HARVEY MUDD COLLEGE TEACHING AND LEARNING CENTER SECTION Page 1 of 6 VOIDED CONCRETE SLAB
|
|
- Bartholomew French
- 5 years ago
- Views:
Transcription
1 Page 1 of 6 PART 1 - GENERAL 1.1 SUMMARY A. This Section specifies: 1. Voided concrete floor and roof slab system consisting of structural reinforced concrete containing hollow (bubbles) spherical concrete saving elements of various nominal thicknesses and widths; with lifting, supporting, and connecting devices. B. Related Sections include the following: 1. Division 03 Section Cast-in-Place Concrete for site poured concrete and reinforcing. 2. Division 05 Section Structural Steel for steel embed plates, supports, and hangers. 1.2 DEFINITIONS A. Filigree Elements: Precast elements consisting of 2-1/2 inches to 3 inches of filigree concrete, top and bottom wire mesh, and bubbles. 1.3 REFERENCES A. American Concrete Institute (ACI): 1. ACI 237R Self-Consolidating Concrete. 2. ACI Specifications for Structural Concrete. 3. ACI 302.1R Guide to Concrete Floors and Slab Construction. 4. ACI 315 Details and Detailing of Concrete Reinforcement. 5. ACI Building Code Requirements for Structural Concrete and Commentary. 6. ACI 347 Guide Formwork for Concrete. 7. ACI SP.66-ACI Detailing Manual. B. American Society for Testing and Materials (ASTM International): 1. ASTM A108 Specification for Steel Bar, Carbon and Alloy, Cold-Finished 2. ASTM A497 Specification for Steel Welded Wire Reinforcement, Deformed, for Concrete. 3. ASTM A615 - Standard Specification for Deformed and Plain Billet-Steel Bars for Concrete Reinforcement. 4. ASTM A706 Specification for Low-Alloy Steel Deformed and Plains Bars for Concrete Reinforcement. C. American Welding Society (AWS): 1. AWS B2.1 - Specification for Welding Procedure and Performance Qualification. 2. AWS D1.1 - Structural Welding Code - Steel. 3. AWS D1.4 - Structural Welding Code - Reinforcing Steel. D. Precast/Prestressed Concrete Institute (PCI): 1. PCI MNL-116S - Manual for Quality Control for Plants and Production of Precast and Prestressed Concrete Products. 2. PCI MNL PCI Design Handbook - Precast and Prestressed Concrete. E California Building Code (CBC) based on the 2006 International Building Code (IBC 2006) 1.4 PERFORMANCE REQUIREMENTS A. Design voided concrete slabs to withstand imposed loads with limited long-term deflection. 1. Design voided concrete slabs to withstand all dead loads and live loads: a. For Strength Design: Dead load as indicated on drawings, including all topping slabs, curbs, landscaping, superimposed loads, etc. Live load shall be 100 psf minimum unless indicated higher on drawings. b. For Serviceability Considerations (Long-term Deflection): All dead and live loads as indicated on the drawings. 2. Deflection Requirements a. Roof and Floor Slabs: The following load combination shall be used to compare deflection limits: Total long-term deflection (including live load) minus (-) initial dead load (from elastic analysis). 1) L/480 (or ¾ max.) for portions of the slabs that support or are attached to non-structural elements that are likely to be damaged by large deflections including partitions. 2) L/360 (or 1 max.) for portions of the slabs that do not support or are attached to nonstructural elements, or are attached to non-structural elements that are not likely to be damaged by large deflections, including canopies and exterior walkways.
2 Page 2 of 6 B. Additional Structural Design Requirements 1. Slab Design Strength: a. Bending: Flexure design shall be provide so that the compressive stress block does not encroach into the bubble zone. b. Shear: Shear strength of voided slab sections shall be 60% of a solid slab of equivalent thickness. c. Punching Shear: In addition to punching shear at solid slab sections, punching shall be evaluated at the interface of the solid and bubble zones using the reduced shear strength of the voided slab section (60%). 2. Slab Stiffness: a. Flexural stiffness shall be evaluated at 90% of a solid slab of equivalent thickness. b. The cracked moment for the slab shall be evaluated at 80% of that of a solid slab. c. Reduced effective depth shall be considered at the filigree panel joints. 3. Load History: The following load history shall be assumed for the design of the voided slabs: a. Slab shoring shall remain in place for 28 days, so initial loading will not occur until that time. b. A 30-day initial load duration assuming 100% dead load plus 20 psf construction live load. c. A 7-day load duration assuming 100% dead and live loads. d. Long term duration assuming 100% dead load and 50% sustained live loads. 15% of sustained live load may be used for corridors and walkways. 4. Seismic Drift: Voided slab design, including punching shear, shall consider load contribution from seismic inelastic drifts as indicated on Drawings, or provide minimum steel requirements in accordance with ACI. C. Fire Resistance: Provide designs acceptable to code requirements of authorities having jurisdiction to achieve hourly ratings as follows: 1. In accordance with equivalent thickness concept of CBC 2007 Section Cover thickness for reinforced concrete floor or roof slabs in accordance with CBC 2007 table (1). D. Design precast filigree elements to withstand initial and handling stresses. Elements shall withstand all dead loads and live loads: 1. Roof Assembly: Selfweight of voided concrete slab system and a minimum 20 psf construction live load. 2. Floor Assembly: Selfweight of voided concrete slab system and a minimum 20 psf construction live load. E. Camber: Provide camber for all voided slabs as indicated on drawings. F. Slab Restraint: Effects of slab restraint shall be considered in the design analysis. 1.5 SUBMITTALS A. Shop Drawings: Indicate panel layout, panel thickness, layout of lattice girder, layout of top and bottom mesh, side lap bars, bubble layout, layout of control strips, unit identification marks, connection details, edge conditions, bearing requirements, support conditions, dimensions, openings, openings intended to be field cut, and relationship to adjacent materials. B. Layout drawing of field placed negative and punching shear reinforcement. C. Design Data: Indicate calculations for loadings including uniform loads, point loads, and special loadings resulting from openings. Submit complete analysis and design calculations signed and sealed by Structural Engineer licensed in the State of California, including. 1. Strength design. 2. Serviceability considering long-term deflections. 3. Vibration analysis of slabs indicating acceptable vibration performance under normal footfall suitable for higher education classroom use. D. Shop Drawings and Design Data shall be submitted and reviewed by the Engineer and Architect. 1. Upon approval by Engineer and Architect shop drawings shall be submitted for review and approval by the local building jurisdiction. E. Shoring supplier shall coordinate shoring design with voided slab engineer. Shoring and reshoring shop drawings shall be stamped by a professional engineer licensed in the state of California. Voided slab engineer shall review shoring and reshoring calculations and shop drawings.
