TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS

Size: px
Start display at page:

Download "TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS"

Transcription

1 TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 11

2 TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS 1.0 Scope : The specification covers the manufacture, testing at works supply and delivery of procelain Insulators for overhead power lines with a nominal voltage below 1000 volts. Nothe pin and shackles type insulators are covered. 2.0 Climatic conditions : The insulators specified herein shall be suitable for outdoor use under the following climate conditions. 2.1 Maximum ambient temperature (Degree C) Maximum temperature in shade (Degree C) Minimum temperature of Air in shade (Degree C) Relative Humidity (Percent) to Maximum annual rain fall (mm) Maximum wind pressure (kg/sq.m) Maximum altitude above mean seal level (meter) Isoceranic level (days per year) Seismic level (Horizontal Acceleration) g 1.10 Moderately hot and humid tropical climate Conductive to trust and fungus growth 3.0 System : 3.1 The insulators will be installed be installed on three phase 433 volts. AC & 50 HZ system in which the neutral is effectively grounded. The insulators shall be designed to work continuously at a voltage. 10% in excess of the normal rated voltage. 4.0 Design Specification : 4.1 The insulators shall confirm to provisions under IS : or its latest version in all respects. The dimensions of the insulators are as per Drawing No The Pin insulators shall be threaded to take mild steel pin of dimensions given below : SEAL & SIGNATURE OF THE TENDERER PAGE 2 OF 11

3 Pin Insulator Type - 1 Suitable for Head Shank Steel Threads as per profile of threads as insulators as given in Fig.5 of IS : 1445/1977 Dia. 16 mm Remarks Pin Insulators threads as per profile given in Fig.5/1445/ The design of the insulators shall be such that stress due to expansion and contraction in any Part of the insulators shall not lead to its deterioration. 4.3 The insulators shall be suitable for use with all Aluminium Conductor or copper conductor or ACSR up to 100 mm sq. The insulators should withstand the conductor tension the reversible wind lead as well as the high frequency vibrations set due to wind. 5.0 Insulation Characteristics : 5.1 The insulators shall have the electrical and mechanical characteristic given in the table below : Type of Insulators Power frequency flashover Voltage in KV (RMS One minute power frequency with stand voltage in KV (RMS) Power frequency puncture withstand voltage KV (RMS Dry Wet Dry Wet Pin x the actual flashover voltage Minimum failing load kg Shackle (Type Type - 2) 6.0 General Requirements : 6.1 The porcelain used in the manufacture shall be sound free from defects, thoroughly vitrified and smoothly glazed. 6.2 The glaze on the insulators shall generally to White/Cream Brown except for the screw threads and the parts on which the porcelain is supported during fittings, which may be left unglazed, all other surfaces of the insulators shall be efficiently glazed. 6.3 The insulators shall be in one piece. The pin type shall a top groove and shall have dimensions as shown in the drawing. 6.4 The insulators shall be marked properly in accordance with clause 6 of ISS : SEAL & SIGNATURE OF THE TENDERER PAGE 3 OF 11

4 7.0 Testing facilities : The tenderer must clearly indicate what testing facilities are available in the works of the manufacturer and whether the facilities are adequate to carry out all the routine as well as type tests. These facilities should be made available to Board s Engineers if deputed to carry out or witness should be made any tests cannot be carried out at the manufacturers works, the reasons should be clearly stated in the tender. 8.0 Tests : The insulators shall be tested in accordance with the procedures detailed in IS : 1445/1977 which are reproduced below : 8.1 Routine Tests : 8.2 Type Tests : Type tests shall be made on the insulators that has passed the routine tests. For requirements of insulators up to 2000 no. One insulators shall be selected for the type test mentioned below. However, maximum no. of insulators to be tested in the lot shall be limited to twenty to twenty numbers only. a) Dry one minute power frequency À Withstand test & dry flash over test À As per IS: 1445/1977 b) Wet one minute power frequency À withstand and wet flash over test À As per IS : 1445/ Acceptance tests : The number of insulators for the acceptance tests mentioned below shall be selected at random from the lot in accordance with the table below : Lot size Sample size of Insulators Up to to to to to above The insulators, after having withstand the routine test shall be subjected to the following tests in the order given below : SEAL & SIGNATURE OF THE TENDERER PAGE 4 OF 11

5 a) Verification of dimensions À b) Temperature cycle test À As per IS : 1445 c) Mechanical failing load test À d) Power frequency puncture withstand test À e) Porosity test À The insulators selected in accordance with 8.3 shall be up to two equal parts and subjected to the tests indicated. Tests Part of sample a) & b) Both Parts c) & e) First Part d) Second Part 9.0 Rejection : 9.1 Criteria of conforming and Rejection : If only one insulators fails to comply with any one of the tests given in (a) to (b) a fresh quantity equal to twice the first quantity shall be subjected to retesting. The retesting shall comprise the test in which the failure occurred preceded by house, test which may be considered to have influenced the results of the original tests if no failure occurs, the lot shall be accepted. 9.2 It two or more insulators fail to comply with any sample tests given in (a) to (d) or if any failure occurs on insulators subjected to retesting described in 8.2, the complete lot shall be withdrawn for further examination by the manufacturer after which the lot of any part thereof may be resubmitted for tests. 9.3 The number then selected shall be three times the first quantity chosen for tests. This testing shall comprise the test in which the failure occurred proceeded by those test which may be considered to have influenced the results of the original test. If failure occurs the last lot shall be rejected. Insulators which do not conform to the requirements of 8.1 and 8.2 shall be rejected Test Certificates : 10.1 Along with the tender, the tenderer shall submit the test certificate for all routine, type and sample tests specified above If required, the board shall subject the consignment of insulators supplied to the aforementioned test. The testing under this clause will be carried out in any laboratory including boards own laboratory. Notice of such tests will be given by the Board to the supplier by ordinary post. However, the date of testing will not be postponed or altered at the request of the supplier. The supplier is at liberty to be present during this test. SEAL & SIGNATURE OF THE TENDERER PAGE 5 OF 11

