INTERNATIONAL BUILDING CODE - ADOPTION AND AMENDMENTS Effective July 1, 2004

Size: px
Start display at page:

Download "INTERNATIONAL BUILDING CODE - ADOPTION AND AMENDMENTS Effective July 1, 2004"

Transcription

1 CITY OF MERCER ISLAND 9611 SE 36 th Street, Mercer Island, Washington PHONE (206) FAX (206) TDD (206) INTERNATIONAL BUILDING CODE - ADOPTION AND AMENDMENTS Effective July 1, 2004 The 2003 edition of the International Building Code (IBC), as adopted and amended by the State Building Code Council in Chapter WAC, as published by the International Code Council, excluding Chapter 1 Administration, is adopted by reference, together with the following amendments and additions. The Construction Administrative Code, as set forth in MICC Chapter 17.14, shall be used in place of IBC Chapter 1, Administration. The following Appendices of the 2003 edition of the International Building Code are also adopted by reference: Appendix E Supplementary Accessibility Requirements, Sections 101 through 106 only and Appendix H Signs. Amendments and Additions. A. IBC Section Amended Utility and Miscellaneous Group U, General. Section of the International Building Code is hereby amended to read as Section General. Buildings and structures of an accessory character and miscellaneous structures not classified in any specific occupancy shall be constructed, equipped and maintained to conform to the requirements of this code commensurate with the fire and life hazard incidental to their occupancy. Group U shall include, but not be limited to, the following: Agricultural buildings Aircraft hangars, accessory to a one- or two-family residence (see Section 412.3) Barns Carports Fences more than 6 feet (1829 mm) high Grain silos, accessory to a residential occupancy Greenhouses Livestock shelters private garages Retaining walls Sheds Stables Tanks Towers Waterfront structures s:\dsg\forms_all_dsg\form2000\building\icodes\i ibc adoption and amendments.doc Page 1 of 5 7/1/2004

2 B. IBC Section Amended Underground Buildings, Standby power. Section of the International Building Code is hereby amended to read as Section Standby power. A standby power system complying with Section 2702 shall be provided for standby power loads specified in Section Fuel-fired emergency generator sets and associated fuel storage, including optional generator sets, located more than 30 feet below the lowest level of exit discharge requires the approval of the Fire Code Official. C. IBC Section Amended General Building Heights and Areas, General, Premises identification. Section of the International Building Code is hereby amended to read as Section Premises identification. Approved numbers or addresses shall be provided for new buildings in such a position as to be clearly visible and legible from the street or roadway fronting the property. Letters or numbers shall be a minimum 6 inches (152mm) in height and stroke of minimum 0.5 inch (12.7mm) of contrasting color to the background itself. D. IBC Section Amended Shaft Enclosures, Shaft enclosure required. Section 707.2, Exception 2.1 of the International Building Code is hereby amended to read as Section Shaft enclosure required, Exception 2.1. Where the area of the floor opening between stories does not exceed twice the horizontal projected area of the escalator or stairway and the opening is protected by a draft curtain and closely spaced sprinklers in accordance with NFPA 13. This application is limited to openings that do not connect more than four stories in buildings not required to have smoke control systems. In buildings that are required to have smoke control systems, escalators are limited to openings that do not connect more than four stories and non-egress stairs are limited to openings that do not atmospherically connect more than two stories in buildings that are required to have smoke control systems. E. IBC Section Amended Load Combinations, Load Reduction. Section of the International Building Code is hereby amended to read as Section Load Reduction. It is permitted to multiply the combined effect of two or more variable loads by 0.75 and add to the effect of dead load. The combined load used in design shall not be less than the sum of the effects of dead load and any one of the variable loads. s:\dsg\forms_all_dsg\form2000\building\icodes\i ibc adoption and amendments.doc Page 2 of 5 7/1/2004

3 Increases in allowable stresses specified in the appropriate materials section of this code or referenced standard shall not be used with the load combinations of Section except that a duration of load increase shall be permitted in accordance with Chapter 23. F. IBC Section Amended Snow Loads, General. Section of the International Building Code is hereby amended to read as Section General. Design snow loads shall not be less than 25 psf, but the design roof loads shall not be less than that determined by Section G. IBC Section Amended Special Inspections, General. Section of the International Building Code is hereby amended by deleting Exception 3 that exempts special inspection requirements for R-3 and U occupancies to read as Section General. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner s agent shall employ one or more special inspectors to provide inspections during construction on the types of work listed under Section The special inspector shall be a qualified person who shall demonstrate competence, to the satisfaction of the building official, for inspection of the particular type of construction or operation requiring special inspection. These inspections are in addition to the inspections specified in Section 109. Exceptions: 1. Special inspections are not required for work of a minor nature or as warranted by conditions in the jurisdiction as approved by the building official. 2. Special inspections are not required for building components unless the design involves the practice of professional engineering or architecture as defined by applicable state statutes and regulations governing the professional registration and certification of engineers or architects. H. IBC Section Amended Special Inspections, Exterior insulation and finish systems (EIFS). Section of the International Building Code is hereby amended to read as IBC Section Exterior insulation and finish systems (EIFS). Special inspections shall be required for all EIFS applications. All EIFS applications shall be certified by the manufacturer as having been installed per the manufacturer s installation recommendations or other agency approved by the building official. The manufacturer certification shall serve as the special inspection requirement when approved by the building official. s:\dsg\forms_all_dsg\form2000\building\icodes\i ibc adoption and amendments.doc Page 3 of 5 7/1/2004