3 Page 3 of 6 F. Voided slab site poured concrete mix design shall be marked approved by voided slab engineer. G. Voided slab site poured concrete test cylinder results shall be marked approved by voided slab engineer. H. LEED Submittals: 1. Product Data for Credit MR 4: For products having recycled content, documentation indicating percentages by weight of postconsumer and preconsumer recycled content. Include statement indicating cost for each product having recycled content. 2. Product Certificates for Credit MR 5: For products and materials required to comply with requirements for regional materials, certificates indicating location of material manufacturer and point of extraction, harvest, or recovery for each raw material. Include statement indicating distance to Project, cost for each regional material, and fraction by weight that is considered regional. 3. Design Mixtures for Credit ID 1.1: For each concrete mixture containing fly ash as a replacement for portland cement or other portland cement replacements, and for equivalent concrete mixtures that do not contain portland cement replacements. 1.6 QUALITY ASSURANCE A. Design voided concrete slabs and precast filigree panels in accordance with requirements of: 1. ACI ACI 301. B. Sustainable Design Requirements: 1. Recycled Content Materials: Furnish materials with recycled content as indicated in cast in place concrete section. 2. Regional Materials: Furnish materials extracted, processed, and manufactured within 500 miles of Project site, including polyethylene bubbles and precast filigree panels. C. Sample Panels: Before fabricating units, produce a minimum of 2 sample panels approximately 16 sq. ft. in area for review by Architect. Incorporate full-scale details of architectural finishes, textures, panel joints, and transitions in sample panels. 1. Locate panels where indicated or, if not indicated, as directed by Architect. 2. Damage part of an exposed-face surface for each finish, color, and texture, and demonstrate adequacy of repair techniques proposed for repair of surface blemishes. 3. After acceptance of repair technique, maintain one sample panel at manufacturer's plant and one at Project site in an undisturbed condition as a standard for judging the completed Work. 4. Demolish and remove sample panels when directed. 1.7 QUALIFICATIONS A. Fabricator: Precast concrete fabricator shall be certified by the Precast/Prestressed Concrete Institute (PCI) Plant Certification Program. B. Welder: Qualified within previous 12 months in accordance with AWS B2.1. C. Design voided concrete slab and precast filigree panels under direct supervision of Structural Engineer experienced in design of this Work and licensed in State of California. 1.8 PRE-INSTALLATION MEETINGS A. Slab pre-construction meeting: At least 20 days prior to placing first voided concrete slab, Contractor shall hold a meeting to review detailed requirements for preparing final concrete design mixes and to establish procedures for placing, finishing, curing, and protecting concrete to meet required quality under anticipated conditions. B. Contractor shall request responsible representative of each party concerned with concrete work to attend meeting, including but not limited to following: 1. Contractors Superintendent. 2. Testing Laboratory responsible for field quality control. 3. Concrete Subcontractor s Project Manager. 4. Ready-mix Concrete Supplier. 5. Concrete Pumping Equipment Supplier. 6. Resident Project Representative. 7. Voided Concrete Slab Engineer. 8. Structural Engineer of Record. 9. Architect. 10. Owner's Project Representative.
