BUILDING CODE COMMISSION

Size: px
Start display at page:

Download "BUILDING CODE COMMISSION"

Transcription

1 Ruling No Application No BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Clause (1)(c) of Regulation 403, as amended by O. Reg. 22/98, 102/98, 122/98, 152/99, 278/99, 593/99, 597/99, 205/00, 283/01 and 220/02 (the Ontario Building Code ). AND IN THE MATTER OF an application by Blair Kohlmeier, Stafford Haensli Architects Inc., for the resolution of a dispute with Doug Robertson, Chief Building Official, Town of Tillsonburg, to determine whether the omission of continuous guards between constructed rows of successive fixed seating provides sufficiency of compliance with Clause (1)(c) of the Ontario Building Code at the Tillsonburg Community Centre and Arena Complex, 45 Hardy Avenue, Tillsonburg, Ontario. APPLICANT RESPONDENT PANEL PLACE Blair Kohlmeier Stafford Haensli Architects Inc. Mississauga, Ontario Doug Robertson Chief Building Official Town of Tillsonburg Tony Chow, Chair John Guthrie Michael Steele Toronto, Ontario DATE OF HEARING July 22, 2004 DATE OF RULING July 22, 2004 APPEARANCES Rick Mori Leber Rubes Inc. Toronto, ON Agent for the Applicant Doug Robertson Chief Building Official Town of Tillsonburg The Respondent

2 -2- RULING 1. The Applicant Blair Kohlmeier, Stafford Haensli Architects Inc., has received a building permit under the Building Code Act, S.O. 1992, c. 23, as amended, and has undertaken an extensive renovation at the Tillsonburg Community Centre and Arena Complex at 45 Hardy Avenue, Tillsonburg, Ontario. 2. Description of Construction The Applicant has constructed an addition to, and renovation of, a combination Group A, Division 2 and Group A, Division 3 facility, having a building height of 2 storeys and building area of 2 approximately 10,000 m. The structure is comprised of a combination of combustible and noncombustible construction and is partially equipped with both sprinkler and standpipe and hose systems. In addition, a fire alarm system serves the entire building. The construction in dispute involves the fixed seating arrangement where no fixed guard is provided between successive rows of seating. The community centre complex has approximately 750 fixed seats with backs arranged in five tiers with a 600 mm vertical rise between each tier. The risers are constructed of precast concrete steps. The subject stepped seating arrangement has been designed in accordance with NFPA 101 Life Safety Code requirements. The fixed seat backs on each level project 228 mm above the adjacent platform and a clearance distance of approximately 500 mm is provided between the seat backs and the seats above (in the unoccupied position). In addition, handrails will be installed at the centre of the stepped aisles serving the seating areas. 3. Dispute The issue at dispute between the Applicant and Respondent is whether the proposed stepped seating arrangement, that does not include a guard between each successive row of fixed seating, provides sufficiency of compliance with Clause (1)(c) of the Building Code. Clause (1)(c) requires that, where seating is arranged in successive tiers and the rise between the platform measures more than 450 mm, the height of the guards is to be not less than 660 mm along the entire row of seats. As noted above, the rise between platforms measures 600 mm, however, no guard is proposed between the rows of fixed seating. 4. Provisions of the Ontario Building Code Clause (1)(c) (1) Except as required by Sentences (2) to (4) for bleacher seats, guards shall be installed in outdoor and indoor places of assembly with fixed seats so that (c) where the seating is arranged in successive tiers and the height of rise between platforms is more than 450 mm (17¾ in), the height of guards is not less than 660 mm (2 ft 2 in) along the entire row of seats at the edge of the platform.

