DECK DAMAGE AND PENETRATIONS
|
|
- Ashlee Holt
- 5 years ago
- Views:
Transcription
1 DECK DAMAGE AND PENETRATIONS Prepared By Richard B. Heagler, P.E. SDI CONSULTANT Copyright 1987 (Rev. 2000) All rights reserved P.O. Box 25 Fox River Grove, IL Phone: (847) Fax: (847)
2 Deck Damage and Penetrations Damage to and purposeful penetrations have much in common - the location and severity are seldom known beforehand. Usually the designer knows the general area where a vent stack may cut the roof, or approximately where a telephone conduit may pierce the slab; and he may not know how big the hole will be. This lack of information makes it hard to advise how a hole should be reinforced - if at all - or how damaged should be repaired. Guide specifications reflect this lack of specific knowledge; the Steel Deck Institute states, Openings not shown on the erection diagrams, such as those required for stack, conduits, plumbing, vents, etc., shall be cut (and reinforced, if necessary) by the trades requiring the openings. The designer should certainly be consulted for reinforcing requirements, but frequently, unless details are shown on the plans, no reinforcing is provided and the designer is not consulted. Deck damage presents similar problems. Broad statements can be made such as, All damaged must be repiaced ; then the designer must make the decision as to what constitutes damaged, and he must also consider how replacement may delay the job. How much damage can be tolerated depends on architectural and structural considerations. If the underside of the is to be exposed to public view then very little visible damage may be allowed. In most cases, the will be hidden by a ceiling, or by ducts and utilities so the usual question Is about structural performance. Roof Deck Roof Deck is designed to carry live and dead load without acting in conjunction with other materials. Horizontal as well as vertical loads may be considered. For most 1 1/2 (38 mm) deep roof s the loss of one rib, either by denting or penetration, can be tolerated and no reinforcement will be required. The Canadian Standard for Steel Roof Deck (CSSBI 10M-96) allows an unreinforced opening of 6 (152 mm) as long as not more than 2 webs are removed. A simple and conservative estimate of the capacity would be to take out one rib (about 20% at the worst) and apply this to the uniform loads shown in the tables; in most cases the load capacity is greater than required anyway. A six inch diameter hole will probably not bother the diaphragm strength; a dent can be larger than 6 (152 mm) and still carry the necessary horizontal load. Covering the dent or an 8 (203 mm) maximum hole with a (1.14 mm) plate and carrying the plate to adjacent ribs could eliminate worries about insulation board spanning the dent and about a soft spot in the roof. For holes or dents greater than a rib (8 to 13 ) (203 mm to 330 mm) it would be advisable to use a (1.45 mm) minimum plate. The following are exceptions to this advice: 1.) the hole may be located in such a place that the can safely cantilever from each adjacent support; 2.) a group of holes may be so close together that a frame Is required. A special case of roof penetration is the sump pan. Generally, when properly attached (see page 7) the sump pan will carry the load of the it replaces. It also acts as a small header to transfer loads into adjacent uncut sheets. Approximate per foot (of width) section properties of standard (0.075 ) (1.91 mm) sump pan are: I = 0.36 in. 4 (150 x 10 3 mm 4 ); Sp = 0.20 in. 3 (3,277 mm 3 ). Sump pan analysis methods are shown in Appendix A, as well as a reinforcing technique. Burn holes in side laps, caused by welded side lap attachments, are spaced far enough apart not to cause problems. However most manufacturers advise not welding the side laps of (0.71 mm) (or thinner) because of the difficulty of obtaining a good weld. Typically, a side lap weld will cause a hole, the perimeter of the weld does the work. Burn holes near intermediate supports are unlikely to cause much loss of strength. (These holes are usually caused by the welder searching for the unseen structural member.) Distributed small dents, such as caused by foot traffic, will not cause a structural problem; but, if the denting covers a large percentage of the job, the insulation board may be better attached with mechanical fasteners rather than by adhesives. Holes caused by mechanical fasteners or screws are not problems. If the is not galvanized it is good practice to paint burned or abraded areas. 1