4 Page 4 of 6 C. Discuss anchor and weld plate locations, sleeve locations, and cautions regarding cutting or core drilling. D. Minutes of the meeting shall be recorded, typed, reproduced and distributed by Contractor to all parties concerned within five working days of meeting. E. Minutes shall include a statement by admixture manufacturer (s) indicating that proposed mix design and placing can produce concrete quality required by this Section. F. During construction, additional meetings may be held to review and modify procedures and materials established to assure attainment of high quality level. 1.9 DELIVERY, STORAGE, AND HANDLING A. Division 01 Section Product Requirements for product storage and handling requirements. B. Lifting or Handling Devices: Capable of supporting member in positions anticipated during manufacture, storage, transportation, and erection. C. Precast filigree panels shall achieve adequate strength prior to handling to prevent distortion or warping. D. Number each member to show location according to layout drawings. E. Store all units off ground. F. Separate stacked members by battens across full width of each bearing point. G. Stack so that lifting devices are accessible and undamaged. H. Store so that bubbles are not damaged. PART 2 - PRODUCTS 2.1 VOIDED SLAB SYSTEM SUPPLIERS A. Voided slab system shall be manufactured by BubbleDeck. 2.2 MATERIALS A. Filigree Concrete Materials: Self-consolidating concrete; Compressive strength (28 days) f c = 5000 psi. B. Molds: Rigid, dimensionally stable, non-absorptive material, warp and buckle free, that will provide continuous and true precast concrete surfaces within fabrication tolerances indicated; nonreactive with concrete and suitable for producing required finishes. C. Voided Slab Site Poured Concrete Materials: As specified in Division 03 Section Cast-in-Place Concrete ; the max aggregate size is 3/4 inch diameter for all slabs greater than or equal to 11 inch total slab thickness. The max aggregate size is 3/8 inch diameter for all slabs less than 11 inch total slab thickness. D. Reinforcing Steel: ASTM A615, Grade 60, deformed steel bars, unless otherwise noted on drawings. E. Deformed Welded Wire Reinforcement: ASTM A497, and as follows: 1. WWR Yield Strength: Provide minimum yield strength of 80,000 psi. 2. Wire Spacing and Size: Provide wire spacing and size, as calculated to maintain the specified area of steel as required by performance. F. Bubbles: High density polyethylene, with color as chosen by the manufacturer, with the following properties: 1. Must not react chemically with concrete and all reinforcing steel and welded wire reinforcement. 2. Must be non-porous. 3. Shall be of sufficient strength to carry loads induced by construction activities. 4. Safety characteristics a. Decomposition temperatures > 572 deg F b. Flashpoint > 671 deg F c. Spontaneous ignition temperature > 671 deg F G. Lattice Girders: Bars with the yield strength of 72.5 ksi and tensile strength of 80 ksi consisting of a top chord, a bottom chord, and a diagonal. H. Shear Rail Reinforcement: Plain, ASTM A108, yield strength 50 ksi, tensile strength 60 ksi. 2.3 FABRICATION A. Filigree Precast Panels: Plant cast. B. Fabricate openings required by other sections, at locations indicated.
5 Page 5 of 6 C. Panel manufacturer shall provide for openings 8 inches round, square or larger as indicated on structural drawings. D. All other openings shall be located and field drilled or cut by contractor requiring such work after precast filigree panels have been erected. E. Openings shall be approved by Engineer/Architect and manufacturer before drilling or cutting. F. Finishes: Bottom surface shall be flat and uniform without major chips, spalls, and imperfections. G. Patching: Will be acceptable providing the structural adequacy of the system, as confirmed by the voided slab engineer, is not impaired. H. Plant Finish: Finish members to PCI MNL-116S Finish A Grade. 2.4 FABRICATION TOLERANCES A. Conform to PCI MNL-116S. B. Length of precast filigree elements shall not vary from design dimensions by more than plus or minus 3/16 inch. C. Deviations from straight lines shall not exceed 1/8 inch in 30 feet. D. Precast filigree elements shall not vary by more than plus or minus 1/8 inch from true overall cross sectional shape as measured by difference in diagonal dimensions. 2.5 FINISHES A. Underside of slabs are exposed finished surface. Underside panel faces shall be free of joint marks, grain, and other obvious defects. Corners, including false joints shall be uniform, straight, and sharp. Finish exposed-face surfaces to match approved sample panels and as follows: 1. As-Cast Surface Finish: Provide surfaces free of pockets, sand streaks, and honeycombs. PART 3 - EXECUTION 3.1 PREPARATION A. Prepare support devices for erection procedure and temporary bracing. 3.2 ERECTION A. Install voided slab system in accordance with supplier s requirements. B. Contractor shall be responsible for providing suitable access to the building, proper drainage and firm, level bearing for the hauling and erection equipment to operate under their own power. C. Contractor shall be responsible for providing true, level bearing surfaces on all field placed bearing walls and other field placed supporting members. D. Contractor shall be responsible for placement and accurate alignment of anchor bolts, plates or dowels in columns and walls. E. Erect members without damage to structural capacity, shape, finish, or edges. Replace or repair damaged members. F. Bubbles shall not be significantly damaged during construction activities. Replace or repair all significantly damaged bubbles. G. Align and maintain uniform horizontal intermediate and end joints, as erection progresses. H. Maintain temporary bracing in place until final connections are made. Protect members from staining. I. Adjust differential elevation between precast filigree panels to tolerance before pouring of site concrete. J. After pouring site concrete maintain temporary shoring in place for 28 days. 1. Do not place construction loads on slab for 28 days after pouring days after pouring slab a maximum construction live load of 20 psf may be placed on the slab days after pouring slab a short term construction live load of 50 psf may be placed on the slab lasting no more than 7 days. K. Seal precast joints to prevent concrete leakage when joints between precast filigree panels have not been closely butted.
