ASSEMBLY INSTRUCTIONS for DATASAFE TM HX and HX FRONT TERMINAL UBC BATTERY RACKS

Size: px
Start display at page:

Download "ASSEMBLY INSTRUCTIONS for DATASAFE TM HX and HX FRONT TERMINAL UBC BATTERY RACKS"

Transcription

1 US-HXRACK-IM-002 ASSEMBLY INSTRUCTIONS for DATASAFE TM HX and HX FRONT TERMINAL UBC BATTERY RACKS Read all instructions carefully and observe all warnings before installation. See Installation, Operation and Maintenance Instructions for battery information. 1. GENERAL INFORMATION DataSafe TM HX and HX front terminal UBC battery racks are available in 1 Tier through 5 Tier configurations. Rack lengths are determined by a pre-set number of battery blocs (blocs) per tier. Number of DataSafe blocs per tier: 6HX800: 4, 5, 6, or 10 12HX205*: 8, 10, 12 or 20 12HX300: 4, 5, 6 or 10 12HX330: 4, 5, 6 or 10 12HX400: 4, 5, 6 or 10 12HX500, 505, 540: 4, 5, 6 or 10 16HX550F: 4, 5 or 6 16HX800F, 925F: 4, 5 or 6 * The 12HX205 battery rack is a 2 Row per Tier design. Racks are available in non-seismic and seismic versions. The seismic versions have been qualified to UBC Zone 4 Essential, for at or below grade installations. Racks are supplied unassembled. The components consist of: corner frames, cross braces, shelves, top cover, assembly hardware and retainers (seismic racks only). This manual covers the assembly of the DataSafe HX and HX front terminal battery rack models separately. For PowerSafe VE battery models, use the HX section. 2. SAFETY PRECAUTIONS Assemble racks in accordance with the instructions contained in this document without deviations. Refer to UBC, OSHA and EPA regulations and other federal, state or local ordinances that pertain to battery installation and storage. Refer to additional safety precautions contained in the DataSafe TM HX and HX front terminal Installation, Operation and Maintenance Instructions. For installations where grounding is required for NEC and/or other federal, state or local codes, refer to the section on rack grounding in this manual. 3. SERVICE INFORMATION Should you require installation supervision, service, parts, accessories or maintenance, EnerSys has a service organization to assist with your new rack purchase. Contact your nearest EnerSys office or call the corporate number listed on the back of this manual and ask for EnerSys Reserve Power Service. 4. INSPECTION OF BATTERY PACK COMPONENTS Upon receipt, check each package against the packing list to ensure all components and quantities are correct. Publication No. US-HXRACK-IM August 2009 Page 1 of 16

2 Inspect for visual damage while the carrier representative is still on-site. Make note of any damage. If any part has not been received or has been damaged, DO NOT proceed with installation until all parts are available. 5. INSTALLATION CONSIDERATIONS If you have any questions concerning the following installation considerations, contact your EnerSys sales representative. Consider available floor space, including aisles for bloc installation, maintenance, and possible bloc replacement. Aisle spacing should be in accordance with the NEC. ALL OTHER APPLICABLE CODE REQUIREMENTS SHOULD ALSO BE CONSIDERED. Minimum clearance between seismic racks and any objects (including walls, equipment and other racks) is recommended to be 4 in. (100 mm). NO SEISMIC RACKS SHOULD BE BUTTED TOGETHER, END-TO-END OR BACK-TO-BACK. If inter-rack cable connectors are provided by EnerSys, they are based on a rack spacing of 4 in. (100 mm); any length over this is the responsibility of the purchaser. The floor/mounting platform must be reasonably level. Shimming up to 0.25 in. (6 mm) maximum may be used to have cell support rails level both frontto-back and side-to-side. Shims and shimming hardware are user supplied. The floor/mounting platform must be capable of supporting the weight of the bloc and rack system, as well as any auxiliary equipment. ALL APPLICABLE CODE REQUIREMENTS SHOULD BE CONSIDERED. FLOOR ANCHORING AND ITS DESIGN ARE THE RESPONSIBILITY OF THE PURCHASER. Anchoring should meet all federal, state and local codes and industry standards. 6. INSTALLATION EQUIPMENT AND SUPPLIES Before working with the battery rack system, ensure that you have the tools and equipment listed below. Chalk line Concrete drill (for floor anchors) Floor shims (user-supplied) Level Ohmmeter (for ground testing) Open end/box wrenches (SAE dimensions) Ratchet set w/ sockets (SAE dimensions) Square Tape measure Torque wrench ( ft-lb.) Table 1 - Torque Specifications Bolt Size ½-13 Torque ft-lb. Nm Page 2 of 16 Publication No. US-HXRACK-IM-002 August 2009

3 7. DATASAFE TM HX FRONT TERMINAL UBC BATTERY RACK ASSEMBLY TOP COVER 7.1 DATASAFE TM HX FRONT TERMINAL UBC BATTERY RACK FLOOR ANCHORING FLOOR ANCHORING AND ITS DESIGN ARE THE RESPONSIBILITY OF THE PURCHASER. Contact your EnerSys sales representative if you have any questions. Refer to the rack assembly drawing for corner frame and anchor bolt layout. Each rack requires 4 anchor bolts. Anchoring holes are 0.56 in. (14.2 mm) diameter. Mark locations for anchor bolts. It may be helpful to assemble the corner frames, bottom shelf and top cover to use as a template to mark the locations of the anchor bolts. See Figure 7.1 and Sections 7.2, 7.3 and 7.4 for assembly instructions. CAUTION: The partial rack assembly will have to be moved to install the anchors. Use appropriate lifting equipment to avoid injury. BOTTOM SHELF Figure 7.1 CORNER FRAMES Install anchor bolts as indicated by the manufacturer s instructions. 7.2 DATASAFE TM HX FRONT TERMINAL UBC BATTERY RACK BOLTED CONNECTIONS All bolted connections will be made with ½-13 x 1.75 Hex Bolts and associated hardware. Torque bolted connections per Table 1. Bolted connections should be assembled per Figure 7.2. Figure 7.2 Publication No. US-HXRACK-IM August 2009 Page 3 of 16

4 7.3 DATASAFE TM HX FRONT TERMINAL UBC BATTERY RACK SEISMIC SHELF PREPARATION Seismic racks require neoprene strips to be installed on the shelves and top cover. Install the self-adhesive strips per the following: Top Cover: inside bottom of flanges, see Figure 7.3a. Shelf: inside bottom of flanges and back lip of shelf, see Figure 7.3b. Bottom Shelf: back lip of shelf, see Figure 7.3c. NEOPRENE STRIPS Figure 7.3a - Top Cover Non-seismic racks do not require the neoprene strips. NEOPRENE STRIPS Figure 7.3b - Shelf NEOPRENE STRIPS Figure 7.3c - Bottom Shelf Page 4 of 16 Publication No. US-HXRACK-IM-002 August 2009

