1 City of Jacksonville Beach Purchasing Division 1460A Shetter Avenue Jacksonville Beach, FL Tel: (904) Fax: (904) THIS IS NOT THE COMPLETE PACKAGE INVITATION TO BID BID NUMBER: TITLE: WIRE AND CABLE BID SUBMITTAL DEADLINE: Day / Date: Wednesday, August 21, 2013 Time: 2:00 p.m. Location: City of Jacksonville Beach Purchasing Division 1460A Shetter Avenue, 2 nd Floor Jacksonville Beach, FL Jason Phitides Jason Phitides, Purchasing Administrator 1460A Shetter Avenue, Jacksonville Beach, FL Page 1 of 9 BID TENDER FORM

2 THIS IS NOT THE COMPLETE PACKAGE INVITATION TO BID Sealed bids in DUPLICATE, subject to the terms and conditions specified in this Invitation to Bid (ITB), will be received until 2:00pm, Wednesday, August 21, 2013, then opened publicly by the Purchasing & Procurement Division, 1460A Shetter Avenue, 2 nd Floor, Jacksonville Beach, Florida for furnishing the following: Wire and Cable for the City of Jacksonville Beach, d/b/a Beaches Energy Services for a period of one year, with an option to renew the contract for two (2) additional years, if mutually agreeable to both parties and if the vendor will hold bid prices (or Initial Prices) firm for the second and third years. THESE SPECIFICATIONS ARE INTENDED AS MINIMUM REQUIREMENTS FOR THE PROCUREMENT OF THE ITEMS LISTED HEREIN. Bid Number WIRE AND CABLE Bid packages can be obtained from the Purchasing & Procurement Division, 1460A Shetter Avenue, 2 nd Floor, Jacksonville Beach, Florida 32250, telephone Please submit bids to the same address. Please submit duplicate completed Bid Package in one sealed envelope clearly marked with bid number and bidder name. It is incumbent upon the Bidders to ensure that all copies of the Bid Package submittal are complete and exact replicas of each other. Packages received without the requested information or quantities may be rejected. Place the sealed envelope within another sealed envelope clearly marked in the same manner as the first envelope. This is done to prevent accidental opening of the sealed submittals in our mailroom. Please mark on the envelope SEALED BID ENCLOSED. The Bidder shall be solely responsible for delivery of the bid. Reliance upon mail or public carriers is at the Bidder s risk. Submissions, received after the due date and time, are late and will not be considered. Modifications received after the due date and/or letters of withdrawal received after the due date or after contract award, whichever is applicable, are also late and will not be considered. No verbal interpretations will be made of any documents. Requests for such interpretations shall be made in writing or via Purchasing@jaxbchfl.net at least seven (7) days prior to the bid/proposal opening date. Interpretation will be in the form of an addendum and issued to all bidders. CITY OF JACKSONVILLE BEACH Jason Phitides Purchasing Administrator Purchasing & Procurement Division Page 2 of 9 BID TENDER FORM

3 THIS IS NOT THE COMPLETE PACKAGE SPECIFICATIONS FOR WIRE AND CABLE FOR THE CITY OF JACKSONVILLE BEACH, FL. (dba/beaches ENERGY SERVICES) General: Shipping: Quantities: It is the intent of this bid document to procure Wire and Cable for the City of Jacksonville Beach, Florida for a period of one year, with an option to renew the contract for two (2) additional years, if mutually agreeable to both parties and if the vendor will hold bid prices (or Initial Prices) firm for the second and third years. THESE SPECIFICATIONS ARE INTENDED AS MINIMUM REQUIREMENTS FOR THE PROCUREMENT OF THE ITEMS LISTED HEREIN. ALL WIRE AND CABLE SHALL BE DELIVERED IN OPEN TOP TRAILERS. The estimated quantities contained herein reflect an approximate annual usage. The City may elect to purchase more of any item and the estimated quantities shall in no way restrict the number of any units purchased. The Initial Price, as bid, shall remain firm for the duration of the contract. (This Initial Price will be used to calculate the escalation or de-escalation of the actual Purchase Price, in accordance with changes in the metal price indices, as described in Section 3., Prices.) Numbers: Delivery: Specific industry-recognized wire and cable code names and detailed technical specifications have been provided to assist the bidders and help clarify the specifications for the Wire and Cable. The specifications still take precedence and it is the bidder s responsibility to determine that each manufacturer s Wire or Cable, as bid, meets the specifications. If there are any exceptions, they are to be clearly noted with the bid documents. The Wire and Cable shall be delivered FOB Destination to the City of Jacksonville Beach Storeroom located at 1460A Shetter Avenue, Jacksonville Beach, FL during normal City hours of business. At least 48 hours notice must be given prior to delivery to enable the City to arrange for unloading. Notice will be given to: Donna Baity City of Jacksonville Beach 1460A Shetter Avenue Jacksonville Beach, Florida (904) Page 3 of 9 BID TENDER FORM

4 BID SPECIFICATIONS 1. GENERAL 1.1 This section covers the general purchase specifications to procure wire and cable for the City of Jacksonville Beach, Florida for a period of one year, with an option to renew the purchase order for two (2) additional years, if mutually agreeable by both parties and if the vendor will hold his Initial Price firm for the second and third year. 1.2 The wire and cable shall be as specified herein and as indicated on the Technical Specifications and Data Sheets included in these Specifications. 2. CODES AND STANDARDS 2.1 The wire and cable shall be designed and fabricated in accordance with applicable AEIC, ANSI, ASTM, ICEA, IEEE, NEMA, and UL Standards. 2.2 All materials and devices shall be in accordance with applicable requirements of the Federal "Occupational Safety and Health Standards". 3. PRICES 3.1 Escalation/De-escalation Bid prices shall remain firm from the date of the bid award until the last day of the month of the bid award. On the first business day of each month, following the first month, the Current Prices (or actual Purchase Prices) will be changed according to the change in the metals price index, as described in Paragraphs 3.2 through 3.6, below. The Current Price (or actual Purchase Price) is the amount that will be on the Purchase Order for each order of wire or cable, and the amount that will be paid after delivery of each order. 3.2 Prices bid (or Initial Prices), including payment discount if applicable, shall be used for payment and these prices shall be deemed to include payment in full for all transportation, labor and equipment used in delivering all supplies to the point of delivery. All items to be provided under this Contract shall be new (not used or reconditioned, and not of such age or so deteriorated as to impair their usefulness or safety), of current production and of the most suitable grade for the purpose intended. 3.3 Bidders shall provide unit bid prices (or Initial Prices), in dollars per thousand feet for each item listed on the bid forms assuming copper or aluminum, as appropriate, is the price per pound shown on the bid forms. This initial metal price shall be the most recent price available to the City of Jacksonville Beach and as published in American Metal Market Closing Prices or Platts Metals Monthly Averages. The aluminum price used shall be for Unalloyed Ingot, NY merchant, 99.7%, delivered Midwest, and shall be shown in U.S. dollars per pound. The copper price shall be for either Platts or Comex, high-grade electrolytic cathode, Spot, and shall be shown in U.S. dollars per pound. The bid price (or Initial Price), provided by the bidder shall be the basis for evaluation and award of the bid and shall constitute the firm price for the materials listed for the first month following the bid award. Page 4 of 9 BID TENDER FORM