3 Roof Deck Plate Welds or fasteners at 8 (203 mm) c/c maximum Suggested schedule: Up to 6 (152 mm) - no reinforcing or (1.14 mm) minimum plate thickness 6 to 8 (152 mm to 203 mm) diameter (1.14 mm) minimum plate thickness 8 to 13 (203 mm to 330 mm) diameter (1.45 mm) minimum plate thickness Over 13 (330 mm) - frame opening* (design by project engineer) *check cantilever ability of. Plate 2
4 Composite Floor Deck Floor serves a dual purpose - after it has done its work as a form it becomes the positive bending reinforcing for the slab. The first function, as a form, is usually more critical than the second function of carrying the live load because contractors do not like shoring the. Any damage or penetration must then be first examined as to how it affects the capacity to carry the concrete. Just as roof, the floor can be examined as a cantilever; the SDl does not publish a cantilever table for floor because of the great number of profile variations available. A method for calculating allowable cantilever is shown in Appendix B. Note that if the is used as a cantilever, adequate top reinforcing steel must be installed. Many contractors prefer to block out concrete where a penetration will occur; and, after the concrete cures sufficiently, burn the away. The need for additional bars or mesh would be determined by the engineer. The contractor should also inspect for adequate attachment at supports and side laps. Although collapsing failures are rare, most of them can be traced to inadequate fastening at the beams. Side laps that open during the pour are more common and are obviously caused by poor sheet to sheet connections. Concrete provides an alkaline environment that discourages corrosion; also, most applications of composite are in dry interior areas and most is galvanized. Painting burned, cut, and abraded areas is not usually required. But, if the is not galvanized or the anticipated atmosphere is corrosive, then touching up damaged exposed areas is recommended. Before concrete is poured the contractor shall inspect the to find any areas that may be damaged (crushed) and may require shoring for the pour. FAILURE TO REPAIR OR SHORE DAMAGED DECK BEFORE THE POUR OF THE CONCRETE MAY RESULT IN INJURY. Crushed areas or areas that buckle during the pour (usually caused by damage or by overspanning the ) do not adversely affect the live load capacity. Tests at West Virginia University, by Dr. Larry Luttrell, showed no loss in live load capacity when the was purposely buckled. 3
5 Floor Deck 1 0 (305 mm) maximum opening C4 x 5.4 extend & weld to 3 ribs beyond opening. (each side) 2 0 ( 610 mm) maximum opening Concrete stop required at all openings. DETAIL FOR OPENINGS TO 2 ft. 0 in. (610 mm) PERPENDICULAR TO DECK L 13 (330 mm) maximum opening (1.80 mm) sheet welded to each cell all around or fasteners varies (see plan) 6 (152 mm) minimum each side of opening No reinforcement required where L is 6 (152 mm) or less, in direction perpendicular to. DETAIL FOR OPENINGS TO 13 in. (330 mm) PERPENDICULAR TO DECK 4
6 Appendix A Sump Pans Example 1: 22 gauge WR design L.L. = 40 psf (1.92 kpa) T.L. = 50 psf (2.39 kpa) Sump located at center of span 1 1/2 38 mm 6 0 (1,829 mm) 6 0 (1,829 mm) 22 1/2 (572 mm) 27 (686 mm) 22 1/2 (572 mm) IMPERIAL SI Total linear load on sump = = 113 lb./ft lb./ft. Total linear load on sump = 2.39 x.686 = 1.64 kn/m 1.64 kn/m 56.5 lb./ft lb./ft kn/m 0.82 kn/m or construction concentrated load = 200 lb./ft. 200 lb./ft. or construction concentrated load = 2.92 kn/m 2.92 kn/m 100 lb./ft. 100 lb./ft kn/m 1.46 kn/m 50 psf 2.39 kpa /2 100 lb./ft. 572 mm 1.46 kn/m M = (22.5) = 3,305 in. lb M = (0.572) = kn mm Typical s n = in. 3 /ft. of width fb = 3,305 = 18,000 psi < 20,000 O.K < 26,000 O.K. (temp. man load) Typical s n = 9,886 mm 3 /m of width fb = 1,226,000 N mm = 124 MPa < 138 O.K. 9,886 < 179 O.K. (temp. man load) 5
7 Appendix A Example 1: Cantilever span of /2 (572 mm) is less than the maximum recommended span for roof cantilever shown in the Steel Deck Institute Design Manual for WR20. O.K. No reinforcing required. Example 2: (same dimensions as Example 1.) /2 (572 mm) Sump end laps at this support Cantilever OK 6 0 (1,829 mm) This end of makes unstable work place Sump Install reinforcing channels as shown on sketch at page 7 before cutting opening. 6
8 Appendix A Roof Deck Cut-out for sump pan Reinforcing channel (0.034" min.) (0.86 mm) Reinforcing channel (0.034" min (0.86 mm) Reinforcing channel (0.034" min.) (0.86 mm) Reinforcing channel (0.034" min.) (0.86 mm) Put 1 1/2 (38 mm) deep reinforcing channels or zees in each rib at each side of opening (flush with top of ). Channels (zees) span between joists. Attach flanges of sump pan to channels or Z reinforcing. Cut-out for Sump Pan 3 (76 mm) min. Fasteners or welds at 8 (203 mm) c/c max. Cut-out for Sump Pan 3 (76 mm) min. Fasteners or welds at 8 (203 mm) c/c max. Sump Pan Reinforcing Z Sump Pan Reinforcing C Sump pan attachment to channel or Z reinforcing 7
