SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS:
|
|
- Nickolas Wilkinson
- 5 years ago
- Views:
Transcription
1 SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - [THIS TENDER IS FOR PURCHASE OF HT (11KV) PIN INSULATORS ONLY] 1. SCOPE: - This specification covers 11KV Disc Type & 11KV / 22KV Pin Type Insulators for 11/22KV H.T. over head power lines. 2. APPLICABLE STANDARDS: - Except when they conflict with specific requirement in this specification, the insulators shall comply with the Indian Standard specification, IS-731/1971and the latest version thereof. The insulators fittings shall comply with the Indian Standard specification IS-2486/Part-I/1993, IS-2486/Part. II/1989 or the latest version thereof. 3. DESCRIPTION: DISC INSULATORS. :- 11KV Brown Glazed 'Disc' insulators conforming to IS-731/71 and subsequent amendment No. 1 to 5 for suspension or tension strings, ball and socket type having ball shank dia.16mm and minimum failing load of 70 KN along with phospher bronze 'W' clips. 3.2 PIN INSULATORS:- 11/22KV Brown Glazed pin insulators confirming to IS-731/1971 and subsequent amendment No.1 to 5 to give rigid support to an over-head line and intended to be mounted vertically on supporting structure by GI Pin passing up inside this insulator with minimum failing loads 10 KN. 4. GENERAL REQUIREMENT: - i) The porcelain shall be sound and free from defects, thoroughly vitrified and smoothly glazed. ii) The glaze shall be brown in colour. The glaze shall cover all the porcelain parts of the insulator except those areas which serve as support during fixing or are left unglazed for the Purpose of assembly. iii) The design of the insulators shall be such that stresses due to expansion and contraction in any part of the insulator shall not lead to deterioration. The porcelain shall not engage directly with hard metal. iv) Cement used in the construction of the insulators shall not cause fracture by expansion or lessen by contraction and proper care shall be taken to locate the individual parts correctly during cementing. The cement shall not give rise to chemical reaction with metal fitting and its thickness shall be as uniform as possible. 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS : - The electrical and mechanical particulars of 11KV Disc and 11/22KV Pin insulators shall be as per the Guaranteed Technical Particulars shown in Annexure-A & B attached herewith, measured at the following standard atmospheric conditions. 1. Ambient temperature 20 Deg. C 2. Barometric pressure 1013 millibars 11 Grams of water per cubic mtrs. 3. Absolute Humidity Corresponding to 63% relative humidity at 20 Deg. C. [Technical Specification and GTP of 11 KV Pin and Disc Insulators: Ceramic//Page 1 of 7]
2 6. BASIC INSULATION LEVELS: The test voltage of Disc. And Pin insulators shall be as per the values given in Guaranteed Technical Particulars shown in Annexure-A & attached. 6.2 In this specification power frequency voltages are expressed as peak values divided by 2 and impulse voltages are expressed as peak values. 6.3 The withstand flashover voltages are referred to the reference atmospheric conditions. 7. Ferrous parts of Disc. Insulators as per IS-2108/1977 shall be hot dip galvanized as per IS-2633/ As the insulators are to be used anywhere in Gujarat State including the coastal area, the Creepage distances of specified in GTP are minimum. However, the firm may offer insulators of higher creepage distance, but the mechanical and electrical parameters of their product shall be as per the mechanical and electrical requirement given in Appendix-A & B attached. 9. TESTS: - i) All the tenderers must submit copies of type test certificates along with laboratory approved drawings for the products offered by them. The Certificates shall be from CPRI, ERDA, and Indian Institute of Science, Bangalore or any other Govt. recognized laboratory, but not more than 5 years old as on date of opening the tender. ii) Copy of type test certificate of each type offered must be submitted. iii) The type test certificate shall be final and complete for all the tests as per the list of type tests given in specification Cl.No.9.1of the specification. iv) Failure to submit the type test certificates as described above shall be liable for rejection of tender offer. v) Routine test shall be carried out on every insulator as specified in IS-731/71 with amendment No.1 to 5 and certificate issued with each batch. Details of test result on each of the insulator supplied, has to be submitted to inspector for his perusal and verification. vi) The insulators shall comply with the type tests as per IS-731/1971with latest amendment 1 to 5 and as mentioned in Cl.No.9.1 below. 9.1 TYPE TESTS: - The following shall constitute the type tests (Cl.No of IS-731/1971). However, the test voltage value shall be as per GTP enclosed. a) Visual examination. b) Verification of dimensions. c) Visible discharge test. d) Impulse voltage withstand test (+ve wave & -ve wave) e) Impulse voltage flashover test (+ve wave & -ve wave) f) Dry and wet power frequency voltage withstands test. g) Dry and wet power frequency flashover voltage test. h) Temperature Cycle test. i) 24 Hours mechanical failing load test (for Disc insulators only) or mechanical performance test. j) Electro mechanical failing load test (for Disc insulators only) k) Mechanical failing load test (for Pin insulators only) [Technical Specification and GTP of 11 KV Pin and Disc Insulators: Ceramic//Page 2 of 7]
