Online publication date: 01 March 2010 PLEASE SCROLL DOWN FOR ARTICLE

Size: px
Start display at page:

Download "Online publication date: 01 March 2010 PLEASE SCROLL DOWN FOR ARTICLE"

Transcription

1 This article was downloaded by: [University of California, Berkeley] On: 25 March 2010 Access details: Access Details: [subscription number ] Publisher Taylor & Francis Informa Ltd Registered in England and Wales Registered Number: Registered office: Mortimer House, Mortimer Street, London W1T 3JH, UK Journal of Earthquake Engineering Publication details, including instructions for authors and subscription information: Lessons Learned from Seismic Analysis of a Seven-Story Concrete Test Building Jonathan D. Waugh a ;Sri Sritharan a a Department of Civil, Construction, and Environmental Engineering, Iowa State University, Ames, Iowa, USA Online publication date: 01 March 2010 To cite this Article Waugh, Jonathan D. andsritharan, Sri(2010) 'Lessons Learned from Seismic Analysis of a Seven-Story Concrete Test Building', Journal of Earthquake Engineering, 14: 3, To link to this Article: DOI: / URL: PLEASE SCROLL DOWN FOR ARTICLE Full terms and conditions of use: This article may be used for research, teaching and private study purposes. Any substantial or systematic reproduction, re-distribution, re-selling, loan or sub-licensing, systematic supply or distribution in any form to anyone is expressly forbidden. The publisher does not give any warranty express or implied or make any representation that the contents will be complete or accurate or up to date. The accuracy of any instructions, formulae and drug doses should be independently verified with primary sources. The publisher shall not be liable for any loss, actions, claims, proceedings, demand or costs or damages whatsoever or howsoever caused arising directly or indirectly in connection with or arising out of the use of this material.

2 Journal of Earthquake Engineering, 14: , 2010 Copyright Ó A.S. Elnashai & N.N. Ambraseys ISSN: print / X online DOI: / Lessons Learned from Seismic Analysis of a Seven-Story Concrete Test Building JONATHAN D. WAUGH and SRI SRITHARAN Department of Civil, Construction, and Environmental Engineering, Iowa State University, Ames, Iowa, USA A uniaxial shake table test of a full-scale slice of a seven-story reinforced concrete wall building was performed at the University of California, San Diego. A 2D analytical model that primarily employed fiber-based beam-column elements was used for a blind prediction of the global response of the building to the imposed input accelerations. An improved analytical model, which adequately simulates the building s dynamic response and comparison of measured and analytical results, is presented. The lessons learned from participation in the blind prediction with particular attention to the effects of issues commonly ignored in analytical modeling of concrete buildings are included. Keywords Concrete; Wall; Multi-story Building; Shake Table Testing; Seismic; Dynamic; Analysis; Nonlinear 1. Introduction In the fall of 2005, a portion of a full-scale seven-story concrete building, which is hereafter refered to as the test building, was constructed and tested under unidirectional earthquake motions using an outdoor shake table at the University of California, San Diego (UCSD). A capacity-based design approach was used to determine the structural details of the building elements, which led to smaller member dimensions and reduced amounts of reinforcing steel than those typically required by a traditional design code approach [Restrepo, 2006]. The smaller member sizes and reduced reinforcing steel created a more flexible structure that was both economical and easier to construct, while satisfying criteria to produce ductile response for the building under the selected seismic input motions. A blind prediction contest was held from April to May 2006, in which teams of practicing engineers, researchers, and students from all over the world participated and predicted the expected response of the test structure using the construction details and measured engineering material properties made available to them. The time-histories of the four input motions, named EQ1, EQ2, EQ3, and EQ4, were also provided as part of the contest. The model used for the blind prediction by the writers, hereafter referred to as the original model, was developed based on fiber-based beam column elements available in OpenSees [Mazzoni et al., 2004]. Other participants used various modeling approaches including: 3D solid elements, plain stress elements, multiple vertical line elements, and elastic beam elements [Restrepo, 2006]. The original model under predicted the overturning moments by 30 40%, story shear forces by 20 40%, and the residual displacements by 50 70%. The lateral displacement envelope was adequately predicted for EQ1 Received 10 December 2007; accepted 22 July Address correspondence to Sri Sritharan, Department of Civil, Construction, and Environmental Engineering, Iowa State University, 394 Town Engineering Building, Ames, IA 50011, USA; sri@iastate.edu 448

3 Seismic Analysis of a Seven-Story Building 449 and EQ3, and under predicted for EQ2 and EQ4. In general, the floor accelerations were the best predicted quantities for events EQ1, EQ2, and EQ3, where the original model predicted values within 20% of the recorded floor accelerations of the test building. For EQ4, the floor accelerations were over predicted by 20 35%. The response of the building to EQ3, particularly the overturning moments, was difficult for participants to capture [Restrepo, 2006; Trevor, 2007]. A full description and discussion of the original model and corresponding results can be found in Waugh and Sritharan [2006]. A number of components were responsible for the discrepancies between the results from the original model and the recorded test data. The components that were ignored in the original model were the couple generated by the gravity columns, the stiffening effect of the link slab, and the flexibility of the shake table and foundation. Most of the participants made similar decisions about the importance of modeling these portions of the structure, as reported in the articles found in the proceedings of the NEES/UCSD Workshop on the Analytical Modeling of Reinforced Concrete Walls [Restrepo, 2006]. However, the excluded structural elements played an important role in the overall response, and thus influenced the accuracy of the predicted response parameters. Additionally, the structure had limited non structural elements, which in general significantly contribute to viscous damping, causing most of the analytical models to experience an excessive amount of viscous damping. In this article, an improved analytical model is presented by addressing the shortcomings of the original model. This model, hereafter referred to as the improved model, builds on the strengths of the original model and includes additional important features that are typically ignored when modeling multi-story buildings. The most significant feature is the inclusion of the effects of gravity columns, which is given a full treatment in this article due to its significance to seismic design practice. A brief description of the test building and testing methodology are presented first to show how the structure was constructed and tested at UCSD. Next, the description of the improved analytical model used to characterize the response of the test building using measured properties is presented, with emphasis on overcoming the limitations of the original model. The analytical results, including envelopes of design forces, floor level displacements, and inter-story drift ratios as well as time-histories of the base moment, top floor displacement, and top floor acceleration of the structure, are then presented and compared with the experimental values. Finally, based on the comparison of results, lessons learned from participation in the blind prediction contest and recommendations to improve seismic modeling of buildings consisting of structural walls and gravity columns are presented. 2. Test Building and Test Methodology Figures 1a and 1b show, respectively, the floor plan and elevation of the test building which consisted of a 4.88 m long cast-in-place (CIP) flange wall, a 3.66 m long CIP web wall, and a C-shaped precast, segmental pier with unbonded post-tensioning. The web wall primarily provided the lateral force resistance in the earthquake loading direction, while the flange wall and precast pier primarily provided stability in the transverse direction and torsional resistance for the test building. In addition, four pin-ended Dywidag prestressing bars, 44.5 mm in diameter for the first story and 25.4 mm in diameter for the second story and above, were used as columns within each story. The Dywidag bars were grouted inside mm diameter, 8.6 mm thick steel pipes to prevent them from experiencing buckling. Due to the pin-ended connections, these columns were assumed in design to act as gravity columns and not to contribute to lateral

4 450 J. D. Waugh and S. Sritharan FIGURE 1 Floor plan and elevation of the test building [after NEES7Story, 2006]. force resistance. The floor at each level was 3.66 m wide, 8.13 m long, and mm thick reinforced concrete slab, and was supported by the web wall and four steel columns. Both the flange and web walls had fixed connections to the shake table, while the precast pier connection to the shake table was designed to act as a pin in the loading direction while providing large moment resistance in the orthogonal direction. This was achieved by aligning the post-tensioning tie-downs to the shake table in the direction orthogonal to the direction of the shaking such that it led to relatively small moment resistance in the loading direction. Discussions with researchers at UCSD confirmed that the longitudinal mild steel reinforcement in the pier was not extended into the foundation and that pier was free to rock at the base. The flange wall and the precast pier were designed to have pin connections to the floor slab. Figure 1b includes a magnification of the link slab connecting the main floor slab and web wall to the flange wall. The link slab incorporated two mm deep by 50.8 mm wide slots in the slab near the flange wall to accomplish the pin connection to the main floor slab. The pin connection between the pier and the floor slab was accomplished by using steel angles bolted to the floor slab and precast pier. The bolted connections and the limited moment capacity of the angles prevented the transfer of moment from the main floor slab to the pier. The shake table testing of the building included several input motions, which were: one low amplitude white noise, three low intensity earthquakes, and one high intensity earthquake. The low intensity earthquake records chosen were the longitudinal (EQ1) and transverse (EQ2) components from the 1971 San Fernando earthquake recorded at site, vnuy, and the longitudinal component from the 1994 Northridge earthquake at site, whox (EQ3). The high intensity record was the 360 component taken from Sylmar Olive View Med (EQ4) that was recorded in the 1994 Northridge earthquake located near the epicenter of the earthquake [NEES7Story, 2006]. The strongest 30 s of ground motions EQ1, EQ2, EQ3, and EQ4 are shown in Fig. 2, while the response spectra of these

5 Seismic Analysis of a Seven-Story Building 451 FIGURE 2 Earthquake input motions used for the shake table test. motions corresponding to 5% viscous damping are shown in Fig. 3. The input ground motions for the blind prediction were given at both 50 and 240 Hz; the 50 Hz motions were selected for the dynamic analyses reported in this article. The low-intensity input motions were expected to cause limited damage to the test building while the highintensity earthquake was anticipated to cause significant damage. In all cases, the plastic hinge and the associated damage was expected to concentrate in the first floor level of the test building. FIGURE 3 Earthquake input motions response spectra with 5% damping.

