1 Ruling No Application No BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, AND IN THE MATTER OF Articles , and Sentence (1) of Regulation 403, as amended by O. Reg. 22/98, 102/98, 122/98, 152/99, 278/99, 593/99, 597/99 and 205/00 (the Ontario Building Code ). AND IN THE MATTER OF an application by Mr. Christian Wingelaar, Waterloo, Ontario, for the resolution of a dispute with Mr. James A. Witmer, Chief Building Official, City of Kitchener, Ontario, to determine whether the proposed guard comprised mainly of 35 mm diameter acrylic rods complies with Articles and and whether the irregular curved stair provides sufficiency of compliance with Sentence (1) of the Ontario Building Code at the Zinger Residence, Lot 9, 2121 Hidden Valley Crescent, Kitchener, Ontario. APPLICANT RESPONDENT PANEL PLACE Mr. Christian Wingelaar, President Wingelaar Estate Homes Waterloo, Ontario Mr. James A. Witmer Chief Building Official City of Kitchener Dr. Kenneth Peaker, Chair Mr. Fred Barkhouse Mr. Donald Pratt Toronto, Ontario DATE OF HEARING November 2, 2000 DATE OF RULING November 2, 2000 APPEARANCES Mr. Hans Gollek, President/Owner Wooden Stairs & Railing Ltd. Kitchener, Ontario Agent for the Applicant Mr. Glen D. Good Deputy Chief Building Official City of Kitchener Designate for Respondent
2 -2- RULING 1. The Applicant Mr. Christian Wingelaar, Waterloo, Ontario, has received a building permit under the Building Code Act, 1992 and has constructed a new detached dwelling at Lot 9, 2121 Hidden Valley Crescent, Kitchener, Ontario. 2. Description of Construction The Applicant has recently constructed a new single detached dwelling, one storey in building height and less than 600 m 2 in building area. The building is to be used as the principal residence of the Zinger family. At the request of the owners, the stairs and guards in the subject house were custom built. The Applicant, the general contractor, contracted out the construction of the stairs and guards to a custom builder. There are two areas of construction in dispute. The first involves the design and structural integrity of the guard serving stairs that connect the ground floor of the dwelling to the basement level. The guard is also installed on the ground floor to protect the elliptical opening for the subject stair assembly. The balusters that make up the guard are solid acrylic rods, spaced at 100 mm (4 in) on centre and are secured into the wooden handrail at the top and into each stair tread at the bottom. The acrylic rods are 35 mm (1 3/8 in) in diameter and are embedded 50 mm (2 in) into the stair and 38 mm (1 ½ in) into the railing. The second issue at dispute involves the design of the aforementioned stair. Described as providing access to egress, the proposed 17 riser stair has a modified curved design. As part of this unique design, the stair treads do not radiate from a common point nor are the curved stringers parallel to one another throughout the stair run. In fact, as the stairs descend they become wider. The width between stringers at the top of the stairs is 1,118 mm (44 in) and at the bottom is 1,486 mm (58 ½ in). As well, the second, third and fourth lower most stairs have elliptical nosing, i.e., they are slightly bowed or outward projecting. The minimum run of the individual stairs, ranging between and mm (8.12 and 8.13 in), surpasses the 150 mm (5 7/8 in) requirement. No measurements were provided for the average stairs runs, but it exceeds the minimum required of 200 mm (7 7/8 in) since even the minimum run is greater than 200 mm. The bottom stair, however, which functions more like a landing, proposes a tread depth of 813 mm (32 in) and has a semi-elliptical shape. In terms of the uniformity of the stair run, again no measurements were provided at the average or midpoint of each tread. The Applicant, however, has noted that the proposed stair (including stairs 2, 3 and 4) has runs varying between 243 and 245 mm (9.57 to 9.59 in) at the walking line. The walking line (see BCC Ruling # ) is an imaginary line running throughout the stair and is measured at 300 mm (12 in) from the inside handrail. This is the line, according to the Applicant, which, from an ergonometric point of view, represents the path of the mid-point of the body that an individual would actually take to ascend or descend the stair, and not the average run (i.e., the precise middle of each stair) that the Code recognizes. 3. Dispute The two issues at dispute between the Applicant and Respondent are i) whether the proposed guard, comprised mainly of 35 mm diameter acrylic rods, complies with Articles and of the
3 -3- Ontario Building Code; and ii) whether and the irregular curved stair provides sufficiency of compliance with Sentence (1) of the OBC. Article stipulates that all guards shall conform to the loading criteria in Article except where guards are constructed with the requirements outlined in the Supplementary Guidelines (SG-7), in which case they are deemed to satisfy the requirements of Sentence (1). Article outlines the requirements for loads on guards. Sentences (1) and (2) indicate the specifications required for the minimum horizontal load applied inward or outward at the top of every guard and for the individual elements within the guard, including solid panels and pickets. As outlined by the Housing Development and Building Branch of the Ministry of Municipal Affairs and Housing in their memorandum dated October 12, 2000, (w)here guards differ from the prescriptive code requirements outlined in the Supplementary Guidelines to the OBC, guards may be designed according to the Part 4 requirements to determine the loading criteria. The Branch opinion further stated that (w)here the railing does not conform to the requirements of the SG-7 Guidelines, it shall conform to the applicable requirements of Article In this instance, the proposed guard that