4 I. IBC Table , Footnote i Amended Allowable Stress Design, Allowable Shear, etc., Table , Footnote i of the International Building Code is hereby amended to read as Table , Allowable Shear for Wood Structural Panel Shear Walls, etc., Footnote i. In Seismic Design Category D, E or F, where shear design values exceed 490 pounds per lineal foot (LRFD) or 350 pounds per lineal foot (ASD) all framing members receiving edge nailing from abutting panels shall not be less than a single 3-inch nominal member, or two 2-inch nominal members fastened together in accordance with Section (LRFD) or Section (ASD) to transfer the design shear value between the framing members. Plywood joint and sill plate nailing shall be staggered in all cases. See Section for sill plate side and anchorage requirements. J. IBC Section 3110 Added Waterfront Structures. Section 3110 of the International Building Code is hereby added to read as SECTION 3110 WATERFRONT STRUCTURES Section General. In addition to other requirements of this code, all waterfront structures including, but not limited to docks, piers, wharves, floats, mooring piles, anchor buoys, bulkheads, submerged or overhead wires, pipes, and cables, and any object passing beneath, through or over the water beyond the line of ordinary high water shall comply with the regulations of this section. Section Approvals required. Before any permit for a new waterfront structure or revisions to an existing waterfront structure is issued by the building official, the applicant shall obtain prior approval from all applicable state and federal agencies. Section Definitions. For the purposes of this section, certain terms are defined as BULKHEAD. A retaining wall or erosion-control structure along a waterfront. COVERED WATERFRONT STRUCTURE. Any waterfront structure covered in whole or in part by a roof. COVERED WATERFRONT STRUCTURE BUILDING AREA. The area lying directly beneath the portion of a structure covered by a roof. SUBSTRUCTURE. That portion of the construction of a dock, pier, wharf or other similar waterfront structure below and including the deck. SUPERSTRUCTURE. That portion of the construction of a dock, pier, wharf or other similar waterfront structure above the deck. s:\dsg\forms_all_dsg\form2000\building\icodes\i ibc adoption and amendments.doc Page 4 of 5 7/1/2004

5 Section Construction Requirements. Waterfront structures shall comply with Sections through Section Substructure. The substructure may be constructed of any materials allowed by this code. All decks shall sustain, within the limitations of this code, all dead loads plus a live load of not less than 100 pounds per square foot, assumed to act vertically. In addition to the live load requirement, all structures and every portion thereof shall be designed and constructed to resist a horizontal force of not less than 100 pounds per lineal foot acting at the deck line, in any direction. Exception: For waterfront structures serving only a single dwelling, a live load of 40 psf may be used and a horizontal force need only be considered where applicable. Section Superstructure. The superstructure shall be designed and constructed to sustain all dead loads, live loads, and wind loads required by this code, and shall be constructed of any materials allowed by this code, except when the building area of a covered waterfront structure exceeds 1,000 square feet the entire superstructure and deck shall be constructed of noncombustible materials or as required for Type IV-HT Construction per IBC Section Section Hardware. All hardware used structurally shall be of a corrosive-resistant metal such as aluminum, brass, copper, and stainless steel, or be completely protected by a coating of approved paint or corrosiveresistant metal, such as zinc. K. IBC Appendix H, Section H101.3, Added Signs, General, Conflict with Mercer Island City Code. Appendix H, Section H101.3 of the International Building Code is hereby added to read as Section H101.3, Conflict with Mercer Island City Code. If any provisions of IBC Appendix H are in conflict with any provisions of the Mercer Island City Code, the applicable provisions of the Mercer Island City Code shall govern. s:\dsg\forms_all_dsg\form2000\building\icodes\i ibc adoption and amendments.doc Page 5 of 5 7/1/2004

Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION

Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION Sections: 4-16-01 PURPOSE 4-16-02 APPLICABLE AREA 4-16-03 CONSTRUCTION AND OCCUPANCY 4-16-04 UPPER BUILDING AREA, HEIGHT, NUMBER OF STORIES

More information

APPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO:

APPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO: COUNTY OF KAUAI BUILDING DIVISION, DEPARTMENT OF PUBLIC WORKS 4444 RICE STREET, SUITE 175, LIHUE, HAWAII 96766 Telephone: (808) 241-6655 Fax Number: (808) 241-6806 BUILDING CODE COMMERCIAL CHECKLIST APPLICATION

More information

Applying the Building Code During Design

Applying the Building Code During Design Applying the Building Code During Design A Step-By-Step Process AIA Learning Units The Salt Lake City CSI Chapter is a Registered Provider with The American Institute of Architects Continuing Education

