1 Ruling No Application No BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentences (1), (2) and (3) of Regulation 403, as amended by O. Reg. 22/98, 102/98, 122/98, 152/99, 278/99, 593/99, 597/99, 205/00 and 283/01 (the Ontario Building Code ). AND IN THE MATTER OF an application by Matthew Stanton, Project Manager, PCL Constructors Canada Inc., for the resolution of a dispute with Frank Asta, Chief Building Official, Town of Oakville, to determine whether the combustible wood screen cladding proposed on the exterior of the north, east and south faces of a parking structure provides sufficiency of compliance with Sentence (1), (2) and (3) of the Ontario Building Code at the Oakville Trafalgar Memorial Hospital Parking Garage, Oakville, Ontario. APPLICANT RESPONDENT PANEL PLACE Matthew Stanton PCL Constructors Canada Inc. Mississauga, ON Frank Asta Chief Building Official Town of Oakville Len King, Vice-Chair Gary Burtch Tony Chow Toronto, Ontario DATE OF HEARING March 14 th, 2002 DATE OF RULING March 14 th, 2002 APPEARANCES Les Muniak Larden Muniak Consulting Inc., Toronto, ON Agent for the Applicant Frank Asta Chief Building Official Town of Oakville The Respondent
2 -2- RULING 1. The Applicant Matthew Stanton, Project Manager, PCL Constructors Canada Inc., has received a building permit under the Building Code Act, S.O. 1992, c. 23, as amended, and is constructing a parking garage to serve the Oakville Trafalgar Memorial Hospital, Oakville, Ontario. 2. Description of Construction The Applicant is proposing the construction of a parking garage having an F3 occupancy classification and a building area of 4,200 m 2. The structure will be comprised of noncombustible construction and is five storeys in building height. A further two storeys, proposed below grade level, will be equipped with a sprinkler system. The construction in dispute involves the wood screen combustible cladding proposed for use on the north, east and south faces of the parking structure. The proposed cladding would be comprised of western cedar that has a low combustibility level, however, the wall assembly has not been tested in accordance with CAN/ULC-S134 standards. The cladding would be positioned approximately 406 mm (16 in) from the exterior face of the structure and tied off to the parking structure at the top and mid-point. In addition, as compensation for the use of combustible cladding which has not been subjected to Code prescribed testing, a closed-head sprinkler system is proposed around the perimeter of the structure located at the downturn on each level of the parking garage. Sprinkler heads are to be positioned approximately 2.4 m (8 ft) on centres and will be activated in the event of a fire. 3. Dispute The issue at dispute between the Applicant and Respondent is whether the proposal for combustible wood screen cladding on the north, east and west facings of the subject parking garage will provide sufficiency of compliance with Sentences (1), (2) and (3) of the Ontario Building Code (OBC). Article sets out restrictions on the use of combustible components in the construction of exterior walls. Sentence (1) provides that, with exceptions not applicable here, an exterior nonloadbearing wall assembly which includes combustible components may be used in a building requiring noncombustible construction provided that a) the building is not more than three storeys in building height or b) is not more than six storeys if the building is sprinklered. As a further requirement, this sentence stipulates that the interior surfaces of the wall assembly must be protected with a thermal barrier and that the wall assembly must satisfy the criteria set out in Sentences (2) and (3) when subjected to testing in conforming with CAN/ULC-S134 standards. In this regard, Sentences (2) and (3) prescribe that flaming on or in the wall shall not spread more than 5 m above the opening during the test procedure and that the heat flux during flame exposure on the wall assembly shall not be more than 35 kw/m 2 when measured at 3.5 m above the opening during the same procedure. As noted above, the proposed combustible exterior cladding has not been tested in conformance with CAN/ULC-S134 Standard Method of Fire Test of Exterior Wall Assemblies, however, testing has been conducted in accordance with CAN/ULC-S102 Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies. The Applicant argues that there is a good
3 -3- correlation between these two tests when materials such as the proposed combustible cladding are being analysed. Results from the S102 test would appear to meet the parameters outlined in Sentences (2) and (3). Further, as an additional measure of fire protection for the wood cladding, a closed-head sprinkler system, which would be activated in the event of a fire, is also being offered as compensation. 4. Provisions of the Ontario Building Code Combustible Components for Exterior Walls (1) Except for an exposing building face required to conform to Sentence (1) or Sentence (4), an exterior non-loadbearing wall assembly that includes combustible components is permitted to be used in a building required to be of noncombustible construction provided (a) the building is (i) not more than 3 storeys in building height, or (ii) not more than 6 storeys in building height if sprinklered, (b) the interior surfaces of the wall assembly are protected by a thermal barrier conforming to Sentence (3), and (c) the wall assembly satisfies the criteria of Sentences (2) and (3) when subjected to testing in conformance with CAN/ULC-S134, Standard Method of Fire Test of Exterior Wall Assemblies. (See Appendix A.) (2) Flaming on or in the wall assembly shall not spread more than 5 m (16 ft 5 in) above the opening during