5 7.4 DATASAFE TM HX FRONT TERMINAL UBC BATTERY RACK FRAME ASSEMBLY This rack is best assembled with a minimum of 2 people. Refer to the rack assembly drawing in addition to this manual. A seismic, 5 Tier rack is shown. This rack has 4 corner frames to which the shelves, top and cross braces will be fastened to. See Figure 7.4a. Attach the bottom shelf to the 4 corner frames per Figure 7.4b. The 3-hole pattern in the bottom shelf is to have bolts in the upper and lower holes when fastening to each corner frame (middle hole is left empty). Finger tighten bolts. Attach the top cover to the 4 corner frames per Figure 7.4c. The 3-hole pattern in the top cover is to have bolts in the upper 2 holes when fastening to each corner frame (lower hole is left empty). Place bolts in each of the holes in the top and back of the top cover. Finger tighten bolts. Figure 7.4b Figure 7.4a Figure 7.4c Figure 7.4a Publication No. US-HXRACK-IM August 2009 Page 5 of 16

6 7.5 DATASAFE TM HX FRONT TERMINAL UBC BATTERY RACK SHELF ASSEMBLY The bottom shelf was installed in section 7.4; install the remaining shelves beginning at the lower portion of the rack and work up. The quantity of shelves will be dependent on the rack style purchased. A 1 Tier rack will not have any shelves. NOTE: It is recommended that blocs are not placed on the rack until all shelves are installed and all bolted connections are torqued per Table 1. Figure 7.5a Attach a shelf to the 4 corner frames per Figures 7.5a, 7.5b and 7.5c. The 3-hole pattern in the shelf is to have bolts in the upper 2 holes when fastening to each corner frame (lower hole is left empty). Finger tighten bolts. Figure 7.5b Page 6 of 16 Figure 7.5c Publication No. US-HXRACK-IM-002 August 2009

7 7.6 DATASAFE TM HX FRONT TERMINAL UBC BATTERY RACK CROSS BRACE ASSEMBLY Non-seismic racks will only have rear cross braces, seismic racks will have rear and side cross braces. Install the rear cross braces per Figure 7.6a. For seismic racks, install the side cross braces per Figure 7.6b. Torque ALL connections per Table 1. Figure 7.6a - Rear view of rack Figure 7.6b - Front view of rack Publication No. US-HXRACK-IM August 2009 Page 7 of 16

8 7.7 DATASAFE TM HX FRONT TERMINAL UBC BATTERY RACK CELL INSTALLATION Refer to DataSafe TM HX front terminal battery Installation, Operation and Maintenance Instructions for additional instructions. NOTE: The bottom tier(s) should contain the largest number of blocs when applicable. Make sure all bolts are torqued per Table 1 before installing blocs. Figure 7.7a Install blocs on shelves beginning on the bottom tier. Push each bloc as far back on the shelf as possible. Battery bloc spacing is determined by the handle tab on each jar. This tab should be touching the tab on the adjacent battery bloc for proper fit of the cell to cell connectors. Each tier is designed to have a tight bloc fit. There will approximately be a 1/8 in. (3 mm) gap between the blocs and rack when the tier is full. See Figures 7.7a, 7.7b and 7.7c. Figure 7.7b CAUTION: Use appropriate lifting equipment to move the blocs to avoid injury. Page 8 of 16 Figure 7.7c Publication No. US-HXRACK-IM-002 August 2009

9 7.8 DATASAFE TM HX FRONT TERMINAL UBC BATTERY RACK SEISMIC RACK RETAINERS Retainers are required on all seismic racks. Install seismic retainers per Figure 7.8. Torque all connections per Table GROUNDING RACK (OPTIONAL) Racks should be grounded when it is required for NEC and/or federal, state or local codes. Remove/Scratch paint as necessary keeping the exposed metal to a minimum. Install lug and cable (lug and cable not furnished by EnerSys.) Ohmmeter readings between each component and a common point on the frame must indicate continuity to ensure proper grounding. Figure 7.8 Publication No. US-HXRACK-IM August 2009 Page 9 of 16

10 8. DATASAFE TM HX UBC BATTERY RACK ASSEMBLY 8.1 DATASAFE TM HX UBC BATTERY RACK FLOOR ANCHORING FLOOR ANCHORING AND ITS DESIGN ARE THE RESPONSIBILITY OF THE PURCHASER. Contact your EnerSys sales representative if you have any questions. Refer to the rack assembly drawing for corner frame and anchor bolt layout. Each rack requires 4 anchor bolts. Anchoring holes are 0.56 in. (14.2 mm) diameter. Mark locations for anchor bolts. It may be helpful to assemble the corner frames, top cover and side cross braces to use as a template to mark the locations of the anchor bolts. See Figure 8.1 and Section 8.3 for assembly instructions. Figure 8.1 CAUTION: The partial rack assembly will have to be moved to install the anchors, use appropriate lifting equipment to avoid injury. Install anchor bolts as indicated by the manufacturer s instructions. 8.2 DATASAFE TM HX UBC BATTERY RACK BOLTED CONNECTIONS All bolted connections will be made with ½-13 Hex Bolts and associated hardware. Torque bolted connections per Table 1. Figure 8.2a Bolted connections (without cross braces) should be assembled per Figure 8.2a. Cross brace bolted connections should be assembled per Figure 8.2b. Figure 8.2b Page 10 of 16 Publication No. US-HXRACK-IM-002 August 2009

11 8.3 DATASAFE TM HX UBC BATTERY RACK FRAME ASSEMBLY This rack is best assembled with a minimum of 2 people. Refer to the rack assembly drawing in addition to this manual. A seismic, 3 tier rack is shown. This rack has 4 corner frames to which front supports, rear supports, side supports, top cover and cross braces will be fastened to. See Figure 8.3a. Loosely attach (finger-tight) top cover and 2 side cross braces on each side to sturdy the corner frames, see Figure 8.3b. Figure 8.3b Loosely attach (finger-tight) lower tier front and rear supports in the holes second from the bottom of the rack as shown in Figure 8.3c. Front supports have holes to mount the seismic retainer, these holes point toward the front of the rack. Rear supports have a flange that keeps the blocs on the rack, see Figure 8.3c insert. Continue to move up the rack installing the front and rear supports as shown in Figure 8.3d. FLANGE REAR SUPPORT NOTE: It is recommended that blocs are not placed on the rack until all supports are installed and all bolted connections are torqued per Table 1. Figure 8.3c Figure 8.3a Figure 8.3d Publication No. US-HXRACK-IM August 2009 Page 11 of 16