5 Thereafter, on the first business day of each succeeding month, the price for each item will be adjusted according to the change in the copper price as published in American Metal Market or Platts Metals and described above and the change in aluminum price as published in American Metal Market or Platts Metals and described above. Specifically, the Current Price for an item will be calculated according to the following formula: CP = IP + {(NCP ICP) * CC} + {(NAP IAP) * AC} where: CP is the Current Price for an item in $/1000 feet; IP is the Initial Price (Bid Price) for the same item in $/1000 feet; NCP is the New Copper Price published on the last business day of the preceding month in $/pound; ICP is the Initial Copper Price listed on the bid forms in $/pound; CC is the Copper Content in lb/1000 feet, as provided by bidder on the bid forms; NAP is the New Aluminum Price published on the last business day of the preceding month in $/pound; IAP is the Initial Aluminum Price listed on the bid forms in $/pound; and, AC is the Aluminum Content in pounds/1000 feet, as provided by the bidder on the bid forms. It shall be the responsibility of the awarded bidder(s) to forward to the City of Jacksonville Beach the copper and aluminum price as described above, published on the last business day of the preceding month. These prices shall be sent to the City of Jacksonville Beach by noon on the first business day of each month. 3.4 No bidder will be allowed to offer more than one price on each item, even if the bidder has two or more types or styles that would meet specifications. Bidders must determine for themselves which to offer. 3.5 Provide both unit price and extend and total. Prices must be stated in units of quantity specified in the bidding specifications. In case of discrepancy in computing the amount of the bid, the Unit Price quoted will govern. Each item must be bid separately and no attempt is to be made to tie any item or items together with any other item or items, unless specifically stated otherwise in these Terms and Conditions. Unless a Bidder offers a discount on payment terms, it is understood that a minimum of 30 days will be required for payment, with time being computed from the latter of the date of satisfactory delivery at place of acceptance and receipt of correct invoice at the office specified. Payment discounts, if offered, shall be as requested by these Terms and Conditions and/or bid terms. 3.6 Any and all discounts, other than a payment discount, must be incorporated as a reduction in the bid price and not shown separately. The price as shown on the bid shall be the price used in determining award(s). 4. HONORING PRICES, TERMS AND CONDITIONS Bidder warrants, by virtue of bidding, that orders placed within the specified period shall be honored at the prices, terms, and conditions quoted. Page 5 of 9 BID TENDER FORM

6 5. City of Jacksonville Beach Technical Specifications for Medium Voltage 28 kv TRXLP Insulated URD Cable Scope: To furnish complete, factory pre-assembled 28 kv cable, designed for installation on a grounded wye system having a distribution primary voltage of 15,240/26,400 volts. This cable shall be suitable for underground, or interior power circuits in either wet or dry applications, and are used for primary distribution in power plants and URD and network feeder applications, transformer and generator leads apparatus connections and vertical risers where high reliability and long life are desired, and where higher temperatures may be encountered. Applicable Standards: All cable shall conform to all applicable National Electrical Manufactures Association (NEMA), Association of Edison Illuminating Companies (AEIC), American Standards for Testing Materials (ASTM), Underwriters' Laboratories (UL), and Insulated Cable Engineers Association (ICEA) standards. Designations: TRXLP cables shall have an extruded semi-conducting material applied on the conductor, followed by the insulation, with a semi-conducting shield, solid coated copper concentric neutral wires applied spirally, all protected with a low density polyethylene compound jacket. The maximum continuous operating temperature of conductor, at rated load, shall be limited to 90 degrees Celsius, the emergency operating temperature shall not exceed 130 degrees Celsius, and the short circuit operating temperature shall not exceed 250 degrees Celsius as per the latest revision AEIC. Conductor: Aluminum conductor shall be hard drawn, Class B, stranded, central grade 1350, compressed conductor. Concentric - a conventional concentric untinned copper conductor, in accordance with ASTM specifications, is to be furnished for single conductor cables. Solid copper concentric neutral wires shall be spirally applied and the entire assembly covered with a LLDPE jacket. Strand filling - in order to alleviate water (electrochemical) treeing in the insulation, strand-filling compound will completely fill the conductor's inner strand layer(s). This compound shall be flexible and stable under the conditions imposed by the cable's operation within limits stipulated herein, and compatible with the conductor, strand shield and insulation materials per ICEA Publication T The outer strand layer of the conductor shall be clean from the filling compound so that splices and terminations can be readily applied using standard compression type connectors employing the same techniques as for unfilled conductors. Copper conductors are to be composed of untinned soft or annealed concentric copper wires and conforming to reduce diameter compressed formation meeting, before stranding physical requirements of ASTM specifications. Page 6 of 9 BID TENDER FORM

