SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System
|
|
- Diana Walker
- 5 years ago
- Views:
Transcription
1 SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Pan System Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ (973)
2 RF MODULAR PAN SYSTEM PART 1 GENERAL 1.1 SECTION INCLUDES A. Design and engineering of complete system. B. All shielding components required for complete installation, including but not limited to the following: 1. Shielding pans. 2. Vapor barrier. 3. Dielectric barrier. 4. As required structural supports. 5. Doors, frames, and hardware. 6. Wave guide vents for HVAC penetrations of shielding. 7. Filters for power penetration of shielding. 8. RF/EMI Gasketing 9. Fasteners and accessories. 1.2 RELATED SECTIONS A. Section Door Hardware. B. Section Glazing. C. Section Gypsum Board Systems. D. Section Resilient Flooring. E. Section Painting. F. Section Plumbing Piping. G. Section Air Conditioning Ductwork. H. Section Building Wire and Cable. 1.3 REFERENCES A. AISC M016 - Manual of Steel Construction -- Allowable Stress Design; American Institute of Steel Construction, Inc. B. ASTM A 36/A 36M - Standard Specification for Carbon Structural Steel
3 C. ASTM A 366/A 366M - Standard Specification for Steel, Sheet, Carbon, Cold- Rolled, Commercial Quality. D. ASTM A 653/A 653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process. E. AWS D1.1 - Structural Welding Code - Steel; American Welding Society. F. MIL-E-4957A - Enclosure for Electromagnetic Shielding, Demountable, Prefabricated for Electronic Test Purposes. G. MIL-STD-220A - Method of Insertion Loss for Radio Frequency Filters. H. MIL-STD Method of Attenuation Measurements for Electromagnetic Shielding Enclosures for Electronic Test Purposes. I. NSA National Security Agency Specification for RF Shielded Enclosures for Communication Equipment. J. NSA 73-2A - National Security Agency Specification for RF Shielding of Large Architectural Areas. 1.4 PERFORMANCE REQUIREMENTS A. Provide a controlled area in which radio frequency signals from any source will be contained or prevented from entering. Provide minimum attenuation versus frequency characteristics as listed below. B. Modular Pan Room: 1. Magnetic Field Attenuation: 60 db at 14 khz, increasing to 110 db at 200 khz. 2. Electric Field Attenuation: 120 db db from 200 khz through 50 MHz. 3. Plane Wave Attenuation: 100 db from 50 MHz through 10 GHz. 1.5 SUBMITTALS A. Submit a minimum of three sets of each type of document for review prior to commencement of fabrication. B. Product Data: Include manufacturer's complete information on system, including system specifications, operation and maintenance procedures, installation instructions, filter cut sheets which include data confirming performance, gasket cut
4 sheets which include data confirming performance, and air flow characteristics of waveguide air vents. C. Shop Drawings: Show full layout of system, including all dimensions and required points of coordination with work of other sections. Demonstrate full compliance with contract documents. 1.6 QUALITY ASSURANCE A. Standards: Perform work of this section in accordance with provisions of the following: 1. MIL-STD MIL-E-4957A. 3. MIL-STD-220A. 4. NSA NSA 73-2A 6. ISO 9001:2000 B. Manufacturer Qualifications: Company with demonstrated experience in successful design and installation of radio frequency shielding enclosures. 1. Manufacturer must have ISO 9001:2000 certification. 2. Submit information on not less than 5 completed projects that are similar to system specified. 3. Include name and location of project, date installation completed, name and telephone numbers of Architect, Owner, and Contractor. C. Installer Qualifications: Company approved by system manufacturer. 1.7 ENVIRONMENTAL REQUIREMENTS A. Do not begin work of this section until building has been enclosed and the area to receive radio frequency shielding is fully protected from the weather. 1.8 WARRANTY A. Provide manufacturer's standard warranty against defective materials and workmanship for the following periods after Date of Substantial Completion: 1. Enclosure: Ten (10) years. 2. Movable Components (Doors, Demountable Panels) and Power Filters: Two (2) years. PART 2 PRODUCTS 2.1 MANUFACTURERS A. This section is based on products manufactured by Global Partners in Shielding, Inc; 90 Dayton Avenue, Unit 4B Passaic, NJ 07055; Tel: ; Fax:
5 B. Substitutions: No substitutions permitted. 2.2 MODULAR PAN ROOM MATERIALS AND FABRICATION A. Floor, Wall, and Ceiling RF Pans: (1) Minimum 14 gage galvanized steel sheet, formed and welded into pan configuration with channel formed edges. Each pan edge to have a 40mm stiffening flange perpendicular to the field of the pan, and a 40mm return flange perpendicular to the stiffening flange. Overall dimensions of pans to be 1 meter maximum width, 2.44 meters maximum length. (2) Corners: Continuously weld corners of pans and grind smooth. All welds must be RF tight. Begin welds at the field of the pan and weld up to the flange corners. (3) Pan Joining System: Provide for fasteners on 6 inch centers on all 4 sides of each pan. Fasteners to be 5/16 hex head bolts with matching nuts, flat washers and lock washers. (4) Include railroad type steel gasket between pans at each connection point. B. Vapor Barrier: Polyethylene sheet, 4 mils minimum thickness. C. Dielectric Floor Underlayment: Masonite board, thickness 1/8 inch. D. Steel Supports: Lightweight steel framing, 14 gauge minimum thickness, 6 deep x 2 flange C channel with G60 minimum coating. Align channels back to back to form a modified I beam over the rooms center seam. Channels to be attached together with two #12 sheet metal screws at 12 on center. Overlap splices by a minimum of two feet on each side and secure with a minimum of six #12 sheet metal screws arranged around the perimeter of each side of the splice. Secure each pan to the supports by means of 5/16 nuts, bolts and washers at a maximum spacing of 6 on center. RF seal connections with an RF doughnut gasket placed between the pans and the supports. E. Door and Frame Assembly: Provide doors that have been mortised, fit, and hung at the factory, with a continuous RF shield around entire door perimeter. (1) Provide galvanized steel door and frame with a clear opening of 3 0 x 7 0 (1.2m x 2.1m) clear opening. Door and frame materials to be 11 gauge minimum galvanized steel with G-60 coating. (2) RF Seal: Recessed contact mechanism built into door frame, consisting of RF welded galvanized steel door frame pocket containing two sets of beryllium copper contact fingers concealed in the pocket against damage; design copper finger system to be capable of replacement without special tools, soldering, or welding. Use Tecknit Shielding Systems # special clip on beryllium copper fingers. Attach fingers over 11 gauge pocket edges and secure in place with J moulding attached to side of pockets. (3) Door Edge: Design knife edge extension of 11 gauge galvanized steel angle on door edge to fit between the two rows of contact fingers in door frame pocket
6 when door is closed. Edges must contact and compress all fingers to achieve RF seal. (4) Locking Device: Cam actuated type latch, operable from both sides of door. Equip hardware with permanently lubricated bearings at all points of pivot or rotation. Design cam latching mechanism to draw door to its final closing position or release door upon application of not more than 18 pounds of pressure to rotating lever handle. F. Wave Guide Vents: Provide 380mm x 380mm steel honeycomb vents with integral mounting collars for mounting and attachment to the RF pans, sized to accommodate HVAC requirements. Include appropriate RF gasketing and fasteners to facilitate the required shielding seal between the pan and the waveguide frame. G. RF Filters: Provide filters that allow penetration of RF shield by power line wires without degradation of RF shield attenuation characteristics. (1) Provide two two-wire 480V x 50Amp single phase AC power filters. Filter to be individual wall mount type. All ratings will meet or exceed specific requirements. H. RF/EMI Gasketing: Provide double core wire mesh gasketing at all pan to pan connections, pan to door frame connections, and pan to waveguide frame connections. (1) Provide Global Partners in Shielding, Inc gasket part number (2) Wire mesh to be tin/copper/iron composition (3) Minimum core diameter to be (4mm) (4) Minimum overall width to be 1.0 (25mm) I. Fasteners and accessories: utilize zinc plated steel bolts, nuts and washers at all connections. PART 3 EXECUTION 3.1 EXAMINATION A. Verify that substrates are ready to receive work of this section and openings correspond to locations and dimensions indicated on approved shop drawings. 1. Verify that floors are level to within 1/8 inch in 10 feet. 2. Verify that required utilities are available. B. Do not begin work of this section until unacceptable conditions have been corrected. 3.2 INSTALLATION