12 8.4 DATASAFE TM HX UBC BATTERY RACK CROSS BRACE ASSEMBLY Non-seismic racks will have less cross braces than seismic racks, consult rack assembly drawing. Install the lower tier side supports per Figure 8.4a. Working up the rack, install the side supports and side cross braces per Figures 8.4b and 8.4c. Install rear cross braces and shims per Figures 8.4d & e. Torque ALL connections per Table 1. Figure 8.4a Figure 8.4a Figure 8.4b Figure 8.4b Page 12 of 16 Publication No. US-HXRACK-IM-002 August 2009

13 Figure 8.4c Figure 8.4d Figure 8.4e Publication No. US-HXRACK-IM August 2009 Page 13 of 16

14 8.5 DATASAFE TM HX UBC BATTERY RACK BLOC INSTALLATION Refer to DataSafe TM HX battery Installation, Operation and Maintenance Instructions for additional battery information. NOTE: The bottom tier(s) should contain the largest number of blocs when applicable. Make sure ALL bolts are torqued per Table 1 before installing any blocs. Install blocs on supports beginning at the bottom tier. Push each bloc back as far as possible on each tier. Work up the rack, see Figures 8.5a & b. Figure 8.5a Figure 8.5b NOTE: For 12HX205 2 Row per Tier racks, see Figure 8.5c & d for assembly of additional supports to be assembled during the bloc installation. CAUTION: Use appropriate lifting equipment to move the blocs to avoid injury. Bloc spacing is determined by the string connectors. Consider the string + & - connections as blocs are loaded on the rack. Figure 8.5c Each tier is deigned to have a tight bloc fit. There will approximately be a 1/8 in. (3 mm) gap between the last bloc and the rack on a full tier. Page 14 of 16 Figure 8.5d Publication No. US-HXRACK-IM-002 August 2009

15 8.6 DATASAFE TM HX UBC BATTERY RETAINERS Retainers are required on all seismic racks. Install retainers. The retainer should not exert any force on the bloc jar after it is installed. A minimal gap (equal to the thickness of a business card) should exist between the installed retainer and jar. The retainer bolts do not have to be torqued tight but the lock washers must be flattened out against the retainer. See Figure DATASAFE TM HX UBC BATTERY FRONT CROSS BRACES Front cross braces are required on all seismic racks. Figure 8.6 Install cross braces and shims per Figure 8.7a & 8.7b. Torque all bolted rack connections per Table GROUNDING RACK Racks should be grounded when it is required for NEC and/or federal, state or local codes. Remove/Scratch paint as necessary keeping the exposed metal to a minimum. Figure 8.7a Install lug and cable (lug and cable not furnished by EnerSys ). Ohmmeter readings between each component and a common point on the frame must indicate continuity to ensure proper grounding. Figure 8.7b Publication No. US-HXRACK-IM August 2009 Page 15 of 16

16 GLOSSARY OF TERMS BATTERY BLOC/BLOC CONNECTORS CORNER FRAME CROSS BRACE EPA NEC NON-SEISMIC RACK NEOPRENE STRIPS OSHA RESERVE POWER SERVICE SEISMIC RACK SHIMS UBC Internally connected multi-cell VRLA battery unit Electrical conductors used to connect adjacent cells on the same tier of a rack Vertical steel support structure of battery rack Steel brace used to connect rack frames together U.S. Environmental Protection Agency U.S. National Electric Code Rack designed to support the weight of the battery system only Self-Adhesive strips used to cushion the batteries on seismic racks (DataSafe TM HX FRONT TERMINAL UBC Battery racks only) U.S. Occupational Safety & Health Administration The EnerSys service and installation group Rack designed to withstand lateral loading in addition to the weight of the battery system Thin metal spacers used to level rack due to uneven flooring U.S. Uniform Building Code EnerSys P.O. Box Reading, PA USA Tel: Fax: EnerSys Europe Zurich, Switzerland Tel: +41 (0) EnerSys Asia Guangdong, China Tel: Distributed by: Publication No. US-HXRACK-IM-002 August Subject to revision without prior notice. E.&O.E EnerSys. All rights reserved. Trademarks and logos are the property of EnerSys and its affiliates unless otherwise noted.

INSTRUCTIONS FOR ASSEMBLING NEBS FLOODED RACKS

INSTRUCTIONS FOR ASSEMBLING NEBS FLOODED RACKS INSTRUCTIONS FOR ASSEMBLING NEBS FLOODED RACKS Publication No. US-NEBS-IM-003 September 2013 INSTRUCTIONS for ASSEMBLING NEBS FLOODED RACKS Read all instructions carefully and observe all warnings before

More information

L SERIES NEBS COMPLIANT STANDBY BATTERY RACKS ASSEMBLY INSTRUCTIONS

L SERIES NEBS COMPLIANT STANDBY BATTERY RACKS ASSEMBLY INSTRUCTIONS RETURN RECYCLE RS 1942 LEAD L SERIES NEBS COMPLIANT STANDBY BATTERY RACKS ASSEMBLY INSTRUCTIONS General: These instructions detail the proper procedure for installing C&D Technologies' Powercom Division

More information

Standard Duty Cantilever Rack Installation and Assembly Guide

Standard Duty Cantilever Rack Installation and Assembly Guide Standard Duty Cantilever Rack Installation and Assembly Guide Steel King Industries, Inc. 2700 Chamber St Stevens Pont, WI 54481 (800) 826 0203 www.steelking.com info@steelking.com ASSEMBLY INSTRUCTIONS:

More information

SK3000 Structural Pallet Rack Installation and Assembly Manual

SK3000 Structural Pallet Rack Installation and Assembly Manual SK3000 Structural Pallet Rack Installation and Assembly Manual Steel King Industries, Inc. 2700 Chamber St Stevens Pont, WI 54481 (800) 826 0203 www.steelking.com info@steelking.com ASSEMBLY INSTRUCTIONS:

More information

Preference Slimline 5537 Utility Console I NSTALLATION GUIDE

Preference Slimline 5537 Utility Console I NSTALLATION GUIDE Preference Slimline 5537 Utility Console I NSTALLATION GUIDE WARNING Failure to install the 5537 as described in this installation guide may cause the unit to collapse, resulting in serious injury to personnel.