6 Page 6 of FIELD QUALITY CONTROL A. Voided slab representative and engineer shall visit the job site prior to first slab pour and at appropriate intervals thereafter (minimum of 2 visits) to ensure conformance with design. END OF SECTION
GUIDE SPECIFICATIONS For STRUCTURAL PRECAST HOLLOW CORE SLABS SECTION 03410
GUIDE SPECIFICATIONS For STRUCTURAL PRECAST HOLLOW CORE SLABS SECTION 03410 Note to user: These guide specifications are provided by Mid- States Concrete Products as a service to you; they are NOT specific
More informationSECTION ARCHITECTURAL PRECAST CONCRETE. C. Section Joint Sealers: Perimeter joints with sealant and backing.
SECTION 03451 ARCHITECTURAL PRECAST CONCRETE PART 1 GENERAL 1.01 SECTION INCLUDES A. Architectural precast concrete wall panels; with integral insulation. B. Supports, anchors, and attachments. C. Intermediate
More informationSECTION STRUCTURAL PRECAST HOLLOW CORE SLABS
PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish all labor, materials, equipment and incidentals to provide a complete structural precast hollow core slab system as shown on the Contract
More informationSECTION PRECAST STRUCTURAL PRETENSIONED CONCRETE
PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 03 41 33 PRECAST STRUCTURAL PRETENSIONED CONCRETE SPEC WRITER NOTE: Delete between //--// if not applicable to project. Also delete any other item or paragraph
More informationSECTION STRUCTURAL PRECAST CONCRETE
SECTION 03500 STRUCTURAL PRECAST CONCRETE PART 1 GENERAL 1.01 SUMMARY A. Section Includes. This section covers Prestressed or Precast concrete member construction, including product design not shown on
More informationWHAT IS PRECAST/PRESTRESSED CONCRETE?
PRODUCT LOAD TABLES 1 WHAT IS PRECAST/PRESTRESSED CONCRETE? PRECAST/PRESTRESSED CONCRETE is an architectural and structural material possessing great strength. Specifically, PRESTRESSED CONCRETE has unique
More informationSECTION PRECAST CONCRETE COVER SYSTEM
SECTION 13500 PRECAST CONCRETE COVER SYSTEM PART 1 GENERAL 1.1 SYSTEM DESCRIPTION A. Design Criteria: 1. Precast manufacturer shall be responsible for structural design of individual precast components,
More informationSECTION ARCHITECTURAL PRECAST CONCRETE. A. American Society for Testing and Materials (ASTM):
SECTION 03450 ARCHITECTURAL PRECAST CONCRETE PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 03100 - Concrete Formwork 2. 03200 - Concrete Reinforcement 3. 03300 - Cast-in-Place Concrete 4. 03600 -
More information1. Cast-in-place concrete is specified in Section
SECTION 03 38 00 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section describes the requirements for furnishing and installing post-tensioned slabs, jacks, jacking and anchors at Parking Structure, and record
More information***************************************************************************************************************
03450 ARCHITECTURAL PRECAST CONCRETE *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 03 45 13 ***************************************************************************************************************
More informationADDENDUM NUMBER 3 AUGUST 18, Jackson County Utility Authority Project No Pascagoula/Moss Point WWTP Escatawpa WWTP Repairs
ADDENDUM NUMBER 3 AUGUST 18, 2016 Jackson County Utility Authority Project No. 20150619124 Pascagoula/Moss Point WWTP Escatawpa WWTP Repairs FROM: BURK-KLEINPETER, INC. ENGINEERS, ARCHITECTS, PLANNERS,
More informationSTRUCTURAL PRECAST CONCRETE
SECTION 03410 STRUCTURAL PRECAST CONCRETE PART 1 GENERAL 1.01 SUMMARY A. Provide labor, materials, necessary equipment, services and included, but not limited to, related work to complete the structural
More informationSECTION EMBEDDED CMU/SPLIT FACE ARCHITECTURAL PRECAST/SITECAST CONCRETE. A. Site Cast or Tilt-Up CMU/Split Face Concrete Panels.
SECTION 03460 EMBEDDED CMU/SPLIT FACE ARCHITECTURAL PRECAST/SITECAST CONCRETE PART 1 GENERAL 1.1 SECTION INCLUDES A. Site Cast or Tilt-Up CMU/Split Face Concrete Panels. B. Shop/Plant Cast CMU/Split Face
More informationSECTION BRICK FACED ARCHITECTURAL PRECAST CONCRETE. A. Section Cast-In-Place Concrete: Concrete, reinforcing, anchors, etc.
SECTION 03460 BRICK FACED ARCHITECTURAL PRECAST CONCRETE PART 1 GENERAL 1.1 SECTION INCLUDES A. Site Cast (Tilt-Up) Brick Faced Concrete Panels. B. Plant Cast (Precast) Brick Faced Concrete Panels. 1.2
More informationPRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS
PRODUCTION SPECIFICATIONS SECTION 03135 INSULATED CONCRETE FORMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulated panel permanent concrete form system for: 1. Exterior structural wall panels. 2. Interior
More informationPRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS
PRODUCTION SPECIFICATIONS SECTION 03135 INSULATED CONCRETE FORMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulated panel permanent concrete form system for: 1. Exterior structural wall panels. 2. Interior
More informationA. Section includes cast-in-place concrete, including reinforcement, concrete materials, mixture design, placement procedures, and finishes.
SECTION 033053 - CONCRETE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More information1. Cast-in place structural concrete including footers, foundations, and other non-slab applications. 2. Formwork 3. Reinforcement
SECTION 03 31 00 - CAST-IN-PLACE STRUCTURAL CONCRETE PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Cast-in place structural concrete including footers, foundations, and other non-slab applications.