7 A. Install all components of RF/EMI shielding system in strict conformance with manufacturer's instructions and, if possible, under direct supervision of a factory representative. 1. Install all materials to be straight, level, true, and plumb. 2. Verify integrity of RF shielding before covering shield material with other finish materials. 3. Coordinate locations of penetrations with installation of RF shielding and approved shop drawings. B. Install a ground stud on the RF shield adjacent to power line filters inside the shield, as shown on shop drawings, for subsequent attachment of a dedicated wire to the electrical ground point of the building under Section Internal to RF shield, the ground stud shall become the attachment point for a green wire system. C. Modular Pan Room: 1. Floor, Wall, and Ceiling Panels: Install as indicated on drawings. 2. Install vapor retarder over floor substrate. 3. Floor Underlayment: Loose-lay sheets over substrate. D. Wave Guides: Attach securely to RF shielded enclosure with frames or attachment collars as detailed. E. Filters: Attach securely to RF shielding at all power line and communication wire penetrations, as required to prevent degradation of RF shield attenuation characteristics. 3.3 FIELD QUALITY CONTROL A. Perform field inspection and testing in accordance with provisions of Section B. Perform field testing of completed RF shielding installation in presence of Owner's representative, to verify compliance with specified attenuation versus frequency characteristics. C. Conduct test by manufacturer's qualified personnel, following procedures outlined in approved test plan and using calibrated test instrumentation. D. Issue formal test report detailing results of the RF testing process. E. Correct conditions responsible for any failure of RF shielding to meet specified attenuation characteristics at no additional cost to Owner. END OF SECTION
SECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Galvanized System
SECTION 13096 RADIO FREQUENCY SHIELDING ENCLOSURE RF Modular Galvanized System Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13096-1 RF MODULAR GALVANIZED SYSTEM PART
More informationSECTION RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System
SECTION 13096 RADIO FREQUENCY SHIELDING ENCLOSURE RF Welded System Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13096-1 RF WELDED SYSTEM PART 1 GENERAL 1.1 SECTION
More informationSECTION MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS
SECTION 13096 MODULAR GALVANIZED RF SHIELDING SYSTEM SPECIFICATIONS Prepared by: NELCO 125 Chenoweth Lane, Ste. 206 Louisville, KY 40207 (502) 899-3726 13096-1 MODULAR GALVANIZED RF SHIELDING SYSTEM PART
More informationSECTION COPPER/ SOLDERED RF SYSTEM SPECIFICATIONS
SECTION 13096 COPPER/ SOLDERED RF SYSTEM SPECIFICATIONS Prepared by: NELCO 125 Chenoweth Lane, Ste. 206 Louisville, KY 40207 (502) 899-3726 13096-1 SECTION 13096 COPPER RADIO FREQUENCY SHIELDING ENCLOSURE
More informationSECTION RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection
SECTION 13090 RADIATION SHIELDING ENCLOSURE Low Intensity Radiation Protection Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13090-1 LOW INTENSITY RADIATION PROTECTION
More informationArchitectural Roof and Wall Products Guide Specifications
Architectural Roof and Wall Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL WALL PANELS This Guide Specification
More informationSECTION METAL STAIRS
SECTION 05 51 00 METAL STAIRS PART 1 GENERAL 1.1 SUMMARY A. Section includes steel stair frame of structural sections, with closed risers; pan to receive concrete fill stair treads and landings; integral
More informationSECTION MULTI-USE COMPOSITE ALUMINUM PANELS
SECTION 07416 MULTI-USE COMPOSITE ALUMINUM PANELS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationHOLLOW METAL DOORS AND FRAMES SECTION HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL
13686.00 HOLLOW METAL DOORS AND FRAMES 081113-1 SECTION 081113 - HOLLOW METAL DOORS AND FRAMES 1.1 RELATED DOCUMENTS: PART 1 - GENERAL A. Drawings and general provisions of Contract, including General
More informationK. ASTM F436- Standard Specification for Hardened Steel Washers; 2011.