3 -3-5. Applicant s Position The Applicant provided the Commission with an overview of the extensive renovation and expansion of the existing facility and highlighted several limitations on the subject construction. He acknowledged the Building Code issue that resulted in this dispute and noted several compensating measures that would ensure the safety of patrons to the stadium. He advised that handrails would be installed in the aisles, bright paint would be applied to the edge of the stairs, and gaps between seat backs would be minimized where possible. He suggested that most falls occur on the stairs rather than in the cross-aisle spaces between seats. In this regard, the handrails at the stepped aisles will increase the overall level of occupant safety, he submitted. The Agent for the Applicant continued by advising that there is a clear 500 mm row width, which exceeds the requirements established in the Building Code. This would also contribute to the safety of the design, he submitted. He noted that seating is limited to 750 persons and exiting can be accomplished safely. The Agent pointed to the similarities between the subject dispute and an earlier ruling of the Building Code Commission involving the Corel Centre in Ottawa. He also noted that the subject proposal meets the requirements of NFPA 101 Life Safety Code which does not require fixed guards between adjacent rows, but admitted that NFPA 101 was not used as the design basis for the entire building. In summation, the Agent for the Applicant argued that the seat back projection above the walking surface of an adjacent row is not mandated by the Building Code. He submitted that, if no seats were present and the rows were limited to standing room only, there would be no requirement for guards at the edge of the platforms. He questioned why guards would be required where seats are present and suggested that tiers of fixed seats, with fixed seat backs, perform in an acceptable manner without the provision of between-row guards. 6. Respondent s Position The Respondent submitted that his primary concern is that the back of the seats represent a tripping hazard as the projection is too low and infringes upon the walking surface of the rows behind. He suggested that this tripping hazard is exacerbated by the lack of guard to protect from falling over the top of seats into the rows below. The Respondent noted that the original design of the seating was not to NFPA 101 and argued that this standard has been used selectively by the Applicant. He submitted that he did not have the authority to permit this alternate design as it deviates from the Building Code and the anticipated acceptance of equivalents as regulated by Section 2.7. of the Code. Although unable to accept the subject proposal, he suggested that by adding handrails in the centre of the stairways, marking the nosing in a contrasting colour and placing guards in any gaps between seats where seat backs are not present, his safety concerns may be somewhat alleviated and a sufficient level of compliance may be achieved. 7. Commission Ruling It is the decision of the Building Code Commission (the BCC ) that the omission of continuous guards between the constructed rows of successive fixed seating provides sufficiency of compliance with Clause (1)(c) of the 1997 Ontario Building Code (the Building Code ) at the Tillsonburg Community Centre and Arena, 45 Hardy Avenue, Tillsonburg, Ontario, on the condition that:

4 -4-1. The gaps and spaces between seating within rows be provided with guards to the satisfaction of the Chief Building Official; 2. The handrails will be installed at the centre of the stepped aisles as described in the appropriate section of NFPA 101; 3. The leading edge of the steps on the aisle be identified by stripes of contrasting colour. 8. Reasons i) The clear width between the back of seats and the projection of seats in the unoccupied position is 500 mm, being 100 mm greater than the requirement of Clause (1)(c); ii) The back of the seats rise 228 mm above the platform level, which is greater than the dimension of a maximum riser and should minimize the potential of accidental tripping.

5 Dated at Toronto this 22nd day in the month of July in the year 2004 for application number Tony Chow, Chair John Guthrie Michael Steele

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-28-883 Application No. 2002-25 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Clauses 3.2.2.67.(2)(c)

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-35-890 Application No. 2002-22 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 3.4.3.6. and

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-21-876 Application No. 2002-17 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 3.2.2.24. and

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 01-38-831 Application # 2001-47 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, 1992. AND IN THE MATTER OF Sentence 3.3.1.17.(1) of Regulation 403, as amended

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 10-21-1257 Application No. B-2010-13 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Articles 9.8.8.3.

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 05-18-1032 Application No. 2005-11 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF in Article 9.10.14.11.

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-13-868 Application No. 2002-11 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 3.2.2.9. and

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-05-860 Application No. 2001-82 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 4.1.10.8. of

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 03-07-905 Application No. 2002-51 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.2.2.35.(4)

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-22-877 Application No. 2002-19 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentences 3.3.1.2.(3),

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 01-22-815 Application # 2001-14 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, 1992. AND IN THE MATTER OF Articles 3.3.1.8. and 3.4.3.6. of Regulation

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-11-866 Application No. 2002-06 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentences 3.1.5.5.(1),

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 05-07-1021 Application No. 2005-02 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 3.2.2.67.,

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 05-08-1022 Application No. 2005-03 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF in Articles 9.10.14.1.

