FEMA P-593 STEP-BY STEP PRESCRIPTIVE RETROFIT FOR CRIPPLE WALL BRACING & ANCHORAGE TO FOUNDATION

Size: px
Start display at page:

Download "FEMA P-593 STEP-BY STEP PRESCRIPTIVE RETROFIT FOR CRIPPLE WALL BRACING & ANCHORAGE TO FOUNDATION"

Transcription

1 INTRODUCTION Objective of provisions: The provisions of IEBC Appendix Chapter A3 are intended to reduce hazard of earthquake-induced damage (IEBC A301.1). These provisions are not intended to eliminate earthquake damage. This is partial seismic upgrade of vulnerable configuration. Alternative prescriptive provisions: Some local jurisdictions and regional groups have developed bolting and bracing provisions similar to the IEBC provisions, with modifications deemed appropriate for local use. The following information will be applicable in general concept, but may vary from local provisions in some details. Consult with building department regarding local revisions and resources. When this prescriptive design method should be used: 1) When undertaking voluntary seismic retrofit 2) When otherwise deemed appropriate by the building official. STEP 1: VERIFY IEBC SCOPE LIMITATIONS ARE MET (IEBC A301.2) (circle YES or NO) Building Configuration Scope YES NO One to four-family detached dwelling with crawlspace YES NO No lateral resistance is from poles or columns embedded in the ground YES NO Cripple walls do not exceed 4 ft in height (level and low-slope sites) YES NO 3 stories or less with no cripple walls, OR 3 stories or less with cripple walls less than 14 inches, OR 2 stories or less with cripple walls up to 4 ft high If all answers YES then proceed. If any of the above are NO, consult with building official or design professional regarding applicability of these provisions. Structural Weakness to be Retrofit YES NO 1. Sill plates or floor framing supported on ground without foundation system YES NO 2. Perimeter foundation system is isolated footings supporting posts and beams YES NO 3. Perimeter foundation system is not continuous YES NO 4. Perimeter foundation system is unreinforced masonry or stone YES NO 5. Foundation sill plates not connected or not adequately connected to foundation YES NO 6. Cripple walls not braced or not adequately braced If YES to one or more items above, proceed with those items. STEP 2 (RECOMMENDED): DRAW PLAN OF HOUSE AND CRAWL SPACE (Check each item when done) Identify location and extent of foundation Identify location of existing anchor bolts, if applicable Identify extent and location of cripple walls if applicable Indicate locations of cripple wall openings and interruptions including: ventilation and flood openings access openings fireplaces to the extent that they affect potential areas of access or work: o utility meters o plumbing o water heaters o HVAC equipment Indicate direction of floor framing Page 1 of 10

2 STEP 3: CONDUCT CONDITION SURVEY Identify whether any of the following conditions exist (circle YES or NO) REQUIRED CONDITION SURVEY YES NO Decay in members to be part of strengthening requires replacement of decayed framing (A ). Recommend replacement with decay-resistant material. YES NO Insect infestation in members to be part of strengthening requires strengthening or replacement of damaged framing (A ). YES NO Partial perimeter foundation requires evaluation by engineer or architect to determine if adequate for anticipated cripple wall loads (A ). YES NO Unreinforced masonry foundation requires evaluation by engineer or architect to determine 1) if adequate for anticipated cripple wall loads and 2) if anchorage to foundation will be adequate for anticipated cripple wall loads (A ). RECOMMENDED ADDITIONAL SURVEY ITEMS YES NO Signs of decay or water intrusion recommend that owner take steps to identify and repair water sources (leaking pipes, grading and drainage, etc) YES NO Anchor bolts rusted to the extent that their area is significantly reduced (i.e. loss of 25% of bolt area or more) recommend addition of replacement bolts YES NO Deteriorated existing foundation such that concrete or masonry mortar can be easily scrapped out with screw driver adhesive anchors may not hold well, consider 1) replace foundation, 2) add new foundation segments alongside existing or 3) cut out 1 by 1 keys in foundation and cast new concrete around new anchor bolts Page 2 of 10

3 STEP 4: DETERMINE NEW FOUNDATION REQUIREMENTS (IF APPLICABLE) (A304.2) New foundations are needed when: Structural weaknesses 1 and 2 are present (Step 1) Partial continuous foundations are found to not be adequate (Step 1, Weakness 3) Unreinforced masonry foundations are found to not be adequate (Step 1, Weakness 4) When otherwise determined appropriate New perimeter foundations are to be continuous and conform to Figure A3-1 or A3-2 and their table, or be designed by an engineer or architect. A geotechnical (soil) investigation may be required is the site is located in a special study zone. Check with building department. Figure A3-1 Figure A3-2 RECOMMEND: Indicating extent and detail for new foundation on retrofit plan (See Step 2). STEP 5: INDENTIFY FOUNDATION SILL PLATE ANCHOR SPACING (A304.3) All perimeter foundation sill plates are to be anchored to the foundation. Foundation sill plate anchor bolt spacing (or spacing of alternate connectors if applicable) needs to meet the requirements of Table A3-A: Page 3 of 10

4 Number of anchor bolts (or alternate connectors if applicable) per section of sill needs to meet requirements of Table A3-B: For sections of sill less than 30 inches one anchor bolt or alternate connection is required. Anchor bolts are to start between 9 and 12 inches from the end of the sill, and in the center of the stud bay closest to the required spacing. When the intended location is obstructed, place as close to the intended location as possible. RECOMMEND: Locating new anchor locations on retrofit plan (See Step 2). STEP 6: SELECT FOUNDATION SILL PLATE ANCHORAGE DETAILS (A304.3) Where cripple walls exist and height permits rotary hammer access, anchor bolts shall be per Figure A3-3. Where no cripple walls are present or height is inadequate, use of connectors per Figures A3-4A to A3-4C is permitted. Page 4 of 10