More information

City of Tacoma Planning and Development Services

City of Tacoma Planning and Development Services City of Tacoma Planning and Development Services ORDINANCE NO. 28155 Adopt and Amend the City s Building Code; amending Title 2 of the Tacoma Municipal Code, implement the 2012 International Building,

More information

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures

CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person

More information

TOWN OF DEWITT PLANNING AND ZONING PERMIT REQUIREMENTS FOR DECKS

TOWN OF DEWITT PLANNING AND ZONING PERMIT REQUIREMENTS FOR DECKS TOWN OF DEWITT PLANNING AND ZONING PERMIT REQUIREMENTS FOR DECKS 1) Copy of survey within ten years showing all structures, property lines and deck location drawn to scale. SURVEYS REDUCED IN SIZE ARE

More information

TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:

TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit: TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION 355-7575 Ext. 395 Needed to Obtain Permit: 1. Building Permit Application, and/or residential plumbing permit application, as applicable, to be

More information

PRESCRIPTIVE COMPLIANCE METHOD

PRESCRIPTIVE COMPLIANCE METHOD CHAPTER 3 PRESCRIPTIVE COMPLIANCE METHOD [B] SECTION 301 GENERAL 301.1 Scope. The provisions of this chapter shall control the alteration, repair, addition and change of occupancy of existing structures,

More information

EXETER TOWNSHIP HOOD AND DUCT SYSTEMS FOR COMMERCIAL KITCHENS

EXETER TOWNSHIP HOOD AND DUCT SYSTEMS FOR COMMERCIAL KITCHENS HOOD AND DUCT SYSTEMS FOR COMMERCIAL KITCHENS POLICY STATEMENT This policy applies to NEW Hood and Duct systems. The Authority Having Jurisdiction will not waive major criteria in the applicable standards

More information

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) 2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of Project: Address:

More information

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings

ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings Building Safety Department 400-2 nd Street South St. Cloud, MN 56301 (320) 255-7239 A building permit is required for any accessory

More information

Flotation Docking Systems, Inc.

Flotation Docking Systems, Inc. GENERAL SPECIFICATIONS The following data outlines the design calculations and specifications around which Flotation Docking Systems, Inc. products are constructed. The use of such information for contract

More information

FS , 712, 713, 714

FS , 712, 713, 714 VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL JUNE 28-29, 2012 PUBLIC COMMENTS CTC Code Change Proposal FS50-12 was Approved as Modified as shown below - No public comments for the Group

More information

Administrative Changes

Administrative Changes Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings

More information

Project Address: Name of Person Completing Form:

Project Address: Name of Person Completing Form: Statement of Inspections This form is provided as a way to list aspects of the project that require special inspection and testing in accordance with IBC Sections 107.1, 1704, and 1705 and define duties

More information

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3145 Reissued 02/2017 This report is subject to renewal 02/2018. DIVISION: 05 00 00 METALS SECTION:

More information

Individual Truss Marking Is it a Building Code Requirement?

Individual Truss Marking Is it a Building Code Requirement? Introduction: Individual Truss Marking Is it a Building Code Requirement? Released April 1, 2010 On January 1, 2008, the 2007 edition of the California Building Code (CBC) 1 was adopted for use and replaced

More information

Residential Building Inspections

Residential Building Inspections Residential Building Inspections Foundations, Grade Beams, Pile Caps, Foundation Pads 1. All trenches or excavations and formwork shall be in accordance with the size(s) and configuration(s) as per approved

More information

The Building Codes A.R.E. Building Design and Construction Exam Prep

The Building Codes A.R.E. Building Design and Construction Exam Prep Know Thy Codes! The Building Codes Building Codes The Code of Hammurabi 4000bc Developed 19 th and 20 th c. Codes define what you can and can t do Allowable area and height based on degree of danger Fire

More information

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION CHAPTER 26 PLASTIC SECTION BC 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic

More information

Commercial Remodel Permit

Commercial Remodel Permit Commercial Remodel Permit Zoning requirements Staff recommends always verifying the zoning requirements for your project before deciding to build. Warrensburg has eleven separate zoning districts, each

More information

PRESCRIPTIVE COMPLIANCE METHOD

PRESCRIPTIVE COMPLIANCE METHOD CHAPTER PRESCRIPTIVE COMPLIANCE METHOD 3 SECTION 301 GENERAL 301.2 Building materials. Building materials shall comply with the requirements of this section. 301.2.1 Existing materials. Materials already

More information

2009 IBC Section 1024 Approved Luminous Egress Path Markings

2009 IBC Section 1024 Approved Luminous Egress Path Markings 2009 IBC Section 1024 Approved Luminous Egress Path Markings Where Required Buildings of Groups A (Assembly), B (Business), E (Education), I (Institutional), M (Mercantile) and R-1 (Residential transient

