REPORT NUMBER: SAT-001A_Rev.2 ORIGINAL ISSUE DATE: April 7, 2015 REVISED DATE: July 21, 2015

Size: px
Start display at page:

Download "REPORT NUMBER: SAT-001A_Rev.2 ORIGINAL ISSUE DATE: April 7, 2015 REVISED DATE: July 21, 2015"

Transcription

1 TEST REPORT REPORT NUMBER: SAT-001A_Rev.2 ORIGINAL ISSUE DATE: April 7, 2015 REVISED DATE: July 21, 2015 EVALUATION CENTER Shady Falls Road Elmendorf, TX Phone: (210) Fax: (210) RENDERED TO Wall and Ceiling Conference 5726 Sonoma Dr. Pleasanton, CA PRODUCT EVALUATED: Fire Rated Wall EVALUATION PROPERTY: Fire Resistance Report of Testing a Fire Rated Wall for compliance with the applicable requirements of the following criteria: ASTM E119-14, Standard Methods for Fire Tests of Building Construction and Materials, 2014 Edition (Modified per Section 4.2.1). This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to copy or distribute this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. 1

2 Report No SAT-001A_Rev.2 Page 2 of 45 1 Table of Contents 1 Table of Contents Introduction Test Samples SAMPLE SELECTION SAMPLE AND ASSEMBLY DESCRIPTION Testing and Evaluation Methods INSTRUMENTATION TEST STANDARD Deviation from Standard Method Testing and Evaluation Results RESULTS AND OBSERVATIONS Surface Deflection Analysis Conclusion... 7 APPENDIX A Assembly Drawings APPENDIX B - Test Data...13 APPENDIX C - Test Photographs..25 LIST OF CALIBRATED INSTRUMENTATION...44 REVISION SUMMARY / LAST PAGE OF REPORT.. 45

3 Report No SAT-001A_Rev.2 Page 3 of 45 2 Introduction Intertek Testing Services NA, Inc. (Intertek) has conducted testing for the Wall and Ceiling Conference, on a Fire Rated Wall Assembly, to evaluate Fire Resistance. Testing was conducted in accordance with the following the standard methods: ASTM E119-14, Standard Methods for Fire Tests of Building Construction and Materials, 2014 Edition (Modified per Section in this report). This evaluation took place on March 11, The intent of this testing was to see how the rating of an approved 1-hour wall assembly might be impacted by "typical" field damage. 3 Test Samples 3.1. SAMPLE SELECTION Intertek acquired all items for this testing from locally sourced providers and constructed the wall assembly as described in Section 3.2 of this document SAMPLE AND ASSEMBLY DESCRIPTION Framing 3-5/8 deep, 25EQ (25 GA "equivalent") G90 galvanized steel studs spaced 24 o.c. between 25EQ top and bottom track. 2. Interior and Exterior Cladding One layer of 4 x 10 x 5/8 USG SheetRock Brand Firecode Core TYPE X (ASTM C 1396 compliant) gypsum board oriented vertically secured using 1-1/4 self-drilling drywall screws spaced 8 o.c around the perimeter and 12" o.c. in the field. Exposed seams were covered with joint tape, and the tape and fasteners received 2 layers of joint compound. On the exposed and unexposed surfaces, the following typical field damages were simulated: Note For simplicity of this test/report, the following eight different conditions were identified by the test sponsor as typical field damages. Nominal 1/8" vertical gap (as measured from the face of the gypsum board) at one board joint filled with joint compound Damaged drywall board corner covered with joint compound Trade Damage: Nominal 1-1/2" x 1/2" chip in gypsum board core and face paper covered with joint compound Missed fastener removed and filled with joint compound Over-driven fastener covered with joint compound Gypsum board paper face torn and filled with joint compound Drywall board edge covered with joint compound Interior paper (brown paper) scratched/torn not covered with joint compound

4 Report No SAT-001A_Rev.2 Page 4 of 45 4 Testing and Evaluation Methods 4.1. INSTRUMENTATION The unexposed surface of the assembly was instrumented with a total of thirteen (13), 24 GA, Type K, fiberglass jacketed thermocouples; TCs 1-9 were evenly distributed across the face of the specimen in compliance with the test standard (however, these nine TCs were not used to determine pass/fail conditions for this test). TC #10 was installed over the vertical joint with the nominal 1/8" gap, #11 was over the missed fastener, TC #12 was near the over-driven fastener and TC #13 was located over the trade damage (see Appendix A). The output of the thermocouples and the furnace probes were monitored by a 100-channel Yokogawa, Inc., Darwin Data Acquisition Unit. The computer was programmed to scan and save data every 30 seconds. Following the test, the files were imported into MS Excel for tabular and graphical display (presented in Appendix B) TEST STANDARD 1 Testing was conducted in accordance with the applicable requirements of, and following the standard methods of ASTM E119-14, Standard Methods for Fire Tests of Building Construction and Materials, 2014 Edition (Modified per Section 4.2.1). The assembly was secured to the large scale vertical furnace and was tested to the standard time-temperature curve described in the E119 standard Deviation from Standard Method The intent of this testing is to see how the rating of an approved 1-hour wall assembly would be impacted by "typical" field damage. For this reason, an hourly rating for the wall assembly was not reported. The test standard requires a hose stream test to be performed at the end of the fire test, but none was conducted as part of this evaluation. 5 Testing and Evaluation Results 5.1. RESULTS AND OBSERVATIONS The test was initiated on March 11, Ben Duterte, Darin Coats and Mike Nonn representing the Wall and Ceiling Conference were present to witness the test. The ambient temperature at the time of the test was 57 F and the humidity was 81% R.H.