5 RECOMMEND: Identifying applicable detail at each perimeter wall on retrofit plan (See Step 2). STEP 7: VERIFY/ RETROFIT RIM JOIST, BLOCKING & CONNECTION (A & A ) Where floor joists are perpendicular to the foundation need to have: 1 & 2-story buildings: A continuous rim joist or full depth blocking in alternate joist bays 3-story buildings: A continuous rim joist of full depth blocking in every joist bay Where required rim joist or blocking does not exist, provide wood structural panel blocking in accordance with Figure A3-8. In 2 & 3 story buildings, the connection of the rim joist or blocking to the foundation sill plate or cripple wall top plate must be: Verified to be a minimum of 8d toenails at 6 in. for rim joist or 3-8d per block, or Retrofit with framing clip in accordance with Figure A3-8. Page 5 of 10

6 STEP 7 (CONTD): VERIFY/ RETROFIT RIM JOIST, BLOCKING & CONNECTION (A & A ) Where floor joists are parallel to the foundation need to have: End joist located over the foundation and in contact with the foundation sill plate or cripple wall top plates End joist continuous except for ventilation/ access openings Where required end joist is not adequately installed, provide wood structural panel blocking in accordance with Figure A3-9. In 2 & 3 story buildings, the connection of the end joist to the foundation sill plate or cripple wall top plate must be: Verified to be a minimum of 8d toenails at 6 in., or Retrofit with framing clip in accordance with Figure A3-9. Page 6 of 10

7 STEP 8: IDENTIFY DISTRIBUTION AND AMOUNT OF CRIPPLE WALL BRACING Amount of bracing needs to: Meet the requirements of Table A3-A, and Meet the requirements of Figure A3-10, and Have a bracing panel (plywood or OSB) width not less than two times the bracing panel height, and Where obstructions occur, the bracing shall be located as close to the intended location as possible; the total amount of bracing shall not be reduced. Where these requirements cannot be met, design by an engineer or architect is required. Page 7 of 10

8 STEP 9: SELECT DETAILS OF CRIPPLE WALL BRACING Cripple wall bracing detailing shall be: Conforming to Figures A3-5 (exterior sheathing) or A3-6 (interior sheathing) and A3-7 Plywood/ OSB sheathing, minimum 15/32 in thickness All vertical plywood/ OSB edges shall fall on existing studs and be installed with 1/8 in gap between sheathing panels or be installed on doubled studs in accordance with Figure S3-7 All other plywood/osb edges shall be blocked with 2x4 minimum blocking installed with 4-in face flat against sheathing Sheathing nailing shall be with 8d common nails, and penetrate 1-1/2 inches minimum into framing Sheathing nailing shall be at 4 in. on center at plywood/ OSB panel edges, 12 inches at other framing Sheathing nailing shall be driven flush with the sheathing surface, but not break the sheathing face. Where nail breaks the sheathing face, add another nail half way between existing nails and hand-drive flush. Page 8 of 10

9 STEP 10: VERIFY VENTILATION (A , A ), ACCESS AND FLOOD OPENINGS Cripple wall bracing, blocking, etc need to allow for ventilation, etc. as follows: Where sheathing is installed on inside face, stud bay ventilation is required per A See also Figure A3-7. Under floor ventilation shall be in accordance with A See also Figure A3-7. Flood vents, if required, are recommended to the in accordance with A Required access openings shall be maintained. STEP 11: QUALITY CONTROL (A304.5) Inspections: IEBC Section A304.5 lists minimum required inspections. OTHER NOTES Steps 1-11 address the primary steps identified in IEBC Appendix Chapter 3. Fee the chapter for additional details. References - This section is drawn primarily from IEBC provisions, FEMA G225 Seismic Retrofit Training, and ATC 48 Built to Resist Earthquakes. The ICC/SEAOC commentary to IEBC provides detailed explanations of Appendix Chapter A3 requirements, along with many applicable recommendations and cautions. Page 9 of 10

10 Example Plan with Typical Retrofit Design Information Page 10 of 10

INSTRUCTORS GUIDE. FEMA P-593 CD, Seismic Rehabilitation Training for One- and Two-Family Wood-Frame Dwellings

INSTRUCTORS GUIDE. FEMA P-593 CD, Seismic Rehabilitation Training for One- and Two-Family Wood-Frame Dwellings INSTRUCTORS GUIDE FEMA P-593 CD, Seismic Rehabilitation Training for One- and Two-Family Wood-Frame Dwellings ****************************************************************************** This Instructors

More information

FEMA P 50 & FEMA P 50 1

FEMA P 50 & FEMA P 50 1 & Seismic Retrofit Guidelines for Detached, Single Family, Wood Frame Dwellings FEMA P 50 & FEMA P 50 1 & Seismic Retrofit Guidelines for Detached, Single Family, Wood Frame Dwellings FEMA P 50 1 & Seismic

More information

VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.)

VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.) DIVISION 94 VOLUNTARY - EARTHQUAKE HAZARD REDUCTION IN EXISTING HILLSIDE BUILDINGS (Division 94 Added by Ord. No. 171,258, Eff. 8/30/96.) SEC. 91.9401. PURPOSE. (Amended by Ord. No. 172,592, Eff. 6/28/99,

More information

Simplified Seismic Assessment & Seismic Retrofit Guidelines for Detached, Single-Family, Wood-Frame Dwellings FEMA P-50 & FEMA P-50-1

Simplified Seismic Assessment & Seismic Retrofit Guidelines for Detached, Single-Family, Wood-Frame Dwellings FEMA P-50 & FEMA P-50-1 & Seismic Retrofit Guidelines for Detached, Single-Family, Wood-Frame Dwellings FEMA P-50 & FEMA P-50-1 & Seismic Retrofit Guidelines for Detached, Single-Family, Wood-Frame Dwellings FEMA P-50 & Seismic

More information

Home Not Anchored to Foundation

Home Not Anchored to Foundation IDENTIFY WEAKNESSES Home Not Anchored to Foundation Houses that are not bolted to the foundation can move off their foundations during earthquakes. Go down into the crawl space the area between the first

More information

Module number 3 provides an on-line, self-paced training seminar on chapter 4, foundations and chapter 5, floors from the residential code of ohio.