6 452 J. D. Waugh and S. Sritharan 3. Analytical Model and Key Features The original model used for the blind prediction contest was a simple centerline model that included the web wall, flange wall, and post-tensioned segmental pier. As previously stated, this model was generally satisfactory in predicting the displacements and accelerations, but not overturning moments. The concept and relevant details of the improved model, together with discussion of critical issues that eliminated the deficiencies of the original model are presented below Overview As noted, both the original and improved models of the test building were created to balance the need for accuracy with the desire for a relatively simple model that would run quickly and could be built based on the geometry and measured material properties. Because the accelerations were only applied in one direction, a two-dimensional model parallel to the web wall was preferred. OpenSees [Mazzoni et al., 2004] was selected as the analysis software because of its use in an ongoing PreNEESR project that focuses on concrete wall buildings [Sritharan et al., 2005]. As part of this project, the capabilities of OpenSees for analyzing walls have been studied and new features have been added [e.g., Zhao and Sritharan, 2007]. The seismic mass of the structure was lumped at the floor levels to simplify the model and expedite the analysis. The mass corresponding to each floor was calculated by determining the mass of the floor slab and one half-story height of the flange wall, web wall, pier, and gravity columns above and below the floor, and concentrated at the node located a the floor level. The weight of the structure was also applied as point loads on the nodes at each floor level to account for the gravity effects. Table 1 summarizes the point loads and masses applied to the model. The number of elements and nodes in the improved analytical model maintains the simplicity and efficiency of the original model. A diagram delineating the improved OpenSees model is shown in Fig. 4, which had a total of 83 nodes and 81 elements including 56 beam-column elements, 22 truss elements, and 3 zero-length interface elements. In comparison, the models used by other participants had as many as 3,143 elements and 3,360 nodes [Restrepo, 2006]. TABLE 1 Nodal gravity forces and masses Location Nodal force (kn) Mass (kn*s 2 /m) 1 st Floor Web Wall st Floor Flange Wall st Floor Pier nd 6 th Floor Web Walls nd 6 th Floor Flange Walls nd 6 th Floor Piers th Floor Web Wall th Floor Flange Wall th Floor Pier

7 Seismic Analysis of a Seven-Story Building 453 FIGURE 4 Schematic of the improved OpenSees model diagram of the test building Lateral Force Resisting System Based on the previous work done in modeling the response of structural walls to cyclic displacements by the writers, the flange and web walls of the test building were modeled using fiber-based beam-column elements. Due to difficulties in obtaining compatible forces and deformations for the force-based beam-column elements modeling the flange and web walls in the dynamic analysis, displacement-based beam-column elements were chosen. However, the first-story web and flange walls were modeled using the forcebased beam-column elements because they are considered to be a better choice for modeling the plastic hinge regions [Neuenhofer and Filippou, 1997]. The beam-column elements were assigned fiber sections that discretely modeled the reinforcement as well as confined and unconfined concrete regions. The first floor web wall section was discretized using 100 confined concrete fibers and 302 unconfined concrete fibers, while the first-floor flange wall section was discretized with 20 confined concrete and 456 unconfined concrete fibers. The sections for the upper-level flange wall used 60 unconfined concrete fibers to discretize the wall, while the upper-level web wall section used 72 unconfined concrete fibers. A single beam-column element with five integration points along the element length was used to represent each wall within each story. The choice of

8 454 J. D. Waugh and S. Sritharan FIGURE 5 Wall and pier reinforcement details [after NEES7Story, 2006]. using five integration points for the beam-column elements representing the walls at each floor level was based on the experience of the OpenSees community, and that of the writers work on simulating the response of concrete walls. The fibers representing the longitudinal reinforcement in various elements were located according to the as-built drawings shown in Figs. 5a and 5b, which depict the dimensions and reinforcement details of the flange and web walls at the first floor and for floors two through seven, respectively. The properties of the confined concrete were calculated using the transverse reinforcement details and the confined concrete model proposed by Mander et al. [1988], and were assigned to the corresponding fibers in the wall cross-sections at the first story of the building model. The upper stories had no confinement reinforcement and thus the concrete was modeled using unconfined concrete fibers. Material models Steel02 and Concrete03 available in OpenSees were used to model the reinforcing steel and concrete behavior. The properties of the unconfined concrete and steel reinforcement material models were chosen to closely match the experimental stress-strain behavior established for these materials. Figures 6a and 6b show the measured and modeled monotonic stress-strain curves of the unconfined concrete in the first story walls and the #4 (d b = 12.7 mm, where d b is the bar diameter) longitudinal bars used in the flange and web walls, respectively. It can be seen that the chosen concrete model adequately captures the unconfined concrete behavior. The behavior of the reinforcing steel was accurately modeled up to a strain of about 0.06 and significant discrepancies between the measured and modeled behaviors were expected at larger strains. To account for the low-cycle fatigue behavior, the fracture strain for the longitudinal reinforcement was taken as 0.06 and thus the longitudinal steel reinforcement strains were limited to 0.06 during the analysis. The tension capacity of concrete was modeled using a peak tensile strength of 0.59 p f c with nonlinear post-peak softening

9 Seismic Analysis of a Seven-Story Building 455 FIGURE 6 Material model comparisons. following the University of Houston model proposed by Hsu [1993], where f c is in MPa. Figures 6c and 6d show the cyclic response characteristics of the steel and concrete material models, while the parameters used for the concrete and reinforcement material models in the analysis are given in Tables 2 and 3, respectively. The strain penetration effects resulting from anchoring of the wall longitudinal reinforcing bars into the foundation block were included in the model using a zerolength section element with the same cross-section as the wall element above it. However, TABLE 2 Concrete material properties as defined in OpenSees Location Peak compressive stress (MPa) Peak compressive strain (mm/mm) Ultimate compressive stress (MPa) Ultimate compressive strain (mm/mm) Peak tension stress (MPa) Peak tension strain (mm/mm) 1 st Level Walls Unconfined 2 nd 6th Level Walls Precast Segmental Pier Slab Beams & Link Slab 37.4* * * * * * * * * Based on the average response of tested concrete cylinders.

10 456 J. D. Waugh and S. Sritharan TABLE 3 Steel material properties as defined in OpenSees Size & location Yield stress (MPa) Young s modulus (MPa) Strain hardening ratio #4 - Flange and Web Walls 434.4* 199,948* #5 - Flange and Web Walls 434.4* 199,948* #6 - Flange and Web Walls 475.7* 199,948* #7 - Flange and Web Walls 461.9* 199,948* #4 - Precast Pier 461.9* 199,948* #5 Precast Pier 489.5* 199,948* Pier Bracing , Gravity Columns , * Based on the average response of tested reinforcement bars. the steel material model in this element was replaced with the strain penetration model developed by Zhao and Sritharan [2007], which describes the total bar slip due to strain penetration as a function of stress in the bar. This accounted for the additional flexibility resulting from the wall end rotation due to penetration of strain along the longitudinal reinforcement into the foundation block. The bottom node on the interface element was fixed for all degrees-of-freedom while the top node was only restrained against lateral translation. The bottom ends of the beam-column elements modeling the first-story flange and web walls of the building were connected to the top nodes of the interface elements. The unbonded post-tensioned pier was also modeled using displacement beamcolumn elements. A fiber section was used to represent the pier cross-section shown in Fig. 5c. The section was defined using 40 unconfined concrete fibers; the material properties used for the pier concrete and reinforcement are included in Tables 2 and 3, respectively. Similar to the flange and web walls, a single beam-column element with five integration points along the element was used to represent the pier within each story. Anticipating primarily an elastic response, the unbonded post-tensioning rods in the pier were modeled using a single truss element that was given an elastic perfectly plastic material behavior and an initial strain to simulate the effect of prestress. The truss element shared the nodes at the top and bottom of the beam-column element modeling precast pier without any additional constraints along the height of the pier. Since the pier base moment resistance was relatively small and had limited impact on the overall response, this approach was deemed appropriate. As previously noted, the base of the pier was not rigidly connected to its foundation, but it allowed a small moment resistance to be generated at this location by developing compression force at the base of pier and tension force in the post-tensioning rods. The braces connecting the pier to the floor slab (see Fig. 1a) were modeled using truss elements and the Steel02 material model. The truss elements connected the nodes at floor levels on the post-tensioned pier to the nodes at the end of the floor slab elements Floor Slabs and Gravity Columns As discussed, the gravity columns were very important to the overall structural response, but were ignored in the original model. Consistent with the design assumptions, most

11 Seismic Analysis of a Seven-Story Building 457 participants in the blind prediction did not model the floor slab and columns because the specially detailed pinned connections at the column ends were intended to remove them from providing the lateral load resistance. However, the influence of the gravity columns and floor slab on the overall force-displacement response of the test building was evident during testing, and was confirmed by Panagioutou and Restrepo [2006] using a pushover analysis of the building. The primary reason for this influence was that the columns developed significant axial strains during testing due to their interactions with the floor slab. Consequently, the columns closer to the compression side of the web wall were subjected to compression forces and those near the tension side of the web wall were subjected to tensile forces. This enabled a large moment couple to be developed due to the distance of 3.05 m between the compression and tension columns, effectively contributing up to 24% to the lateral force resistance of the test building. The interaction between the floor slabs and gravity columns were dictated by the flexural stiffness of the floors, fixed connection between the slab and walls, and axial constraints imposed to the floor slabs by the gravity columns. Therefore, it was expected that the extent of the flexural cracking of the concrete floor slab occurring perpendicular to the direction from the compression region of the web wall to the tension columns and tension region of the web wall to the compression columns to have influenced the amount of force developed in the gravity columns. Figure 7 shows a part of the 3D ANSYS [Swanson Analysis Systems, 1992] model created to understand the interaction between the floor slab and gravity columns. The ANSYS model included the web wall, floor slab, and four gravity columns per floor for the seven floors in the building slice. The floor slab and web wall were modeled using the concrete element Solid65, but the flange wall was not modeled. This element is an eight node brick element that incorporated tension cracking and compression crushing of the concrete material, but the latter capability of the model was turned off because crushing of concrete can prematurely occur in an ANSYS analysis as reported by Barbosa and Ribeiro [1998]. The effect of the confined concrete was modeled by modifying the uniaxial behavior defined for the material in the boundary elements of the web wall using the confined concrete model of Mander et al. [1988]. The longitudinal and transverse reinforcement in the Solid65 element is smeared across the element area and defined with orientation relative to the global coordinate system and a uniaxial material model describing its stress-strain characteristics. The nodes along the top of the wall in the model were constrained to displace equally in the direction parallel to the length of the web wall. The behavior of this 3D model was studied by imposing monotonic displacement pattern that followed the first mode response of the test building. FIGURE 7 The ANSYS model used to understand the 3D effects of the floor slab.

