A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein.
|
|
- Irene Snow
- 5 years ago
- Views:
Transcription
1 16470 PANELBOARDS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: An optional keynote to the Drawings follows major product titles, for A/Es using National CAD Standard. ************************************************************************************************************* PART 1 GENERAL 1.1 SUMMARY A. Provide a complete Distribution Panelboard system as indicated on the drawings, and as specified herein. B. All materials shall be listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL). C. Related Sections: Painting Wire and Cable Overcurrent Protective Devices. 1.2 SYSTEM DESCRIPTION A. Panelboards used as service entrance equipment shall be NRTL labeled as service entrance equipment. 1.3 SUBMITTALS A. Submit shop drawings, manufacturer's literature, and technical data before starting work. B. All switchboards and panelboards submitted shall be designed and manufactured according to the latest revisions of the following specifications: 1. UL 50, UL 67, UL 89, Ul489, Ul 891, UL 1283, UL Nema AB-1, PB1, PB1.1, PB2, PB2.1 PB NFPA Federal Specifications: W-C-375B, W-P-115C PART 2 PRODUCTS 2.1 MANUFACTURERS A. Panelboards: 1. General Electric. 2. Siemens. 3. Square D. Project No. SPECIFICATION GUIDELINES
2 4. Eaton Corp. 2.2 EQUIPMENT A. Distribution and Power Panelboards: 1. Interior: Provide fully rated plated copper bus. Plating shall run the entire length of the bus bar. Solid neutral and ground bar shall be copper. Maximum rating: 1200 amp. 2. Main breaker shall be horizontally mounted. Main breakers shall have conspicuous marking labels. 3. Trims shall have door with keyed lock. All locks shall be keyed the same. 4. Provide directory holder and typed directory for all circuits. 5. Enclosure shall be galvanized galvaneal steel constructed in accordance with UL50 and NEMA 250. Box end walls shall be blank. 6. Short circuit current ratings shall be equal to or greater than available fault current at point of application. NRTL listed series ratings may be utilized, where not in violation of NEC Provide documentation of NRTL listed series rating used. 7. Surge Protective Devices (SPD) shall be provided when specified in the design and associated electrical plans, with optional peak surge current of 260kA. 8. Distribution panels for use at 120/208 volts shall ne NRTL listed with minimum integrated assembly rating of 22K AIC. 9. Distribution panelboards, 400 amperes and over, shall be provided with molded case circuit breakers tested and labeled according to UL 489. B. Lighting, Receptacle and Power Panelboards 1. Interior: Provide fully rated plated copper bus. Plating shall run the entire length of the bus bar. Solid neutral and ground bar to be copper. Maximum rating: 600amp. 2. Main breaker shall be vertically or horizontally located and have conspicuous marking labels. 3. Trims shall have door with keyed lock. All locks to be keyed the same. Provide trims with concealed door hinges and trim screws for panels 600 amps or less. 4. Provide directory holder and typed directory for all circuits. 5. Enclosure shall be galvanized steel constructed in accordance with UL50. Box endwalls shall be blank. 6. Short circuit current ratings shall be equal to or greater than available fault current at point of application. NRTL listed series ratings may be utilized, where not in violation of NEC Provide documentation of NRTL listed series rating used. 7. Provide SPD s when specified in the design and associated electrical plans, with optional peak surge current of 100kA. 8. Minimum rating of breakers shall be as follows: a. Lighting and power panels for use at 120/208 volts: 225 amp maximum with circuit breakers rated at 10K AIC symmetrical at 240 volts. b. Lighting and power panels for use at 480/277 volts: 225 amp maximum with circuit breakers rated at 14K AIC symmetrical at 480 volts. 9. Interiors shall be factory assembled and designed to allow switching and protective devices to be replaced without disturbing adjacent units, without removing the main bus connectors, and allowing circuits to change without machining, drilling or tapping. Project No. SPECIFICATION GUIDELINES