will run the length of the stair opening and the 17 riser stair, has been reviewed Truetek Engineering Inc. with respect to certain loading capabilities. At dispute however, is whether further loading calculations are required to confirm compliance with the OBC requirements. In respect to the second area of dispute involving the design of the stair, Sentence (1) requires that stairs have a uniform rise and run in any one flight. This requirement, which must be applied to exit and non-exit stairs alike is intended to provide consistent and uniform stair construction so that users will avoid missteps potentially resulting in injury. With the irregular curve of the stair (as noted, they do not radiate from a common point) and the elliptical shape of stairs two to four, the run has certain variations. At issue then, is whether the proposed design, with the previously described discrepancies in run uniformity, provides sufficiency of compliance with OBC Sentence (1). The Respondent raised concerns regarding whether the stair also failed to comply with Article which requires that curved stairs in exits meet Article Among other stipulations, Sentence (2) of Article mandates that the inside radius must be not less than twice the stair width. In doing so, this provision assumes that curved exit stairs are designed so that a line drawn at the riser face of each individual tread towards the inside of the stair would meet at a common, single point. These provisions, OBC and , however, are applicable only to exit stairs. The present disputed stairs, as private stairs within a dwelling, are considered as access to egress stairs and not exit stairs. As a result, their failure to meet at a common radius point is not a Code violation and will therefore not be addressed. 4. Provisions of the Ontario Building Code Article Construction of Guards (1) Except as permitted in Sentence (2), guards shall conform to the loading criteria in Article (2) Guards constructed in accordance with the requirements in the Supplementary Guidelines shall be deemed to satisfy the requirements of Sentence (1).
4 -4- Article Loads on Guards (1) The minimum specified horizontal load applied inward or outward at the top of every required guard shall be (a) 3.0 kn/m (200 lb/ft) for means of egress in grandstands, stadia, bleachers and arenas, (b) a concentrated load of 1.0 kn (225 lb) applied at any point for access walkways to equipment platforms, contiguous stairs and similar areas where the gathering of many people is improbable, and (c) 0.75 kn/m (50 lb/ft) or a concentrated load of 1.0 kn (225 lb) applied at any point, whichever governs, for locations other than described in Clauses (a) and (b). (2) Individual elements within the guard, including solid panels and pickets, shall be designed for a concentrated load of 0.5 kn (113 lb) at any point in the element. (3) The loads required in Sentence (2) need not be considered to act simultaneously with the loads provided for in Sentences (1) and (4). (4) The minimum specified load applied vertically at the top of every required guard shall be 1.5 kn/m (100 lb/ft) and need not be considered to act simultaneously with the horizontal load provided for in Sentence (1). Sentence (1) Uniform Treads and Risers (1) Treads and risers shall have uniform rise and run in any one flight. 5. Applicant s Position The Agent for the Applicant submitted that, when designing a stair they always keep the Ontario Building Code requirements uppermost in their minds. Nevertheless, he argued that, in the design of this stair, the walking line concept measured at 300 mm (12 in) from the inside handrail was applied and therefore a consistent tread run has been provided at that distance. This walking line they submit, is the area determined to be the centerline of an adult body transcending the stair, while holding on to the handrail. The only exception to this consistent stair run, he acknowledged, is the first stair which has a width of 813 mm (32 in); it has been designed more as a landing than a stair. The Agent argued that, when considering this design in the context of Article and taking into account a minimum variation allowed in the home construction industry, the run along the inside/right stringer and any slight alteration thereof due to the change in focal point are deemed permissible. In respect to the rise of the stair, the Agent submitted that the Zinger stair is 7 1/4 (in), a comfortable rise for a 17 rise staircase. In the Agent s opinion, Article does not state that the stair must be exactly as shown in article , nor that it must be a 90 o curved stair, nor that the stair can t be flared, nor that the stair can t have elliptical treads, nor that the stair can t not have multiple focal points along the inside stringer. In respect to the guards located along both the balcony and the stair, the Agent submitted that the Zinger handrail design is based on previous staircases (which have been built over the last 10 years), where the handrail design has been made with the same profile, the same manufacturing techniques and the same installation techniques. There has been no record of design and/or structural failure with this design.... He emphasized that the acrylic rods have been reviewed and approved by Truetek Engineering to meet the requirements of article In addition, they have followed all OBC and SG-7 requirements for the stair and handrails and the connection system. In the Agent s opinion,