the test procedure referenced in Sentence (1). (See Appendix A.) (3) The heat flux during the flame exposure on a wall assembly shall be not more than 35 kw/m 2 (11,100 Btu/ft 2 h) measured 3.5 m (11 ft 6 in) above the opening during the test procedure referenced in Sentence (1). (See Appendix A.) 5. Applicant s Position The Agent for the Applicant advised that the proposed parking garage was a part of the current redevelopment project for the hospital. The aim of providing the wood cladding was to make the design of the parking garage blend into the residential streetscape and to avoid creating what might appear to be a concrete bunker. The Agent described the cladding as a series of interwoven telephone poles with lattice in between. This wall assembly, he submitted, would be applied to three sides of the 5 storey parking structure. The Agent acknowledged the OBC requirement for testing in accordance with the CAN/ULC-S134 standards. He advised that this test has not been conducted because the Applicant had been unable to find a testing facility that was equipped to test a 5 storey high structure. Furthermore, he suggested that this test would be cost and time prohibitive. In support of this application, however, the Agent advised that a test had been conducted in accordance with CAN/ULC-S102 standards. He suggested that a (c)correlation has previously been demonstrated between the CAN/ULC-S134 test on a 3-storey high wall assembly and the extended CAN/ULC-S102 test in the Steiner Tunnel Furnace. In support of this argument, testimony from a former ULC employee revealed that the two flame spread tests being considered operate on the same principal. The witness submitted that, if S134 is designed to test flame spread, then all the data needed to analyse the result of flame spread for the subject assembly could be gathered in the smaller, simpler, S102 tunnel test. The Agent submitted that the correlation developed previously between CAN/ULC-S102 and the
4 -4- Standard CAN/ULC-S134 demonstrates that exterior claddings having 1.8 m of flame propagation in the extended Steiner Tunnel Furnace test perform favourably when tested on a 3-storey high wall assembly. Further, the Agent advised that (t)he limited distance of flame propagation in the tunnel furnace over a prolonged period indicates that the wood screen will not propagate flame more than 5 m above the opening nor develop a heat flux exceeding 35 kw/m 2 above the opening during a 3-storey high wall test. As such, the wood screen will not contribute to fire growth on the exterior face of the parking structure beyond that permitted for exterior claddings that have demonstrated favourable performance when tested in accordance with the Standard CAN/ULC-S134. The Agent advised that a sample of the lattice had been subjected to a tunnel test and was examined for a period longer than the standard test would require. In the Agent s view, he was satisfied that the results achieved in this test indicate that the wall assembly would perform well and would meet the requirements of CAN/ULC-S134. Moreover, despite the successful testing of the product, the Applicant is offering an additional measure of compensation for the use of combustible exterior wall components. To protect the wood screen, a closed-head sprinkler system will be provided at the downturn on each level of the parking garage. The sprinkler heads will be spaced at approximately 8- foot OC and will activate in the event fire occurs within the parking structure. The Agent argued that, because the OBC does not require the provision of a fire suppression system for combustible exterior cladding, this sprinkler system around the perimeter will contribute to the provision of an equivalent level of life safety to that of noncombustible exterior construction. In summation, the Agent submitted that, in his opinion, the proposal meets the intent of the requirements of Sentence (1) of the Code. The provision of the sprinkler system around the perimeter will provide protection to the combustible elements of the proposal. A thermal barrier is, in his opinion, being provided through the use of 1,117.6 mm (44 in) of concrete upstand at the exterior walls and the mm (16 in) separation between the wood lattice and the main structure. Further, the comparable test that has been conducted illustrates that the cladding will perform to an acceptable degree during a fire. 6. Respondent s Position The Respondent submitted that the proposed combustible wall assembly did not meet the requirements set out in Article In his opinion, he could see no correlation between the required testing method of CAN/ULC-S134 and that of the much smaller test conducted using the CAN/ULC-S102 standard. Further, he advised that he could see no similarity of comparison in the results obtained from a closed horizontal test (S102) and the open vertical test anticipated by S134. In summation, the Respondent argued that the proposed wood screening represented a substantial amount of highly combustible material which would contribute to the overall fire load of the building. He emphasized that the building was not fully sprinklered and questioned the benefit of sprinkler heads around the perimeter as proposed by the Applicant. In his opinion, sufficiency of compliance with the prescriptive requirements of Article was not being provided. 7. Commission Ruling It is the decision of the Building Code Commission that the combustible wood screen cladding proposed on the exterior of the north, east and south faces of the parking structure does not provide sufficiency of compliance with Sentences (1), (2) and (3) of the Ontario Building Code at the Oakville Trafalgar Memorial Hospital Parking Garage, Oakville, Ontario.