More information

SKATEWHEEL FLOW RACK

SKATEWHEEL FLOW RACK SKATEWHEEL FLOW RACK 2 ASSEMBLY INSTRUCTIONS: Steel King Industries recommends that this product be assembled only by qualified personnel, experienced in assembly of storage racks, and knowledgeable of

More information

C.R. LAURENCE CO., INC. Intelli-Track SPS. Phase One - Installation Instructions

C.R. LAURENCE CO., INC. Intelli-Track SPS. Phase One - Installation Instructions Tools and Supplies: C.R. LAURENCE CO., INC. Intelli-Track SPS Phase One - Installation Instructions Ratchet Wrench with 4" Extension 9/16" Open-End Wrench (two required for suspension mounting) 9/16" Hex

More information

PV Mounting System 2703 SERIES 200 UL GROUND MOUNT SYSTEM. SnapNrack Residential PV Mounting Systems Code Compliant Installation Manual

PV Mounting System 2703 SERIES 200 UL GROUND MOUNT SYSTEM. SnapNrack Residential PV Mounting Systems Code Compliant Installation Manual PV Mounting System 2703 SERIES 200 UL GROUND MOUNT SYSTEM SnapNrack Residential PV Mounting Systems Code Compliant Installation Manual Series 200 UL Introduction Series 200 UL Introduction SnapNrack Series

More information

SELECTIVE PALLET RACK

SELECTIVE PALLET RACK SELECTIVE PALLET RACK Selective Pallet Rack 2 www.mecaluxusa.com Selective Pallet Rack Selective Pallet Rack is one of the best solutions for warehouses where it is necessary to keep a wide variety of

More information

INSTALLATION MANUAL. All Types F Series Rev G

INSTALLATION MANUAL. All Types F Series Rev G INSTALLATION MANUAL All Types - 1570 F Series Page 1 of 16 TABLE OF CONTENTS DESCRIPTION PAGE GENERAL INFORMATION & ADVISORIES 2 PRODUCT INFORMATION 3 GET TO KNOW YOUR CBU 4 HARDWARE AND COMPONENTS 5 CONCRETE

More information

SK2000 Boltless Pallet Rack Installation and Assembly Manual

SK2000 Boltless Pallet Rack Installation and Assembly Manual SK2000 Boltless Pallet Rack Installation and Assembly Manual Steel King Industries, Inc. 2700 Chamber St Stevens Pont, WI 54481 (800) 826 0203 www.steelking.com info@steelking.com ASSEMBLY INSTRUCTIONS:

More information

Aurora Genmounts Install LT Installation Manual

Aurora Genmounts Install LT Installation Manual Aurora Genmounts Install LT Installation Manual TABLE OF CONTENTS 1.0 INTRODUCTION 2.0 PRODUCT OVERVIEW 3.0 TECHNICAL SPECS 4.0 INSTALLER RESPONSIBILITY 5.0 SITE SELECTION 6.0 TOOLS REQUIRED 7.0 COMPONENT

More information

Adjustable Pallet Racking Installation Guide

Adjustable Pallet Racking Installation Guide Adjustable Pallet Racking Installation Guide Read this Guide thoroughly before commencing assembly and retain for future reference. Installation plans and design drawings should be strictly adhered to.

More information

V 2.0 ASSEMBLY GUIDE. TS Platform Scale Series 2

V 2.0 ASSEMBLY GUIDE. TS Platform Scale Series 2 V 2.0 ASSEMBLY GUIDE Series 2 TABLE OF CONTENTS OVERVIEW General Specifications...1 Cautions and Disclaimers...1 Contents of Kit...1 Tools Required For Assembly...2 Time Required to Assemble...2 ASSEMBLING

More information

GroundTrac. Installation Manual

GroundTrac. Installation Manual APPLICATION: The GroundTrac system is designed with a minimum amount of installed footings at greatly reduced labor. The system integrates with ordinary 1-1/2 schedule #40 galvanized water pipe. This ground

More information

Bravo Platform Unpacking Guide

Bravo Platform Unpacking Guide This guide describes how to unpack the Bravo device from the shipping carton. Depending on the order, the shipment can include additional packages for the Bravo utilities, pipetting head, computer, and

More information

METALWorkS. RH200 Custom Hook-on Panels. General Installation Instructions. Ceiling 1.0 GENERAL Site Conditions Product Description

METALWorkS. RH200 Custom Hook-on Panels. General Installation Instructions. Ceiling 1.0 GENERAL Site Conditions Product Description Ceiling Systems Between us, ideas become reality METALWorkS General Installation Instructions RH200 Custom Hook-on Panels 1.0 GENERAL 1.1. Product Description RH200 system is a downward accessible, metal

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

Structural Cantilever Installation Manual

Structural Cantilever Installation Manual Structural Cantilever Installation Manual 944 Fisher St. Houston, TX 77018 ~ 713-957-1111 Table of Contents Assembly... 3 Warnings... 3 Tools... 3 Components... 4 Begin Assembly... 5 Step #1: Check all

More information

" RISKS ASSOCIATED WITH THE INSTALLATION OF THE SYSTEM

 RISKS ASSOCIATED WITH THE INSTALLATION OF THE SYSTEM PALLET RACK 85-110 installation, use and maintenance instructions Shelving made entirely of first grade certified steel sheet and cold-profiled steel with galvanized steel according to SENDZIMIR process

More information

Instructions for the use of the Link 4 Pallet Rack Lifter (PRL) model 5000

Instructions for the use of the Link 4 Pallet Rack Lifter (PRL) model 5000 Instructions for the use of the Link 4 Pallet Rack Lifter (PRL) model 5000 (How to move your pallet racking using the Link 4 Pallet Rack Lifter) This process is for a typical rack move and reset. Each

More information

MASONRY ANCHORS AND CONNECTORS May 6, 2014

MASONRY ANCHORS AND CONNECTORS May 6, 2014 Page - 1 This section includes specification text to assist in describing a variety of masonry anchors, connectors, and accessories intended for masonry construction. This document contains prepared master

More information

Installation. Smart-UPS VT in Parallel kva 380/400/415 V 208/220 V 200/208 V

Installation. Smart-UPS VT in Parallel kva 380/400/415 V 208/220 V 200/208 V Installation Smart-UPS VT in Parallel 10-40 kva 380/400/415 V 208/220 V 200/208 V Contents Safety... 1 IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS.............................. 1 Prepare for

More information

INSTALLATION GUIDE. 4-Post Lift. Model United States. United Arab Emirates. Egypt.

INSTALLATION GUIDE. 4-Post Lift. Model United States. United Arab Emirates. Egypt. 4-Post Lift INSTALLATION GUIDE United States 17779 Main Street Suite C Irvine, CA 92614 USA Tel: +1(949) 333-3800 Fax: +1(949) 333-3804 United Arab Emirates Model 46614 P.O. Box 121971 Saif Zone A2-032

More information

Mounting systems for solar technology

Mounting systems for solar technology Mounting systems for solar technology ASSEMBLY INSTRUCTIONS CROSSRAIL TILT KIT 7 / 0 / 5 TILT FOR LOW-SLOPE AND STEEP-SLOPE ROOFS TABLE OF CONTENTS TABLE OF CONTENTS THE COMPANY SAFETY REGULATIONS MATERIALS

More information

Mecalux Pallet Racking Assembly

Mecalux Pallet Racking Assembly Guide to Assembly & Usage Mecalux Pallet Racking Assembly Read this Guide thoroughly before commencing assembly and retain for future reference. Installation plans and design drawings should be strictly

More information

MAX-RAK 246 INSTANTLY ADJUSTABLE PALLET RACK

MAX-RAK 246 INSTANTLY ADJUSTABLE PALLET RACK MAX-RAK 246 INSTANTLY ADJUSTABLE PALLET RACK WWW.RAPISTAK.COM Max-Rak 246 Instantly Adjustable Pallet Rack Features Removable and instantly adjustable steel fabricated pallets instead of fixed beam shelving.