More information

General Residential Code Requirements

General Residential Code Requirements Residential building code review will be based on compliance with the requirements of the Louisiana State Uniform Construction code in accordance with ACT 12 of the 2005 First Extraordinary Session of

More information

LINCOLN COUNTY REQUIRED INSPECTIONS (Last updated August 23, 2017)

LINCOLN COUNTY REQUIRED INSPECTIONS (Last updated August 23, 2017) LINCOLN COUNTY REQUIRED INSPECTIONS (Last updated August 23, 2017) It is the responsibility of the permit applicant to notify the building inspector when the work is ready for inspection. To request an

More information

Special Inspections for Wood Construction BCD710 Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council

Special Inspections for Wood Construction BCD710 Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council Special Inspections for Wood Construction BCD710 Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council Copyright Materials This presentation is protected by US and International

More information

BUILDING CODES & DESIGN CRITERIA

BUILDING CODES & DESIGN CRITERIA BUILDING CODES & DESIGN CRITERIA Adopted Building Codes: 2006 International Building Code (IBC) 2006 International Residential Code (IRC) 2006 International Mechanical Code (IMC) 2006 International Plumbing

More information

City of Des Moines. Permit and Development Center 602 Robert D Ray Drive Des Moines, IA Phone: Fax:

City of Des Moines. Permit and Development Center 602 Robert D Ray Drive Des Moines, IA Phone: Fax: City of Des Moines Permit and Development Center 602 Robert D Ray Drive Des Moines, IA 50309 Phone: 515-283-4200 Fax: 515-283-4270 This Code Analysis Form must be completed and returned with the Building

More information

RESIDENTIAL DETACHED STORAGE STRUCTURES (GARAGE)

RESIDENTIAL DETACHED STORAGE STRUCTURES (GARAGE) City Of Austin 500 Fourth Avenue N.E. Austin, Minnesota 55912-3773 Building Department 507-437-9950 Fax 507-437-7101 RESIDENTIAL DETACHED STORAGE STRUCTURES (GARAGE) *A Building permit is required for

More information

Sponsored by The Boston Association of Structural Engineers and the Structural Engineers Association of Massachusetts

Sponsored by The Boston Association of Structural Engineers and the Structural Engineers Association of Massachusetts Commonwealth of Massachusetts State Building Code 780-CMR 9 th Edition Renovation of Existing Buildings Using The International Existing Building Code IEBC 2015 with Massachusetts Amendments Sponsored

More information

Georgia State Amendments to the International Residential Code for One- and Two- Family Dwellings

Georgia State Amendments to the International Residential Code for One- and Two- Family Dwellings Georgia State Amendments to the International Residential Code for One- and Two- Family Dwellings (2006 Edition) Georgia Department of Community Affairs Planning and Environmental Management Division 60

More information

City of Donnelly. Permit Application Information and Instructions

City of Donnelly. Permit Application Information and Instructions 169 Halferty Street PO Box 725 Donnelly, Idaho 83615 Phone: 208-325-8859 Fax: 208-325-4091 City of Donnelly Permit Application Information and Instructions Any questions regarding this information may

More information

CONTACT INFORMATION. PV System will require a separate Electrical Permit.

CONTACT INFORMATION. PV System will require a separate Electrical Permit. SOLAR APPLICATION P. O. Box 72 Mountlake Terrace, WA 98043 Phone 425.744.6267 Fax 425.778.6421 PermitSpecialist@ci.mlt.wa.us www.cityofmlt.com Application # Job Site Address Single-Family Residential Multi-Family

More information

FENCE PERMIT APPLICATION

FENCE PERMIT APPLICATION Department of Building, Zoning & Housing 26789 Highland Road Richmond Heights, Ohio 44143-1429 216-383-6312 Fax: 216-383-6319 richmondheightsohio.org FENCE PERMIT APPLICATION LOCATION OF JOB LOT # SUBDIVISION

More information

CARROLL COUNTY BUREAU OF PERMITS AND INSPECTIONS RESIDENTIAL CODE COMPLIANCE GUIDELINES FOR DECKS

CARROLL COUNTY BUREAU OF PERMITS AND INSPECTIONS RESIDENTIAL CODE COMPLIANCE GUIDELINES FOR DECKS CARROLL COUNTY BUREAU OF PERMITS AND INSPECTIONS RESIDENTIAL CODE COMPLIANCE GUIDELINES FOR DECKS Code Reference: Chapter 97, Code of Public Local Laws and Ordinances of Carroll County and The International

More information

Garage Construction. Permit Guide. Development Center. General Information. Zoning Ordinance Requirements. Building Code Requirements

Garage Construction. Permit Guide. Development Center. General Information. Zoning Ordinance Requirements. Building Code Requirements General Information Site Card. Before starting construction, post the site card (issued by the City) in a front window visible from the street. Miss Dig. Before you dig, call Miss Dig at 800.482.7171 This

More information

CHAPTER 26 PLASTIC SECTION 2601 SECTION 2603 GENERAL FOAM PLASTIC INSULATION

CHAPTER 26 PLASTIC SECTION 2601 SECTION 2603 GENERAL FOAM PLASTIC INSULATION CHAPTER 26 PLASTIC SECTION 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic veneer,