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 07-42-1171 Application No. B-2007-37 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.4.6.5.(8)

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 08-12-1186 Application No. 2008-03 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.6.3.1.(2)

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-04-859 Application No. 2001-81 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentences 3.2.3.7.(7)

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 03-16-914 Application No. 2003-08 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 9.8.8.2.(4)

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 05-26-1040 Application No. 2005-17 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 4.1.1.3.(1)

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 05-22-1036 Application No. 2005-18 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 9.8.8.5.(1)

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 03-40-938 Application No. 2003-40 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 3.1.5.1. of

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 10-35-1271 Application No. B-2010-26 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 4.3.4.3.

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 04-27-982 Application No. 2004-19 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 9.8.8.8.(2)

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 07-39-1168 Application No. 2007-35 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 9.10.12.3.

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 03-54-952 Application No. 2003-64 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 6.2.3.2. of

More information

EGRESS CHAPTER ,500 3 Over 2,500 4 OCCUPANT LOAD REQUIRED MEANS OF EGRESS

EGRESS CHAPTER ,500 3 Over 2,500 4 OCCUPANT LOAD REQUIRED MEANS OF EGRESS CHAPTER 4 EGRESS SECTION 401 GENERAL 401.1 General. The means of egress for new bleachers, folding and telescopic seating, and grandstands shall comply with this chapter. SECTION 402 TRAVEL 402.1 Exit

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 00-54-786 Application No. 2000-66 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, 1992. AND IN THE MATTER OF Articles 9.8.8.8., 4.1.10.1. and Sentence 9.8.2.1.(1)

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 09-06-1218 Application No. B-2009-04 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Article 3.1.9.1.

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-38-893 Application No. 2002-33 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Clause 3.3.4.4.(1)(a)

More information

BUILDING CODE VARIANCE

BUILDING CODE VARIANCE BUILDING CODE VARIANCE April 2009 06-BCV-011-R1 Page 1 of 8 DISCUSSION MULTI-LEVEL STORAGE RACKING SYSTEMS The Alberta Building Code 2006 contains no specific requirements for multi-level storage racking

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 09-14-1226 Application No. B-2009-15 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Clause 9.25.2.2.(1)(g)

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 03-32-930 Application No. 2003-31 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 5.1.4.2. and

More information

Work Group Item Stairways serving an occupant load of less than 50 shall have a width of not less than 36 inches (914 mm).

Work Group Item Stairways serving an occupant load of less than 50 shall have a width of not less than 36 inches (914 mm). IBC-12/13 1009.1, 1009.4, 1009.7.2, 1009.7.4, 1009.8, 1009.10, 1009.15 (IFC [B] 1009.1, 1009.4, 1009.7.2, 1009.7.4, 1009.8, 1009.10, 1009.15) Proponent: S. Bajnai, Chesterfield County, VA, ICC Building

More information

Standard for Bleachers, Folding and Telescopic Seating, and Grandstands

Standard for Bleachers, Folding and Telescopic Seating, and Grandstands International Code Council Standard for Bleachers, Folding and Telescopic Seating, and Grandstands ICC 300-2017 edition Public Comment Draft October 2017 The ICC Consensus Committee on Bleachers, Folding

More information

Schedule A. a representative appointed from among persons nominated by the Nova Scotia Accessibility Advisory Board.

Schedule A. a representative appointed from among persons nominated by the Nova Scotia Accessibility Advisory Board. Schedule A Amendment to the Nova Scotia Building Code Regulations made by the Minister of Municipal Affairs under Section 4 of Chapter 46 of the Revised Statutes of Nova Scotia, 1989, the Building Code

More information

Stairs have many potential violations this Newsletter is Part 1 of two parts.

Stairs have many potential violations this Newsletter is Part 1 of two parts. Stairs have many potential violations this Newsletter is Part 1 of two parts. Violation 1 : Risers do not meet requirements: riser heights too high/low; too much variation between riser heights; risers

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling # 01-12-805 Application # 2000-83 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, 1992. AND IN THE MATTER OF Articles 9.26.5.1. and 9.26.5.2. of Regulation

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 08-24-1198 Application No. 2008-21 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Sentence 9.19.1.1.(1)

More information

Description Accessibility Standards. AODA OBC 2015 Ramps

Description Accessibility Standards. AODA OBC 2015 Ramps Ramps OBC Ammendments are related to the following accessibility standards: The ramp must have a minimum clear width of 900 mm. The ramp must have a clear height that provides a minimum Tactile Attention

More information

HOUSING CONVERSION Guidelines for the conversion of a house to commercial use.