Module number 3 provides an on-line, self-paced training seminar on chapter 4, foundations and chapter 5, floors from the residential code of ohio. Module number 3 provides an on-line, self-paced training seminar on chapter 4, foundations and chapter 5, floors from the residential code of ohio. 1 This chapter sets forth the prescriptive requirements

More information

Stone and Masonry Veneer

Stone and Masonry Veneer Stone and Masonry Veneer R703.7 Stone and masonry veneer, general. Stone and masonry veneer shall be installed in accordance with this chapter, Table R703.4 and Figure R703.7. These veneers installed over

More information

Fallen buildings have collapsed, caught fire or needed extensive repairs to restore occupancy.

Fallen buildings have collapsed, caught fire or needed extensive repairs to restore occupancy. Sec. 763. The last sentence of the second unnumbered paragraph of Subsection 91.9201.1 of the Los Angeles Municipal Code is amended to read as follows: Fallen buildings have collapsed, caught fire or needed

More information

RESIDENTIAL SEISMIC RETROFITS

RESIDENTIAL SEISMIC RETROFITS RESIDENTIAL Barry H. Welliver Structural Engineer BHW Engineers SEAU 6th Annual Education Conference Davis Conference Center - Layton, Utah February 21st, 2018 TOPICS Introduction to Seismic Retrofits

More information

Building Division Informational Handout

Building Division Informational Handout CITY OF SAN JOSÉ, CALIFORNIA Building Division Informational Handout Conventional Light Frame Construction Design Provisions 2007 CBC Handout No. 2-21 Published: 1/1/08 Page 1 of 3 This document summarizes

More information

INSPECTION GUIDELINES: JOIST AND UNDERFLOOR COMBO

INSPECTION GUIDELINES: JOIST AND UNDERFLOOR COMBO Joist and Underfloor Combo Page 1 of 7 Revision Date: 10/02/2017 DEVELOPMENT SERVICES BUILDING INSPECTION INSPECTION GUIDELINES: JOIST AND UNDERFLOOR COMBO INSPECTION CODE: 212, 213 SCOPE: RESIDENTIAL

More information

CALBO Annual Business Meeting The Building Official and the CEA

CALBO Annual Business Meeting The Building Official and the CEA CALBO Annual Business Meeting The Building Official and the CEA Janiele Maffei, S.E. Chief Mitigation Officer CEA Established Following Northridge Earthquake 2 1 Northridge Earthquake $20 Billion residential

More information

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC)

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC) Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC) Plan Check Submittal Date: Plan Check #: Permit App.# Job Address: Applicant: Phone: ( ) Plan Check Engineer:

More information

Attachment A. USG Minimum Design and Construction Requirements for Wood Framed Structures

Attachment A. USG Minimum Design and Construction Requirements for Wood Framed Structures Attachment A USG Minimum Design and Construction Requirements for Wood Framed Structures 1. General Design Criteria 1.1. Per Adopted Georgia State Minimum Standard Building Code 1.2. Minimum Live Loads

More information

Administrative Changes

Administrative Changes Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings

More information

7 NON-STRUCTURAL ELEMENTS

7 NON-STRUCTURAL ELEMENTS Non-Structural Elements 85 7 NON-STRUCTURAL ELEMENTS Edited by Timothy P. McCormick, P.E. 86 Non-Structural Elements Non-Structural Elements 87 NON-STRUCTURAL ELEMENTS CHIMNEYS The first nonstructural

More information

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC)

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC) Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC) Plan Check Submittal Date: Plan Check #: Permit App.# Job Address: Applicant: Phone: ( ) P.C. Engineer: Phone:

More information

Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS

Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS Chapter 2 EARTHQUAKE-RESISTANCE REQUIREMENTS This chapter explains the International Residential Code s (IRC s) general earthquake-resistance requirements as well as specific IRC requirements concerning

More information

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings Building Safety Department 400-2 nd Street South St. Cloud, MN 56301 (320) 255-7239 A building permit is required for any accessory

More information

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued)

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued) 2000 IRC 1997 NEHRP Section Provision Section Provision Comments CHAPTER 3 BUILDING PLANNING R301 DESIGN CRITERIA R301.2.2 Seismic Provisions R301.2.2.1 Determination of Seismic Design Category R301.2.2.1.1

More information

ORDINANCE. APPROVED EMERGENCY: (Yes) (No) VETOED: Date

ORDINANCE. APPROVED EMERGENCY: (Yes) (No) VETOED: Date ORDINANCE AN ORDINANCE OF THE COMMISSION OF KNOX COUNTY, TENNESSEE RESCINDING ARTICLE III. CABO ONE- AND TWO-FAMILY DWELLING CODE, SEC. 10-56, SEC. 10-57 AND SEC. 10-58 AND ADOPTING THE 2006 INTERNATIONAL

More information

Mandatory Wood Frame Soft-story Retrofit Program STRUCTURAL DESIGN GUIDELINES

Mandatory Wood Frame Soft-story Retrofit Program STRUCTURAL DESIGN GUIDELINES INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC Division 93 Effective: 11/22/15 DOCUMENT NO.: P/BC 2014-137 Revised: 06/07/16 Previously Issued As: N/A Mandatory Wood Frame Soft-story