More information

Dave Harper, Building Official (509) Susan Davis, Administrative Secretary (509)

Dave Harper, Building Official (509) Susan Davis, Administrative Secretary (509) City of Colville Building Department The Building Department is responsible for the issuance of permits for commercial and residential construction projects within the city. This responsibility includes

More information

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1530 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 03 00

More information

GENERAL BUILDING HEIGHTS AND AREAS

GENERAL BUILDING HEIGHTS AND AREAS CHPTER GENERL BUILDING HEIGHT ND RE ECTION 0 GENERL 0. cope. The provisions of this chapter control the height and area of structures hereafter erected and additions to existing structures. [F] 0. ddress

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD Fire Water Supply without a Purveyor Residential & Commercial STANDARD #D-003 EFFECTIVE 01-04-2016 1. PURPOSE 1.1. The California Fire Code (CFC) requires

More information

R CODE CHANGE PROPOSAL FORM (See instructions on page 2)

R CODE CHANGE PROPOSAL FORM (See instructions on page 2) CODE CHANGE PROPOSAL FORM (See instructions on page 2) Code: IRC 12/13 Sections 301.2.2.2.1 Proponent: Charles S. Bajnai, Chesterfield County, VA, ICC Building Code Action Committee 1. Delete as shown

More information

Chapter UNIFORM CODES FOR CONSTRUCTION BUILDING CODE

Chapter UNIFORM CODES FOR CONSTRUCTION BUILDING CODE Chapter 23.12 UNIFORM CODES FOR CONSTRUCTION BUILDING CODE 23.12.010 Adoption of the 2010 California Building Code. Part 2. Title 24 of the California Code of Regulations. There is adopted and incorporated

More information

Code Compliance Research Report CCRR-0213

Code Compliance Research Report CCRR-0213 Code Compliance Research Report CCRR-0213 Issue Date: 08-04-2017 Renewal Date: 08-01-2018 DIVISION: 05 50 00 METAL FABRICATIONS Section: 05 52 00 Metal Railings REPORT HOLDER: Key Link Fencing & Railing,

More information

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617)

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) Code Requirements for Existing Buildings R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS) was established in 1945 and currently

More information

TENTS AND OTHER MEMBRANE STRUCTURES

TENTS AND OTHER MEMBRANE STRUCTURES CHAPTER 31 TENTS AND OTHER MEMBRANE STRUCTURES SECTION 3101 GENERAL 3101.1 Scope. Tents and membrane structures shall comply with this chapter. The provisions of Section 3103 are applicable only to temporary

More information

GENERAL BUILDING HEIGHTS AND AREAS

GENERAL BUILDING HEIGHTS AND AREAS CHPTER GENERL BUILDING HEIGHT ND RE ECTION 0 GENERL 0. cope. The provisions of this chapter control the height and area of structures hereafter erected and additions to existing structures. [F] 0. ddress

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: FCP, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: FCP, INC. 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2937 Reissued 05/2016 This report is subject to renewal 05/2018. DIVISION: 07 00 00 THERMAL

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 6587 (562) 699 0543 www.icc es.org ESR 3152 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00

More information

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2) Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction

More information

Combustible Exterior Wall Cladding Systems: An ICC Perspective

Combustible Exterior Wall Cladding Systems: An ICC Perspective Combustible Exterior Wall Cladding Systems: An ICC Perspective The tragic Grenfell Tower fire in London brought extensive public focus on combustible exterior wall systems, often called cladding, prompting

More information

CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT. Submittal Requirements

CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT. Submittal Requirements CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT 1 East Franklin Street Phone: 301-790-4163 Third Floor Hagerstown, MD 21740 Fax: 301-791-2650 BUILDING PERMIT APPLICATION FOR RESIDENTIAL ACCESSORY

More information

SECTION PLATE CONNECTED WOOD TRUSSES

SECTION PLATE CONNECTED WOOD TRUSSES SECTION 06173 PLATE CONNECTED WOOD TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Shop fabricated wood trusses for roof and floor framing. 2. Bridging, bracing, and anchorage. B. Related Sections:

More information

4. Number of drawings required: ( ) Locations of nearest streets

4. Number of drawings required: ( ) Locations of nearest streets CITY OF MANSFIELD BUREAU OF BUILDING AND CODES 30 NORTH DIAMOND STREET 3RD FLOOR MANSFIELD, OHIO 44902 Phone (419) 755-9688 Fax (419) 755-9453 www.ci.mansfield.oh.us COMMERCIAL BUILDING PLAN REQUIREMENTS

More information

Short title. This chapter may be cited as the "Kern County Building Code."