3 l) Puncture test. m) Porosity test. n) Galvanizing test (for Disc Insulators only) The tests shall be carried out on the two samples in the order mentioned in the Cl of IS-731/1971. All the tests shall be carried out in the same laboratory ACCEPTANCE TESTS: - From the offered lot, samples shall be drawn randomly as per the criteria given. The firm has to arrange for carrying out all following acceptance tests at firms works only at firm's cost in presence of inspector deputed by MGVCL. a) Verification of dimensions and Visual examination. b) Temperature cycle tests. c) 24 Hours mechanical failing load test or mechanical performance test. (For disc. insulators only) d) Electro mechanical failing load test (for disc. insulators only) e) Mechanical failing load test (for pin insulators only) f) Puncture test. g) Porosity test. h) Galvanizing test (for disc. insulators only) 9.3. ROUTINE TESTS: - The following tests shall be carried out as routine tests by firm on each insulator before offering the lot for inspection. a) Visual examination. b) Mechanical routine test (for type 'B' string insulators units only) c) Electrical routine test (for type 'B' string insulators and rigid insulators). 10. DRAWING AND CATALOGUES: - The tenderer shall furnish catalogues, literature and detailed dimensional drawing of insulators offered showing section of the insulators to show the method of construction connecting arrangement, length and type of threads etc. The drawing shall be got approved by the User Department prior to commencing the bulk supply. 11. MARKING: Each insulator shall be legibly and indelibly marked to show the following. a) Name or trade mark of the manufacturer. b) Month and year of manufacturer. c) Minimum failing load. d) Country of manufacture. e) ISI Certification mark, if any. f) Word 'MGVCL' marked stickers to be provided on each insulator Marking on porcelain shall be printed and shall be applied before firing. [Technical Specification and GTP of 11 KV Pin and Disc Insulators: Ceramic//Page 3 of 7]
4 12. PACKING:- i) All insulators (without fittings) shall be packed in wooden crates suitable for easy but rough handling suitable for rail/road transport. Where more than one insulator is packed in a crate, wooden separators shall be fixed between the insulators to keep individual insulator in position, without movement within the crates. Disc. Insulators however, may be assembled in a string and then packed inside a crate, in above fashion. ii) The wooden crates shall be provided with steel hoop and bends for strength and durability to withstand rough handling. The bends shall have descriptive marking of the firm thereon. iii) The firm shall provide at his cost, lead seal and wire on each wooden crate to facilitate sealing by the inspector of MGVCL after acceptance of the lot. 13. INSPECTION: - Party has to offer the materials for inspection duly packed in crates as mentioned in GTP. The inspection approval is valid for a period of 15 days from the date of inspection to enable the firm to dispatch the materials by arranging transportation at destination allotted thereof within the said period. After this period of 15 days, the validity of the inspection will lapse. Thereafter, the inspection approval will be revalidated by competent authority on furnishing written application explaining therein the valid reasons for delay in affecting dispatches. 14. The firm shall not dispatch the offered lot unless the same is inspected by the inspector of MGVCL & accepted by him after passing in all acceptance tests, and/or receipt of waival of inspection in writing from competent authority of MGVCL. Manufacturer's Name and Address. [Technical Specification and GTP of 11 KV Pin and Disc Insulators: Ceramic//Page 4 of 7]
5 Schedule for requirement of 11/22KV Pin & Disc Insulators Sr. No Description of materials 11KV Pin Insulators Brown Glazed porcelain Insulator confirming to IS-731/1971 Ammendment 1 to 5 Type-B with 320mm minimum creepage distance and with lead/zinc thimble suitable for use with G.I.Forged pin having small steel heads as per IS-2486 (P.I)/1993 & IS-2486 (P.II)/1989 and revision with latest ammendment if any. - Confirming to REC Specification. - With minimum failing load of 10 KN. -Confirming to MGVCL specification attached herewith. 11KV Disc Insulators Brown Glazed porcelain Insulator confirming to IS-731/1971 and subsequent amendment 1 to 5 for suspension and tension strings ball and socket type having pin ball. The minimum creepage distance shall be 320 mm. shank dia of 16 mm and minimum failing load of 7140 Kgs (70 KN) confirming to Board's specification attached herewith. The insulators shall have 'W' type phospher Bronze security clips for ball sockets portion of insulators confirming to IS-2486 (P-III/1974). The insulators shall also confirm to MGVCL specifications attached herewith. 22KV Pin Insulators Brown Glazed porcelain Pin Insulators confirming to IS-731/1971 Ammendment 1 to 5 Type-B with 560mm minimum creepage distance and with lead/zinc thimble suitable for use with G.I.Forged pin having large steel head as per IS-2486 (P.I)/1993 & IS-2486 (P.II)/1989- second revision and conforming REC specification. Quantity required. Type Test:- 1. The offers without type test certificate and certified drawing by Government approved laboratory will not be considered. 2. Party should submit his own design drawing with all dimensional details to be supported by type test certificate and attested drawings. [Technical Specification and GTP of 11 KV Pin and Disc Insulators: Ceramic//Page 5 of 7]