9 Appendix B Maximum Floor Deck Cantilevers Bearing Width See note 3 Reinforcing steel for negative bending Pour Stop Cell. Closure Slab Depth Adjacent Span Cantilever Span 1.) Allowable bending stress of 20 ksi (138 MPa) with loading of concrete psf (1 kpa) or concrete lb. (667 N) concentrated load, whichever is worse. 2.) Allowable deflection of free edge (based on fixed end cantilever) of 1/120 of cantilever span under loading of concrete +. 3.) Bearing width of 3 1/2 (89 mm) assumed for web crippling check, which is; concrete psf (1 kpa) over cantilever and adjacent span. 8
SECTION STEEL DECKING
SECTION 05 31 00 STEEL DECKING SPEC WRITER NOTE: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Refer to Section 05 36 00, COMPOSITE METAL DECKING for floor
More informationAnchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi
STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel
More informationDIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2047 Reissued 07/207 This report is subject to renewal 07/209. DIVISION: 05 00 00
More informationThe Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.
SECTION 05 31 13 STEEL FLOOR DECKING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 01 - Specification
More informationStructural Technical Report #2 Pro/Con Study of Alternate Floor Systems
Christopher McCune Structural Option Eight Tower Bridge Faculty Advisor: Dr. Hanagan October 31 st, 2005 Structural Technical Report #2 Pro/Con Study of Alternate Floor Systems Executive Summary This technical
More informationThe Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.
SECTION 05 31 33 - STEEL FORM DECKING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 01 - Specification
More informationDESIGNING WITH STEEL FORM DECK
DESIGNING WITH STEEL FORM DECK All rights reserved 2003 P.O. Box 25 Fox River Grove, IL 60021 Phone: (847) 458-4647 Fax: (847) 458-4648 Form deck is a term used to describe deck that is most frequently
More informationThe Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.
SECTION 05 31 23 - STEEL ROOF DECKING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 01 - Specification
More informationIndustry Standard Terms & Definitions Of The Steel Deck Institute
Industry Standard Terms & Definitions Of The Steel Deck Institute A specialized set of jargon to describe common terms used by manufacturers and other professionals associated with the usage of Steel Deck
More informationACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings
ACCESSORY STRUCTURE Building permit information For 1 & 2-family dwellings Building Safety Department 400-2 nd Street South St. Cloud, MN 56301 (320) 255-7239 A building permit is required for any accessory
More informationDesign Manual and Catalog of Steel Deck Products STEEL DECK INSTITUTE MEMBER
Design Manual and Catalog of Steel Deck Products s STEEL DECK INSTITUTE MEMBER Manufacturers of products History CMC Joist & Deck is a leading producer of steel deck, open-web steel joists, long span steel
More informationA. Product Data: For each type of deck, accessory, and product indicated.
SECTION 053100 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Roof deck. 2. Composite floor deck. 3. Noncomposite form deck. 1.2 SUBMITTALS A. Product Data: For each type of deck, accessory, and
More informationStructural vs Nonstructural Members. Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures
Structural vs Nonstructural Members Roger LaBoube, Ph.D., P.E. Wei-Wen Yu Center for Cold-Formed Steel Structures Behavior of Cold-Formed Steel Members STEEL DESIGN SPECIFICATIONS Type of steel Specification
More informationNorth Mountain IMS Medical Office Building
North Mountain IMS Medical Office Building Phoenix, Arizona Michael Hopple Technical Assignment 2 October 29 th, 2007 AE 481W-Senior Thesis The Pennsylvania State University Faculty Adviser: Dr. Ali Memari,
More informationLPI 56 Technical Guide
LPI 56 Technical Guide Floor & Roof Applications Product Specifications & Design Values 2 Floor Tables 3 Uniform Floor Load (PLF) Tables: Simple s 4 Uniform Floor Load (PLF) Tables: Continuous s 5 Uniform
More informationThe New SDI Diaphragm Design Manual
Missouri University of Science and Technology Scholars' Mine International Specialty Conference on Cold- Formed Steel Structures (2006) - 18th International Specialty Conference on Cold-Formed Steel Structures
More informationFORMDECK. constructions. constructions
FORMDECK constructions constructions Introduction Formdeck300 (FD300) is a very efficient and durable permanent metal tray formwork, reinforcement and ceiling system used for suspended concrete slab construction.