12 458 J. D. Waugh and S. Sritharan FIGURE 8 Calibration of axial force induced in columns vs. inter-story displacement and the model chosen for the cyclic behavior. The 3D slab effect was introduced into the 2D OpenSees model using a beamcolumn element at each floor level. A bilinear moment-curvature envelope was selected to define the section behavior of this element. The initial slope of the moment-curvature relation is based on the uncracked slab properties with the flexural stiffness of 1,130 and 3,390 MN-m-rad for the positive and negative moments, respectively. The two different stiffness values are due to the different reinforcement mats in the top and bottom of the slab. The moment at the transition between the two linear portions was defined by the flexural cracking moment occurring over an effective width of the slab. This moment was estimated to be kn-m, based on an effective slab width of 11.5 times the slab thickness (or 2.33 m) that was determined from the ANSYS analysis results (see Fig. 6b). A post cracking stiffness ratio of 20% that was determined using the nominal strength and the corresponding curvature of the slab section over the effective width defined the second slope. This approach for modeling the 3D effects of the slab-to-gravity column interaction in the 2D OpenSees model was validated by comparing the axial force induced in the columns vs. inter-story displacement with that obtained from the ANSYS model. Figure 8a depicts this response at the first story level and confirms that the 3D effects of the slab-column interaction was satisfactory addressed in the 2D model, while Fig. 7b shows the origin centered hysteretic model used for the moment-curvature behavior of the section of this beam-column element. The gravity columns were modeled using truss elements with the appropriate crosssectional area to simulate the axial constraints provided by the Dywidag bars. Since the OpenSees model was only 2D, the area of the two columns on each end of the web wall were modeled with a single truss element with twice the area of a single column. Small rigid links were used to model the thickness of the floor slab to accurately simulate the clear length of the gravity columns Link Slab Connection Similar to the gravity columns, the effects of the link slabs were typically overlooked by the participants in the blind prediction contest. The link slab shown in Figs. 1a and 1b refers to the regions where notches were cut in the portion of floor slab connecting the flange and web walls. The intent of this detail was to minimize the moment resistance at the flange wall-to-slab interface while allowing the transfer of in-plane inertia forces.

13 Seismic Analysis of a Seven-Story Building 459 Despite minimizing the moment, a significant shear along the length of the notch was possible, which, in turn, increased the axial load in the web wall. Panagioutou and Restrepo [2006] also observed this stiffening effect in their pushover model and showed that it almost doubled the axial load on the web wall when yielding of the horizontal notch reinforcement occurred as observed in the test. In the original model, the effect of the notches was included by constraining the lateral displacements of the flange and web wall, while the rotational DOFs for the flange and web wall nodes were not constrained. Other participants in the contest used similar approaches by using either constraint equations or truss elements to model the effect of the link slab; however, neither approach captures the axial stiffening of the web wall and associated increase in the lateral force resistance adequately. In the improved model, the link slab was modeled using three beam-column elements with fiber sections. Two beamcolumn elements were used to model each of the reduced sections of the slot, and the third beam-column element modeled the slab between the slots. The cross-sections for both the slab and slot regions were modeled using fibers representing the unconfined concrete and longitudinal reinforcement. This approach allowed yielding of the slab reinforcement along the notch, imposing the appropriate amount of additional axial load on the web wall. The additional axial load increased the resistance of the web wall by approximately 16%. The beam-columns elements modeling the notch did not include the effects of shear deformation. It is not clear if the notch regions sustained significant shear deformation. However, the UCSD researchers did not provide any specifics information about this issue in their discussions of the behavior of the link slab Table and Foundation Flexibility The connection between the test building and the shake table was modeled in the boundary conditions for the wall and pier elements. However, the shake table and foundation as a whole experienced some rotation and the building s response was influenced by the rotational stiffness of the table. The table flexibility was neglected in the original model. As shown in Fig. 4, a zero-length elastic rotational spring was used to account for this additional flexibility in the improved model; rigid beams were used to link the rotational spring to the bases of the web and flange walls, gravity columns, and precast pier. Table 4 lists the rotational stiffness of the table and foundation measured in each direction by the UCSD researchers for each of the ground motions. As indicated in this table, the average rotational stiffness obtained from the stiffness reported for the two directions during testing to EQ2, EQ3, and EQ4 defined the behavior of the rotational spring in the improved analytical model. The rotational stiffness reported for EQ1 was relatively high compared to the values for the other events and thus was not included when finding the average value. This approximation was preferred since the effects of all earthquakes were examined in one TABLE 4 Base spring rotational stiffness Rotational spring stiffness due to combined flexibility of table and foundation *10 7 (kips-ft/rad) EQ1 EQ2 EQ3 EQ4 Model Direction Direction

14 460 J. D. Waugh and S. Sritharan analysis and the expected error in displacement due to underestimating the table stiffness for EQ1 was found to be less than 5%. With this average value representing the rotational stiffness, one node of the rotational spring was fully fixed against deformation while the other node was allowed to rotate parallel to the web wall Influence of Shear Deformation Experimental research has shown that shear deformation can contribute significantly to the lateral displacement, especially at the lower floor levels, even in slender, flexuredominated walls [e.g., Thomsen and Wallace, 1995]. The effects of shear deformation need to be included to better simulate the lateral displacement, especially at the lower floor levels. The fiber sections used for the wall in the original model did not include any shear effects in the section formulation, requiring the shear response to be handled separately. Some of the other participants did not have to separately handle the shear deformation because the modeling approach they used included the effects of shear within their chosen elements. However, OpenSees did not have an option for including shear in the selected element definition and the fiber sections used in the analysis sums the uniaxial response of the fibers to determine the axial and moment resistance of the section. Because the fibers have zero resistance to transverse loads, the shear deformation cannot be determined at the section level. In the original model, an estimate of the additional lateral displacement due to shear deformation was added during post-processing of the results. In the improved model, the shear force-deformation response was added to the beam-column elements modeling the web wall during the analysis. The shear deformation of the flange wall was, however, neglected since its resistance was relatively small and the short dimension of the wall section was parallel to the direction of shear force. Aggregating the shear response onto the flexural response does not cause the axial strains experienced by the fibers due to curvature of the wall to change, neglecting the possible flexure-shear interaction. The lateral force vs. shear deformation hysteretic response of the web wall was modeled using a uniaxial material model. Figure 9 shows the pinching4 material model available in OpenSees that was used for this purpose at the first floor level. A FIGURE 9 Pinching4 material model used to account for the shear deformation contribution [Mazzoni et al., 2004].

15 Seismic Analysis of a Seven-Story Building 461 minimum of three points with an optional fourth point are needed to define the response envelope for this model. Because the measured shear deformation of the web wall was not available, only three points were defined for the pinching model as follows: (1) point 1 was defined using the lateral force corresponding to the first flexural cracking of the web wall (111.2 kn) and the uncracked shear stiffness; (2) point 2 was defined using the lateral force that was expected to cause flexural yielding of the longitudinal reinforcement (311.4 kn) and effective shear stiffness; and (3) point 3 was defined using the ultimate lateral force resistance (467.1 kn) and post-yield shear stiffness. The uncracked shear stiffness was obtained following the recommendation of Park and Paulay [1975] for an uncracked rectangular beam. The effective shear stiffness to the uncracked shear stiffness was taken as the same ratio as the flexural stiffness at yield to the gross flexural stiffness; this ratio was determined to be 20% of the uncracked stiffness. This choice to relate the cracked shear stiffness to the cracked flexural stiffness was based on observations of the behavior of RW2 and TW2 tested by Thomsen and Wallace [1993], RWN and NTW1 tested by Brueggen et al. [2007], and the rectangular walls tested by Oesterle et al. [1979]. Furthermore, research by Massone and Wallace [2004] showed that when inelastic flexural action occurs, inelastic shear action also begins because of coupling of the two responses. In order to simulate this coupling, the lateral force at yield was used to define the point when the tangent stiffness changes from the effective shear stiffness to the post-yield shear stiffness. The post-yield stiffness was defined based on the observed shear force versus deformation responses of NTW1 and RWN from the PreNEESR wall tests [Brueggen et al., 2007] and RW2 and TW2 tested by Thomsen and Wallace [1995]. Based on those data sets, the post-yield shear stiffness was approximated to 1.0% of the effective shear stiffness. Shear stiffness for the second floor and above was modeled using an elastic material model with stiffness equal to 35% of the uncracked shear stiffness to reflect the cracking of the wall Viscous Damping OpenSees includes Rayleigh damping as an option to capture the effects of the viscous damping during dynamic analysis. In a nonlinear system, the stiffness matrix used for calculating the damping matrix can have a significant impact on the results of the analysis. In the original model, Rayleigh damping was used in conjunction with the current stiffness matrix, allowing damping to decay as the damage accumulated. The coefficients needed to define the Rayleigh damping were obtained assuming 5% viscous damping for the first and third modes that were found from cracked section properties. Priestley and Grant [2004] recommended that tangent stiffness proportional damping be used for nonlinear analysis because Rayleigh damping heavily weights the mass matrix, leading to an almost constant damping matrix during the nonlinear response of the structure regardless of the degradation that occurred to the stiffness of the structure. Furthermore, observations by Moaveni et al. [2006] of the test building indicated approximately 3% damping on the first longitudinal mode when testing to white noise. However, Panagioutou and Restrepo [2006] used only 0.3% damping for the first longitudinal mode for accurate simulation of the test building s response to earthquake input motions. Such low damping may have been due to excluding the non structural elements in the test structure and limiting flexural cracking largely to the lower portion of the building due to the use of reduced longitudinal reinforcement. Consequently, in the improved model stiffness proportional viscous damping corresponded to 0.5% damping on the uncracked first mode period and 0.8% damping on the uncracked third mode period was used. This resulted in 0.02 and 0.5% viscous damping, respectively, on the cracked first and third

16 462 J. D. Waugh and S. Sritharan mode responses of the building. Since the damping was determined from the tangent stiffness matrix as recommended by Priestley and Grant, viscous damping was further reduced during response in the post-yield region Dynamic Analysis The input accelerations shown in Fig. 2 were applied to the base of the building model in the direction parallel to the web wall. Using the Newmark s constant average acceleration method for the integrator, the analysis was conducted at a time increment of 0.02 s to limit the amount of output that must be post-processed. However, when the analysis failed to converge, 10 substeps were carried out at s to find a solution, and then the time step was increased back to 0.02 s. In order to account for the effects of accumulated structural damage on the response of the test building, all input motions were concatenated. Six seconds of zero ground acceleration was added between the earthquake records to allow the structure to come to rest prior to being subjected to the next base input motion. The low accelerations at the end of the ground motions combined with the 6 s of padding were adequate for the structure to return to rest. The total applied ground motion record to the test building was slightly more than 522 s long from start to finish. The entire analysis took approximately 45 min to run on a 2.0 GHz Pentium IV based-computer with 1 GB of RAM running Windows XP. 4. Comparison of Results The capabilities of the improved model can be seen best by comparing key time-history responses with the measured data provided for the test building [NEES7Story, 2006]. For this purpose, the top-floor displacement, base moment, and top-floor acceleration are used. This is followed by comparison of envelope responses for variables that are of interest from a design viewpoint Time-History Responses Top-Floor Displacement. The top-floor displacement time-history is shown in Fig. 10 with a, b, c, and d representing, respectively, the response during the most intense 30 s of EQ1, EQ2, EQ3, and EQ4. The figures show that the period of the test building was well captured by the analysis model for all earthquake intensities, except around s into the EQ4 motion. Table 5 shows the period of the structure at various stages of loading. The analytical model simulated the period of the structure within 0.1 s. Additionally, all the significant peak displacements recorded during EQ1, EQ2, and EQ4 were generally well simulated, and were within 5% of the measured values. The peaks on EQ3 were under predicted by as much as 25%. The cause of the discrepancy for the EQ3 event was extensively studied, because similar discrepancies were observed in the predictions by other participants (e.g., Kelly, 2007). The fact that EQ2 and EQ3 were comparable to each other in earthquake intensity was the primary cause for large discrepancies in the response of EQ3 and consequently the unloading and reloading behaviors of the material models rather than their envelopes had a large influence on the analytical response of EQ3. Typically, the response envelopes of materials are more accurately characterized than their reloading and unloading action. This hypothesis was confirmed by scaling