5 Report No SAT-001A_Rev.2 Page 5 of 45 Observations made during the test are as follows: Time (min:sec) Observation(s) 0:00 The test was initiated at 9:36 AM 2:08 Gypsum paper on exposed surface flaming 3:40 Drywall paper consumed on exposed surface 9:18 Joint compound beginning to flake and fall from wall on exposed surface 19:00 Most joint compound has fallen on exposed surface; little remains 27:00 Horizontal crack developing on exposed surface at mid-height of wall 39:00 Fastener heads scorching paper on unexposed surface of wall 45:00 Crack developing on unexposed surface of wall in drywall mud 60:00 Burners extinguished; test terminated There were no flames or gases hot enough to ignite cotton waste on the unexposed surface. No hose stream was conducted on the wall assembly Surface Deflection The deflection of the unexposed surface was measured at 3 equidistant locations, 30, 60, and 90 from left to right, across the horizontal midline, during the span of the test. The amount of that deflection is presented in the table below. Time (min) Position 1 (in) Position 2 (in) Position 3 (in) Start of Test : :00 1/2 3/4 3/4 45:00 1-1/4 1-3/4 1-3/4 58:00 1-1/4 1-1/2 1-1/2

6 Report No SAT-001A_Rev.2 Page 6 of 45 Correction Factor for the Fire Endurance Test In accordance with the E119 test standard, a calculation for any correction to the indicated fire resistance period was done. The calculated correction factor was -11 seconds. The standard specifies that the fire resistance be determined to the nearest integral minute. Consequently, if the correction factor is less than 30 seconds, and the test specimen met the criteria for the full indicated fire resistance period, no correction is deemed necessary Analysis The following simulated field damage conditions were instrumented with thermocouples on the unexposed side of the wall assembly: 1/8 joint; missed fastener, over-driven fastener, trade damage (1-1/2 x ½ paper damage). At 60 minutes, the temperatures at the instrumented typical field damaged locations were as follows: Location TC # Max Temp ( F) Max Allowed ( F) 1/8" Joint Missed Fastener Over-driven Fastener Trade Damage The temperature data for the selected field damage demonstrated equal or better temperature rise than the standard nine (9) thermocouples required by ASTM E119. The highest temperature measured was on the over-driven fastener (TC#12) which normally would not be instrumented with a thermocouple per ASTM E119. Note - The intent of this test was to see how the rating of an approved 1-hour wall assembly might be impacted by selected typical field damage. The individual temperature rise criteria as listed in the table above were based on ASTM E119 requirements of 325 F above the initial temperature: 56 F or 57 F, as applicable, at the start of this test for a maximum temperature of 381 F or 382 F. The other field damage was not instrumented, and included the following: Damaged drywall board corner covered with joint compound Drywall board edge covered with joint compound Interior paper (brown paper) scratched/torn not covered with joint compound There was no evidence of reduced fire resistance due to these simulated field damage conditions. Intertek considers that this would apply to the same wall assembly, but constructed with other manufacturer's listed 5/8" Type X gypsum board (compliant with ASTM C1396).

7 Report No SAT-001A_Rev.2 Page 7 of 45 6 Conclusion Intertek Testing Services NA, Inc. (Intertek) has conducted testing for the Wall and Ceiling Conference, on a Fire Rated Wall Assembly, to evaluate Fire Resistance. Testing was conducted in accordance with the following the standard methods of ASTM E119-14, Standard Methods for Fire Tests of Building Construction and Materials, 2014 Edition (Modified per Section in this report). This evaluation took place on March 11, The intent of this testing was to see how the rating of an approved 1-hour wall assembly might be impacted by "typical" field damage. There was no evidence of reduced fire resistance due to any of the simulated typical field damage conditions in the assembly as tested. The conclusions of this test report may not be used as part of the requirements for Intertek product certification. Authority to Mark must be issued for a product to become certified. INTERTEK TESTING SERVICES NA, INC. Tested and Reported by: Signature on File Jeffrey Patterson Project Engineer, Fire Resistance Reviewed by: Signature on File Victor M. Burgos Project Engineer, Fire Resistance

8 Report No SAT-001A_Rev.2 Page 8 of 45 APPENDIX A Assembly Drawings

9 Report No SAT-001A_Rev.2 Page 9 of 45

10 Report No SAT-001A_Rev.2 Page 10 of 45

11 Report No SAT-001A_Rev.2 Page 11 of 45

12 Report No SAT-001A_Rev.2 Page 12 of 45

13 Report No SAT-001A_Rev.2 Page 13 of 45 APPENDIX B Temperature Data

14 Report No SAT-001A_Rev.2 Page 14 of 45

15 Report No SAT-001A_Rev.2 Page 15 of 45

16 Report No SAT-001A_Rev.2 Page 16 of 45

17 Report No SAT-001A_Rev.2 Page 17 of 45

18 Report No SAT-001A_Rev.2 Page 18 of 45

19 Report No SAT-001A_Rev.2 Page 19 of 45

20 Report No SAT-001A_Rev.2 Page 20 of 45

21 Report No SAT-001A_Rev.2 Page 21 of 45

22 Report No SAT-001A_Rev.2 Page 22 of 45

23 Report No SAT-001A_Rev.2 Page 23 of 45

24 Report No SAT-001A_Rev.2 Page 24 of 45

25 Report No SAT-001A_Rev.2 Page 25 of 45 APPENDIX C Photographs

26 Report No SAT-001A_Rev.2 Page 26 of 45

27 Report No SAT-001A_Rev.2 Page 27 of 45

28 Report No SAT-001A_Rev.2 Page 28 of 45

29 Report No SAT-001A_Rev.2 Page 29 of 45

30 Report No SAT-001A_Rev.2 Page 30 of 45

31 Report No SAT-001A_Rev.2 Page 31 of 45

32 Report No SAT-001A_Rev.2 Page 32 of 45

33 Report No SAT-001A_Rev.2 Page 33 of 45

34 Report No SAT-001A_Rev.2 Page 34 of 45

35 Report No SAT-001A_Rev.2 Page 35 of 45

36 Report No SAT-001A_Rev.2 Page 36 of 45

37 Report No SAT-001A_Rev.2 Page 37 of 45

38 Report No SAT-001A_Rev.2 Page 38 of 45

39 Report No SAT-001A_Rev.2 Page 39 of 45

40 Report No SAT-001A_Rev.2 Page 40 of 45

41 Report No SAT-001A_Rev.2 Page 41 of 45

42 Report No SAT-001A_Rev.2 Page 42 of 45

43 Report No SAT-001A_Rev.2 Page 43 of 45

44 Report No SAT-001A_Rev.2 Page 44 of 45 CALIBRATED INSTRUMENTATION USED FOR TESTING Description Serial No. Calibration Due Date 100-Channel Data Acquisition System 99LE004 3/19/2015 Thermo/Hygrometer /19/2015 Stop Watch /20/2016

45 Report No SAT-001A_Rev.2 Page 45 of 45 REVISION SUMMARY DATE April 7, 2015 July 1, 2015 JMFlores, P.E. MDey SUMMARY Original Issue Date 1) Updated revision number and date through report 2) Added details related to modification of the test standard throughout report (Sections 2, 4, and 6) 3) Added Section Analysis 4) Revised Section 6 Conclusion to incorporate results from Section ) Removed signature from test engineer on Section 6 6) Removed TCs 1-9 from the Graph on page 14 as they were not part of this evaluation 7) Removed Graph on page 15 as it was not part of this evaluation July 21, 2015 JMFlores, P.E. MDey 1) Revised Section 3.2 and Section descriptions of typical field damages 2) Revised Section to include maximum temperature rise criteria on typical field damages 3) Revised Section to add discussion of applicability of findings to the tested assembly but constructed using other manufacturer s listed Type X, 5/8 gypsum board. 4) Revised Section 6 to remove test results table and performance observations repeated from section 5.1.2

REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: September 14, 2012 REVISED DATE: N/A

REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: September 14, 2012 REVISED DATE: N/A TEST REPORT REPORT NUMBER: 100595243SAT-005 ORIGINAL ISSUE DATE: September 14, 2012 REVISED DATE: N/A EVALUATION CENTER 16015 Shady Falls Road Elmendorf, TX 78112 Phone: (210) 635-8100 Fax: (210) 635-8101

More information

OBJECTIVE TEST ASSEMBLY

OBJECTIVE TEST ASSEMBLY OBJECTIVE The ASTM E 119 test method is intended to evaluate the duration for which a building element will contain a fire, or retain its structural integrity, or display both properties dependent upon

More information

REPORT NUMBER: SAT-001 ORIGINAL ISSUE DATE: March 23, 2010 REVISED DATE: NA

REPORT NUMBER: SAT-001 ORIGINAL ISSUE DATE: March 23, 2010 REVISED DATE: NA TEST REPORT REPORT NUMBER:3195900SAT-001 ORIGINAL ISSUE DATE: March 23, 2010 REVISED DATE: NA EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112 RENDERED TO

More information

Fire Testing Laboratory

Fire Testing Laboratory Fire Testing Laboratory Page 1 of 39 TEST REPORT for 2148 S. 41st Street Lousiville, KY 40211 Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load- Bearing

More information

LISTING INFORMATION OF ClarkDietrich Steel 'H' Stud and 'U' Track Fire-resistance-rated Area Separation Wall Assemblies SPEC ID: 26662

LISTING INFORMATION OF ClarkDietrich Steel 'H' Stud and 'U' Track Fire-resistance-rated Area Separation Wall Assemblies SPEC ID: 26662 LISTING INFORMATION OF ClarkDietrich Steel 'H' Stud and 'U' Track Fire-resistance-rated Area Separation Wall Assemblies SPEC ID: 26662 ClarkDietrich Building Systems 9100 Centre Pointe Drive, Suite 210

More information

LISTING INFORMATION OF ClarkDietrich Wall Assembly Design No. CD/WA SPEC ID: 26053

LISTING INFORMATION OF ClarkDietrich Wall Assembly Design No. CD/WA SPEC ID: 26053 LISTING INFORMATION OF ClarkDietrich Wall Assembly Design No. CD/WA 120-03 SPEC ID: 26053 ClarkDietrich Building Systems 9100 Centre Pointe Drive, Suite 210 West Chester, OH 45069 This report is for the

More information

ASTM E Fire Tests of Building Construction and Materials* Protective Structures, Ltd. Bullet-Resistant FRP Panel

ASTM E Fire Tests of Building Construction and Materials* Protective Structures, Ltd. Bullet-Resistant FRP Panel ASTM E119-98 Fire Tests of Building Construction and Materials* Protective Structures, Ltd. Bullet-Resistant FRP Panel Project No. 16410-108710 ONE-HOUR FIRE RESISTANCE TEST OF A NONBEARING STEEL STUD

More information

WFCi Report # Conducted For: Supress Products LLC. 5/8 Supress Sound-Engineered Drywall SED58410C; U305 Design

WFCi Report # Conducted For: Supress Products LLC. 5/8 Supress Sound-Engineered Drywall SED58410C; U305 Design Fire Performance Evaluation of a Load- Bearing 2 x 4 Wood Stud Wall Construction in Accordance With ASTM E119-05: Standard Test Methods for Fire Tests of Building Construction and Materials 5/8 Supress

More information

Product Test Summaries Nichiha Fiber Cement Products Sierra Premium Boards

Product Test Summaries Nichiha Fiber Cement Products Sierra Premium Boards Product Test Summaries Nichiha Fiber Cement Products Sierra Premium Boards Sierra Premium Certifications Test Summaries Certifications 1 ASTM C 1185 2 ASTM E 84/CAN/ULC S102-07 3 ASTM E 228 4 ASTM E 330

More information

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: April 30, 2013 REVISED DATE:

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: April 30, 2013 REVISED DATE: Page 1 of 9 REPORT NUMBER: 101145451SAT-001A ORIGINAL ISSUE DATE: April 30, 2013 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112 TEST REPORT

More information

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: December 18, 2012 REVISED DATE:

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: December 18, 2012 REVISED DATE: Page 1 of 9 REPORT NUMBER: 100986570SAT-001A ORIGINAL ISSUE DATE: December 18, 2012 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112 TEST REPORT

More information

REPORT NUMBER: SAT-002A ORIGINAL ISSUE DATE: August 16, 2017 REVISED DATE:

REPORT NUMBER: SAT-002A ORIGINAL ISSUE DATE: August 16, 2017 REVISED DATE: Page 1 of 9 REPORT NUMBER: 103188888SAT-002A ORIGINAL ISSUE DATE: August 16, 2017 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112 TEST REPORT

More information

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: March 13, 2017 REVISED DATE:

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: March 13, 2017 REVISED DATE: Page 1 of 9 REPORT NUMBER: 102855649SAT-001A ORIGINAL ISSUE DATE: March 13, 2017 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112 TEST REPORT

More information

REPORT NUMBER: SAT-001A Rev 1 ORIGINAL ISSUE DATE: November 16, 2010 REVISED DATE: June 20, 2011

REPORT NUMBER: SAT-001A Rev 1 ORIGINAL ISSUE DATE: November 16, 2010 REVISED DATE: June 20, 2011 Page 1 of 9 REPORT NUMBER: 100261621SAT-001A Rev 1 ORIGINAL ISSUE DATE: November 16, 2010 REVISED DATE: June 20, 2011 EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf,

More information

Title: WF Report No: Prepared for: Alstrong Enterprises India (PVT) Limited E-40/3, Okhla Industrial Area, New Delhi, India Date: 15 th June 2015

Title: WF Report No: Prepared for: Alstrong Enterprises India (PVT) Limited E-40/3, Okhla Industrial Area, New Delhi, India Date: 15 th June 2015 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: A fire resistance test performed

More information

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: March 13, 2013 REVISED DATE:

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: March 13, 2013 REVISED DATE: Page 1 of 9 REPORT NUMBER: 101095500SAT-001A ORIGINAL ISSUE DATE: March 13, 2013 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112 TEST REPORT

More information

SHOWER WALLS S.A. DE C.V. FIRE TEST REPORT

SHOWER WALLS S.A. DE C.V. FIRE TEST REPORT SHOWER WALLS S.A. DE C.V. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON CULTURED MARBLE SHOWER WALL REPORT NUMBER 103701089SAT-001 TEST DATE 10/23/18 ISSUE DATE 10/23/18 PAGES 11 DOCUMENT CONTROL

More information

DICKSON COATINGS FIRE TEST REPORT

DICKSON COATINGS FIRE TEST REPORT DICKSON COATINGS FIRE TEST REPORT SCOPE OF WORK ASTM E84-17a TESTING ON JET TEX WALL REPORT NUMBER 103427765SAT-001B TEST DATE(S) 2/28/18 ISSUE DATE 2/28/18 PAGES 10 DOCUMENT CONTROL NUMBER RT-R-AMER-Test-2780

More information

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: Page 1 of 9 REPORT NUMBER: 102490596SAT-001A ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112 TEST REPORT

More information

REPORT NUMBER: SAT-004A ORIGINAL ISSUE DATE: April 13, 2017 REVISED DATE:

REPORT NUMBER: SAT-004A ORIGINAL ISSUE DATE: April 13, 2017 REVISED DATE: Page 1 of 9 REPORT NUMBER: 102951522SAT-004A ORIGINAL ISSUE DATE: April 13, 2017 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112 TEST REPORT

More information

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON 18" OPEN WEB TRUSS WITH 3MM SONUS, HARDWOOD FLOOR AND SONUSCLIP CEILING SPECIMEN TYPE Open Web Truss -

More information

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: December 29, 2011 REVISED DATE:

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: December 29, 2011 REVISED DATE: Page 1 of 9 TEST REPORT REPORT NUMBER: 100582856SAT-001A ORIGINAL ISSUE DATE: December 29, 2011 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112

More information

DICKSON COATINGS FIRE TEST REPORT

DICKSON COATINGS FIRE TEST REPORT DICKSON COATINGS FIRE TEST REPORT SCOPE OF WORK ASTM E84-17a TESTING ON JET UP BC REPORT NUMBER 103427765SAT-001A TEST DATE(S) 2/27/18 ISSUE DATE 2/28/18 PAGES 10 DOCUMENT CONTROL NUMBER RT-R-AMER-Test-2780

More information

REPORT NUMBER: SAT-001D ORIGINAL ISSUE DATE: February 24, 2012 REVISED DATE:

REPORT NUMBER: SAT-001D ORIGINAL ISSUE DATE: February 24, 2012 REVISED DATE: Page 1 of 9 REPORT NUMBER: 100617566SAT-001D ORIGINAL ISSUE DATE: February 24, 2012 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112 TEST REPORT

More information

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: October 30, 2014 REVISED DATE:

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: October 30, 2014 REVISED DATE: Page 1 of 9 REPORT NUMBER: 101878070SAT-001B ORIGINAL ISSUE DATE: October 30, 2014 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112 TEST REPORT

More information

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON FUSION HYBRID OVER 2 MM ECOSILENCE UNDERLAYMENT SPECIMEN TYPE Vulcraft 2 Gage Dove Tail 3.5 Steel

More information

REPORT NUMBER: TOR-009 ISSUE DATE: October 15, EVALUATION CENTER Intertek 6225 Kenway Drive Mississauga, Ontario L5T 2L3 RENDERED TO

REPORT NUMBER: TOR-009 ISSUE DATE: October 15, EVALUATION CENTER Intertek 6225 Kenway Drive Mississauga, Ontario L5T 2L3 RENDERED TO REPORT NUMBER: 3196773TOR-009 ISSUE DATE: October 15, 2010 EVALUATION CENTER Intertek 6225 Kenway Drive Mississauga, Ontario L5T 2L3 TEST REPORT RENDERED TO NATIONAL GYPSUM COMPANY 2001 Rexford Road Charlotte,

More information

TEST REPORT. Acoustical Surfaces, Inc. ASTM E84-04 SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS. We Identify and S.T.O.P. Your Noise Problem

TEST REPORT. Acoustical Surfaces, Inc. ASTM E84-04 SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS. We Identify and S.T.O.P. Your Noise Problem Acoustical ASTM E84-04 TEST REPORT SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS Report No. 3081720-507 3497-010 Groove Prepared for: 120 Gilboa Street East Douglas, MA 01516 Intertek Testing Services

More information

calibrated gas flows from the room burner.

calibrated gas flows from the room burner. April 6, 2016 Hohmann & Barnard, Inc. 30 Rasons Court Hauppauge Hauppauge, New York 11788 WeAnchor@h-b.com RE: Summary Letter on Fire Performance of Polymer Based Brick-ties Exterior Wall Systems for Project

More information

EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 RENDERED TO

EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 RENDERED TO REPORT NUMBER: 3144559COQ-002B ORIGINAL ISSUE DATE: March 27, 2008 TEST REPORT EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 1500 BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 RENDERED TO GIGACRETE INC.

More information

ACOUSTICAL PERFORMANCE TEST REPORT

ACOUSTICAL PERFORMANCE TEST REPORT REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON 1MM REGUPOL SONUS SOUND CONTROL UNDERLAYMENT UNDER CERAMIC TILE SPECIMEN TYPE 23 mm Concrete Slab with

More information

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 8" Thick 3 Hour Fire Rated Panels SPEC ID: 29868

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 8 Thick 3 Hour Fire Rated Panels SPEC ID: 29868 LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 8" Thick 3 Hour Fire Rated Panels SPEC ID: 29868 Metl-Span, A Division of NCI Group, Inc. 1720 Lakepointe Drive, Suite 101 Lewisville, TX 75057 This report

More information

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E90 AND ASTM E492 TESTING ON ATTAIN LVT OVER 2 MM ECOSILENCE UNDERLAYMENT

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E90 AND ASTM E492 TESTING ON ATTAIN LVT OVER 2 MM ECOSILENCE UNDERLAYMENT VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON ATTAIN LVT OVER 2 MM ECOSILENCE UNDERLAYMENT SPECIMEN TYPE Vulcraft 2 Gage Dove 2. Tail Steel Deck