3 10. Branch circuits shall be arranged using double row construction unless narrow column panels are indicated. A nameplate shall be provided listing panel type and ratings. Circuit breakers shall be bolt-on type. 11. Unless otherwise noted, full size insulated neutral bars shall be included. Bus bar taps for panels with single pole branches shall be arranged for sequence phasing of the branch circuit devices. Neutral bussing shall have a suitable lug for each outgoing feeder requiring a neutral connection. A ground bus shall be provided in all panels. C. Boxes and Trims shall meet the following criteria: 1. Boxes shall be at least 20 inches wide made from code gage galvanized sheet steel. a. Provide minimum gutter space according to NEC requirements. b. Where feeder cables supplying the mains of a panel are carried through its box to supply other electrical equipment, the box shall be sized to include the additional required wiring space. c. At least 4 interior mounting studs with adjustable nuts shall be provided. 2. Switching device handles shall be accessible. a. Doors and panelboard trims shall not uncover any live parts. b. Doors shall have flush chrome plated handle with cylinder lock and catch, except doors over 48 inches in height shall have auxiliary fasteners top and bottom of door in addition to the flush type cylinder lock and catch. c. Panelboard switching devices with individual dead front doors shall be acceptable instead of standard door in trim design. d. Panelboard trim clamps shall be of the indicating type. 3. Exterior and interior steel surfaces of the trim shall be properly cleaned, primed with rust inhibiting phosphatic coating, and finished with manufacturer's standard gray paint. a. Trims for flush panels shall overlap the box for at least 3/4" all around. b. Surface trims shall have the same width and height as the box. c. Trims shall be mountable by a screwdriver without the need for special tools. d. After installation, trim clamps shall not be accessible when the panel door is closed and locked. 4. Panelboards exposed to the weather shall have NEMA type 3R raintight enclosure or NEMA 4X in corrosive environments. D. Electrical Components: 1. Main bus bars shall be fully rated copper bus bars, with plating shall running the entire length of the bus bar, and shall be sized according to NRTL standards to limit the temperature rise on any current carrying part to a maximum of 50 degrees C. above an ambient of 40 degrees C. maximum. Provide main circuit breakers, main lugs, or sub-feed lugs as required. 2. Each panelboard shall incorporate breakers as shown with AIC or higher, at the application voltage, than the available fault at its location along the electrical Project No. SPECIFICATION GUIDELINES
4 distribution system, as determined by the short circuit study. Minimum rating of breakers shall be: a. Lighting and power panels for use at 120/208 volts: 225 amp maximum with circuit breakers rated at 10K AIC symmetrical at 240 volts. b. Lighting and power panels for use at 480/277 volts: 225 amp maximum with circuit breakers rated at 14K AIC symmetrical at 480 volts. c. Distribution panels for use at 120/208 volts: UL listed with minimum integrated assembly rating of 22K AIC. 3. Panels tested and listed according to UL 67 and bearing an integrated short circuit rating shall be determined by the short circuit study on the electrical system with 10,000 AIC minimum. 4. Any 2 single pole circuit breakers shall be replaceable by 1 two-pole circuit breaker and any 3 single-pole breakers shall be replaceable by 1 three-pole circuit breaker. 5. Where new circuit breakers are specified to be installed within existing panelboards, they shall be compatible in terms of manufacture, type, and AIC. 6. Breakers 100 ampere through 400 ampere frame sizes shall be thermal-magnetic trip with inverse time current characteristics, unless otherwise noted. 7. Provide ground fault circuit interrupter circuit breakers where indicated. 8. Emergency Panelboards Identification: Paint door red and stencil in 1 inch high yellow letters "EMERGENCY PANEL" in addition to appropriate individual panel identification as shown on drawings. PART 3 EXECUTION 3.1 INSPECTION A. Do not proceed with the work of this section until conditions detrimental to the proper and timely completion of the work have been corrected in an acceptable manner. 