1 WAFFLE-CRETE DESIGN INFORMATION STRUCTURAL PRECAST PRECAST CONCRETE CONCRETE BUILDING BUILDING SYSTEMS SYSTEMS FOR MORE INFORMATION, WRITE OR CALL WAFFLE-CRETE International, Inc. P.O. BOX 1008 Hays, Kansas USA Ph: Fx: Web: waffle-crete.com & picturetrail.com/wafflecrete1

2 WAFFLE-CRETE STRUCTURAL PRECAST CONCRETE BUILDING SYSTEMS NOTICE Design Information for WAFFLE-CRETE panels has been prepared by WAFFLE-CRETE International, Inc. to provide fabricators, designers, and contractors with suggested uses and practical applications of the WAFFLE-CRETE panels in building construction. The structural capacities and characteristics described herein are to be used as guidelines only. The included information is not to be considered as a final structural design. WAFFLE-CRETE International, Inc. recommends that a qualified structural engineer evaluate each application of WAFFLE-CRETE panels. The engineer shall be directed to determine the actual loads and limitations of the panels under each specific application. Materials, codes and manufacturing methods peculiar to the particular operation and market area shall be considered. WAFFLE-CRETE molds are covered by: U.S. PATENT NO. 5,667,192; CANADA PATENT NO. 1,109,653; JAPAN PATENT NO. 1,364,341. WAFFLE-CRETE is a registered trademark of WAFFLE-CRETE International, Inc. of Hays, Kansas. Reg. U.S. Pat. Off., Reg. No. 1,116,050. Canadian Trade Mark Office Registration No. 241,383. Other foreign patents pending. WAFFLE-CRETE panels are recognized by the I.C.B.O. (International Conference of Building Officials). See I.C.B.O. Research Report Number PFC Copyright WAFFLE-CRETE International, Inc All rights reserved.

3 MATERIALS Material properties and criteria used in the design information contained herein are as follows: A. Normal Weight Precast Concrete ( #/cubic foot) day compressive strength f c = 5000 psi (34,416 KN/m 2 ) or 4000 psi (27,533 KN/m 2 ) 2. Maximum shear strength v c =.75 (2) f c 3. Modulus of elasticity e = w (1.5) 33 f c B. Reinforcing Steel 1. Deformed Billet Steel Bars, ASTM A-615, Grade 60 fy = 60 ksi (412,992 KN/m 2 ) or 40 ksi (275,328 KN/m 2 ) 2. Welded wire fabric, ASTM A-185 fy = 60 ksi (412,992 KN/m 2 ) or 40 ksi (275,328 KN/m 2 ) DESIGN A. Code 1. Uniform Building Code, 1991 Edition 2. American Concrete Institute Building Code B. Spans 1. The spans are in 2 and 4 foot intervals to best utilize the WAFFLE-CRETE form dimensions. Lengths other than those shown may be obtained through the use of headers in the forms during fabrications. 2. Panels were designed in accordance with ultimate strength design methods for maximum allowable stresses. 3. All panels are designed for yield of reinforcing steel prior to concrete failure. C. Loading 1. Panel loading was calculated with dead load and superimposed loads. The dead load included only the panel weight. All superimposed weight, such as partitions, toppings, and live loads shall be considered superimposed loads. 2. Design loading was calculated in conformance with ACI Ultimate strength load factors as follows: U = 1.4D + 1.7L D = dead load or L= live load U =.75 (1.4D + 1.7L W) W = wind load D. Deflections 1. Live load deflections were calculated by: = 5WL El W = uniform live load L = span length E = modulus of elasticity I = effective moment of inertia 2. Deflections shown are elastic short duration only. Upper limit of span lengths do not consider deflection limits for varying applications. General deflection limits are L/240 for roofs and L/360 for floors. E. Transportation and Erection 1. Handling designs assumes Swift Lift anchors cast in the top edge of walls and top of floors. 2. Panels 16 feet and longer require two Swift Lifts for walls and four for floors to be located in top surface of panel in ribs 4 feet from each end. -1-

4 REINFORCING AND DEFLECTION U.S. TABLES 6 FLOOR/ROOF PANEL -- f c = 5000 psi fy = 60,000 psi (grade 60 steel) Superimposed Load 20 psf 30 psf 40 psf 50 psf 100 psf FLOOR AND ROOF SPAN Reinforcing #3 #4 #5 #6 #8 Defl. (inches) Reinforcing #3 #4 #5 #7 #8 Defl. (inches) Reinforcing #3 #4 #6 #8 Defl. (inches) Reinforcing #4 #5 #6 Defl. (inches) Reinforcing #4 #6 Defl. (inches) FLOOR/ROOF PANEL -- f c = 5000 psi fy = 60,000 psi (grade 60 steel) Superimposed Load 20 psf 30 psf 40 psf 50 psf FLOOR AND ROOF SPAN Reinforcing #4 #4 #5 #6 #7 Defl. (inches) Reinforcing #4 #4 #5 #6 #7 Defl. (inches) Reinforcing #4 #4 #5 #6 #8 Defl. (inches) Reinforcing #4 #5 #6 #7 #8 * Defl. (inches) psf Reinforcing #4 #5 #7 #8 * Defl. (inches) * - Indicates shear reinforcement is required. DESIGN NOTES: 1. Design assumes fy = 60 ksi for all reinforcing. Area of reinforcing may be approximated at 1.5 times that shown if fy = 40 ksi. 2. Reinforcing shown above is for span direction only. 3. All panel designs require 6x6 W1.4xW1.4 welded wire fabric at middle of skin, and #3 bar at bottom of each non-span rib in 6 thick panels and #4 bar in non-span ribs of 8 panels. 4. Deflection design in chart is for superimposed loads only. Design assumes all loads other than panel weight are superimposed loads. 5. Panels over 12 feet long should be pre-cambered to minimize deflection. 6. Design information in these charts was derived utilizing ACI-SP and Defl

5 REINFORCING AND DEFLECTION U.S. TABLES 6 FLOOR/ROOF PANEL -- f c = 4000 psi fy = 40,000 psi (grade 40 steel) Superimposed Load 20 psf 30 psf 40 psf 50 psf 100 psf FLOOR AND ROOF SPAN Reinforcing #3 #5 #6 #8 Defl. (inches) Reinforcing #3 #5 #6 Defl. (inches) Reinforcing #3 #5 #7 Defl. (inches) Reinforcing #3 #6 #7 Defl. (inches) Reinforcing #3 #7 Defl. (inches) FLOOR/ROOF PANEL -- f c = 4000 psi fy = 40,000 psi (grade 40 steel) Superimposed FLOOR AND ROOF SPAN Load psf 30 psf 40 psf 50 psf Reinforcing #4 #4 #6 #7 #8 Defl. (inches) Reinforcing #4 #5 #6 #7 #9 Defl. (inches) Reinforcing #4 #5 #6 #8 Defl. (inches) Reinforcing #4 #6 #7 #8 * Defl. (inches) Reinforcing #4 #6 #8 * 100 psf Defl. (inches) Indicates shear reinforcement is required. DESIGN NOTES: 1. Design assumes fy = 40 ksi for all reinforcing. Area of reinforcing may be approximated at 0.67 times that shown if fy = 60 ksi (grade 60 steel). 2. Reinforcing shown above is for span direction only. 3. All panel designs require 6x6 W1.4xW1.4 welded wire fabric at middle of skin, and #3 bar at bottom of each non-span rib in 6 thick panels and #4 bar in non-span ribs of 8 panels. 4. Deflection design in chart is for superimposed loads only. Design assumes all loads other than panel weight are superimposed loads. 5. Panels over 12 feet long should be pre-cambered to minimize deflection. 6. Design information in these charts was derived utilizing ACI-SP and Defl