HOUSING CONVERSION Guidelines for the conversion of a house to commercial use. PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT HOUSING CONVERSION Guidelines for the conversion of a house to commercial use. HAIR 105 January 2017 contents General Information 3 Zoning Information 4 Building

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION - 1 - Ruling No. 07-31-1160 Application No. 2007-15 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 8.7.3.2.

More information

(Statute, Rule, FBC, Industry) FBC 406.3, see also FBC No provisions in FBC or FS

(Statute, Rule, FBC, Industry) FBC 406.3, see also FBC No provisions in FBC or FS Florida Specific Amendment Code Reference NFPA 101 Open Parking Structure. A parking structure that, at each parking level, has wall openings open to the atmosphere, for an area of not less than 1.4 ft2

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 03-34-932 Application No. 2003-41 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.7.4.1.(3)

More information

2012 IBC Assembly Means of Egress. Based on the 2012 International Building Code

2012 IBC Assembly Means of Egress. Based on the 2012 International Building Code 2012 IBC Assembly Means of Egress Based on the 2012 International Building Code Overview This seminar deals with those means of egress provisions of the IBC that are intended to address the concerns related

More information

BUILDING CODE VARIANCE

BUILDING CODE VARIANCE BUILDING CODE VARIANCE December 2017 14-BCV-015 Page 1 of 6 MULTI-LEVEL STORAGE RACKING SYSTEMS PURPOSE The purpose of this variance is to allow for an alternative solution for multi-level storage racking

More information

2. Plot plan showing deck scaled with stairs. 3. Building Permit Application signed by owner or licensed contractor and fee paid.

2. Plot plan showing deck scaled with stairs. 3. Building Permit Application signed by owner or licensed contractor and fee paid. DECK GUIDELINES All information in this handout pertains to 1 and 2 family residential decks. The City of Derby is offering this informational handout as representative of typical issues/questions that

More information

EGRESS AZMIR SULTANA NICOLAS MIMU SAKUMA EDWIN VEGA CHAMORRO

EGRESS AZMIR SULTANA NICOLAS MIMU SAKUMA EDWIN VEGA CHAMORRO EGRESS AZMIR SULTANA NICOLAS CHAMORRO MIMU SAKUMA EDWIN VEGA DEFINITIONS NC ACCESSIBLE MEANS OF EGRESS. A continuous and unobstructed way of egress travel from any accessible point in a building or facility

More information

Section 1 OBC FADS /13 Access to Parking Areas

Section 1 OBC FADS /13 Access to Parking Areas Section 1 OBC 3.8.2.2 4.3.12/13 Access to Parking Areas A barrier-free path of travel is provided from: a) the entrance to the exterior parking area b) at least one parking level where a passenger elevator

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 08-06-1180 Application No. B- 2007-49 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 7.4.8.2.,

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

Project Address Applicant: (Please Print) Plan review Engineer: Phone: Date

Project Address Applicant: (Please Print) Plan review Engineer: Phone: Date BUILDING AND SAFETY Tenant Improvement Checklist Project Address Applicant: (Please Print) Plan review Engineer: Phone: Date APPLICATION The following items will be required at the permit counter before

More information

International Code Council

International Code Council Page 1 of 21 International Code Council ICC 300-2012 edition Committee Actions Report For Committee Actions taken at the November 24 th and December 14 th, 2010 meetings Page 2 of 21 IS-BLE1-10/11 ICC

More information

WHO IS THIS COURSE FOR?

WHO IS THIS COURSE FOR? INTRODUCTION INSTRUCTIONS - READ ME FIRST BEFORE THE COURSE STARTS, WORK ON YOUR OWN AND COMPLETE ALL OF THE EXERCISES. If you come unprepared, you will have a difficult time to keep up with the pace of

More information

Description Accessibility Standards. University of Toronto

Description Accessibility Standards. University of Toronto Ramps The ramp must have a minimum clear width of 900 mm. The ramp must have a clear height that provides a minimum headroom clearance of 2,100 mm above the ramp. The surface of the ramp must be firm and

More information

E?? , , , , , , , , , , , , Table ,

E?? , , , , , , , , , , , , Table , CTC to BCAC Unenclosed Exits 2015 Group A Code Change Cycle Copyright 2014 International Code Council, Inc. IBC 10-31 E?? 15 202, 1005.3.2, 1009.3, 1009.4, 1019.3, 1029.6, 1029.6.3, 1029.7, 1029.8, 1029.8.1,