Short title. This chapter may be cited as the Kern County Building Code. Chapter 17.08 BUILDING CODE Sections: 17.08.010 Short title. 17.08.020 Applicability. 17.08.030 Uniform Building CodeBAdopted. 17.08.040 Uniform Building CodeBProvisions not adopted. 17.08.050 Uniform

More information

High Piled Combustible Storage Guideline

High Piled Combustible Storage Guideline Moreno Valley High Piled Combustible Storage Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 5, 2017 Rev: 7-28-16 City of Moreno Valley Fire Department Page 1 of 19 High Piled Storage

More information

ATI Evaluation Service A Division of Architectural Testing Certification Services

ATI Evaluation Service A Division of Architectural Testing Certification Services ATI Evaluation Service A Division of Architectural Testing Certification Services Subject to Renewal: 08/09/2014 Issued: 08/09/2013 Visit www.ati-es.com for current status Revised: 08/12/2013 Page 1 of

More information

E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e

E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e I N D E X E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e Title Course Number *Seminar Length (days) Pg. Class Scheduling Policies 8 International Building Code

More information

SECTION : FIRE WALL AND FIRE SUPPRESSION REGULATIONS FOR R1-Z, R-2, R-3 ZONING AND PDD CATEGORIES

SECTION : FIRE WALL AND FIRE SUPPRESSION REGULATIONS FOR R1-Z, R-2, R-3 ZONING AND PDD CATEGORIES SECTION 500.110: FIRE WALL AND FIRE SUPPRESSION REGULATIONS FOR R1-Z, R-2, R-3 ZONING AND PDD CATEGORIES A. Purpose. The intent of this regulation is to amend the current adopted edition of the International

More information

Showing Only Sections Changed 6 th Edition FBC (2017) from 5 th Edition FBC (2015) [changes shown with underline and strike-through]

Showing Only Sections Changed 6 th Edition FBC (2017) from 5 th Edition FBC (2015) [changes shown with underline and strike-through] Showing Only Sections Changed 6 th Edition FBC (2017) from 5 th Edition FBC (2015) [changes shown with underline and strike-through] This publication reproduces excerpts from the Florida Building Code,

More information

RESIDENTIAL CONSTRUCTION New Dwellings and Additions

RESIDENTIAL CONSTRUCTION New Dwellings and Additions How to Obtain a Building Permit For RESIDENTIAL CONSTRUCTION New Dwellings and Additions MIAMI COUNTY, KANSAS CODE SERVICES DEPARTMENT 201 South Pearl Street, Suite 201 Paola, Kansas 66071-1777 Phone:

More information

Comparison of the life safety elements of the 1997 UBC and the IBC 2000.

Comparison of the life safety elements of the 1997 UBC and the IBC 2000. Comparison of the life safety elements of the 1997 UBC and the IBC 2000. Introduction The Building Performance Research Institute s mission is primarily one of education on building safety and performance.

More information

Building Codes and Ordinances ARC 227

Building Codes and Ordinances ARC 227 Building Codes and Ordinances ARC 227 Week 6 Fire Resistive Construction 03.02.10 Instructor: Rick Staub, AIA Email: staub@pointonearchitects.com Phone: 860-434-7707 Fire Resistive Construction Passive

More information

CHAPTER 6 TYPES OF CONSTRUCTION

CHAPTER 6 TYPES OF CONSTRUCTION CHAPTER 6 TYPES OF CONSTRUCTION SECTION 61 GENERAL 61.1 Scope. The provisions of this chapter shall control the classification of buildings as to type of construction. SECTION 62 CONSTRUCTION CLASSIFICATION

More information

CITY OF ST. PETERSBURG PLANNING & ECONOMIC DEVELOPMENT DEPT

CITY OF ST. PETERSBURG PLANNING & ECONOMIC DEVELOPMENT DEPT CITY OF ST. PETERSBURG PLANNING & ECONOMIC DEVELOPMENT DEPT 2016 Residential LDR Update DETAILED AGENDA Workshop #1 March 08, 2016 Main Library 3745 9 th Ave N; 6 PM-8 PM 1. Introduction (15 minutes) Overview

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3340 Reissued 05/2017 This report is subject to renewal 05/2018. DIVISION: 07 00 00 THERMAL

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1780 Reissued 11/2017 This report is subject to renewal 11/2019. DIVISION: 06 00

More information

CHAPTER 13 R-5 MANUFACTURED MOBILE HOME PARK RESIDENTIAL DISTRICT

CHAPTER 13 R-5 MANUFACTURED MOBILE HOME PARK RESIDENTIAL DISTRICT 15.1300 CHAPTER 13 R-5 MANUFACTURED MOBILE HOME PARK RESIDENTIAL DISTRICT 15.1301 SECTION 13.01 STATEMENT OF PURPOSE To provide for manufactured home park development, of long-term duration of stay, in

More information

2015 Special Design Provisions for Wind and Seismic Philip Line, P.E., John Buddy Showalter, P.E., Michelle Kam-Biron, P.E., S.E., Jason Smart, P.E.