3.2 INSTALLATION A. Panelboards shall be installed where indicated and with top of cabinet 6'-6" above floor, and shall be rigidly and securely attached to building construction and shall not depend upon conduit for support. Allow at least 1/2" air space behind wall mounted panelboards. B. Install panelboards according to manufacturer's recommended data. Maintain clearances required by the National Electrical Code, with particular attention to working space around panelboards. Maintain clear space above panelboards, coordinate with other trades to avoid placement of panelboards below piping, ductwork, or other foreign appurtenances. Relocate panels at no additional cost should such interferences occur. C. Supply panelboards with phenolic nameplate 1 inch x 3 inch on exterior of panels and engraved with panel designation and voltage rating. Lighting and power panelboards shall be provided with a clear plastic enclosed typewritten directory inside. Circuit identification shall include load type (lighting, receptacles, etc.) and rooms served. D. Where flush type panelboards are indicated, provide one 3/4" empty conduit terminated in accessible ceiling above for each 3 spare circuit breakers provided in the panelboard. Project No. SPECIFICATION GUIDELINES
5 E. Install circuit breakers in existing panelboards according to manufacturer's recommendation. Verify tightness of connections including mains. Identify new circuits on the panel directory. If none exists, provide one. F. Clean and touch up panelboard as required at completion of the project. G. Support surface mounted panelboards for other than masonry walls, from floor slab secured "Kindorf" or "Unistrut" channels. Mount those installed on masonry walls to back boards secured to walls, and according to manufacturer s recommendations and applicable codes and regulations. Contractor shall coordinate manufacturer s actual panelboard dimensions with room clearances to conform with NEC requirements. END OF SECTION Project No. SPECIFICATION GUIDELINES
SECTION SECONDARY UNIT SUBSTATIONS
SECTION 26 12 16 SECONDARY UNIT SUBSTATIONS PART 1 GENERAL 1.1 SUMMARY This section describes metal-clad, indoor or outdoor, secondary unit substations with integral primary fused disconnect switches,
More informationHouston First Corporation Package 1 SECTION MEDIUM VOLTAGE FUSED SWITCH INTERRUPTER
PART 1 - GENERAL 1.1 SUMMARY SECTION 26 13 16 MEDIUM VOLTAGE FUSED SWITCH INTERRUPTER A. The scope of this section includes providing and assembling materials and equipment for the dead-front, medium voltage
More informationSECTION OUTLET, PULL, AND JUNCTION BOXES
SECTION 16131 OUTLET, PULL, AND JUNCTION BOXES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16112 - Raceways and Conduits. 1.02 SYSTEM DESCRIPTION A. Performance Requirements:
More informationCONTENTS. B. System Design and Performance Requirements
16060 Grounding and Bonding This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or
More informationSECTION ENCLOSED BUS ASSEMBLIES
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the
More informationSECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:
SECTION 16130 (Master Template Final-05) ELECTRICAL BOXES PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide boxes for electrical equipment and wiring devices as follows: 1. Wall and ceiling outlet boxes.
More informationA. Section includes busway and fittings including plug-in units.
SECTION 26 25 00 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes busway and fittings including plug-in units. 1.2 REFERENCES A. Institute of Electrical and Electronics Engineers:
More informationSECTION GROUNDING
SECTION 16450 GROUNDING PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies general grounding and bonding requirements of electrical and telecommunication installations for personnel safety, equipment
More informationSECTION MOTOR CONTROL CENTER
SECTION 16445 MOTOR CONTROL CENTER PART 1 GENERAL 1.01 DESCRIPTION A. This section covers the contract item Motor Control Center (MCC). The contract item includes demolition and removal of existing MCC;
More informationSECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number
MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number PART 1 GENERAL 01 02 03 04 SCOPE Furnish and install Manual Transfer Switches (MTS) and
More informationA. All materials shall be tested and listed by an OSHA approved Nationally Recognized Testing Laboratory (NRTL).
