building Regulations Bluebird Fixings Limited Westminster Industrial Estate Station Road North Hykeham Lincoln LN6 3QY Tel: 01522 697776 Fax: 01522 697771 CI/SfB Xt6 Agrément Certificate No 93/2878 Second issue* Designated

More information

ALUMINIUM FOIL BUBBLE INSULATION AIRTEC SINGLE AND AIRTEC DOUBLE DRY LINING WALL INSULATION

ALUMINIUM FOIL BUBBLE INSULATION AIRTEC SINGLE AND AIRTEC DOUBLE DRY LINING WALL INSULATION YBS Insulation Ltd Unit 1 Crags Industrial Park Morven Street Creswell Derbyshire S80 4AJ Tel: 01909 721662 Fax: 01909 721442 e-mail: sales@ybsinsulation.com website: www.ybsinsulation.com APPROVAL INSPECTION

More information

LAPOLLA SPRAY APPLIED OPEN CELL INSULATION LAPOLLA ATOC

LAPOLLA SPRAY APPLIED OPEN CELL INSULATION LAPOLLA ATOC Lapolla Industries, Inc 15402 Vantage Parkway East, Suite 322 Houston Texas 77032 USA Tel: + 001 877 636 2648 e-mail: info@lapolla.com website: www.lapolla.com APPROVAL INSPECTION TESTING CERTIFICATION

More information

ALUMINIUM FOIL BUBBLE INSULATION AIRTEC DOUBLE DOUBLE BUBBLE CAVITY WALL INSULATION

ALUMINIUM FOIL BUBBLE INSULATION AIRTEC DOUBLE DOUBLE BUBBLE CAVITY WALL INSULATION YBS Insulation Ltd Unit 1 Crags Industrial Park Morven Street Creswell Derbyshire S80 4AJ Tel: 01909 721662 Fax: 01909 721442 e-mail: sales@ybsinsulation.com website: www.ybsinsulation.com APPROVAL INSPECTION

More information

INSTARMAC PERMANENT COLD LAY SURFACING MATERIALS ULTRACRETE INSTANT ROAD REPAIR 6 MM

INSTARMAC PERMANENT COLD LAY SURFACING MATERIALS ULTRACRETE INSTANT ROAD REPAIR 6 MM H A P A S Instarmac Group plc Danny Morson Way Birch Coppice Business Park Dordon, Tamworth Staffordshire B78 1SE Tel: 01827 872244 Fax: 01827 874466 HAPAS Certificate e-mail: enquiries@instarmac.co.uk

More information

XTRATHERM THIN-R INSULATION XTRATHERM THIN-R FLAT ROOF INSULATION BOARD (FR ALU)

XTRATHERM THIN-R INSULATION XTRATHERM THIN-R FLAT ROOF INSULATION BOARD (FR ALU) Xtratherm UK Ltd Park Road Holmewood Industrial Park Holmewood Chesterfield Tel: 0371 222 1033 Fax: 0371 222 1044 e-mail: info@xtratherm.com website: www.xtratherm.com APPROVAL INSPECTION TESTING CERTIFICATION

More information

VISQUEEN DAMP-PROOF MEMBRANES VISQUEEN HIGH PERFORMANCE DPM

VISQUEEN DAMP-PROOF MEMBRANES VISQUEEN HIGH PERFORMANCE DPM Visqueen Building Products Heanor Gate Heanor Derbyshire DE75 7RG Tel: 0845 302 4758 Fax: 0845 017 8663 e-mail: enquiries@visqueenbuilding.co.uk website: www.visqueenbuilding.co.uk APPROVAL INSPECTION

More information

WAVIN ROAD GULLIES. Date of First issue: 16 April 2014 Brian Chamberlain Claire Curtis-Thomas

WAVIN ROAD GULLIES. Date of First issue: 16 April 2014 Brian Chamberlain Claire Curtis-Thomas HAPAS Wavin Ltd Parsonage Way Chippenham Wiltshire SN15 5PN Tel: 01249 766600 Fax: 01249 443286 e-mail: info@wavin.co.uk website: www.wavin.co.uk WAVIN ROAD GULLIES APPROVAL INSPECTION TESTING CERTIFICATION