More information

Garage/Accessory Structures

Garage/Accessory Structures Garage/Accessory Structures City of New Prague Building Inspections Department 118 Central Ave N New Prague, MN 56071 (952) 758-4401 Fax (952) 758-1149 Requirements for submitted Building Plans Signed

More information

Residential Patio Cover Specifications

Residential Patio Cover Specifications Residential Patio Cover Specifications This information bulletin describes the minimum requirements for obtaining patio cover permits for residential buildings using the City of Vista standard plan or

More information

DECK PERMIT APPLICATION

DECK PERMIT APPLICATION DECK PERMIT APPLICATION APPLICANT S INFORMATION Name: Company Name: Current address: City: State: ZIP Code: Phone: Email: PROPERTY OWNER S INFORMATION Name: Property Address: Phone: E-mail: City: State:

More information

Building Guide. Colorado Chapter of the International Code Council

Building Guide. Colorado Chapter of the International Code Council 12/29/16 Building uide Colorado Chapter of the International Code Council How to Use this uide Check with your jurisdiction regarding type of submittal (paper or electronic) and for additional requirements.draw

More information

Earthquake Resistant Residential Design and Construction, Part 2

Earthquake Resistant Residential Design and Construction, Part 2 Earthquake Resistant Residential Design and Construction, Part 2 Course No: S05-007 Credit: 5 PDH John L. Galinski, PE Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY

More information

2003 International Residential Building Code

2003 International Residential Building Code 2003 International Residential Building Code Section R305 Ceiling Height Habitable rooms, hallways, corridors, bathrooms, toilet rooms, laundry rooms and basements shall have a ceiling height of not less

More information

FIGURE R502.2 FLOOR CONSTRUCTION

FIGURE R502.2 FLOOR CONSTRUCTION CHAPTER 5 FLOORS 11 I SECTION R501 GENERAL R501.1 Application. The provisions of this chapter shall control the design and construction of the floors for all buildings including the floors of attic spaces

More information

R Code and Commentary for 2012 NC Residential Code final 03/06/13

R Code and Commentary for 2012 NC Residential Code final 03/06/13 R602.10 Code and Commentary for 2012 NC Residential Code final 03/06/13 Commentary italicized and printed in red 1. Section R602.10 -- provides charging language for two simplified bracing approaches (isolated

More information

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 psf Live Loading

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 psf Live Loading CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 psf Live Loading April 1, 2017 This Tip Sheet reflects code requirements of the 2015 International Residential Code (IRC) with Washington State Amendments which

More information

SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION

SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION Section R614 Add new section to read as shown: (RB34-06/07) SECTION R614 STRUCTURAL INSULATED PANEL WALL CONSTRUCTION R614.1 General. Structural insulated panel (SIP) walls shall be designed in accordance

More information

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 lb Live Loading

Typical Deck. CONSTRUCTION TIP SHEET 5 Basic Decks w/ 60 lb Live Loading CONSTRUCTION TIP SHEET 5 w/ 60 lb Live Loading April 1, 2017 This Tip Sheet reflects code requirements of the 2015 International Residential Code (IRC) with Washington State Amendments which update the

More information

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs November 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements....................................

More information

EMERGENCY MANAGEMENT PREPAREDNESS AND ASSISTANCE TRUST FUND ARC 4496 Evaluation Questionnaire

EMERGENCY MANAGEMENT PREPAREDNESS AND ASSISTANCE TRUST FUND ARC 4496 Evaluation Questionnaire EMERGENCY MANAGEMENT PREPAREDNESS AND ASSISTANCE TRUST FUND ARC 4496 Evaluation Questionnaire Additional Instructions and Clarifications 1. Please review ARC 4496 before beginning the project identification

More information

Mandatory Wood Frame Soft-story Retrofit Program PERMITTING AND INSPECTION PROCESS GUIDELINES

Mandatory Wood Frame Soft-story Retrofit Program PERMITTING AND INSPECTION PROCESS GUIDELINES INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC Division 93 Effective: 11/22/2015 DOCUMENT NO.: P/BC 2017-136 Revised: 1/11/2017 Previously Issued As: N/A Mandatory Wood Frame Soft-story

More information

Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage

Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage Carroll County Bureau of Permits and Inspection Residential Code Compliance Guidelines Detached Garage The following list of code requirements is intended to assist you in complying with the Code of Public

More information

First Published in The Wichita Eagle on September 23, CLEAN 8/30/2011 ORDINANCE NO

First Published in The Wichita Eagle on September 23, CLEAN 8/30/2011 ORDINANCE NO First Published in The Wichita Eagle on September 23, 2011 230100 CLEAN 8/30/2011 ORDINANCE NO. 49-085 AN ORDINANCE AMENDING AND REPEALING THE ORIGINAL OF SECTIONS 18.51.115, 18.51.390, 18.51.400, 18.51.402

More information

R CODE CHANGE PROPOSAL FORM (See instructions on page 2)

R CODE CHANGE PROPOSAL FORM (See instructions on page 2) CODE CHANGE PROPOSAL FORM (See instructions on page 2) Code: IRC 12/13 Sections 301.2.2.2.1 Proponent: Charles S. Bajnai, Chesterfield County, VA, ICC Building Code Action Committee 1. Delete as shown

More information

Building Guide. olorado Chapter of the International Conference of Building Officials. Lancaster County Building Department

Building Guide. olorado Chapter of the International Conference of Building Officials. Lancaster County Building Department olorado Chapter of the International Conference of Building Officials Lancaster County Building Department Single Family Residential One Story Detached Garage How to Use this Guide Provide two sets of