16450 GROUNDING ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 05 26 An optional keynote to the
More informationSPECIFICATION FOR SIMPLEX SWITCHBOARDS
SPECIFICATION FOR SIMPLEX SWITCHBOARDS 1.0 SCOPE This specification presents general guidelines, design criteria, and construction requirements for AZZ ENCLOSURE SYSTEMS SIMPLEX PANELS for providing control
More informationSECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph
More informationBUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466
BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein
More informationSECTION to 5000 AMPERE PLUG-IN AND FEEDER BUSWAYS - SPECTRA. A. Low-Voltage Plug-in Busway to 5000 ampere, 600 VAC
PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low-Voltage Plug-in Busway - 225 to 5000 ampere, 600 VAC 1.02 RELATED
More informationADDENDUM NO. 1 BID AND CONTRACT DOCUMENTS FOR. BID No. 2019PW299
ADDENDUM NO. 1 BID AND CONTRACT DOCUMENTS FOR BID No. 2019PW299 CHAFFEY COMMUNITY COLLEGE DISTRICT TRANSFORMER REPLACEMENT PROJECT RANCHO CUCAMONGA, CALIFORNIA COUNTY OF SAN BERNARDINO CHAFFEY COMMUNITY
More informationSECTION ENCLOSED BUS ASSEMBLIES
SECTION 262500 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationW-P-115C March 14, 1990 SUPERSEDING W-P-115B June 8, 1984 FEDERAL SPECIFICATION PANEL, POWER DISTRIBUTION
March 14, 1990 SUPERSEDING W-P-115B June 8, 1984 FEDERAL SPECIFICATION PANEL, POWER DISTRIBUTION This specification is approved by the Commissioner, Federal Supply Service, General Services Administration,
More information1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.
ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 11 00 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationSECTION BUSWAYS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 25 11 BUSWAYS SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable to the section and
More informationSPECIAL SPECIFICATION 6499 Environmentally controlled Communications Building
2004 Specifications CSJ 0720-03-095 SPECIAL SPECIFICATION 6499 Environmentally controlled Communications Building 1. Description. Furnish and install Environmentally Controlled Communications Building
More informationDIVISION 16. Electrical Specifications
DIVISION 16 Electrical Specifications 16.1 General - Provide all electrical materials and methods as shown on the Drawings, as specified herein, and as needed for a complete and proper installation, including
More informationSECTION PATIENT BED SERVICE WALLS
PART 1 GENERAL 1.1 DESCRIPTION: SECTION 10 25 13 PATIENT BED SERVICE WALLS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Due to the very specialized nature of Patient Wall
More informationAugust 2011 DSC DeLand Campus COOP # SECTION INTERIOR DISTRIBUTION SYSTEM
SECTION 262000 INTERIOR DISTRIBUTION SYSTEM PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the
More information31-SDMS-03 REV. 01 SPECIFICATIONS FOR
31-SDMS-03 REV. 01 SPECIFICATIONS FOR LOW VOLTAGE CABINET FOR POLE MOUNTED TRANSFORMER This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Description
More informationTechnical Specifications
ST007-005 Lighting for Public Safety College Of Staten Island Technical Specifications (Issued for Bid) April 19, 2010 SUBMITTED BY: W-engineering, P.C. 240 W. 35 th Street, Suite 302 New York, NY 10001
More informationSECTION LOW-VOLTAGE SWITCHGEAR
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 00 LOW-VOLTAGE SWITCHGEAR SPEC WRITER NOTE: This specification is not for general use. Use Section 26 24 13, DISTRIBUTION SWITCHBOARDS for most applications.
More informationOVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE. See Chapter 3, Section 3.01 for more information about point of entrance (POE).
6.01 GENERAL OVERHEAD SERVICES - RESIDENTIAL & GENERAL SERVICE See Chapter 3, Section 3.01 for more information about point of entrance (POE). In all cases, the customer installs, owns, and maintains the
More informationNOVADYNE 365 Lansdowne St. E., Unit 1, Peterborough, ON K9L 2A3
SYMBOL MODEL NUMBER LIGHTING CONTROLS SCHEDULE MANUFACTURER DESCRIPTION EMERGENCY LIGHTING & EXIT SCHEDULE SYMBOL MODEL NUMBER MANUFACTURER DESCRIPTION RECEPTACLE LEGEND LIGHTING LEGEND 15 Lansdowne Street
More informationB. Scope of work includes replacement of all existing panels or panel interiors, reconnection of existing loads, electric services, etc.
Farmington, Missouri Project Number M1801-01 SECTION 262416- PANELBOARDS PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationELECTRIC METERING GENERAL
1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 EQUIPMENT 5.0 METER REQUIREMENTS 6.0 METER FACILITIES 7.0 ELECTRICAL CONNECTIONS 2.0 SCOPE This guide covers general requirements and codes for
More informationSECTION CONDUITS AND BOXES PART 1- GENERAL. A. Work covered by this section includes the furnishing and installation of conduits and boxes.
