Technical Justification for

Size: px
Start display at page:

Download "Technical Justification for"

Transcription

1 ECOGLO INTERNATIONAL LIMITED Technical Justification for To meet the Exit Signage Requirements of NCC 2016 EP4.2 For the most current solution documents refer to: (from the Home Page select Technical then Code Compliance) V17.1

2 Introduction This document examines NCC 2016 Performance Requirement EP4.2 of the BCA and demonstrates how Ecoglo photoluminescent signs can be used to meet NCC 2016 via the following methodology: The signs are of suitable size and sufficient brightness to be clearly visible; Charging requirements can be prescribed to ensure the signs can be charged to maintain adequate brightness for sufficient time to allow safe evacuation of the building as per the requirements of EP4.2; The signs can be suitably positioned to identify the location of exits; Ecoglo manufactures photoluminescent sign material to different grades of brightness. Although S14 grade can be used to meet Deemed to Satisfy (DtS) Provisions of Specification E4.8, any reference to Ecoglo signs in this document means Ecoglo S20 grade photoluminescent signs. Performance Requirements are the mandatory requirements of the code and specify the minimum level of performance for all buildings. A Performance Requirement can be satisfied through a Performance Solution or a Deemed-to-Satisfy (DtS) Solution or a combination of both. A Performance Solution is defined as any solution that can meet the Performance Requirements, other than a DtS Solution. A Performance Solution may differ in whole or in part from the DtS Provisions, but will still meet the Performance Requirements as long as it can be successfully demonstrated how this will be achieved. A Deemed-to-Satisfy Solution uses the DtS Provisions and any referenced documents contained within the NCC. These provisions include prescriptive examples of materials, products, design factors, construction and installation methods, which if followed in full, are deemed to comply with the Performance Requirements of the NCC. Performance Requirement EP4.2 specifies To facilitate evacuation, suitable signs or other means of identification must to the degree necessary- (a) be provided to identify the location of exits; and (b) guide occupants to exits; and (c) be clearly visible to occupants; and (d) operate in the event of a power failure of the main lighting system for sufficient time for occupants to safely evacuate. 1

3 NCC 2016 A1.7 (b) clarifies what is meant by the degree necessary - A reference in a Performance Requirement of the BCA to the degree necessary means that consideration of all the criteria referred to in the Performance Requirement will determine the outcome appropriate to the circumstances. These words have been inserted to indicate that in certain situations it may not be necessary to incorporate any specific measures to meet the Performance Requirements. Sufficient time, while not defined, can be taken to mean enough time in particular or given circumstances and/or environments. For example, in a building where occupants have undergone an induction which includes familiarity with evacuation routes and in which trial evacuations are regularly performed, the evacuation time can be expected to be less than that required in a building where there may be many occupants unfamiliar with the layout of the building and its evacuation route. Similarly, the size and type of building, number of occupants, and hours of occupancy all need to be taken into consideration when determining a sufficient time for occupants to safely evacuate. E4.8 NCC E4.8 Design and Operation of Exit Signs DtS Provisions states that every required exit sign must be clearly visible at all times when the building is occupied by any person having the right of legal entry to the building. Required means required to satisfy a Performance Requirement or a DtS Provision of the BCA as appropriate. Exit means (a) Any, or any combination of the following if they provide egress to a road or open space (i) An internal or external stairway. (ii) A ramp. (iii) A fire-isolated passageway. (iv) A doorway opening to a road or open space. (b) A horizontal exit or a fire-isolated passageway leading to a horizontal exit. NCC Specification E4.8 further lists the DtS Provisions for Photoluminescent Exit Signs. Size and brightness of Ecoglo signs to ensure they are clearly visible The two critical aspects to consider to ensure visibility of an exit sign are the size of the sign, and how bright it is. photoluminescent signs. The following table gives the dimensions for Ecoglo signs with 16m and 24m maximum viewing distance. Sign sizes NCC 2016 Specification E4.8 details the sizes and viewing distances required of 2