6 Manufacturer's Name and Address: MGVCL/MM/1023/11 KV Pin Insulators: Porcelain/ ANNEXURE-'A' TECHNICAL INFORMATION AND GUARANTEED TECHNICAL PARTICULARS: PART-A BIDDER HAS TO CONFIRM FOLLOWING IMPORTANT REQUIREMENT: Sr. No. Particulars 11KV Pin Insulator 11KV Disc. Insulator 1 Insulator shall be manufactured as per IS-731/1971 and subsequent amendment 1 to 5 or latest amendment of it. 2 Brown colour glazed 3 320mm (Min) creepage distance. 4 Mechanical failing load (Min) i) 10 KN (1020KG for Pin Insulator) ii) 70KN (7140KG for Disc. Insulator) Lead/Zinc thimble suitable for fixing with 11KV G.I. Pin as per IS-2486 (Part-I)/1993 & IS-2486 (Part-II)/1989 with latest amendment (small steel head) -- 6 Melleable cast iron as per IS-2108/1977 & hot dip galvanized socket as per IS-2633/ High tensile forged steel hardened and tampered duly hot dip galvanized BALL Pin Phospher bronze 'W' clips -- 9 Ball & Socket size 16mm Impulse withstands test voltage. a) 1.2/50 micro sec. +ve wave KV b) 1.2/50 Micro sec. ve Wave KV Impulse flashover test voltage. a) 1.2/50 micro sec. +ve wave KV b) 1.2/50 Micro sec. -ve Wave KV. Power frequency withstand test voltage a) Dry - 70 KV b) Wet - 45 KV Power frequency flashover test voltage. a) Dry - 80 KV b) Wet -50 KV Power frequency puncture voltage KV. [Technical Specification and GTP of 11 KV Pin and Disc Insulators: Ceramic//Page 6 of 7]
7 15 Visible discharge -9KV voltage. 16 Marking on Insulator as per Clause No and 12.2 of MGVCL Specification. Insulator shall be packed in wooden crates as 17 per Cl.No.13 (i), 13(ii) & 13 (iii) of MGVCL Specification. PART-'B': (Both for 11KV Pin Insulator & 11KV Disc. Insulator) BIDDER HAS TO FURNISH BELOW DETAILS ABOUT MATERIAL. 1. No. Of Insulator to be Packed in one crate. a) For 11KV Pin Insulator: b) For 11KV Disc Insulator: 2. Drawing Number/Product Number. a) For 11KV Pin Insulator: b) For 11KV Disc Insulator. PART-'C': ENCLOSURES: (Both for 11KV Pin Insulator and 11KV Disc. Insulator) Bidder has to enclose following documents and has to confirm for the same. Sr.N o. Particulars Confirmation 1. Drawing with detailed dimension duly signed & stamped 2 Type test certificate covering all the tests as per Cl. No. 9.1 along with attested drawing from Govt. approved laboratory. 3 List of Plant & Machinery at firms works. 4 List of Testing equipments at firms works. 5 List of orders pending/executed at least for past two years for the items offered a) With GUVNL/MGVCL/DISCOM. b) With the purchases other than GUVNL/MGVCL/DISCOM PART-'D':- Bidder has to mention below deviation if any, quoting relevant clause of specification. Signature & Seal of Tenderer Manufacturer's Name and Address [Technical Specification and GTP of 11 KV Pin and Disc Insulators: Ceramic//Page 7 of 7]
SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: -
SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - 1. SCOPE: - This specification covers 11KV Disc Type & 11KV/ 22KV Pin Type Insulators for 11/22KV H.T. over head power lines. 2. APPLICABLE
More informationMGVCL/MM/1043/13-14/11 KV Disc Insulators (Porcelain)
SPECIFICATION FOR 11KV DISC. INSULATORS: - 1. SCOPE: - This specification covers 11KV Disc Type Insulators for 11KV H.T. over head power lines. 2. APPLICABLE STANDARDS: - Except when they conflict with
More informationPART-II SPECIFICATION OF 22KV PIN INSULATORS. This specification covers 22KV Pin Type Insulators for 22KV H.T. over head power lines.
1. SCOPE: PART-II SPECIFICATION OF 22KV PIN INSULATORS This specification covers 22KV Pin Type Insulators for 22KV H.T. over head power lines. 2. APPLICABLE STANDARDS: Except when they conflict with specific
More informationDate: TECHNICAL SPECIFICATION FOR (LT,11KV, 33KV) PORCELAIN PIN INSULATORS
Date26.09.2013 TECHNICAL SPECIFICATION FOR (LT,11KV, 33KV) PORCELAIN 1. SCOPE PIN INSULATORS The specification provides for manufacture, testing before dispatch, supply and delivery of (LT/11KV/33KV) Porcelain
More informationMaharashtra State Electricity Distribution Co. Ltd.
Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO. MSEDCL/ DIST:MM-III/06/2006 SPECIFICATION FOR H.T.DISC INSULATORS 1 TECHNICAL SPECIFICATION FOR 11 KV 45 KN / 70 KN DISC. INSULATORS
More informationMaharashtra State Electricity Distribution Co. Ltd.
Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO. MSEDCL/ DIST:MM-III/06/2006 SPECIFICATION FOR H.T.DISC INSULATORS 1 TECHNICAL SPECIFICATION FOR 11 KV 45 KN / 70 KN DISC INSULATORS
More informationSPECIFICATION OF HT-LT STAY (GUY) INSULATORS:
1. SCOPE: SPECIFICATION OF HT-LT STAY (GUY) INSULATORS: This specification covers the details of the Guy (Strain) insulators Porcelain White/Brown glazed insulators suitable for G.I. Stay Wire 7/3.15mm
More informationSPECIFICATION FOR HT-LT STAY (GUY) INSULATORS:
SPECIFICATION FOR HT-LT STAY (GUY) INSULATORS:. SCOPE: This specification covers the details of the Guy (Strain) insulators Porcelain White/Brown glazed insulators suitable for G.I. Stay Wire 7/3.mm and
More informationSpecification No. CSC- XXIX/DH/UH/P&D/
UTTAR & DAKSHIN HARYANA BIJLI VITRAN NIGAM Specification No. CSC- XXIX/DH/UH/P&D/2009-2010 TECHNICALSPECIFICATION FOR PORCELAIN INSULATROS AND INSULATORS FITTINGS FOR 11 KV OVERHEAD POWER LINES Issue of
More information11KV PORCELAIN INSULATORS AND FITTINGS
REC Specification 3/1971 (Revised 1993) 11KV PORCELAIN INSULATORS AND FITTINGS FOREWORD This specification was originally issued in 1971 on the basis of the decisions taken in the First and Second Standardisation
More informationMaharashtra State Electricity Distribution Co. Ltd.
Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO. MSEDCL/ DIST/MM-III/02/2008/R1(010111) SPECIFICATION FOR L.T. PIN/SHACKLE INSULATORS Page 1 of 12 MAHARASHTRA STATE ELECTRICITY DISTRIBUTION
More informationSPECIFICATION FOR DISC INSULATORS (Standard Type)
Doc. KPLC1/3CB/TSP/04/015 1 Page 1 of 6 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6. MARKING,
More informationANNEXURE - ' D ' TECHNICAL SPECIFICATION FOR INSULATOR PINS ( PINS FOR 11,22 AND 33 kv INSULATORS )
ANNEXURE - ' D ' TECHNICAL SPECIFICATION FOR INSULATOR PINS ( PINS FOR 11,22 AND 33 kv INSULATORS ) SPECIFICATION NO:DIST/MM/I/G.I. PINS -2006) INDEX ------------------------------------------------------------------------------------------------------------
More informationMAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. Ltd. (MUMBAI) SCHEDULE 'A' TECHNICAL SPECIFICATION FOR. 11 kv, 22 kv & 33 kv HORN GAP FUSES FOR
MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. Ltd. (MUMBAI) SCHEDULE 'A' TECHNICAL SPECIFICATION FOR 11 kv, 22 kv & 33 kv HORN GAP FUSES FOR DISTRIBUTION NETWORK IN MAHARASHTRA SPECIFICATION NO:DIST/MM/I/HGF2006
More informationTECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS
TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 11 TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS 1.0 Scope : The specification covers the manufacture,
More information094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA
094: 2000 CEB STANDARD MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEB Standard
More informationTECHNICAL SPECIFICATION FOR CONDUCTOR HARDWARE FITTING FOR 11/22/33 kv OVERHEAD POWER LINES
ANNEXURE - D SCHEDULE - `A' TECHNICAL SPECIFICATION FOR CONDUCTOR HARDWARE FITTING FOR 11/22/33 kv OVERHEAD POWER LINES SPECIFICATION NO:DIST/MM/I/CONDHARD-2006) INDEX -----------------------------------------------------------------------------------------------------------------------
More information093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA
093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEB Standard 093 : 2000 CEYLON
More information9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA
9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA Technical specification for 9KV/18KV 5KA Metal oxide Lightning Arrestors without Gap. ----------------------------------------------------------------------------------------------------------------
More informationTECHNICAL SPECIFICATION FOR 11 POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC INSULATORS.
Vidyut Bhavan( 4th Floor),Bidhannagar, Block-DJ Sector-II Kolkata-700 091 Phone No.033-2359-8397 Fax No.033-2359-1921 TECHNICAL SPECIFICATION FOR 11 POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11
More informationTECHNICAL SPECIFICATION FOR 11 KV & 33 KV POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC INSULATORS.
Vidyut Bhavan( 4th Floor),Bidhannagar, Block-DJ Sector-II, Kolkata-700 091 TECHNICAL SPECIFICATION FOR 11 KV & 33 KV POST INSULATORS, 11 KV & 33 KV PIN INSULATORS AND 11 KV, B&S TYPE 45 KN & 70 KN DISC
More informationGUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220, 132 & 66 COMPOSITE SOLIDCORE STATION POST INSULATORS GETCO/E/2,1,6
More informationSPECIFICATION FOR STAY INSULATORS (PORCELAIN)
Doc. KPLC1/3CB/TSP/04/016-1 Issue 1 Page 1 of 7 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION
More informationTRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1
I NDEPENDE N T POWER TR ANSM ISSION OP ER AT O R S.A. TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1 STRING INSULATOR
More informationSPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type
Doc. KPLC1/3CB/TSP/04/017/1 1 Page 1 of 7 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6.
More informationTECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS Insulators & Lightening Arrestor GROUP K & L
TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS Insulators & Lightening Arrestor GROUP K & L GROUP C Insulator Sl. No. Item Description Unit Qty. 1 11 KV Pin Insulator No 7488 2 11 KV Disc Insulator 45KN
More informationSPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY)
SPECIFICATION OF LT AERIAL BUNCHED (AB) CABLES (Size: 3C x 35mm² +1C x16 + 25mm²) FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY) 1. SCOPE: This specification covers XLPE insulated
More informationTECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS. Insulators & Lightening Arrestors GROUP A
TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS Insulators & Lightening Arrestors GROUP A Tender Notice No. NESCO Utility / MR Materials / 19 /17-18/ 13002, dtd.09.10.17 1 P a g e GROUP A Insulator & LA
More informationTECHNICAL SPECIFICATION OF UNARMOURED FLAT 1100 VOLTS L.T. PVC INSULATED TWIN CORE 4.0mm² CABLE WITH ROUND ALUMINIUM CONDUCTOR BLACK SHEATHED.