SECTION 16111 CONDUITS AND BOXES 1.01 DESCRIPTION PART 1- GENERAL A. Work covered by this section includes the furnishing and installation of conduits and boxes. 1.02 SUBMITTALS A. The Contractor shall
More informationOVERHEAD SERVICES - SECONDARY
OVERHEAD SERVICES - SECONDARY Contents - Overhead Services... O-1 General Requirements for Overhead Service... O-2 Names of Parts for Overhead Service... O-3 Service Attachment on an Unguyed Service Mast...
More informationThis product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.
AFC Cable Systems, Inc. Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519.13 METAL CLAD CABLE-MC
More informationMETERING INSTALLATION
4.01 METERING SPECIFICATIONS METERING INSTALLATION Metering specifications will be issued to the customer by OPPD. Metering specifications are required before any work is started on all new wiring or additions
More informationSECTION AUTOMATIC TRANSFER SWITCH
SECTION 26 36 23 AUTOMATIC TRANSFER SWITCH PART 1: GENERAL 1.01 SCOPE A. Furnish all labor, materials, equipment and appurtenances, install and test electrically operated, automatic transfer switch (ATS)
More informationSUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard
SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard PART 1 GENERAL 1.1 Scope A. The intent of this specification is to provide power control for the parallel operation of generator
More informationSECTION GENERAL ELECTRICAL REQUIREMENTS PART 1- GENERAL
1.01 DESCRIPTION SECTION 16000 GENERAL ELECTRICAL REQUIREMENTS PART 1- GENERAL A. This Section includes the general provisions applicable to electrical work and testing of the completed electrical systems.
More information2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING
2003 International Residential Code ELECTRICAL PROVISIONS ONLY October 2005 EDITORIAL CHANGES SEVENTH PRINTING E3305.3: now reads The space equal to the width and depth of the panelboard and extending
More informationThis product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update.
Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519 METAL CLAD CABLE - MC-PLUS Neutral
More informationA. Basket Cable Tray: A fabricated structure consisting of wire mesh bottom and side rails.
SECTION 16714 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationHOTEL SPECIFICATION SECTION 08100
Part 1 General HOTEL SPECIFICATION SECTION 08100 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified including, but not limited
More informationHOLLOW METAL DOORS AND FRAMES SECTION HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL
13686.00 HOLLOW METAL DOORS AND FRAMES 081113-1 SECTION 081113 - HOLLOW METAL DOORS AND FRAMES 1.1 RELATED DOCUMENTS: PART 1 - GENERAL A. Drawings and general provisions of Contract, including General
More informationINDEX. Page SECTION 1.0: SCOPE Toronto Hydro Requirements Ontario Electrical Safety Code 1 SECTION 2.0: PURPOSE 1
INDEX Page SECTION 1.0: SCOPE 1 1.1 Toronto Hydro Requirements 1 1.2 Ontario Electrical Safety Code 1 SECTION 2.0: PURPOSE 1 SECTION 3.0: DEFINITIONS AND THE INTERNATIONAL SYSTEM OF UNITS 1 3.1 Definitions
More information37-SDMS-01 REV. 03 SPECIFICATIONS FOR
37-SDMS-01 REV. 03 SPECIFICATIONS FOR LOW VOLTAGE MOLDED CASE CIRCUIT BREAKERS FOR SERVICE CONNECTIONS This specification is property of SEC and subject to change or modification without any notice CLAUSE
More informationDIVISION 26 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL RELATED DOCUMENTS
PART 1 - GENERAL 01.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification sections, apply to work of this Section.
More informationSECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and
More informationSECTION EARTHING AND EARTH FAULT PROTECTION
SECTION 16660 PART 1 - GENERAL 1.01 DESCRIPTION A. The work to be performed includes, but is not necessarily limited to, all work involved with the construction and assembly of a complete electrical earthing
More informationSERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES
SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED SWITCHGEAR WITH VACUUM LOAD INTERRUPTING
More informationSECTION LOW-VOLTAGE TRANSFORMERS
PART 1 GENERAL 1.1 DESCRIPTION SECTION 26 22 00 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between // // if not applicable to project. Also, delete any other item or paragraph not
More informationKaf-Tech Product Specification
Kaf-Tech Product Specification This product specification is written according to the Construction Specifications Institute MasterFormat, 2014 Update. SECTION 260519.13 METAL CLAD CABLE-LUMINARY CABLE
More informationSECTION ELECTRICAL MATERIALS AND METHODS
SECTION 26 00 20 ELECTRICAL MATERIALS AND METHODS PART 1: GENERAL 1.01 WORK INCLUDED A. Furnish and install all conduit, conduit fittings and boxes to complete the installation of all electrically operated
More informationCOLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100
COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 Part 1 General 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified,
More informationSECTION FACILITY LIGHTNING PROTECTION
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 41 00 FACILITY LIGHTNING PROTECTION SPEC WRITER NOTE: Delete between //----//if not applicable to project. Also delete any other item or paragraph not applicable
More informationSECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE
METAL-ENCLOSED BUS MEDIUM VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. The medium
More informationTitle: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards
Date Description of Change Pages / Sections Modified ID 6/15/16 Updated format, division title, and removed references to other sections. - mgl44 A. Summary This section contains design criteria for the
More informationA. American Society for Testing and Materials (ASTM): Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft.
SECTION 260000 ELECTRICAL PART 1- GENERAL 2.1 SUMMARY : Provide complete distribution systems for electrical power as shown on the drawings or required by other sections of these specifications. A. Work
More informationSECTION A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013.
PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 26 0519 A. Single conductor building wire. B. Metal-clad cable. C. Wiring connectors. D. Electrical tape. E. Wire pulling lubricant. F. Cable ties. 1.2 RELATED
More informationThe fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general specifications:
Query No.1 ; we need more specs. about fire resistant doors Answer to Query No. 1: The fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general
More informationLOW-VOLTAGE SERVICE ENTRANCE SWITCHBOARDS SECTION D
SECTION 16428D (26 24 13.01) LOW VOLTAGE SWITCHBOARDS TYPE POW-R-LINE C 600 VAC MAXIMUM PART 1 GENERAL 1.01 SCOPE A. The contractor shall furnish and install where indicated on the drawings a dead front
More informationa) Line and load compartments must be separated by a stable barrier.
1.00 GENERAL 1.01 The electric utility shall furnish and connect all meters, instrument transformers, test switches, and meter control wiring necessary to complete the meter installation. 1.02 The customer
More informationUNDERGROUND SERVICES SECONDARY
Reference UNDERGROUND SERVICES SECONDARY Underground services secondary... U- 1 General requirements for underground service... U- 2 Name of parts for underground service... U- 3 Conduit layouts... U-
More information(Condensed from National Electric Code)
WIRING, SPECIFICATIONS, INSPECTION, AND METER INSTALLATION PROCEDURES FOR RESIDENTIAL CUSTOMERS SERVED BY SOUTHWEST ARKANSAS ELECTRIC COOPERATIVE CORPORATION Effective April 1, 1974 Revised February 3,
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS. Use for Southeast projects only **************************************************************************
USACE / NAVFAC / AFCESA / NASA UFGS-26 13 00.00 25 (July 2006) ------------------------------- Preparing Activity: NAVFAC Superseding Southeast UFGS-S-16345N (March 2001) Use in lieu of UFGS-26 13 00.00
More informationSECTION FIELD PANELS
Stanford University Facilities Design Guidelines SECTION 25 14 23 FIELD PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section includes control panel and enclosure requirements for building control systems.
More informationSECTION WIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.