More information

FUNDERMAX GMBH LETTER OF RESULTS

FUNDERMAX GMBH LETTER OF RESULTS FUNDERMAX GMBH LETTER OF RESULTS SCOPE OF WORK ASTM E84 TESTING ON FUNDERMAX 13MM MAX COMPACT & 19MM MAX COMPACT REFERENCE PROJECT NUMBERS I0002.01-121-24-R0 & I0002.02-121-24-R0 TEST DATES 01/26/18 &

More information

Guardian Fire Testing Laboratories, Inc. Phone: ; Fax: Wenonah Terr. (Office) Lab Phone & Fax:

Guardian Fire Testing Laboratories, Inc. Phone: ; Fax: Wenonah Terr. (Office) Lab Phone & Fax: GUARDIAN Page 1 of 12 FIRE TESTING LABORATORIES, INC. Testing & Listing Field Labeling Engineering & Consulting Services Guardian Fire Testing Laboratories, Inc. Phone: 716 835 6880; Fax: 716 835 5682

More information

Title: WF Report No: Prepared for: International Petroleum Products Ltd Bradwell Hall Bradwell-On-Sea Essex CMO 7HX. Date: 24 th August 2015

Title: WF Report No: Prepared for: International Petroleum Products Ltd Bradwell Hall Bradwell-On-Sea Essex CMO 7HX. Date: 24 th August 2015 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The fire resistance performance

More information

URBAN SURFACES TEST REPORT

URBAN SURFACES TEST REPORT URBAN SURFACES TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON URBAN SURFACES SOUNDTEC REPORT NUMBER H4383.13311R TEST DATE 8/1/17 ISSUE DATE 8/16/17 RECORD RETENTION END 8/1/21 PAGES 13 DOCUMENT

More information

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No October 15, REPORT NO CRT-002d3

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No October 15, REPORT NO CRT-002d3 REPORT ACCREDITATION UNDER NVLAP 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 Order No. 3166866 October 15, 2013 REPORT NO. 3166866CRT-002d3 IMPACT SOUND TRANSMISSION TEST AND CLASSIFICATION OF LAMINATE FLOORING

More information

FIRE RESISTANCE TESTS OF BRICK VENEER / WOOD FRAME WALLS J. GREGG BORCHELT

FIRE RESISTANCE TESTS OF BRICK VENEER / WOOD FRAME WALLS J. GREGG BORCHELT FIRE RESISTANCE TESTS OF BRICK VENEER / WOOD FRAME WALLS J. GREGG BORCHELT Vice President Engineering and Research Brick Industry Association Reston, VA United States of America JOHN SWINK Regional Engineer

More information

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance Pei Evaluation Service is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Assembly Evaluation Report represents a product that Pei ES has Evaluated. This Assembly Evaluation

More information

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance

Assemblies Evaluated For 1. Non Axial Load Bearing Wall 2. Transverse Load Capacity 3. Fire Resistance 4. Abuse Resistance Pei Evaluation Service is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Assembly Evaluation Report represents a product that Pei ES has Evaluated. This Assembly Evaluation

More information

MILLENNIUM METALS, INC TEST REPORT

MILLENNIUM METALS, INC TEST REPORT MILLENNIUM METALS, INC TEST REPORT SCOPE OF WORK WIND DRIVEN RAIN RESISTANCE TESTING OF MMI 26 GA OFF RIDGE VENT WITH DETACHABLE BAFFLE REPORT NUMBER H7685.03-450-18 R1 TEST DATE 11/29/17 ISSUE DATE 12/18/17

More information

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 4" Thick 1 Hour Fire Rated Wall Panels SPEC ID: 29555

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 4 Thick 1 Hour Fire Rated Wall Panels SPEC ID: 29555 LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 4" Thick 1 Hour Fire Rated Wall Panels SPEC ID: 29555 Metl-Span, A Division of NCI Group, Inc. 1720 Lakepointe Drive, Suite 101 Lewisville, TX 75057 This

More information

ASTM E84-05 SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS

ASTM E84-05 SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS Page 1 of 9 ASTM E84-05 SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS Report No. 100057890SAT-001 Wallscapes III March 17, 2010 Prepared For: Ultraflex Systems Inc. 1578 Sussex Turnpike Bldg. #4

More information

REPORT NUMBER: TOR-002 ORIGINAL ISSUE DATE: June 28, 2013 EVALUATION CENTER RENDERED TO

REPORT NUMBER: TOR-002 ORIGINAL ISSUE DATE: June 28, 2013 EVALUATION CENTER RENDERED TO REPORT NUMBER: ORIGINAL ISSUE DATE: June 28, 2013 EVALUATION CENTER Intertek Testing Services Ltd. 6225 Kenway Drive Mississauga, Ontario L5T 2L3 TEST REPORT RENDERED TO 1792418 Ontario Inc. 108 Allingham

More information

LISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316

LISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316 LISTING INFORMATION OF International Beams - IB Series Joists SPEC ID: 27316 International Beams Inc. 2010 Boul. St-Elzear Quest Laval, QC H7L 3N4 CANADA This report is for the exclusive use of Intertek

More information

AUTHORIZATION TO MARK

AUTHORIZATION TO MARK AUTHORIZATION TO MARK This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set

More information

TEST REPORT. Acoustical Surfaces, Inc. ASTM E84-04 SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS. We Identify and S.T.O.P. Your Noise Problem

TEST REPORT. Acoustical Surfaces, Inc. ASTM E84-04 SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS. We Identify and S.T.O.P. Your Noise Problem Acoustical ASTM E84-04 TEST REPORT SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS Report No. 16715-124678 2537-040 Auster Pc# 41146001 Prepared for: 120 Gilboa Street East Douglas, MA 01516 OMEGA

More information

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E90 SOUND TRANSMISSION LOSS TESTING ON A STEEL STUD WALL ASSEMBLY WITH SONUSCLIP REPORT NUMBER H7677.03-113-11-R0 TEST DATE 11/20/17

More information

Prepared for: American Frame Manufacturing Co Bristow Court, Unit B San Diego, CA Phone: Web:

Prepared for: American Frame Manufacturing Co Bristow Court, Unit B San Diego, CA Phone: Web: TESTING LISTING EVALUATION 257 EAST RANDOLPH STREET NAPPANEE, INDIANA 46550 PHONE: 574-773-7975 WWW.NTAINC.COM TESTLAB@NTAINC.COM FAX: 574-773-2260 NEGATIVE WIND PRESSURE TEST ON EXTERIOR SHEATHING FOR

More information

BRE Global Test Report

BRE Global Test Report BRE Global Test Report Ad-hoc fire resistance test on a galvanised steel Tunnel Ventilation Damper employing procedures and criteria from BS 476: Part 20 : 1987. Prepared for: Betec Cad Industries Date:

More information

REPORT NUMBER: COQ-003 ORIGINAL ISSUE DATE: July 19, 2013

REPORT NUMBER: COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 TEST REPORT EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 1500 BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 CANADA RENDERED TO PHOENIX

More information

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 6" Thick 2-hour Fire Rated Panels SPEC ID: 29771

LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 6 Thick 2-hour Fire Rated Panels SPEC ID: 29771 LISTING INFORMATION OF Metl-Span, LLC THERMALSAFE 6" Thick 2-hour Fire Rated Panels SPEC ID: 29771 Metl-Span, A Division of NCI Group, Inc. 1720 Lakepointe Drive, Suite 101 Lewisville, TX 75057 This report

More information

Code Compliance Research Report CCRR-0228

Code Compliance Research Report CCRR-0228 Code Compliance Research Report CCRR-0228 Issue Date: 05-09-2017 Renewal Date: 05-11-2018 Revision Date: 06-23-2017 DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION Section: 07 40 00 Roofing and Siding

More information

RENDERED TO. CastleRock Building Products Incorporated P.O. Box 1258 Meridian, ID USA 83680

RENDERED TO. CastleRock Building Products Incorporated P.O. Box 1258 Meridian, ID USA 83680 REPORT NUMBER: 3173059COQ-008 ORIGINAL ISSUE DATE: April 28, 2009 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO CastleRock Building

More information

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post TEST REPORT Rendered to: SENTINEL FENCE AND RAIL For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post Report No: Report Date: 10/23/12 130 Derry Court York, PA 17406-8405

More information

LISTING INFORMATION OF Mitek Design No. MCI/WI SPEC ID: MiTek Canada, Inc. 100 Industrial Road Bradford, ON L3Z 3G7 Canada

LISTING INFORMATION OF Mitek Design No. MCI/WI SPEC ID: MiTek Canada, Inc. 100 Industrial Road Bradford, ON L3Z 3G7 Canada LISTING INFORMATION OF Mitek Design No. MCI/WI 60-02 SPEC ID: 27680 MiTek Canada, Inc. 100 Industrial Road Bradford, ON L3Z 3G7 Canada This report is for the exclusive use of Intertek s Client and is provided

More information

Prepared for: American Frame Manufacturing Co Bristow Court, Unit B San Diego, CA Phone: Web:

Prepared for: American Frame Manufacturing Co Bristow Court, Unit B San Diego, CA Phone: Web: TESTING LISTING EVALUATION 257 EAST RANDOLPH STREET NAPPANEE, INDIANA 46550 PHONE: 574-773-7975 WWW.NTAINC.COM TESTLAB@NTAINC.COM FAX: 574-773-2260 NEGATIVE WIND PRESSURE TEST ON EXTERIOR SHEATHING FOR

More information

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK AAMA 1801 TESTING ON IT451, STOREFRONT WINDOW REPORT NUMBER H7645.03-303-11 R0 TEST DATE 11/03/17 ISSUE DATE 11/17/17 RECORD RETENTION

More information

TEST REPORT. Acoustical Surfaces, Inc. ASTM E84-03 SURFACE BURNING CHARACTERISTICS. We Identify and S.T.O.P. Your Noise Problems

TEST REPORT. Acoustical Surfaces, Inc. ASTM E84-03 SURFACE BURNING CHARACTERISTICS. We Identify and S.T.O.P. Your Noise Problems Acoustical ASTM E84-03 TEST REPORT SURFACE BURNING CHARACTERISTICS Report No. 16715-120253 2823-026 Pc# 92686008 Hopscotch Prepared for: 120 Gilboa Street East Douglas, MA 01516 OMEGA POINT LABORATORIES,

More information

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK AAMA 1801 TESTING ON IT451, STOREFRONT WINDOW REPORT NUMBER H7645.02-303-11 R0 TEST DATE 11/03/17 ISSUE DATE 11/17/17 RECORD RETENTION

More information

Performance of wood stud shear walls exposed to fire. Kodur, V.R.; Sultan, M.A. NRCC-41733

Performance of wood stud shear walls exposed to fire. Kodur, V.R.; Sultan, M.A. NRCC-41733 Performance of wood stud shear walls exposed to fire Kodur, V.R.; Sultan, M.A. NRCC-41733 A version of this document is published in / Une version de ce document se trouve dans : Fire and Materials, v.

More information

NOVAWALL SYSTEMS, INC. ACOUSTICAL PERFORMANCE TEST REPORT

NOVAWALL SYSTEMS, INC. ACOUSTICAL PERFORMANCE TEST REPORT NOVAWALL SYSTEMS, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON A 2" NOVAWALL SQUARE EDGE SYSTEM REPORT NUMBER H8708.02-113-11-R0 TEST DATE 12/28/17 ISSUE

More information

9WOOD, INC. ACOUSTICAL PERFORMANCE TEST REPORT

9WOOD, INC. ACOUSTICAL PERFORMANCE TEST REPORT 9WOOD, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM C423 SOUND ABSORPTION TESTING ON 1000 SERIES SKU 1113-6 CROSS PIECE WOOD GRILLES WITH FIBERGLASS DUCT LINER REPORT NUMBER H5145.04-303-11

More information

Testing in Accordance with SFM Standard 12-7A-1: Fire Resistive Standard for Exterior Wall Siding and Sheathing

Testing in Accordance with SFM Standard 12-7A-1: Fire Resistive Standard for Exterior Wall Siding and Sheathing Testing in Accordance with SFM Standard 12-7A-1: Fire Resistive Standard for Exterior Wall Siding and Sheathing LP FlameBlock Fire-Rated OSB Sheathing (7/16 Minimum Nominal Thickness) with Various Claddings:

More information

TEST REPORT. Acoustical Surfaces, Inc. ASTM E84-03 SURFACE BURNING CHARACTERISTICS. We Identify and S.T.O.P. Your Noise Problem.