TECHNICAL SPECIFICATION OF UNARMOURED FLAT 1100 VOLTS L.T. PVC INSULATED TWIN CORE 4.0mm² CABLE WITH ROUND ALUMINIUM CONDUCTOR BLACK SHEATHED. I. SCOPE: This specification covers Manufacture, testing at
More informationCHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS
CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS 6.1 Introduction An electrical porcelain insulator plays an eminent role in electrical power system. As the insulators have high resistance path so it
More informationTECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1
ANNEXURE TO TENDER NO. PUR42396GM DATED 06 th FEBRUARY 2014 SUPPLY OF 1.1KV GRADE LT POWER CABLES FOR THE PERIOD APRIL 2014 MARCH 2016 TECHNICAL SPECIFICATION FOR 1.1KV XLPE POWER CABLE SECTION-1 1.1 SCOPE
More information2. RATED VOLTAGE: The rated voltage of the AB cables shall be 1100 volts
TECHNICAL SPECIFICATION OF LT AERIAL BUNCHED CABLES FOR LT LINES (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY) (Size 1C x35mm²+1c x16 + 25mm² and 2C x50mm² +1Cx25 + 35mm²) 1. SCOPE: This specification
More informationTECHNICAL SPECIFICATION OF 70KN & 45KNDISC INSULATOR (B & S)
TECHNICAL SPECIFICATION OF 70KN & 45KNDISC INSULATOR (B & S) SCOPE. This specification provides for design, manufacture, engineering, inspection and testing before dispatch packing and delivery FOR (destination)
More informationSEAL & SIGNATURE OF THE TENDERER
MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO. LTD. SCHEDULE - `A' TECHNICAL SPECIFICATION FOR 11 kv & 22 kv A.B. SWITCH. SPECIFICATION NO:RE/II/A.B.SWITCH/2005 INDEX -----------------------------------------------------------------------------------------------------------------------
More informationTECHNICAL SPECIFICATION OF LONG ROD PORCELAIN INSULATORS FOR TRANSMISSION LINES
GETCO/E/TS INS021/R0 DT 25/10/2007 GUJARAT ENERGY TRANSMISSION CORPORATION LTD Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF LONG ROD PORCELAIN INSULATORS FOR TRANSMISSION
More informationTECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE
TECHNICAL SPECIFICATION FOR L. T. XLPE POWER CABLE SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 14 TECHNICAL SPECIFICATION FOR LT XLPE POWER CABLES (SPECIFICATION NO.MM/I/LTXLPE/2006) 1. SCOPE: The specification
More informationGeneral Requirements. Technical Specifications for Insulators of Transmission Lines
Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Insulators of Transmission
More informationTECHNICAL SPECIFICATION
TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS DEVKON KIT AND HAND GLOVES GROUP F Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 1 Group-F Sl no. Material Description Unit Quantity
More informationPOST AND DISC INSULATOR
POST AND DISC INSULATOR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:
More informationTURKISH ELECTRICITY DISTRIBUTION CO. TECHNICAL SPECIFICATION FOR POST (SUPPORT) INSULATORS FOR MEDIUM VOLTAGE SYSTEMS
TURKISH ELECTRICITY DISTRIBUTION CO. TECHNICAL SPECIFICATION FOR POST (SUPPORT) INSULATORS FOR MEDIUM VOLTAGE SYSTEMS CONSULTANT: ELTEM-TEK ELECTRICAL INSTALLATIONS ENGINEERING SERVICES AND TRADE CO. JUNE,
More informationTECHNICAL SPECIFICATION OF ACCESSORIES SUITABLE FOR 7/3.15 mm G.I. EARTH WIRE
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF ACCESSORIES SUITABLE FOR 7/3.15 mm G.I. EARTH WIRE GETCO/E/TS EAC020/R0
More informationTechnical Specification for 11 KV, 5KN, 340 Creepage Distance Pin type Composite (Polymer) Insulator with rod
Technical Specification for 11 KV, 5KN, 340 Creepage Distance Pin type Composite (Polymer) Insulator with rod 1. SCOPE: This specification covers design, manufacture, testing, inspection, packing and supply
More informationa) Temperature Variation : 5ºC to 55ºC b) Relative humidity : Upto 95% c) Altitude : 0 to 1000 Mtrs. d) No.of tropical monsoon months : 3 (Three)
TECHNICAL SPECIFICATION OF UNARMOURED 1100 VOLTS L.T.PVC INSULATED 4 CORE 6mm², 10mm², 16mm² PVC INSULATED PVC SHEATHED CABLE WITH CIRCULAR ALUMINIUM CONDUCTOR: I. SCOPE: This specification covers Manufacture,
More informationGeneral Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)
Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators
More informationTECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED)
TECHNICAL SPECIFICATION FOR 11KV COMPOSITE INSULATORS (SILICON RUBBER HOUSED) Regd. & Corporate Office: Visnagar Road, MEHSANA 384 001 (North Gujarat) Telephone: (02762) 222880, 222080-81 Fax: (02762)
More information1. 8mtr 200Kg PSC Pole 2. 9mtr 300Kg PSC Pole
SECTION - V Group -A Technical Specification of 1. 8mtr 200Kg PSC Pole 2. 9mtr 300Kg PSC Pole TECHNICAL SPECIFICATIONS I. Applicable Standard: The Poles shall comply with latest standards as under: REC
More informationTECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132/220/400 KV SUB-STATION GETCO/E/TS-C&C
More informationSCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA
SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR L.T.PVC POWER AND CONTROL CABLES FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/LTPVC & CONTROL/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION
More informationNo: PUR/IMP/JPL/UVIT/ISO/39 July 29, 2008
No: PUR/IMP/JPL/UVIT/ISO/39 July 29, 2008 M/s. Dear Sirs, The Director, Indian Institute of Astrophysics, Bangalore invites Sealed Tenders for the Import of Dichroic mirrors & NUV Interference filters
More informationPART-II. TECHNICAL SPECIFICATIONS FOR 11 KV, 45KN, 320 Creepage Distance, Long rod (B&S) type Composite (Polymer) Insulator.