6 11. Marking : As per IS : 1445/ Packing: All insulators shall be packed in suitable double gunny bags and shall be transported by road. 13. Inspection : The Board may be depute an Engineer to witness the routine and sample tests at their manufacturers works for which advance intimation shall be given the manufacturers whenever a lot is ready for dispatch. 14. Schedule : The tenderer shall fill in the following schedule which is part and parcel of the tender specification and offer. If the schedules are not submitted duly filled in with the offer, the offer shall be liable for rejection. Schedule A - Guaranteed technical particulars Schedule B - Schedule of deviation Schedule C - Tenderer s experience Schedule D - Schedule of deviation form Specification standards Schedule E - Deviation from specified test Requirements. Unless otherwise brought out separately by the tenderer in the schedule of deviations (Schedule B, D & E ) for this item offered shall be deemed to confirm to the specification scrupulously. All deviations from the specification shall be brought out in the Schedules of deviation (Schedule B, D & E ). The discrepancies between the specification and the catalog or literature submitted as part of the offer shall not be considered as valid deviation unless specifically brought out in the schedule of deviation as stated above. SEAL & SIGNATURE OF THE TENDERER PAGE 6 OF 11

7 SCHEDULE A GURANTEED TECHNICAL PARTICULARS The guaranteed technical particulars as given below shall be furnished. 1. TYPE OF INSULATORS: 2. APPLICABLE IS ; 3. SYSTEM VOLTAGE AND FREQUENCY 4. CONFIRMATION TO DRAWING NO: POWER FREQUENCY FLASHOVER VOLTAGE (DRY) 6. POWER FREQUNCY FLASHOVER VOLTAGE (WET) 7. ONE MINUTE POWER FREQUENCY WITHSTAND VOLTAGE (RMS (DRY) 8. POWER FREQUENCY WITHSTAND VOLTAGE (RMS) (WET) 9. POWER FREQUENCY PUNCTURE WITHSTAND AND VOLTAGE 10. MINIMUM FAILING LOAD 11. TYPE TEST REPORTS ENCLOSED : YES OR NOT. 12. PACKING 13. NET WEIGHT OF ONE INSULATORS SEAL & SIGNATURE OF THE TENDERER PAGE 7 OF 11

8 SCHEDULE - B SCHEDULE OF DEVIATIONS FROM SPECIFICATION SR.NO. CLAUSE NO. DETAILS OF DEVIATION NAME OF FIRM NAME & SIGNATURE OF THE TENDERER DESIGNATION DATE SEAL & SIGNATURE OF THE TENDERER PAGE 8 OF 11

9 SCHEDULE C SCHEDULE OF TENDERER S EXPERIENCE Tenderer shall furnish here a list of similar orders executed/under execution by him to whom a reference may be made by Purchaser in case in considers such & reference necessary. Sr.No Name of Client & Description order Value of Order Period of supply & commissioning Name & address to whom reference may be made NAME OF FIRM NAME & SIGNATURE OF TENDERER DESIGNATION DATE SEAL & SIGNATURE OF THE TENDERER PAGE 9 OF 11

10 SCHEDULE D SCHEDULE OF DEVIATIONS FROM SPECIFIED STANDARDS SR. Particulars Stipulation of Specified Standards Standard Ref. Stipulation Stipulation of standard adopted by terderers Standard Stipulation Ref. Remarks NAME OF FIRM NAME & SIGNATURE OF TENDERER DESIGNATION DATE SEAL & SIGNATURE OF THE TENDERER PAGE 10 OF 11

11 SCHEDULE E DEVIATION FROM SPECIFIED TEST REQUIREMENTS SPECIFIED IN RELEVANT AND PRESENT SPECIFICATIONS Sr. No. Name of Test Standard No. & Clause No. Requirement of Standard Proposed deviation Reasons for deviation NAME OF FIRM NAME & SIGNATURE OF TENDERER DESIGNATION DATE SEAL & SIGNATURE OF THE TENDERER PAGE 11 OF 11

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 14 TECHNICAL SPECIFICATION FOR LT XLPE POWER CABLES (SPECIFICATION NO.MM/I/LTXLPE/2006) 1. SCOPE: The specification

More information

ANNEXURE - ' D ' TECHNICAL SPECIFICATION FOR INSULATOR PINS ( PINS FOR 11,22 AND 33 kv INSULATORS )

ANNEXURE - ' D ' TECHNICAL SPECIFICATION FOR INSULATOR PINS ( PINS FOR 11,22 AND 33 kv INSULATORS ) ANNEXURE - ' D ' TECHNICAL SPECIFICATION FOR INSULATOR PINS ( PINS FOR 11,22 AND 33 kv INSULATORS ) SPECIFICATION NO:DIST/MM/I/G.I. PINS -2006) INDEX ------------------------------------------------------------------------------------------------------------

More information

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - 1. SCOPE: - This specification covers 11KV Disc Type & 11KV/ 22KV Pin Type Insulators for 11/22KV H.T. over head power lines. 2. APPLICABLE

More information

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/LTPVC & CONTROL/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION

More information

TECHNICAL SPECIFICATION FOR CONDUCTORS

TECHNICAL SPECIFICATION FOR CONDUCTORS TECHNICAL SPECIFICATION FOR CONDUCTORS SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 9 TECHNICAL SPECIFICATION FOR CONDUCTORS SPECIFYING TECHNICAL PARAMETERS OF THE CONDUCTOR SPECIFICATION NO. RE/ II/ ACSR

More information

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA 094: 2000 CEB STANDARD MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEB Standard

More information

TURKISH ELECTRICITY DISTRIBUTION CO. TECHNICAL SPECIFICATION FOR POST (SUPPORT) INSULATORS FOR MEDIUM VOLTAGE SYSTEMS

TURKISH ELECTRICITY DISTRIBUTION CO. TECHNICAL SPECIFICATION FOR POST (SUPPORT) INSULATORS FOR MEDIUM VOLTAGE SYSTEMS TURKISH ELECTRICITY DISTRIBUTION CO. TECHNICAL SPECIFICATION FOR POST (SUPPORT) INSULATORS FOR MEDIUM VOLTAGE SYSTEMS CONSULTANT: ELTEM-TEK ELECTRICAL INSTALLATIONS ENGINEERING SERVICES AND TRADE CO. JUNE,

More information

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA 9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA Technical specification for 9KV/18KV 5KA Metal oxide Lightning Arrestors without Gap. ----------------------------------------------------------------------------------------------------------------

More information

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEB SPECIFICATION 005-1: 2012 P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS PAGE 1. Scope 03

More information

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS Insulators & Lightening Arrestor GROUP K & L

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS Insulators & Lightening Arrestor GROUP K & L TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS Insulators & Lightening Arrestor GROUP K & L GROUP C Insulator Sl. No. Item Description Unit Qty. 1 11 KV Pin Insulator No 7488 2 11 KV Disc Insulator 45KN

More information

TECHNICAL SPECIFICATION FOR 11 POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC INSULATORS.

TECHNICAL SPECIFICATION FOR 11 POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC INSULATORS. Vidyut Bhavan( 4th Floor),Bidhannagar, Block-DJ Sector-II Kolkata-700 091 Phone No.033-2359-8397 Fax No.033-2359-1921 TECHNICAL SPECIFICATION FOR 11 POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11

More information

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION GETCO/E/TS-C&C

More information

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 REVISION NO. 0 NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 PAGE NO. 1 OF 24 DATE OF ISSUE (MONTH/YEAR) TOTAL NO. OF PAGES (Including cover

More information

SEAL & SIGNATURE OF THE TENDERER

SEAL & SIGNATURE OF THE TENDERER MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. LTD. SCHEDULE - `A' TECHNICAL SPECIFICATION FOR 11 kv & 22 kv A.B. SWITCH. SPECIFICATION NO:RE/II/A.B.SWITCH/2005 INDEX -----------------------------------------------------------------------------------------------------------------------

More information

SECTION 07 TECHNICAL SPECIFICATIONS 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO) GAPLESS LIGHTNING ARRESTER (LA)

SECTION 07 TECHNICAL SPECIFICATIONS 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO) GAPLESS LIGHTNING ARRESTER (LA) SECTION 07 TECHNICAL SPECIFICATIONS OF 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO) GAPLESS LIGHTNING ARRESTER (LA) 7.0 TECHNICAL SPECIFICATIONS OF 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO)

More information

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION GETCO/E/TS C&C057/R0 DT.

More information

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION

TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION GETCO/E/TS C&C057/R0 DT.

More information

P.V.C. INSULATED UNARMOURED COPPER CABLES

P.V.C. INSULATED UNARMOURED COPPER CABLES 083 : 2007 CEB SPECIFICATION P.V.C. INSULATED UNARMOURED COPPER CABLES CEYLON ELECTRICITY BOARD SRI LANKA Specification for P.V.C. INSULATED UNARMOURED COPPER CABLES CEB Specification 083 : 2007 CEYLON

More information

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008 Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4

More information

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220, 132 & 66 COMPOSITE SOLIDCORE STATION POST INSULATORS GETCO/E/2,1,6

More information

General Requirements. Technical Specifications for Insulators of Transmission Lines

General Requirements. Technical Specifications for Insulators of Transmission Lines Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Insulators of Transmission

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS DEVKON KIT AND HAND GLOVES GROUP F Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 1 Group-F Sl no. Material Description Unit Quantity

More information

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators Version:- 3.1 Date of Issue:- June 2014 Page 1 of 13 NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators 1. Purpose This document is the technical specification for 33kV, 66kV

More information

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES

RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES CEB STANDARD 030-1 : 1996 Specification for RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES CEYLON ELECTRICITY BOARD SRI LANKA Specification for RESIN FILLING TYPE JOINTING KITS FOR

More information

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR

SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR 003: 2008 CEB SPECIFICATION SPECIFICATION FOR ALL ALUMINIUM ALLOY STRANDED CONDUCTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for Specification For All Aluminium Alloy Stranded Conductor CEB Specification

More information

Technical Specifications 25 KVA/40 KVA L.T. DISTRIBUTION BOX WITH KITKATs (for Rural Area) NO. DIST/DB/ 03/2006 INDEX

Technical Specifications 25 KVA/40 KVA L.T. DISTRIBUTION BOX WITH KITKATs (for Rural Area) NO. DIST/DB/ 03/2006 INDEX Technical Specifications 25 KVA/40 KVA L.T. DISTRIBUTION BOX WITH KITKATs (for Rural Area) NO. DIST/DB/ 03/2006 INDEX CL. NO. CONTENTS. SCOPE 2. SERVICE CONDITIONS 3. SYSTEM DETAILS 4. APPLICABLE STANDARDS