More information

Ground Fault Protection. Medium Voltage Artificial Neutrals

Ground Fault Protection. Medium Voltage Artificial Neutrals Ground Fault Protection Medium Voltage Artificial Neutrals Installation and Maintenance Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472

More information

Aluminum Headache Rack

Aluminum Headache Rack Instruction Manual Aluminum Headache Rack ITEM NO.: AHAR Read and understand this entire manual before assembling, installing, operating, or servicing this product. SAVE THIS MANUAL IMPORTANT SAFETY INFORMATION

More information

24 Portable Saw Mill OWNER S MANUAL

24 Portable Saw Mill OWNER S MANUAL 24 Portable Saw Mill OWNER S MANUAL WARNING: Carefully read and understand all ASSEMBLY AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions

More information

20 Portable Saw Mill OWNER S MANUAL

20 Portable Saw Mill OWNER S MANUAL 20 Portable Saw Mill OWNER S MANUAL WARNING: Carefully read and understand all ASSEMBLY AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions

More information

ERS2010 ERSW2010. Users Manual. Seismic Restraint System

ERS2010 ERSW2010. Users Manual. Seismic Restraint System ERS2010 ERSW2010 Seismic Restraint System Users Manual II. ii Warranty Newport Corporation warrants that this product will be free from defects in material and workmanship and will comply with Newport

More information

VIA BOWLING. File No.: M COPYRIGHT 2005, VIA BOWLING PRODUCTS

VIA BOWLING. File No.: M COPYRIGHT 2005, VIA BOWLING PRODUCTS VIA BOWLING File No.: M200510-01 COPYRIGHT 2005, VIA BOWLING PRODUCTS CONTENTS Warning --------------------------------------------------------------------------------------2 How to Use the Manual -----------------------------------------------------------------3

More information

Washer, Electrical Equipment Bond. WEEB Patent Pending INSTALLATION INSTRUCTIONS. For POWER-STRUT Mounting System only

Washer, Electrical Equipment Bond. WEEB Patent Pending INSTALLATION INSTRUCTIONS. For POWER-STRUT Mounting System only Washer, Electrical Equipment Bond WEEB Patent Pending INSTALLATION INSTRUCTIONS For POWER-STRUT Mounting System only Please read carefully before installing. Burndy LLC recommends that the sufficient details

More information

Installation and Maintenance Manual for EMH Freestanding Workstation Jib Cranes

Installation and Maintenance Manual for EMH Freestanding Workstation Jib Cranes 1 Installation and Maintenance Manual for EMH Freestanding Workstation Jib Cranes Installation and Maintenance Manual for EMH Freestanding Workstation Jib Cranes Table of Contents Forward.... 3 Mast Installation...

More information

SEISMIC PROTECTION SYSTEMS Bracing Products for Racks & Cabinets

SEISMIC PROTECTION SYSTEMS Bracing Products for Racks & Cabinets SEISMIC PROTECTION SYSTEMS Bracing Products for Racks & Cabinets Seismic Frame Two-Post Rack Page 11-3 Seismic Protection Products - Racks Page 11-6 Seismic Protection Products - Runway Page 11-8 Seismic

More information

ZS880 Linear Shower Drain Installation Instructions

ZS880 Linear Shower Drain Installation Instructions Introduction PATENT PENDING The Zurn ZS880 Stainless Steel Linear Shower Drain incorporates a simple approach to bathroom shower design, when compared to traditional point-drain applications. The linear

More information

Suspension System Data Center Ceiling Solutions

Suspension System Data Center Ceiling Solutions Hardware That Needs to be Purchased Separately Screws are fine listed as shown: Min 1-1/4" or longer #8 Truss head self-tapping screws for attaching structural wall angle, lateral support bar 16" or 4"

More information

SECTION (16071) - VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION (16071) - VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS SECTION 26 05 48 (16071) - VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. This Section includes seismic restraints and other earthquake-damage-reduction measures for

More information

Quick-release pins swing the rack open from left to right to simplify installing and maintaining your equipment.

Quick-release pins swing the rack open from left to right to simplify installing and maintaining your equipment. RM070A-R3 RM080A-R3 Wallmount Frame User s Manual Quick-release pins swing the rack open from left to right to simplify installing and maintaining your equipment. Customer Support Information Order toll-free

More information

FEATURES APPLICATIONS. Technical data sheet SSW - STEEL STRONG-WALL FOR TIMBER FRAME RACKING RESISTANCE.

FEATURES APPLICATIONS. Technical data sheet SSW - STEEL STRONG-WALL FOR TIMBER FRAME RACKING RESISTANCE. The Steel Strong-Wall is a corrugated steel panel which is designed to be fixed directly to the concrete foundations of a building, within the external or internal wall, via a bolted connection. FEATURES

More information

Axiom. SURFACE MOUNTED ARRAY Patient Headwall. Installation Guidelines. Installation Instructions.

Axiom. SURFACE MOUNTED ARRAY Patient Headwall. Installation Guidelines. Installation Instructions. Axiom www.hsiheadwalls.com SURFACE MOUNTED ARRAY Patient Headwall Installation Instructions Installation Guidelines Tel: 925.427.7800 Fax: 925.427.0800 support@hsiheadwalls.com Hospital Systems Inc. 750

More information

B. Shop Drawings: Include plans, elevations, sections, details, and attachments.

B. Shop Drawings: Include plans, elevations, sections, details, and attachments. SECTION 055119 - METAL GRATING STAIRS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

1.2M Ku-BAND Rx/Tx SERIES 1135 FEED SYSTEM

1.2M Ku-BAND Rx/Tx SERIES 1135 FEED SYSTEM May 24, 2016 ASSEMBLY MANUAL Revision E 1.2M Ku-BAND Rx/Tx SERIES 1135 FEED SYSTEM General Dynamics SATCOM Technologies 1700 Cable Drive NE Conover NC 28613 USA Phone 770-689-2040 www.gdsatcom.com 1.2M

More information

SYSTEM 600 BILL CHANGER INSTALLATION INSTRUCTIONS Congratulations...