PART-II TECHNICAL SPECIFICATIONS FOR 11 KV, 45KN, 320 Creepage Distance, Long rod (B&S) type Composite (Polymer) Insulator. 1. SCOPE: This specification covers design, manufacture, testing, inspection,
More informationAPDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS
PART 1: SCOPE AND CONDITIONS 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, off-loading and performance requirements of 33kV, 200 amp, triple pole Gang
More informationSpecification No. CSC-70/DH/UH/P&D/
Specification No. CSC-70/DH/UH/P&D/2011-2012 TECHNICAL SPECIFICATION FOR TWIN CORES PVC SHEATHED PVC INSULATED WEATHER PROOF CABLE FOR WORKING VOLTAGE UPTO & INCLUDING 1100 V, FOR SERVICE CONNECTIONS.
More information11 KV, 45KN, 320 Creepage Distance, Long rod (B&S) type Composite (Polymer) Insulator
TECHNICAL SPECIFICATIONS FOR 11 KV, 45KN, 320 Creepage Distance, Long rod (B&S) type Composite (Polymer) Insulator Page 1 of 18 1. SCOPE: Technical Specification for 11 KV, 45KN, 320 Creepage Distance,
More informationNATIONAL ELECTRIC POWER COMPANY (NEPCO) TENDERNO. 9/2013 FOR THE SUPPLY OF INSULATORS AND FITTINGS FOR DOUBLE AND QUADRUPLE CIRCUITS 132 kv OHTL's
TENDERNO. 9/2013 7. TECHNICAL SPECIFICATION 7.A SCOPE: This specification covers the design, manufacture, testing, packing, supply, CFR delivery to Aqaba Docks in Jordan and guarantee (maintain) the following
More informationTechnical Specification for Steel Forged Fittings
Ergon Energy Corporation Limited Technical Specification for Steel Forged Fittings ETS 01-01-01 ETS 01-01-01 Ver 2 Contents 1. Purpose and Scope... 1 2. References... 1 2.1 Applicable Standards... 1 3.
More informationASSAM POWER DISTRIBUTION COMPANY LIMITED. OFFICE OF THE CHIEF GENERAL MANAGER (HQ),APDCL BIJULEE BHAWAN, PALTANBAZAR, GUWAHATI
1 ASSAM POWER DISTRIBUTION COMPANY LIMITED. OFFICE OF THE CHIEF GENERAL MANAGER (HQ),APDCL BIJULEE BHAWAN, PALTANBAZAR, GUWAHATI -781001 Tender Notice No: 14/7 Sealed offers with validity up to 365 days
More informationTECHNICAL SPECIFICATION FOR G.I. BARBED WIRE. (SPECIFICATION NO.MM/I/G.I.BARBED WIRE/2006) (Dt )
TECHNICAL SPECIFICATION FOR G.I. BARBED WIRE (SPECIFICATION NO.MM/I/G.I.BARBED WIRE/2006) (Dt. 29-09-2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 6 1. SCOPE: TECHNICAL SPECIFICATION
More informationNotes Changed note Date. 1 (A) Changed template 09 / 07 / 2008
Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4
More information5.2 The phase conductors shall be provided with one, two & three ridges for easy identification.
LT Aerial Bunched Cables for LT Lines (APPLICABLE FOR LT AB CABLE WITH XLPE INSULATION ONLY) 1. SCOPE: This specification covers XLPE insulated Aluminum cable twisted over a central bare Aluminum Alloy
More informationCOMPOSITE INSULATORS
Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO.MSEDCL/ DIST: MM-III/07/2007 SPECIFICATION FOR 11 KV/22 KV/33 KV COMPOSITE INSULATORS 1 TECHNICAL SPECIFICATION FOR 11 KV/22 KV/33 KV
More informationTechnical Specifications for 11 KV, 45KN, 320 mm. Creepage Distance, Long rod, (B&S) type Composite (Polymer) Insulator
Technical Specifications for 11 KV, 45KN, 320 mm. Creepage Distance, Long rod, (B&S) type Composite (Polymer) Insulator 1. SCOPE: This specification covers design, manufacture, testing, inspection, packing
More information30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH
SPECIFICATIONS FOR LOAD BREAK SWITCH This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE CODES
More informationTechnical Specification for Helical Fittings for Overhead Power Lines
Ergon Energy Corporation Limited Technical Specification for Helical Fittings for Overhead Power Lines ETS01-09-03 Specification ETS01-09-03 Ver 3 Contents 1. Purpose and Scope... 4 2. References... 4
More informationGUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara:
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF G.I. EARTHING STRIP FOR SUB-STATION & LINE GETCO/E/TS GIF022/REV-01 DT.