5 neither the requirements nor the intent of the Building Code are being violated. 6. Respondent s Position -5- The Designate for the Respondent stated that the stair designer has not considered the Ontario Building Code s prescriptive requirements in the design of this stair. He submitted that the stair incorporates a curved section, a modified winder section (at Top & Bottom) complete with elliptical shaped nosing on the bottom three treads. The curved and winder sections do not comply with the Ontario Building Code due to the fact that the treads do not radiate from a common centre point, and /or turn through an angle of 30 o ; the curved stringers are not parallel to each other and therefore are neither a curved stair or a stair with winders. The Designate argued that the stair that is the subject of this dispute is not the stair for which a permit was issued. This stair was built completely in the designers shop, without notice to the Respondent of any proposed changes. The Designate submitted that, in his opinion, when you descend these stairs, your body naturally wants to move from the inside to the outside of the curved path of travel which results in having to negotiate a non-uniform run and tread width and a tendency for your body to move away from the handrail. This is not an appropriate design nor is it compliant with the OBC requirements. He did state however, that he has come to an agreement with the Applicant that the bottom stair can be considered as a landing. In respect to the proposed guards, the Designate for the Respondent submitted that the design does not comply with SG-7, nor has it been reviewed for compliance with Part 4 of the OBC. While he acknowledges that this type of guard is structurally sound in respect to vertical loading, there is no confirmation that these balusters would meet the requirements for lateral loading. He indicated that he would need confirmation from a qualified engineer to satisfy his concerns in that regard. 7. Commission Ruling It is the decision of the Building Code Commission that concerning the Zinger Residence, Lot 9, 2121 Hidden Valley Crescent, Kitchener, Ontario, the proposed guard, comprised mainly of 35 mm diameter acrylic rods complies with Articles and of the Ontario Building Code on the condition that: (1) the lateral capacity of the guard is verified by a qualified engineer. It is also the decision of the Building Code Commission that the irregular curving stair provides sufficiency of compliance with Sentence (1) of the Ontario Building Code at the aforementioned Zinger Residence. 8. Reasons i) With verification of the lateral capacity, the guard will comply with the Ontario Building Code. ii) The variations related to the run of the stair are considered minimal and therefore sufficiently comply with OBC requirements.
6 -6- Dated at Toronto this 2nd day in the month of November in the year 2000 for application number Dr. Kenneth Peaker, Chair Mr. Fred Barkhouse Mr. Donald Pratt
BUILDING CODE COMMISSION
Ruling No. 01-38-831 Application # 2001-47 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, 1992. AND IN THE MATTER OF Sentence 3.3.1.17.(1) of Regulation 403, as amended
More informationBUILDING CODE COMMISSION
Ruling No. 01-22-815 Application # 2001-14 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, 1992. AND IN THE MATTER OF Articles 3.3.1.8. and 3.4.3.6. of Regulation
More informationBUILDING CODE COMMISSION
Ruling # 01-12-805 Application # 2000-83 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, 1992. AND IN THE MATTER OF Articles 9.26.5.1. and 9.26.5.2. of Regulation
More informationBUILDING CODE COMMISSION
Ruling No. 02-38-893 Application No. 2002-33 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Clause 3.3.4.4.(1)(a)
More informationDesign Manual for M.C.M.E.L Railing System
Design Manual for M.C.M.E.L Railing System FOR DESIGNERS, ENGINEERS, ARCHITECTS, CONTRACTORS & INSTALLERS. 1 - USES OF RAILINGS M.C.M.E.L. railing systems are used in homes and in residential, commercial,
More informationEGRESS CHAPTER ,500 3 Over 2,500 4 OCCUPANT LOAD REQUIRED MEANS OF EGRESS
CHAPTER 4 EGRESS SECTION 401 GENERAL 401.1 General. The means of egress for new bleachers, folding and telescopic seating, and grandstands shall comply with this chapter. SECTION 402 TRAVEL 402.1 Exit
More informationStairs have many potential violations this Newsletter is Part 1 of two parts.
Stairs have many potential violations this Newsletter is Part 1 of two parts. Violation 1 : Risers do not meet requirements: riser heights too high/low; too much variation between riser heights; risers
More informationBUILDING CODE COMMISSION
Ruling No. 02-05-860 Application No. 2001-82 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 4.1.10.8. of
More informationSTAIRWAYS, HANDRAILS, AND GUARDRAILS (RESIDENTIAL)
01/25/08 STAIRWAYS, HANDRAILS, AND GUARDRAILS (RESIDENTIAL) City of Austin International Residential Code: 500 Fourth Avenue NE R314.1 Width. Stairways shall not be less than 36 in clear width at all points
More informationWork Group Item Stairways serving an occupant load of less than 50 shall have a width of not less than 36 inches (914 mm).
IBC-12/13 1009.1, 1009.4, 1009.7.2, 1009.7.4, 1009.8, 1009.10, 1009.15 (IFC [B] 1009.1, 1009.4, 1009.7.2, 1009.7.4, 1009.8, 1009.10, 1009.15) Proponent: S. Bajnai, Chesterfield County, VA, ICC Building
More informationPRESCRIPTIVE COMPLIANCE METHOD
CHAPTER PRESCRIPTIVE COMPLIANCE METHOD 3 SECTION 301 GENERAL 301.2 Building materials. Building materials shall comply with the requirements of this section. 301.2.1 Existing materials. Materials already
More informationWood Decks. Zoning and Construction requirements for open non-sheltered wood decks for residential dwellings.
Wood Decks Zoning and Construction requirements for open non-sheltered wood decks for residential dwellings. General Information 3 Zoning 7 Foundations 8 Structural 11 Design 16 Compliance 20 NOTE The
More informationPROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED
Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-03-13-05 Ontario CODE REFERENCE: Div. B 3.13.4.5. DESCRIPTION OF THE PROPOSED
More informationCity of of Dauphin WOOD DECKS. Zoning and construction requirements for non-sheltered wood decks for residential dwellings.