5 -5-8. Reasons i) The entire building is not sprinklered as would be required by Clause (1)(a). ii) iii) The interior surfaces of the wall are not protected in their entirety by a thermal barrier conforming to (3). There are concerns with the sprinkler heads located along the perimeter of the building in regard to whether there would be a sufficient rise in temperature to activate the system.
6 Dated at Toronto this 14th day in the month of March in the year 2002 for application number Len King, Vice-Chair Gary Burtch Tony Chow
BUILDING CODE COMMISSION
Ruling No. 02-21-876 Application No. 2002-17 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 3.2.2.24. and
More informationBUILDING CODE COMMISSION
Ruling No. 05-18-1032 Application No. 2005-11 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF in Article 9.10.14.11.
More informationBUILDING CODE COMMISSION
Ruling No. 03-54-952 Application No. 2003-64 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 6.2.3.2. of
More informationBUILDING CODE COMMISSION
Ruling No. 02-22-877 Application No. 2002-19 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentences 3.3.1.2.(3),
More informationBUILDING CODE COMMISSION
Ruling No. 02-28-883 Application No. 2002-25 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Clauses 3.2.2.67.(2)(c)
More informationBUILDING CODE COMMISSION
Ruling No. 02-05-860 Application No. 2001-82 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 4.1.10.8. of
More informationBUILDING CODE COMMISSION
Ruling No. 02-04-859 Application No. 2001-81 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentences 3.2.3.7.(7)
More informationBUILDING CODE COMMISSION
Ruling No. 03-32-930 Application No. 2003-31 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 5.1.4.2. and
More informationBUILDING CODE COMMISSION
Ruling No. 05-08-1022 Application No. 2005-03 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF in Articles 9.10.14.1.
More informationBUILDING CODE COMMISSION
Ruling No. 02-13-868 Application No. 2002-11 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 3.2.2.9. and
More informationBUILDING CODE COMMISSION
Ruling No. 05-07-1021 Application No. 2005-02 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 3.2.2.67.,
More informationBUILDING CODE COMMISSION
Ruling No. 08-12-1186 Application No. 2008-03 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.6.3.1.(2)
More informationBUILDING CODE COMMISSION
Ruling No. 04-32-987 Application No. 2004-24 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Clause 3.3.2.1.(1)(c)
More informationBUILDING CODE COMMISSION
Ruling No. 02-35-890 Application No. 2002-22 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 3.4.3.6. and
More informationBUILDING CODE COMMISSION
Ruling No. 03-07-905 Application No. 2002-51 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.2.2.35.(4)
More informationBUILDING CODE COMMISSION
Ruling No. 10-21-1257 Application No. B-2010-13 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Articles 9.8.8.3.