7 Conductor Shielding: This cable shall have an extruded super smooth semiconducting shield (HFDA-0800 or HFDA-0802 or LE-0504 or LE-0500) applied directly on the conductor for stress relief and better adhesion of the insulation, and be compatible with the insulation material. LE-0594 or LE is also allowed. HFDA 0802, LE 0504 and LE0594 are only allowed for use with aluminum conductors. Insulation: The insulation thickness shall meet or exceed 100% of the recommended voltage rated insulation. Insulation shall be free of contamination of any kind. The cable shall consist of thermosetting extruded, unfilled, tree retardant cross-linked polyethylene (TRXLPE) insulation (HFDB-4202 or LE-4212) directly over the conductor shield, and free of contamination of any kind. The extrusion shall be smooth, free from voids and imperfections, and have uniform thickness with the conductor well centered. The insulation diameter shall be in accordance with ICEA. Insulation Shielding: Extruded semiconducting shield (HFDA-0693 or LE-0310) shall be used between the insulation and the outer jacket to relieve stress. The insulation shield diameter shall be in accordance with ICEA. Jacket: For corrosion protection in duct installations as well as in other types of installation, the cable shall be jacketed with a Linear Low Density Polyethylene Compound. The jacket shall be extruded to encapsulate the concentric and shall be free stripping. The jacket thickness shall be in accordance with the applicable section of ICEA. This jacket is to be applied without contamination or oil between the jacket and cable, and shall be suitable for exposure to direct sunlight. A water swellable powder or tape shall be applied between the insulation shield and the jacket to block the ingress of moisture into and along the interface and around the concentric wires of the cable. Assembly: The cable shall be assembled in a continuous single run in the same head, free from contamination, and dry cured. It shall be assembled with the insulation shield as one congruous smooth bond to minimize insulation stress. The cable shall be assembled in lengths specified for each cable size on the purchase order. Dimensions and Data: Prior to manufacturing, the successful bidder shall be required to provide a cross sectional drawing of the cable and dimensions, including: outside diameter; diameter over conductor shield; diameter over insulation; diameter over insulation shield. The dimensions provided must be given with plus and minus tolerances. Ampacities, impedance values and cable weight per thousand feet (lbs./1000ft) shall also be included. This information shall be mailed within 10 days ARO to Steve Lancaster; City of Jacksonville Beach; 1460A Shetter Avenue, Jacksonville Beach, FL Identification: The cable shall have permanent contrasting marking (indented or hot foil tape) on the jacket at interval not to exceed five feet. The marking on each cable jacket shall contain the manufacturer s name, plant designation, conductor size and type, insulation and wall thickness, voltage rating and year of manufacture. Sequential footage markings shall be applied at a maximum of every three feet on all single conductor cables. Page 7 of 9 BID TENDER FORM

8 Markings shall meet the requirements of AEIC. Shipping: Each reel shall be shipped complete with protective cover and I.D. marking for storage. The reels must be able to withstand shipping, handling and storage for at least one year without decomposition. Heat shrink type cable end caps shall be installed on each cable end. Non-returnable wood reels shall meet the requirements of NEMA WC-26, Class II (Note: Arbor holes minimum diameter allowed 3-1/4 ). Any material shipped to BES and deemed Unacceptable shall be returned to the manufacturer at his expense. General: The cable shall be built in a clean environment as a continuous run, complete, factory assembled and packaged. The finished product shall be free of defect and able to operate on nominal system voltage of 15,240/26,400 volts. Approved Manufacturers: Listed below are the current approved cable manufacturers. Canada Wire Phillips Cables Bekaert CPI Pirelli PRYSMIAN Nexans Nehring Hendrix Alcan Southwire BICC General Okonite Construction: URD TRXLP cable shall consist of filled strand central conductor with a semiconducting conductor shield, insulation, insulation shield, concentric stranded neutral and an outer encapsulating jacket according to the latest AEIC specifications. Packaging: Provide the smallest reel required to meet the designated cable length. The reel dimensions indicated reflect the maximum size allowable. Reel length tolerance is -0% + 10%. CJB Min Max Stock Conductor Reel Reel Item No. Size Concentric Length (ft) Size (28 Kv) /0 11 #14 AWG 2,000 NR58x MCM 18 #14 AWG 1,000 NR72x36 (or 60x00, if requested.) (600 v) T N/A 1,000 NR /0 N/A 1,000 NR50.32 Proof Testing: Each length of cable shall be tested in accordance with AEIC Specifications. The results of all production tests shall be mailed within 30 days of shipment to Steve Lancaster; City of Jacksonville Beach, 1460A Shetter Avenue, Jacksonville Beach, FL The City of Jacksonville Beach reserves the right to subject cable to test by a recognized laboratory before it leaves the factory. Page 8 of 9 BID TENDER FORM

9 Certified test reports shall be furnished on all cables shipped. The report shall include the master reel numbers, CBJ Stock item No. purchase order number, shipping reel number(s) and the actual test results compared to the required values. The conductor shield, insulation and insulation shield compound designation shall also be included in the certified test report. Each length of cable shall be tested in accordance with AEIC specifications. ICEA T Guide For Conducting Longitudinal Water Penetration Resistance Tests On Longitudinal Water Blocked Cables shall be used to test the entire cable cross section at 10 PSIG for embedded jacket cables and 5 PSIG for modified overlaying jacket cables. Water block test is not required on tape shielded cable designs. 6. WIRE AND CABLE BID DATA CITY OF JACKSONVILLE BEACH, FL. REEL EST. MIN DESCRIPTION CODE SIZE JB# USE/ft STK/ft 1 #4/0 Al, 28kV URD N/A ,000 0 Cable per Jax Bch Tech. Specifications kcmil Al, 28kV N/A , URD cable per Jax Bch Tech. Spec s kcm USE AL Weslayan ,000 3,000 Triplex, 600V XLP insulation 4 4/0 CU, THW N/A , stranded, 600 volt THE CITY OF JACKSONVILLE BEACH RESERVES THE RIGHT TO PURCHASE MORE OF ANY ITEM AND THE ESTIMATED QUANTITIES SHALL IN NO WAY RESTRICT THE NUMBER OF ANY UNITS PURCHASED. ALL WIRE & CABLE MUST BE QUOTED PRICE PER THOUSAND FEET (M/FT). THE CITY OF JACKSONVILLE BEACH AGREES TO PURCHASE REMAINING VENDOR STOCK AT EXPIRATION OF THIS BID IN AMOUNTS NOT TO EXCEED THE MINIMUM STOCKING QUANTITY FOR EACH ITEM. To request a bid package, please contact the Purchasing Division at: Purchasing@jaxbchfl.net or call Page 9 of 9 BID TENDER FORM

3 MODIFICATIONS TO EXISTING STANDARDS

3 MODIFICATIONS TO EXISTING STANDARDS 1 SCOPE This specification covers the requirements for 25 kv rated single-phase primary cable with shielded concentric neutral and an insulating jacket. The cable may be used in single or multi-phase application

More information

15 kv EPR Insulated, Jacketed, URD Cable

15 kv EPR Insulated, Jacketed, URD Cable 15 kv EPR Insulated, Jacketed, URD Cable 1000 kcm Copper Conductor with Tape Shield Page 1 of 11 Table Of Contents 1 GENERAL... 3 2 STANDARDS... 3 3 APPROVED CABLE MANUFACTURERS... 3 4 REEL SPECIFICATIONS...