SECTION 16120 WIRE AND CABLE PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 16112 - Raceways and Conduit. 2. 16155 - Motor Power and Control Wiring. 1.02 SYSTEM DESCRIPTION A. Performance Requirements:
More informationSECTION BASIC ELECTRICAL REQUIREMENTS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions, apply to work of this section. 1.2 SUMMARY A. This section specifies
More informationPoint Eight Power, Inc. Switchgear Specification Low Voltage UL 1558 Metal-Enclosed Switchgear
Table of Content 1.0 General... 2 2.0 Scope... 2 3.0 Applicable Codes, Standards and Qualifications... 2 4.0 Service and Environmental Conditions... 3 5.0 Construction... 3 6.0 Front Breaker Compartment
More informationWIRE AND CABLE Raceways and Conduit Motor Power and Control Wiring.
SECTION 16120 WIRE AND CABLE PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 16112 - Raceways and Conduit. 2. 16155 - Motor Power and Control Wiring. 1.02 SYSTEM DESCRIPTION A. Performance Requirements:
More informationDOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES
Guidelines effective March 5, 2007 NES is committed to providing safe, reliable electric service at a reasonable price for all of our customers. These guidelines offer direction for activities relating
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract apply to this Section. 1.2 SUMMARY A. This Section
More informationMANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS
DAIMLERCHRYSLER MANUFACTURING TECHNICAL INSTRUCTIONS SAFETY Subject: DESIGN, MAINTENANCE AND INSPECTION OF SECONDARY ELECTRICAL DISTRIBUTION SYSTEMS ISSUE DATE: 5/1/90 EFFECTIVE DATE: 2/4/92 REVIEW DATE:
More information6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4.
6. SECONDARY SERVICES (under 600 volts) 6.1 AVAILABILITY For the electrical characteristics of available secondary services see Section 3.4. 6.2 OVERHEAD SERVICES Wiring of any premises for connection
More informationOPERATING PROCEDURE NO. 310
OPERATING PROCEDURE NO. 310 Related Operating Procedures: 310A; 310B; 310C; 310D SUBJECT: Conditions of Service Issued: February 10, 2014 Revised: March 28, 2016 OBJECTIVE: To establish the rules, regulations
More informationSECTION GROUNDING AND BONDING
SECTION 16060 PART 1 GENERAL 1.01 DESCRIPTION A. Section includes requirements for an electrical grounding system, including electrodes, grounding rods, connectors, insulators, equipment grounding and
More informationA. Product Data: For surface pathways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.
ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 05 28 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More information56-SDMS-01 REV. 01 SPECIFICATIONS FOR
56-SDMS-01 REV. 01 SPECIFICATIONS FOR 13.8KV UNIT SUBSTATIONS This specification is property of SEC and subject to change or modification without any notice CONTENTS PAGE No. 1.0 SCOPE 3 2.0 CROSS REFERENCES
More informationE001 TERRACE VIEW APARTMENTS ELECTRICAL LEGEND, NOTES, AND ABBREVIATIONS 02/13/18 HUNT CLUB ROAD BLACKSBURG, VA KEY PLAN
DATE PROJECT ENGINEER LEGEND, NOTES, AND ABBREVIATIONS E00 SECTION 6000 - SPECIFICATIONS PART - GENERAL. BASIC METHODS A. DRAWINGS ARE SCHEMATIC AND DIAGRAMMATIC. WORK SHALL BE PERFORMED IN A NEAT AND
More information2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2008 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
More informationSECTION (16071) - VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
SECTION 26 05 48 (16071) - VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. This Section includes seismic restraints and other earthquake-damage-reduction measures for
More informationSECTION LIGHTNING PROTECTION SYSTEM
SECTION 16670 - LIGHTNING PROTECTION SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION GROUNDING AND BONDING
SECTION 16060 GROUNDING AND BONDING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationCONSOLIDATED EDISON COMPANY OF NEW YORK, INC Van Dam Street Long Island City, NY ELECTRIC METER SHOP DEPARTMENT
CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 48-05 Van Dam Street Long Island City, NY 11101 ELECTRIC METER SHOP DEPARTMENT METER ENGINEERING SPECIFICATION MES-350 REVISION 3 June 2016 EFFECTIVE DATE
More informationELECTRICAL SECTION 2
ELECTRICAL SECTION 2 COMMON WORK RESULTS FOR ELECTRICAL PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. This Section includes raceways, conductors and cables, grounding materials, boxes, electrical identification
More informationPower Electronics, Inc. Packaged Equipment Center Standard Construction and Design Features
DESIGN CRITERIA FOR STANDARD CONSTRUCTION: These standard design elements of the P.E.I. Power Equipment Center are utilized to meet the following design criteria per ASCE 7-05 as adopted by the IBC (International
More informationSECTION LIGHTING. A. Section Basic Electrical Materials and Methods
SECTION 16500 LIGHTING PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide lighting fixtures of sizes, types and ratings as indicated; complete with, but not necessarily limited to, housings, lamps, lamp holders,
More informationDESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7
DESIGN GUIDELINES WIRING AND CONDUITS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification
More informationSECTION CONDUITS AND BACKBOXES FOR COMMUNICATIONS SYSTEMS
SECTION 16711-27 05 28.33 PART 1 - GENERAL 1.01 SUMMARY A. This section includes Labor, materials and equipment necessary to complete the installation required for the items specified under this Section,
More information3. Intermediate metal conduit (IMC). 4. Electric metallic tubing (EMT). 5. Flexible metal conduit (FLEX). 6. Polyvinyl chloride conduit (PVC).