More information

Technical Specification for Live Line Tap Connectors

Technical Specification for Live Line Tap Connectors Ergon Energy Corporation Limited Technical Specification for Live Line Tap ETS-06-01-01 Check this is the latest Process Zone version before use. Specification ETS 06-01-01 Ver 1 Contents 1. Purpose and

More information

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS SPEC.NO. MSEDCL/ DIST:MSC-III/SPRING LOADED CONNECTOR BOX/05/10/R0/ 200510 TECHNICAL SPECIFICATIONS FOR TAMPER PROOF SERVICE CONNECTION BOX FOR L.T. LINES / CONSUMER MAINS (20.05.2010) Page 1 of 14 Clause

More information

TECHNICAL SPECIFICATION OF ACCESSORIES SUITABLE FOR 7/3.15 mm G.I. EARTH WIRE

TECHNICAL SPECIFICATION OF ACCESSORIES SUITABLE FOR 7/3.15 mm G.I. EARTH WIRE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF ACCESSORIES SUITABLE FOR 7/3.15 mm G.I. EARTH WIRE GETCO/E/TS EAC020/R0

More information

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED WITH METALLIC SCREEN Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 400mm 2 ALUMINIUM CONDUCTOR 1.9kV XLPE INSULATED Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

ACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME. Technical Specification (T.S)

ACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME. Technical Specification (T.S) ACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME SECTION - V Technical Specification (T.S) 37 (SCHEDULE I) TECHNICAL SPECIFICATION FOR SUPPLY OF AB CABLE 38 1. SCOPE: TECHNICAL SPECIFICATION This specification

More information

Technical Specification for LV ABC Fuse Switch Disconnectors

Technical Specification for LV ABC Fuse Switch Disconnectors Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and

More information

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS

SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS Page no. :1 of 11 SPECIFICATION: LINE TAPS FOR ALUMINIUM/ACSR AND COPPER CONDUCTORS Prepared by: Eng. T. Lev (-חתום-) Checked by: I. Bester (-חתום (- Approved by: Eng. Y. Samoocha (-חתום (- 1 Page no.

More information

TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED)

TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED) TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED) Regd. & Corporate Office: Visnagar Road, MEHSANA 384 001 (North Gujarat) Telephone: (02762) 222880, 222080-81 Fax: (02762)

More information

Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg.

Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg. DAKSHIN HARYANA BIJLI VITRAN NIGAM LIMITED Specification No. S-95/DD-177 Technical Specifications of 8 M and 9 M PCC Poles (F.O.S.-2.5) with working load 200 Kg. Chief Engineer/P&D, DHBVN, Hisar. Issue

More information

TECHNICAL SPECIFICATION A.B. CABLE

TECHNICAL SPECIFICATION A.B. CABLE TECHNICAL SPECIFICATION A.B. CABLE 1.0 NATURE OF WORK The work covered by this Specification is for L.T lines in A.B cable as specified herein and in the attached Schedules. The overhead distribution lines

More information

NPS/002/001 Technical Specification for Earthing Materials

NPS/002/001 Technical Specification for Earthing Materials Version:- 6.0 Date of Issue:- October 2017 Page 1 of 14 NPS/002/001 Technical Specification for Earthing Materials 1. Purpose The purpose of this document is to detail the requirements of Northern Powergrid

More information

TECHNICAL SPECIFICATION FOR 11mtr. LONG STEEL TUBULAR POLE

TECHNICAL SPECIFICATION FOR 11mtr. LONG STEEL TUBULAR POLE Annexure-A TECHNICAL SPECIFICATION FOR 11mtr. LONG STEEL TUBULAR POLE 1.0 SCOPE 1.1 This specification covers the design, manufacture, testing at works, supply / delivery & transportation of 11 mtr long

More information

2. Test Records - All records of analysis and tests shall be kept in suitable forms approved by the Bureau of Indian Standards.

2. Test Records - All records of analysis and tests shall be kept in suitable forms approved by the Bureau of Indian Standards. Doc. STI 1848/6 January 1995 SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF WRITING AND PRINTING PAPERS ACCORDING TO IS : 1848-1991 (Third Revision) (Amendment No.1 OF September 1993) 1. Laboratory

More information

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

NPS/002/020 Technical Specification for 11 & 20kV Power Cables Version:- 3.1 of Issue:- Nov - 09 Page 1 of 11 NPS/002/020 Technical Specification for 11 & 20kV Power Cables 1. Purpose The purpose of this document is to detail Northern Powergrid (the Company) requirements

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 66 kv LIGHTNING ARRESTORS GETCO/ENGG/TECH SPECI.- 66 KV LA/R4/Jan11 Sign

More information

Date: TECHNICAL SPECIFICATION FOR ACSR Panther Conductor

Date: TECHNICAL SPECIFICATION FOR ACSR Panther Conductor 1.0 SCOPE: Date:23.09.2013 TECHNICAL SPECIFICATION FOR ACSR Panther Conductor 1.1 This specification provides for design, manufacture, engineering inspection stage testing and testing before despatch,

More information

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN

MESP TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN Engineering Specification Electrical Networks MESP 030000-04 TECHNICAL SPECIFICATION FOR ELECTRIC CABLE 70mm 2 FLEXIBLE TINNED COPPER CONDUCTOR 3.3kV EPR INSULATED WITHOUT METALLIC SCREEN Version: 1 Issued:

More information

Pins Insulator. Composite/Polymers Insulators

Pins Insulator. Composite/Polymers Insulators Composite/Polymers Insulators Electric network in India operates under very harsh environments. Industrial pollution, marshy land, hilly and unfriendly terrain, extreme weather, coastal region etc. make

More information

Product Specification JUL 14 Rev. A1

Product Specification JUL 14 Rev. A1 Industrial SCSI Connector 1. Scope 1.1 Contents This specification covers the requirements for product performance, test methods and quality assurance provisions of SCSI Connector. 2. Applicable Documents

More information

NPS/002/023 Technical Specification for 132kV Power Cables.