6 REINFORCING AND ALLOWABLE AXIAL LOAD U.S. TABLES 6 WALL PANEL -- f c = 5000 psi fy = 60,000 psi (grade 60 steel) Wind Speed Exposure Mph UBC Pressure UNBRACED WALL HEIGHT psf C C C D D Reinforcing B-#4 B-#4 B-#4 B-#5, T-#4 B-#5, T-#4 B-#6, T-#5 Load/plf 13,500 13,500 13,500 13,200 12,700 12,050 Reinforcing B-#4 B-#4, T-#3 B-#4, T-#4 B-#5, T-#4 B-#6, T-#5 Load/plf 13,500 13,500 13,200 12,700 12,050 Reinforcing B-#4 B-#5, T-#4 B-#5, T-#4 B-#6, T-#5 Load/plf 13,500 13,500 12,700 12,050 Reinforcing B-#5,T-#4 B-#6, T-#5 B-#6, T-#5 Load/plf 12,700 12,700 12,050 Reinforcing B-#5, T-#4 B-#6, T-#5 Load/plf 12,700 12,700 8 WALL PANEL -- f c = 5000 psi fy = 60,000 psi (grade 60 steel) Wind Speed Exposure Mph UBC Pressure UNBRACED WALL HEIGHT psf C C C D 66.4 Reinforcing B-#4 B-#4 B-#4 B-#5, T-#4 B-#5, T-#4 B-#6, T-#5 Load/plf 15,500 15,500 15,500 13,200 12,700 12,050 Reinforcing B-#4 B-#4 B-#4 B-#5, T-#4 B-#6, T-#5 B-#6, T-#5 Load/plf 15,500 15,500 15,500 12,700 12,050 15,200 Reinforcing B-#4 B-#4 B-#4 B-#6, T-#5 B-#6, T-#5 B-#7, T-#6 Load/plf 15,500 15,500 15,500 12,050 15,200 14,600 Reinforcing B-#5,T-#4 B-#5, T-#4 B-#5, T-#4 B-#6, T-#5 B-#7, T-#6 Load/plf 15,500 15,500 15,500 15,200 12, D T - Refers to reinforcing at skin side of each vertical rib. B Refers to reinforcing at bottom of each vertical rib. DESIGN NOTES: Reinforcing B-#5, T-#4 B-#5, T-#4 B-#6, T-#5 B-#7, T-#6 Load/plf 15,500 15,500 15,200 12, Design assumes fy = 60 ksi for all reinforcing. Area of reinforcing may be approximated at 1.5 times that shown if fy = 40 ksi. 2. All panel designs require 6x6 W2.9xW2.9 welded wire fabric at middle of skin, and #4 bar at bottom of each horizontal rib. 3. Allowable axial load assumes concentric loading with maximum.84 inch eccentricity from centroid of panel. 4. Design information in these charts was derived utilizing ACI-SP and

7 REINFORCING AND ALLOWABLE AXIAL LOAD U.S. TABLES 6 WALL PANEL -- f c = 4000 psi fy = 40,000 psi (grade 40 steel) Wind Speed Exposure Mph UBC Pressure UNBRACED WALL HEIGHT psf C C C D D Reinforcing B-#4 B-#4 B-#5, T-#4 B-#6, T-#5 B-#7, T-#6 B-#8, T-#7 Load/plf 10,600 10,600 10,600 10,600 9,700 9,300 Reinforcing B-#4 B-#5, T-#4 B-#5, T-#4 B-#6, T-#5 B-#7, T-#6 Load/plf 10,600 10,600 10,600 9,700 9,300 Reinforcing B-#5, T-#4 B-#5, T-#4 B-#6, T-#5 B-#7, T-#6 Load/plf 10,600 10,600 9,700 9,300 Reinforcing B-#5,T-#4 B-#6, T-#5 B-#7, T-#6 Load/plf 10,600 9,700 9,300 Reinforcing B-#6, T-#5 Load/plf 9,700 8 WALL PANEL -- f c = 4000 psi fy = 40,000 psi (grade 40 steel) Wind Speed Exposure Mph UBC Pressure UNBRACED WALL HEIGHT psf C C C D 66.4 Reinforcing B-#4 B-#4 B-#5, T-#4 B-#5, T-#4 B-#6, T-#5 B-#7, T-#6 Load/plf 12,800 12,800 12,800 12,800 12,800 11,700 Reinforcing B-#4 B-#5, T-#4 B-#5, T-#4 B-#6, T-#5 B-#6, T-#5 B-#7, T-#6 Load/plf 12,800 12,800 12,800 12,800 11,700 11,000 Reinforcing B-#4 B-#5, T-#4 B-#5, T-#4 B-#6, T-#5 B-#8, T-#7 Load/plf 12,800 12,800 12,800 11,700 11,000 Reinforcing B-#5,T-#4 B-#5, T-#4 B-#6, T-#5 B-#7, T-#6 Load/plf 12,800 12,800 11,700 11, D Reinforcing B-#6, T-#5 B-#6, T-#5 B-#7, T-#6 Load/plf 12,800 11,700 11,000 T - Refers to reinforcing at skin side of each vertical rib. B Refers to reinforcing at bottom of each vertical rib. DESIGN NOTES: 1. Design assumes fy = 40 ksi for all reinforcing. Area of reinforcing may be approximated at.67 times that shown if fy = 60 ksi (greade 60 steel). 2. All panel designs require 6x6 W2.9xW2.9 welded wire fabric at middle of skin, and #4 bar at bottom of each horizontal rib. 3. Allowable axial load assumes concentric loading with maximum.84 inch eccentricity from centroid of panel. 4. Design information in these charts was derived utilizing ACI-SP and

8 REINFORCING AND DEFLECTION METRIC TABLES 6 FLOOR/ROOF PANEL -- f c = 34,416 KN/m 2 fy = 412,992 KN/m 2 (grade 60 steel) Superimposed Load FLOOR AND ROOF SPAN Reinforcing 10 mm 12 mm 16 mm 20 mm 25 mm 1.0 KN/m 2 Defl. (cm) Reinforcing 10 mm 12 mm 16 mm 20 mm 25 mm 1.5 KN/m 2 Defl. (cm) Reinforcing 10 mm 16 mm 20 mm 25 mm 2.0 KN/m 2 Defl. (cm) Reinforcing 12 mm 16 mm 20 mm 2.5 KN/m 2 Defl. (cm) Reinforcing 12 mm 20 mm 5.0 KN/m 2 Defl. (cm) FLOOR/ROOF PANEL -- f c = 34,416 KN/m 2 fy = 412,992 KN/m 2 (grade 60 steel) Superimposed Load FLOOR AND ROOF SPAN KN/m 2 Reinforcing 12 mm 12 mm 16 mm 20 mm 25 mm Defl. (cm) KN/m 2 Reinforcing 12 mm 12 mm 16 mm 20 mm 25 mm Defl. (cm) KN/m 2 Reinforcing 12 mm 16 mm 16 mm 20 mm 25 mm Defl. (cm) KN/m 2 Reinforcing 12 mm 16 mm 20 mm 25 mm 25 mm * Defl. (cm) Reinforcing 16 mm 16 mm 20 mm 25 mm 5.0 KN/m 2 Defl. (cm) * - Indicates shear reinforcement is required. DESIGN NOTES: 1. Design assumes fy = 412,992 KN/m 2 for all reinforcing. Area of reinforcing may be approximated at 1.5 times that shown if fy = 275,328 KN/m 2 (grade 40 steel). 2. Reinforcing shown above is for span direction only 2. All panel designs require 6x6 W1.4xW1.4 welded wire fabric at middle of skin, and 10 mm bar at bottom of each non-span rib in 6 thick panels and 12 mm bar in non-span ribs of 8 panels. 3. Allowable axial load assumes concentric loading with maximum 2.2 cm eccentricity from centroid of panel 5. Panels over 3.7 meters long should be pre-cambered to minimize deflection. 6. Design information in these charts was derived utilizing ACI-SP and Defl