City of of Dauphin WOOD DECKS Zoning and construction requirements for non-sheltered wood decks for residential dwellings. General Information.3-6 Zoning..7 Foundations..8-10 Structural 11-14 Design..15-18
More informationLINCOLN COUNTY REQUIRED INSPECTIONS (Last updated August 23, 2017)
LINCOLN COUNTY REQUIRED INSPECTIONS (Last updated August 23, 2017) It is the responsibility of the permit applicant to notify the building inspector when the work is ready for inspection. To request an
More informationWood Decks Zoning and construction requirements for open non-sheltered wood decks for residential dwellings
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Wood Decks Zoning and construction requirements for open non-sheltered wood decks for residential dwellings November 2017 contents General Information... 3
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-24057-8 SOUTH AFRICAN NATIONAL STANDARD The application of the National Building Regulations Part M: Stairways Published by SABS Standards Division 1 Dr Lategan Road Groenkloof Private Bag
More informationBUILDING CODE COMMISSION
Ruling No. 02-22-877 Application No. 2002-19 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentences 3.3.1.2.(3),
More informationBUILDING CODE VARIANCE
BUILDING CODE VARIANCE April 2009 06-BCV-011-R1 Page 1 of 8 DISCUSSION MULTI-LEVEL STORAGE RACKING SYSTEMS The Alberta Building Code 2006 contains no specific requirements for multi-level storage racking
More informationVisual Interpretation Of The
Visual Interpretation Of The N T E R N A T I O N A L E S I D E N T I A L O D E 2006 IRC NEW JERSEY EDITION RESIDENTIAL BUILDING CODE SECTION R314 STAIRWAYS R314.1 Width. Stairways shall not be less than
More informationWHO IS THIS COURSE FOR?
INTRODUCTION INSTRUCTIONS - READ ME FIRST BEFORE THE COURSE STARTS, WORK ON YOUR OWN AND COMPLETE ALL OF THE EXERCISES. If you come unprepared, you will have a difficult time to keep up with the pace of
More informationBUILDING CODE COMMISSION
Ruling No. 08-05-1179 Application No. B-2007-48 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 6.2.1.4.
More informationPIP STF05511 Fixed Industrial Stairs
TECHNICAL CORRECTION January 2017 Structural PIP STF05511 Fixed Industrial Stairs PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice
More informationSECTION ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck)
SECTION 13125 ELEVATED BLEACHERS (Angle Frame Semi-Closed Deck) PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationIntroduction. Products conforming with a European Council Directive. CE marked construction products. Other regulations
Introduction This Technical Booklet has been prepared by the Department of Finance and Personnel and provides for certain methods and standards of building which, if followed, will satisfy the requirements
More informationPRESCRIPTIVE COMPLIANCE METHOD
CHAPTER 3 PRESCRIPTIVE COMPLIANCE METHOD [B] SECTION 301 GENERAL 301.1 Scope. The provisions of this chapter shall control the alteration, repair, addition and change of occupancy of existing structures,
More informationHILLSBOROUGH TOWNSHIP CODE ENFORCEMENT
HILLSBOROUGH TOWNSHIP CODE ENFORCEMENT SAMPLE GUIDE FOR RESIDENTIAL DECKS revised 7 16 Call before you dig! 1 800 272 1000 New Jersey One Call. Utility Mark Out. THIS GENERIC GUIDE IS NOT ALL INCLUSIVE
More informationAccessibility for Ontarians with Disabilities Act (AODA), 2005
Accessibility for Ontarians with Disabilities Act (AODA), 2005 Allstate Canada Group of Companies (ACG) Integrated Accessibility Standards Multi Year Plan Part I General Requirements Section 3 Establishment
More informationBUILDING CODE COMMISSION
Ruling No. 05-08-1022 Application No. 2005-03 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF in Articles 9.10.14.1.
More informationICC CODE CORNER 2012 IFC Code & Commentary
Chapter 10: Means of Egress General Comments The general criteria set forth in Chapter 10 regulating the design of the means of egress are established as the primary method for protection of people in
More informationBS 6180: 1999: Barriers in and about buildings Code of practice - General Contract use Clauses 6.4.1
RICHARD BURBIDGE LTD Our Ref.: Whittington Road Date: 12 th March 2008 Oswestry Date delivered: 4 th March 2008 Shropshire Date of tests: 4 th March 2008 SY11 1HZ For the attention of Mr Tony Jones SAMPLE(S)
More informationVehicle Impact Barriers for Elevated Structures
technical notes CAR IMPACT BARRIERS FOR ELEVATED STRUCTURES Wheel stops should not be relied upon to prevent cars falling off elevated structures. Impact barriers must be provided. Impact barriers must
More information2003 International Residential Building Code
2003 International Residential Building Code Section R305 Ceiling Height Habitable rooms, hallways, corridors, bathrooms, toilet rooms, laundry rooms and basements shall have a ceiling height of not less
More informationInternational Code Council
Page 1 of 21 International Code Council ICC 300-2012 edition Committee Actions Report For Committee Actions taken at the November 24 th and December 14 th, 2010 meetings Page 2 of 21 IS-BLE1-10/11 ICC
More informationICC CODE CORNER 2012 IFC Code & Commentary
SECTION 1005 MEANS OF EGRESS SIZING [B] 1005.1 General. All portions of the means of egress system shall be sized in accordance with this section. Exception: Means of egress complying with Section 1028.