DIVISION 05 METALS 05 12 00 STRUCTURAL STEEL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Structural steel framing members, support members. 1.2 RELATED REQUIREMENTS A. Section 05 50 00 - Metal Fabrications:
More informationB. Polyethylene samples shall be submitted for Owner approval of color and quality.
Glass Rail ENGINEERED DASHERBOARD SPECIFICATIONS PART 1 - GENERAL 1.01 PROJECT SCOPE A. Contractor shall furnish and install one complete set of steel framed dasherboards as indicated on the drawings and
More informationB. Shop Drawings: For metal lockers. Include plans, elevations, sections, details, and attachments to other work.
SECTION 10 5113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,
More informationSECTION COLD-FORMED METAL TRUSSES
SECTION 054400 COLD-FORMED METAL TRUSSES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationArchitectural Wall Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Wall Products Guide Specifications FORMED METAL WALL PANELS This Guide Specification is
More informationSECTION MISCELLANEOUS METALS
PART 1 GENERAL 1.1 WORK OF THIS SECTION A. Contractor shall provide all labor, materials, equipment and incidentals as shown, specified and required to furnish and install all miscellaneous metal fabrications
More informationArchitectural Roof and Wall Products Guide Specifications
Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used
More informationSECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and
More informationSECTION COLD-FORMED METAL FRAMING
SECTION 05.40.00 COLD-FORMED METAL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Cold-formed metal framing for: B. Exterior load-bearing steel stud walls. 1. Interior load-bearing steel stud walls. 2.
More informationSECTION SOUND CONTROL DOORS
SECTION 08380 SOUND CONTROL DOORS 1.0 GENERAL 1.1 DESCRIPTION OF WORK A. Furnish and install Sound Control Doors specified herein and per the locations and orientations shown on the Contract Documents.
More informationAMBICO Limited Section and RFI\EMI SHEILDED STEEL DOOR AND FRAME ASSEMBLIES Page 1
Page 1 This section includes AMBICO RFI/EMI Steel Shielding Steel Door and Frame assemblies. This section relies on both the Canadian Steel Door Manufacturers Association (CSDMA.org) industry standard,
More informationSTRUCTURAL STEEL FRAMING
SECTION 05 12 00 - STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Section includes 1. Structural steel framing 2. Structural steel framing required for support and framing of rooftop mechanical
More informationDIVISION 5 - STRUCTURAL STEEL AND IRON WORK
DIVISION 5 - STRUCTURAL STEEL AND IRON WORK SECTION 05100 STRUCTURAL METAL FRAMING PART 1.00 GENERAL 1.01 SCOPE OF WORK A. Work Included: 1. 2. Structural steel complete in place. Steel joists complete
More informationSECTION PRE-ENGINEERED COLD-FORMED METAL ROOF AND FLOOR TRUSSES
SECTION 05440- PRE-ENGINEERED COLD-FORMED METAL ROOF AND FLOOR TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section includes pre-engineered, pre-fabricated cold formed steel framing elements. Work includes:
More informationSECTION COLD-FORMED METAL FRAMING
SECTION 05 40 00 COLD-FORMED METAL FRAMING SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the
More informationSECTION COLD-FORMED METAL FRAMING
SECTION 05.40.00 COLD-FORMED METAL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Cold-formed metal framing for: B. Exterior load-bearing steel stud walls. 1. Interior load-bearing steel stud walls. 2.
More informationHome Depot Page 1 of 5 HDPB Humacao, PR 10/19/09
PART 1 - GENERAL 1.01 SUMMARY A. Types of cold-formed metal framing units include the following: 1. C-shaped steel studs B. Related work specified elsewhere includes but may not be limited to: 1. Section
More informationSECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM
Page 1 of 6 SECTION 08 32 20 LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS SLIDING DOORS. SECTION INCLUDES OVERHEAD SLIDING TUBE ASSEMBLY, MOUNTING
More informationSECTION NON-STRUCTURAL METAL FRAMING
SECTION 09 22 16 PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories
More informationSECTION NON-LOAD BEARING WALL FRAMING. B. Section Furring and Lathing: Lath and furring for interior plaster applications.