9 REINFORCING AND DEFLECTION METRIC TABLES 6 FLOOR/ROOF PANEL -- f c = 27,533 KN/m 2 fy = 275,328 KN/m 2 (grade 40 steel) Superimposed Load FLOOR AND ROOF SPAN Reinforcing 10 mm 16 mm 20 mm 25 mm 1.0 KN/m 2 Defl. (cm) Reinforcing 10 mm 16 mm 20 mm 1.5 KN/m 2 Defl. (cm) Reinforcing 10 mm 16 mm 25 mm 2.0 KN/m 2 Defl. (cm) Reinforcing 16 mm 20 mm 25 mm 2.5 KN/m 2 Defl. (cm) Reinforcing 16 mm 25 mm 5.0 KN/m 2 Defl. (cm) FLOOR/ROOF PANEL -- f c = 27,533 KN/m 2 fy = 275,328 KN/m 2 (grade 40 steel) Superimposed FLOOR AND ROOF SPAN Load Reinforcing 12 mm 12 mm 20 mm 25 mm 25 mm 1.0 KN/m 2 Defl. (inches) Reinforcing 12 mm 16 mm 20 mm 25 mm 1.5 KN/m 2 Defl. (inches) Reinforcing 12 mm 16 mm 20 mm 25 mm 2.0 KN/m 2 Defl. (inches) Reinforcing 12 mm 20 mm 20 mm 25 mm * 2.5 KN/m 2 Defl. (inches) Reinforcing 12 mm 20 mm 25 mm * 5.0 KN/m 2 Defl. (inches) Indicates shear reinforcement is required. DESIGN NOTES: 1. Design assumes fy = 275,328 KN/m 2 for all reinforcing. Area of reinforcing may be approximated at 0.67 times that shown if fy = 412,992 (grade 60 steel). 2. Reinforcing shown above is for span direction only. 3. All panel designs require 6x6 W1.4xW1.4 welded wire fabric at middle of skin, and 10 mm bar At bottom of each non-span rib in 6 thick panels and 12 mm bar in non-span ribs of 8 panels. 4. Deflection design in chart is for superimposed loads only. Design assumes all loads other than Panel weight are superimposed loads. 5. Panels over 3.7 meters long should be pre-cambered to minimize deflection. 6. Design information in these charts was derived utilizing ACI-SP and Defl

10 REINFORCING AND ALLOWABLE AXIAL LOAD METRIC TABLES 6 WALL PANEL -- f c = 34,416 KN/m 2 fy = 412,992 KN/m 2 (grade 60 steel) Wind Speed Exposure Km/h UBC Pressure UNBRACED WALL HEIGHT N/m C C C D D Reinf. (mm) B-12 B-12 B-12 B-16, T-12 B-16, T-12 B-20, T-16 Load (KN/m) Reinf. (mm) B-12 B-12, T-10 B-12, T-10 B-16, T-12 B-20, T-16 Load (KN/m) Reinf. (mm) B-12 B-16, T-12 B-16, T-12 B-20, T-16 Load (KN/m) Reinf. (mm) B-16, T-12 B-20, T-16 B-20, T-16 Load (KN/m) Reinf. (mm) B-16, T-12 B-20, T-16 Load (KN/m) WALL PANEL -- f c = 34,416 KN/m 2 fy = 412,992 KN/m 2 (grade 60 steel) Wind Speed Exposure Mph UBC Pressure UNBRACED WALL HEIGHT psf C C C D Reinf. (mm) B-12 B-12 B-12 B-12, T-10 B-16, T-12 B-20, T-16 Load (KN/m) Reinf. (mm) B-12 B-12 B-12 B-12, T-10 B-16, T-12 B-20, T-16 Load (KN/m) Reinf. (mm) B-12 B-12 B-12 B-16, T-12 B-20, T-16 B-25, T-20 Load (KN/m) Reinf. (mm) B-12 B-16, T-12 B-16, T-12 B-20, T-16 B-25, T-20 Load (KN/m) D T - Refers to reinforcing at skin side of each vertical rib. B Refers to reinforcing at bottom of each vertical rib. DESIGN NOTES: Reinf. (mm) B-16, T-12 B-16, T-12 B-20, T-16 B-25, T-20 Load (KN/m) Design assumes fy = 412,992 KN/m 2 for all reinforcing. Area of reinforcing may be approximated at 1.5 times that shown if fy = 275,328 KN/m 2 (grade 40 steel). 2. All panel designs require 6x6 W2.9xW2.9 welded wire fabric at middle of skin, and 12 mm bar at bottom of each horizontal rib. 3. Allowable axial load assumes concentric loading with maximum 2.2 cm inch eccentricity from centroid of panel. 4. Design information in these charts was derived utilizing ACI-SP and

11 REINFORCING AND ALLOWABLE AXIAL LOAD METRIC TABLES 6 WALL PANEL -- f c = 27,533 KN/m 2 fy = 275,328 KN/m 2 (grade 40 steel) Wind Speed Exposure Km/h UBC Pressure UNBRACED WALL HEIGHT N/m C C C D D Reinf. (mm) B-12 B-12 B-16, T-12 B-20, T-16 B-25, T-20 B-25, T-20 Load (KN/m) Reinf. (mm) B-12 B-16, T-12 B-16, T-12 B-20, T-16 B-25, T-20 Load (KN/m) Reinf. (mm) B-16, T-12 B-16, T-12 B-20, T-16 B-25, T-20 Load (KN/m) Reinf. (mm) B-20, T-16 B-20, T-16 B-25, T-20 Load (KN/m) Reinf. (mm) B-20, T-16 Load (KN/m) WALL PANEL -- f c = 27,533 KN/m 2 fy = 275,328 KN/m 2 (grade 40 steel) Wind Speed Exposure Mph UBC Pressure UNBRACED WALL HEIGHT psf C C C D Reinf. (mm) B-12 B-12 B-16, T-12 B-16, T-12 B-20, T-16 B-25, T-20 Load (KN/m) Reinf. (mm) B-12 B-16, T-12 B-16, T-12 B-20, T-16 B-20, T-16 B-25, T-20 Load (KN/m) Reinf. (mm) B-12 B-16, T-12 B-16, T-12 B-20, T-16 B-25, T-20 Load (KN/m) Reinf. (mm) B-16, T-12 B-16, T-12 B-20, T-16 B-25, T-20 Load (KN/m) D Reinf. (mm) B-20, T-16 B-20, T-16 B-25, T-20 Load (KN/m) T - Refers to reinforcing at skin side of each vertical rib. B Refers to reinforcing at bottom of each vertical rib. DESIGN NOTES: 1. Design assumes fy = 275,328 KN/m 2 for all reinforcing. Area of reinforcing may be approximated at.67 times that shown if fy = 412,992 KN/m 2 (grade 60 steel). 2. All panel designs require 6x6 W2.9xW2.9 welded wire fabric at middle of skin, and 12 mm bar at bottom of each horizontal rib. 3. Allowable axial load assumes concentric loading with maximum 2.2 cm inch eccentricity from centroid of panel. 4. Design information in these charts was derived utilizing ACI-SP and

12

13

14

15

16

17

18

19

20

21

22

23

24 FOR MORE INFORMATION, WRITE OR CALL WAFFLE-CRETE International, Inc. P.O. BOX 1008 Hays, Kansas USA Ph: Fx: Web: waffle-crete.com & picturetrail.com/wafflecrete1

MASONRY WALL DATA: Wall Height = ft. Nominal Wall Thickness = 8.00 in. Depth to c.g. Steel, Wall = 3.81 in.