More informationTECHNICAL SPECIFICATION FOR RATE CONTRACT OF INSULATING MATS
TECHNICAL SPECIFICATION FOR INSULATING MAT 1.0 SCOPE 1.1 The scope includes design, manufacturing, inspection, testing, packing and delivery to site of protective mats for placing in front of HT (11kV,
More informationTechnical Specification for. Insulators. Part 1. Insulators for High and Extra-High Voltage Overhead Lines
Page: 1 / 18 for Insulators Part 1 Insulators for High and Extra-High Voltage Overhead Lines 1.2 Cap-and-pin insulators made of pre-stressed glass This technical specification is valid for the business
More informationNEPAL ELECTRICITY AUTHORITY (An Undertaking of Government of Nepal) Distribution and Consumer Services Butwal Regional Office
NEPAL ELECTRICITY AUTHORITY (An Undertaking of Government of Nepal) Distribution and Consumer Services Butwal Regional Office VOLUME II OF II Supply, Delivery, Installation/Erection, Testing and Commissioning
More information8. Hydrophobicity classification guide STRI guide 1.92/1 9. Radio interference characteristics of overhead power lines and high-voltage equipment
Revised in Jan 14 TECHNICAL SPECIFICATION FOR 11KV POLYMER INSULATORS (C&T) 1.0. Scope This specification covers design, manufacture, testing and supply of composite insulators for use in the 11KV overhead
More informationMGVCL/MM/ 3Cx240 mm 2 XLPE Cables/2077 TECHNICAL SPECIFICATION FOR 11 KV XLPE POWER CABLE (CROSS LINKED POLYTHELENE DRY GAS CURED) SECTION I
1.1 SCOPE MGVCL/MM/ 3Cx240 mm 2 XLPE Cables/2077 TECHNICAL SPECIFICATION FOR 11 KV XLPE POWER CABLE (CROSS LINKED POLYTHELENE DRY GAS CURED) SECTION I 1.1.1 This Section of the Specification covers design,
More informationNUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0
REVISION NO. 0 NUCLEAR POWER CORPORATION OF INDIA LTD. (A GOVT. OF INDIA ENTERPRISE) SPECIFICATION NO.PB-E-542/REV. No.0 PAGE NO. 1 OF 24 DATE OF ISSUE (MONTH/YEAR) TOTAL NO. OF PAGES (Including cover
More informationSECTION-II (VOLUME-II) PAGE 1
TECHNICAL SPECIFICATIONS SECTION-II 1.0 Technical Description of Disc Insulators 1.1 Details of Disc Insulators 1.1.1 The Insulator strings shall consist of Standard discs for a three phase, 50 Hz, effectively
More informationTECHNICAL SPECIFICATIONS FOR. 11 KV, 45 KN, 320 mm. Creepage Distance, Long rod (B&S) type Composite (Polymer) Insulators
TECHNICAL SPECIFICATIONS FOR 11 KV, 45 KN, 320 mm. Creepage Distance, Long rod (B&S) type Composite (Polymer) Insulators Page 1 of 22 1. SCOPE: Technical Specifications for 11 KV, 45KN, 320 mm. Creepage
More informationTECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATION FOR FRP FENCING AROUND DISTRIBUTION TRANSFORMER STATIONS
Page 1 of 5 TECHNICAL SPECIFICATIONS 1.0 SCOPE: TECHNICAL SPECIFICATION FOR FRP FENCING AROUND DISTRIBUTION TRANSFORMER STATIONS This specification covers the basic requirement for the complete design,
More informationStandard. Extra High Voltage (EHV) Post Insulators Standard R Version 1.0, June Tasmanian Networks Pty Ltd (ABN )
Standard Extra High Voltage (EHV) Post Insulators Standard R574184 Version 1.0, June 2018 Tasmanian Networks Pty Ltd (ABN 24 167 357 299) Authorisations Action Name and title Date Prepared by Michael Verrier,
More informationSPECIFICATION FOR POLYMER DISC INSULATOR
SPECIFICATION FOR POLYMER DISC INSULATOR Scope : This specification cover the design, manufacturing, testing at manufacturers works, transport to site, insurance, unloading & storage of 11 KV & 33 KV Polymer
More informationTechnical Specification for Outdoor Porcelain Station Post Insulators
Ergon Energy Corporation Limited Technical Specification for Outdoor Porcelain ETS10-01-02 Specification ETS10-01-02 Ver 2 Contents 1. Purpose and Scope... 1 2. References... 1 2.1 Applicable Standards...
More informationRESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES
CEB STANDARD 030-1 : 1996 Specification for RESIN FILLING TYPE JOINTING KITS FOR LOW VOLTAGE UNDERGROUND CABLES CEYLON ELECTRICITY BOARD SRI LANKA Specification for RESIN FILLING TYPE JOINTING KITS FOR
More informationTECHNICAL SPECIFICATION FOR 3-PH SMC BOXES MADE FROM THERMOSETTING PLASTIC FOR 3-PH ENERGY METER.