More informationBUILDING CODE COMMISSION
Ruling No. 04-27-982 Application No. 2004-19 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 9.8.8.8.(2)
More informationBUILDING CODE COMMISSION
Ruling No. 08-24-1198 Application No. 2008-21 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Sentence 9.19.1.1.(1)
More informationBUILDING CODE COMMISSION
Ruling No. 05-26-1040 Application No. 2005-17 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 4.1.1.3.(1)
More informationBUILDING CODE COMMISSION
Ruling No. 07-42-1171 Application No. B-2007-37 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.4.6.5.(8)
More informationBUILDING CODE COMMISSION
Ruling No. 07-39-1168 Application No. 2007-35 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 9.10.12.3.
More informationBUILDING CODE COMMISSION
Ruling No. 01-22-815 Application # 2001-14 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, 1992. AND IN THE MATTER OF Articles 3.3.1.8. and 3.4.3.6. of Regulation
More informationBUILDING CODE COMMISSION
Ruling No. 02-38-893 Application No. 2002-33 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Clause 3.3.4.4.(1)(a)
More informationBUILDING CODE COMMISSION
Ruling No. 03-40-938 Application No. 2003-40 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 3.1.5.1. of
More informationBUILDING CODE COMMISSION
Ruling No. 09-06-1218 Application No. B-2009-04 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Article 3.1.9.1.
More informationBUILDING CODE COMMISSION
Ruling No. 03-34-932 Application No. 2003-41 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.7.4.1.(3)
More informationBUILDING CODE COMMISSION
Ruling No. 09-14-1226 Application No. B-2009-15 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Clause 9.25.2.2.(1)(g)
More informationBUILDING CODE COMMISSION
Ruling No. 09-17-1229 Application No. 2009-10 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Article 9.19.1.1.
More informationBUILDING CODE COMMISSION
Ruling No. 01-38-831 Application # 2001-47 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, 1992. AND IN THE MATTER OF Sentence 3.3.1.17.(1) of Regulation 403, as amended
More informationWOOD USE IN NONCOMBUSTIBLE BUILDINGS
INTRODUCTION The National Building Code of Canada (NBCC) 1 requires that some buildings be of noncombustible construction under its prescriptive requirements. Its use in certain types of buildings such
More informationBUILDING CODE COMMISSION
Ruling No. 10-37-1273 Application No. B-2010-33 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Clauses 9.7.2.1.(1)(a)
More informationBUILDING CODE COMMISSION
Ruling No. 03-16-914 Application No. 2003-08 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 9.8.8.2.(4)
More informationNEWS LETTER MARCH 27, 2009
PLANNING, BUILDING & DEVELOPMENT SERVICES DEPARTMENT 580-1 Street S.E. Medicine Hat, Alberta T1A 8E6 Telephone: 529-8374 FAX 502-8038 1 NEWS LETTER MARCH 27, 2009 GENERAL As you are probably aware there
More informationBUILDING CODE COMMISSION
Ruling No. 10-35-1271 Application No. B-2010-26 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 4.3.4.3.
More informationBUILDING CODE COMMISSION
Ruling # 01-12-805 Application # 2000-83 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, 1992. AND IN THE MATTER OF Articles 9.26.5.1. and 9.26.5.2. of Regulation
More informationNRC Research Update on Mid-Rise Wood Construction. Joseph Su Principal Research Officer, Fire Safety
NRC Research Update on Mid-Rise Wood Construction Joseph Su Principal Research Officer, Fire Safety Outline Benefits and uses of wood structures Code developments to permit midrise R&D for solutions and
More informationBUILDING CODE COMMISSION
Ruling No. 05-22-1036 Application No. 2005-18 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 9.8.8.5.(1)
More informationBUILDING CODE COMMISSION
Ruling No. 08-06-1180 Application No. B- 2007-49 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 7.4.8.2.,
More informationBUILDING CODE COMMISSION
- 1 - Ruling No. 07-31-1160 Application No. 2007-15 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 8.7.3.2.