More informationSECTION MISCELLANEOUS CAST-IN-PLACE CONCRETE
SECTION 033053- MISCELLANEOUS CAST-IN-PLACE CONCRETE PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationSPECIAL SPECIFICATION 2043 Brick Veneer on MSE Wall
2004 Specifications CSJ 0196-02-120 SPECIAL SPECIFICATION 2043 Brick Veneer on MSE Wall 1. Description. This Item shall govern for the furnishing of the materials and construction of brick veneers on abutment
More informationCONCRETE TECHNOLOGY CORPORATION
PRECAST, PRESTRESSED HOLLOW CORE SLABS DESIGN CRITERIA & SPAN-LOAD CHARTS Introduction 2 Design Criteria for Development of the Span-Load Charts 2 Related Publications 3 Manufacturing Tolerances 4 8" Bare
More informationAnchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel ASTM A36, Fy = 36 ksi
STRUCTURAL NOTES MATERIAL STRENGTHS Structural Steel Reinforcing Steel Concrete Masonry Structural Lumber Anchor bolts ASTM F1554, Gr. 36 Wide flange beams ASTM A992, Fy = 50 ksi Misc. structural steel
More informationDIVISION 03 CONCRETE SPECIFICATION : FORMS AND FORMWORK
DIVISION 03 CONCRETE SPECIFICATION 031000: FORMS AND FORMWORK PART 1.0 GENERAL 1.1 DESCRIPTION The work of this specification includes furnishing of all labor, materials, equipment and incidentals to install,
More information***************************************************************************************************************
03410 STRUCTURAL PRECAST CONCRETE *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 03 41 00 ***************************************************************************************************************
More informationSECTION FABRICATED ENGINEERED STRUCTURES. A. Pre-engineered, shop-fabricated structural steel building with formed purlin framing.
PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 13 34 00 FABRICATED ENGINEERED STRUCTURES A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
More informationREINFORCED CONCRETE MASONRY SECTION
SECTION 04 22 02 - REINFORCED CONCRETE MASONRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 01 Specification
More informationTILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following:
PART 1 GENERAL 1.01 SUMMARY SECTION 03460 TILT-UP PRECAST CONCRETE SANDWICH PANELS A. Work includes, but is not limited to, the following: 1. Architectural precast concrete sandwich wall panels. 2. Integral
More informationSTRUCTURAL STEEL FRAMING
SECTION 05 12 00 - STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Section includes 1. Structural steel framing 2. Structural steel framing required for support and framing of rooftop mechanical
More informationTCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II
SECTION 052100 - STEEL JOISTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections
More informationThe Contractor is responsible for quality control, including workmanship and materials furnished by his subcontractors and suppliers.
SECTION 05 31 13 STEEL FLOOR DECKING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 01 - Specification
More informationPreassembled steel stairs with concrete-filled treads.
SECTION 055113 - PART 1 - GENERAL 1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this
More informationSECTION TILT-UP PRECAST CONCRETE SANDWICH PANELS. A. Work includes, but is not limited to, the following:
PART 1 GENERAL 1.01 SUMMARY SECTION 03460 TILT-UP PRECAST CONCRETE SANDWICH PANELS A. Work includes, but is not limited to, the following: 1. Architectural precast concrete sandwich wall panels. 2. Integral
More informationUPRR INDUSTRIAL LEAD BRIDGE T-WALL RETAINING WALL SYSTEM 5.0 x 7.5 UNITS DESIGN UNIT 018 WORK PACKAGE 04
UPRR INDUSTRIAL LEAD BRIDGE T-WALL RETAINING WALL SYSTEM 5.0 x 7.5 UNITS DESIGN UNIT 018 WORK PACKAGE 04 1. Description This work shall consist of the design, manufacture and construction of a T-WALL structure
More informationStructural Design Engineers 120 Montgomery Street, Suite 1410 San Francisco, California / Fax 415/
120 Montgomery Street, Suite 1410 San Francisco, California 94104 415/781-1505 Fax 415/781-2718 sde@sdesf.com Rajendra Sahai, SE Principal John W. Laws, SE Principal Steven Lepisto, SE Principal STRUCTURAL
More informationSECTION FIBERGLASS REINFORCED POLYMER (FRP) PANELS
SECTION 07 44 50 FIBERGLASS REINFORCED POLYMER (FRP) PANELS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Design, Engineering, manufacturing and erection of fiberglass reinforced panels. Delegated Design of
More informationSECTION PLATE CONNECTED WOOD TRUSSES
SECTION 06173 PLATE CONNECTED WOOD TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Shop fabricated wood trusses for roof and floor framing. 2. Bridging, bracing, and anchorage. B. Related Sections:
More information1. Base plates, setting plates and anchor rods for columns. 8. Lintels if connected to structural steel columns.
PAGE 051200-1 SECTION 051200 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification sections,
More informationSPECIAL SPECIFICATION 4584 Segmental Concrete Bridge Unit
2004 Specifications CSJ: 0028-09-111 SPECIAL SPECIFICATION 4584 Segmental Concrete Bridge Unit 1. Description. Construct cast-in-place segmental concrete box girder superstructure according to the plans,
More informationNarrow Modular Pavers (NMP) for Sand-Set Installations
The following specification refers to the Stepstone, Inc. product known as: Narrow Modular Pavers (NMP) for Sand-Set Installations Narrow Modular Pavers are part of the California Architectural Paver line
More informationSECTION UNIT MASONRY
SECTION 04200 UNIT MASONRY PART 1 GENERAL 1.01 SUMMARY A. Furnish labor, materials, and equipment and perform functions required in the installation and maintenance of the work covered by this Section.