More informationDECK INFORMATION SHEET
Community Development Department 925 Burlington Avenue Lisle, Illinois 60532 630-271-4150 DECK INFORMATION SHEET The Village of Lisle requires a permit to build, repair or replace a deck. Decks are permitted
More informationManual for design of Guardrails
Manual for design of Guardrails for Designers, Engineers, Architects, Contractors, Installers www.allium.com Table of contents Introduction. 2 Types of guardrails systems......4 o Series 100 4 o Series
More informationAustralian Standard. Fixed platforms, walkways, stairways and ladders Design, construction and installation AS
AS 1657 1992 Australian Standard Fixed platforms, walkways, stairways and ladders Design, construction and installation First published as AS CA10-1938. Second edition 1963. Third edition 1966. Fourth
More informationModule 8: Ontario Building Code Fire and Spatial Separations
Ontario Building Code (OBC) 1. Fire Separations 2. Fire Resistance Ratings By Classification 3. Fire Resistance Ratings By Adjacent Use 4. Fire Resistance Ratings By Specific Space 5. Fire Resistance Ratings
More information4188 East Andrew Johnson Highway Morristown, TN
4188 East Andrew Johnson Highway Morristown, TN 37814 800-225-7814 education@precisionladders.com Super Simplex Disappearing Stairway Automatic Electric Disappearing Stairway Automatic Super Simplex FL
More informationVTU EDUSAT PROGRAMME Lecture Notes on Design of Stair cases
VTU EDUSAT PROGRAMME 17 2012 Lecture Notes on Design of Stair cases DESIGN OF RCC STRUCTURAL ELEMENTS - 10CV52 (PART B, UNIT 8) Dr. M. C. Nataraja Professor, Civil Engineering Department, Sri Jayachamarajendra
More information2015 International Fire Code
1001, 1001.1, 1001.2, 1002, [BE] 1002.1, 1003, [BE] 1003.1, [BE] 1003.2, [BE] 1003.3, [BE] 1003.3.1, [BE] 1003.3.2, [BE] 1003.3.3, [BE] 1003.3.4, [BE] 1003.4, [BE] 1003.5, [BE] 1003.6, [BE] 1003.7, 1004,
More informationCITY OF BRISTOL DECK CONSTRUCTION GUIDE ACCORDING TO THE 2012 IRC WITH THE 2016 CT AMMENDMENTS
CITY OF BRISTOL DECK CONSTRUCTION GUIDE ACCORDING TO THE 2012 IRC WITH THE 2016 CT AMMENDMENTS To construct an attached deck in to a residential home in the City of Bristol, you must provide the following:
More informationProject Address Applicant: (Please Print) Plan review Engineer: Phone: Date
BUILDING AND SAFETY Tenant Improvement Checklist Project Address Applicant: (Please Print) Plan review Engineer: Phone: Date APPLICATION The following items will be required at the permit counter before
More informationPERMIT APPLICATION CHECKLIST Municipal Address, Phone & Fax NONRESIDENTIAL
PERMIT APPLICATION CHECKLIST Municipal Address, Phone & Fax NONRESIDENTIAL Permit Application #: Date: mm/dd/yy Project Address Applicant s Name NOTE TO PERMIT APPLICANTS: All permit applications must
More informationGeneral Requirements Yes N/A 1. Is the designer qualified for the proposed work?