SECTION 09.22.16 NON-LOAD BEARING WALL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Non-load bearing metal studs for wall assemblies. B. Area Separation and shaft wall framing products. 1.2 RELATED SECTIONS
More informationSECTION / STC 52 METAL SOUND CONTROL DOORS
SECTION 08 34 73 / 08 34 73.13 STC 52 METAL SOUND CONTROL DOORS PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including general and Supplementary Conditions
More informationN-SERIES: NTH3500 SPECIFICATIONS Hollow Metal Sliding Door System
Version 5.22.13 N-SERIES: NTH3500 SPECIFICATIONS Hollow Metal Sliding Door System OPTIONS ARE LISTED IN BOLD, PLEASE MODIFY THESE AREAS AS NEEDED BASED ON YOUR PROJECT CONSULT MANUFACTURER FOR ADDITONAL
More informationSECTION EZ-SLIDE 80 AND 180 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS
Page 1 of 6 SECTION 08 32 20 EZ-SLIDE 80 AND 180 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,
More informationN-SERIES: NTH2700 SPECIFICATIONS Tubular Composite Top Hung Sliding Door System
Version 5.22.13 N-SERIES: NTH2700 SPECIFICATIONS Tubular Composite Top Hung Sliding Door System OPTIONS ARE LISTED IN BOLD, PLEASE MODIFY THESE AREAS AS NEEDED BASED ON YOUR PROJECT CONSULT MANUFACTURER
More informationSECTION STRUCTURAL METAL FRAMING
SECTION 05100 STRUCTURAL METAL FRAMING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Structural steel framing including lintels, shelf angles, bearing plates, anchor bolts and other items as shown on
More informationSECTION CRL70 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS
Page 1 of 6 SECTION 08 32 20 CRL70 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS [OR WOOD] PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,
More informationSECTION FABRICATED ENGINEERED STRUCTURES. A. Pre-engineered, shop-fabricated structural steel building with formed purlin framing.
PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 13 34 00 FABRICATED ENGINEERED STRUCTURES A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
More informationAMBICO Limited Section and ACOUSTIC STEEL DOOR AND FRAME ASSEMBLIES Page 1
Page 1 This section includes AMBICO Acoustic Steel Doors and Frames as well as perimeter and bottom acoustic seals, and glazing if required all of which can be fire rated or non-rated. The aforementioned
More informationArchitectural Roof Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification
More information1. Seismic Loads: Reference structural drawings.
SECTION 102213 ~WIRE MESH PARTITIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general prov1s1ons of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES
SECTION 07 4243 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Composite wall panel system consisting of aluminum-faced composite panels in a rainscreen application as part of the assembly described below.
More informationSECTION MISCELLANEOUS METALS THIS SECTION TO BE INCLUDED IN SUB BID FOR SECTION MISCELLANEOUS AND ORNAMENTAL IRON
SECTION 055000 THIS SECTION TO BE INCLUDED IN SUB BID FOR SECTION 050001 MISCELLANEOUS AND ORNAMENTAL IRON PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a
More information1. Include plans, elevations, sections, details, and attachments to other work.
SECTION 102213- PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationSECTION DETENTION WINDOW SCREENS. 1. Detention screens for interior and exterior installations at exterior windows in existing buildings.
SECTION 08 56 66 DETENTION WINDOW SCREENS SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: SPEC
More informationArchitectural Roof Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification
More informationSECTION NON-STRUCTURAL METAL FRAMING
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 09 22 16 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable
More informationLTH3700, HOLLOW METAL SLIDING FIRE DOOR
LTH3700, HOLLOW METAL SLIDING FIRE DOOR Consult Manufacturer for additional options or modifications PART 1-GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General
More informationSECTION / / BULLET RESISTANT SOUND CONTROL WINDOWS
SECTION 08381 / 088856 / 085673 BULLET RESISTANT SOUND CONTROL WINDOWS 1.0 GENERAL 1.1 DESCRIPTION OF WORK A. Furnish and install FACTORY PREGLAZED Bullet Resistant Sound Control Windows specified herein
More information1. Standard two tier metal lockers and metal base.