MASONRY WALL DATA: Wall Height = ft. Nominal Wall Thickness = 8.00 in. Depth to c.g. Steel, Wall = 3.81 in. TIME: 10:49 AM Page: 1 DESIGN METHOD : ACI 530-99: Working Stress Design MASONRY MATERIAL : Hollow Core Concrete Masonry Units MORTAR TYPE : Type S MORTAR MATERIAL : Portland Cement Lime Mortar BLOCK PLACEMENT

More information

Pro-Con Structural Study for Alternative Floor Systems October 27, 2004

Pro-Con Structural Study for Alternative Floor Systems October 27, 2004 Ismail Al-Hadhrami Structural Option Faculty Consultant: Dr. Thomas Boothby Agricultural Hall and Annex East Lansing, MI Pro-Con Structural Study for Alternative Floor Systems October 27, 2004 Executive

More information

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California Reissued June 1, 2002 ICBO Evaluation Service, Inc. 5360 Workman Mill Road, Whittier, California 90601 www.icboes.org Filing Category: DESIGN Concrete DURISOL WALL FORMS FOR CONCRETE CONSTRUCTION DURISOL

More information

DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104

DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2047 Reissued 07/207 This report is subject to renewal 07/209. DIVISION: 05 00 00

More information

Armopanel Concrete Wall System. Design Guide B-3.1. BASEMENT WALLS

Armopanel Concrete Wall System. Design Guide B-3.1. BASEMENT WALLS Design Guide B-.. BASEMENT WALLS There are three options for using Armopanel system in low-rise residential buildings. The summaries of these three options are presented in basement wall tables below.

More information

Lintel Tables Design Notes and Limitations

Lintel Tables Design Notes and Limitations LINTEL TABLES Lintel Tables Design Notes and Limitations 1. These tables apply to one and two family residential structures only that conform to the requirements of the 2006, 2009 or 2012 International

More information

GLOBAL LVL HEADERS, BEAMS AND COLUMNS. 1.9E-2850Fb. 1.9E-2850Fb. User guide User guide. lvlglobal.com

GLOBAL LVL HEADERS, BEAMS AND COLUMNS. 1.9E-2850Fb. 1.9E-2850Fb. User guide User guide. lvlglobal.com GLOBAL LVL HEADERS, BEAMS AND COLUMNS 1.9E-2850Fb GLOBAL LVL HEADERS, BEAMS AND COLUMNS 1.9E-2850Fb User guide User guide lvlglobal.com Global LVL, the product of choice for all of your residential, commercial

More information

Structural Technical Report 1 Structural Concepts/ Structural Existing Conditions Report

Structural Technical Report 1 Structural Concepts/ Structural Existing Conditions Report Kelly M. Sadusky The Food Science Building Oct. 6, 2004 Professor Parfitt University Park, PA Structural Option Executive Summery: Structural Technical Report 1 Structural Concepts/ Structural Existing

More information

Figure: Grid or Waffle slab

Figure: Grid or Waffle slab Two Way Beam Supported Slab References: 1. Design of. Reinforced Concrete, 2014, 9 th Edition, ACI 318-11 Code Edition, by Jack C. McCormac. Clemson University. Russell H. Brown. Clemson University 2.

More information

North Mountain IMS Medical Office Building

North Mountain IMS Medical Office Building North Mountain IMS Medical Office Building Phoenix, Arizona Michael Hopple Technical Assignment 2 October 29 th, 2007 AE 481W-Senior Thesis The Pennsylvania State University Faculty Adviser: Dr. Ali Memari,

More information

Table of Contents 2. Structural Systems.4 Foundations.4 Floor System...4 Columns..5 Lateral System...5

Table of Contents 2. Structural Systems.4 Foundations.4 Floor System...4 Columns..5 Lateral System...5 WISCONSIN PLACE RESIDENTIAL TECHNICAL ASSIGNMENT 1 OCTOBER 5, 2007 KURT KRASAVAGE THE PENNSYLVANIA STATE UNIVERSITY STRUCTURAL OPTION FACULTY ADVISOR: DR. ALI MEMARI Table of Contents Table of Contents

More information

HARVEY MUDD COLLEGE TEACHING AND LEARNING CENTER SECTION Page 1 of 6 VOIDED CONCRETE SLAB

HARVEY MUDD COLLEGE TEACHING AND LEARNING CENTER SECTION Page 1 of 6 VOIDED CONCRETE SLAB 030111 Page 1 of 6 PART 1 - GENERAL 1.1 SUMMARY A. This Section specifies: 1. Voided concrete floor and roof slab system consisting of structural reinforced concrete containing hollow (bubbles) spherical

More information

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code LEGACY REPORT ER-4203 Reissued June 1, 2004 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office #

More information

Foundation Specifications

Foundation Specifications Installation Instructions Bulletin 237684 Foundation Specifications for 5.6-Meter Ka-Band Earth Station Antennas 1.0 INTRODUCTION 1.1 This document specifies typical foundation characteristics, designs,

More information

Foundation Specifications

Foundation Specifications Installation Instructions Bulletin 7581438 Revision C Foundation Specifications for 6.5-Meter Modular Earth Station Antennas Introduction This document specifies typical foundation characteristics, designs,

More information

Agricultural Hall and Annex East Lansing, MI. Structural Design. Gravity Loads. 1- Based on US Standards

Agricultural Hall and Annex East Lansing, MI. Structural Design. Gravity Loads. 1- Based on US Standards Structural Design Gravity Loads 1- Based on US Standards Occupancy or Use Uniform (psf) Concentrated (lbs) Office building -Office -Lobbies and first-floor corridors -Corridor above first floor -Partitions

More information

HIGH RISE CONDO SOHO, NEW YORK, NY

HIGH RISE CONDO SOHO, NEW YORK, NY HIGH RISE CONDO SOHO, NEW YORK, NY TECHNICAL ASSIGNMENT 1 October 5, 2006 Joseph The Pennsylvania State University Structural Option Faculty Advisor: Andres Lepage TABLE OF CONTENTS TABLE OF CONTENTS 2

More information

Atkinson Engineering, Inc.