DECKS BUILDING PERMIT REQUIREMENTS May 216 Below is a checklist outlining the requirements to obtain a building permit to construct a deck for a single detached, semi-detached, duplex or townhouse dwelling
More informationCode Compliance Research Report CCRR-0185
Code Compliance Research Report CCRR-0185 Issue Date: 12-09-2016 Renewal Date: 12-10-2017 Revision Date: 04-20-2017 DIVISION: 06 00 00 WOOD, PLASTICS, AND COMPOSITES Section: 06 50 00 Structural Plastics
More informationCopyright Materials. Presented by: The Wagner Companies R & B Wagner, Inc. The myth of the Ladder Effect and other railing safety issues
The myth of the Ladder Effect and other railing safety issues Presented by: The Wagner Companies R & B Wagner, Inc. Copyright Materials This presentation is protected by US and International copyright
More informationSupplementary Standard SB-13. Glass in Guards
Ministry of Municipal Affairs and Housing Building and Development Branch 2006 Building Code - Supplementary Standards Supplementary Standard SB-13 Glass in Guards June 12, 2012 COMMENCEMENT Supplementary
More informationBUILDING CODE COMMISSION
Ruling No. 03-27-925 Application No. 2003-14 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 9.14.2.1.,
More informationSteps And Stairs Installation Steps In Wall - Option 1 Steps In Front of Walls - Option 2 Steps In Wall; 10 (25cm) Tread - Option 3 Step Parallel to
Steps And Stairs Installation Steps In Wall - Option 1 Steps In Front of Walls - Option 2 Steps In Wall; 10 (25cm) Tread - Option 3 Step Parallel to Wall - Option 4 Steps and Stairs Q & A E CONSTRUCTION
More informationORDINANCE. APPROVED EMERGENCY: (Yes) (No) VETOED: Date
ORDINANCE AN ORDINANCE OF THE COMMISSION OF KNOX COUNTY, TENNESSEE RESCINDING ARTICLE III. CABO ONE- AND TWO-FAMILY DWELLING CODE, SEC. 10-56, SEC. 10-57 AND SEC. 10-58 AND ADOPTING THE 2006 INTERNATIONAL
More informationRESIDENTIAL BUILDING REQUIREMENTS
RESIDENTIAL BUILDING REQUIREMENTS Residential Building Requirements This is an informational booklet with some of the general residential construction requirements taken from the codes adopted by Campbell
More informationATI Evaluation Service A Division of Architectural Testing Certification Services
ATI Evaluation Service A Division of Architectural Testing Certification Services Subject to Renewal: 04/08/2014 Issued: 04/08/2013 Visit www.ati-es.com for current status Revision: 11/11/2013 Page 1 of
More informationATI Evaluation Service A Division of Architectural Testing Certification Services
ATI Evaluation Service A Division of Architectural Testing Certification Services Subject to Renewal: 05/16/2016 Issued: 06/29/2015 Visit www.ati-es.com for current status Page 1 of 9 CPG Building Products
More informationTolerances for Concrete Construction. Tolerances for Concrete Construction. Tolerance 6/16/2015
Tolerances for Concrete Construction Thomas J Downs P.E., FACI President Forensic Experts Minneapolis, MN What is it? Tolerances for Concrete Construction When did we start this anyway? Who said we needed
More information2010 National Building Code Adoption and Associated Process Changes
Building Inspection City of Moncton 655 Main Street Moncton, NB E1C 1E8 Phone: (506) 856-4375 Fax: (506) 856-4348 Bulletin No. 14 From: Randy Richard Date: February 9, 2015 Subject: 2010 National Building
More informationSteps And Stairs Installation Option 1 - Steps In Wall Option 2 - Steps With Plant Space Option 3 - Steps In Front of Walls Option 4 - Steps Along
Steps And Stairs Installation Option 1 - Steps In Wall Option 2 - Steps With Plant Space Option 3 - Steps In Front of Walls Option 4 - Steps Along Wall Face Option 5 - Steps In Wall; 10 (25cm) Tread Option
More informationTECHNICAL RECOMMENDATION NO: 11
9142 1 I I (K24) Date October 1992 TECHNICAL RECOMMENDATION NO: 11 METHOD FOR DETERMINING THE MINIMUM WIDTH OF EXITWAYS MEANS OF ESCAPE Colleen Wade METHOD FOR DETERMINING THE MINIMUM WIDTH OF EXITVVAYS
More informationBLOCK, LOT ; Section Requirement Status of Permit Review Status of C.O. Review The first 6 items are relevant to the principal building (house):
R-1A - ZONING REVIEW WORKSHEET Note: The items below must be reviewed and found in compliance prior to issuance of a zoning permit. Therefore, the appropriate data must be shown on the survey/lot development
More informationATI Evaluation Service A Division of Architectural Testing Certification Services
ATI Evaluation Service A Division of Architectural Testing Certification Services PCA-125 Subject to Renewal: 05/16/2018 Issued: 05/24/2017 Visit www.ati-es.com for current status Page 1 of 9 CPG Building
More informationBuilding Guide. Colorado Chapter of the International Conference of Building Officials. Building Guide
12/29/2016 Building Guide Colorado Chapter of the International Conference of Building Officials Building Guide Colorado Chapter of the International Code Council Single Family Residential Uncovered Decks
More informationRISK BULLETIN. Walking & Work Surfaces: Floors, Stairs and Elevated Workstations Checklist DATE / / NAME SIGNATURE WALKWAYS YES NO ACTION ASSIGNED
RISK BULLETIN Walking & Work Surfaces: Floors, Stairs and Elevated Workstations Checklist DATE / / NAME SIGNATURE WALKWAYS Are aisles and passageways kept clear? Are aisles and walkways marked to separate
More informationFACT SHEET #2 DECK INFORMATION
Borough of Doylestown Building and Zoning Department 57 West Court Street, Doylestown, PA 18901 215.345.4140 FACT SHEET #2 DECK INFORMATION BACKGROUND The provisions of the PAUCC. ICC Property Maintenance
More informationSmall. Application. Regulation Reference: (see page 23 for link to the regulation)
The Requirements of this Section apply to: Government of Ontario, Legislative Assembly, and Designated Public Sector Organizations Private / Not-for-Profit Sector Organizations Large Small Regulation Reference:
More informationWorkplaces must be kept clean, orderly, and sanitary. Workroom floors must be maintained as clean and dry as possible.