SECTION 105113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSECTION CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS
SECTION 08 32 20 CRL50 AND CRL51 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,
More informationStudent Services & Classroom Addition
SECTION 055113 - METAL PAN STAIRS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationGUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM
1 GUIDE SPECIFICATION EXETER SECURITY SHIELD SECURITY WINDOW BARRIER SYSTEM 1.01 WORK INCLUDED PART 1: GENERAL A. Provide for all labor, equipment, materials and services to furnish and install SECURITY
More informationGUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM
1 GUIDE SPECIFICATION EXETER VERSA SHIELD SECURITY SCREEN SYSTEM 1.01 WORK INCLUDED PART 1: GENERAL A. Provide for all labor, equipment, materials, and services to furnish and install VERSA SHIELD Window
More informationSECTION RADIO FREQUENCY SHIELDING ENCLOSURE Magnetic Shielding
SECTION 13096 RADIO FREQUENCY SHIELDING ENCLOSURE Magnetic Shielding Prepared by: 90 Dayton Avenue, Unit 4B, Suite 13 Passaic, NJ 07055 (973) 574-9077 13096-1 MAGNETIC SHIELDING PART 1 GENERAL 1.1 GENERAL
More informationSECTION FOLDING DOORS AMSTEL AS900CC DIVIDER SOUND
SECTION 08352 FOLDING DOORS AMSTEL AS900CC DIVIDER SOUND THREE PART SHORT FORM SPECIFICATIONS (CSI) PART 1 GENERAL 1.1 SUMMARY A. Section Includes: manually operated, side folding accordion- type products
More informationHOTEL SPECIFICATION SECTION 08100
Part 1 General HOTEL SPECIFICATION SECTION 08100 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified including, but not limited
More informationProduct Guide Specification
February 2015 528 Pioneer Parkway Clare, Michigan 48617 Toll Free 800-631-0212 Website www.tranquilsystems.com E-mail sales@tranquilsystems.com Product Guide Specification Tranquil Acoustic Walls with
More informationProduct Guide Specification
February 2015 528 Pioneer Parkway Clare, Michigan 48617 Toll Free 800-631-0212 Website www.tranquilsystems.com E-mail sales@tranquilsystems.com Product Guide Specification Tranquil Acoustic Walls with
More informationCentral Dartmouth Section Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Dartmouth, NS
Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Part 1 General 1. RELATED SECTIONS 1. Section 07 92 10 Joint Sealing 2. Section 08 71 00 Door Hardware 2. REFERENCES 1. American Society
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 105113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 SUBMITTALS A. Product Data: For each type of
More information1. Base plates, setting plates and anchor rods for columns. 8. Lintels if connected to structural steel columns.
PAGE 051200-1 SECTION 051200 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification sections,
More informationInsulating Cellular Concrete Steel Joists Painting. A. America Society for Testing and Materials (ASTM):
SECTION 05120 STRUCTURAL STEEL PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 03342 - Insulating Cellular Concrete. 2. 05210 - Steel Joists. 3. 09900 - Painting. 1.02 REFERENCES A. America Society
More informationBEARING METAL STUD FRAMING
L-1 Section 05410 Long Form Specification LOAD BEARING METAL STUD FRAMING This section includes axially loaded steel studs, with unique slotted top channels, usually of 0.91, 1.2 and 1.5 mm (16, 18, or
More information603 Summit Avenue, Suite 102 Greensboro, N.C Voice/FAX (336)
Ricky L. Loman, AIA Architect 603 Summit Avenue, Suite 102 Greensboro, N.C. 27405-7700 Voice/FAX (336) 273-7999 ADDENDUM: Number 1 ISSUED: March 14, 2017 SUBJECT: New Agriculture & Equipment Storage Barn
More informationA. Submit the following in addition to the standard requirements.