More informationSECTION COLD-FORMED METAL TRUSSES
SECTION 054400 COLD-FORMED METAL TRUSSES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More information***************************************************************************************************************
03365 POST-TENSIONED CONCRETE *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 03 38 00. ***************************************************************************************************************
More informationSECTION BRICK FACED ARCHITECTURAL PRECAST CONCRETE. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.
SECTION 03460 BRICK FACED ARCHITECTURAL PRECAST CONCRETE Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Site Cast or Tilt-Up Brick
More informationSECTION CONCRETE FORMWORK
SECTION 03100 CONCRETE FORMWORK PART 1 GENERAL 1.1 REFERENCES A. The following is a list of standards which may be referenced in this section: 1. American Concrete Institute (ACI): a. 117, Standard Specifications
More information- PRECAST CONCRETE POTABLE WATER STORAGE TANKS
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2
More informationDesign Reference Sample: Sample of approved precast structural concrete color, finish, and texture, preapproved by Architect.
SECTION 034100 - PART 1 - GENERAL 1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this
More informationSECTION NON--STRUCTURAL METAL FRAMING
The Collective Voice of America s Steel Framing Industry The Steel Framing Industry Association (SFIA) is dedicated to expanding the market for cold-formed steel in construction through programs and initiatives
More informationUniversity of Delaware
University Contact: Energy & Engineering Group (302) 831-1744 SECTION 03 45 00_PRECAST CONCRETE STRUCTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including
More informationA. The extent of extruded aluminum walkway covers is shown on the Drawings and as specified herein.
SECTION 10530 - EXTRUDED ALUMINUM WALKWAY COVERS PART I - GENERAL.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General, Supplementary, and Special Conditions and Division
More informationSECTION RIGID PAVEMENT
SECTION 02750 PART 1 GENERAL RIGID PAVEMENT 1.1 SUMMARY A. Section Includes: 1. Concrete sidewalks. 2. Concrete stair steps. 3. Concrete integral curbs gutters. 4. Concrete parking areas and roads. B.
More informationCSU GUIDELINES. April 27, 2018 FOR POST-TENSIONED CONCRETE STRUCTURES.
CSU GUIDELINES FOR POST-TENSIONED CONCRETE STRUCTURES April 27, 2018 http://www.calstate.edu/cpdc/ae California State University Seismic Review Board Technical Guidelines January 9, 2018 The CSU Seismic
More informationSECTION PRE-ENGINEERED COLD-FORMED METAL ROOF AND FLOOR TRUSSES
SECTION 05440- PRE-ENGINEERED COLD-FORMED METAL ROOF AND FLOOR TRUSSES PART 1 GENERAL 1.01 SUMMARY A. Section includes pre-engineered, pre-fabricated cold formed steel framing elements. Work includes:
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-03 11 13.00 10 (May 2014) --------------------------------- Preparing Activity: USACE Superseding UFGS-03 11 13.00 10 (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationSECTION (05300) - STEEL DECKING
SECTION 05 31 00 (05300) - STEEL DECKING PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Roof Deck 2. Composite Floor Deck 3. Noncomposite Form Deck B. Related Sections: 1.02 SUBMITTALS 1. Section
More informationProject Address: Name of Person Completing Form:
Statement of Inspections This form is provided as a way to list aspects of the project that require special inspection and testing in accordance with IBC Sections 107.1, 1704, and 1705 and define duties
More informationSPECIFICATIONS: Architectural Aluminum Railings
PART ONE: GENERAL 1.1 SUMMARY SPECIFICATIONS: Architectural Aluminum Railings A. Work in this section includes custom and standard Interior and Exterior aluminum railings and guardrails. 1.2 PERFORMANCE
More informationSECTION HANDRAILS AND RAILINGS. A. Section Cast-In-Place Concrete; coordination with substrate.
SECTION 05520 HANDRAILS AND RAILINGS PART 1 GENERAL 1.1 SECTION INCLUDES A. Welded stainless steel railing systems. 1.2 RELATED SECTIONS A. Section 03300 - Cast-In-Place Concrete; coordination with substrate.
More informationPART 1 / GENERAL SECTION ALUMINUM PLATE PANEL SYSTEM. ALPLY Insulated Panels. Alply TECH WALL Aluminum Plate System 2002
SECTION 07 42 13 ALUMINUM PLATE PANEL SYSTEM ALPLY Insulated Panels Alply TECH WALL Aluminum Plate System 2002 PART 1 / GENERAL 1.1 SYSTEM DESCRIPTION A. Preformed Aluminum Plate System for Screen wall
More informationMulti-Institutional Academic Health Science & Research Center Evansville, IN
SECTION 05 5117 ALTERNATING TREAD STEEL STAIRS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationA. Product Data: For each type of cold-formed steel framing product and accessory.
SECTION 05400 - COLD-FORMED METAL FRAMING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Exterior non-load-bearing wall framing. 1.2 ACTION SUBMITTALS A. Product Data: For each type of cold-formed
More informationDESIGN INFORMATION WAFFLE-CRETE. FOR MORE INFORMATION, WRITE OR CALL International, Inc.