More information

FRANK MERCER MEMBRANES TOUGHSHEET 250, TOUGHSHEET 300 AND TOUGHSHEET 500 MAX DAMP-PROOF MEMBRANES

FRANK MERCER MEMBRANES TOUGHSHEET 250, TOUGHSHEET 300 AND TOUGHSHEET 500 MAX DAMP-PROOF MEMBRANES Frank Mercer & Sons Ltd Chequerbent Works Manchester Road Chequerbent Westhoughton Bolton Lancashire BL5 3JF Tel: 01942 841111 Fax: 01942 842388 e-mail: sales@toughsheet.co.uk website: www.toughsheet.co.uk

More information

Regulations Detail Sheet 1

Regulations Detail Sheet 1 Ancon Building Products President Way President Park Sheffield S4 7UR Tel: 0114 275 5224 Fax: 0114 276 8543 e-mail: info@ancon.co.uk website: www.ancon.co.uk Agrément Certificate No 99/3659 Fourth issue*

More information

ROCKWOOL BUILT IN CAVITY WALL INSULATION BATTS ROCKWOOL CAVITY WALL BATT

ROCKWOOL BUILT IN CAVITY WALL INSULATION BATTS ROCKWOOL CAVITY WALL BATT Rockwool Ltd Pencoed Bridgend CF35 6NY Tel: 01656 862621 Fax: 01656 862302 e-mail: customer.support@rockwool.co.uk website: www.rockwool.co.uk APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL APPROVALS

More information

YBS MULTI-LAYER INSULATION SUPERQUILT

YBS MULTI-LAYER INSULATION SUPERQUILT Yorkshire Building Services (Whitwell) Limited T/A YBS Insulation Crags Industrial Park Morven Street Creswell Derbyshire S80 4AJ Tel: 0844 99 100 44 e-mail: technical@ybsinsulation.com website: http://www.ybsinsulation.com

More information

WEDI SHOWER ELEMENTS WEDI FUNDO SHOWER ELEMENTS

WEDI SHOWER ELEMENTS WEDI FUNDO SHOWER ELEMENTS wedi Systems (UK) Ltd Unit 4 Mercury Park Mercury Way Trafford Park Manchester M41 7LY Tel: 0161 864 2336 Fax: 0161 864 1323 e-mail: info@wedi.co.uk website: www.wedi.co.uk APPROVAL INSPECTION TESTING

More information

TYVEK ROOF LINING SYSTEMS DUPONT AIRGUARD REFLECTIVE

TYVEK ROOF LINING SYSTEMS DUPONT AIRGUARD REFLECTIVE DuPont de Nemours (Luxembourg) S.à r.l. Rue General Patton L-2984 Luxembourg Tel: 01275 879770 Fax: 01275 879773 e-mail: tyvek.construction@lux.dupont.com website: www.tyvekhome.com APPROVAL INSPECTION

More information

DON & LOW CONSTRUCTION MEMBRANES REFLECTASHIELD TF

DON & LOW CONSTRUCTION MEMBRANES REFLECTASHIELD TF Don & Low Ltd Glamis Road Forfar Angus DD8 1EY Tel: 01307 452600 Fax: 01307 452610 Agrément Certificate e-mail: nonwovens@donlow.co.uk 11/4732 website: www.donlow.co.uk Product Sheet 1 This Agrément Certificate

More information

TIMBERWISE DAMP-PROOF SYSTEMS DRIWISE

TIMBERWISE DAMP-PROOF SYSTEMS DRIWISE Timberwise (UK) Ltd 1 Drake Mews Gadbrook Way Gadbrook Park Cheshire CW9 7XF Tel: 01606 333636 Fax: 01606 334748 e-mail: hq@timberwise.co.uk website: www.timberwise.co.uk APPROVAL INSPECTION TESTING CERTIFICATION