SECTION [13120] OMNIFLEX 300 MODULAR WALL SYSTEM SECTION 1 GENERAL 1.01 SECTION INCLUDES A. This Section specifies all requirements necessary to furnish and install a complete modular wall system including,
More informationSECTION PRE-ENGINEERED MEMBRANE STRUCTURE
SECTION 13125 PART 1 - GENERAL 1.1 SUMMARY A. Section includes the design, engineering, fabrication and erection of a frame-supported, tensilemembrane structure complete with entrance and exit doors and
More information.1 American Institute of Steel Construction (AISC) Specifications for Steel Buildings AISC
05 12 00 STRUCTURAL STEEL FRAMING Page 1 of 3 1 General 1.1 SECTION INCLUDES.1 Structural steel framing and support members 1.2 RELATED SECTIONS.1 Section 05 50 00 Metal Fabrications 1.3 REFERENCES.1 American
More informationGUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION REROOFING ADJUSTABLE FRAMING SYSTEM
- --- -- ----..-------~------------------------------------ GUIDE SPECIFICATIONS CURA ADJUSTABLE REROOF FRAMING SYSTEMS SECTION 07415 REROOFING ADJUSTABLE FRAMING SYSTEM PART 1 - GENERAL 1.01 SCOPE A.
More informationBanyan Air Service November 18, 2011 AVE Aviation and Commerce Center Building 1 Miami, FL
SECTION 09511 - ACOUSTICAL PANEL CEILINGS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION SECURITY PROTECTION PART 1 GENERAL
SECTION 13 1010 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Bullet Resistant Aluminum Windows. B. Bullet Resistant Transaction Equipment. C. Bullet Resistant Speakers. D. Bullet Resistant Glazing. E. Bullet
More informationSECTION (05300) - STEEL DECKING
SECTION 05 31 00 (05300) - STEEL DECKING PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Roof Deck 2. Composite Floor Deck 3. Noncomposite Form Deck B. Related Sections: 1.02 SUBMITTALS 1. Section
More informationK. All mechanical rooms shall be designed with a minimum 3-1/2 dropped floor.
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationSECTION METAL STAIRS
SECTION 05510 METAL STAIRS PART 1 GENERAL 1.01 SECTION INCLUDES A. Stairs with concrete treads. B. Stairs with metal treads. C. Structural steel stair framing and supports. D. Handrails and guards. 1.02
More informationSECTION EXTERIOR GRILLS AND SCREENS
SECTION 10 82 13 PART 1 GENERAL PART 1 1 SUMMARY A. Section Includes: 1. Exterior perforated aluminum screen wall system with Ombrae TM Optical Tile imaging technology. 2. Accessories including attachments,
More informationJAMISON SOUND DOOR SPECIFICATIONS VERTICAL SLIDING SOUND REDUCTION DOOR - STC 53 POWERED OPERATION
JAMISON SOUND DOOR SPECIFICATIONS VERTICAL SLIDING SOUND REDUCTION DOOR - STC 53 POWERED OPERATION PART 1 - GENERAL 1.1 APPLICABLE PUBLICATIONS: The publications listed below form a part of this specification
More informationSECTION METAL ATHLETIC LOCKERS
SECTION 10 51 13 - METAL ATHLETIC LOCKERS PART 1 GENERAL 1.1 SECTION INCLUDES A. DESCRIPTION: Furnish and install factory-assembled Heavy-Duty MIG-Welded Metal Lockers, complete, as shown and specified
More informationCOLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100
COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 Part 1 General 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified,
More informationSECTION C. Water Infiltration: Provide manufactured cupolas and dormers that do not allow water infiltration to cupola and dormer interiors.
PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Manufactured exterior cupolas. 2. Manufactured dormers. 3. Historical locomotive weather Vane. 1.2 PERFORMANCE REQUIREMENTS A. General:
More information1. Temperature Change: 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces.
SECTION 05500- METAL FABRICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationL-SERIES: LTH3900 SPECIFICATIONS Stainless Steel Hollow Metal Sliding Fire Door System
Version 5.22.13 L-SERIES: LTH3900 SPECIFICATIONS Stainless Steel Hollow Metal Sliding Fire Door System OPTIONS ARE LISTED IN BOLD, PLEASE MODIFY THESE AREAS AS NEEDED BASED ON YOUR PROJECT CONSULT MANUFACTURER
More informationSECTION ACCESS DOORS AND FRAMES
11303, 26 th avenue Montreal, Quebec Canada H1E 6N6 Phone: (800) 479-1489 Fax: (800) 297-1489 PRODUCT GUIDE SPECIFICATION SECTION 08 31 00 S PART 1 - GENERAL 1.1 SUMMARY A. Provide access doors, frames
More informationFacility Repairs - MCAS Cherry Point - Tank Farm A SECTION STRUCTURAL STEEL 05/14
SECTION 05 12 00 STRUCTURAL STEEL 05/14 PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the
More informationA. Access doors and frames are part of an access door and frame allowance.