SECTION 16111 CONDUITS PART 1 - GENERAL 1.01 DESCRIPTION A. General: Provide conduits, complete, as shown, specified or required per Contract Documents. Principal items include: 1. Rigid aluminum conduit.
More informationUniversity of Rochester October 17, 2008 Brooks Landing Business Center
SECTION 260500 COMMON WORK RESULTS FOR ELECTRICAL PART 1 - GENERAL 1.1 SCOPE A. Minimum composition requirements and/or installation methods for the following materials and work are included in this section:
More informationInspection Guide for PV Systems in One- and Two- Family Dwellings (For Rooftop Photovoltaic Systems meeting the Standard Plan)
TOOLKIT DOCUMENT #7 Inspection Guide for PV Systems in One- and Two- Family Dwellings (For Rooftop Photovoltaic Systems meeting the Standard Plan) This document has two sections. Neither section is all-inclusive
More informationHUMBOLDT COUNTY BUILDING & SAFETY DEPARTMENT CITY OF WINNEMUCCA BUILDING DEPARTMENT
HUMBOLDT COUNTY BUILDING & SAFETY DEPARTMENT CITY OF WINNEMUCCA BUILDING DEPARTMENT FOR PRIVATE THREE-SIDED POST FRAMED (NON-ENGINEERED) OUTBUILDINGS LOCATED ON RESIDENTIAL LOTS ONLY Buildings must meet
More informationAPPLICATION FOR FINISHED BASEMENT PERMIT
APPLICATION FOR FINISHED BASEMENT PERMIT REAL ESTATE TAX I.D. #: - - _ - _ 7607 W College Drive Ph: (708) 361-1804 Fax: (708) 923-7112 building@palosheights.org APPLICANTS: COMPLETE ALL ITEMS AND SUBMIT
More informationSECTION CONVECTORS
SECTION 23 82 33 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph
More informationSECTION SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION
SECTION 16-372 SUBSTATION BUS ASSEMBLIES ERGLE SUBSTATION 1. GENERAL SPECIFICATIONS The work of this Section includes furnishing all labor, equipment, materials (unless specifically identified as Owner-furnished)
More informationSECTION BASIC ELECTRICAL MATERIALS AND METHODS
SECTION 26 05 05 BASIC ELECTRICAL MATERIALS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the limited scope construction materials and methods for application with electrical installations as follows:
More informationSECTION PART 1 GENERAL
SECTION 16060 GROUNDING AND BONDING PART 1 GENERAL 1.1 SUMMARY A. Section Includes: Grounding of electrical systems and equipment and basic requirements for ground for equipment, circuits, and systems.
More informationUNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES
7.01 GENERAL UNDERGROUND SERVICES (RESIDENTIAL) SINGLE FAMILY RESIDENTIAL, DUPLEXES, OR TOWNHOUSES Also refer to Chapter 3 (Service Entrances), and Chapter 4 (Metering Installation). OPPD will install,
More informationSECTION STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 08110 - STEEL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General, Supplementary, and Special Conditions and Division 1 Specification
More information