More information

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION

SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION SOUTH CAROLINA ELECTRIC COOPERATIVES' PRIMARY UNDERGROUND POWER CABLE SPECIFICATION 1.0 SCOPE 1.1 This specification covers the construction, mechanical, and electrical requirements of single conductor,

More information

Clark Public Utilities

Clark Public Utilities Clark Public Utilities TECHNICAL SPECIFICATIONS 15KV MEDIUM VOLTAGE 1000 MCM AL URD CABLE 175 MIL EPR FEBRUARY 1994 REVISED MAY 1996 REVISED JUNE 2001 REVISED MARCH 2002 REVISED MARCH 2005 REVISED MAY

More information

*** Supercedes: BECO E and COM , , & ***

*** Supercedes: BECO E and COM , , & *** 7/27/09 Page 1 of 9 R5 *** Supercedes: BECO E2.9-27.4 and COM 1-0696, 2-0196, & 5-0385 *** 1.0 Scope #2 AWG to 1000 KCMIL CONCENTRIC NEUTRAL JACKETED CABLES RATED 5-35 kv These Specifications cover single

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990) WESTERN UNDERGROUND COMMITTEE GUIDE 2.14 (2.14/01/0990) ABRASION RESISTANT 600V CABLE NOTE: This "Guide" summarizes the opinions, recommendations, and practices of the Western Underground Committee members

More information

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR

Section ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR PART 1 - GENERAL Section 26 05 15 SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR 1.1 Cable shall be 15 kv, shielded, three conductor with ground, stranded copper, with continuously welded and corrugated

More information

017-17 Appendix B Reponse Workbook for Primary Underground Cable for JEA Inventory Stock Vendor Name: Instructions: Insert the requested information in the green highlighted sections. The lead time listed

More information

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

The Contractor shall furnish and install all shielded power cable suitable for use on this project. Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 6/15/16 Updated division section from 16124 to 2605 - mgl44 13, removed references to other section 10/17/14

More information

PV Solar Wiring Solutions

PV Solar Wiring Solutions Priority Solar Projects Across the US 14 DISTRIBUTION CENTERS PV Solar Wiring Solutions ON TIME ACCURATE FLEXIBLE SERVICE CUSTOM SOLUTIONS Priority Capabilities: Premier Supplier of Wire & Cable Cut to

More information

SECTION MEDIUM-VOLTAGE CABLES PART 1 GENERAL

SECTION MEDIUM-VOLTAGE CABLES PART 1 GENERAL SECTION 260513 - MEDIUM-VOLTAGE CABLES PART 1 GENERAL 1.1 SECTION INCLUDES A. Medium voltage cable. B. Cable terminations. C. This specification describes single conductor EPR (Ethylene-propylene-rubber)

More information

STANDARD SPECIFICATION FOR SIGNAL CABLE. A. This Specification provides for single and multi-conductor insulated and jacketed cable for

STANDARD SPECIFICATION FOR SIGNAL CABLE. A. This Specification provides for single and multi-conductor insulated and jacketed cable for STANDARD SPECIFICATION FOR SIGNAL CABLE 1.01 SCOPE A. This Specification provides for single and multi-conductor insulated and jacketed cable for installation in direct contact with the earth, in ducts,

More information

Procurement Department Bid Office Customer Center 1 st Floor, Room W. Church Street Jacksonville, Florida 32202

Procurement Department Bid Office Customer Center 1 st Floor, Room W. Church Street Jacksonville, Florida 32202 Procurement Department Bid Office Customer Center 1 st Floor, Room 002 21 W. Church Street Jacksonville, Florida 32202 October 26, 2017 ADDENDUM NUMBER: ONE (1) TITLE: Arc-Resistant Metal-Clad Switchgear

More information

SECTION INSULATED WIRE AND CABLE

SECTION INSULATED WIRE AND CABLE SECTION 16120 INSULATED WIRE AND CABLE PART 1 GENERAL 1.01 DESCRIPTION A. This section covers the contract item Insulated Wire and Cable, which includes the following items with accessories, and appurtenances:

More information

Standard of Practice - Campus Electrical Distribution System

Standard of Practice - Campus Electrical Distribution System A26.3 Standard of Practice - Campus Electrical Distribution System NOTE: Significant revisions or additions to the previous standards are highlighted in italics. GENERAL Designers shall verify that all

More information

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE METAL-ENCLOSED BUS MEDIUM VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. The medium

More information

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES

11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES 11-SDMS-01 REV. 02 SPECIFICATIONS FOR LOW VOLTAGE POWER AND CONTROL CABLES This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-26 05 19.10 10 (May 2016) ----------------------------------- Preparing Activity: USACE Superseding UFGS-26 05 19.00 10 (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE. ANSI/ICEA S-108-720-2012 STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV Approved by AMERICAN NATIONAL STANDARDS INSTITUTE November 27, 2012 Publication # ANSI/ICEA S-108-720-2012

More information

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072.

Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072. 37-105VFD MMV-VFD Power Cable Three : kv - 15kV 133% Level Rated 90 C s (3) Soft annealed flexible stranded tinned copper per IEEE 150 Table 11. Extruded thermosetting 90 C Ethylene Propylene Rubber (EPR),

More information

SECTION ELECTRICAL CABLE. 1. Trench excavation, backfill, and compaction; Section

SECTION ELECTRICAL CABLE. 1. Trench excavation, backfill, and compaction; Section 02735-1 of 5 SECTION 02735 ELECTRICAL CABLE 02735.01 GENERAL A. Description Electrical cable installation shall include, but not necessarily be limited to, furnishing and placing electrical cable as shown

More information

NPS/002/020 Technical Specification for 11 & 20kV Power Cables

NPS/002/020 Technical Specification for 11 & 20kV Power Cables Version:- 3.1 of Issue:- Nov - 09 Page 1 of 11 NPS/002/020 Technical Specification for 11 & 20kV Power Cables 1. Purpose The purpose of this document is to detail Northern Powergrid (the Company) requirements

More information

NPS/002/023 Technical Specification for 132kV Power Cables.

NPS/002/023 Technical Specification for 132kV Power Cables. Version:- 2.2 of Issue:- June 09 Page 1 of 11 NPS/002/023 Technical Specification for 132kV Power Cables. 1. Purpose The purpose of this document is to detail the technical requirements of Northern Powergrid

More information

MATERIAL AND WORKMANSHIP

MATERIAL AND WORKMANSHIP PURCHASING AND PROCUREMENT DIVISION City of Jacksonville Beach Purchasing and Procurement Division 1460A Shetter Avenue Jacksonville Beach FL 32250 Phone: 904.247.6229 Fax: 904.247.1639 Email: purchasing

More information

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor

IEEE 1580 Type P MOR Polyrad XT-125 Multi Conductor TABLE OF CONTENTS SECTION SUBJECT PAGE I. SCOPE...1 II. APPLICABLE DOCUMENTS...1 III. CONDUCTOR...2 IV. SEPARATOR...2 V. INSULATION...2 A. Physical Properties...2 B. Electrical Properties...3 C. Qualification

More information

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0

NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 REVISION NO. 0 NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 PAGE NO. 1 OF 24 DATE OF ISSUE (MONTH/YEAR) TOTAL NO. OF PAGES (Including cover

More information

GENERAL PACIFIC HD SUPPLY WESCO

GENERAL PACIFIC HD SUPPLY WESCO INVITATION TO BID 2007-103 ELECTRIC WIRE GENERAL PACIFIC HD SUPPLY WESCO 2-3019 25,000 Feet 1/0 Primary Aluminum Wire, *Jacketed*, Underground, 220 Mil, EPR, 15 kv, Full Concentric Neutral, 10 Reels @

More information

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways.