Atkinson Engineering, Inc. Atkinson Engineering, Inc. Atkinson Engineering, Inc. One of the problems in underpinning a typical post-tensioned foundation is support for the slab part that spans between the stiffening beams. An example

More information

Foundation Specifications

Foundation Specifications Installation Instructions Bulletin 237684 Foundation Specifications for 5.6-Meter Ka-Band Earth Station Antennas 1.0 INTRODUCTION 1.1 This document specifies typical foundation characteristics, designs,

More information

Structural Design Engineers 120 Montgomery Street, Suite 1410 San Francisco, California / Fax 415/

Structural Design Engineers 120 Montgomery Street, Suite 1410 San Francisco, California / Fax 415/ 120 Montgomery Street, Suite 1410 San Francisco, California 94104 415/781-1505 Fax 415/781-2718 sde@sdesf.com Rajendra Sahai, SE Principal John W. Laws, SE Principal Steven Lepisto, SE Principal STRUCTURAL

More information

MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS

MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS PARKERSBURG, WEST VIRGINIA DOMINIC MANNO STRUCTURAL OPTION FACULTY CONSULTANT: DR. ANDRES LEPAGE Technical Report 3 11-21-08 TABLE OF CONTENTS TABLE OF

More information

ALLOWABLE STRESS DESIGN OF CONCRETE MASONRY LINTELS. TEK 17-1C Structural (2009) Related TEK: Uniform load. Triangular load. Concentrated loads

ALLOWABLE STRESS DESIGN OF CONCRETE MASONRY LINTELS. TEK 17-1C Structural (2009) Related TEK: Uniform load. Triangular load. Concentrated loads An information series from the national authority on concrete masonry technology ALLOWABLE STRESS DESIGN OF CONCRETE MASONRY LINTELS TEK 17-1C Structural (2009) INTRODUCTION Lintels and beams are horizontal

More information

OVERALL STRUCTURAL SYSTEM

OVERALL STRUCTURAL SYSTEM EXECUTIVE SUMMARY The at the Pittsburgh International Airport, PA, is a 275,000 square foot multi-use building located directly adjacent to the airport s landside terminal. The building consists of an

More information

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued January 1, Legacy report on the 1997 Uniform Building Code

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued January 1, Legacy report on the 1997 Uniform Building Code LEGACY REPORT Reissued January 1, 2004 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office # 900 Montclair

More information

Level 6 Graduate Diploma in Engineering Structural analysis

Level 6 Graduate Diploma in Engineering Structural analysis 9210-111 Level 6 Graduate Diploma in Engineering Structural analysis Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler, drawing

More information

Crossroads at Westfields Building II

Crossroads at Westfields Building II Crossroads at Westfields Building II Chantilly, Va STEPHEN LUMPP Structural option Faculty Consultant: Dr. Andres Lepage Technical Report 2 EXECUTIVE SUMMARY This report is a study of alternate floor systems

More information

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi

Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel

More information

Recessed Door Header Engineering PSBox8LT(5-5/8") 22ga.

Recessed Door Header Engineering PSBox8LT(5-5/8) 22ga. Florida 3000psi Recessed Door Header Engineering PSBox8LT(5-5/8") 22ga. October 2012 888.525.0108 www.powerssteel.com/lintels By: sws PSbox8LT (5-5/8") Lintels Date: 3/2012 8" inch block width (22ga.

More information

DIVISION: CONCRETE SECTION: SPECIALTY PLACED CONCRETE REPORT HOLDER: EMMEDUE S.P.A.

DIVISION: CONCRETE SECTION: SPECIALTY PLACED CONCRETE REPORT HOLDER: EMMEDUE S.P.A. 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-2037 Reissued 07/2016 This report is subject to renewal 07/2018. DIVISION: 03 00 00 CONCRETE

More information

16. Design of Pipeline Structures.

16. Design of Pipeline Structures. 16. Design of Pipeline Structures. a. General. 1) The following guidelines are for the design of structures for water and sewer pipelines including structural concrete and miscellaneous metals design.

More information

CONCRETE TECHNOLOGY CORPORATION

CONCRETE TECHNOLOGY CORPORATION PRECAST, PRESTRESSED HOLLOW CORE SLABS DESIGN CRITERIA & SPAN-LOAD CHARTS Introduction 2 Design Criteria for Development of the Span-Load Charts 2 Related Publications 3 Manufacturing Tolerances 4 8" Bare

More information

REINFORCING TABLES INSTALLATION MANUAL

REINFORCING TABLES INSTALLATION MANUAL REINFORCING TABLES 201 REINFORCING TABLES Design Limitations Introduction The structural wall reinforcing and lintel design tables contained within the Appendix of NUDURA s Installation Manual have been

More information

City of Mesquite General Design Standards Revision Date:

City of Mesquite General Design Standards Revision Date: SCREENING WALLS (Public and Private) Page 1 of 6 Section 1 General Design & Notes 1.1 Standards 1.1.1 All screening walls in the City of Mesquite and within its Extraterritorial Jurisdiction (ETJ), both

More information

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan Brief Building Overview: 200 Minuteman Park stands as a 200,000 square foot Class A office building in Andover, Massachusetts, worth roughly $15,000,000. Although the building has a large square footage,

More information

Design of Reinforced Concrete Slabs

Design of Reinforced Concrete Slabs Lecture 07 Design of Reinforced Concrete Slabs By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar drqaisarali@uetpeshawar.edu.pk 1 Topics Addressed Introduction Analysis and Design of slabs

More information

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II SECTION 052100 - STEEL JOISTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections

More information

Foundation Specifications

Foundation Specifications Installation Instructions Bulletin 237731 Revision E Foundation Specifications for 3.5-Meter Earth Station Antennas 1.0 INTRODUCTION 1.1 This document specifies typical foundation characteristics, designs,

More information

151 First Side. Technical Assignment 2 November 16 th, William J. Buchko. AE 481w Senior Thesis The Pennsylvania State University

151 First Side. Technical Assignment 2 November 16 th, William J. Buchko. AE 481w Senior Thesis The Pennsylvania State University November 16 th, 2007 William J. Buchko AE 481w Senior Thesis The Pennsylvania State University Thesis Advisor: Kevin Parfitt Table of Contents Executive Summary... 3 Structural System Overview Foundation...

More information

Comparison of One-way and Two-way slab behavior. One-way slabs carry load in one direction. Two-way slabs carry load in two directions.

Comparison of One-way and Two-way slab behavior. One-way slabs carry load in one direction. Two-way slabs carry load in two directions. Two-way Slabs Comparison of One-way and Two-way slab behavior One-way slabs carry load in one direction. Two-way slabs carry load in two directions. Comparison of One-way and Two-way slab behavior One-way

More information

A Guide for the Interpretation of Structural Design Options for Residential Concrete Structures

A Guide for the Interpretation of Structural Design Options for Residential Concrete Structures CFA Technical Note: 008-2010 A Guide for the Interpretation of Structural Design Options for Residential Concrete Structures CFA Technical This CFA Technical Note is intended to serve as a guide to assist

More information

SJI Updates Expanded Load Tables for Noncomposite Joists / Joist Girders and Development of New Composite Joist Series

SJI Updates Expanded Load Tables for Noncomposite Joists / Joist Girders and Development of New Composite Joist Series SJI Updates Expanded Load Tables for Noncomposite Joists / Joist Girders and Development of New Composite Joist Series SUMMARY David Samuelson Steel joists are growing in recognition as being a very economical

More information

Structural Technical Report #2 Pro/Con Study of Alternate Floor Systems

Structural Technical Report #2 Pro/Con Study of Alternate Floor Systems Christopher McCune Structural Option Eight Tower Bridge Faculty Advisor: Dr. Hanagan October 31 st, 2005 Structural Technical Report #2 Pro/Con Study of Alternate Floor Systems Executive Summary This technical

More information

Technical Assignment 3 December 3, 2007

Technical Assignment 3 December 3, 2007 Technical Assignment 3 December 3, 2007 101 Eola Drive, Orlando, FL Justin Raducha Pennsylvania State University Faculty Advisor: M. Kevin Parfitt Table of Contents Table of Contents... 2 Executive Summary...