NPS/002/023 Technical Specification for 132kV Power Cables. Version:- 2.2 of Issue:- June 09 Page 1 of 11 NPS/002/023 Technical Specification for 132kV Power Cables. 1. Purpose The purpose of this document is to detail the technical requirements of Northern Powergrid

More information

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols

Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols Ergon Energy Corporation Limited Technical Specification for Aluminium Castings, Pole Caps and Pressed Symbols ETS-01-05-01 Check this is the latest Process Zone version before use. Specification ETS 01-05-01

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 400 kv, 220 kv & 132 kv LIGHTNING ARRESTORS (SURGE ARRESTORS) GETCO/ENGG/TECH

More information

2. TEST RECORDS: All records of tests and analysis shall be kept in suitable forms approved by the Bureau.

2. TEST RECORDS: All records of tests and analysis shall be kept in suitable forms approved by the Bureau. SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF CARBON STEEL BILLETS, BLOOMS, SLABS AND BARS FOR FORGINGS ACCORDING TO IS:1875-1992 (Fifth Revision) 1. LABORATORY: A laboratory shall be maintained

More information

Mar11 Rev B

Mar11 Rev B Product Specification 108-1163-7 11Mar11 Rev B Inverted Six and Eight Position Surface Mount Shielded Modular Jack Assembly 1. SCOPE 1.1. Content This specification covers performance, tests and quality

More information

3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series

3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series 3M Cold Shrink Silicone Rubber Connector Insulators 8440 Series Data Sheet May 2014 Product Description 3M Cold Shrink Connector Insulators 8440 Series are open-ended, silicone rubber, tubular sleeves.

More information

TECHNICAL SPECIFICATION OF TOWER MATERIAL FOR132KV-PANTHER TRANSMISSION LINE

TECHNICAL SPECIFICATION OF TOWER MATERIAL FOR132KV-PANTHER TRANSMISSION LINE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF TOWER MATERIAL FOR132KV-PANTHER TRANSMISSION LINE GETCO/E/TS TM051/R0

More information

NPS/003/033 Technical Specification for Substation Support Structures

NPS/003/033 Technical Specification for Substation Support Structures Version:- 2.0 Date of Issue:- April 2015 Page 1 of 21 NPS/003/033 Technical Specification for Substation Support Structures 1. Purpose The purpose of this document is to specify the technical requirements

More information

VERSAFIT V2 AND V4 TUBING Polyolefin, Flexible, Heat-Shrinkable, Flame-Retardant

VERSAFIT V2 AND V4 TUBING Polyolefin, Flexible, Heat-Shrinkable, Flame-Retardant TE Connectivity 300 Constitution Drive Menlo Park, CA 94025 USA Raychem Tubing Specification This Issue: Date: Replaces: RW-3023 Issue 9 Nov 21, 2016 Issue 8 VERSAFIT V2 AND V4 TUBING Polyolefin, Flexible,

More information

SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF ALLUMINIUM ALLOY TUBES FOR IRRIGATION PURPOSES; WELDED TUBES ACCORDING TO IS: 7092 (PART I)-1992

SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF ALLUMINIUM ALLOY TUBES FOR IRRIGATION PURPOSES; WELDED TUBES ACCORDING TO IS: 7092 (PART I)-1992 SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF ALLUMINIUM ALLOY TUBES FOR IRRIGATION PURPOSES; WELDED TUBES ACCORDING TO IS: 7092 (PART I)-1992 1. LABORATORY: A laboratory shall be maintained which

More information

SCHEDULE-III TECHNICAL SPECIFICATION OF 11 KV CTPT METERING SETS AGAINST TN-2134

SCHEDULE-III TECHNICAL SPECIFICATION OF 11 KV CTPT METERING SETS AGAINST TN-2134 Common Spec-2134.doc - 1-3.01 SCOPE: SCHEDULE-III TECHNICAL SPECIFICATION OF 11 KV CTPT METERING SETS AGAINST TN-2134 This specification covers the design, manufacture, assembly, testing and delivery of

More information

INDIAN REGISTER OF SHIPPING CLASSIFICATION NOTES. Type Approval of Mechanical Joints used in Piping

INDIAN REGISTER OF SHIPPING CLASSIFICATION NOTES. Type Approval of Mechanical Joints used in Piping INDIAN REGISTER OF SHIPPING CLASSIFICATION NOTES Type Approval of Mechanical Joints used in Piping January 2017 Page 2 of 16 Changes in JANUARY 2017 Version Type Approval of Mechanical Joints used in Piping

More information

Specification Technical Requirements for Revenue Electricity Meters

Specification Technical Requirements for Revenue Electricity Meters Specification Technical Requirements for Revenue Electricity Meters Standard Number: HPC-8DJ-16-0001-2013 Document Control Author Name: Richard Flett Position: Metering Technician Document Owner (May also

More information

PART 7 Technical Specification for Overhead and Underground Service Connection works for the Year