SYSTEM 600 BILL CHANGER INSTALLATION INSTRUCTIONS Congratulations... www.standardchange.com 1-800-968-6955 Technical Phone Support is from 8:00AM to 7:30PM E.S.T., Monday-Friday Walk-in Service is from 8:00AM to 4:30PM E.S.T., Monday-Friday Parts Department is from 8:00AM

More information

Low-profile, 11U high cabinets hold networking equipment, servers, and phone equipment.

Low-profile, 11U high cabinets hold networking equipment, servers, and phone equipment. RM140A-R3 RM140A-M-R3 RM145A-R3 RM145A-M-R3 Small Office/Home Office (SOHO) Cabinets Low-profile, 11U high cabinets hold networking equipment, servers, and phone equipment. Fit under most desktops in the

More information

Modular Simplicity Dero

Modular Simplicity Dero B I K E H AV E N Modular Simplicity The Bike Haven bridges the gap between short and long term bike parking. The simple, modular canopy design makes it easy to create the bike shelter that fits your needs.

More information

Instruction Manual TWISTLOCK SAND VOLLEYBALL SOCKETS SVB23/SVB27

Instruction Manual TWISTLOCK SAND VOLLEYBALL SOCKETS SVB23/SVB27 Instruction Manual TWISTLOCK SAND VOLLEYBALL SOCKETS Customer Service (800) 247-7668 SVB23/SVB27 P A R T S L I S T Item Qty Description Item Qty Description A 1 Sand Volleyball Socket (3 or 4 ) B 1 Twistlock

More information

For Silverback Solar

For Silverback Solar Washer, Electrical Equipment Bond WEEB Patent Pending INSTALLATION INSTRUCTIONS For Silverback Solar Please read carefully before installing. Wiley Electronics recommends that the sufficient details of

More information

VIBRATING CONVEYORS MODEL VMC

VIBRATING CONVEYORS MODEL VMC VM-3671 Installation, Operation and Maintenance Instructions VIBRATING CONVEYORS MODEL VMC ERIEZ MAGNETICS HEADQUARTERS: 2200 ASBURY ROAD, ERIE, PA 16506 1440 U.S.A. WORLD AUTHORITY IN ADVANCED TECHNOLOGY

More information

Rack-in-a-BoxTM INSTALLATION MANUAL

Rack-in-a-BoxTM INSTALLATION MANUAL INSTALLATION MANUAL TM 1.0 INTRODUCTION 3 2.0 PRODUCT RANGE 4 2.1 Systems 4 2.2 Accessories 4 3.0 PREPARATION FOR INSTALLATION 5 3.1 Applications 5 3.2 Tools for Installation 5 3.3 Additional Materials

More information

OWNER S MANUAL SERIES MDS-96-BK, SM, DR

OWNER S MANUAL SERIES MDS-96-BK, SM, DR VESTIL MANUFACTURING CORP. 2999 N. Wayne St., Angola, IN 46703 Ph: 260-665-7586 Fax: 260-665-1339 E-mail: sales@vestil.com Website: www.vestil.com SERIES MDS-96-BK, SM, DR OWNER S MANUAL Introduction...

More information

OWNER S MANUAL SERIES MDS-96-BK, SM, DR

OWNER S MANUAL SERIES MDS-96-BK, SM, DR SERIES MDS-96-BK, SM, DR OWNER S MANUAL Introduction... 1 Bill of Materials... 2 Assembly Instructions. 3 Warranty....12 IMPORTANT NOTES, WARNINGS AND SAFETY INSTRUCTIONS Ensure that all employees understand

More information

INSTALLING A POUR-IN-PLACE DOCK LEVELER (EH & RR)

INSTALLING A POUR-IN-PLACE DOCK LEVELER (EH & RR) INSTALLING A POUR-IN-PLACE DOCK LEVELER (EH & RR) Part A: Prepare the Site & Make the Floor 1.) Prepare (concrete) dock wall and pit floor as shown in the diagrams. Pit floor should taper from back to

More information

SECTION METAL FLOOR PLATE STAIRS

SECTION METAL FLOOR PLATE STAIRS SECTION 05513 - METAL FLOOR PLATE STAIRS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

LIB System for UPS Installation Manual (136S)

LIB System for UPS Installation Manual (136S) LIB System for UPS Installation Manual (136S) ET003193796 English 1/2018. Rev 0.3 Read this manual carefully before starting to install the battery system. Keep these instructions for future reference.

More information

Assembly and users manual. Pallet racking Alfa

Assembly and users manual. Pallet racking Alfa Assembly and users manual Pallet racking Alfa ASSEMBLING OF FRAMES Tightening Torque Screw M0 8.8 Max. tightening torque 7 Nm Taptite M6 Max. tightening torque 5 Nm Taptite M8 Max. tightening torque 5

More information

Panel Jack Pro System BRACING, ALIGNMENT AND SCAFFOLDING EQUIPMENT

Panel Jack Pro System BRACING, ALIGNMENT AND SCAFFOLDING EQUIPMENT IMPORTANT SAFETY INFORMATION FOR USERS OF THE REECHCRAFT, BRACING SYSTEM PLEASE READ BEFORE USE Panel Jack Pro System BRACING, ALIGNMENT AND SCAFFOLDING EQUIPMENT UK Edition 1.3 26/11/2012 1 TABLE OF CONTENTS

More information

Conergy SolarFamulus II

Conergy SolarFamulus II Conergy SolarFamulus II Installation manual www.conergy.com Table of Contents Table of Contents SolarFamulus II for universal use on flat roofs 1 Introduction 1 1.1 Short description 1 1.2 Intended use

More information

Repackaging the Router

Repackaging the Router APPENDIXA Revised: March 16, 29, Introduction This appendix describes two separate but related router repackaging tasks: How to remove the router from the equipment rack and repackage the router for shipment

More information

Solutions Railing Overview ACTUAL FREIGHT CHARGES APPLY TO ALL SOLUTIONS RAIL ORDERS

Solutions Railing Overview ACTUAL FREIGHT CHARGES APPLY TO ALL SOLUTIONS RAIL ORDERS 60 Aluminum Railing Systems SOLUTIONSTM Solutions Railing Overview Post to Post - PTP Solutions PTP application method is the traditional surface mount installation method with the rail terminating into

More information

Mounting Screw. Channel Filler. Light Angle Adjustable Screw. LED Board Vertical stud and blocking Locking Nose. Driver.