More information

PRESCRIPTIVE COMPLIANCE METHOD

PRESCRIPTIVE COMPLIANCE METHOD CHAPTER PRESCRIPTIVE COMPLIANCE METHOD 3 SECTION 301 GENERAL 301.2 Building materials. Building materials shall comply with the requirements of this section. 301.2.1 Existing materials. Materials already

More information

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-03-04-10 Ontario-NBC CODE REFERENCE: Division B / 3.4.6.8. Division B / 3.3.1.13.

More information

Code Technology Committee Area of Study Climbable Guards

Code Technology Committee Area of Study Climbable Guards Code Technology Committee Area of Study Climbable Guards 2009/2012 Cycle Code changes related to the CTC area of study noted above The following are code changes related to the CTC Climbable Guards Area

More information

4/24/2015. Context: Codes ONTARIO BUILDING CODE CONCEPTS AND CODE ANALYSIS

4/24/2015. Context: Codes ONTARIO BUILDING CODE CONCEPTS AND CODE ANALYSIS ONTARIO BUILDING CODE CONCEPTS AND CODE ANALYSIS Deborah Levine Farrow, Architect, OAA, FRAIC James Farrow, Architect, OAA, OAQ, FRAIC Get the habit of analysis analysis will in time enable synthesis to

More information

Acceptable Solution F4/AS1

Acceptable Solution F4/AS1 1.0 Barriers in Buildings 1.1 Barrier heights 1.1.1 Minimum barrier heights are given in Table 1. COMMENT: Refer to NZBC Clause D1 for handrails on stairs. Handrails can be constructed as an integral part

More information

2009 IBC Section 1024 Approved Luminous Egress Path Markings

2009 IBC Section 1024 Approved Luminous Egress Path Markings 2009 IBC Section 1024 Approved Luminous Egress Path Markings Where Required Buildings of Groups A (Assembly), B (Business), E (Education), I (Institutional), M (Mercantile) and R-1 (Residential transient

More information

COMMUNITY RISK REDUCTION BUREAU MANUAL CODE REQUREMENTS TEMPORARY TENTS AND MEMBRANE STRUCTURES EFFECTIVE: APRIL 1, 2016 AUTHORIZED: R.

COMMUNITY RISK REDUCTION BUREAU MANUAL CODE REQUREMENTS TEMPORARY TENTS AND MEMBRANE STRUCTURES EFFECTIVE: APRIL 1, 2016 AUTHORIZED: R. COMMUNITY RISK REDUCTION BUREAU MANUAL CODE REQUREMENTS 423.7 TEMPORARY TENTS AND MEMBRANE STRUCTURES EFFECTIVE: APRIL 1, 2016 AUTHORIZED: R. Pearce SCOPE This policy applies to temporary tents, air-supported,

More information

Annotated Accessibility Changes to the 2012 Ontario Building Code, as Amended by Ontario Regulation 368/13

Annotated Accessibility Changes to the 2012 Ontario Building Code, as Amended by Ontario Regulation 368/13 Annotated Accessibility Changes to the 2012 Ontario Building Code, as Amended by Ontario Regulation 368/13 RED indicates new text. O. Reg. 368/13 comes into force on 1 January, 2015 DIVISION A PART 1 COMPLIANCE,

More information

SUPPLEMENTAL ACCESSIBILITY NO. 5 PLAN REVIEW CHECKLIST

SUPPLEMENTAL ACCESSIBILITY NO. 5 PLAN REVIEW CHECKLIST GEORGE CHAVEZ, City Building Official DAVID YELTON, Building Inspection Manager NESTOR OTAZU, Community Preservation Manager BUILDING & SAFETY DIVISION 455 North Rexford Drive, 1 st Floor Beverly Hills,

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 03-27-925 Application No. 2003-14 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 9.14.2.1.,

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 10-37-1273 Application No. B-2010-33 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Clauses 9.7.2.1.(1)(a)