SECTION WIRE, CABLE AND BUSWAYS. A. This section specifies providing wire, cable and busways. SECTION 16120 WIRE, CABLE AND BUSWAYS PART 1 - GENERAL 1.01 DESCRIPTION: A. This section specifies providing wire, cable and busways. B. Definitions: 1. Cable: Cable having low smoke generating characteristics.

More information

12-SDMS-01 Rev.02 SPECIFICATIONS FOR

12-SDMS-01 Rev.02 SPECIFICATIONS FOR 12-SDMS-01 Rev.02 SPECIFICATIONS FOR CABLE JOINTS, TERMINATIONS, AND ACCESSORIES UP TO 36 KV This specification is property of SEC and is subject to change or modification without any notice. TABLE OF

More information

10-SDMS-02 SPECIFICATIONS FOR BARE COPPER CONDUCTORS

10-SDMS-02 SPECIFICATIONS FOR BARE COPPER CONDUCTORS SPECIFICATIONS FOR BARE COPPER CONDUCTORS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

SECTION WIRES AND CABLES

SECTION WIRES AND CABLES SECTION 16120 - WIRES AND CABLES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Heavy Wall Heat Shrinkable Tubing 5-7. Flame Retardant Heavy Wall Heat Shrinkable Tubing 8. Heat Shrinkable Ends Caps 9

Heavy Wall Heat Shrinkable Tubing 5-7. Flame Retardant Heavy Wall Heat Shrinkable Tubing 8. Heat Shrinkable Ends Caps 9 Heavy Wall Heat Shrinkable Tubing 5-7 Flame Retardant Heavy Wall Heat Shrinkable Tubing 8 Heat Shrinkable Ends Caps 9 Heat Shrinkable Breakout Boots 10 Shrink Ratio 3:1 Shrink-Kon Heavy Wall Heat Shrinkable

More information

NORMAS DE REFERENCIA AEIC CS 1: ASTM B

NORMAS DE REFERENCIA AEIC CS 1: ASTM B AEIC CS 1: Especificación para Solid-Type Impregnated-Paper-Insulated Metallic Sheathed AEIC CS2: Especificación para Impregnated-Paper and Laminated Paper- Polypropylene Insulated, High- Pressure Pipe-Type

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

SECTION PARK NON-SEGREGATED BUS SPECIFICATION

SECTION PARK NON-SEGREGATED BUS SPECIFICATION Page 1 of 5 SECTION ------- PARK NON-SEGREGATED BUS SPECIFICATION 1.0 SCOPE 1.1. This specification describes assemblies of 600V, 5Kv and 15Kv non-segregated bus duct, which will be installed indoors and

More information

CITY OF MOBILE. Purchasing Department and Package Delivery: Government Plaza 4th Floor, Room S Government St Mobile, Alabama 36644

CITY OF MOBILE. Purchasing Department and Package Delivery: Government Plaza 4th Floor, Room S Government St Mobile, Alabama 36644 Typed by: DATE Mailing Address: P. 0. Box 1948 Mobile, Alabama 36633 (251) 208-7 434 05/09/2016 sd CITY OF MOBILE Buyer: 006 Purchasing Department and Package Delivery: Government Plaza 4th Floor, Room

More information

SECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013.

SECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013. PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 26 0519 A. Single conductor building wire. B. Metal-clad cable. C. Wiring connectors. D. Electrical tape. E. Wire pulling lubricant. F. Cable ties. 1.2 RELATED

More information

SPECIFICATIONS FOR TENDER # SUPPLY AND INSTALLATION OF LAUNDRY ROOM AIR SUPPLY FAN WESTERN HEALTH

SPECIFICATIONS FOR TENDER # SUPPLY AND INSTALLATION OF LAUNDRY ROOM AIR SUPPLY FAN WESTERN HEALTH SPECIFICATIONS FOR TENDER #0171-1807 SUPPLY AND INSTALLATION OF LAUNDRY ROOM AIR SUPPLY FAN WESTERN HEALTH CLOSING DATE: 20th of March, 2018 CLOSING TIME: 2:00 PM (Newfoundland Time) Invitation to Tender

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less) SECTION 260523 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (24 Volt AC/DC or Less) PART 1 - GENERAL 1.1 SUMMARY A. Related Documents: 1. Drawings and general provisions of the Subcontract apply

More information

SPECIFICATION FOR FRLS POWER CABLES

SPECIFICATION FOR FRLS POWER CABLES SPECIFICATION FOR FRLS POWER CABLES 1.0 SCOPE This specification cover the technical requirements of design, manufacture, testing and delivery to site of Power Cables of 1100V grade with FRLS PVC Sheathed,

More information

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR

SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR SECTION 7.3 TECHNICAL SPECIFICATION OF POWER CABLES & CONDUCTOR 458 7.3.1 11 KV Cables 7.3.1.1 General Where a Manufacturer s Standard or a national Standard equal to or better than the appropriate specified

More information

MATERIAL STANDARD FOR CABLES AND WIRES

MATERIAL STANDARD FOR CABLES AND WIRES MATERIAL STANDARD FOR CABLES AND WIRES CONTENTS : PAGE No. 1. SCOPE... 2 2. SERVICE CONDITIONS... 2 3. REFERENCES AND STANDARDS... 2 4. UNITS... 3 5. CABLE DESIGN AND CONSTRUCTION... 3 5.1 Applicable Cable

More information

DISTRIBUTION TRANSFORMER SPECIFICATION #

DISTRIBUTION TRANSFORMER SPECIFICATION # DISTRIBUTION TRANSFORMER SPECIFICATION #1212.03 15kV Single Phase Submersible Transformer Stainless Steel 12/2/2011 Page 1 of 8 1. SCOPE This specification covers single-phase submersible transformers

More information

1.2 REFERENCES.1 CSA C22.2 No.0.3, Test Methods for Electrical Wires and Cables.

1.2 REFERENCES.1 CSA C22.2 No.0.3, Test Methods for Electrical Wires and Cables. Issued 2005/06/01 Section 16122 Wire and Cables (0 1000V) Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 16151 Wire and Box Connectors 0 1000 1.2 REFERENCES.1 CSA C22.2 No.0.3, Test Methods