TEST REPORT. Acoustical Surfaces, Inc. ASTM E84-03 SURFACE BURNING CHARACTERISTICS. We Identify and S.T.O.P. Your Noise Problem. Acoustical ASTM E84-03 TEST REPORT SURFACE BURNING CHARACTERISTICS Report No. 16715-118472 Spinel 3582-070 Prepared for: 120 Gilboa Street East Douglas, MA 01516 OMEGA POINT LABORATORIES, INC. 16015 Shady

More information

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: WIRE-BOND. SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall)

ASTM C THERMAL PERFORMANCE TEST REPORT. Rendered to: WIRE-BOND. SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall) ASTM C 1363-11 THERMAL PERFORMANCE TEST REPORT Rendered to: WIRE-BOND SERIES/MODEL: Masonry Tie Thermal Evaluations (2x6 Steel Stud Wall) TYPE: Masonry Wall Assembly Summary of Results Test Unit R-Value

More information

TEST REPORT. Fire resistance load-bearing test of a 136mm thick Ozone Panels wall system tested in accordance with AS

TEST REPORT. Fire resistance load-bearing test of a 136mm thick Ozone Panels wall system tested in accordance with AS TEST REPORT Fire resistance load-bearing test of a 136mm thick Ozone Panels wall system tested in accordance with AS 1530.4 2005. EWFA Report No: 2758400 Report Sponsor: Ozone Panels Level 31, 367 Collins

More information

TEST REPORT. Bushfire resistance test of an external wall system to BAL A40 in accordance with AS EWFA Report No:

TEST REPORT. Bushfire resistance test of an external wall system to BAL A40 in accordance with AS EWFA Report No: TEST REPORT Bushfire resistance test of an external wall system to BAL A40 in accordance with AS1530.8.1-2007 EWFA Report No: 38031900.1 Report Sponsor: Ullrich Aluminium PO BOX 246 Carole Park QLD 4300

More information

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT

VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT VULCRAFT/VERCO GROUP ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9 AND ASTM E492 TESTING ON CERAMIC TILE OVER 5 MM ECOSILENCE UNDERLAYMENT SPECIMEN TYPE Vulcraft 2 Gage Dove Tail 3.5 Steel Deck

More information

Report on Structural Stability of Engineered Lumber in Fire Conditions Project Number: 08CA33476 File Number: NC10412

Report on Structural Stability of Engineered Lumber in Fire Conditions Project Number: 08CA33476 File Number: NC10412 Report on Structural Stability of Engineered Lumber in Fire Conditions Project Number: 08CA33476 File Number: NC10412 Underwriters Laboratories Inc. 333 Pfingsten Road, Northbrook, IL 60062 Submitted to

More information

WESTERN SPINDLE LLC TEST REPORT

WESTERN SPINDLE LLC TEST REPORT WESTERN SPINDLE LLC TEST REPORT SCOPE OF WORK STRUCTURAL PERFORMANCE TESTING ON THE 12 FOOT BY 42 INCH URETHANE BALUSTRADE SYSTEM REPORT NUMBER 80916.02-119-19 R0 TEST DATE 04/11/08 ISSUE DATE 09/24/18

More information

Test Report: Fire resistance test in accordance with BS EN :1999 on a nonloadbearing. incorporating Scolmore Doubled Switched electrical sockets

Test Report: Fire resistance test in accordance with BS EN :1999 on a nonloadbearing. incorporating Scolmore Doubled Switched electrical sockets Test Report: Fire resistance test in accordance with BS EN 1364-1:1999 on a nonloadbearing wall incorporating Scolmore Doubled Switched electrical sockets Prepared for: Scolmore International Limited,

More information

TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey

TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey TEST REPORT Report No.: F399.01-109-44 Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey PRODUCT TYPE: ACP Panel System (Dry Seal) SERIES/MODEL: Dry Econect-RS Title Design Pressure Air Infiltration

More information

AIR INFILTRATION TESTING

AIR INFILTRATION TESTING AIR INFILTRATION TESTING Prepared for Norbord Prepared by NAHB Research Center 400 Prince George s Blvd Upper Marlboro, MD 20774 www.nahbrc.com September 21, 2009 America s Housing Technology and Information

More information

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT

REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT REGUPOL AMERICA ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK ASTM E9, ASTM E492, AND ASTM E2179 TESTING ON 4X SOUNDPANEL WITH AKUSTIPRO 8 RUBBER TILE SPECIMEN TYPE Concrete Slab - 152 mm REPORT NUMBER

More information

QUANEX BUILDING PRODUCTS TEST REPORT

QUANEX BUILDING PRODUCTS TEST REPORT QUANEX BUILDING PRODUCTS TEST REPORT SCOPE OF WORK DUAL PANE INSULATING GLASS UNIT PERFORMANCE & GAS EVALUATION REPORT NUMBER H1694.01-119-28 TEST DATE(S) 05/24/17-09/28/17 ISSUE DATE 10/18/17 RECORD RETENTION

More information

Carter Fabricating Inc. 326 Deerhurst Drive Brampton, Ontario L6T 5H9. Mr. Mike Libreiro

Carter Fabricating Inc. 326 Deerhurst Drive Brampton, Ontario L6T 5H9. Mr. Mike Libreiro PERFORMANCE EVALUATION OF THE CARTER FABRICATING INC. EVO RIVETLESS PANEL SYSTEM WALL ASSEMBLY FOR AIR INFILTRATION, WATER PENETRATION AND STRUCTURAL PERFORMANCE Report to: Carter Fabricating Inc. 326

More information

FIRE TEST REPORT FP 5663

FIRE TEST REPORT FP 5663 1222 Moonshine Road Judgeford RD1 Porirua 5381 New Zealand T +64 4 237 1170 F +64 4 237 1171 branz@branz.co.nz www.branz.co.nz FIRE TEST REPORT FP 5663 FIRE RESISTANCE OF PIPE PENETRATIONS IN A 60 MINUTE

More information

BS :2005 test on a Kingspan Benchmark External Wall Insulation System

BS :2005 test on a Kingspan Benchmark External Wall Insulation System BS 8414-2:2005 test on a Kingspan Benchmark External Wall Insulation Prepared for: Kingspan Ltd. Carrickmacross Road Kingscourt County Cavan Ireland 7 September 2011 0578 Page 1 of 30 Prepared on behalf

More information

LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848

LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848 LISTING INFORMATION OF International Fireproof Technology Inc. - Joint Systems SPEC ID: 43848 International Fireproof Technology Inc. 17528 Von Karman Avenue Irvine, CA 92614 This report is for the exclusive

More information

research report Fire Resistance Ratings of Load Bearing Steel Stud Walls With Gypsum Wallboard Protection RESEARCH REPORT RP REVISION 2007

research report Fire Resistance Ratings of Load Bearing Steel Stud Walls With Gypsum Wallboard Protection RESEARCH REPORT RP REVISION 2007 research report Fire Resistance Ratings of Load Bearing Steel Stud Walls With Gypsum Wallboard Protection RESEARCH REPORT RP81-1 1981 REVISION 2007 American Iron and Steel Institute Fire Resistance Ratings

More information

LISTING INFORMATION OF SIPA - Structural Insulated Panels (SIPs) SPEC ID: Structural Insulated Panel Association (SIPA) P.O.