17 Seismic Analysis of a Seven-Story Building 463 FIGURE 10 Comparison of measured and simulated displacement time-histories. TABLE 5 Comparison of measured and calculated structure fundamental period Measured period (s) Calculated period (s) Before Testing Following EQ Following EQ Following EQ Following EQ the accelerations of EQ2 by 0.6 without altering the other events and rerunning the analysis. This modification significantly improved the EQ3 response of the test building, bringing the peak displacements for this event to within 5% of the measured values. The concrete material model used for the analysis here used very simple unloading and reloading behavior, as shown in Fig. 6c. The poor simulation of EQ3 is, therefore, expected to be improved by using an improved constitutive model for concrete with more accurate representation for the unloading and reloading paths. Furthermore, the pinching4 model may not be adequately simulating the shear deformation of the web wall; however, without the measured data for the shear deformation, the accuracy of the shear behavior cannot be evaluated. The simple unloadingandreloadingbehaviorofthepinching4modelwasalsoexpectedtohave influenced the response of the test building to EQ3.

18 464 J. D. Waugh and S. Sritharan Base Overturning Moment. The base moment was determined by summing the moments at the base of the web and flange walls, and the couple generated by the gravity columns that had about 10 24% contribution to the base overturning moment. Time history comparison for the base moment is shown in Fig. 11, in which many of the characteristics observed for the top-floor displacement time-history are also seen in the base moment plot comparison. Again, it is noted that the period of the structure was well captured, showing that the analysis adequately captured the damage and subsequent softening of the structural stiffness. The peak values were generally well captured and are within 10 15% of the measured values for EQ1, EQ2, and EQ4. As expected, the response of EQ3 was not as well simulated giving results within 25% of the measured values due to the aforementioned reasons Top-Floor Acceleration. The top-floor acceleration time histories for all ground motions are shown in Fig. 12. The acceleration time history shows the expected response considering the under prediction of the lateral displacement. Despite capturing the period of the structure accurately, the peak floor accelerations are typically over predicted by the analysis by approximately 10 20% when compared with the responses measured during the test. The simulation of the top-floor acceleration was generally considered satisfactory given the large time step used for the input excitations used for the analysis and analysis time step. Simulation of the accelerations in a dynamic analysis can be sensitive to the time step used in the analysis and it typically requires a small time step to obtain accurate acceleration responses. The large time step used in the analysis allows a good simulation of the floor level accelerations without requiring an extensive amount of computational time needed to use a small time step and post-process the corresponding analysis output. FIGURE 11 Comparison of measured and simulated base moment time-histories.

19 Seismic Analysis of a Seven-Story Building 465 FIGURE 12 Comparison of measured and simulated acceleration time-histories Envelope Responses The envelope responses of the test building model along with their experimental values are shown in Figs. 13 with a, b, c, and d representing the lateral displacement, inter-story drift, overturning moment, and story shear, respectively. The comparisons of the envelopes are discussed below in recognition of their influence on design Lateral Displacement. The floor-level lateral displacements shown in Fig. 13a are generally well simulated, with the exception of EQ3. The displacements of EQ3 were under predicted by about 17%. For the rest of the ground motions, the predicted lateral floor displacements were within 10% of the recorded values during the shake table tests. The top floor displacements were generally better captured than the first floor displacements. This could be due to the influence of the shear deformation, since shear deformation has a larger impact on the lower floor level displacements. The peak average interstory drift obtained from the top floor displacement divided by the height of the building is used in the design of the structure. Despite designing the building as a flexible structure, the test building did not experience excessive lateral drifts. The maximum average drift ratios were found to be 0.27% for EQ1, 0.81% for EQ2, and 1.88% for EQ4, and the corresponding measured values were 0.27%, 0.76%, and 2.06%, respectively. As expected, a poor comparison was obtained for EQ3 response and the calculated and measured peak average drifts for this event were 0.69% and 0.83%, respectively Interstory Drift Ratio. An accurate simulation of the inter-story drift is important to predict the damage to structural as well as non structural elements. The inter-story drift

20 466 J. D. Waugh and S. Sritharan FIGURE 13 Comparison of measured and simulated response envelopes. ratios, shown in Fig. 13b, were well simulated by the analysis and were within 10% of the experimental values for EQ1, EQ2, and EQ4. The EQ3 inter-story drift was poorly simulated with results being within 20% of the measured values for the reasons previously discussed Overturning Moment Envelope. The overturning moments, shown in Fig. 13c, were generally under predicted by the analysis compared to the envelopes established from the measured data. If the results for EQ3 are ignored, then the analytical results were within 5 15% of the recorded values. The results for EQ3 were within 25% of the measured values except for the top two floors, where they were under predicted by 30 40%. The moment generated by the gravity columns contributed 18 24% of the overturning moment resistance for EQ2, EQ3, and EQ4, while approximately 10% for EQ1. The difference between the measured and calculated overturning moments was expected due to the influence of the higher-mode effects. However, it is noted that the time-history shown in Fig. 11 for the base moment was generally well simulated as a function of time Story Shear Forces. The story shear forces, depicted in Fig. 13d, show a similar trend to that observed for the overturning moments. The analysis under predicted the measured responses by approximately 5 15% for EQ1, EQ2, and EQ4; however, EQ3 was under predicted by approximately 25%. As stated before, the analytical response of the test building during EQ3 was controlled by the unloading and reloading behavior of the material models and improvements to the cyclic behavior of the material models would improve the

21 Seismic Analysis of a Seven-Story Building 467 analytical response of the building to EQ3. Overall, the story shear forces were adequately captured, and an accurate prediction of the shear demand would help ensure that shear failure of the walls would not control the seismic behavior of the building. 5. Summary, Conclusions, and Lessons Learned A 2D centerline model was created in OpenSees for a full-scale portion of a building that was designed and subjected to shake table tests at UCSD. This model emphasized simplicity and ease of creation based on the geometry and material properties. The original model used beam-column elements to model the flange and web walls, and the post-tensioned pier that was used primarily to provide stability to the test building. The improved model added elements that were ignored in the original model such as the link slab, gravity columns, and a rotational spring to simulate the flexibility of the shake table, all of which led to significant improvements to the analytical model. The link slab and notches were modeled with beam-column elements, providing the stiffening of the web wall observed in the test. The gravity columns contributed to the lateral resistance by developing axial tension and compression in the columns located at opposite ends of the web wall, thereby creating a moment couple. The axial loads in the columns were controlled by the 3D deformation of the floor slabs. A 3D ANSYS analysis determined an effective slab width of 11.5 times the slab thickness, which was used to define the behavior of a beam-column element at each floor level to capture the corresponding effect in the 2D OpenSees model. The improved model remains simple and easy to construct, while giving accurate simulation of the structural response. The conclusions drawn from the analysis of a large system such as the test building studied herein are: Simple, computationally efficient 2D models with fiber sections that satisfactorily account for any 3D effect are sufficient to predict the response of concrete wall buildings subjected to unidirectional earthquake motions. In this study, the effect that the floor slabs had on the axial load of the gravity columns was investigated using a 3D ANSYS model, but such an effort will not be needed if an effective floor slab width needed to account for the effect in the 2D model is known. Inclusion of the gravity columns, link slab, and table flexibility were required to accurately capture the response of the structure to the earthquake input motions. Neglecting these components in the original model significantly affected the ability of the model to predict the dynamic response of the building. The gravity columns contributed significantly to the overturning moment in the structure. The couple generated by the axial load in the columns contributed 10 24% to the overturning moment. The contribution of the gravity columns generally increased as the intensity of the earthquake motions increased. The time-history responses for the top-floor displacement, base overturning moment, and top-floor acceleration were well predicted by the improved 2D model for EQ1, EQ2, and EQ4 motions. The analysis gave results within 5% of the measured values for displacements while the base overturning moments and top-floor acceleration peak values were within 10 15%. When subjected to input motions EQ1, EQ2, and EQ4, the improved 2D model gave results that were within 5 15% of the envelope for displacement, inter-story drift, overturning moment, and story shear forces. Under input motion EQ3, the discrepancies between the analytical responses and the measured values were as large as 25%. This was due to EQ3 having a similar

Modeling of Coupled Nonlinear Shear and Flexural Responses in Medium-Rise RC Walls

Modeling of Coupled Nonlinear Shear and Flexural Responses in Medium-Rise RC Walls ing of Coupled Nonlinear Shear and Flexural Responses in Medium-Rise RC Walls Burak HOROZ 1, M.Fethi GÜLLÜ 2, and Kutay ORAKÇAL 3 1 Research Assistant Bogazici University, Istanbul, Turkey 2 Research Assistant

More information

Modelling of RC moment resisting frames with precast-prestressed flooring system

Modelling of RC moment resisting frames with precast-prestressed flooring system Modelling of RC moment resisting frames with precast-prestressed flooring system B.H.H. Peng, R.P. Dhakal, R.C. Fenwick & A.J. Carr Department of Civil Engineering, University of Canterbury, Christchurch.