WAFFLE-CRETE DESIGN INFORMATION STRUCTURAL PRECAST PRECAST CONCRETE CONCRETE BUILDING BUILDING SYSTEMS SYSTEMS FOR MORE INFORMATION, WRITE OR CALL WAFFLE-CRETE International, Inc. P.O. BOX 1008 Hays, Kansas
More informationSECTION COLD-FORMED METAL FRAMING
The Collective Voice of America s Steel Framing Industry The Steel Framing Industry Association (SFIA) is dedicated to expanding the market for cold-formed steel in construction through programs and initiatives
More informationPASSAIC COUNTY TECHNICAL INSTITUTE CCA 1422 NEW S.T.E.M. BUILDING 2017
SECTION 053100 STEEL DECKING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 096623 - RESINOUS MATRIX TERRAZZO FLOORING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSECTION PRECAST STRUCTURAL PRETENSIONED CONCRETE
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 03 41 33 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // -- // if not applicable to project. Also delete any other item or paragraph
More informationSECTION 1 TERMS, DEFINITIONS, ABBREVIATIONS, UNITS OF MEASURE, AND SYMBOLS 1-3 ABBREVIATIONS Common Usage.
SECTION 1 TERMS, DEFINITIONS, ABBREVIATIONS, UNITS OF MEASURE, AND SYMBOLS 1-3 ABBREVIATIONS. 1-3.2 Common Usage. Abbreviations Word or Words PAV.Pressure Aging Vessel PCC..Portland Cement Concrete PE.Polyethylene
More informationSECTION CAST-IN-PLACE CONCRETE
PART 1 - GENERAL 1.01 RELATED DOCUMENTS SECTION 03300 - A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 requirements are applicable to
More informationSECTION GLASS-FIBER-REINFORCED PRECAST CONCRETE
SECTION 03490 GLASS-FIBER-REINFORCED PRECAST CONCRETE PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSummary of Modifications/Changes in this Update
Summary of Modifications/Changes in this Update This Summary of Changes is for information only. It is not a part of the referenced document, and should not be used for project documentation. U.S. Department
More informationG. Shop drawing of wall with all dimensions, details, and finishes. Drawings must include post foundations.
DURA-CRETE S-SERIES PRECAST CONCRETE WALL SPECIFICATIONS PART 1 GENERAL 1.01 SECTION INCLUDES A. Concrete Screen Wall Description: Work under this item shall consist of furnishing and erecting a wall in
More informationSPECIAL INSPECTION AGREEMENT
PART 1 STATEMENT OF SPECIAL INSPECTIONS When special inspection is required to be performed in accordance with International Building Code Chapter 17, a building permit cannot be issued until a statement
More informationNITTERHOUSE CONCRETE PRODUCTS, INC Molly Pitcher Highway South Chambersburg, PA
NITTERHOUSE CONCRETE PRODUCTS, INC. 2655 Molly Pitcher Highway South Chambersburg, PA 17201 717-267-4505 GUIDE SPECIFICATION FOR PRECAST PARKING STRUCTURES INDEX Page PART I - GENERAL...1 A. SECTION INCLUDES...1
More informationST. JOHNS COUNTY ARCH. PROJ. NO SECTION PREFABRICATED ALUMINUM CANOPIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 10530 PREFABRICATED ALUMINUM CANOPIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION ARCHITECTURAL CAST STONE
PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 047200 ARCHITECTURAL CAST STONE A. RELATED DRAWINGS All drawings, to include supplemental drawings, instructions and conditions of this contract. B. RELATED
More informationThis section applies to the design and installation of cast-in-place concrete, shotcrete, precast concrete, and post-tensioned concrete.
Basis of Design This section applies to the design and installation of cast-in-place concrete, shotcrete, precast concrete, and post-tensioned concrete. Design Criteria Use most recent version of the International
More informationSECTION (16071) - VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
SECTION 26 05 48 (16071) - VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. This Section includes seismic restraints and other earthquake-damage-reduction measures for
More informationDIVISION 5 METALS SECTION METAL DECKING
DIVISION 5 METALS SECTION 05 30 00 PART 1 GENERAL 1.01 SUMMARY A. Section Includes: All labor and materials required to furnish and install metal decking and accessories including shear connectors, closures,
More informationStudent Services & Classroom Addition
SECTION 055113 - METAL PAN STAIRS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION METAL STAIRS
SECTION 05 51 00 METAL STAIRS PART 1 GENERAL 1.1 SUMMARY A. Section includes steel stair frame of structural sections, with closed risers; pan to receive concrete fill stair treads and landings; integral
More informationStructural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)
Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction
More informationGUIDE SPECIFICATION FOR CARBONCAST WALL PANELS SECTION 03450
GUIDE SPECIFICATION FOR CARBONCAST WALL PANELS SECTION 03450 PART 1 - GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY A. This Section includes CarbonCast precast concrete wall panel units, including manufacture,
More informationSECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
SECTION 260548 - VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Isolation pads. 2. Spring isolators. 3. Restrained spring isolators. 4. Channel
More informationSPECIFICATIONS PRECAST PRESTRESSED CONCRETE PART 1 GENERAL 1.6.2.5 Openings, inserts and related reinforcement 1.6.3 Each drawing submitted to bear stamp of 1.1 Related Work qualified Professional Engineer
More informationStatement of Special Inspection Requirements
Statement of Special Inspection Requirements California Building Code Chapter 17 Construction plans shall include a statement of special inspection in accordance with CBC chapter 17. The statement of special
More informationPro-Con Structural Study for Alternative Floor Systems October 27, 2004
Ismail Al-Hadhrami Structural Option Faculty Consultant: Dr. Thomas Boothby Agricultural Hall and Annex East Lansing, MI Pro-Con Structural Study for Alternative Floor Systems October 27, 2004 Executive
More informationDivision 03 - Concrete Section New Westminister Multi-Use Civic Facility & Office Building Project No Page 1
Project No. 210022 Page 1 PART 1 GENERAL 1.7 Documents.1 The General Conditions of the Canadian Standard Construction Document CCDC-2, together with all amendments and supplements and Division 1 General
More informationK. ASTM F436- Standard Specification for Hardened Steel Washers; 2011.