2015 Special Design Provisions for Wind and Seismic Philip Line, P.E., John Buddy Showalter, P.E., Michelle Kam-Biron, P.E., S.E., Jason Smart, P.E. 2015 Special Design Provisions for Wind and Seismic Philip Line, P.E., John Buddy Showalter, P.E., Michelle Kam-Biron, P.E., S.E., Jason Smart, P.E. The 2015 Edition of Special Design Provisions for Wind

More information

Neighborhood Suburban Single-Family District Regulations City of St. Petersburg City Code Chapter 16, Land Development Regulations

Neighborhood Suburban Single-Family District Regulations City of St. Petersburg City Code Chapter 16, Land Development Regulations Section 16.20.020 - Neighborhood Suburban Single-Family Districts ( NS ) Sections: Typical Block in a Neighborhood Suburban District 16.20.020.1 History and Composition of Suburban Neighborhoods 16.20.020.2

More information

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS SECTION 08 32 20 CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

NEW HAMPSHIRE CODE OF ADMINISTRATIVE RULES

NEW HAMPSHIRE CODE OF ADMINISTRATIVE RULES CHAPTER Puc 1800 ADMINISTRATION OF NEW HAMPSHIRE CODE FOR ENERGY CONSERVATION IN NEW BUILDING CONSTRUCTION PART Puc 1801 DEFINITIONS Puc 1801.01 Applicant means the general contractor, builder, owner or

More information

HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW

HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW 27 September 2007 prepared by: J. CHRIS EVANS ARCHITECT 3220 E. Terra Alta Blvd. No. 9 Tucson, Arizona 85716 520.319.8835 evansarch@hotmail.com

More information

Quality Control and Quality Assurance for Installation of Steel Deck

Quality Control and Quality Assurance for Installation of Steel Deck s American National standards institute/ steel deck institute QA/QC - 2011 Standard for Quality Control and Quality Assurance for Installation of Steel Deck copyright 2012 steel deck institute 1. General

More information

Fire Inspection and Code Enforcement, 7 th Edition. Chapter 6 Building Construction: Components Inspector II

Fire Inspection and Code Enforcement, 7 th Edition. Chapter 6 Building Construction: Components Inspector II Fire Inspection and Code Enforcement, 7 th Edition Chapter 6 Building Construction: Components Today we will Discuss fire walls, party walls, fire partitions, and curtain walls Discuss roof types and coverings

More information

Joint Evaluation Report ICC-ES (800) (562)

Joint Evaluation Report ICC-ES (800) (562) 0 Joint Evaluation Report ICC-ES (800) -658 (56) 699-05 www.icc-es.org 000 ESR-0 Reissued 0/0 This report is subject to renewal 0/08. DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION: 06 6 00 SHEATHING

More information

Work Group Item Stairways serving an occupant load of less than 50 shall have a width of not less than 36 inches (914 mm).

Work Group Item Stairways serving an occupant load of less than 50 shall have a width of not less than 36 inches (914 mm). IBC-12/13 1009.1, 1009.4, 1009.7.2, 1009.7.4, 1009.8, 1009.10, 1009.15 (IFC [B] 1009.1, 1009.4, 1009.7.2, 1009.7.4, 1009.8, 1009.10, 1009.15) Proponent: S. Bajnai, Chesterfield County, VA, ICC Building

More information

2015 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2015 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs Class Outline Inspection of Fire-Resistance-Rated Floors, Ceilings and Roofs Based on 2015 International Building Code, (IBC ) Introduction Determining fire resistance Test standards Definitions Alternate

More information

10/23/2011. Plan Examination. Plan ExaminationPurpose. Catch problems in advance of construction.

10/23/2011. Plan Examination. Plan ExaminationPurpose. Catch problems in advance of construction. Plan Examination 1 Plan ExaminationPurpose 2 Catch problems in advance of construction. 3 1 Discovery of problems in the field results in higher cost. 4 Can a good plan review eliminate all problems in

More information

CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1%

CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1% CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE EXAM ID: I1 80 multiple-choice questions 3-1/2-hour time limit Open book 01. GENERAL ADMINISTRATION 6% 0101. Project Administration 1% Verify that

More information

1. Frozen food warehouses used solely for storage of Class I and II commodities where protected by an approved automatic sprinkler system.

1. Frozen food warehouses used solely for storage of Class I and II commodities where protected by an approved automatic sprinkler system. Draft curtains are typically used in warehouses, aircraft hangars and large industrial plants to contain or channel smoke that rises to the ceiling in a fire. They can keep the smoke from rolling across

More information

TOWN OF SOUTH KINGSTOWN REQUIREMENTS FOR BUILDING PERMITS RESIDENTIAL SINGLE FAMILY

TOWN OF SOUTH KINGSTOWN REQUIREMENTS FOR BUILDING PERMITS RESIDENTIAL SINGLE FAMILY TOWN OF SOUTH KINGSTOWN REQUIREMENTS FOR BUILDING PERMITS RESIDENTIAL SINGLE FAMILY ACCESSORY STRUCTURES (Barn, Garage, Shed) ********************************* BUILDING PERMIT APPLICATIONS FOR ACCESSORY

More information

FIRE AND SMOKE PROTECTION FEATURES

FIRE AND SMOKE PROTECTION FEATURES CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated

More information

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617)

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) Code Requirements for Existing Buildings R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS) was established in 1945 and currently

More information

The following are details of the code requirements of the 2015 International Residential Code for single-story decks.