More information

Analytical Modeling of the Contribution of Transverse Reinforcement in Prestressed Concrete Bridge Girders

Analytical Modeling of the Contribution of Transverse Reinforcement in Prestressed Concrete Bridge Girders Analytical Modeling of the Contribution of Transverse Reinforcement in Prestressed Concrete Bridge Girders Katie Boris, REU Student Padmanabha Rao Tadepalli, Graduate Mentor Y. L. Mo, Faculty Advisor Final

More information

10. Model Discretization and Calibration

10. Model Discretization and Calibration 10. Model Discretization and Calibration Lesson Objectives: 1) Define various model discretization types and select the appropriate discretization for the analysis objective, model accuracy, and computational

More information

INELASTIC SEISMIC RESPONSE ANALYSES OF REINFORCED CONCRETE BRIDGE PIERS WITH THREE-DIMENSIONAL FE ANALYSIS METHOD. Guangfeng Zhang 1, Shigeki Unjoh 2

INELASTIC SEISMIC RESPONSE ANALYSES OF REINFORCED CONCRETE BRIDGE PIERS WITH THREE-DIMENSIONAL FE ANALYSIS METHOD. Guangfeng Zhang 1, Shigeki Unjoh 2 INELASTIC SEISMIC RESPONSE ANALYSES OF REINFORCED CONCRETE BRIDGE PIERS WITH THREE-DIMENSIONAL FE ANALYSIS METHOD Abstract Guangfeng Zhang 1, Shigeki Unjoh 2 This paper aims to provide an analysis method

More information

Performance based Displacement Limits for Reinforced Concrete Columns under Flexure

Performance based Displacement Limits for Reinforced Concrete Columns under Flexure Performance based Displacement Limits for Reinforced Concrete Columns under Flexure Ahmet Yakut, Taylan Solmaz Earthquake Engineering Research Center, Middle East Technical University, Ankara,Turkey SUMMARY:

More information

Fiber-Based Modeling for Investigating the Effect of Load History on the Behavior of RC Bridge Columns

Fiber-Based Modeling for Investigating the Effect of Load History on the Behavior of RC Bridge Columns Fiber-Based Modeling for Investigating the Effect of Load History on the Behavior of RC Bridge Columns Y. Feng, M.J. Kowalsky & J.M. Nau North Carolina State University, Raleigh SUMMARY: Ensuring that

More information

MODELLING OF SHEAR WALLS FOR NON-LINEAR AND PUSH OVER ANALYSIS OF TALL BUILDINGS

MODELLING OF SHEAR WALLS FOR NON-LINEAR AND PUSH OVER ANALYSIS OF TALL BUILDINGS MODELLING OF SHEAR WALLS FOR NON-LINEAR AND PUSH OVER ANALYSIS OF TALL BUILDINGS Naveed Anwar 1, Thaung Htut Aung 2 ABSTRACT: The Performance Based Analysis and design of buildings and structures, especially

More information

CHAPTER 5 FINITE ELEMENT MODELLING

CHAPTER 5 FINITE ELEMENT MODELLING 53 CHAPTER 5 FINITE ELEMENT MODELLING 5.1 GENERAL Reinforced concrete structures are largely employed in engineering practice in a variety of situations and applications. In most cases these structures

More information

The Effect of Frame Geometry on the Seismic Response of Self-Centering Concentrically- Braced Frames

The Effect of Frame Geometry on the Seismic Response of Self-Centering Concentrically- Braced Frames International Journal of Civil and Environmental Engineering 6 212 The Effect of Frame Geometry on the Seismic Response of Self-Centering Concentrically- Braced Frames David A. Roke and M. R. Hasan Abstract

More information

Comparison of Chevron and Suspended Zipper Braced Steel Frames

Comparison of Chevron and Suspended Zipper Braced Steel Frames 9 th International Congress on Advances in Civil Engineering, 27-30 September 2010 Karadeniz Technical University, Trabzon, Turkey Comparison of Chevron and Suspended Zipper Braced Steel Frames A. Y. Ozcelik

More information

Seismic Performance and Modeling of Post-Tensioned, Precast Concrete Shear Walls

Seismic Performance and Modeling of Post-Tensioned, Precast Concrete Shear Walls Seismic Performance and Modeling of Post-Tensioned, Precast Concrete Shear Walls A.C. Tanyeri & J.P. Moehle University of California, Berkeley, USA T. Nagae National Research Institute for Earth Science

More information

User Elements Developed for the Nonlinear Dynamic Analysis of Reinforced Concrete Structures

User Elements Developed for the Nonlinear Dynamic Analysis of Reinforced Concrete Structures Research Collection Conference Paper User Elements Developed for the Nonlinear Dynamic Analysis of Reinforced Concrete Structures Author(s): Wenk, Thomas; Linde, Peter; Bachmann, Hugo Publication Date:

More information

CHAPTER 1: INTRODUCTION

CHAPTER 1: INTRODUCTION CHAPTER 1: INTRODUCTION 1.1 Introduction Inadequate performance of reinforced concrete bridges during the 1989 Loma Prieta and 1994 Northridge earthquakes focussed attention on the design of these structures.

More information

Inelastic Behavior of Hollow Reinforced Concrete Bridge Columns

Inelastic Behavior of Hollow Reinforced Concrete Bridge Columns Inelastic Behavior of Hollow Reinforced Concrete Bridge Columns T.-H. Kim Construction Product Technology Research Institute, Samsung Construction & Trading Corporation, Korea SUMMARY The purpose of this

More information

CHAPTER 7 ANALYTICAL PROGRAMME USING ABAQUS

CHAPTER 7 ANALYTICAL PROGRAMME USING ABAQUS 87 CHAPTER 7 ANALYTICAL PROGRAMME USING ABAQUS 7.1 GENERAL With the advances in modern computing techniques, finite element analysis has become a practical and powerful tool for engineering analysis and

More information

Fagà, Bianco, Bolognini, and Nascimbene 3rd fib International Congress

Fagà, Bianco, Bolognini, and Nascimbene 3rd fib International Congress COMPARISON BETWEEN NUMERICAL AND EXPERIMENTAL CYCLIC RESPONSE OF ALTERNATIVE COLUMN TO FOUNDATION CONNECTIONS OF REINFORCED CONCRETEC PRECAST STRUCTURES Ettore Fagà, Dr, EUCENTRE, Pavia, Italy Lorenzo

More information

BEHAVIOR OF REINFORCED CONCRETE BEAM WITH OPENING

BEHAVIOR OF REINFORCED CONCRETE BEAM WITH OPENING International Journal of Civil Engineering and Technology (IJCIET) Volume 8, Issue 7, July 2017, pp. 581 593, Article ID: IJCIET_08_07_062 Available online at http:// http://www.iaeme.com/ijciet/issues.asp?jtype=ijciet&vtype=8&itype=7

More information

STRUCTURAL APPLICATIONS OF A REINFORCED CONCRETE BEAM-COLUMN-SLAB CONNECTION MODEL FOR EARTHQUAKE LOADING

STRUCTURAL APPLICATIONS OF A REINFORCED CONCRETE BEAM-COLUMN-SLAB CONNECTION MODEL FOR EARTHQUAKE LOADING STRUCTURAL APPLICATIONS OF A REINFORCED CONCRETE BEAM-COLUMN-SLAB CONNECTION MODEL FOR EARTHQUAKE LOADING B.B. Canbolat 1 1 Assistant Professor, Dept. of Civil Engineering, Middle East Technical University,

More information

FINITE ELEMENT ANALYSIS OF REINFORCED CONCRETE BRIDGE PIER COLUMNS SUBJECTED TO SEISMIS LOADING

FINITE ELEMENT ANALYSIS OF REINFORCED CONCRETE BRIDGE PIER COLUMNS SUBJECTED TO SEISMIS LOADING FINITE ELEMENT ANALYSIS OF REINFORCED CONCRETE BRIDGE PIER COLUMNS SUBJECTED TO SEISMIS LOADING By Benjamin M. Schlick University of Massachusetts Amherst Department of Civil and Environmental Engineering

More information

Modeling of Shear Walls for Nonlinear and Pushover Analysis of Tall Buildings

Modeling of Shear Walls for Nonlinear and Pushover Analysis of Tall Buildings Asian Center for Engineering Computations and Software, AIT Asian Institute of Technology, Thailand 14th ASEP International Convention, Philippines, May 2009 Modeling of Shear Walls for Nonlinear and Pushover

More information

3-D FINITE ELEMENT ANALYSIS OF PILE-TO-PILE CAP CONNECTIONS SUBJECTED TO SEISMIC ACTION

3-D FINITE ELEMENT ANALYSIS OF PILE-TO-PILE CAP CONNECTIONS SUBJECTED TO SEISMIC ACTION 3-D FINITE ELEMENT ANALYSIS OF PILE-TO-PILE CAP CONNECTIONS SUBJECTED TO SEISMIC ACTION M. Teguh 1,2), C.F. Duffield 1), P. A. Mendis 1), G.L. Hutchinson 1) 1) University of Melbourne, Melbourne, Victoria

More information

Effect of Axial load on deformation capacity of RC column

Effect of Axial load on deformation capacity of RC column Effect of load on deformation capacity of RC column N. G. Patoliya 1, Prof. C. S. Sanghvi 2 1 Narmada, Water Resources, Water Supply and Kalpsar Department, Government of Gujarat,, patoliyanirav@yahoo.co.in

More information

EXPERIMENTAL INVESTIGATION ON THE INTERACTION OF REINFORCED CONCRETE FRAMES WITH PRECAST-PRESTRESSED CONCRETE FLOOR SYSTEMS

EXPERIMENTAL INVESTIGATION ON THE INTERACTION OF REINFORCED CONCRETE FRAMES WITH PRECAST-PRESTRESSED CONCRETE FLOOR SYSTEMS EXPERIMENTAL INVESTIGATION ON THE INTERACTION OF REINFORCED CONCRETE FRAMES WITH PRECAST-PRESTRESSED CONCRETE FLOOR SYSTEMS B.H.H. Peng 1, R.P. Dhakal 2, R.C. Fenwick 3, A.J. Carr 4 and D.K. Bull 5 1 PhD

More information

SEISMIC BEHAVIOR OF FOUR-CIDH PILE SUPPORTED FOUNDATIONS

SEISMIC BEHAVIOR OF FOUR-CIDH PILE SUPPORTED FOUNDATIONS SEISMIC BEHAVIOR OF FOUR-CIDH PILE SUPPORTED FOUNDATIONS José I. Restrepo 1, Inho Ha 2 and M.J.Nigel Priestley 3 Abstract This paper discusses the results of two large-scale models of Four-Cast-In-Drilled-

More information

UNIVERSITY OF PADUA ITALY Dept. Civil Environmental Arch. Eng. UNIVERSITY OF CALIFORNIA BERKELEY Dept. Civil and Environmental Eng.