More informationNATIONAL BUILDING CODE OF CANADA 1985
NATIONAL BUILDING CODE OF CANADA 1985 FIRST REVISIONS Issued by the Associate Committee on the National Building Code National Research Council of Canada Ottawa January 1986 Revisions to the National Building
More informationFire Considerations. Combustible Cladding and Components Of Exterior Walls and Curtain Walls. APEGBC/BCBEC Seminar, April
Fire Considerations Combustible Cladding and Components Of Exterior Walls and Curtain Walls APEGBC/BCBEC Seminar, April 21 2016 Andrew Harmsworth M Eng, P Eng, PE, CP Jun H. Kim, BASc, EIT Email: ah@ghl.ca/
More informationBUILDING CODE COMMISSION
Ruling No. 00-54-786 Application No. 2000-66 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, 1992. AND IN THE MATTER OF Articles 9.8.8.8., 4.1.10.1. and Sentence 9.8.2.1.(1)
More informationDate of Authorization APRIL 29, 2004 BMEC Authorization BMEC # BMEC Application #A
Building Materials Evaluation Commission 777 Bay Street, 2 nd Floor Toronto, Ontario, M5G 2E5 Tel: 416: 585. 4234 / Fax: 416. 585. 7531 www.obc.mah.gov.on.ca Date of Authorization APRIL 29, 2004 BMEC Authorization
More informationChoosing Between Fire Retardant and Standard Core Metal Composite Material (MCM)
WHITE PAPER Choosing Between Fire Retardant and Standard Core Metal Composite Material (MCM) WHITE PAPER UPDATE 7/18 As a proactive response to the events involving MCM assemblies around the world, the
More informationModule 8: Ontario Building Code Fire and Spatial Separations
Ontario Building Code (OBC) 1. Fire Separations 2. Fire Resistance Ratings By Classification 3. Fire Resistance Ratings By Adjacent Use 4. Fire Resistance Ratings By Specific Space 5. Fire Resistance Ratings
More informationBUILDING CODE COMMISSION
Ruling No. 03-27-925 Application No. 2003-14 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 9.14.2.1.,
More information6-Storey Residential Buildings Combustible Construction. A Regulator s Perspective City of Richmond, BC Canada
6-Storey Residential Buildings Combustible Construction A Regulator s Perspective City of Richmond, BC Canada Our first...learning curve Remy mid-rise Project 5388 Cambie Street, Richmond BC It s Allowed
More informationDECKS INCLUDED: LIST OF REQUIREMENTS DECK DESIGN MATRIX APPLICATION FORM SAMPLE DRAWINGS
DECKS INCLUDED: LIST OF REQUIREMENTS DECK DESIGN MATRIX APPLICATION FORM SAMPLE DRAWINGS This content is available in alternative formats upon request by contacting 905-683-4550 or emailing contactus@ajax.ca.
More informationBUILDING CODE COMMISSION
Ruling No. 08-05-1179 Application No. B-2007-48 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 6.2.1.4.
More informationCOUNCIL ORDER No
SAFETY CODES COUNCIL #1000, 10665 Jasper Avenue N.W., Edmonton, Alberta, Canada, T5J 389 Tel: 780-413-0099 I 1-888-413-0099 Fax: 780-424-5134 I 1-888-424-5134 www.safetycodes.ab.ca COUNCIL ORDER No. 0015437
More informationAlternative Solution Approach to Fire Design
Alternative Solution Approach to Fire Design A Presentation for Cross-Laminated Timber Symposium and Workshop New Brunswick October, 2011 Presented by Andrew Harmsworth, M Eng, P Eng, CP Who Am I? Andrew
More informationBUILDING CODE COMMISSION
Ruling No. 02-19-874 Application No. 2002-16 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 11.3.1.1. of
More informationROXUL SAFE Applications Guide
FIRE-FIRST APPLICATIONS ROXUL SAFE Applications Guide TM Fire blocks, firestops, and rated assemblies 3 Introduction 4 ROCKWOOL Solutions for Fire Separation and Firestopping 6 Project The Ritz-Carlton
More informationReference Guide: Mid-Rise Wood Construction in the Ontario Building Code Report by Morrison Hershfield (January 2015)
2015 Reference Guide: Mid-Rise Wood Construction in the Ontario Building Code Report by Morrison Hershfield (January 2015) Ontario Wood WORKS! 60 Commerce Court P.O. Box 5001 Office W113 North Bay, ON
More information1.2 EXAMINATION SYLLABUS AND EXAMINATION FORMAT
MODULE 1 INTRODUCTION AND INSTRUCTIONS structural provisions of the Building Code. These skills are necessary to be successful in passing the qualification examination. Recognizing that some readers will