More information

CITY OF BRISTOL DECK CONSTRUCTION GUIDE ACCORDING TO THE 2012 IRC WITH THE 2016 CT AMMENDMENTS

CITY OF BRISTOL DECK CONSTRUCTION GUIDE ACCORDING TO THE 2012 IRC WITH THE 2016 CT AMMENDMENTS CITY OF BRISTOL DECK CONSTRUCTION GUIDE ACCORDING TO THE 2012 IRC WITH THE 2016 CT AMMENDMENTS To construct an attached deck in to a residential home in the City of Bristol, you must provide the following:

More information

COUNCIL ORDER No

COUNCIL ORDER No SAFETY CODES COUNCIL #1000, 10665 Jasper Avenue N.W., Edmonton, Alberta, Canada, T5J 389 Tel: 780-413-0099 I 1-888-413-0099 Fax: 780-424-5134 I 1-888-424-5134 www.safetycodes.ab.ca COUNCIL ORDER No. 0015437

More information

IBC MEANS OF EGRESS. Code Change No: E5-07/08. Original Proposal

IBC MEANS OF EGRESS. Code Change No: E5-07/08. Original Proposal DOCUMENTATION IBC MEANS OF EGRESS Code Change No: E5-07/08 Sections: 1002.1 (IFC [B] 1002.1) Proponent: Gerard Hathaway, New York State Department of State Building Codes Division, representing himself

More information

Plan Check No. A. ELEVATORS

Plan Check No. A. ELEVATORS Elevators, Egress and Areas of Refuge, Platform Lifts Plan Check No. A. ELEVATORS NOTE: In buildings two or more stories in height, served by an elevator, or a building served by an elevator required by

More information

Workplaces must be kept clean, orderly, and sanitary. Workroom floors must be maintained as clean and dry as possible.

Workplaces must be kept clean, orderly, and sanitary. Workroom floors must be maintained as clean and dry as possible. Section C.19 University of South Carolina Safety Program Guide WALKING AND WORKING SURFACES Introduction Occupational Safety and Health Administration (OSHA) CFR 1910 Subpart D Walking and Working Surfaces

More information

BENZIE COUNTY BUILDING SAFETY and CODE ENFORCEMENT DEPARTMENT 448 Court Place, Beulah, Michigan Ph Fax.

BENZIE COUNTY BUILDING SAFETY and CODE ENFORCEMENT DEPARTMENT 448 Court Place, Beulah, Michigan Ph Fax. BENZIE COUNTY BUILDING SAFETY and CODE ENFORCEMENT DEPARTMENT 448 Court Place, Beulah, Michigan 49617 Ph. 231-882-9673 Fax. 231-882-0033 DECK SPEC INFORMATION Footing Inspections: Dig footing to required

More information

Wood Decks. Zoning and Construction requirements for open non-sheltered wood decks for residential dwellings.

Wood Decks. Zoning and Construction requirements for open non-sheltered wood decks for residential dwellings. Wood Decks Zoning and Construction requirements for open non-sheltered wood decks for residential dwellings. General Information 3 Zoning 7 Foundations 8 Structural 11 Design 16 Compliance 20 NOTE The

More information

DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS. Public Safety Services ADA-ABA COMMENT ASSISTANCE GUIDE

DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS. Public Safety Services ADA-ABA COMMENT ASSISTANCE GUIDE DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS BOBBY JINDAL GOVERNOR Public Safety Services H. BUTCH BROWNING STATE FIRE MARSHAL ADA-ABA COMMENT ASSISTANCE GUIDE The information submitted is not sufficient

More information

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-03-13-05 Ontario CODE REFERENCE: Div. B 3.13.4.5. DESCRIPTION OF THE PROPOSED

More information

ONTARIO REGULATION 350/06 BUILDING CODE

ONTARIO REGULATION 350/06 BUILDING CODE ONTARIO REGULATION 350/06 BUILDING CODE Consolidation Period: From August 12, 2010 http://www.e-laws.gov.on.ca/html/regs/english/elaws_regs_060350_e.htm Section 9.36. Cottages 9.36.1. Scope 9.36.1.1. Application

More information

2009 IBC/IFC Photoluminescent Signs & Pathway Marking Systems Frequently Asked Questions

2009 IBC/IFC Photoluminescent Signs & Pathway Marking Systems Frequently Asked Questions 2009 IBC/IFC Photoluminescent Signs & Pathway Marking Systems Frequently Asked Questions 1. What is the difference between IBC & IFC? a. IBC International Building Code covers new construction b. IFC International