LISTING INFORMATION OF SIPA - Structural Insulated Panels (SIPs) SPEC ID: Structural Insulated Panel Association (SIPA) P.O. LISTING INFORMATION OF SIPA - Structural Insulated Panels (SIPs) SPEC ID: 32805 Structural Insulated Panel Association (SIPA) P.O. Box 39848 Fort Lauderdale, FL 33339 This report is for the exclusive use

More information

ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015.

ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-2847 Reissued September 1, 2013 This report is subject to renewal September 1, 2015. A Subsidiary of the International Code Council

More information

KNOTWOOD, A DIVISION OF OMNIMAX INTERNATIONAL MIAMI-DADE TEST REPORT

KNOTWOOD, A DIVISION OF OMNIMAX INTERNATIONAL MIAMI-DADE TEST REPORT KNOTWOOD, A DIVISION OF OMNIMAX INTERNATIONAL MIAMI-DADE TEST REPORT SCOPE OF WORK TAS 201, TAS 202, AND TAS 203 TESTING ON KNOTWOOD, ALUMINUM POWDER-COATED CLADDING REPORT NUMBER I6115.01-109-18 TEST

More information

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana Architectural Testing TEST REPORT Report No.: D0162.01-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite

More information

LEGACY REPORT Reissued October 1, Legacy report on the BOCA National Building Code/1999

LEGACY REPORT Reissued October 1, Legacy report on the BOCA National Building Code/1999 LEGACY REPORT 90-26.01 Reissued October 1, 2003,&&(YDOXDWLRQ6HUYLFH,QF www.icc-es.org Business/Regional Office 5360 Workman Mill Road, Whittier, California 90601 (562) 699-0543 Regional Office 900 Montclair

More information

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No Date: May 24, 2008 REPORT NO CRT-001

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK Order No Date: May 24, 2008 REPORT NO CRT-001 REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 Order No. 3151742 Date: May 24, 2008 REPORT NO 3151742CRT-001 IMPACT SOUND TRANSMISSION TEST AND CLASSIFICATION OF LM FLOORING ½ INCH ENGINEERED HARDWOOD

More information

Carter Architectural Panels Inc. 221 E. Willis Road A Unit 18 Chandler, AZ Mr. Bruce Bourne

Carter Architectural Panels Inc. 221 E. Willis Road A Unit 18 Chandler, AZ Mr. Bruce Bourne PERFORMANCE EVALUATION OF THE CARTER ARCHITECTURAL PANELS INC. FUSION TM DRILLFREE TM PANEL SYSTEM WALL ASSEMBLY FOR AIR INFILTRATION, WATER PENETRATION AND STRUCTURAL PERFORMANCE Report to: Carter Architectural

More information

SAN DIEGO STATE UNIVERSITY PACIFIC CORNERSTONE ARCHITECTS TENOCHCA HALL PROJECT NO FAN COIL UNITS, RESTROOM AND FINISH RENOVATION

SAN DIEGO STATE UNIVERSITY PACIFIC CORNERSTONE ARCHITECTS TENOCHCA HALL PROJECT NO FAN COIL UNITS, RESTROOM AND FINISH RENOVATION SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Various gypsum board panels types. 2. Joint treatment materials. 3. Panel trim. 4. Supplementary components and accessories

More information

Technical Features Fire Construction There Is A Difference In Drywall

Technical Features Fire Construction There Is A Difference In Drywall Technical Features Fire Construction There Is A Difference In Drywall UNIQUE FORMULATIONS GIVE U. S. GYPSUM DRYWALL EXCEPTIONAL FIRE PERFORMANCE (Editor s Note: This article originally appeared in the

More information

Test Summaries: AWP 1818 & 3030

Test Summaries: AWP 1818 & 3030 Test Summaries: AWP 1818 & 3030 ASTM C 1185/6 - Physical Properties Tests ASTM C 518 - Steady-State Heat Flex & Thermal Tests (R-Value) ASTM E 84 - Surface Burning Characteristics CAN/ULC - S102 Surface

More information

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to URBAN SURFACES. Series/Model: Urban Surfaces Soundtec

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to URBAN SURFACES. Series/Model: Urban Surfaces Soundtec ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to URBAN SURFACES Series/Model: Urban Surfaces Soundtec Specimen Type: 152 mm Concrete Slab with Drop Ceiling Overall Size: 3048 mm

More information

TEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia

TEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia TEST REPORT Report No.: H3615.01-550-44 Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia PRODUCT TYPE: EIFS Panel Systems SERIES/MODEL: GP ForceField Air & Water Barrier Sheathing with

More information

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio Architectural Testing TEST REPORT Report No.: B2739.02-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Air Barrier System SERIES/MODEL: ExoAir 230, ProGlaze ETA System 1, Spectrem

More information

PROJECT NUMBER: ISSUE DATE: EXPIRY DATE: PAGE: FT March March of 28

PROJECT NUMBER: ISSUE DATE: EXPIRY DATE: PAGE: FT March March of 28 1222 Moonshine Road Judgeford RD1 Porirua 5381 New Zealand T +64 4 237 1170 F +64 4 237 1171 branz@branz.co.nz www.branz.co.nz BRANZ Type Test FR 5740-TT [2016] FIRE RESISTANCE OF A LOAD BEARING TIMBER

More information

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Determination of the fire resistance according to EN 1364-1:1999 and FprEN 1364-1:2014

More information

Not to be distributed outside of FM Global except by Customer

Not to be distributed outside of FM Global except by Customer Not to be distributed outside of FM Global except by Customer APPROVAL REPORT APPROVAL OF HILTI CABLE TRANSIT SYSTEM CFS-T FOR USE IN WALL AND FLOOR ASSEMBLIES RATED UP TO AND INCLUDING 2 HOURS Prepared

More information

Duct Wrap Flexible Wraps

Duct Wrap Flexible Wraps Design No. 3MU/ 60-01 December 23, 2010 VENTILATION DUCT PROTECTION 3M Company 3M Fire Barrier Duct Wraps: 615 and 615+ 3M Fire Barrier Sealants: Water-Tight 1000-NS Silicone, Water-Tight 1003-SL Silicone

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1 ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: ACOUSTIBLOK, INC. WALL ASSEMBLY: #1 TYPE: Standard 8" Hollow Block Wall With Single Stud Wall Construction SOUND ISOLATION MATERIAL: Acoustiblok

More information