TECHNICAL SPECIFICATION FOR 3-PH SMC BOXES MADE FROM THERMOSETTING PLASTIC FOR 3-PH ENERGY METER. 1.0 SCOPE: This specification covers the design, manufacturing and testing of anticorrosive, dust proof,
More information6C-001 High-Voltage Pin-Type Insulator
DISCLAIMER: This translation may be used for reference purpose only. This English version is not an official translation of the original Japanese document. In cases where any differences occur between
More informationFIJI ELECTRICITY AUTHORITY BIDDING DOCUMENT
FIJI ELECTRICITY AUTHORITY BIDDING DOCUMENT MR 15/2018 PREFERRED SUPPLIER FOR 33KV INSULATORS i Section 1: Instructions to Bidders 1. Scope of Bid The Fiji Electricity Authority (hereinafter referred to
More informationSECTION 07 TECHNICAL SPECIFICATIONS 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO) GAPLESS LIGHTNING ARRESTER (LA)
SECTION 07 TECHNICAL SPECIFICATIONS OF 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO) GAPLESS LIGHTNING ARRESTER (LA) 7.0 TECHNICAL SPECIFICATIONS OF 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO)
More information10-SDMS-02 SPECIFICATIONS FOR BARE COPPER CONDUCTORS
SPECIFICATIONS FOR BARE COPPER CONDUCTORS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE
More informationSPECIFICATION FOR FRLS POWER CABLES
SPECIFICATION FOR FRLS POWER CABLES 1.0 SCOPE This specification cover the technical requirements of design, manufacture, testing and delivery to site of Power Cables of 1100V grade with FRLS PVC Sheathed,
More informationTABLE OF CONTENTS. Page FOREWORD INTRODUCTION SCOPE NORMATIVE REFERENCES
TITLE SPECIFICATION FOR STAYS AND REFERENCE DATE: PAGE: 1 REV 1 APRIL 2009 OF 16 TABLE OF CONTENTS Page FOREWORD...... 3 INTRODUCTION...... 4 1 SCOPE...... 4 2 NORMATIVE REFERENCES...... 4 3 DEFINITIONS
More informationTECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT
TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.
More informationGUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 66 kv LIGHTNING ARRESTORS GETCO/ENGG/TECH SPECI.- 66 KV LA/R4/Jan11 Sign
More informationTECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 400/220 KV SUB-STATION GETCO/E/TS C&C057/R0 DT.
More informationTECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION OF SILICON RUBBER HOUSED COMPOSITE INSULATORS FOR TRANSMISSION LINES GETCO/E/TS
More informationTECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR CLAMPS & CONNECTORS FOR 66/132 KV SUB-STATION GETCO/E/TS C&C057/R0 DT.
More informationTECHNICAL SPECIFICATION FOR CONDUCTORS
TECHNICAL SPECIFICATION FOR CONDUCTORS SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 9 TECHNICAL SPECIFICATION FOR CONDUCTORS SPECIFYING TECHNICAL PARAMETERS OF THE CONDUCTOR SPECIFICATION NO. RE/ II/ ACSR
More informationTECHNICAL SPECIFICATION FOR SUPPLY OF WEDGE CONNECTOR TO BE USED IN POWER DISTRIBUTION SYSTEM
TECHNICAL SPECIFICATION FOR SUPPLY OF WEDGE CONNECTOR TO BE USED IN POWER DISTRIBUTION SYSTEM :: TECHNICAL SPECIFICATIONS:: Sr. No Technical Specification No./Revision Date of revision 1. GUVNL/CPRND/TS/P-018/Wedge
More information33-SDMS-02 SPECIFICATIONS FOR
SPECIFICATIONS FOR MV AUTOMATIC LINE SECTIONLIZER UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS SECTION T I T L E PAGE NO.
More information660 Volts 630 & 800AMP
Ergon Energy Corporation Limited Technical Specification for Switch- Disconnectors and Fuse-Switch- Disconnectors 660 Volts 630 & 800AMP ETS-06-02-01 Check this is the latest Process Zone version before
More informationACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME. Technical Specification (T.S)
ACCELARATED POWER DEVELOPMENT AND REFORM PROGRAMME SECTION - V Technical Specification (T.S) 37 (SCHEDULE I) TECHNICAL SPECIFICATION FOR SUPPLY OF AB CABLE 38 1. SCOPE: TECHNICAL SPECIFICATION This specification
More informationSPECIFICATION OF NEOPRENE RUBBER SEALS
SPECIFICATION OF NEOPRENE RUBBER SEALS 1.0 SCOPE This specification establishes the requirements for the manufacture, inspection, testing, packing, guarantee & supply of Neoprene Rubber Seals for Fuelling
More informationNPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators
Version:- 3.1 Date of Issue:- June 2014 Page 1 of 13 NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators 1. Purpose This document is the technical specification for 33kV, 66kV
More informationP.V.C. INSULATED UNARMOURED COPPER CABLES
083 : 2007 CEB SPECIFICATION P.V.C. INSULATED UNARMOURED COPPER CABLES CEYLON ELECTRICITY BOARD SRI LANKA Specification for P.V.C. INSULATED UNARMOURED COPPER CABLES CEB Specification 083 : 2007 CEYLON
More informationFOREWORD SCOPE NORMATIVE REFERENCES DEFINITIONS REQUIREMENTS... 4
INSULATORS VERTICAL & HORIZONTAL MOUNTING - SPECIFICATION Page 1 of 20 Table of Contents FOREWORD... 2 1. SCOPE... 2 2. NORMATIVE REFERENCES... 3 3. DEFINITIONS... 4 4. REQUIREMENTS... 4 4.1. SERVICE CONDITIONS...
More information