PART 7 Technical Specification for Overhead and Underground Service Connection works for the Year PART 7 Technical Specification for Overhead and Underground Service Connection works for the Year 2016-17 Technical Specification for Overhead and Underground Service Connection works for the Year 2016-17

More information

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE ONTARIO PROVINCIAL STANDARD SPECIFICATION OPSS.PROV 604 NOVEMBER 2017 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

THE KENYA POWER AND LIGHTING CO. LTD

THE KENYA POWER AND LIGHTING CO. LTD THE KENYA POWER AND LIGHTING CO. LTD SPECIFICATION for SINGLE PHASE STATIC METERS FOR ACTIVE ENERGY Compiled by NAME DESIGNATION SIGNATURE DATE Ephantus Nyagah Ag. Senior Engineer Checked by Approved by

More information

Mar11 Rev D

Mar11 Rev D Product Specification 108-1542 11Mar11 Rev D Mini-Universal MATE-N-LOK* Connector 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for MATE-N-LOK* mini-universal

More information

SPECIFICATION SHEET JUNCTION BOXES

SPECIFICATION SHEET JUNCTION BOXES SPECIFICATION SHEET JUNCTION BOXES 8484-SS8201-8010 0 DOCUMENT NO REV SHEET 1 OF 1 CLIENT : HPCL, MUMBAI PROJECT : LPG BOTTLING PLANT, ANANTAPUR PLANT : - LPG BOTTLING PLANT ISSUED FOR : PROPOSAL ENQUIRY

More information

SUPPLY AND DELIVERY OF 200KVA EARTHING TRANSFORMER TENDER DOCUMENTS: SARAWAK ENERGY REF. NO. PLS PART I TENDER PROCEDURES

SUPPLY AND DELIVERY OF 200KVA EARTHING TRANSFORMER TENDER DOCUMENTS: SARAWAK ENERGY REF. NO. PLS PART I TENDER PROCEDURES SUPPLY AND DELIVERY OF 200KVA EARTHING TRANSFORMER TENDER DOCUMENTS: SARAWAK ENERGY REF. NO. PLS-160091 PART I TENDER PROCEDURES SECTION 1 INTRODUCTION This Introduction should be read in conjunction with

More information

ELECTRICAL INSPECTION BULLETIN (Effective )

ELECTRICAL INSPECTION BULLETIN (Effective ) ELECTRICAL INSPECTION BULLETIN (Effective 2009-02-01) Rule 36-000 Customer Owned High Voltage Installations With the increase in customer own high voltage equipment there appears to be confusion over which

More information

DATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0

DATA SHEET. EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0 DATA SHEET EM1000 Fine Ribbed Electrical Safety Matting, rated to IEC61111:2009 Class 0 Unit 21 Priory Industrial Park Airspeed Road Christchurch Dorset BH23 4HD Tel: 01425 278011 Fax: 01425 278012 www.deltarubber.co.uk

More information

765kV/400kV S/S Powergrid Raichur Rev. 00 Technical Specification for Disc Insulators & String Hardware SECTION 1

765kV/400kV S/S Powergrid Raichur Rev. 00 Technical Specification for Disc Insulators & String Hardware SECTION 1 1.1 SCOPE SECTION 1 This technical specification covers the requirements of design, manufacture, testing at works, packing and dispatch of Disc Insulators & String Hardwares to site. This section covers

More information

QUALITY DEPT request to have FORM 1135 for REVIEW/APPROVAL Cycle everytime form will be updated/revised.

QUALITY DEPT request to have FORM 1135 for REVIEW/APPROVAL Cycle everytime form will be updated/revised. REF ONLY-DATA MANAGEMENT: 1 ST (2) PAGES IS NOT PART OF FORM 1135. QUALITY DEPT request to have FORM 1135 for REVIEW/APPROVAL Cycle everytime form will be updated/revised. FORM 1135 QUALITY ASSURANCE CLAUSES

More information

TECHNICAL SPECIFICATION FOR 22 kv, 1.2/2.4/3.0 MVAR CAPACITOR BANK WITH DOUBLE STAR ARRANGEMENT & ASSOCIATED EQUIPMENTS

TECHNICAL SPECIFICATION FOR 22 kv, 1.2/2.4/3.0 MVAR CAPACITOR BANK WITH DOUBLE STAR ARRANGEMENT & ASSOCIATED EQUIPMENTS Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO. MSEDCL/ DIST: MSC-III/06/2009 TECHNICAL SPECIFICATION FOR 22 KV 1.2/2.4/3.0 MVAR CAPACITOR BANK WITH DOUBLE STAR ARRANGEMENT AND ASSOCIATED

More information

SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF TITANIUM DIOXIDE, ANATASE, FOR PAINTS ACCORDING TO IS :

SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF TITANIUM DIOXIDE, ANATASE, FOR PAINTS ACCORDING TO IS : SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF TITANIUM DIOXIDE, ANATASE, FOR PAINTS ACCORDING TO IS : 411-1991 Doc. STI 411/3. November 1994 1 Laboratory A laboratory shall be maintained, which

More information

TECHNICAL SPECIFICATIONS FOR CROSS LINKED POLYETHYLENE INSULATED 3 CORE llkv CABLES

TECHNICAL SPECIFICATIONS FOR CROSS LINKED POLYETHYLENE INSULATED 3 CORE llkv CABLES TECHNICAL SPECIFICATIONS FOR CROSS LINKED POLYETHYLENE INSULATED 3 CORE llkv CABLES 1.00.00 SCOPE: 1.01.00 The scope of this package, covers the design, manufacture, stage inspection at works, inspection