More informationDesign of Reinforced Concrete Slabs
Lecture 07 Design of Reinforced Concrete Slabs By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar drqaisarali@uetpeshawar.edu.pk 1 Topics Addressed Introduction Analysis and Design of slabs
More informationInstalling DELTABEAM. Installation of DELTABEAM. Deliveries. Storage on-site
Installing DELTABEAM Installation of DELTABEAM These DELTABEAM installation instructions are intended to complement the project s erection plan. Peikko s technical support can help with the erection plan
More informationDESIGN CALCULATIONS INSTA-FOOTING LOAD BEARING CAPACITIES ON CONCRETE SLAB. January 14, 2017 Rev -
DESIGN CALCULATIONS INSTA-FOOTING LOAD BEARING CAPACITIES ON CONCRETE SLAB January 14, 2017 Rev - Projection Name: Owner: Prepared by: Insta-Footing Design Calculations Insta-footing, LLC Richard Nolan,
More informationAnalysis and Design of One-way Slab System (Part-I)
Lecture-02 Analysis and Design of One-way Slab System (Part-I) By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar www.drqaisarali.com 1 Topics Addressed Concrete Floor Systems Analysis and
More informationCITY OF RICHMOND PINE CAMP COMMUNITY CENTER ROOF REPLACEMENT PROJECT RCS PROJECT NO
SECTION 07220 - ROOF INSULATION PART 1 - GENERAL 1.01 DESCRIPTION A. Work included: The Roofing Contractor will provide all polyisocyanurate insulation and high density wood fiber roof insulation (tapered
More informationLysaght Bondek. Structural steel decking system Design and Construction Manual
Lysaght Bondek Structural steel decking system Design and Construction Manual Excellent spanning capacities for greater strength and less deflection Acts as permanent formwork with minimal propping and
More informationSECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
SECTION 220529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationINTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS, UNIFORM EVALUATION SERVICES
INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS, UNIFORM EVALUATION SERVICES EVALUATION CRITERIA FOR STEEL COMPOSITE, NON-COMPOSITE AND ROOF DECK CONSTRUCTION EC 007-2015 (Adopted April
More informationPro-Con Structural Study for Alternative Floor Systems October 27, 2004
Ismail Al-Hadhrami Structural Option Faculty Consultant: Dr. Thomas Boothby Agricultural Hall and Annex East Lansing, MI Pro-Con Structural Study for Alternative Floor Systems October 27, 2004 Executive
More informationCavity ShAftwall System
09 9 00/NGC Cavity shaftwall systems are non-load-bearing, -hour to -hour, fire-rated partitions constructed from one side used to enclose elevator shafts, stairs and mechanical shafts where the design
More informationREPORT HOLDER: ispan SYSTEMS LP 70 BRENTWOOD DRIVE PRINCETON, ONTARIO N0J 1V0 CANADA EVALUATION SUBJECT:
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 2-6587 (562) 699-05 www.icc-es.org ESR-787 Issued 07/2017 This report is subject to renewal 07/2018. DIVISION: 05 00 00 METALS
More informationOriginally Issued: 03/10/2017 Revised: 03/30/2019 Valid Through: 03/31/ Design
Originally Issued: 03/10/2017 Revised: 03/30/2019 Valid Through: 03/31/2019 EVALUATION SUBJECT: STEEL DECK PANELS REPORT HOLDER NUCOR CORPORATION - VULCRAFT/VERCO GROUP VULCRAFT GROUP 7205 Gault Avenue
More informationTHE FORENSIC MEDICAL CENTER
THE FORENSIC MEDICAL CENTER Image courtesy of Gaudreau, Inc. TECHNICAL REPORT #2 OCTOBER 26, 2007 KEENAN YOHE STRUCTURAL OPTION DR. MEMARI FACULTY ADVISOR EXECUTIVE SUMMARY Image courtesy of Gaudreau,
More information14240 W. 151 st Street, Homer Glen, IL Phone Fax Deck Building Guide
14240 W. 151 st Street, Homer Glen, IL. 60491 Phone 708-301-1301 Fax 708-301-0417 Deck Building Guide Single Family Residential Uncovered Decks and Porches APPLICATION: Submit a completed application Review
More informationSJI Updates Expanded Load Tables for Noncomposite Joists / Joist Girders and Development of New Composite Joist Series
SJI Updates Expanded Load Tables for Noncomposite Joists / Joist Girders and Development of New Composite Joist Series SUMMARY David Samuelson Steel joists are growing in recognition as being a very economical
More informationENGINEERS ENGINEERED SOLUTIONS DEEP-DEK COMPOSITE COMPOSITE LONG SPAN FLOOR DECK.