More information

Alexis Pacella Structural Option Dr. Schneider Lexington II, Washington D.C. Technical Report #3 November 21,

Alexis Pacella Structural Option Dr. Schneider Lexington II, Washington D.C. Technical Report #3 November 21, 1 Executive Summary: Lateral System Analysis and Confirmation Design is an depth look at the lateral system of Lexington II and the loads of which it must carry. The structural system of Lexington II is

More information

Hyatt Place North Shore. Pittsburgh, PA T. Technical Assignment #1. Kyle Tennant. Kyle Tenn. Structural (IP) [Type the document subtitle]

Hyatt Place North Shore. Pittsburgh, PA T. Technical Assignment #1. Kyle Tennant. Kyle Tenn. Structural (IP) [Type the document subtitle] Technical Assignment #1 Hyatt Place North Shore [Type the document subtitle] T Kyle Tenn Kyle Tenn Kyle Tennant Structural (IP) Dr. Ali Memari O c t o b e r 4 2 0 1 0 Table of Contents I. Executive Summary

More information

Foundation Specifications for 3.6-/3.7-Meter Earth Station Antennas

Foundation Specifications for 3.6-/3.7-Meter Earth Station Antennas Installation Instructions Foundation Specifications for 3.6-/3.7-Meter Earth Station Antennas Bulletin 37835A Revision E Introduction This document specifies typical foundation characteristics, designs,

More information

48.5% Throughput. 6 Connector 51.5% Plastic. 45.7% Throughput. 4 Connector 54.3% Plastic. 51.0% Throughput. 2 Connector 49.

48.5% Throughput. 6 Connector 51.5% Plastic. 45.7% Throughput. 4 Connector 54.3% Plastic. 51.0% Throughput. 2 Connector 49. TABLE OF CONTENTS 1 Percentage Hollow Areas Vs. Plastic Areas (Concrete Throughput) 2 Axial Loading / Bending Moment Interaction Diagrams 6 Concrete Wall 8 Concrete Wall 10 Concrete Wall 3 3 5 7 EZ Form

More information

The Hashemite University Department of Civil Engineering. Dr. Hazim Dwairi 1

The Hashemite University Department of Civil Engineering. Dr. Hazim Dwairi 1 Department of Civil Engineering Lecture 8 Deflection and Camber Introduction Prestressed concrete beams are more slender than R.C. beams, high span/depth ratios; thus, more deflection. Camber may be important.

More information

TECHNICAL REPORT 1. Structural Concepts / Structural Existing Conditions. Penn State Hershey Medical Center Children s Hospital. Hershey, Pennsylvania

TECHNICAL REPORT 1. Structural Concepts / Structural Existing Conditions. Penn State Hershey Medical Center Children s Hospital. Hershey, Pennsylvania TECHNICAL REPORT 1 Structural Concepts / Structural Existing Conditions Penn State Hershey Medical Center Children s Hospital Matthew V Vandersall The Pennsylvania State University Architectural Engineering

More information

PRODUCT: Structural Insulated Panels (SIP) DIVISION: Wood and Plastics (06) SECTION: Structural Panels ( )

PRODUCT: Structural Insulated Panels (SIP) DIVISION: Wood and Plastics (06) SECTION: Structural Panels ( ) PRODUCT: Structural Insulated Panels (SIP) DIVISION: Wood and Plastics (06) SECTION: Structural Panels (06 12 16) Report Holder General Panel Corporation PO Box 279 2604 Sunset Drive Grenada, Mississippi

More information

Structural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity

Structural System. Design Criteria Fire Resistance Concrete designed for 2 HR rating (worst case) Geotechnical Report Allowable Bearing Capacity System Codes and Criteria Design Codes and Standards The design code used is the Wisconsin Administrative Code along with the State of Wisconsin Department of Commerce-Safety & Buildings Chapters Comm

More information

David A. Walenga Technical Assignment #2

David A. Walenga Technical Assignment #2 Executive Summary This report explores multiple structural design alternatives for the Residence Inn by Marriott. The existing system, precast concrete plank on steel, is the basis for comparison with

More information

STRUCTURAL ENGINEERING CALCULATIONS NEW WINDOW OPENING IN EXISTING PERIMETER LOAD BEARING WOOD FRAMED WALL Project Address: Job #: 80167

STRUCTURAL ENGINEERING CALCULATIONS NEW WINDOW OPENING IN EXISTING PERIMETER LOAD BEARING WOOD FRAMED WALL Project Address: Job #: 80167 4533 MacArthur Blvd., Ste A-2003 Newport Beach, CA 92660 949-478-4026 cell www.ocstructurecheck.com jeremy@ocstructurecheck.com STRUCTURAL ENGINEERING CALCULATIONS NEW WINDOW OPENING IN EXISTING PERIMETER

More information

Simplified Building Schematic for Typical Floor (Levels 9 through 22):

Simplified Building Schematic for Typical Floor (Levels 9 through 22): Introduction to Structural System Simplified Building Schematic for Typical Floor (Levels 9 through 22): Key: - Tower Columns - Tower Shear Walls - Parking Garage Columns - Parking Garage Shear Walls Solid

More information

Temecula Medical Center Temecula, CA

Temecula Medical Center Temecula, CA Temecula Medical Center Temecula, CA Technical Assignment #2 Sean F. Beville The Pennsylvania State University Architectural Engineering Structural Option Senior Thesis Project Student Advisor: Thomas

More information

North Mountain IMS Medical Office Building

North Mountain IMS Medical Office Building North Mountain IMS Medical Office Building Phoenix, Arizona Michael Hopple Technical Assignment 1 October 5 th, 2007 AE 481W-Senior Thesis The Pennsylvania State University Faculty Adviser: Dr. Ali Memari,

More information

Software Verification

Software Verification EXAMPLE 9 ACI Handbook Two-Way Slab Example 2 PROBLEM DESCRIPTION The two-way slab system arranged three-by-three is shown in Figure 9-1. The slab consists of nine 6.5-inch-thick 20-foot 24-foot panels.

More information

Listing Report: MUR Reissue Date: 12/07/17 This report is subject to annual review

Listing Report: MUR Reissue Date: 12/07/17 This report is subject to annual review CSI 06 12 16 PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood and Plastics SECTION: Structural Panels Report Holder The Murus Company PO Box 220 Mansfield, PA 16933 Manufacturing Locations The

More information

Steel Design Guide Series. Steel and Composite Beams with. Web Openings

Steel Design Guide Series. Steel and Composite Beams with. Web Openings Steel Design Guide Series Steel and Composite Beams with Web Openings Steel Design Guide Series Steel and Composite Beams with Web Openings Design of Steel and Composite Beams with Web Openings David Darwin

More information

1 Prepared By:Mr.A.Sathiyamoorthy, M.E., AP/Civil

1 Prepared By:Mr.A.Sathiyamoorthy, M.E., AP/Civil UNIVERSITY QUESTIONS PART A UNIT 1: INTRODUCTION THEORY AND BEHAVIOUR 1. List the loss of prestress. 2. Define axial prestressing. 3. What is the need for the use of high strength concrete and tensile

More information

STANDARD SPECIFICATIONS

STANDARD SPECIFICATIONS American National Standard SJI-K 1.1 STANDARD SPECIFICATIONS FOR OPEN WEB STEEL JOISTS, K-SERIES Adopted by the Steel Joist Institute November 4, 1985 Revised to November 10, 2003 - Effective March 01,

More information

William W. Wilkins Professional Building Columbus, Ohio

William W. Wilkins Professional Building Columbus, Ohio William W. Wilkins Professional Building Columbus, Ohio Technical Assignment 1 October 5, 2006 Michelle Structural Option AE 481W Senior Thesis Faculty Advisor: Dr. Boothby Table of Contents Executive