UNIVERSITY OF PADUA ITALY Dept. Civil Environmental Arch. Eng. UNIVERSITY OF CALIFORNIA BERKELEY Dept. Civil and Environmental Eng. UNIVERSITY OF PADUA ITALY Dept. Civil Environmental Arch. Eng. UNIVERSITY OF CALIFORNIA BERKELEY Dept. Civil and Environmental Eng. Cyclic Inelastic Analysis of RC Shear Walls and Plates Leopoldo Tesser

More information

Deformation Capacity of RC Structural Walls without Special Boundary Element Detailing

Deformation Capacity of RC Structural Walls without Special Boundary Element Detailing Proceedings of the Tenth Pacific Conference on Earthquake Engineering Building an Earthquake-Resilient Pacific 6-8 November 2015, Sydney, Australia Deformation Capacity of RC Structural Walls without Special

More information

Seismic Analysis and Design of Flared Bridge Columns

Seismic Analysis and Design of Flared Bridge Columns Seismic Analysis and Design of Flared Bridge Columns by Hisham Nada 1, David Sanders 2, and M. Saiid Saiidi 3 ABSTRACT Past earthquakes have shown that flared columns are susceptible to premature shear

More information

SEISMIC PERFORMANCE OF BRIDGE COLUMNS WITH DOUBLE INTERLOCKING SPIRALS

SEISMIC PERFORMANCE OF BRIDGE COLUMNS WITH DOUBLE INTERLOCKING SPIRALS 13 th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 4 Paper No. 2198 SEISMIC PERFORMANCE OF BRIDGE COLUMNS WITH DOUBLE INTERLOCKING SPIRALS Juan F. Correal 1, M. Saiid

More information

EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS

EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS By H.S. Lew 1 and Sashi K. Kunnath Presented at the rd Joint Meeting of the UJNR Panel on Wind and Seismic Effects ABSTRACT This

More information

Overview of Presentation. SCBFs are Conceptually Truss Structures

Overview of Presentation. SCBFs are Conceptually Truss Structures Ultimate Strength and Inelastic Behavior of Braced Frame Gusset Plate Connections Charles W. Roeder University of Washington Department of Civil and Environmental Engineering Seattle, WA 98195 Structural

More information

Effect of Geometry of Vertical Rib Plate on Cyclic Behavior of Steel Beam to Built-up Box Column Moment Connection

Effect of Geometry of Vertical Rib Plate on Cyclic Behavior of Steel Beam to Built-up Box Column Moment Connection Available online at www.sciencedirect.com Procedia Engineering 14 (2011) 3010 3018 The Twelfth East Asia-Pacific Conference on Structural Engineering and Construction Effect of Geometry of Vertical Rib

More information

VERIFICATION OF A REINFORCED CONCRETE COLUMN COMPUTER MODEL UNDER UNIAXIAL AND BIAXIAL BENDING LOADING CONDITIONS

VERIFICATION OF A REINFORCED CONCRETE COLUMN COMPUTER MODEL UNDER UNIAXIAL AND BIAXIAL BENDING LOADING CONDITIONS Konferensi Nasional Teknik Sipil 4 (KoNTekS 4) Sanur-Bali, 2-3 Juni 2010 VERIFICATION OF A REINFORCED CONCRETE COLUMN COMPUTER MODEL UNDER UNIAXIAL AND BIAXIAL BENDING LOADING CONDITIONS Jimmy Chandra

More information

SHAKE TABLE TESTING OF BRIDGE REINFORCED CONCRETE COLUMNS UNDER COMBINED ACTIONS

SHAKE TABLE TESTING OF BRIDGE REINFORCED CONCRETE COLUMNS UNDER COMBINED ACTIONS SHAKE TABLE TESTING OF BRIDGE REINFORCED CONCRETE COLUMNS UNDER COMBINED ACTIONS Juan G. Arias Acosta, Graduate Student David H. Sanders, Professor and Project PI University of Nevada, Reno NEESR SG 53737

More information

In-plane testing of precast concrete wall panels with grouted sleeve

In-plane testing of precast concrete wall panels with grouted sleeve In-plane testing of precast concrete wall panels with grouted sleeve P. Seifi, R.S. Henry & J.M. Ingham Department of Civil Engineering, University of Auckland, Auckland. 2017 NZSEE Conference ABSTRACT:

More information

EXPERIMENTAL INVESTIGATION OF PRECAST CONCRETE BEAM TO COLUMN CONNECTIONS SUBJECTED TO REVERSED CYCLIC LOADS

EXPERIMENTAL INVESTIGATION OF PRECAST CONCRETE BEAM TO COLUMN CONNECTIONS SUBJECTED TO REVERSED CYCLIC LOADS 6 th International Conference on Seismology and Earthquake Engineering EXPERIMENTAL INVESTIGATION OF PRECAST CONCRETE BEAM TO COLUMN CONNECTIONS SUBJECTED TO REVERSED CYCLIC LOADS H. Shariatmadar 1, E.

More information

PLEASE SCROLL DOWN FOR ARTICLE

PLEASE SCROLL DOWN FOR ARTICLE This article was downloaded by:[bhattacharya, Baidurya] On: 24 March 2008 Access Details: [subscription number 787846188] Publisher: Taylor & Francis Informa Ltd Registered in England and Wales Registered

More information

Modelling of Reinforced Concrete Core Walls Under Bi-directional Loading

Modelling of Reinforced Concrete Core Walls Under Bi-directional Loading Modelling of Reinforced Concrete Core Walls Under Bi-directional Loading R. Constantin & K. Beyer Ecole Polytechnique Fédérale de Lausanne (EPFL), Switzerland SUMMARY: Reinforced concrete core walls with

More information

XTRACT: A Tool for Axial Force - Ultimate Curvature Interactions. C.B. Chadwell 1 and R.A. Imbsen 2

XTRACT: A Tool for Axial Force - Ultimate Curvature Interactions. C.B. Chadwell 1 and R.A. Imbsen 2 XTRACT: A Tool for Axial Force - Ultimate Curvature Interactions C.B. Chadwell 1 and R.A. Imbsen 2 1 Assistant Professor, Department of Civil and Environmental Engineering, California Polytechnic State

More information

Experimental study on the seismic performance of RC moment resisting frames with precast-prestressed floor units.

Experimental study on the seismic performance of RC moment resisting frames with precast-prestressed floor units. Experimental study on the seismic performance of RC moment resisting frames with precast-prestressed floor units. B.H.H. Peng, R.C. Fenwick, R.P. Dhakal & D.K. Bull Department of Civil and Natural Resources

More information

Nonlinear Finite Element Analysis of Composite Cantilever Beam with External Prestressing

Nonlinear Finite Element Analysis of Composite Cantilever Beam with External Prestressing Nonlinear Finite Element Analysis of Composite Cantilever Beam with External Prestressing R. I. Liban, N. Tayşi 1 Abstract This paper deals with a nonlinear finite element analysis to examine the behavior

More information

Comparisons to Tests on Reinforced Concrete Members

Comparisons to Tests on Reinforced Concrete Members 82 Chapter 6 Comparisons to Tests on Reinforced Concrete Members Finite element (FE) model predictions of laboratory test results of reinforced concrete members with various confinement methods are presented

More information

Simulation of Nonlinear Seismic Response of Reinforced Concrete Structural Walls

Simulation of Nonlinear Seismic Response of Reinforced Concrete Structural Walls Simulation of Nonlinear Seismic Response of Reinforced Concrete Structural Walls CE Magna University of California, Davis, CA, United States Universidad Diego Portales, Santiago, Chile SK Kunnath University

More information

Seismic Performance of Residential Buildings with Staggered Walls

Seismic Performance of Residential Buildings with Staggered Walls Seismic Performance of Residential Buildings with Staggered Walls Hyungoo Kang and Joonho Lee Graduate Student, Department of Architectural Engineering, Sungkyunkwan University, Suwon, Korea Jinkoo Kim

More information

Simulation of the shaking table test of a seven-story shear wall building

Simulation of the shaking table test of a seven-story shear wall building EARTHQUAKE ENGINEERING AND STRUCTURAL DYNAMICS Earthquake Engng Struct. Dyn. 29; 38:587 67 Published online 3 February 29 in Wiley InterScience (www.interscience.wiley.com). DOI:.2/eqe.897 Simulation of

More information

APPLICATIONS OF STRESS FIELDS TO ASSESS THE BEHAVIOR AND STRENGTH OF COUPLING BEAMS SUBJECTED TO SEISMIC ACTIONS

APPLICATIONS OF STRESS FIELDS TO ASSESS THE BEHAVIOR AND STRENGTH OF COUPLING BEAMS SUBJECTED TO SEISMIC ACTIONS Breña, Fernández Ruiz, Muttoni 3 rd fib International Congress 21 APPLICATIONS OF STRESS FIELDS TO ASSESS THE BEHAVIOR AND STRENGTH OF COUPLING BEAMS SUBJECTED TO SEISMIC ACTIONS Sergio F. Breña, University

More information

Pile to Slab Bridge Connections

Pile to Slab Bridge Connections Pile to Slab Bridge Connections Mohamed I. Ayoub 1, David H. Sanders 2 and Ahmed Ibrahim 3 Abstract Slab bridges are a common bridge type, where the pile extends directly from the ground to the superstructure.

More information

Earthquake Design of Flexible Soil Retaining Structures

Earthquake Design of Flexible Soil Retaining Structures Earthquake Design of Flexible Soil Retaining Structures J.H. Wood John Wood Consulting, Lower Hutt 207 NZSEE Conference ABSTRACT: Many soil retaining wall structures are restrained from outward sliding

More information

This document is downloaded from DR-NTU, Nanyang Technological University Library, Singapore.

This document is downloaded from DR-NTU, Nanyang Technological University Library, Singapore. This document is downloaded from DR-NTU, Nanyang Technological University Library, Singapore. Title Modeling of reinforced concrete sub-frame under cyclic load reversals Author(s) Khoo, Jyh Hao; Li, Bing

More information

REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS

REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS REHABILITATION OF RC BUILDINGS USING STRUCTURAL WALLS Ahmed GHOBARAH 1 And Maged YOUSSEF 2 SUMMARY A developed macroscopic model is applied to the analysis of an example structure to demonstrate the use

More information

EVALUATION OF SEISMIC PERFORMANCE OF SLENDER L- SHAPED AND T-SHAPED RC STRUCTURAL WALLS

EVALUATION OF SEISMIC PERFORMANCE OF SLENDER L- SHAPED AND T-SHAPED RC STRUCTURAL WALLS EVALUATION OF SEISMIC PERFORMANCE OF SLENDER L- SHAPED AND T-SHAPED RC STRUCTURAL WALLS Zhong Wen ZHANG and Bing LI 2 * ABSTRACT L and T-shaped slender reinforced concrete (RC) structural walls are commonly

More information

Truss Analysis for Evaluating the Behavior of Reinforced Concrete Moment-Resisting Frames with Poorly Reinforcing Details

Truss Analysis for Evaluating the Behavior of Reinforced Concrete Moment-Resisting Frames with Poorly Reinforcing Details October 12-17, 28, Beijing, China Truss Analysis for Evaluating the Behavior of Reinforced Concrete Moment-Resisting Frames with Poorly Reinforcing Details Yung-Chin Wang 1, Kai Hsu 2 1 Associate Professor,

More information

LATERAL LOAD BEHAVIOR OF UNBONDED POST-TENSIONED HYBRID COUPLED WALLS. Qiang SHEN Graduate Research Assistant. Yahya C. KURAMA Assistant Professor

LATERAL LOAD BEHAVIOR OF UNBONDED POST-TENSIONED HYBRID COUPLED WALLS. Qiang SHEN Graduate Research Assistant. Yahya C. KURAMA Assistant Professor LATERAL LOAD BEHAVIOR OF UNBONDED POST-TENSIONED HYBRID COUPLED WALLS Qiang SHEN Graduate Research Assistant Yahya C. KURAMA Assistant Professor University of Notre Dame, Civil Engineering and Geological