The following are details of the code requirements of the 2015 International Residential Code for single-story decks. The following are details of the code requirements of the 2015 International Residential Code for single-story decks. The 2015 International Residential Code Section R507 contains additional information

More information

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2787 Reissued 05/2017 This report is subject to renewal 05/2019. DIVISION: 03 00

More information

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2012 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs Class Outline Inspection of Fire-resistance-Rated Floors, Ceilings and Roofs Based on 2012 International Building Code (IBC) Introduction Determining fire resistance Test standards Definitions Alternate

More information

RESIDENTIAL BUILDING PLAN REQUIREMENTS

RESIDENTIAL BUILDING PLAN REQUIREMENTS CITY OF MANSFIELD BUREAU OF BUILDING AND CODES 30 NORTH DIAMOND STREET 3RD FLOOR MANSFIELD, OHIO 44902 Phone (419) 755-9688 Fax (419) 755-9453 www.ci.mansfield.oh.us RESIDENTIAL BUILDING PLAN REQUIREMENTS

More information

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products.

SECTION ORNAMENTAL ALUMINUM RAILING. ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products. SECTION 05720 ORNAMENTAL ALUMINUM RAILING ** NOTE TO SPECIFIER ** Superior Aluminum Products, Inc.; Ornamental aluminum railing products. This section is based on the products of Superior Aluminum Products,

More information

RESIDENTIAL BUILDING REQUIREMENTS

RESIDENTIAL BUILDING REQUIREMENTS RESIDENTIAL BUILDING REQUIREMENTS Residential Building Requirements This is an informational booklet with some of the general residential construction requirements taken from the codes adopted by Campbell

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

TENTS AND MEMBRANE STRUCTURES

TENTS AND MEMBRANE STRUCTURES CHAPTER 24 TENTS AND MEMBRANE STRUCTURES SECTION 2401 GENERAL 2401.1 Scope. Tents and membrane structures shall comply with this chapter. The provisions of Section 2403 are applicable only to temporary

More information

Commercial Tax Abatement

Commercial Tax Abatement A confirmation letter is issued by the City upon receipt of this application. This application is not effective and not considered filed until the confirmation letter has been issued. Filing does not assure

More information

Ordinance No July 1, 2016

Ordinance No July 1, 2016 (Insert Facing Page 3 IRC) 2.02.540 Amendment to IRC Section R105.2 Work Exempt From Permit, Building and Electrical Sections. The following additional exception shall be added to R105.2 Building: Building:

More information

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures.

SECTION A. ACSE 7 Minimum Loads for Buildings and other Structures. SECTION 06 12 00 STRUCTURAL INSULATED PANELS ------------------------------------------------------------------------------------------------------------ PART 1- GENERAL ----------------------------- 1.1

More information

CITY OF MERCER ISLAND

CITY OF MERCER ISLAND CITY OF MERCER ISLAND DEVELOPMENT SERVICES GROUP 9611 SE 36TH STREET MERCER ISLAND, WA 98040 PHONE: 206.275.7605 www.mercergov.org Inspection Requests: Online: www.mybuildingpermits.com VM: 206.275.7730

More information

Structural vs Nonstructural Members. Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures

Structural vs Nonstructural Members. Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures Structural vs Nonstructural Members Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures Behavior of Cold-Formed Steel Members STEEL DESIGN SPECIFICATIONS Type of steel Specification

More information

Received by:* Date Received:* Zoning Approval:* Date:* PERMIT#:* *ZONING: *SETBACKS: FRONT ft/ SIDE ft/ REAR ft *FLOOD ZONE:

Received by:* Date Received:* Zoning Approval:* Date:* PERMIT#:* *ZONING: *SETBACKS: FRONT ft/ SIDE ft/ REAR ft *FLOOD ZONE: HENDRY COUNTY BUILDING, LICENSING & CODE ENFORCEMENT POST OFFICE BOX 2340 * 640 SOUTH MAIN STREET * LABELLE, FLORIDA 33975 * (863) 675-5245 * FAX: (863) 674-4194 1100 OLYMPIA ST CLEWISTON, FLORIDA 33440

More information

LP OSB Sheathing & Structural 1 Sheathing

LP OSB Sheathing & Structural 1 Sheathing Rated OSB Sheathing Roof Panels Span Ratings Max. Live Load Thickness Span Rating for Roofs (lbs)** 3/8" 24/0 30 7/16" 24/16 40 15/32" 32/16 70 1/2" 32/16 70 19/32" 40/20 130 23/32" 48/24 175 1-1/8" 48

More information

PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION

PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION Permit No. 175 Beaver Drive, P.O. Box 486 DuBois, PA 15801 Phone: 814-375-1111 Fax: 814-375-1117 Toll Free: 855-PENNSAF LOCATION OF PROPOSED

More information