More informationDate of Authorization September 27, 2007 BMEC Authorization Number BMEC Application A
777 Bay Street, 2 nd Floor Toronto, Ontario, M5G 2E5 Tel: 416 585 4234 Fax: 416 585 7531 Web: www.ontario.ca/buildingcode/ Date of Authorization September 27, 2007 BMEC Authorization Number 07-04-334 BMEC
More informationSupplementary Standard SB-12. Energy Efficiency For Housing
Ministry of Municipal Affairs and Housing Building and Development Branch 2006 Building Code - Supplementary Standards Supplementary Standard SB-12 Energy Efficiency For Housing January 1, 2012 update
More informationProduct Information Bulletin
Product Information Bulletin CCMC Evaluation Report 13101-R Advantage Insulating Concrete Forming (ICF) System BULLETIN NO. ISSUED: REPLACES: 201 November 25, 2010 January 2, 2009 Canadian Construction
More informationSupplementary Standard SB-12. Energy Efficiency For Housing
OBC Excerpt: SB 12 Ministry of Municipal Affairs and Housing Building and Development Branch 2006 Building Code - Supplementary Standards Supplementary Standard SB-12 Energy Efficiency For Housing November
More informationMass Timber in the Code and Alternative Solutions
1 Mass Timber in the Code and Alternative Solutions ELEVATE: MASS TIMBER DESIGN SOLUTIONS June 5, 2018 Edmonton June 6, 2018 Calgary Ineke Van Zeeland, M.Eng., MSFPE Senior Manager, Codes and Standards
More informationEngineering Analysis of NFPA 285 Tested Assemblies
Engineering Analysis of NFPA 285 Tested Assemblies Introduction Foam plastics used in buildings of Types I-IV construction require an assessment of their ability to resist vertical and lateral flame spread
More information2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012
2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,
More informationDeer Ridge Consulting, Inc.
Deer Ridge Consulting, Inc. Code Compliance Research Report 505 Deer Ridge Lane Ararat, VA 24053 Office: 276-755-9162 Fax: 866-441-1054 www.deer-ridge-consulting.com Subject: NCFI 12-008 Spray Polyurethane
More informationFIRE RATING AND FIRE PERFORMANCE
FIRE RATING AND FIRE PERFORMANCE FOR WOOD BUILDINGS St. John s, NL February 3, 2015 Introductions Fire Ratings Background Where are They Needed How are they Achieved Fire Performance AGENDA Historical
More informationPROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED
Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-03-04-10 Ontario-NBC CODE REFERENCE: Division B / 3.4.6.8. Division B / 3.3.1.13.
More informationOriginally Issued: 11/06/2017 Valid Through: 11/30/2018
ACCELLA POLYURETHANE SYSTEMS, LLC. SEALTITE CC+ SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION CSI Section: 07 21 00 Thermal Insulation 1.0 RECOGNITION insulations described in this report have been
More informationCode Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings
Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council Copyright This presentation is protected
More informationEvaluation Report CCMC R Superior Walls Xi Precast Concrete Insulated Wall Panels
CONSTRUCTION Evaluation Report CCMC 13628-R Superior Walls Xi Precast Concrete Insulated Wall Panels MASTERFORMAT: 03 41 10.03 Evaluation issued: 2012-11-08 Revised: 2014-06-05 Re-evaluation due: 2015-11-08
More informationCode Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings. John Buddy Showalter, PE VP, Technology Transfer American Wood Council
Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings John Buddy Showalter, PE VP, Technology Transfer American Wood Council Copyright This presentation is protected by US and International
More informationArxx High Performance Wallsystems
National Research Council Canada Institute for Research in Construction Conseil national de recherches Canada Institut de recherche en construction CCMC 12641-R &&0& EVALUATION DIVISION 03131 REPORT Issued
More informationDate of Authorization February 23, 2012 BMEC Authorization Number BMEC Application A BMEC Expiration Date February 23, 2017