More information

CITY OF OCEANSIDE. Single Family Dwelling Stairways/Guards. Informational Bulletin

CITY OF OCEANSIDE. Single Family Dwelling Stairways/Guards. Informational Bulletin Single Family Dwelling Stairways/Guards Informational Bulletin Width Stairways shall not be less than 36 inches wide. The handrail may enter a maximum of 4 1/2 inches into this dimension. (2016 CRC R311.7.1

More information

International Code Council

International Code Council International Code Council ICC 300-2012 edition Public comments received On the 2007 edition of the ICC 300 Standard For November 24, 2010 Meeting - Teleconference Page 1 of 15 2007 ICC 300 Standard Revision

More information

Design Aid for Barrier-Free Accessibility in Existing Buildings

Design Aid for Barrier-Free Accessibility in Existing Buildings Design Aid for Barrier-Free Accessibility in Existing Buildings July 9, 2004 Table of Contents 1. Introduction 1 2. References 2 3. Access to the Building 2.1 Site Accessibility 2 4. Building Access 3.1

More information

Report on First Revisions with Statement June 2014 NFPA 5000

Report on First Revisions with Statement June 2014 NFPA 5000 5000 FR1000 BLD-AXM (16.1 through 16.1.7) Recommendation: 16.1 General Requirements. 16.1.1 Application. 16.1.1.1 The requirements of this chapter shall apply to new buildings or portions thereof used

More information

Typical Deck Details. Shenandoah County, Virginia. Based on the 2012 International Residential Code

Typical Deck Details. Shenandoah County, Virginia. Based on the 2012 International Residential Code Shenandoah County, Virginia Typical Deck Details Based on the 2012 International Residential Code The design details in this document apply to residential decks only. Framing requirements are limited to

More information

Typical Deck Details. Shenandoah County, Virginia. Based on the 2012 Virginia Residential Code

Typical Deck Details. Shenandoah County, Virginia. Based on the 2012 Virginia Residential Code Shenandoah County, Virginia Typical Deck Details Based on the 2012 Virginia Residential Code The design details in this document apply to residential decks only. Framing requirements are limited to single

More information

CITY OF DANA POINT SITE ACCESSIBILITY AND PARKING B103 SITE INTRODUCTION

CITY OF DANA POINT SITE ACCESSIBILITY AND PARKING B103 SITE INTRODUCTION INTRODUCTION CITY OF DANA POINT COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 33282 Golden Lantern, Suite 209 Dana Point, CA 92629 949 248-3594 www.danapoint.org SITE ACCESSIBILITY AND PARKING B103 SITE 2013

More information

SITE ACCESSIBILITY AND PARKING

SITE ACCESSIBILITY AND PARKING SITE ACCESSIBILITY AND PARKING The purpose of this handout is to clarify the requirements of site accessibility under the 2013 California Building Codes, Specifically, Section 11B. Each lot or parking

More information

Dear Customer. Section Old F4 January 2017 Amendment 2. Remove title page and document history page 1-2B

Dear Customer. Section Old F4 January 2017 Amendment 2. Remove title page and document history page 1-2B Dear Customer Please find enclosed Amendment 2, effective 1 January 2017, to the Acceptable Solution and Verification Method for Clause F4 Safety from Falling of the New Zealand Building Code. The previous

More information

Bleacher Safety Guidelines

Bleacher Safety Guidelines Bleacher Safety Guidelines Line of Business: Property, General Liability, Workers Compensation www.tridentinsurance.net Risk Control Strategy/ Key Issues: To provide schools and municipalities with bleacher

More information

MVRTA Newburyport Intermodal Parking Facility Newburyport, Massachusetts

MVRTA Newburyport Intermodal Parking Facility Newburyport, Massachusetts PARKING CONSULTANTS GREEN PARKING CONSULTING PLANNERS ARCHITECTS STRUCTURAL ENGINEERS RESTORATION ENGINEERS MVRTA Newburyport Intermodal Parking Facility Newburyport, Massachusetts Code Analysis 12/9/2016

More information

ONTARIO BUILDING CODE CONCEPTS AND CODE ANALYSIS

ONTARIO BUILDING CODE CONCEPTS AND CODE ANALYSIS ONTARIO BUILDING CODE CONCEPTS AND CODE ANALYSIS Deborah Levine Farrow, Architect, OAA, FRAIC James Farrow, Architect, OAA, OAQ, FRAIC Get the habit of analysis analysis will in time enable synthesis to