More information

MIL-L-26764B 4 March 1970 SUPERSEDING MIL-L-26764(ASG) 12 December 1963 MILITARY SPECIFICATION

MIL-L-26764B 4 March 1970 SUPERSEDING MIL-L-26764(ASG) 12 December 1963 MILITARY SPECIFICATION 4 March 1970 SUPERSEDING MIL-L-26764(ASG) 12 December 1963 MILITARY SPECIFICATION LIGHT, MARKER, AIRPORT APPROACH, HIGH INTENSITY, TYPE MB-2 This specification has been approved by the Department of the

More information

CONTENTS. IEC Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60

CONTENTS. IEC Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60 IEC 61109 Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60 CONTENTS FOREWORD...4 INTRODUCTION...5 1 Scope and object...7 2 Normative references...7 3 Definitions...8 4 Abbreviations...9 5 Identification...9

More information

4. GENERAL REQUIREMENTS

4. GENERAL REQUIREMENTS 4. GENERAL REQUIREMENTS 4.1 APPLICATION FOR SERVICE Application for service must be made to, and accepted by, the Company before service will be furnished. At the time of application, the Customer shall

More information

Version: 1.1 Date of Issue: March 2017 Page: 1 of 23

Version: 1.1 Date of Issue: March 2017 Page: 1 of 23 Version: 1.1 Date of Issue: March 2017 Page: 1 of 23 NPS/002/034 - Technical Specification for Metering Base Unit for Connection to Extra High Voltage Metering Circuit Breakers in accordance with COP2

More information

Feb12 Rev D

Feb12 Rev D Product Specification AMPSEAL* Connectors 108-1329 01Feb12 Rev D 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for AMPSEAL* connectors. 1.2. Qualification

More information

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained.

1.1 All testing apparatus shall be periodically checked and calibrated records of such checks/calibration shall be maintained. DOC: STI//1 SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF ACCORDING TO IS/IEC:2003 1. LABORATORY A laboratory shall be maintained which shall be suitably equipped and staffed, where different tests

More information

DETAIL SPECIFICATION. MICROPHONE, CARBON (MICROPHONE M-29( )/U and M-52( )/U) INACTIVE FOR NEW DESIGN AS OF 30 MARCH 1999

DETAIL SPECIFICATION. MICROPHONE, CARBON (MICROPHONE M-29( )/U and M-52( )/U) INACTIVE FOR NEW DESIGN AS OF 30 MARCH 1999 INCH-POUND MIL-DTL-11193E 20 August 2009 SUPERSEDING MIL-M-11193D(SigC) 31 July 1960 DETAIL SPECIFICATION MICROPHONE, CARBON (MICROPHONE M-29( )/U and M-52( )/U) INACTIVE FOR NEW DESIGN AS OF 30 MARCH

More information

Supplier Quality Requirements Q Clauses

Supplier Quality Requirements Q Clauses Supplier Quality Requirements Q Clauses QA-0100032-Rev D DCR# 1603139 4/8/16 The following supplier quality requirements (Q Clauses), when specifically referenced in the Purchase Order by number, form

More information

PART MATERIAL REMARK Metal Case with Pig-tail. Brass (Metal Case) Copper (Pig-tail) Star Contact Copper Silver Plated

PART MATERIAL REMARK Metal Case with Pig-tail. Brass (Metal Case) Copper (Pig-tail) Star Contact Copper Silver Plated 1. SCOPE This specification defines the technical requirements of TZ-D series thermal-link with PROFFUSE brand that are produced according to IEC 60691, UL 60691,GB 9816. 2. APPLICABLE STANDARDS IEC 60691,

More information

TENDER FOR APPOINTMENT OF COURIER AGENCY AS OFFICIAL COURIER SERVICE AGENCY FOR

TENDER FOR APPOINTMENT OF COURIER AGENCY AS OFFICIAL COURIER SERVICE AGENCY FOR CENTRE FOR DEVELOPMENT OF IMAGING TECHNOLOGY (C-DIT) Chithranjali Hills, Thiruvallom, Thiruvananthapuram- 695 027 Phone: 0471-2380910/912/895 Fax: 0471-2380681 Ref. No. C-DIT/3/GNL/14/T 364 Dated 17.09.14

More information

Quality Management System

Quality Management System Quality Management System 6.1 Quality Q-Codes () 6.1 Quality Q-Codes Quality Clauses The following quality control clauses apply when specifically noted on the Gear Technology purchase order: Q1- Material

More information

Section - III Evaluation and Qualification Criteria

Section - III Evaluation and Qualification Criteria Section - III Evaluation and Qualification Criteria 1-2 Table of Clauses TABLE OF CLAUSES... 2 1. EVALUATION... 4 1.1 TECHNICAL EVALUATION... 4 1.2 ECONOMIC EVALUATION... 5 2. QUALIFICATION... 6 2.1 ELIGIBILITY...