777 Bay Street, 2 nd Floor 777, rue Bay, 2 e etage Toronto, Ontario, M5G 2E5 Toronto, Ontario, M5G 2E5 T: 416 585 4234 T: 416 585 4234 F: 416 585 7531 TC: 416 585 7531 W: www.ontario.ca/buildingcode/ W:
More informationA guide to: ACCESSORY BUILDINGS. Brought to you by: City of Port Colborne - Building Division
A guide to: ACCESSORY BUILDINGS Brought to you by: City of Port Colborne - Building Division -----------------------------------------Disclaimer---------------------------------------- This information
More informationCANADA SPECIFIC FIRESTOPPING REQUIREMENTS
APPENDIX I FCIA MOP CANADA AMENDMENT CANADA SPECIFIC FIRESTOPPING REQUIREMENTS FCIA s Manual of Practice is written to reflect worldwide practices of firestopping and compartmentation Each country will
More informationCode Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings
Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council Copyright This presentation is protected
More informationBMEC AUTHORIZATION: Camino Modular Floor System: SC Series
777 Bay Street, 16 th Floor Toronto, Ontario, M5G 2E5 777, rue Bay, 16 e etage Toronto, Ontario, M5G 2E5 T: F: W: 416 585 4234 416 585 7455 www.ontario.ca/buildingcode/ T: TC: W: 416 585 4234 416 585 7455
More informationTownship Of Blandford-Blenheim Permit Guide
Township Of Blandford-Blenheim Permit Guide When do I require a building permit? Building Permits are required before any construction can begin. The following is a typical list of project that DO REQUIRE
More informationResidential Fire Sprinklers & On-site Sewage Systems: A Consultation on Proposed Changes to Ontario s Building Code. February 15 to May 1, 2008
Ministry of Municipal Affairs and Housing Residential Fire Sprinklers & On-site Sewage Systems: A Consultation on Proposed Changes to Ontario s Building Code February 15 to May 1, 2008 An electronic copy
More informationDate of Authorization June 29, 2006 BMEC Authorization Authorization Report - Camino Modular Floor System: SC Series
Building Materials Evaluation Commission 777 Bay Street, 2 nd Floor Toronto, Ontario, M5G 2E5 Tel: 416 585-4234 / Fax: 416 585-7531 www.obc.mah.gov.on.ca Date of Authorization June 29, 2006 BMEC Authorization
More informationNational Building Code Part 9 Energy Efficiency: Focus Paper to Assist in the Review of Proposed Changes
National Building Code Part 9 Energy Efficiency: Focus Paper to Assist in the Review of Proposed Changes February 2012 Contents 0. Background and Purpose of the Paper 1. Development of NBC Part 9 Energy
More informationProduct Information Bulletin
Product Information Bulletin BULLETIN NO. ISSUED: REPLACES: 258 September 12, 2014 April 16, 2007 National Building Code 2010 Prescriptive Requirements for ICF Construction (see also attached Detail Dwgs.
More informationDate of Authorization June 29, 2006 BMEC Authorization Authorization Report - Camino Modular Floor System: WC Series
Building Materials Evaluation Commission 777 Bay Street, 2 nd Floor Toronto, Ontario, M5G 2E5 Tel: 416 585-4234 / Fax: 416 585-7531 www.obc.mah.gov.on.ca Date of Authorization June 29, 2006 BMEC Authorization
More informationCombustible Exterior Wall Cladding Systems: An ICC Perspective
Combustible Exterior Wall Cladding Systems: An ICC Perspective The tragic Grenfell Tower fire in London brought extensive public focus on combustible exterior wall systems, often called cladding, prompting
More informationIn the matter of Section 4 of Chapter 46 of the Revised Statutes of Nova Scotia, 1989, the Building Code Act. - and
N.S. Reg. 26/2017 Made: February 28, 2017 Filed: March 1, 2017 Nova Scotia Building Code Regulations Order dated February 28, 2017 Repeal of regulations and regulations made by the Minister of Municipal
More informationBUILDING CODE COMMISSION
Ruling No. 05-15-1029 Application No. 2005-07 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 1.1.3.2. of
More informationTOWNSHIP OF DRUMMOND/NORTH ELMSLEY. Deck/Porch Guide & Permit
TOWNSHIP OF DRUMMOND/NORTH ELMSLEY Deck/Porch Guide & Permit New Dwelling Living Space Additions to Dwelling Living Space Summary of Building Permit Rates (calculations are based on outside dimensions)