ENGINEERS ENGINEERED SOLUTIONS DEEP-DEK COMPOSITE COMPOSITE LONG SPAN FLOOR DECK www.metaldek.com DEEP-DEK 4.5 COMPOSITE DEEP-DEK 6 COMPOSITE DEEP-DEK COMPOSITE Deep-Dek Composite* is a long-span composite
More informationROOFING APPLICATION STANDARD (TAS) No. 102(A)-95
ROOFING APPLICATION STANDARD (TAS) No. 102(A)-95 TEST PROCEDURE FOR STATIC UPLIFT RESISTANCE OF MECHANICALLY ATTACHED, CLIPPED, RIGID, ROOF SYSTEMS (For Methods of Mechanical Attachment Excluding Clips,
More informationSECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
SECTION 220529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The General Conditions, Special Conditions and Division 1 through Division 22 as set forth in
More informationConcrete Framing systems. Design choices. Basic flavors
Concrete Framing systems Design choices Site Cast Concrete gives a designer a lot of freedom in the design and construction of walls, columns and surface textures. When it comes to spanning, concrete offers
More informationDIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: HILTI, INC.
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 43 6587 (56) 699 0543 www.icc es.org ESR 97 Reissued /7 This report is subject to renewal /8. DIVISION: 05 00 00 METALS SECTION:
More informationCOFS Mission. AISI Standards Hierarchy. North American Standards for Cold-Formed Steel Framing. Member versus System Design. Specification 10/21/2016
COFS Mission North American Standards for Cold-Formed Steel Framing Roger LaBoube, Ph.D., P.E. Curators Distinguished Teaching Professor Emeritus Director, Wei-Wen Yu Center for Cold-Formed Steel Structures
More informationSECTION PLATE CONNECTED WOOD TRUSSES
SECTION 06173 PLATE CONNECTED WOOD TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Shop fabricated wood trusses for roof and floor framing. 2. Bridging, bracing, and anchorage. B. Related Sections:
More informationStandard Installation Fire Damper Models: 119, 119(F), 119(SS), D19
Standard Installation Fire Damper Models: 119, 119(F), 119(SS), D19 Page 1 or 8 APPLICATION This fi re damper is intended to restrict the passage of fl ame. The standard installation requires that the
More information151 First Side. Technical Assignment 2 November 16 th, William J. Buchko. AE 481w Senior Thesis The Pennsylvania State University
November 16 th, 2007 William J. Buchko AE 481w Senior Thesis The Pennsylvania State University Thesis Advisor: Kevin Parfitt Table of Contents Executive Summary... 3 Structural System Overview Foundation...
More informationStatement of Special Inspections Michigan Building Code 2012 (MBC 2012)
Gaines Charter Township 8555 Kalamazoo Ave SE Caledonia MI 49316 PH: 616 698-6640 Fax: 616 698-2490 www.gainestownship.org Building Department Statement of Special Inspections Michigan Building Code 2012
More informationFACT SHEET #2 DECK INFORMATION
Borough of Doylestown Building and Zoning Department 57 West Court Street, Doylestown, PA 18901 215.345.4140 FACT SHEET #2 DECK INFORMATION BACKGROUND The provisions of the PAUCC. ICC Property Maintenance
More informationFIGURE R502.2 FLOOR CONSTRUCTION
CHAPTER 5 FLOORS 11 I SECTION R501 GENERAL R501.1 Application. The provisions of this chapter shall control the design and construction of the floors for all buildings including the floors of attic spaces
More informationPR-L274 Nordic Structures Revised April 16, 2017
Nordic TM PR-L274 Nordic Structures Revised April 16, 2017 Products: NI-20, 40, 40x, 60, 70, 80, 80x, 90, and 90x Prefabricated Wood I-s Nordic Structures 1100 Avenue des Canadiens-de-Montréal, Suite 504
More informationStructural Technical Report 1 Structural Concepts / Structural Existing Conditions Report
Michael A. Troxell Structural Option Advisor: Professor Parfitt College of Business Administration Oct. 5, 2005 Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report
More informationAdministrative Changes
Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings
More informationBuilding with Insul-Deck Floor & Roof System
Building with Insul-Deck Floor & Roof System What is Insul-Deck? Insul-Deck panels are steel-reinforced, foamed plastic in sulation boards used as permanent, stay-in-place concrete formwork for floor and
More informationBUILDING BULLETIN One and Two Family Dwellings Decks and Residential Access Ramps
BUILDING BULLETIN One and Two Family Dwellings Decks and Residential Access Ramps City of Virginia Beach Building Permits & Inspections Updated 4/30/09 Table of Contents I. Introduction... 1 II. Tips
More informationOn Cold-Formed Steel Construction. Light Gauge Steel Engineers Association Washington, D.C Toll Free (866)
TECHNICAL NOTE On Cold-Formed Steel Construction $5.00 Light Gauge Steel Engineers Association Washington, D.C. 20005 Toll Free (866) 465-4732 www.lgsea.com DESIGN OF BY-PASS SLIP CONNECTORS IN COLD-FORMED
More informationHANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
13686.00 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529-1 SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 1.1 SUMMARY A. Section Includes: 1. Metal pipe hangers and supports.