More information

SPECIFICATIONS FOR TENDER # SUPPLY OF UNDERCOUNTER PHARMACY REFRIGERATORS FOR WESTERN HEALTH

SPECIFICATIONS FOR TENDER # SUPPLY OF UNDERCOUNTER PHARMACY REFRIGERATORS FOR WESTERN HEALTH SPECIFICATIONS FOR TENDER #0171-1324 SUPPLY OF UNDERCOUNTER PHARMACY REFRIGERATORS FOR WESTERN HEALTH CLOSING DATE: 31 May 2013 CLOSING TIME: 11:00 AM (Newfoundland Time) Invitation to Tender for Eight

More information

JEA# CAICL TECHNICAL SPECIFICATIONS MEDIUM VOLTAGE TRXLP JACKETED POWER CABLE

JEA# CAICL TECHNICAL SPECIFICATIONS MEDIUM VOLTAGE TRXLP JACKETED POWER CABLE JEA# CAICL CAICLTRXLPE TECHNICAL SPECIFICATIONS MEDIUM VOLTAGE TRXLP JACKETED POWER CABLE 1. SCOPE To furnish complete, factory pre-assembled cable, designed for installation on a grounded wye system having

More information

Request for Bids Capital Region Airport Authority

Request for Bids Capital Region Airport Authority Request for Bids Capital Region Airport Authority Bid Number 18-02 RFB Title Runway De-Icing Fluid Issue Date September 24, 2018 Purpose Deadline for Bid Submissions Submit Bid to This Address Required

More information

SPECIFICATION FOR 600 VOLT CONTROL AND POWER CABLE SPECIFICATION NO. 557

SPECIFICATION FOR 600 VOLT CONTROL AND POWER CABLE SPECIFICATION NO. 557 EXHIBIT A - TECHNICAL SPECIFICATION SPECIFICATION FOR 600 VOLT CONTROL AND POWER CABLE SPECIFICATION NO. 557 DATE: March 31, 2000 (REVISED: October 13, 2006) (REVISED: February 14, 2012) (REVISED: January

More information

600 VOLT 600V, 3 CONDUCTOR (WITH GROUND), FR-EPR OR FR-XLPE INSULATION, PVC JACKET SPECIFICATIONS (FLAME RETARDANT POWER CABLE) (UL TYPE TC-ER) TYPE C3 SPEC 70.0100 PROJECT 196116 REFERENCE: LATEST EDITIONS

More information

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable.

Specification FOR. 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated Copper Wire Screened PVC Sheathed Power Cable. Spec. No. GO 5821-4361Rev.2 Issued date : July 13, 2005 Revised 1 date : April 29, 2015 Revised 2 date : February 19, 2016 Specification FOR 12.7/22KV AL-CV/WS 12.7/22KV Aluminum Conductor XLPE Insulated

More information

HDPE Conduit Specification 2011

HDPE Conduit Specification 2011 General This specification covers the minimum requirements for HDPE conduit and is based on ASTM F 2160. HDPE Conduit is for use primarily in underground applications as conduit, innerduct, direct buried

More information

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE

TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 14 TECHNICAL SPECIFICATION FOR LT XLPE POWER CABLES (SPECIFICATION NO.MM/I/LTXLPE/2006) 1. SCOPE: The specification

More information

SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System

SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System 2004 Specifications Houston District SPECIAL SPECIFICATION 6623 Multi-Duct Conduit System 1. Description. Furnish and place a Multi-Duct Conduit (MDC) system that is suitable for installation in an outdoor

More information

PILC Replacement: Getting the Lead Out

PILC Replacement: Getting the Lead Out PILC Replacement: Getting the Lead Out Spring Cincinnati, OH April 30, 2003 Page 1 PILC IS GREAT! Low Profile High Fault Current Capability on Shield High Degree of Water Blocking So why shouldn t you

More information

QUALIFICATION UPDATE. Eric Rasmussen. Quality Cables Since 1854

QUALIFICATION UPDATE. Eric Rasmussen. Quality Cables Since 1854 QUALIFICATION UPDATE Eric Rasmussen Quality Cables Since 1854 90 C 60 year Four successful qualifications to date: QR-1305: Kerite Shielded MV Power Cables for 60 Year Life at 90 C (LOCA) QR-1403: Kerite

More information

STANDARD FOR CONCENTRIC NEUTRAL CABLES RATED 5 THROUGH 46 KV

STANDARD FOR CONCENTRIC NEUTRAL CABLES RATED 5 THROUGH 46 KV ANSI/ICEA S-94-649-2013 STANDARD FOR CONCENTRIC NEUTRAL CABLES RATED 5 THROUGH 46 KV Approved by AMERICAN NATIONAL STANDARDS INSTITUTE March 19,2013 Publication # ANSI/ICEA S-94-649-2013 2013 by INSULATED

More information

INVITATION FOR BID BID #1037 Parka and Softshell Coats

INVITATION FOR BID BID #1037 Parka and Softshell Coats IFB: Bid #1037 Parka and Softshell Coats INVITATION FOR BID BID #1037 Parka and Softshell Coats ST. CHARLES COUNTY AMBULANCE DISTRICT (Herein referred to as District ) 4169 OLD MILL PARKWAY ST. PETERS,

More information

BID PROPOSAL POLICE VEHICLE INSTALLATION

BID PROPOSAL POLICE VEHICLE INSTALLATION BID PROPOSAL POLICE VEHICLE INSTALLATION Steve Maynard Mitch McKinney Purchasing Manager Captain P.O. Box 250 P.O. Box 250 Apex, NC 27502 Apex, NC 27502 (99) 249-3375 (99) 245-3445 Notice to Prospective

More information

A. Section includes busway and fittings including plug-in units.

A. Section includes busway and fittings including plug-in units. SECTION 26 25 00 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes busway and fittings including plug-in units. 1.2 REFERENCES A. Institute of Electrical and Electronics Engineers:

More information

SECTION GROUNDING

SECTION GROUNDING SECTION 16450 GROUNDING PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies general grounding and bonding requirements of electrical and telecommunication installations for personnel safety, equipment

More information

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES

Purchase Now ANSI/ICEA S STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES ANSI/ICEA S-05-692 STANDARD FOR 600 VOLT SINGLE LAYER THERMOSET INSULATED UTILITY UNDERGROUND DISTRIBUTION CABLES Approved as an American National Standard ANSI Approval Date: 9/29/ ANSI/ICEA Publication

More information

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE

CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE ONTARIO PROVINCIAL STANDARD SPECIFICATION OPSS.PROV 604 NOVEMBER 2017 CONSTRUCTION SPECIFICATION FOR INSTALLATION OF CABLE TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

ADDENDUM NO. 2. Except as hereinafter specified, the work shall be in accordance with the drawings and specifications.