Mounting Screw. Channel Filler. Light Angle Adjustable Screw. LED Board Vertical stud and blocking Locking Nose. Driver. The Knife Edge Cove is a modular lighting system consisting of two parts: 1- An aluminum fixture housing extrusion 2- Drop-in lighting modules The fixture will provide a continuous knife edge architectural

More information

DETAIL INSTRUCTION No. 1

DETAIL INSTRUCTION No. 1 BEFORE BEGINNING INSTALLATION, PLEASE READ THROUGH ALL INSTRUCTIONS. Uncrate shipment and check against packing list to insure all materials are included before beginning installation. If any discrepencies

More information

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection

SECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION

More information

PRB. Flush Mount Racking System. Installation Manual

PRB. Flush Mount Racking System. Installation Manual PRB Flush Mount Racking System Installation Manual Released 5th April 2015 TABLE OF CONTENTS 1. INTRODUCTION 1.1 Product Overview 1.2 About This Manual 1.3 Product Liability 1.4 Standards Compliance 1.5

More information

VISIT THE LIFETIME WEB SITE:

VISIT THE LIFETIME WEB SITE: 04/21/2008 VISIT THE LIFETIME WEB SITE: WWW.LIFETIME.COM ** Do Not Contact the Store ** For Assistance, including missing or broken parts, Call Customer Service at: 1 (800) 225-3865 30 Shed Extension Kit

More information

Ultra-Thin LED/LCD TV Mount 23" to 42" Installation Guide

Ultra-Thin LED/LCD TV Mount 23 to 42 Installation Guide Ultra-Thin LED/LCD TV Mount 23" to 42" Installation Guide Ultra-Thin LED/LCD TV Wall Mount Material: 2.0mm Cold Rolled Steel Plate TV size: 23" - 42" Max load capacity: 110 lbs / 50 kgs Wall distance:

More information

Leveling Foot RB210. Leg Extender RLT66

Leveling Foot RB210. Leg Extender RLT66 Landing for Right & Left Turn R342 ITEMS # 0254049, 0254061, 0254072, 0254076, 0016567, 0254099, 0254110, 0054116, 0254117, 0254126, 0254140, 0254150, 0254156 CUSTOM ACCESS RAMP SYSTEM MODELS # R100, R242,

More information

PRODUCT INFORMATION Dero Hoop Rack

PRODUCT INFORMATION Dero Hoop Rack PRODUCT INFORMATION Dero Hoop Rack 2946 Larimer St. Denver, CO 80205 303-295-1100 / 800-373-7693 FAX 303-295-2464 Email info@snyderequipment.com www.snyderequipment.com H O O P R A C K The Hoop Rack is

More information

Universal Elevator Mount Owners Manual

Universal Elevator Mount Owners Manual REQUIRED TOOLS AND MATERIALS: 2 Capable Adults Universal Elevator Mount Owners Manual 1-00-spalding Carpenter s Level 15 Tape Measure Pencil Adult Assembly Required. This manual, accompanied by sales receipt,

More information

STRUCTURAL STEEL FRAMING

STRUCTURAL STEEL FRAMING SECTION 05 12 00 - STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Section includes 1. Structural steel framing 2. Structural steel framing required for support and framing of rooftop mechanical

More information

INSTALLATION INSTRUCTIONS. Wall Sleeve Kit. For Use With MGE/MCE/MHP Series Magic-Pak Unit

INSTALLATION INSTRUCTIONS. Wall Sleeve Kit. For Use With MGE/MCE/MHP Series Magic-Pak Unit INSTALLATION INSTRUCTIONS Wall Sleeve Kit For Use With MGE/MCE/MHP Series Magic-Pak Unit This manual must be left with the homeowner for future reference. This is a safety alert symbol and should never

More information

H07 H09. BENCH FUME HOOD with Combination Sash. Fume Hoods. Installation Instructions. 48"- 60"- 72"- 96" long

H07 H09. BENCH FUME HOOD with Combination Sash. Fume Hoods. Installation Instructions. 48- 60- 72- 96 long Installation Instructions Supreme Air BENCH FUME HOOD with Combination Sash H07 H09 S T Y L E Fume Hoods 48"- 60"- 72"- 96" long Publication No. IIH07-SA 07/06 Part Number: IMAN-H07 FUME HOOD END PANEL

More information

Installation Guide EcoFoot2+ 10-Degree Ballasted Racking System Document No. ECO-002_850. Rev 1.6, January 2018

Installation Guide EcoFoot2+ 10-Degree Ballasted Racking System Document No. ECO-002_850. Rev 1.6, January 2018 Installation Guide EcoFoot2+ 10-Degree Ballasted Racking System Document No. ECO-002_850 Rev 1.6, January 2018 Sales: 740-249-1877 Sales@EcolibriumSolar.com Field Support: 866-488-6794 FieldSupport@EcolibriumSolar.com

More information

Quick Adjustable Height Stands

Quick Adjustable Height Stands Quick Adjustable Height Stands Installation, Maintenance & Parts Manual DORNER MFG. CORP. INSIDE THE USA OUTSIDE THE USA P.O. Box 0 975 Cottonwood Ave. TEL: -800-397-8664 TEL: 6-367-7600 Hartland, WI 5309-000

More information

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT Page 230548-1 SECTION 230548 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Rough-in frame and flush-mount panel installation instructions

Rough-in frame and flush-mount panel installation instructions Welch Allyn, Inc. 3 State Street Road Skaneateles Falls, NY 33 USA Rough-in frame and flush-mount panel installation instructions 726080 DIR 8002869 Ver. A Revised 206- The Welch Allyn In-Floor Scale models

More information

PRE-INSTALLATION GUIDE

PRE-INSTALLATION GUIDE TRUMPF MEDICAL SYSTEMS Inc. Charleston, SC PRE-INSTALLATION GUIDE FOR CEILING MOUNTED EQUIPMENT MANAGEMENT SYSTEMS, SURGICAL / EXAM LIGHTS, AND FLAT PANELS EMS and Light Pre-installation Guide File: 110720

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 0548 - PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Model # 338SM-OP. 9/30/2011 Page 1 of 12

Model # 338SM-OP. 9/30/2011 Page 1 of 12 Model # 338SM-OP 9/30/2011 Page 1 of 12 9/30/2011 Page 2 of 12 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic

More information

SECTION VIBRATION CONTROLS FOR PLUMBING PIPING AND EQUIPMENT

SECTION VIBRATION CONTROLS FOR PLUMBING PIPING AND EQUIPMENT Page 220548-1 SECTION 220548 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

USER'S GUIDE FOR INSPECTION OF DAMAGED STORAGE RACK SYSTEMS DON T WAIT UNTIL IT S TOO LATE!

USER'S GUIDE FOR INSPECTION OF DAMAGED STORAGE RACK SYSTEMS DON T WAIT UNTIL IT S TOO LATE! USER'S GUIDE FOR INSPECTION OF DAMAGED STORAGE RACK SYSTEMS DON T WAIT UNTIL IT S TOO LATE! TABLE OF CONTENTS Introduction...3 Major Safety Issues For Pallet Racking...4 Industry Standards...5 Severe Column

More information

Site Preparation... 2

Site Preparation... 2 TRUFIREWALLS INSTALLATION MANUAL This Installation Manual is intended to assist in the preparation and installation of TruFireWalls products manufactured by Oldcastle Enclosure Solutions. The TruFireWalls

More information

» Bolted system. the flexible classic. Plug-in system Bolted Office shelving Wide-span shelving Pallet racking Cantilever racking.