More information10 EXTREME BASEMENT PANELS
10 EXTREME BASEMENT PANELS On Granular Footings 1. The type of soil is a factor in determining foundation construction details such as footing design, backfill, and drainage provisions. Soils are classified
More informationSTRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION. Presented by: Susan L. Lasecki P.E., S.E.
STRUCTURAL ISSUES IN RESIDENTIAL CONSTRUCTION Presented by: Susan L. Lasecki P.E., S.E. Presentation Outline Gravity Design Load Paths from Roof to Foundation Roof Framing Floor Framing Wall Framing Lateral
More informationVTU EDUSAT PROGRAMME Lecture Notes on Design of Stair cases
VTU EDUSAT PROGRAMME 17 2012 Lecture Notes on Design of Stair cases DESIGN OF RCC STRUCTURAL ELEMENTS - 10CV52 (PART B, UNIT 8) Dr. M. C. Nataraja Professor, Civil Engineering Department, Sri Jayachamarajendra
More informationLightweight Steel Framing. Composite DeltaStud Load Tables
Lightweight Steel Framing Composite DeltaStud Load Tables January 2011 TABLE OF CONTENTS Introduction and Scope...3 Design Responsibility...3 Design Criteria and Technical Data...3 Composite Action / Materials
More informationCITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures
CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person
More informationAISC Steel & Timber Research for High-Rise Residential Buildings
AISC Steel & Timber Research for High-Rise Residential Buildings Final Report December 4 th, 2017 SOM Designed Benchmark Concrete Building Skidmore, Owings, and Merrill, LLP 2017 224s Michigan Avenue Suite
More informationLateral Design of Mid- Rise Wood Structures
Lateral Design of Mid- Rise Wood Structures Presented by Ricky McLain, MS, PE, SE Technical Director WoodWorks Texas Workshops December, 2016 Insert picture of me graduating college Follow the load Following
More informationThe following are details of the code requirements of the 2015 International Residential Code for single-story decks.
The following are details of the code requirements of the 2015 International Residential Code for single-story decks. The 2015 International Residential Code Section R507 contains additional information
More informationGARAGES/ONE-STORY City of Grand Rapids Building Safety Division
GARAGES/ONE-STORY City of Grand Rapids Building Safety Division 218-326-7601 www.cityofgrandrapidsmn.com This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building
More informationFranklin Square Hospital Center Patient Tower
Thomas Weaver Structural Option Franklin Square Hospital Center Patient Tower Baltimore, MD Thomas Weaver Structural Option AE 481W Senior Thesis Consultant: Professor M. Kevin Parfitt 12/14/2009 Page
More informationTypical Deck Details. Albemarle County, Virginia. Based on the 2012 Virginia Residential Code
Albemarle County, Virginia Typical Deck Details Based on the 2012 Virginia Residential Code The design details in this document apply to residential decks only. Framing requirements are limited to single
More informationSECTION NON-STRUCTURAL METAL FRAMING
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 09 22 16 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable
More informationStructural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity
System Codes and Criteria Design Codes and Standards The design code used is the Wisconsin Administrative Code along with the State of Wisconsin Department of Commerce-Safety & Buildings Chapters Comm
More informationA division of Canam Group
s and Girders Catalogue A division of Canam Group TABLE OF CONTENTS Products, services and solutions.... 4 General information The advantages of using steel joists... 5 Description of a joist girder....5
More informationWALL CONSTRUCTION CHAPTER 6
CHAPTER 6 WALL CONSTRUCTION SECTION R601 GENERAL R601.1 Application. The provisions of this chapter shall control the design and construction of all walls and partitions for all buildings. R601.2 Requirements.