ADDENDUM NO. 2. Except as hereinafter specified, the work shall be in accordance with the drawings and specifications. ITB-CD-CM-14-03 Scoreboards for Indian Trails Sports Complex ISSUE DATE: January 15, 2014 DUE DATE: January 22, 2014 @ 2:00pm ADDENDUM NO. 2 SUBJECT: Bidder question and Clarifications INTENT: This addendum

More information

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. ANSI/SCTE (Formerly IPS SP 100)

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD. ANSI/SCTE (Formerly IPS SP 100) ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 15 2006 (Formerly IPS SP 100) Specification for Trunk, Feeder and Distribution Coaxial Cable NOTICE The Society

More information

MATERIAL SPECIFICATION FOR HIGH PRESSURE SODIUM LUMINAIRES FOR UNDERPASS LIGHTING

MATERIAL SPECIFICATION FOR HIGH PRESSURE SODIUM LUMINAIRES FOR UNDERPASS LIGHTING ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS.PROV 2434 November 2016 MATERIAL SPECIFICATION FOR HIGH PRESSURE SODIUM LUMINAIRES FOR UNDERPASS LIGHTING TABLE OF CONTENTS 2434.01 SCOPE 2434.02 REFERENCES

More information

11-SDMS-01 REV. 03 ( )

11-SDMS-01 REV. 03 ( ) 11-SDMS-01 REV. 03 (19-07-2018) SPECIFICATION FOR LOW-VOLTAGE POWER AND CONTROL CABLES Saudi Electricity Company 1. SCOPE... 3 2. CROSS REFERENCES TO OTHER SEC STANDARDS... 3 3. APPLICABLE CODES AND STANDARDS...

More information

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA

SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW ARROW ROUTE, FONTANA CA SPECIFICATION FOR THHN/THWN-2/THW/THWN/TW THHN/THWN-2/THW/THWN/TW Listed E-492385 / E-472248 APPLICATIONS THHN/THWN-2 building wire is primarily used for general purpose applications in conduit and cable

More information

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION

SECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION SECTION 16-372 SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION 1. GENERAL SPECIFICATIONS The work of this Section includes furnishing all labor, equipment, materials (unless specifically identified as Owner-furnished)

More information

MATERIAL STANDARD FOR COLD-APPLIED LAMINATED PLASTIC TAPE INNER-LAYER TAPE FOR TAPE COATING SYSTEM OF BURIED STEEL PIPES ORIGINAL EDITION JULY 1994

MATERIAL STANDARD FOR COLD-APPLIED LAMINATED PLASTIC TAPE INNER-LAYER TAPE FOR TAPE COATING SYSTEM OF BURIED STEEL PIPES ORIGINAL EDITION JULY 1994 MATERIAL STANDARD FOR COLD-APPLIED LAMINATED PLASTIC TAPE AS INNER-LAYER TAPE FOR TAPE COATING SYSTEM OF BURIED STEEL PIPES ORIGINAL EDITION JULY 1994 This standard specification is reviewed and updated

More information

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed]

MEDIUM VOLTAGE XLPE INSULATED POWER CABLES [6.35/11kV Copper XLPE Three-Core HDPE Sheathed] [6.35/11kV Copper XLPE Three-Core HDPE Sheathed] APPLICATION Mostly used as feeder electric cable for power distribution network such as power supply station, substation, switching system etc. They are

More information

City of Jacksonville Finance Department

City of Jacksonville Finance Department City of Jacksonville Finance Department # 1 Municipal Drive Office Phone: (501) 982-4502 P.O. Box 126 Fax Number: (501) 985-9768 Jacksonville, AR. 72076 E-Mail: rbest@cityofjacksonville.net Cheryl Erkel

More information

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV)

DRAFT TANZANIA STANDARD. Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV) EDC3 (5239) P3 Mini-Grid Systems DRAFT TANZANIA STANDARD Part 7: Underground Power Cables for rated voltages 0.6kV/1kV (Um 1.2kV) TANZANIA BUREAU OF STANDARDS TBS 2017 First Edition 2017 Table of Contents

More information

FENCING AND FENCE REPAIR

FENCING AND FENCE REPAIR INVITATION FOR BIDS FOR FENCING AND FENCE REPAIR As Requested by THE SOUTHERN SANDOVAL COUNTY ARROYO FLOOD CONTROL AUTHORITY IFB No. 2018-04 BID DUE DATE: August 8, 2018 TABLE OF CONTENTS Submission Instructions

More information

SECTION HEAT TRACING FOR PLUMBING PIPING

SECTION HEAT TRACING FOR PLUMBING PIPING SECTION 22 05 33 HEAT TRACING FOR PLUMBING PIPING PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not

More information

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING

2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING 2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING E3305.3: now reads The space equal to the width and depth of the panelboard and extending

More information

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, TYPE LS3SWU (INCLUDING VARIATION LS3SWUS)

DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, TYPE LS3SWU (INCLUDING VARIATION LS3SWUS) INCH-POUND 11 July 2011 USED IN LIEU OF MIL-DTL-24643/36F 01 October 2009 DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, TYPE LS3SWU (INCLUDING VARIATION LS3SWUS) This specification is approved

More information

SECTION GROUNDING AND BONDING

SECTION GROUNDING AND BONDING SECTION 16060 PART 1 GENERAL 1.01 DESCRIPTION A. Section includes requirements for an electrical grounding system, including electrodes, grounding rods, connectors, insulators, equipment grounding and

More information

12-SDMS-01 Rev.03 SPECIFICATIONS FOR

12-SDMS-01 Rev.03 SPECIFICATIONS FOR DATE: 02-2017 G 12-SDMS-01 Rev.03 SPECIFICATIONS FOR CABLE JOINTS, TERMINATIONS, AND ACCESSORIES UP TO 36 KV This specification is property of SEC and is subject to change or modification without any notice.