» Bolted system. the flexible classic. Plug-in system Bolted Office shelving Wide-span shelving Pallet racking Cantilever racking. Plug-in system Office Wide-span Plug-in system Bolted Office Wide-span system» the flexible classic 112 System overview 114-11 Complete units Shelving systems 118-123 MULTIplus shelves 124-12 Angle profiles

More information

USER'S GUIDE FOR INSPECTION OF DAMAGED STORAGE RACK SYSTEMS DON T WAIT UNTIL IT S TOO LATE!

USER'S GUIDE FOR INSPECTION OF DAMAGED STORAGE RACK SYSTEMS DON T WAIT UNTIL IT S TOO LATE! USER'S GUIDE FOR INSPECTION OF DAMAGED STORAGE RACK SYSTEMS DON T WAIT UNTIL IT S TOO LATE! TABLE OF CONTENTS Common Safety Problems...4 Industry Standards...5 Severe Column Damage...6 Horizontal and Diagonal

More information

STP Mount Series. Installation Manual. STP-LSCR-MAN 2017 Edition v1.0. For models: STP-SCR/045 STP-SCR/060 STP-SCR/070 STP-LCR/090 STP-LCR/120

STP Mount Series. Installation Manual. STP-LSCR-MAN 2017 Edition v1.0. For models: STP-SCR/045 STP-SCR/060 STP-SCR/070 STP-LCR/090 STP-LCR/120 Installation Manual STP-LSCR-MAN 2017 Edition v1.0 For models: STP-SCR/045 STP-SCR/060 STP-SCR/070 STP-LCR/090 STP-LCR/120 Table of Contents Introduction... 1 Customer Support... 1 Tools Required... 2

More information

Model # 800SM-PS3. 8/3/2016 Page 1 of 8

Model # 800SM-PS3. 8/3/2016 Page 1 of 8 Model # 800SM-PS3 8/3/2016 Page 1 of 8 /3/2016 Page 2 of 8 1675 Locust Street Red Bud, IL 62278 Phone: 618-282-8200 Fax: 618-282-8202 WARRANTY & TERMS WARRANTY: 5 Year Limited Warranty on Thermoplastic

More information

ASSEMBLY INSTRUCTIONS RESIDENTIAL SOLUTION CROSSRAIL GROUND MOUNT SYSTEM USA

ASSEMBLY INSTRUCTIONS RESIDENTIAL SOLUTION CROSSRAIL GROUND MOUNT SYSTEM USA ASSEMBLY INSTRUCTIONS RESIDENTIAL SOLUTION CROSSRAIL GROUND MOUNT SYSTEM USA TABLE OF CONTENTS TABLE OF CONTENTS SAFETY REGULATIONS MATERIALS REQUIRED ASSEMBLY ENGINEERING DRAWINGS TERMS AND CONDITIONS

More information

PRELUDE. 24 MAX TM Suspension System Data Centre Ceiling Solutions. Assembly and Installation Instructions

PRELUDE. 24 MAX TM Suspension System Data Centre Ceiling Solutions. Assembly and Installation Instructions Hardware That Needs to be Purchased Separately Screws are fine listed as shown: 4. x 3 mm or longer Self Drilling Screw Phillips Pan Head for attaching structural wall angle, lateral support bar 400 mm

More information

Model: LoLander Series Truck Scale Model: LL FT Model: LL FT Installation, Set-Up and Operation Manual

Model: LoLander Series Truck Scale Model: LL FT Model: LL FT Installation, Set-Up and Operation Manual SCALE WORKS, INC. Model: LoLander Series Truck Scale Model: LL8035-10FT Model: LL8035-11FT Installation, Set-Up and Operation Manual Cambridge Scale Works, Inc. P.O. Box 670 Honey Brook, PA. 19344 (800)

More information

B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work.

B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work. SECTION 055116 - METAL FLOOR PLATE STAIRS PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A GENERAL INSTALLATION GUIDE FOR RIDG-U-RAK DRIVE-IN / DRIVE-THRU STORAGE SYSTEMS IG-DI-1

A GENERAL INSTALLATION GUIDE FOR RIDG-U-RAK DRIVE-IN / DRIVE-THRU STORAGE SYSTEMS IG-DI-1 A GENERAL INSTALLATION GUIDE FOR RIDG-U-RAK DRIVE-IN / DRIVE-THRU STORAGE SYSTEMS IG-DI-1 CONTENTS I. INTRODUCTION II. GENERAL GUIDELINES III. SHIPMENT CHECK & UNLOADING INSTRUCTIONS IV. PRIOR TO INSTALLATION

More information

GEMINI G9 PHOTOVOLTAIC RACKING SYSTEM

GEMINI G9 PHOTOVOLTAIC RACKING SYSTEM Installation Instructions GEMINI G9 PHOTOVOLTAIC RACKING SYSTEM SYS TEM DISTRIBUTED BY: RENEWABLE SALES 16 EVERETT ST HOLLISTON MA 01746 508-309-4437 INFO@RENEWABLESALES.COM GEMINI G9 PV RACKING SYSTEM

More information

» Bolted shelving system

» Bolted shelving system Plug-in system Bolted system Office Wide-span Plug-in system Bolted Office Wide-span systembolted system» Bolted system the flexible classic 112 Bolted system System overview 114-11 Complete units Shelving

More information

METALWORKS RH215 Faceted Custom Hook-on Panels

METALWORKS RH215 Faceted Custom Hook-on Panels METALWORKS RH215 Faceted Custom Hook-on Panels Assembly and Installation Instructions 1. GENERAL 1.1 Product Description MetalWorks RH215 Faceted Custom Hook-on panel system is a downward accessible, custom

More information

EASYUP 7000 The ideal open-type boltless long span shelving system Four basic inter-locking components only.

EASYUP 7000 The ideal open-type boltless long span shelving system Four basic inter-locking components only. EASYUP 7000 The ideal open-type boltless long span shelving system Four basic inter-locking components only. STORAGE SYSTEMS LONG SPAN EZ-RECT COMPATIBLE STEEL SHELVING (BULK STORAGE) EASYUP 7000 is the

More information

5-1/2 inch Vinyl Handrail Model(s): BHRVE55C-P

5-1/2 inch Vinyl Handrail Model(s): BHRVE55C-P 5-1/2 inch Vinyl Handrail INSTALLATION, OPERATION & MAINTENANCE MANUAL Table of Contents 5-1/2 inch Vinyl Handrail Table of Contents General Description...3 Installation...4-7 Parts List...8 Maintenance...9

More information