SECTION 08 31 13 ACCESS DOORS AND FRAMES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION DETAILS (MECHANICALLY ASSEMBLY)
COVER SHEET ELEVATION SHEET SECTION DETAILS (MECHANICALLY ASSEMBLY) SECTION DETAILS (MECHANICALLY ASSEMBLY) SECTION DETAILS (WELDED ASSEMBLY) SECTION DETAILS (WELDED ASSEMBLY) SECTION DETAILS (DOOR ASSEMBLY)
More informationPreassembled steel stairs with concrete-filled treads.
SECTION 055113 - PART 1 - GENERAL 1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 102239 - FOLDING PANEL PARTITIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationCOVER SHEET ELEVATION SHEET SECTION DETAILS (MECHANICALLY ASSEMBLY) SECTION DETAILS (WELDED ASSEMBLY)
COVER SHEET ELEVATION SHEET SECTION DETAILS (MECHANICALLY ASSEMBLY) SECTION DETAILS (MECHANICALLY ASSEMBLY) SECTION DETAILS (WELDED ASSEMBLY) SECTION DETAILS (WELDED ASSEMBLY) SECTION DETAILS (DOOR ASSEMBLY)
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 092216 - NON-STRUCTURAL METAL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION COMPOSITE METAL DECKING
PART 1 GENERAL 1.1 DESCRIPTION SECTION 05 36 00 1. Use this section only for NCA projects. 2. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable
More informationDIVISION 10 SPECIALTIES SECTION METAL LOCKERS
DIVISION 10 SPECIALTIES SECTION 10 51 13 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationLouis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1
Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions
More informationSECTION COILING COUNTER DOORS
SECTION 08 33 13 COILING COUNTER DOORS SPEC WRITER NOTES: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. Use overhead coiling counter shutters as closures
More informationAddendum #4 NEW LOW HEAD OXYGEN SYSTEM Contractor EXHIBIT T SPECIAL PROVISIONS SECTION METAL SHADE STRUCTURE
SECTION 13 34 00 METAL SHADE STRUCTURE PART 1 - GENERAL 1.01 STRUCTURE TYPE A. Structure shall be free standing rigid frame and gable roof with slopes as indicated. Structure shall also include foundation,
More informationThe fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general specifications:
Query No.1 ; we need more specs. about fire resistant doors Answer to Query No. 1: The fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general
More informationSTRUCTURAL STEEL FRAMING Section
PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Structural steel. 2. Grout. 1.2 DEFINITIONS A. Structural Steel: Elements of the structural frame indicated on Drawings and as described in AISC 303,
More informationGuide Specifications ADP Series SECTION SHEET METAL ROOFING
PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Sheet metal roofing panels, metal trim, accessories, fasteners, closures, and sealants. [Specifier Note: Edit paragraph below to suit project requirements.]
More informationSECTION SECURITY GRILLES 679 SERIES SUPERGARD SIDE FOLDING GRILLE
SECTION 08 33 00 SECURITY GRILLES 679 SERIES SUPERGARD SIDE FOLDING GRILLE Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on
More informationRAOUL WALLENBERG HIGH SCHOOL SECURITY COILING GRILLE SFUSD PROJECT NO SAN FRANCISCO UNIFIED SCHOOL DISTRICT SECTION 08330
SECTION 08330 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: Provide all labor, materials, necessary equipment, services and included but limited to all related work to complete security coiling grille
More informationAMBICO Limited Section BLAST RESISTANT STEEL OVERHEAD DOOR ASSEMBLIES Page 1
Page 1 This section includes Blast Resistant, Steel, Overhead Door Assemblies, with integral electric operators and accessories. This section includes proprietary, descriptive and performance type specification
More informationAMBICO Limited 7\2018 Section and OVERSIZED METAL DOORS AND FRAMES Page 1
Page 1 This section includes Oversize Steel Doors and Frames and relies on the Canadian Steel Door Manufacturers Association (CSDMA.org) industry standard, as well as on the Hollow Metal Manufacturers
More information