More information

PURCHASING DEPARTMENT

PURCHASING DEPARTMENT PURCHASING DEPARTMENT The bid listed below has had addenda issued. Documents are available over the Internet at http://www.norwalkct.org Adobe Acrobat reader is required to view this document. If you do

More information

P.V.C. INSULATED UNARMOURED COPPER CABLES

P.V.C. INSULATED UNARMOURED COPPER CABLES 083 : 2007 CEB SPECIFICATION P.V.C. INSULATED UNARMOURED COPPER CABLES CEYLON ELECTRICITY BOARD SRI LANKA Specification for P.V.C. INSULATED UNARMOURED COPPER CABLES CEB Specification 083 : 2007 CEYLON

More information

SPECIFICATIONS FOR TENDER # SUPPLY OF TWO OTOACOUSTIC EMISSION SCREENERS FOR WESTERN HEALTH

SPECIFICATIONS FOR TENDER # SUPPLY OF TWO OTOACOUSTIC EMISSION SCREENERS FOR WESTERN HEALTH SPECIFICATIONS FOR TENDER # 0171-1015 SUPPLY OF TWO OTOACOUSTIC EMISSION SCREENERS FOR WESTERN HEALTH CLOSING DATE: March 4,2010 CLOSING TIME: 11:00 AM (Newfoundland Time) Invitation to Tender for 1.0

More information

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT

P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEB SPECIFICATION 005-1: 2012 P.V.C. INSULATED ALUMINIUM SERVICE MAIN WIRE-FINISHED PRODUCT CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS PAGE 1. Scope 03

More information

SECTION HEAT TRACING FOR PLUMBING PIPING

SECTION HEAT TRACING FOR PLUMBING PIPING SECTION 22 05 33 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable in the section

More information

A. This section is intended to provide design guidelines for Utility Direct Buried Piping and Conduit Systems.

A. This section is intended to provide design guidelines for Utility Direct Buried Piping and Conduit Systems. Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 PURPOSE A. This section is intended to provide design guidelines for Utility Direct Buried

More information

SPECIFICATIONS FOR TENDER # SUPPLY OF EXTERIOR RENOVATIONS GATEWAY COTTAGES UNITS 1-20 PORT AUX BASQUES FOR WESTERN HEALTH

SPECIFICATIONS FOR TENDER # SUPPLY OF EXTERIOR RENOVATIONS GATEWAY COTTAGES UNITS 1-20 PORT AUX BASQUES FOR WESTERN HEALTH SPECIFICATIONS FOR TENDER #0671-1046 SUPPLY OF EXTERIOR RENOVATIONS GATEWAY COTTAGES UNITS 1-20 PORT AUX BASQUES FOR WESTERN HEALTH CLOSING DATE: 1 November 2010 CLOSING TIME: 11:00 AM (Newfoundland Time)

More information

INVITATION TO BID CITY OF HOPKINSVILLE

INVITATION TO BID CITY OF HOPKINSVILLE INVITATION TO BID CITY OF HOPKINSVILLE Office of the Procurement Specialist 715 South Virginia Street P. O. Box 707 Hopkinsville, Kentucky 42241-0707 TITLE: DESIGN BUILD BUIDLING FOR THE CITY OF HOPKINSVILLE,

More information

REQUEST FOR PROPOSAL WAYFINDING SIGN DESIGN AND FABRICATION FOR THE CITY OF SALIDA, COLORADO

REQUEST FOR PROPOSAL WAYFINDING SIGN DESIGN AND FABRICATION FOR THE CITY OF SALIDA, COLORADO REQUEST FOR PROPOSAL WAYFINDING SIGN DESIGN AND FABRICATION FOR THE CITY OF SALIDA, COLORADO I. INVITATION AND INTENT The City of Salida invites all interested, qualified persons or firms capable of providing

More information

SAN JOAQUIN COUNTY PURCHASING AND SUPPORT SERVICES PURCHASING DIVISION

SAN JOAQUIN COUNTY PURCHASING AND SUPPORT SERVICES PURCHASING DIVISION SAN JOAQUIN COUNTY PURCHASING AND SUPPORT SERVICES PURCHASING DIVISION David M. Louis, C.P.M., CPPO, CPPB Director Jon Drake, C.P.M. Deputy Director DATE: May 12, 2010 TO: RE: ALL PROSPECTIVE BIDDERS BID

More information

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.

SECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring. SECTION 16120 WIRE AND CABLE PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 16112 - Raceways and Conduit. 2. 16155 - Motor Power and Control Wiring. 1.02 SYSTEM DESCRIPTION A. Performance Requirements:

More information

TECHNIACL SPECIAL PROVISION FOR NON-STRUCTURAL AND STRUCTURAL INTEGRAL PILE JACKET WITH SACRIFICIAL CATHODIC PROTECTION

TECHNIACL SPECIAL PROVISION FOR NON-STRUCTURAL AND STRUCTURAL INTEGRAL PILE JACKET WITH SACRIFICIAL CATHODIC PROTECTION TECHNIACL SPECIAL PROVISION FOR NON-STRUCTURAL AND STRUCTURAL INTEGRAL PILE JACKET WITH SACRIFICIAL CATHODIC PROTECTION Financial Project ID 429140-1-52-01, 429140-2-52-01 & 428267-1-52-01 The official

More information

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1

TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1 ANNEXURE TO TENDER NO. PUR42396GM DATED 06 th FEBRUARY 2014 SUPPLY OF 1.1KV GRADE LT POWER CABLES FOR THE PERIOD APRIL 2014 MARCH 2016 TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1 1.1 SCOPE

More information

U.V resistance UL Sunlight Resistance. Flame retardant IEC

U.V resistance UL Sunlight Resistance. Flame retardant IEC Cable for underground power distribution and subtransmission. Description Application Underground power distribution and subtransmission. As transformer feeders in substations. In power plants, industrial

More information

EHV XLPE CABLES CDCC LINE

EHV XLPE CABLES CDCC LINE PROFILE THE HINDUSTHAN VIDYUT PRODUCTS LIMITED, established in the year 1959 is a leading manufacturer of Overhead Conductors and Underground Cables. The Company at its Faridabad Works has sophisticated

More information

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION

CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 604 NOVEMBER 2004 CONSTRUCTION SPECIFICATION FOR CABLE INSTALLATION TABLE OF CONTENTS 604.01 SCOPE 604.02 REFERENCES 604.03 DEFINITIONS - Not Used

More information

PO Box 1081 Monticello, MN Ph Fax

PO Box 1081 Monticello, MN Ph Fax Copperhead High Strength Tracer Wire Part# (1030* -HS-**) *= Color- B=Blue, G=Green, Y=Yellow, P=Purple, R-Red, B=Black, N=Orange **=Spool Size- 500, 1000, 2500 Tracer wire shall be a #10 AWG HS-CCS high-strength

More information

City of Jacksonville Beach

City of Jacksonville Beach City of Jacksonville Beach Purchasing Division: 1460A Shetter Ave., Jacksonville Beach, FL 32250 Tel: 904-247-6229 Fax: 904-270-1639 THIS IS NOT A COMPLETE RFP PACKAGE REQUEST FOR PROPOSAL RFP Number:

More information

SECTION BASIC ELECTRICAL REQUIREMENTS

SECTION BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions, apply to work of this section. 1.2 SUMMARY A. This section specifies

More information