More information

CLT Structural Design Sylvain Gagnon, Eng. February 8, 2011 Vancouver

CLT Structural Design Sylvain Gagnon, Eng. February 8, 2011 Vancouver www.fpinnovations.ca CLT Structural Design Sylvain Gagnon, Eng. February 8, 2011 Vancouver Structural Design Handbook 10/02/2011 2 Critical Characteristics for CLT used as floor/roof Short-term and long-term

More information

Originally Issued: 05/01/2015 Revised: 09/01/2017 Valid Through: 05/31/2018

Originally Issued: 05/01/2015 Revised: 09/01/2017 Valid Through: 05/31/2018 HEBEL AUTOCLAVED AERATED CONCRETE (AAC) PANELS AND THIN BED MORTAR CSI Section: 03 41 00 Precast Structural Concrete 1.0 RECOGNITION Hebel Autoclaved Aerated Concrete (AAC) and Thin Bed Mortar have been

More information

Project Address: Name of Person Completing Form:

Project Address: Name of Person Completing Form: Statement of Inspections This form is provided as a way to list aspects of the project that require special inspection and testing in accordance with IBC Sections 107.1, 1704, and 1705 and define duties

More information

Technical Notes on Brick Construction Brick Industry Association Commerce Park Drive, Reston, Virginia 20191

Technical Notes on Brick Construction Brick Industry Association Commerce Park Drive, Reston, Virginia 20191 Technical Notes on Brick Construction Brick Industry Association 11490 Commerce Park Drive, Reston, Virginia 20191 31B REVISED Reissued* May 1987 STRUCTURAL STEEL LINTELS Abstract: The design of structural

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-03 11 13.00 10 (May 2014) --------------------------------- Preparing Activity: USACE Superseding UFGS-03 11 13.00 10 (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Foundation Specifications

Foundation Specifications Installation Instructions Foundation Specifications for 3.6-/3.7-Meter Earth Station Antennas ulletin 37835A Revision L Introduction This document specifies typical foundation characteristics, designs,

More information

Multi-Story Solid Tilt-Up Wall Panel Analysis and Design (ACI 551)

Multi-Story Solid Tilt-Up Wall Panel Analysis and Design (ACI 551) Multi-Story Solid Tilt-Up Wall Panel Analysis and Design (ACI 551) Span 1 Span 2 Span 3 Span 4 Reinforced Concrete Multi-Story Tilt-Up Wall Panel Analysis (ACI 551) Tilt-up is form of construction with

More information

Structural Comparison between Pan Joist Concrete and Steel Frame Systems for UMCP Student Housing Building B

Structural Comparison between Pan Joist Concrete and Steel Frame Systems for UMCP Student Housing Building B Structural Comparison between Pan Joist Concrete and Steel Frame Systems for UMCP Student Housing Executive Summary The proposed thesis will include an investigation of two different alternative structural

More information

Bautex Wall System. Design & Engineering Guide

Bautex Wall System. Design & Engineering Guide Bautex Wall System Design & Engineering Guide TM BAUTEX IS A HIGH-PERFORMANCE COMPOSITE CONCRETE WALL SYSTEM THAT MEETS THE DEMANDS OF TODAY S RETAIL, HOSPITALITY, OFFICE, MEDICAL, AND GOVERNMENT BUILDING

More information

Dead Loads (psf): Concrete Floor Slab on Metal Deck 45 psf Mechanical and Ceiling 7 psf Miscellaneous 5 psf Exterior Wall 80 psf

Dead Loads (psf): Concrete Floor Slab on Metal Deck 45 psf Mechanical and Ceiling 7 psf Miscellaneous 5 psf Exterior Wall 80 psf CODES AND REQUIREMENTS The structural design of Northbrook Corporate Center was based on the International Building Code 2003, which incorporates many of the provisions of ASCE 7. The lateral load design

More information

CONCRETE TECHNOLOGY CORPORATION

CONCRETE TECHNOLOGY CORPORATION PRECAST, PRESTRESSED HOLLOW CORE SLABS DESIGN CRITERIA & SPAN-LOAD CHARTS FOR STORM WATER DETENTION VAULT LIDS (CHARTS REVISED /18/08) Introduction Design Criteria for Development of the Span-Load Charts

More information

PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood, Plastics, and Composites (06) SECTION: Structural Panels ( )

PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood, Plastics, and Composites (06) SECTION: Structural Panels ( ) PRODUCT: Structural Insulated Panels (SIPs) DIVISION: Wood, Plastics, and Composites (06) SECTION: Structural Panels (06 12 00) Report Holder ACME Panel Company 1905 West Main St. Radford, VA 24141 Manufacturing

More information

Hilton Baltimore Convention Center Hotel Western Podium

Hilton Baltimore Convention Center Hotel Western Podium Hilton Baltimore Convention Center Hotel Western Podium CHRIS SIMMONS Structural Option Faculty Consultant: Dr. Ali M. Memari Technical Report 2 TABLE OF CONTENTS EXECUTIVE SUMMARY. Page 3 INTRODUCTION..

More information

ADAPT PT7 TUTORIAL FOR ONE-WAY SLAB 1

ADAPT PT7 TUTORIAL FOR ONE-WAY SLAB 1 Structural Concrete Software System TN187_PT7_tutorial_one_way_slab 012705 ADAPT PT7 TUTORIAL FOR ONE-WAY SLAB 1 1. ONE-WAY SLAB SUPPORTED ON BEAMS The objective of this tutorial is to demonstrate the

More information

Technical Report 1. Kingstowne Section 36A 5680 King Center Drive Kingstowne, VA James Chavanic. Structural Option. Advisor: Dr.

Technical Report 1. Kingstowne Section 36A 5680 King Center Drive Kingstowne, VA James Chavanic. Structural Option. Advisor: Dr. Technical Report 1 Rendering provided by DCS Design 5680 King Center Drive Kingstowne, VA 22315 Advisor: Dr. Boothby September 17, 2012 TABLE OF CONTENTS Executive Summary 3 Building Introduction 4 Structural

More information

Lightweight Steel Framing. Composite DeltaStud Load Tables

Lightweight Steel Framing. Composite DeltaStud Load Tables Lightweight Steel Framing Composite DeltaStud Load Tables January 2011 TABLE OF CONTENTS Introduction and Scope...3 Design Responsibility...3 Design Criteria and Technical Data...3 Composite Action / Materials

More information

Third Avenue New York, NY. Structural Concepts/ Structural Existing Conditions Report September 30, Michelle L.