More informationAMERICAN NATIONAL STANDARD ANSI/NAAMM STANDARD. Maximum Bearing Bar Depth / 2 (63.5 mm)
METAL BAR GRATING AMERICAN NATIONAL STANDARD ANSI/NAAMM STANDARD MBG 531-17 GRATINGS 5 ANSI/NAAMM MBG 531-17 SEPTEMBER 7, 2017 METAL BAR GRATING MANUAL EIGHTH EDITION Maximum Bearing Bar Depth... 2 1 /
More informationCOLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100
COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 Part 1 General 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified,
More informationLVL Product Guide 2.0E LVL 1.5E LVL
LVL Product Guide 2.0E LVL 1.5E LVL Our Company Anthony Forest Products Company, a family-owned business founded in 1916, is headquartered in El Dorado, Arkansas. The company operates a southern pine lumber
More informationCopyright. magazine. CFS Load Bearing Construction
Progressive Collapse Requirements Cold-Formed Steel Load Bearing Construction By Nabil A. Rahman, Ph.D., P.E., Michael Booth and Gary Bennett Figure 1: Cold formed steel load bearing mid-rise construction.
More informationThe difference is Guidance for the preparation of Deck Manufacturing Schedules
The difference is Guidance for the preparation of Deck Manufacturing Schedules innovation, commitment, support. 2 Guidance for the preparation of Deck Manufacturing Schedules Minimum Requirements for Schedule
More informationBEARING METAL STUD FRAMING
L-1 Section 05410 Long Form Specification LOAD BEARING METAL STUD FRAMING This section includes axially loaded steel studs, with unique slotted top channels, usually of 0.91, 1.2 and 1.5 mm (16, 18, or
More informationTalk to us, THE SMART DECKING PEOPLE Visit or Global Roofing Solutions Bond-Dek Composite Deck
Talk to us, THE SMART DECKING PEOPLE Visit www.globalroofs.co.za or email info@globalroofs.co.za Global Roofing Solutions Bond-Dek Composite Deck Bond-Dek composite deck Bond-Dek is a composite steel flooring
More informationSpecifying metal studs for interior and exterior walls can be simple.
by Thomas Castle, SE Specifying metal studs for interior and exterior walls can be simple. However, openings in the walls for doors, windows, and HVAC ducts require headers, jambs, and sills around them.
More informationDIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC.
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1780 Reissued 11/2017 This report is subject to renewal 11/2019. DIVISION: 06 00
More informationAssemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance
Pei Evaluation Service is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Assembly Evaluation Report represents a product that Pei ES has Evaluated. This Assembly Evaluation
More informationTechnical Data for. Headers. and Beams
L A M I N A T E D V E N E E R L U M B E R Technical Data for Headers and Beams E A S T E R N E N G I N E E R E D W O O D P R O D U C T S OUR COMPANY Our total focus on engineered wood products and providing
More informationTHE SITUATION WITH STEEL DECKS
THE SITUATION WITH STEEL DECKS Steel roof deck design can affect roof system selection and design by Mark S. Graham 32 www.professionalroofing.net MARCH 2017 teel roof decks commonly are encountered in
More informationPFC-5804* Reissued February 1, Filing Category: DESIGN Wood
PFC-50* Reissued February 1, 2003 ICBO Evaluation Service, Inc. 530 Workman Mill Road, Whittier, California 9001 www.icboes.org Filing Category: DESIGN Wood PACIFIC WOODTECH CORPORATION PWI JOISTS PACIFIC
More informationHeavy Rib. Page 1 of 6. Expanded Mesh & Metal Products. Key Product Features:
TMI- is used widely in construction work for joints, stop-end, retaining walls and columns. It creates a strong bond base for successive pours. is fixed as permanent formwork. Key Product Features: Unique
More informationICBO Evaluation Service, Inc Workman Mill Road, Whittier, California *Revised April 2003
PFC-5804* Reissued February 1, 2003 ICBO Evaluation Service, Inc. 5360 Workman Mill Road, Whittier, California 90601 www.icboes.org Filing Category: DESIGN Wood PACIFIC WOODTECH CORPORATION PWI JOISTS
More informationDIVISION: CONCRETE SECTION: SPECIALTY PLACED CONCRETE REPORT HOLDER: EMMEDUE S.P.A.