Section C.19 University of South Carolina Safety Program Guide WALKING AND WORKING SURFACES Introduction Occupational Safety and Health Administration (OSHA) CFR 1910 Subpart D Walking and Working Surfaces
More informationImportant Notice To Building Permit Applicants and Designers
Important Notice To Building Permit Applicants and Designers Beginning January 1, 2006, Designers of building permit documents who are not licensed architects or Professional Engineers may be required
More informationSNOW LOAD ANALYSIS FOR PUBLIC BUILDING ROOF SYSTEMS
SNOW LOAD ANALYSIS FOR PUBLIC BUILDING ROOF SYSTEMS SEPTEMBER 2002 SNOW LOAD ANALYSIS FOR PUBLIC BUILDING ROOF SYSTEMS SEPTEMBER 2002 ONTARIO RECREATION FACILITIES ASSOCIATION INC. 1185 EGLINTON AVENUE
More informationThe Uniform Building and Accessibility Standards Regulations
UNIFORM BUILDING AND 1 The Uniform Building and Accessibility Standards Regulations being Chapter U-1.2 Reg 5 (effective April 10, 1992) as amended by Saskatchewan Regulations 102/92, 81/93, 35/94, 23/98
More information2012 IBC Assembly Means of Egress. Based on the 2012 International Building Code
2012 IBC Assembly Means of Egress Based on the 2012 International Building Code Overview This seminar deals with those means of egress provisions of the IBC that are intended to address the concerns related
More informationAPPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO:
COUNTY OF KAUAI BUILDING DIVISION, DEPARTMENT OF PUBLIC WORKS 4444 RICE STREET, SUITE 175, LIHUE, HAWAII 96766 Telephone: (808) 241-6655 Fax Number: (808) 241-6806 BUILDING CODE COMMERCIAL CHECKLIST APPLICATION
More informationValue Stair Spiral Kit - Buying Guide
Value Stair Spiral Kit - Buying Guide platform railing * top baluster (1" main) * Shown with option: square platform with railing on 2 parallel sides. platform platform sleeve upper level floor system
More informationDEPARTMENT OF LICENSING AND REGULATORY AFFAIRS CONSUMER AND INDUSTRY SERVICES DIRECTOR S OFFICE BUREAU OF SAFETY AND REGULATION
DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS CONSUMER AND INDUSTRY SERVICES DIRECTOR S OFFICE BUREAU OF SAFETY AND REGULATION GENERAL INDUSTRY SAFETY AND HEALTH STANDARD GENERAL INDUSTRY SAFETY STANDARDS
More information2018 StairCraft Awards. Entry 48. Best Stairway Renovation. Entry Criteria
Aesthetic value: The remodel of this stair was vital to opening up this space. The existing closed-in stair was removed and in its place is now a light-colored maple open riser stair with glass railings,
More informationRS-1 District Schedule
District Schedule 1 Intent The intent of this Schedule is generally to maintain the single-family residential character of the District, but also to permit conditionally one-family dwellings with secondary
More informationWalking-Working Working Surfaces. OSHA Office of Training and Education 1
Walking-Working Working Surfaces OSHA Office of Training and Education 1 Introduction Slips, trips and falls cause: the majority of general industry accidents 15 percent of all accidental deaths more fatalities
More informationJC Code & Construction Consultants, Inc. Advanced 2010 FBC Update Ch. 1 to 16
JC Code & Construction Consultants, Inc. Advanced 2010 FBC Update Ch. 1 to 16 Welcome! This course is designed to provide an overview of the most significant changes to the 2010 edition of the Florida
More informationDECK PLANS City Of Grand Rapids Building Safety Division
DECK PLANS City Of Grand Rapids Building Safety Division 218-326-7601 www.grandrapidsmn.org This handout is intended only as a guide and is based in part on the 2007 Minnesota State Building Code, Grand
More informationE2-09/ (IFC [B] )
Code Technology Committee 2010 Final Action Agenda The following are code changes and public comments to be considered at the 2010 Dallas Final Action Hearings that are related to the CTC Area of Study
More informationBaseline Hillside Ordinance Correction Sheet (Ordinance No. 184,802 Effective 3/17/17)
Baseline Hillside Ordinance Correction Sheet (Ordinance No. 184,802 Effective 3/17/17) Plan Check #: Permit App. #: Job Address: Zone: Maximum Allowed RFA: Plan Check Engineer: Phone: Fax: (E-mail: firstname.lastname@lacity.org)
More informationCARROLL COUNTY BUREAU OF PERMITS AND INSPECTIONS RESIDENTIAL CODE COMPLIANCE GUIDELINES FOR DECKS
CARROLL COUNTY BUREAU OF PERMITS AND INSPECTIONS RESIDENTIAL CODE COMPLIANCE GUIDELINES FOR DECKS Code Reference: Chapter 97, Code of Public Local Laws and Ordinances of Carroll County and The International
More information780 CMR CHAPTER 34 EXISTING BUILDINGS STRUCTURES
780 CMR CHAPTER 34 EXISTING BUILDINGS STRUCTURES SECTION 3401 GENERAL 3401.1 Scope. Chapter 34 of the International Building Code 2009 is deleted in its entirety. The provisions of the International Existing
More informationExcerpts from: International Residential Code 2009
LUMBER & MILLWORK Excerpts from: International Residential Code 2009 R310.1 Emergency escape and rescue required. Basements, habitable attics and every sleeping room shall have at least one operable emergency
More informationClad truss stair. design elements
Clad truss stair design elements T2 Total covered rise Total structural rise Top tread width Total going Tread going (typically 250-280) Clad truss stair T2 design Truss construction methods have natural
More informationRiser and Tread Dimensions Riser Tread inches (mm) inches (mm)
STAIR DESIGN 9.03 The dimensions of risers and treads in a stairway should be proportioned to accommodate our body movement. Their pitch, if steep, can make ascent physically tiring as well as psychologically
More informationATI-ES Code Compliance Research Report
PCA-125 Subject to Renewal: 06/23/2016 Issued: 07/13/2015 Visit www.ati-es.com for current status Revised: 05/23/2016 Page 1 of 17 CPG Building Products LLC 894 Prairie Avenue Wilmington, Ohio 45177 (866)
More informationCITY OF FRUITLAND DIVISION OF PLAN REVIEW & PERMITTING DECK GUIDE. This design guide assumes all lumber to be pressure-treated Southern Pine.