More information

Lehigh Preserve. Lehigh University. Sonam Srivastava Lehigh University. Theses and Dissertations

Lehigh Preserve. Lehigh University. Sonam Srivastava Lehigh University. Theses and Dissertations Lehigh University Lehigh Preserve Theses and Dissertations 2013 Analytical Lateral Load Response of Unbonded Post-Tensioned Cast-in-Place Concrete Special Structural Walls with Bonded or Debonded Longitudinal

More information

SHAKE-TABLE TESTING OF A 3-STORY, FULL-SCALE, REINFORCED MASONRY WALL SYSTEM

SHAKE-TABLE TESTING OF A 3-STORY, FULL-SCALE, REINFORCED MASONRY WALL SYSTEM 15 th International Brick and Block Masonry Conference Florianópolis Brazil 2012 SHAKE-TABLE TESTING OF A 3-STORY, FULL-SCALE, REINFORCED MASONRY WALL SYSTEM Stavridis, Andreas 1 ; Mavridis, Marios 2 ;

More information

PUSHOVER ANALYSIS (NON-LINEAR STATIC ANALYSIS) OF RC BUILDINGS USING SAP SOFTWARE

PUSHOVER ANALYSIS (NON-LINEAR STATIC ANALYSIS) OF RC BUILDINGS USING SAP SOFTWARE PUSHOVER ANALYSIS (NON-LINEAR STATIC ANALYSIS) OF RC BUILDINGS USING SAP SOFTWARE PROJECT REFERENCE NO. : 37S0221 COLLEGE : DAYANANDA SAGAR COLLEGE OF ENGINEERING, BANGALORE BRANCH : CIVIL ENGINEERING

More information

A Comparative Study on Non-Linear Analysis of Frame with and without Structural Wall System

A Comparative Study on Non-Linear Analysis of Frame with and without Structural Wall System A Comparative Study on Non-Linear Analysis of Frame with and without Structural Wall System Dr.Binu Sukumar #1, A.Hemamathi *2, S.Kokila #3 C.Hanish #4 #1 Professor &Head, Department of Civil Engineering,

More information

Chapter 7. Finite Elements Model and Results

Chapter 7. Finite Elements Model and Results Chapter 7 Finite Elements Model and Results 7.1 Introduction In this chapter, a three dimensional model was presented. The analytical model was developed by using the finite elements method to simulate

More information

SHEAR STRENGTH CAPACITY OF PRESTRESSED CONCRETE BEAM- COLUMN JOINT FOCUSING ON TENDON ANCHORAGE LOCATION

SHEAR STRENGTH CAPACITY OF PRESTRESSED CONCRETE BEAM- COLUMN JOINT FOCUSING ON TENDON ANCHORAGE LOCATION th World Conference on Earthquake Engineering Vancouver, B.C., Canada August -6, Paper No. SHEAR STRENGTH CAPACITY OF PRESTRESSED CONCRETE BEAM- COLUMN JOINT FOCUSING ON TENDON ANCHORAGE LOCATION Wei YUE,

More information

SEISMIC RESPONSE OF A REINFORCED CONCRETE ARCH BRIDGE

SEISMIC RESPONSE OF A REINFORCED CONCRETE ARCH BRIDGE 84 SEISMIC RESPONSE OF A REINFORCED CONCRETE ARCH BRIDGE Kazuhiko KAWASHIMA And Atsushi MIZOGUTI SUMMARY This paper presents an analysis of the seismic response characteristics and seismic performance

More information

Experimental Validation of LLNL Finite Element Codes for Nonlinear Seismic Simulations (Progress, Year 1 of 2)

Experimental Validation of LLNL Finite Element Codes for Nonlinear Seismic Simulations (Progress, Year 1 of 2) UCRL-TR-226690 Experimental Validation of LLNL Finite Element Codes for Nonlinear Seismic Simulations (Progress, Year 1 of 2) S.W. Alves, C.R. Noble Structural and Applied Mechanics Group September 2006

More information

EFFECTS OF INTERACTION BETWEEN JOINT SHEAR AND BOND STRENGTH ON THE ELAST-PLASTIC BEHAVIOR OF R/C BEAM-COLUMN JOINTS

EFFECTS OF INTERACTION BETWEEN JOINT SHEAR AND BOND STRENGTH ON THE ELAST-PLASTIC BEHAVIOR OF R/C BEAM-COLUMN JOINTS EFFECTS OF INTERACTION BETWEEN JOINT SHEAR AND BOND STRENGTH ON THE ELAST-PLASTIC BEHAVIOR OF R/C BEAM-COLUMN JOINTS Hitoshi SHIOHARA 1 ABSTRACT The effects of the interaction between (a) joint shear force

More information

ULTIMATE STRENGTH AND DUCTILITY OF PARTIALLY CONCRETE-FILLED STEEL RIGID-FRAME BRIDGE PIERS

ULTIMATE STRENGTH AND DUCTILITY OF PARTIALLY CONCRETE-FILLED STEEL RIGID-FRAME BRIDGE PIERS ULTIMATE STRENGTH AND DUCTILITY OF PARTIALLY CONCRETE-FILLED STEEL RIGID-FRAME BRIDGE PIERS K.A. Saman Susantha Department of Engineering Mathematics, Faculty of Engineering, University of Peradeniya email:

More information

EFFECTS OF AXIAL FORCE ON DEFORMATION CAPACITY OF STEEL ENCASED REINFORCED CONCRETE BEAM-COLUMNS

EFFECTS OF AXIAL FORCE ON DEFORMATION CAPACITY OF STEEL ENCASED REINFORCED CONCRETE BEAM-COLUMNS 75 EFFECTS OF AXIAL FORCE ON DEFORMATION CAPACITY OF STEEL ENCASED REINFORCED CONCRETE BEAM-COLUMNS Li LI And Chiaki MATSUI 2 SUMMARY In this paper, an analytical work has been conducted to investigate

More information

SEISMIC RESPONSE OF LINEAR, FLANGED, AND CONFINED MASONRY SHEAR WALLS

SEISMIC RESPONSE OF LINEAR, FLANGED, AND CONFINED MASONRY SHEAR WALLS SEISMIC RESPONSE OF LINEAR, FLANGED, AND CONFINED MASONRY SHEAR WALLS M. T. Shedid 1, W. W. El-Dakhakhni 2, and R. G. Drysdale 3 1 Ph.D. Candidate, Dept. of Civil Engineering, McMaster University, Hamilton.

More information

RESEARCH PROJECT AT UNIVERSITY OF NEVADA, RENO

RESEARCH PROJECT AT UNIVERSITY OF NEVADA, RENO RESEARCH PROJECT AT UNIVERSITY OF NEVADA, RENO QUARTERLY REPORT October 1, 2016 to December 31, 2016 Period Year 1 Project Development and Seismic Evaluation of Pier Systems w/ Pocket Connections and Square

More information

Tests of structural walls to determine deformation contributions of interest for performance-based design

Tests of structural walls to determine deformation contributions of interest for performance-based design Tests of structural walls to determine deformation contributions of interest for performance-based design Authors: Beth Brueggen, University of Minnesota, Minneapolis, MN, brue92@umn.edu Jon Waugh, Iowa

More information

Flexural, Axial Load and Elongation Response of Plastic Hinges in Reinforced Concrete Member

Flexural, Axial Load and Elongation Response of Plastic Hinges in Reinforced Concrete Member Flexural, Axial Load and Elongation Response of Plastic Hinges in Reinforced Concrete Member Brian H.H. Peng University of Canterbury, Christchurch, New Zealand Rajesh P. Dhakal, Richard C. Fenwick, Athol

More information

SEISMIC VULNERABILITY ASSESSMENT OF STEEL PIPE SUPPORT STRUCTURES

SEISMIC VULNERABILITY ASSESSMENT OF STEEL PIPE SUPPORT STRUCTURES 10NCEE Tenth U.S. National Conference on Earthquake Engineering Frontiers of Earthquake Engineering July 21-25, 2014 Anchorage, Alaska SEISMIC VULNERABILITY ASSESSMENT OF STEEL PIPE SUPPORT STRUCTURES

More information

NONLINEAR TIME HISTORY ANALYSIS OF RC FRAME RETROFITTED WITH BUCKLING RESTRAINED BRACES 1

NONLINEAR TIME HISTORY ANALYSIS OF RC FRAME RETROFITTED WITH BUCKLING RESTRAINED BRACES 1 NONLINEAR TIME HISTORY ANALYSIS OF RC FRAME RETROFITTED WITH BUCKLING RESTRAINED BRACES 1 Ramazan Ozcelik Akdeniz University Faculty of Engineering Civil Engineering Department Dumlupinar Bulvari 07058

More information

The Art of Designing Ductile Concrete in the Past 50 Years: The Impact of the PCA Book and Mete A. Sozen, Part 2

The Art of Designing Ductile Concrete in the Past 50 Years: The Impact of the PCA Book and Mete A. Sozen, Part 2 The Art of Designing Ductile Concrete in the ast 5 Years: The Impact of the CA Book and Mete A. Sozen, art 2 Beth Brueggen, Associate III, Wiss, Janney, Elstner Associates, Inc., Irving, TXrior to joining

More information

Effect of beam dimensions on structural performance of wide beam-column joints

Effect of beam dimensions on structural performance of wide beam-column joints Effect of beam dimensions on structural performance of wide beam-column joints J.S. Kuang 1) and *Wing Shan Kam 2) 1), 2) Department of Civil and Environmental Engineering, Hong Kong University of Science

More information

ANALYTICAL MODEL OF DUCTILE REINFORCED CONCRETE FRAMES ALLOWING FOR ELONGATION OF PLASTIC HINGES

ANALYTICAL MODEL OF DUCTILE REINFORCED CONCRETE FRAMES ALLOWING FOR ELONGATION OF PLASTIC HINGES Eleventh East Asia-Pacific Conference on Structural Engineering & Construction (EASEC-11) Building a Sustainable Environment November 19-21, 28, Taipei, TAIWAN ANALYTICAL MODEL OF DUCTILE REINFORCED CONCRETE

More information

Assessment of Collapse Capacity of RC Buildings Based on Fiber-element Modelling

Assessment of Collapse Capacity of RC Buildings Based on Fiber-element Modelling Assessment of Collapse Capacity of RC Buildings Based on Fiber-element Modelling M.E. Koopaee, R.P. Dhakal, B.A. Bradley, G.A. MacRae Department of Civil and Natural Resources Engineering, University of

More information

Seismic Design Principles for RC Structures

Seismic Design Principles for RC Structures CE 490 Int. to Earthquake Engineering Seismic Design Principles for RC Structures H. Sucuoğlu Introduction Seismic design of structural systems is essentially based on an inherent ductile response under