Third Avenue New York, NY. Structural Concepts/ Structural Existing Conditions Report September 30, Michelle L. Executive Summary The structural design of 554-556 Third Avenue is composed of two way concrete slabs supported by a system of columns spanning an average of twenty feet. Lateral loads are resisted by

More information

ANALYSIS AND DESIGN OF MULTI-STOREY COMPOSITE BUILDING

ANALYSIS AND DESIGN OF MULTI-STOREY COMPOSITE BUILDING ANALYSIS AND DESIGN OF MULTI-STOREY COMPOSITE BUILDING Mr Nann Tin 1, Dr Tin Tin Win 2 1 Postgraduate Student, Department of Civil Engineering, Mandalay Technological University, Myanmar 2 Director, Myanma

More information

DECK DAMAGE AND PENETRATIONS

DECK DAMAGE AND PENETRATIONS DECK DAMAGE AND PENETRATIONS Prepared By Richard B. Heagler, P.E. SDI CONSULTANT Copyright 1987 (Rev. 2000) All rights reserved P.O. Box 25 Fox River Grove, IL 60021 Phone: (847) 458-4647 Fax: (847) 458-4648

More information

ACI Code Revisions Impact on StructurePoint Software

ACI Code Revisions Impact on StructurePoint Software ACI 318-19 Code Revisions Impact on StructurePoint Software General Themes & Summary ACI 318-19 continues to unify and simplify code provisions started in 2014 reorganization of chapters by members. Nearly

More information

SECTION PLATE CONNECTED WOOD TRUSSES

SECTION PLATE CONNECTED WOOD TRUSSES SECTION 06173 PLATE CONNECTED WOOD TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Shop fabricated wood trusses for roof and floor framing. 2. Bridging, bracing, and anchorage. B. Related Sections:

More information

THE FORENSIC MEDICAL CENTER

THE FORENSIC MEDICAL CENTER THE FORENSIC MEDICAL CENTER Image courtesy of Gaudreau, Inc. TECHNICAL REPORT #2 OCTOBER 26, 2007 KEENAN YOHE STRUCTURAL OPTION DR. MEMARI FACULTY ADVISOR EXECUTIVE SUMMARY Image courtesy of Gaudreau,

More information

NCMA TEK. TEK 14-5A Structural (2006) LOADBEARING CONCRETE MASONRY WALL DESIGN

NCMA TEK. TEK 14-5A Structural (2006) LOADBEARING CONCRETE MASONRY WALL DESIGN NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology LOADBEARING CONCRETE MASONRY WALL DESIGN TEK 14-5A Structural (26) Keywords:

More information

TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following:

TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following: PART 1 GENERAL 1.01 SUMMARY SECTION 03460 TILT-UP PRECAST CONCRETE SANDWICH PANELS A. Work includes, but is not limited to, the following: 1. Architectural precast concrete sandwich wall panels. 2. Integral

More information

Trump Taj Mahal Hotel

Trump Taj Mahal Hotel Trump Taj Mahal Hotel Atlantic City, New Jersey Thesis Proposal Prepared By: Stephen Reichwein, Structural Option Faculty Advisor: Dr. Andres Lepage The Pennsylvania State University Department of Architectural

More information

6.0 TUTORIAL. Cascade Consulting Associates, Inc. PO Box 1617 Corvallis, Oregon 97339

6.0 TUTORIAL. Cascade Consulting Associates, Inc. PO Box 1617 Corvallis, Oregon 97339 for WINDOWS TM 6.0 TUTORIAL Cascade Consulting Associates, Inc. PO Box 1617 Corvallis, Oregon 97339 Phone: (541) 753-0117 Fax: (541) 753-9422 www.strucalc.com E-mail: strucalc@strucalc.com 1 1. TUTORIAL

More information

VARIOUS TYPES OF SLABS

VARIOUS TYPES OF SLABS VARIOUS TYPES OF SLABS 1 CHOICE OF TYPE OF SLAB FLOOR The choice of type of slab for a particular floor depends on many factors. Economy of construction is obviously an important consideration, but this

More information

Precast Concrete Bearing Wall Panel Design (Alternative Analysis Method) (Using ACI )

Precast Concrete Bearing Wall Panel Design (Alternative Analysis Method) (Using ACI ) Precast Concrete Bearing Wall Panel Design (Alternative Analysis ethod) (Using ACI 318-14) Precast Concrete Bearing Wall Panel Design (Alternative Analysis ethod) (Using ACI 318-14) A structural precast

More information

ASD OF CONCRETE MASONRY LINTELS BASED ON THE 2012 IBC/2011 MSJC. TEK 17-1D Structural (2011) Related TEK: 14-7C, 14-13B, 17-1C, 17-2A

ASD OF CONCRETE MASONRY LINTELS BASED ON THE 2012 IBC/2011 MSJC. TEK 17-1D Structural (2011) Related TEK: 14-7C, 14-13B, 17-1C, 17-2A n information series from the national authority on concrete masonry technology SD OF CONCRETE MSONRY LINTELS BSED ON THE 2012 IBC/2011 MSJC TEK 17-1D Structural (2011) INTRODUCTION Lintels and beams are

More information

Outline. Introduction. Structural Redesign Gravity System Floor System Lateral System Weight Comparison Seismic Comparison

Outline. Introduction. Structural Redesign Gravity System Floor System Lateral System Weight Comparison Seismic Comparison Outline Breadth Conclusions, Acknowledgements, Questions & Comments Breadth Breadth Location: Wilmington Delaware Owned and managed by: Pettinaro Real Estate Development Company Delivery Method: Design-Bid-Build

More information

Alexis Pacella Structural Option Dr. Schneider Lexington II, Washington D.C. Technical Report #2 October 31,

Alexis Pacella Structural Option Dr. Schneider Lexington II, Washington D.C. Technical Report #2 October 31, 1 Executive Summary: Pro-Con Structural Study of Alternate Floor Systems is an investigation into possible alternative structural systems for Lexington II in Washington, D.C. For this report, several structural

More information

Reinforced Concrete Design. A Fundamental Approach - Fifth Edition

Reinforced Concrete Design. A Fundamental Approach - Fifth Edition CHAPTER REINFORCED CONCRETE Reinforced Concrete Design A Fundamental Approach - Fifth Edition Fifth Edition REINFORCED CONCRETE A. J. Clark School of Engineering Department of Civil and Environmental Engineering

More information

Murphy LVL Limit States Design Guide 2.0 E-LVL 2.2 E-LVL

Murphy LVL Limit States Design Guide 2.0 E-LVL 2.2 E-LVL Murphy LVL Limit States Design Guide 2.0 E-LVL 2.2 E-LVL Our Company At Murphy Company we take pride in providing our customers with premium quality products and services. Our LVL is manufactured to provide

More information

Hilton Baltimore Convention Center Hotel Western Podium

Hilton Baltimore Convention Center Hotel Western Podium Hilton Baltimore Convention Center Hotel Western Podium CHRIS SIMMONS Structural Option Faculty Consultant: Dr. Ali M. Memari Technical Report 1 TABLE OF CONTENTS EXECUTIVE SUMMARY. Page 3 INTRODUCTION..

More information

REINFORCED ENGINEERING HANDBOOK CLAY AND CONCRETE MASONRY SEVENTH EDITION. John M. Hochwalt, PE, SE KPFF Consulting Engineers

REINFORCED ENGINEERING HANDBOOK CLAY AND CONCRETE MASONRY SEVENTH EDITION. John M. Hochwalt, PE, SE KPFF Consulting Engineers REINFORCED MASONRY ENGINEERING HANDBOOK CLAY AND CONCRETE MASONRY SEVENTH EDITION John M. Hochwalt, PE, SE KPFF Consulting Engineers James E. Amrhein Original Author Published by MASONRY INSTITUTE OF AMERICA

More information

Southwest Housing, Arizona State University

Southwest Housing, Arizona State University Prepared by KSENIA TRETIAKOVA Structural Option 01.09.2012 Architectural Engineering Pennsylvania State University 2012 Southwest Housing, Arizona State University Technical Report #3 Lateral System 01.09.2012

More information

Column: Part 2 Courtesy of Dr. Latifee s IMI research group, Text books and others

Column: Part 2 Courtesy of Dr. Latifee s IMI research group, Text books and others Column: Part 2 Courtesy of Dr. Latifee s IMI research group, Text books and others Design for Axial Load: With negligible moment and considerable amount of concentric axial load, failure occurs when the

More information