4 Ecoglo Sign Code Viewing Type Width (mm) Height (mm) Text/Picto Distance Height* (mm) S20-RM m 16m Pictogram S20-RM2916HV-16m 16m Pictogram S20-RML m 16m Pictogram S20-RMR2916HV-16m 16m Pictogram DSS20-RMD m 16m Pictogram S20-RMRL m 16m Pictogram S20-RMRL2916HV-16m 16m Pictogram DSS20-RMRL m 16m Pictogram DSS20-RMRL2916HV-16m 16m Pictogram S20-RM m 24m Pictogram S20-RM4223HV-24m 24m Pictogram S20-RML m 24m Pictogram S20-RMR m 24m Pictogram DSS20-RMD m 24m Pictogram S20-RMRL m 24m Pictogram S20-RMRL4223HV-24m 24m Pictogram DSS20-RMRL m 24m Pictogram DSS20-RMRL4223HV-24m 24m Pictogram *As per the requirements of Specification E4.8 pictorial elements on Ecoglo photoluminescent exit signs are 30% larger than sizes specified in AS AS Emergency Escape Luminaires and Exit Signs uses linear scaling. Ecoglo also manufactures signs in sizes to meet viewing distances of 32m, 40m and 48m. However, for signs with maximum viewing distances greater than 24 metres a Performance Solution must be provided as Specification E4.8 excludes the use of photoluminescent signs for viewing distances greater than 24m. Linear scaling 1, based on maintaining the same subtended visual solid angle across the pictogram elements in the signs, is used to justify the dimensions of Ecoglo signage for viewing distances greater than 24m. Sign brightness During normal lighting conditions the luminance (brightness) of photoluminescent signs is proportional to the illuminance on the sign face from ambient light. During failure of the main lighting, the luminance of photoluminescent signs depends on the brightness and length of time that the previous ambient ( charging ) light has been charging the signs, and also the time since the main lighting has failed. Providing suitable illumination on the face of each photoluminescent sign ensures the signs remain clearly visible during normal occupation, as well as providing sufficient charging to ensure the photoluminescent glow provides suitable visibility after a power failure has caused the loss of all normal lighting. If an exit sign is required in a location where there is insufficient illumination for any reason, a photoluminescent sign will not be appropriate unless a suitable dedicated light source is also installed. During failure of the main lighting Specification E4.8 specifies a minimum luminance of 30mcd/m 2 for not less than 90 minutes for photoluminescent exit signs. NATA accredited luminance testing of Ecoglo S20 Series was performed by Queensland University of Technology (QUT) in April 2014 (see Appendix A). Representative samples of S20 grade material were 3

5 tested in accordance with ASTM E Standard Test Method for Photopic Luminance of Photoluminescent (Phosphorescent) Markings except the activation illumination in clause 8.3 was replaced with 54 lux. Samples exposed to an illumination of 54 lux for 1 hour using a lamp of CCT 4000K gave a reading of 38mcd/m 2 after 90 minutes which well exceeds the E4.8 requirement. However, visibility (legibility) of any specific sign will depend on variables such as contrast (how opaque the background colour is), variations in the text or pictogram, such as size, edge sharpness and stroke width. Ecoglo pictogam exit signs have been tested in accordance with UL 924 Standard for Safety Emergency Lighting and Power Equipment by an independent laboratory to show that they are visible 2 from 24 metres after 90 minutes of darkness (See Appendix B). The independent test also verifies that the pictogram signs are visible from 24 metres when emitting a luminance of 21.4 mcd/m 2. Charging Requirements Specification E4.8 DtS provision requires a minimum of 100 lux at the face of the sign by a dedicated light source with a colour temperature not less than 4000 K. Indoor Charging Indoor spaces are either lit by electric lighting only, or by daylight when sufficient, or supplemented by electric lighting when daylight is not sufficient. Daylight through window glass, whether direct or reflected off room surfaces, provides effective charging for Ecoglo signs. Types of electric lighting that are suitable for charging Ecoglo Exit signs Ecoglo testing (see Appendix C) has verified that fluorescent, metal halide, or LED lighting with a colour temperature of 4000K or greater are all suitable charging sources for Ecoglo exit signage. If the installed lighting in a building has a colour temperature of less than 4000K, a specific design by Ecoglo is required. Illumination The DtS Design Level required of PL Exit signs is that they provide a minimum luminance of 30 mcd/m 2 for not less than 90 minutes in the event of a power failure. Testing performed on Ecoglo exit signs has shown that to reach the Design Level after the sign is completely discharged 3, the following charging is required: 20 minutes with 100 lux on the sign 2 UL 924 defines visible as legible (pertains to text) and distinguishable from other text or symbols. This satisfies the wording clearly visible in both EP4.2 and E To completely discharge, the Ecoglo sign is kept in total darkness for a period of 3 days at a minimum temperature of 20 C. Designing Solutions to meet EP4.2 The scenario below illustrates how the above test result can be used as a starting point for designing solutions to meet Performance Requirement EP4.2. Scenario: The sign has been in total darkness and is fully discharged. If 100 lux is provided on the face of the sign, it will take 20 minutes to reach Design Level. In this situation an operating procedure ensuring 100 lux is on the face of the sign 20 minutes prior to occupation of the building is required. This is a DtS Solution. 4