More information

THE FLORIDA BUILDING CODE

THE FLORIDA BUILDING CODE THE FLORIDA BUILDING CODE 1. According to the Florida Building Code, spiral stairway treads must all be identical and rise must be sufficient enough to provide a headroom of minimum. A. 6'- 4" B. 6'- 6"

More information

U.S. EDITION RESIDENTIAL CONSTRUCTION DETAILS SAMPLE. A visual guide to construction detailing. Emma Walshaw

U.S. EDITION RESIDENTIAL CONSTRUCTION DETAILS SAMPLE. A visual guide to construction detailing. Emma Walshaw RESIDENTIAL CONSTRUCTION DETAILS U.S. EDITION A visual guide to construction detailing Emma Walshaw Contents INTRODUCTION 4 PRINCIPLES OF CONSTRUCTION DETAILING 6 FOUNDATIONS 9 PRINCIPLES OF FOUNDATION

More information

* RESIDENTIAL PLAN REVIEW *

* RESIDENTIAL PLAN REVIEW * CITY OF DES MOINES, IOWA COMMUNITY DEVELOPMENT DEPARTMENT PERMIT AND DEVELOPMENT CENTER 602 Robert D. Ray Drive DES MOINES, IOWA 50309 Phone: 515.283.4200 Facsimile: 515.283.4270 Based on the scope of

More information

APPENDIX A1 WIND AND SEISMIC BRACING GUIDELINE FOR ONE AND TWO FAMILY DWELLINGS AND TOWNHOUSES

APPENDIX A1 WIND AND SEISMIC BRACING GUIDELINE FOR ONE AND TWO FAMILY DWELLINGS AND TOWNHOUSES ST. LOUIS COUNTY DEPARTMENT OF PUBLIC WORKS DIVISION OF CODE ENFORCEMENT APPENDIX A1 WIND AND SEISMIC BRACING GUIDELINE FOR ONE AND TWO FAMILY DWELLINGS AND TOWNHOUSES Lateral Loads All buildings are subject

More information

Colorado Chapter of the International Conference of Building Officials. Building Guide. The Colorado Chapter of the International

Colorado Chapter of the International Conference of Building Officials. Building Guide. The Colorado Chapter of the International Building Guide Colorado Chapter of the International Conference of Building Officials Colorado Building Chapter of the International Guide Code Council Single Family Residential One Story Detached Garage

More information

Building Envelope

Building Envelope 9.36.2. Building Envelope Module 2 BCBC 9.36. 2014 1 Richard Kadulski Architect 9.36.2. Building Envelope Focus is on total building performance, not just thermal insulation Heat transfer and air leakage

More information

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE

CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS WOOD CHAPTER 3 301 SCOPE This chapter prescribes construction requirements for buildings where all exterior walls above the foundation are wood framed

More information

SECTION WOOD FRAMING. A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents.

SECTION WOOD FRAMING. A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents. SECTION 06110 WOOD FRAMING PART 1 GENERAL 1.1 SUMMARY A. Includes But Not Limited To 1. Furnish and install wood framing and blocking as described in Contract Documents. B. Products Installed But Not Supplied

More information

0103 Plan Reading 4% Read plans to verify the project conforms with the code, approved plans, and construction documents.

0103 Plan Reading 4% Read plans to verify the project conforms with the code, approved plans, and construction documents. Certification: Commercial Building Inspector Exam ID: B2 Scope: A Commercial Building Inspector will be responsible for performing inspections of structures to determine compliance with the various Building

More information

ALTERNATE DESIGN METHODOLOGY FOR UNREINFORCED MASONRY BUILDINGS

ALTERNATE DESIGN METHODOLOGY FOR UNREINFORCED MASONRY BUILDINGS INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LABC 8808 Effective: 01-01-2011 DOCUMENT NO. P/BC 2011-053 Revised: Previously Issued As: P/BC 2008-053 I. GENERAL ALTERNATE DESIGN METHODOLOGY

More information

Masonry Veneer - Chapter 6. Masonry Veneer Anchored Veneer

Masonry Veneer - Chapter 6. Masonry Veneer Anchored Veneer Masonry Veneer - Chapter 6 Chapter 6 covers anchored and adhered veneer. Following are prescriptive requirements for areas with wind 110 mph Vertical support of masonry veneer Support: Noncombustible structural

More information

WOOD I-JOIST AWARENESS GUIDE

WOOD I-JOIST AWARENESS GUIDE WOOD I-JOIST AWARENESS GUIDE American Wood Council Flange Web Flange American Forest & Paper Association WOOD I-JOIST AWARENESS GUIDE The American Wood Council is part of the wood products group of the

More information

UCC Permit Application Procedures

UCC Permit Application Procedures How do I apply for a permit? UCC Permit Application Procedures 1. Please complete the CodeMaster Pan Review Application 2. Please provide the scope of work description and/or construction documents/plans.

More information

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE:

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE: IRC CODE UPDATES TO: RESIDENTIAL BUILDING CONTRACTORS FROM: GARY STABER, BUILDING OFFICIAL SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE: 6/1/2003 INTERNATIONAL RESIDENTIAL CODE (IRC) APPLICABILITY:

More information

Earthquake Strengthening of Cripple Walls in Wood-Frame Dwellings SOUTH NAPA EARTHQUAKE RECOVERY ADVISORY

Earthquake Strengthening of Cripple Walls in Wood-Frame Dwellings SOUTH NAPA EARTHQUAKE RECOVERY ADVISORY Cripple Walls in Wood-Frame Dwellings SOUTH NAPA EARTHQUAKE RECOVERY ADVISORY Purpose and Intended Audience The August 4, 04 South Napa earthquake has reinforced past observations that wood-frame dwellings