0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-2037 Reissued 07/2016 This report is subject to renewal 07/2018. DIVISION: 03 00 00 CONCRETE
More informationSJI Code of Standard Practice
Standard Practice CODE OF STANDARD PRACTICE FOR STEEL JOISTS AND JOIST GIRDERS SECTION 1 GENERAL 1.1 SCOPE Adopted by the Steel Joist Institute April 7, 1931 Revised to May 18, 2010 - Effective December
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 6587 (562) 699 0543 www.icc es.org ESR 3152 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00
More informationHAMBRO COMPOSITE FLOOR SYSTEM
HAMBRO COMPOSITE FLOOR SYSTEM OUR EXPERTISE AT YOUR SERVICE Canam has been offering owners, real estate developers, architects, engineers and contractors an array of construction solutions since 1970.
More informationLecture-06 Analysis and Design of Slab Systems
Lecture-06 Analysis and Design of Slab Systems By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar drqaisarali@uetpeshawar.edu.pk www.drqaisarali.com 1 Topics Addressed Organization of the
More informationPLYWOOD FLOATING FLOOR
PLYWOOD FLOATING FLOOR Read First These suggestions represent generally accepted procedures for successful installation of Enka Building Products. These instructions may be followed, modified, or rejected
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.
0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1143 Reissued 04/2017 This report is subject to renewal 04/2018. DIVISION: 07 00 00 THERMAL
More informationComposite Steel Deck - Slabs
American National standards institute / steel deck institute T - CD - 2011 Test Standard for Composite Steel Deck - Slabs copyright 2012 steel deck institute disclaimer The Steel Deck Institute has developed
More informationResidential Deck Guide
Residential Deck Guide The text and illustrations included in this guide represent opinions of the Borough of Mechanicsburg Codes and Zoning Department. This guide is for educational and information purposes
More informationShaftwall and Area Separation Wall Systems.
Shaftwall and Area Separation Wall Systems www.marinoware.com Marino\WARE S Fire Rated Wall Systems Quality that takes you to the top. Marino\WARE created its CT Shaftwall System, to be a flexible shaftwall
More informationDaytona Beach Pier Building Renovation Jun 2010
SECTION 15060 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationTech Tips SidePlate Connections FAQ 09/30/2017
Tech Tips SidePlate Connections FAQ 09/30/2017 Page 1 of 15 Introduction to SidePlate Connection Technology SidePlate Connection Technology is ideally suited to protect structures against seismic events,
More informationSTAY-FORM TRANSFORMING MATERIALS. into products that make a better world
STAY-FORM TRANSFORMING MATERIALS into products that make a better world TABLE OF CONTENTS Product Information... Page 1 Blindside Walls...Pages 2-4 Bulkheads...Page 5 Pile Caps...Page 6 Grade Beams...
More informationCity of of Dauphin WOOD DECKS. Zoning and construction requirements for non-sheltered wood decks for residential dwellings.
City of of Dauphin WOOD DECKS Zoning and construction requirements for non-sheltered wood decks for residential dwellings. General Information.3-6 Zoning..7 Foundations..8-10 Structural 11-14 Design..15-18
More informationSECTION GYPSUM BOARD ASSEMBLIES
SECTION 09 21 16 GYPSUM BOARD ASSEMBLIES PART 1 GENERAL 1.1 SECTION INCLUDES A. Metal stud wall and ceiling framing, 20 gauge. B. Metal channel suspended ceiling framing. C. Gypsum board. D. Gypsum sheathing.
More informationSDI MANUAL OF CONSTRUCTION WITH STEEL DECK SDI MANUAL OF CONSTRUCTION WITH STEEL DECK 2SECOND EDITION
SDI MANUAL OF CONSTRUCTION WITH STEEL DECK SDI MANUAL OF CONSTRUCTION WITH STEEL DECK 2SECOND EDITION MOC2 2006 TABLE OF CONTENTS Page I. PRODUCT DESCRIPTIONS..........................................
More informationLecture Retaining Wall Week 12
Lecture Retaining Wall Week 12 Retaining walls which provide lateral support to earth fill embankment or any other form of material which they retain them in vertical position. These walls are also usually
More informationCHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS 301 SCOPE
CHAPTER 3 BUILDINGS WITH WOOD FRAMED EXTERIOR WALLS WOOD CHAPTER 3 301 SCOPE This chapter prescribes construction requirements for buildings where all exterior walls above the foundation are wood framed
More informationCSU GUIDELINES. April 27, 2018 FOR POST-TENSIONED CONCRETE STRUCTURES.
CSU GUIDELINES FOR POST-TENSIONED CONCRETE STRUCTURES April 27, 2018 http://www.calstate.edu/cpdc/ae California State University Seismic Review Board Technical Guidelines January 9, 2018 The CSU Seismic
More information