More information

Procurement Quality Assurance Requirements

Procurement Quality Assurance Requirements 1. REQUIREMENTS 1.1 Quality System This document provides the minimum Quality System Requirements to externally provided processes, products and services to Superior Thread Rolling (STR). Suppliers must

More information

SMPM Female Cabled Connectors

SMPM Female Cabled Connectors Product Specification 108-2326 28 APR 14 Rev B SMPM Female Cabled Connectors 1. SCOPE This specification covers performance, tests and quality requirements for the TE Connectivity (TE) Subminiature P Miniature

More information

Doc: STI/1166/6 July 2008

Doc: STI/1166/6 July 2008 SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF CONDENSED MILK, PARTLY SKIMMED AND SKIMMED CONDENSED MILK ACCORDING TO IS 1166:1986 (Incorporating Amendment No. 1, 2 & 3) 1. Laboratory - A laboratory

More information

KENYA STANDARD KS 574:2017. Steel fabric for reinforcement of concrete Specification

KENYA STANDARD KS 574:2017. Steel fabric for reinforcement of concrete Specification KENYA STANDARD KS 574:2017 Steel fabric for reinforcement of concrete Specification KEBS 2017 FifthEdition 2017 KS 574:2017 TECHNICAL COMMITTEE REPRESENTATION The following organizations were represented

More information

Addendum No.1 (SUMMARY SHEET) Modifications to Tender Documents S.No. Document In Place of Please read as Remarks

Addendum No.1 (SUMMARY SHEET) Modifications to Tender Documents S.No. Document In Place of Please read as Remarks Contract: DMRC-MU-LINE2A-AEUD-03R TURNKEY PROJECT OF DESIGN, SUPPLY, ERECTION, TESTING &COMMISSIONING FOR MODIFICATION & RAISING OF +HEIGHT OF 110KV TRANSMISSION LINE (BORIVALI- MALAD) SPAN 41 AND 42 &(MALAD-ESSELWORLD)

More information

: 400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu SECTION - 1

: 400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu SECTION - 1 Technical Specification for 420 & 145 kv Post Insulators 1.1 SCOPE SECTION - 1 This technical specification covers the requirements of design, manufacture, testing at works, packing and dispatch of 420

More information

1.1 All testing apparatus shall be periodically checked and calibrated. Records of such checks/calibration shall be maintained.

1.1 All testing apparatus shall be periodically checked and calibrated. Records of such checks/calibration shall be maintained. SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF SINGLE PHASE a.c. INDUCTION MOTORS FOR GENERAL PURPOSE ACCORDING TO IS 996:2009 (Including Amendment No.1) 1. LABORATORY A laboratory shall be maintained

More information

IECEE OPERATIONAL DOCUMENT

IECEE OPERATIONAL DOCUMENT IECEE OD-G-4001 Edition 1.3 2013-06-20 IECEE OPERATIONAL DOCUMENT IEC System of Conformity Assessment Schemes for Electrotechnical Equipment and Components (IECEE System) Guidance for Factory Inspectors

More information

Conduits. Technical Specification for Conduits and Associated Materials. JTS Version 1

Conduits. Technical Specification for Conduits and Associated Materials. JTS Version 1 Conduits Technical Specification for Conduits and Associated Materials JTS-14-05-01 Version 1 Table of Contents 1. Definitions... 1 2. Purpose & Scope... 1 3. Applicable Standards... 8 3.1 Applicable Standards...

More information

TECHNICAL SPECIFICATIONS FOR AERIAL BUNCHED CABLES FOR OVERHEAD DISTRIBUTION

TECHNICAL SPECIFICATIONS FOR AERIAL BUNCHED CABLES FOR OVERHEAD DISTRIBUTION TECHNICAL SPECIFICATIONS FOR AERIAL BUNCHED CABLES FOR OVERHEAD DISTRIBUTION 1 INTRODUCTION Aerial Bunched Cable (ABC) is a very novel concept for Over Head power distribution. When compared to the conventional

More information

SECTION INSTALLATION AND/OR REPLACEMENT OF MASONRY UNITS AND REPOINTING

SECTION INSTALLATION AND/OR REPLACEMENT OF MASONRY UNITS AND REPOINTING SECTION 04210 INSTALLATION AND/OR REPLACEMENT OF MASONRY UNITS AND REPOINTING PART I GENERAL 1.1 SUMMARY A. Provide installation of new or replacement of masonry units and/or repointing of masonry units

More information

Mar11 Rev C

Mar11 Rev C Product Specification 108-1393 11Mar11 Rev C Connector, FPC, 1 mm 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for the TE 1 mm FPC connector. This connector

More information

BANK REFERENCE LETTER/SOLVENCY CERTIFICATE (On Bank s Letter Head) Certified that M/s at (address) is having an account in our bank

BANK REFERENCE LETTER/SOLVENCY CERTIFICATE (On Bank s Letter Head) Certified that M/s at (address) is having an account in our bank Annexure -I BANK REFERENCE LETTER/SOLVENCY CERTIFICATE (On Bank s Letter Head) Certified that M/s at (address) is having an account in our bank as per following particulars:- 1. Type of Account : Cash-Credit/Current/Savings

More information

QUALIFICATION TESTING OF FIELD WELDERS

QUALIFICATION TESTING OF FIELD WELDERS Page 1 of 9 Oklahoma DOT Materials & Testing December 5, 2003 (Updated to Reference 2009 Specifications 11/26/2012) (Added paragraph to the bottom of Roles and Responsibilities section. 11/14/2017) Publication:

More information

BUREAU OF INDIAN STANDARDS CENTRAL MARKS DEPARTMENT-III

BUREAU OF INDIAN STANDARDS CENTRAL MARKS DEPARTMENT-III BUREAU OF INDIAN STANDARDS CENTRAL MARKS DEPARTMENT-III Our Ref: CMD-III/16:814 31 January 2006 Subject: Implementation of Amendment No 1 to IS 814:2004 for Covered Electrodes For Manual Metal Arc Welding

More information

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators HIGH VOLTAGE INSULATORS By JP Holtzhausen The principal dielectric used on overhead power lines is air at atmospheric pressure. The air, surrounding the bare high voltage aluminium or steel- cored aluminium

More information