More information

BALLYTHERM INSULATION BALLYTHERM BTR PITCHED ROOF INSULATION

BALLYTHERM INSULATION BALLYTHERM BTR PITCHED ROOF INSULATION Ballytherm Ltd Annagh Industrial Park Ballyconnell Co Cavan Ireland Tel: 00 353 49 9527000 Fax: 00 353 49 9527002 e-mail: info@ballytherm.ie website: www.ballytherm.ie APPROVAL INSPECTION TESTING CERTIFICATION

More information

KINGSPAN INSULATION KOOLTHERM K15 RAINSCREEN INSULATION BOARD

KINGSPAN INSULATION KOOLTHERM K15 RAINSCREEN INSULATION BOARD Kingspan Insulation Ltd Pembridge Leominster Herefordshire HR6 9LA Tel: 0870 850 8555 Fax: 0870 850 8666 e-mail: info.uk@insulation.kingspan.com website: www.insulation.kingspan.com APPROVAL INSPECTION

More information

HILTI EUROFOX RAINSCREEN SYSTEMS HILTI EUROFOX RAINSCEEEN CLADDING SUPPORT SYSTEMS

HILTI EUROFOX RAINSCREEN SYSTEMS HILTI EUROFOX RAINSCEEEN CLADDING SUPPORT SYSTEMS EUROFO GmbH Gewerbepark 10 A 2821 anzenkirchen Austria Tel: +43-2627 42400 Fax: +43 2627 4240040 e-mail: eurofox@eurofox.com website: www.eurofox.com APPROVA INSPECTION TESTING CERTIFICATION TECHNICA APPROVAS

More information

SOLCO MEMBRANES SOLSHIELD GAS MEMBRANE

SOLCO MEMBRANES SOLSHIELD GAS MEMBRANE Solco Building Products Units 51 52 Portmanmoor Road Industrial Estate Ocean Park Cardiff CF24 5HB Tel: 0808 168 6927 Fax: 02920 491700 e-mail: enquiries@solco.co.uk website: www.solco.co.uk APPROVAL INSPECTION

More information

HAPAS Certificate Tel: Fax: /H271 website: Product Sheet 2

HAPAS Certificate Tel: Fax: /H271 website:   Product Sheet 2 FM Conway Ltd Conway house Vestry Road Sevenoaks Kent TN14 5EL Page 1 of 7 HAPAS Certificate Tel: 0208 636 8822 Fax: 0208 636 8827 17/H271 website: www.fmconway.co.uk Product Sheet 2 FM CONWAY ASPHALT

More information

SWIP SOLID WALL INTERNAL WALL INSULATION SYSTEM

SWIP SOLID WALL INTERNAL WALL INSULATION SYSTEM SWIP Ltd ROC House Unit 15 Key Business Park Kingsbury Road Birmingham West Midlands B24 9PT Tel: 0845 402 3585 email: info@swipiwi.co.uk website: www.swipiwi.co.uk APPROVAL INSPECTION TESTING CERTIFICATION

More information

LAPOLLA SPRAY APPLIED CLOSED CELL INSULATION LAPOLLA FL2000 (FOAM-LOK)

LAPOLLA SPRAY APPLIED CLOSED CELL INSULATION LAPOLLA FL2000 (FOAM-LOK) Lapolla Industries, Inc 15402 Vantage Parkway East, Suite 322 Houston Texas 77032 USA Tel: + 001 877 636 2648 e-mail: info@lapolla.com website: www.lapolla.com APPROVAL INSPECTION TESTING CERTIFICATION

More information

WEBER.REND MT SYSTEMS WEBER.REND MT SYSTEMS APPLIED TO KNAUF AQUAPANEL EXTERIOR CEMENT BOARD

WEBER.REND MT SYSTEMS WEBER.REND MT SYSTEMS APPLIED TO KNAUF AQUAPANEL EXTERIOR CEMENT BOARD Saint-Gobain Weber Ltd Dickens House Enterprise Way Flitwick Bedfordshire MK45 5BY Tel: 0870 3330070 Fax: 0800 0142995 e-mail: mail@netweber.co.uk website: www.netweber.co.uk APPROVAL INSPECTION TESTING

More information