More information

A Simple Solution for Meeting

A Simple Solution for Meeting A Simple Solution for Meeting Narrow Wall Bracing Requirements AND BUILDING A STRONGER, SAFER HOME. APA s Narrow Wall Bracing Method, combined with walls that are fully sheathed with plywood or OSB, helps

More information

SFR SUBMITTAL REQUIREMENTS

SFR SUBMITTAL REQUIREMENTS A. FEES DUE AT TIME OF PERMIT APPLICATION The following non-refundable fees will be collected at the time of application for all residential projects. 1. Building Plan Check Fee B. CODES The City of Oak

More information

STANDARD RESIDENTIAL DECK DETAILS

STANDARD RESIDENTIAL DECK DETAILS STANDARD RESIDENTIAL DECK DETAILS GUARD DECKING FLASHING OVER LEDGER BOARD EXISTING HOUSE FLOOR CONSTRUCTION GUARD POST ATTACHEMENT LEDGER BOARD ATTACHMENT TO HOUSE RIM JOIST JOIST BEAM FOOTING JOIST TO

More information

ONE-STOP S PERMIT INFORMATION PACKAGE FOR RESIDENTIAL PROJECTS

ONE-STOP S PERMIT INFORMATION PACKAGE FOR RESIDENTIAL PROJECTS ONE-STOP S PERMIT INFORMATION PACKAGE FOR RESIDENTIAL PROJECTS This package was prepared by the Customer Assistance & Code Development Office 1002 Washington Avenue 1 st Floor Houston, TX 77002 Phone:

More information

Chapter 2 QUALITY ASSURANCE

Chapter 2 QUALITY ASSURANCE Chapter 2 QUALITY ASSURANCE 2.1 GENERAL 2.1.1 Scope. This chapter provides minimum requirements for quality assurance for seismic-forceresisting systems and designated seismic systems. These requirements

More information

PENNSAFE BUILDING INSPECTION SERVICES LLC Deck and Roof Cross Section Submittal

PENNSAFE BUILDING INSPECTION SERVICES LLC Deck and Roof Cross Section Submittal PENNSAFE BUILDING INSPECTION SERVICES LLC Deck and Roof Cross Section Submittal Roof Size: Width: Length: Roof Type: Gable: Hip: Shed: Roof Pitch: (check one) Trusses: Rafters: Spacing of Trusses or Rafters:

More information

Framing Methods Structural Components

Framing Methods Structural Components Framing Methods Structural Components Balloon Framing *Balloon framing or Eastern framing the exterior studs run from the top of the foundation to the top of the highest level. Benefits of this type of

More information

Florida Building Code 6th Edition (2017) High-Velocity Hurricane Zone Uniform Permit Application Form

Florida Building Code 6th Edition (2017) High-Velocity Hurricane Zone Uniform Permit Application Form Are there Gas Vent Stacks? Yes No Type: Natural LPGX FBC SECTION 1524 HIGH-VELOCITY HURRICANE ZONES REQUIRED OWNER S NOTIFICATION FOR ROOFING CONSIDERATIONS 1524.1 Scope. As it pertains to this section,

More information

INSPECTION REQUIREMENTS: FOUNDATIONS

INSPECTION REQUIREMENTS: FOUNDATIONS Foundations Page 1 of 9 Revision Date: 1/2/2018 DEVELOPMENT SERVICES BUILDING INSPECTION INSPECTION REQUIREMENTS: FOUNDATIONS INSPECTION CODE: 204 SCOPE: RESIDENTIAL APPLICABLE CODES: 2016 CBC, CRC, CPC,

More information

The Homeowner s Building Application Checklist for Constructing a Residential Addition

The Homeowner s Building Application Checklist for Constructing a Residential Addition The Homeowner s Building Application Checklist for Constructing a Residential Addition This checklist provides homeowners a summary of the Building Permit submission requirements for constructing a residential

More information

City of Berkeley Framework Guidelines for Soft, Weak or Open Front Building Retrofit Design

City of Berkeley Framework Guidelines for Soft, Weak or Open Front Building Retrofit Design Planning and Development Building & Safety Division City of Berkeley Framework Guidelines for Soft, Weak or Open Front Building Retrofit Design This document presents Guidelines for complying with Chapter

More information

PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION

PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION Permit No. 175 Beaver Drive, P.O. Box 486 DuBois, PA 15801 Phone: 814-375-1111 Fax: 814-375-1117 Toll Free: 855-PENNSAF LOCATION OF PROPOSED

More information

Signage Code. H101.2 Signs exempt from permits. The following signs are exempt from the requirements to obtain a permit before erection:

Signage Code. H101.2 Signs exempt from permits. The following signs are exempt from the requirements to obtain a permit before erection: Signage Code ICC Code: Appendix H: Signs SECTION H101 GENERAL H101.1 General. A sign shall not be erected in a manner that would confuse or obstruct the view of or interfere with exit signs required by

More information

ILLUSTRATED GUIDE. For Seismic Design of Houses. Lateral Bracing Requirements Part 9 BC Building Code 2012

ILLUSTRATED GUIDE. For Seismic Design of Houses. Lateral Bracing Requirements Part 9 BC Building Code 2012 ILLUSTRATED GUIDE For Seismic Design of Houses Lateral Bracing Requirements Part 9 BC Building Code 2012 This guide has been developed to assist house designers and builders in understanding and complying

More information

ORDINANCE NO. 16- The City Council of the City of West Hollywood does hereby ordain as follows:

ORDINANCE NO. 16- The City Council of the City of West Hollywood does hereby ordain as follows: Page 1 ORDINANCE NO. 16- AN ORDINANCE OF THE CITY OF WEST HOLLYWOOD ESTABLISHING SEISMIC STRENGTHENING REQUIREMENTS FOR FOUR CATEGORIES OF EXISTING BUILDINGS IN THE CITY AND AMENDING THE WEST HOLLYWOOD