More informationOriginally Issued: 08/03/2017 Revised: 02/01/2019 Valid Through: 08/31/2019
ACCELLA POLYURETHANE SYSTEMS, LLC. 100 Enterprise Drive Cartersville, GA 30120 Phone: (770) 607-0755 www.accellapolyurethane.com BAYSEAL CC X AND BAYSEAL CC XP SPRAY-APPLIED POLYURETHANE FOAM PLASTIC INSULATION
More informationDate of Authorization November 25, 2004 BMEC Authorization # BMEC Application # A AUTHORIZATION REPORT- Pavilion Membranes
Building Materials Evaluation Commission 777 Bay Street, 2 nd Floor Toronto, Ontario, M5G2E5 Tel: 416: 585. 4234 / Fax: 416. 585. 7531 www.obc.mah.gov.on.ca Date of Authorization November 25, 2004 BMEC
More informationSTATEMENT OF DESIGN (for Part 3 Buildings) Ont. Reg. 332/12
Building Standards STATEMENT OF DESIGN (for Part 3 Buildings) Ont. Reg. 332/12 Building Standards Department 2141 Major Mackenzie Drive Vaughan, Ontario L6A 1T1 Permit Application No.: Property Address
More informationWood-Framed, Exterior Walls in Type III Construction
Wood-Framed, Exterior Walls in Type III Construction with Engineered Wood Product Floor Framing Disclaimer: This presentation was developed by a third party and is not funded by WoodWorks or the Softwood
More informationNATIONAL BUILDING CODE OF CANADA 1985
NATIONAL BUILDING CODE OF CANADA 1985 FIFTH REVISIONS Issued by the Associate Committee on the National Building Code National Research Council of Canada Ottawa January 1988 Revisions to the National Building
More informationTHE STEELFORM GOLD STANDARD. Product Data Sheet. Non-loadbearing Steel Studs (NLB)
THE STEELFORM GOLD STANDARD Product Data Sheet Non-loadbearing Steel Studs (NLB) SPECIFICATION OF NON-LOADBEARING STEEL STUDS (NLB) Steelform provides Prime Materials that are listed below and the profiles
More informationPERMIT APPLICATION CHECKLIST Municipal Address, Phone & Fax NONRESIDENTIAL
PERMIT APPLICATION CHECKLIST Municipal Address, Phone & Fax NONRESIDENTIAL Permit Application #: Date: mm/dd/yy Project Address Applicant s Name NOTE TO PERMIT APPLICANTS: All permit applications must
More informationLISTING INFORMATION OF Dryvit - Category 1 OUTSULATION EIFS Wall Systems SPEC ID: 29311
LISTING INFORMATION OF Dryvit - Category 1 OUTSULATION EIFS Wall Systems SPEC ID: 29311 Dryvit Systems Canada 129 Ringwood Drive Stouffville, ON, L4A 8A2 Canada This report is for the exclusive use of
More informationFire Retardants and Truss Design. Overview
Fire Retardants and Truss Design Overview Introduction Fire retardant treatments (FRT) were developed to be applied to building materials, such as dimension lumber (FRTW) and plywood, to reduce the ability
More informationOctober 31, Attn: Architects, professional engineers. Design of hazardous areas
B u i l d i n g S e r v i c e s N O T I C E October 31, 2016 Attn: Architects, professional engineers Re: Design of hazardous areas The design of hazardous areas requirements in the Building Code apply
More informationKnowledge Objectives (3 of 3)
Building Systems Knowledge Objectives (1 of 3) Identify construction types in commercial and residential structures. Explain fire behavior as it relates to the method of construction. Discuss the structural
More informationHOUSING CONVERSION Guidelines for the conversion of a house to commercial use.
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT HOUSING CONVERSION Guidelines for the conversion of a house to commercial use. HAIR 105 January 2017 contents General Information 3 Zoning Information 4 Building
More informationBC BUILDING CODE ERRATA
BC BUILDING CODE ERRATA The following changes should be made to print and offline copies of the 2012 BC Codes. The 2012 BC Codes subscription products include these changes. Highlighted text is used in
More informationFire Performance. By Gary Sturgeon, B.Eng., MSc., P.Eng. Technical Services Engineer, CCMPA. w w w. c c m p a. c a 5-0
By Gary Sturgeon, B.Eng., MSc., P.Eng. Technical Services Engineer, CCMPA 5-0 5.1 Codes and Standards Requirements for fire safety and fire protection are provided in Provincial Building Codes and in
More information