DIVISION 05 METALS 05 12 00 STRUCTURAL STEEL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Structural steel framing members, support members. 1.2 RELATED REQUIREMENTS A. Section 05 50 00 - Metal Fabrications:
More informationThermalShell Modular Insulated Pre-Cast Panels
412 N. California St. Building #2 Sycamore IL, 60178 Phone: 815.899.0224 Fax: 815.899.0226 E-mail: info@thermalshell.com Web: www.thermalshell.com ThermalShell Modular Insulated Pre-Cast Panels Construction
More informationSECTION VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT
SECTION 230548 - VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary
More informationSECTION CAST-IN-PLACE CONCRETE
SECTION 03300 CAST-IN-PLACE CONCRETE PART 1 GENERAL 1.01 SECTION INCLUDES A. The Contractor shall furnish all work and materials, including cement, sand and coarse aggregate, water, admixtures, curing
More informationTHE FORENSIC MEDICAL CENTER
THE FORENSIC MEDICAL CENTER Image courtesy of Gaudreau, Inc. TECHNICAL REPORT #2 OCTOBER 26, 2007 KEENAN YOHE STRUCTURAL OPTION DR. MEMARI FACULTY ADVISOR EXECUTIVE SUMMARY Image courtesy of Gaudreau,
More informationSPECIFICATION FOR PRECAST/ COMPOSITE CONCRETE FLOORS/ ROOF DECKS SECTION E60
SPECIFICATION FOR SECTION E60 A 2007-09-26 S.W. Revision Date Issue Authorised By Approved for Issue SW Date 24.09.07 clarkebond Page 1 of 6 To be read with Preliminaries/ General Conditions. GENERAL 10
More informationEndicott Mbrick Thinbrick Color Burgundy Sands
Endicott Mbrick Thinbrick Color Burgundy Sands Innovative Brick Systems, LLC 11625 Reed Ct. Broomfield, CO 80020 Phone: (800) 413-4588 Phone: (720) 890-6032 Fax: (720) 890-6038 Info@mbrick.com www.mbrick.com
More informationCONCRETE FORMWORK. .2 CSA , Supplement No.1 to CAN/CSA , Engineering Design in Wood. .4 CSA O151, Canadian Softwood Plywood.
CITY OF BRAMPTON LANDSCAPE SPECIFICATIONS SECTION 03100-1 PART 1 GENERAL 1.1 Related Work.1 All Division 1 Specification Sections.2 Section 02233 Granular Base.3 Section 02311 Site Grading.4 Section 03200
More informationHome Depot Page 1 of 5 HDPB Humacao, PR 10/19/09
PART 1 - GENERAL 1.01 SUMMARY A. Types of cold-formed metal framing units include the following: 1. C-shaped steel studs B. Related work specified elsewhere includes but may not be limited to: 1. Section
More informationWACEL STUDY GUIDE. Reinforced Concrete Special Inspector (Concrete II)
WACEL STUDY GUIDE Reinforced Concrete Special Inspector (Concrete II) June 2017 Concrete II Study Guide Examination: The Concrete II examination is based on the references cited in this document. It is
More informationSECTION METAL STAIRS
SECTION 05510 METAL STAIRS PART 1 GENERAL 1.01 SECTION INCLUDES A. Stairs with concrete treads. B. Stairs with metal treads. C. Structural steel stair framing and supports. D. Handrails and guards. 1.02
More informationLITHOCRETE ARCHITECTURAL CONCRETE PAVING
LITHOCRETE ARCHITECTURAL CONCRETE PAVING PART 1 GENERAL 1.1 GENERAL CONDITIONS A. Requirements of "General Conditions of the Contract" and of Division 1, "General Requirements," apply to work in this Section
More informationSECTION US Patent 8,857,130 B1 CAST-IN-PLACE CONCRETE WITH ARDEX CONCRETE MANAGEMENT SYSTEMS (ACMS ) EARLY MC APPLICATION
ARDEX GUIDE SPECIFICATION ARDEX CONCRETE MANAGEMENT SYSTEMS (ACMS ) Cast-In-Place Concrete to Receive the ARDEX Concrete Management Systems including ARDEX Self-Leveling Underlayments SECTION 03 30 00
More informationSECTION CAST IN PLACE CONCRETE PART 1 GENERAL 1.01 RELATED DOCUMENTS
SECTION 03301 - CAST IN PLACE CONCRETE PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More information