More information

BROCHURE # 108 CONSTRUCTION PLAN COMPONENTS

BROCHURE # 108 CONSTRUCTION PLAN COMPONENTS BROCHURE # 108 CONSTRUCTION PLAN COMPONENTS Please note: This construction plan component list is to be used as a guide to assist you with your project. There may be elements unique to your project not

More information

SEISMIC DESIGN GUIDELINES

SEISMIC DESIGN GUIDELINES INTRODUCTION The purpose of these Seismic Design Guidelines is to provide additional information and clarification to Civil or Structural engineers in order to comply with Ordinance No. 18-O- 2767 for

More information

CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1%

CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1% CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE EXAM ID: I1 80 multiple-choice questions 3-1/2-hour time limit Open book 01. GENERAL ADMINISTRATION 6% 0101. Project Administration 1% Verify that

More information

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel

More information

HOLDOWN & STRAP SCHEDULE

HOLDOWN & STRAP SCHEDULE SHEAR WALL SCHEDULE STRUCTURAL DESIGN CRITERIA GOVERNING CODE SOIL BEARING PRESSURE HOLDOWN & STRAP SCHEDULE MARK SHEATHING SHEATH BOTH SIDES NAILS EDGE SPACING NOTES MARK SW 7/" OSB NO 8d " OC - A SW

More information

#402 New Residential Submittal Checklist

#402 New Residential Submittal Checklist #402 New Residential Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the City by two methods. This checklist

More information

WALL CONSTRUCTION CHAPTER 6

WALL CONSTRUCTION CHAPTER 6 CHAPTER 6 WALL CONSTRUCTION SECTION R601 GENERAL R601.1 Application. The provisions of this chapter shall control the design and construction of all walls and partitions for all buildings. R601.2 Requirements.

More information

BUILDING PERMIT REQUIREMENTS FOR: RESIDENTIAL DECKS CITY OF ESCONDIDO BUILDING DIVISION 201 N. BROADWAY, ESCONDIDO, CA (760)

BUILDING PERMIT REQUIREMENTS FOR: RESIDENTIAL DECKS CITY OF ESCONDIDO BUILDING DIVISION 201 N. BROADWAY, ESCONDIDO, CA (760) BUILDING PERMIT REQUIREMENTS FOR: RESIDENTIAL DECKS INFORMATION GUIDELINE 9 January 2017 CITY OF ESCONDIDO BUILDING DIVISION 201 N. BROADWAY, ESCONDIDO, CA 92025 (760) 839-4647 This information bulletin

More information

NCMA TEK RESIDENTIAL DETAILS FOR HIGH WIND AREAS. TEK 5-11 Details (2003)

NCMA TEK RESIDENTIAL DETAILS FOR HIGH WIND AREAS. TEK 5-11 Details (2003) NCM TEK National Concrete Masonry ssociation an information series from the national authority on concrete masonry technology RESIDENTIL DETILS FOR HIGH WIND RES TEK 5-11 Details (2003) Keywords: architectural

More information

Borough of Doylestown Building and Zoning Department

Borough of Doylestown Building and Zoning Department Borough of Doylestown Building and Zoning Department 57 West Court Street, Doylestown, PA 18901 215.345.4140 RESIDENTIAL BUILDING AND ZONING PERMIT APPLICATION PACKAGE BACKGROUND A building permit is required

More information

2006 International Residential Code Errata (Portions of text and tables not shown are unaffected by the errata)

2006 International Residential Code Errata (Portions of text and tables not shown are unaffected by the errata) 1st through 6th PRINTING (Posted 07-25-2011) INDEX JOINTS, PIPE Slip.P3003.3.7 P2704.1 2009 International Residential Code Errata Page 1 of 1 FIRST PRINTING (Updated September 12, 2006) CHAPTER 1 ADMINISTRATION

More information

SUBMITTAL REQUIREMENTS FOR EXPEDITED ROOF TOP SOLAR PERMITTING

SUBMITTAL REQUIREMENTS FOR EXPEDITED ROOF TOP SOLAR PERMITTING KERN COUNTY PUBLIC WORKS DEPARTMENT CRAIG M. POPE, P.E., DIRECTOR 2700 M STREET BAKERSFIELD, CA 93301-2370 ADMINISTRATION & ACCOUNTING OPERATIONS & MAINTENANCE BUILDING & DEVELOPMENT ENGINEERING Phone:

More information

DESIGNING SAFE ROOMS AND SAFE HOMES WITH LOGIX.

DESIGNING SAFE ROOMS AND SAFE HOMES WITH LOGIX. . Actual ICF-Built Home That Survived Katrina Table of Contents Section Page Overview Logix Wind Resistance Advantages...3 Logix Wall Engineering To 300 MPH Wind Rating...6 Fema-Compliant Design Specifications

More information

Plan Check No. Checked by: An Appointment Is Required for Verification

Plan Check No. Checked by: An Appointment Is Required for Verification SUPPLEMENTAL CORRECTION SHEET UNREINFORCED MASONRY (URM) RETROFIT ( 2002 LABC ) Plan Check No. Checked by: Permit Appl. # An Appointment Is Required for Verification Job Address: For appt. call: APPLICATION

More information

DRAFT ORDINANCE NO. RD:JAC:CER 9/1/2016

DRAFT ORDINANCE NO. RD:JAC:CER 9/1/2016 ORDINANCE NO. DRAFT AN ORDINANCE OF THE CITY OF SAN JOSE AMENDING VARIOUS SECTIONS OF TITLE 24 (TECHNICAL CODES) OF THE SAN JOSE MUNICIPAL CODE TO ADOPT THE 2016 CALIFORNIA BUILDING, RESIDENTIAL, PLUMBING,