City of Fruitland Building Inspections 208 South Division Street Fruitland, Maryland 21826 410.548.2804 CITY OF FRUITLAND DIVISION OF PLAN REVIEW & PERMITTING DECK GUIDE GENERAL NOTES This design guide
More informationCHAPTER 9 STAIR CASES 9.1 GENERAL FEATURES 9.2 TYPES OF STAIR CASES
CHAPTER 9 STAIR CASES 9.1 GENERAL FEATURES Stair cases are provided for connecting successive floors. It is comprised with flights of steps with inter mediate landings which provides rest to the user and
More informationPENNSAFE BUILDING INSPECTION SERVICES LLC Deck and Roof Cross Section Submittal
PENNSAFE BUILDING INSPECTION SERVICES LLC Deck and Roof Cross Section Submittal Roof Size: Width: Length: Roof Type: Gable: Hip: Shed: Roof Pitch: (check one) Trusses: Rafters: Spacing of Trusses or Rafters:
More informationBUILDING PERMIT GUIDELINES - RESIDENTIAL
TOWN OF MIDLAND 575 Dominion Avenue Midland, ON L4R 1R2 Phone: 705-526-4275 Fax: 705-526-9971 building@midland.ca BUILDING PERMIT GUIDELINES - RESIDENTIAL Applicable Law Description Required Zoning Certificate
More informationWINDOW AND DOOR REPLACEMENT SAMPLE PLAN
To aid in communication between yourself, the inspectors, and the plans examiners, we have prepared this sample plan to assist in the preparations of your plan for window and door replacement. Follow the
More informationPENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION
PENNSAFE BUILDING INSPECTION SERVICES LLC PERMIT APPLICATION Permit No. 175 Beaver Drive, P.O. Box 486 DuBois, PA 15801 Phone: 814-375-1111 Fax: 814-375-1117 Toll Free: 855-PENNSAF LOCATION OF PROPOSED
More informationResidential Decks. NOTE: If you are in a development with a 2. Deck Plan (see below)
Residential Decks A permit is required if the proposed deck will be attached to the dwelling and/or is 30 (or more) off the ground. You must obtain a building permit prior to starting any construction
More informationENGINEERING STANDARD FOR INDUSTRIAL STAIRS, LADDERS, PLATFORMS AND SCAFFOLDS ORIGINAL EDITION JULY 1997
ENGINEERING STANDARD FOR INDUSTRIAL STAIRS, LADDERS, PLATFORMS AND SCAFFOLDS ORIGINAL EDITION JULY 1997 This standard specification is reviewed and updated by the relevant technical committee on June 2003.
More informationVillage of Glencoe 675 Village Court, Glencoe, Illinois
Village of Glencoe 675 Village Court, Glencoe, Illinois 60022 847-835-4111 March 1, 2002 June, 2002 Clarifications Added Dear Homeowner, Architect, and Contractor: The attached materials will help you
More informationWalking-Working Surfaces
Walking-Working Surfaces Introduction Slips, trips and falls cause: the majority of general industry accidents 15 percent of all accidental deaths more fatalities than all other causes but motor vehicles
More informationSafety barrier to a deck located adjacent to a retaining wall at Oraka Beach Road, Mahia
Determination 2008/81 Safety barrier to a deck located adjacent to a retaining wall at Oraka Beach Road, Mahia Figure 1: Section showing deck and top of the bank 1 The matters to be determined 1.1 This
More informationSCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC Permit Requirements
SCREEN PORCHES 101 DEVELOPMENT RESOURCES, INC. 320-226.5189 www.101developmentresources.com While every attempt has been made to insure the correctness of this handout, no guarantees are made to its accuracy
More informationAPPLICATION FOR PORCH / DECK PERMIT
Department of Neighborhood Services and Inspections 625 52nd Street, Room 100, Kenosha, WI 53140 Phone: 262.653.4263, Fax: 262.653.4254 APPLICATION FOR PORCH / DECK PERMIT Permit Fee: $60.00, Zoning Plan
More information2012 Ontario Building Code Report - Part 4
2012 Ontario uilding Code Report - Part WARNING No representation or warranty is given that your particular application of these products complies with relevant building codes or that the fasteners provided
More information