More information

Applying the Building Code During Design

Applying the Building Code During Design Applying the Building Code During Design A Step-By-Step Process AIA Learning Units The Salt Lake City CSI Chapter is a Registered Provider with The American Institute of Architects Continuing Education

More information

Appendix GENERAL INFORMATION TECHNICAL INFORMATION BUILDING CODES INDEX

Appendix GENERAL INFORMATION TECHNICAL INFORMATION BUILDING CODES INDEX Appendix GENERAL INFORMATION TECHNICAL INFORMATION BUILDING CODES INDEX Building Codes Building Codes Prior to using any railing products, it is incumbent on designers, fabricators and installers to make

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 09-17-1229 Application No. 2009-10 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Article 9.19.1.1.

More information

Bryan County Middle/High Renovation SECTION TELESCOPING STANDS

Bryan County Middle/High Renovation SECTION TELESCOPING STANDS SECTION 12 6610 TELESCOPING STANDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

BCAC MOE list of changes to consider PC June 5, 2018

BCAC MOE list of changes to consider PC June 5, 2018 BCAC MOE list of changes to consider PC June 5, 2018 IBC 10-4/IRC 3-1 - EERO E108-D not an errata like Jeff Inks said E109-D committee confused this size with door allowances IBC 10-7 delayed egress locks

More information

TOWN OF PERINTON 1350 TURK HILL ROAD. FAIRPORT, NEW YORK (585) , Fax: (585) ,

TOWN OF PERINTON 1350 TURK HILL ROAD. FAIRPORT, NEW YORK (585) , Fax: (585) , BUILDING PERMIT REQUIREMENTS FOR BASEMENT REMODELING 1. Provide two copies of a detailed floor plan and elevation drawing, see sample drawings on page 9 and 10. Include materials, sizes, supports, heating,

More information

STAIRWAYS, HANDRAILS, AND GUARDRAILS (RESIDENTIAL)

STAIRWAYS, HANDRAILS, AND GUARDRAILS (RESIDENTIAL) 01/25/08 STAIRWAYS, HANDRAILS, AND GUARDRAILS (RESIDENTIAL) City of Austin International Residential Code: 500 Fourth Avenue NE R314.1 Width. Stairways shall not be less than 36 in clear width at all points

More information

SPECIFICATION FOR PRECAST/ COMPOSITE CONCRETE FLOORS/ ROOF DECKS SECTION E60

SPECIFICATION FOR PRECAST/ COMPOSITE CONCRETE FLOORS/ ROOF DECKS SECTION E60 SPECIFICATION FOR SECTION E60 A 2007-09-26 S.W. Revision Date Issue Authorised By Approved for Issue SW Date 24.09.07 clarkebond Page 1 of 6 To be read with Preliminaries/ General Conditions. GENERAL 10

More information

CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE 01. GENERAL ADMINISTRATION 3 % Project Administration 3%

CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE 01. GENERAL ADMINISTRATION 3 % Project Administration 3% CALIFORNIA BUILDING PLANS EXAMINER CONTENT OUTLINE EXAM ID: I6 80 multiple-choice questions 3-1/2-hour time limit Open book 01. GENERAL ADMINISTRATION 3 % 0101. Project Administration 3% Verify that plans,

More information

-=== Building Safety Departnlent 'Neil Avenue, Room 202 Cheyenne, WY Phone: (307) Fax: (307) RAMPS

-=== Building Safety Departnlent 'Neil Avenue, Room 202 Cheyenne, WY Phone: (307) Fax: (307) RAMPS Building Safety Departnlent 2101 0 'Neil Avenue, Room 202 Cheyenne, WY 82001 Phone: (307) 637-6265 Fax: (307) 637-6366 A COMMUNITY -=== II January 24,2017 OF CHOICE RAMPS This handout was prepared in an

More information

Wood Decks Zoning and construction requirements for open non-sheltered wood decks for residential dwellings

Wood Decks Zoning and construction requirements for open non-sheltered wood decks for residential dwellings PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Wood Decks Zoning and construction requirements for open non-sheltered wood decks for residential dwellings November 2017 contents General Information... 3

More information