More information

Seismic Performance and Design of Linked Column Frame System (LCF)

Seismic Performance and Design of Linked Column Frame System (LCF) Seismic Performance and Design of Linked Column Frame System (LCF) M. Malakoutian & J.W. Berman Department of Civil and Environmental Engineering, University of Washington, Seattle, WA, USA P. Dusicka

More information

Modelling for Seismic Analysis of RC Frame Buildings with Infill Wall and Special Shear Wall

Modelling for Seismic Analysis of RC Frame Buildings with Infill Wall and Special Shear Wall Modelling for Seismic Analysis of RC Frame Buildings with Infill Wall and Special Shear Wall Kaustubh Dasgupta Department of Civil Engineering Indian Institute of Technology Guwahati Seismic behaviour

More information

Lateral Force-Resisting Capacities of Reduced Web-Section Beams: FEM Simulations

Lateral Force-Resisting Capacities of Reduced Web-Section Beams: FEM Simulations Lateral Force-Resisting Capacities of Reduced Web-Section Beams: FEM Simulations *Seungpil Kim 1), Myoungsu Shin 2), and Mark Aschheim 3) 1), 2) School of Urban and Environmental Engineering, UNIST, Ulsan

More information

Components and Elements for PERFORM-3D and PERFORM-COLLAPSE

Components and Elements for PERFORM-3D and PERFORM-COLLAPSE Components and Elements for PERFORM-3D and PERFORM-COLLAPSE ISO PER053111M3 Version 5 Berkeley, California, USA June 2011 Copyright Copyright Computers and Structures, Inc., 2006-2011 All rights reserved.

More information

Masonry infills with window openings and influence on reinforced concrete frame constructions

Masonry infills with window openings and influence on reinforced concrete frame constructions Earthquake Resistant Engineering Structures VII 445 Masonry infills with window openings and influence on reinforced concrete frame constructions D. J. Kakaletsis Technological Educational Institution

More information

CAUSES OF ELONGATION IN REINFORCED CONCRETE BEAMS SUBJECTED TO CYCLIC LOADING

CAUSES OF ELONGATION IN REINFORCED CONCRETE BEAMS SUBJECTED TO CYCLIC LOADING CAUSES OF ELONGATION IN REINFORCED CONCRETE BEAMS SUBJECTED TO CYCLIC LOADING By Brian PENG 1, Rajesh DHAKAL 2, Richard C. FENWICK 3 ABSTRACT: Elongation in the plastic hinge regions of reinforced concrete

More information

CYCLIC BEHAVIOR OF AN INNOVATIVE STEEL SHEAR WALL SYSTEM

CYCLIC BEHAVIOR OF AN INNOVATIVE STEEL SHEAR WALL SYSTEM 13 th World Conference on Earthquake Engineering Vancouver, B.C., Canada August 1-6, 2004 Paper No. 2576 CYCLIC BEHAVIOR OF AN INNOVATIVE STEEL SHEAR WALL SYSTEM Qiuhong ZHAO 1 and Abolhassan ASTANEH-ASL

More information

Closure, Wrap Up & 2017 PEER Blind Prediction Contest

Closure, Wrap Up & 2017 PEER Blind Prediction Contest Closure, Wrap Up & 2017 PEER Blind Prediction Contest Khalid M. Mosalam PEER Director, Taisei Prof. of Civil Eng. PEER at 21: The Practice of Performance- Based Engineering for Natural Hazards PEER Annual

More information

COMPARISON OF LOW-RISE STEEL CHEVRON AND SUSPENDED ZIPPER BRACED FRAMES

COMPARISON OF LOW-RISE STEEL CHEVRON AND SUSPENDED ZIPPER BRACED FRAMES Eighth International Conference on ADVANCES IN STEEL STRUCTURES Lisbon, Portugal, July -4, 15 COMPARISON OF LOW-RISE STEEL CHEVRON AND SUSPENDED ZIPPER BRACED FRAMES Yigit Ozcelik*, Afsin Saritas** and

More information

ANALYTICAL STUDIES OF A FULL-SCALE STEEL BUILDING SHAKEN TO COLLAPSE

ANALYTICAL STUDIES OF A FULL-SCALE STEEL BUILDING SHAKEN TO COLLAPSE SDSS Rio STABILITY AND DUCTILITY OF STEEL STRUCTURES E. Batista, P. Vellasco, L. de Lima (Eds.) Rio de Janeiro, Brazil, September 8 -, ANALYTICAL STUDIES OF A FULL-SCALE STEEL BUILDING SHAKEN TO COLLAPSE

More information

Finite Element Model Calibration of An Instrumented Thirteen-story Steel Moment Frame Building in South San Fernando Valley, California

Finite Element Model Calibration of An Instrumented Thirteen-story Steel Moment Frame Building in South San Fernando Valley, California Finite Element Model Calibration of An Instrumented Thirteen-story Steel Moment Frame Building in South San Fernando Valley, California By Erol Kalkan Disclamer The finite element model incuding its executable

More information

Modelling of post-tensioned precast reinforced concrete frame structures with rocking beam-column connections

Modelling of post-tensioned precast reinforced concrete frame structures with rocking beam-column connections Modelling of post-tensioned precast reinforced concrete frame structures with rocking beam-column connections H.A. Spieth, A.J. Carr, A.G. Murahidy, D. Arnolds, M. Davies, J.B. Mander University of Canterbury,

More information

A NOVEL ELASTOMERIC BASE ISOLATION SYSTEM FOR SEISMIC MITIGATION OF LOW-RISE BUILDINGS

A NOVEL ELASTOMERIC BASE ISOLATION SYSTEM FOR SEISMIC MITIGATION OF LOW-RISE BUILDINGS A NOVEL ELASTOMERIC BASE ISOLATION SYSTEM FOR SEISMIC MITIGATION OF LOW-RISE BUILDINGS H. Toopchi-Nezhad 1, M. J. Tait 2, and R. G. Drysdale 3 1 Ph.D. Candidate, Dept. of Civil Engineering, McMaster University,

More information

Numerical and Experimental Behaviour of Moment Resisting Connections using Blind Bolts within CFSHS columns

Numerical and Experimental Behaviour of Moment Resisting Connections using Blind Bolts within CFSHS columns Proceedings of the Tenth Pacific Conference on Earthquake Engineering Building an Earthquake-Resilient Pacific 6-8 November 2015, Sydney, Australia Numerical and Experimental Behaviour of Moment Resisting

More information

SEISMIC PERFORMANCE OF CONCRETE TILT-UP BUILDINGS: CURRENT WALL-TO-SLAB CONNECTIONS

SEISMIC PERFORMANCE OF CONCRETE TILT-UP BUILDINGS: CURRENT WALL-TO-SLAB CONNECTIONS SEISMIC PERFORMANCE OF CONCRETE TILT-UP BUILDINGS: CURRENT WALL-TO-SLAB CONNECTIONS Frank Devine, 1 Omri Olund, 2 Ken Elwood 3 and Perry Adebar 4 1 Graduate Student, Dept. of Civil Engineering, University

More information

Beam-column joint tests with grade 500E reinforcing

Beam-column joint tests with grade 500E reinforcing Beam-column joint tests with grade 500E reinforcing L.M. Megget & N.J. Brooke Department of Civil & Environmental Engineering, University of Auckland, New Zealand. R.C. Fenwick Visitor, Department of Civil

More information

POST-TENSIONED CONNECTION SYSTEMS FOR SEISMIC-RESISTANT STEEL FRAMES

POST-TENSIONED CONNECTION SYSTEMS FOR SEISMIC-RESISTANT STEEL FRAMES POST-TENSIONED CONNECTION SYSTEMS FOR SEISMIC-RESISTANT STEEL FRAMES A.. Introduction The failure of welded connections in steel moment frames during recent earthquakes has led to a renewed interest in

More information

STRUCTURAL PERFORMANCES OF PRESTRESSED CONCRETE INTERIOR BEAM-COLUMN JOINTS

STRUCTURAL PERFORMANCES OF PRESTRESSED CONCRETE INTERIOR BEAM-COLUMN JOINTS STRUCTURAL PERFORMANCES OF PRESTRESSED CONCRETE INTERIOR BEAM-COLUMN JOINTS Takashi KASHIWAZAKI 1 And Hiroshi NOGUCHI 2 SUMMARY Four one-third scaled PC interior beam-column joints were tested by the authors.

More information

Exploring the Implication of Multi-plastic Hinge Design Concept of Structural Walls in Dual Systems

Exploring the Implication of Multi-plastic Hinge Design Concept of Structural Walls in Dual Systems Exploring the Implication of Multi-plastic Hinge Design Concept of Structural Walls in Dual Systems N. Samadzadegan School of Civil Engineering, University of Tehran, Iran M. Khanmohammadi School of Civil

More information

Nonlinear Finite Element Modeling & Simulation

Nonlinear Finite Element Modeling & Simulation Full-Scale Structural and Nonstructural Building System Performance during Earthquakes & Post-Earthquake Fire A Joint Venture between Academe, Industry and Government Nonlinear Finite Element Modeling

More information

Progressive Collapse Assessment of RC Structures under Instantaneous and Gradual Removal of Columns

Progressive Collapse Assessment of RC Structures under Instantaneous and Gradual Removal of Columns Progressive Collapse Assessment of RC Structures under Instantaneous and Gradual Removal of Columns A.R. Rahai, M. Banazadeh, M.R. Seify Asghshahr & H. Kazem Department of Civil Engineering, Amirkabir

More information

SHEAR BEHAVIOR OF MULTI-STORY RC STRUCTURAL WALLS WITH ECCENTRIC OPENINGS

SHEAR BEHAVIOR OF MULTI-STORY RC STRUCTURAL WALLS WITH ECCENTRIC OPENINGS SHEAR BEHAVIOR OF MULTI-STORY RC STRUCTURAL WALLS WITH ECCENTRIC OPENINGS Makoto Warashina 1, Susumu Kono 2, Masanobu Sakashita 3, Hitoshi Tanaka 4 1 Ex-Graduate Student, Dept. of Architecture and Architectural

More information

NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS

NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS Polupalli Victor Paul 1, K Sampath Kumar 2 1 PG Student, Dept of Civil Engineering, Nova College of Engineering & Technology,

More information

Displacement and curvature estimation for the design of reinforced concrete slender walls

Displacement and curvature estimation for the design of reinforced concrete slender walls THE STRUCTURAL DESIGN OF TALL AND SPECIAL BUILDINGS Struct. Design Tall Spec. Build. 2016; 25: 823 841 Published online 18 April 2016 in Wiley Online Library (wileyonlinelibrary.com/journal/tal)..1285

More information