More information

Project Seismic Vulnerability Assessment For SFCC District Building 33 Gough Street San Francisco, California 94103

Project Seismic Vulnerability Assessment For SFCC District Building 33 Gough Street San Francisco, California 94103 Project For SFCC District Building 33 Gough Street San Francisco, California 94103 Prepared For San Francisco Community College District 33 Gough Street San Francisco, California 94103 Prepared By Thornton

More information

#G445 Plans, 48'x28' x 10' detached garage with bonus room By SDS-CAD Specialized Design Systems

#G445 Plans, 48'x28' x 10' detached garage with bonus room By SDS-CAD Specialized Design Systems Architectural asphalt shingles and horizontal True Wood 7" Reveal siding over structural panel. Nailing schedule is 6" on ends 12" on centers 6d nails. Trusses are engineered on Bonus attic trusses 24"

More information

Building for Energy Efficiency Part 2 Advanced Framing Workshop. Objectives for this presentation...

Building for Energy Efficiency Part 2 Advanced Framing Workshop. Objectives for this presentation... Building for Energy Efficiency Part 2 Advanced Framing Workshop Aaron Grin Corporation www.buildingscience.com Objectives for this presentation... 1. Brief History of Advanced Framing 2. Overview 3. Benefits

More information

LPI 56 Technical Guide

LPI 56 Technical Guide LPI 56 Technical Guide Floor & Roof Applications Product Specifications & Design Values 2 Floor Tables 3 Uniform Floor Load (PLF) Tables: Simple s 4 Uniform Floor Load (PLF) Tables: Continuous s 5 Uniform

More information

THE ASHTON PERSPECTIVE VIEW

THE ASHTON PERSPECTIVE VIEW THE ASHTON PERSPECTIVE VIEW TYPICAL DETAILS GENERAL DESIGN NOTES: 1. THESE DRAWINGS ARE OF A GENERAL NATURE AND ARE NOT INTENDED TO CONVEY THE METHOD OR MEANS OF CONSTRUCTION. IT IS ASSUMED THAT ALL WORK

More information

CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT. Submittal Requirements

CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT. Submittal Requirements CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT 1 East Franklin Street Phone: 301-790-4163 Third Floor Hagerstown, MD 21740 Fax: 301-791-2650 BUILDING PERMIT APPLICATION FOR RESIDENTIAL ACCESSORY

More information

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses

Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses Details for Exterior Brick Masonry Veneer Supported by Metal Plate Connected Wood Trusses Released May 20, 2009 Updated March 9, 2011 Introduction: Wood frame structures with attached brick masonry veneer

More information

Residential Deck Guide

Residential Deck Guide Residential Deck Guide The text and illustrations included in this guide represent opinions of the Borough of Mechanicsburg Codes and Zoning Department. This guide is for educational and information purposes

More information

Advanced Wind Mitigation Methodologies, Pt. 1- Internet Course (5th Edition)

Advanced Wind Mitigation Methodologies, Pt. 1- Internet Course (5th Edition) CODE Specifications TAB: Course Title: Advanced Wind Mitigation Methodologies, Pt. 1- Internet Course (5th Edition) Code Edition: Florida Building Code, Existing Building, 5th Edition (2014) Number of

More information

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person

More information

10. Simplified Rehabilitation Scope

10. Simplified Rehabilitation Scope 10. Simplified Rehabilitation 10.1 Scope This chapter presents the Simplified Rehabilitation Method, which is intended primarily for use on a selected group of simple buildings being rehabilitated to the

More information

Wood-Frame Seismic Retrofit Program

Wood-Frame Seismic Retrofit Program City and County of San Francisco Department of Building Inspection London N. Breed, Mayor Tom C. Hui, S.E., C.B.O., Director Wood-Frame Seismic Retrofit Program SCREENING FORM INSTRUCTIONS About the Screening

More information

SECTION WOOD FRAMING. A. Includes But Not Limited To: 1. Furnish and install wood framing and blocking as described in Contract Documents.

SECTION WOOD FRAMING. A. Includes But Not Limited To: 1. Furnish and install wood framing and blocking as described in Contract Documents. SECTION 06 1100 WOOD FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Includes But Not Limited To: 1. Furnish and install wood framing and blocking as described in Contract Documents. B. Products Installed But

More information

TOWN OF FRANCESTOWN BUILDING/CODE ENFORCEMENT 27 MAIN STREET P.O. BOX 5 FRANCESTOWN, NEW HAMPSHIRE Building Permit Application Guide

TOWN OF FRANCESTOWN BUILDING/CODE ENFORCEMENT 27 MAIN STREET P.O. BOX 5 FRANCESTOWN, NEW HAMPSHIRE Building Permit Application Guide TOWN OF FRANCESTOWN BUILDING/CODE ENFORCEMENT 27 MAIN STREET P.O. BOX 5 FRANCESTOWN, NEW HAMPSHIRE 03043-0005 TELEPHONE (603) 547-3469 EMAIL francestownnh@comcast.net FAX (603) 547-2622 Building Permit

More information

*FOR RESIDENTIAL PROJECTS, CALL JACK CARNS AT *FOR COMMERCIAL PROJECTS, CALL BRIAN WRUBLE AT

*FOR RESIDENTIAL PROJECTS, CALL JACK CARNS AT *FOR COMMERCIAL PROJECTS, CALL BRIAN WRUBLE AT MOSHANNON VALLEY COUNCIL OF GOVERNMENTS 501 E. MARKET STREET SUITE 7 CLEARFIELD, PA 16830 814-765- 3080 1. ITEMS TO SUBMIT: A. COMPLETED AND SIGNED APPLICATION B. SIGNED PRIOR MUNICIPAL APPROVAL PAGE C.

More information