6 Suitable positions to identify the locations of exits EP4.2 states that suitable signs must be provided to identify the location of exits and guide occupants to exits, while E4.8 defines an exit as any, or any combination of the following if they provide egress to a road or open space: an internal or external stairway; a ramp; a fire-isolated passageway; a doorway opening to a road or open space; or, a horizontal exit or a fire-isolated passageway leading to a horizontal exit. A Performance Solution will be deemed to meet EP4.2 as long as exit signs are located in all positions required by DtS clause E4.5 Exit Signs. (d) door serving as, or forming part of,a required exit in a storey required to be provided with emergency lighting in accordance with E4.2. AS stipulates that exit signs shall be mounted not less than 2m and not more than 2.7 m above floor level, or immediately above the doorway if the doorway is higher than 2.7m. The purpose of this is to ensure that each exit sign is within the field of view of a person with the applicable viewing distance and looking at the relevant door or along the relevant exit path. E4.5 states that an exit sign must be clearly visible to persons approaching the exit, and must be installed on, above or adjacent to each (a) door providing direct egress from a storey to (i) an enclosed stairway, passageway or ramp serving as a required exit; and (ii) an external stairway, passageway or ramp serving as a required exit; and (iii) an external access balcony leading to a required exit; and (b) (c) door from an enclosed stairway, passageway or ramp at every level of discharge to a road or open space; and horizontal exit; and Note: Smoke can readily obliterate even very bright signs, so another important aspect to also consider is mounting a sign as low as possible in a room so it has least chance of being obscured by smoke. It follows that signs that are mounted high up are more likely to be obscured by smoke than signs mounted lower down. See Designers Guide for High Risk Smoke Areas in Technical section on website ( The practicality of installation of electrical exit signs means that they are often mounted at, or just below, ceiling height. However, there are no such restrictions for photoluminescent signs, which can readily be installed low down and on many types of surface, including glazing. ** Outdoor charging, higher charging illuminance, shorter evacuation time and lower luminance visibility, while not currently described in this document, are all factors which can be considered when designing a performance solution to meet the requirements of EP4.2. Contact Ecoglo for more details. Conclusion The above has shown that: Ecoglo signs are of suitable size and can be sufficiently bright to be clearly visible; Charging requirements can be prescribed to ensure the signs can be charged to maintain adequate brightness for sufficient time to allow safe evacuation of the building as per the requirements of EP4.2; The signs can be suitably positioned to identify the location of exits. In this way Ecoglo photoluminescent signs can be used to meet the requirements of EP4.2. ** 5

7 Appendix A 6

8 Appendix A 7

9 Appendix A 8

10 Appendix A 9

11 Appendix A 10

12 Appendix A 11

13 Appendix A 12

14 Appendix A 13

15 Appendix B 14

16 Appendix B 15

17 Appendix B 16

18 Appendix B 17

19 Appendix B 18

20 Appendix B 19

21 Appendix C Ecoglo test report data (Various lamp types) Test No. Date Lamp Type Charging Lux Charging Luminance after 30 Time (min) Minutes (mcd/m 2 ) e502 17/05/12 Fluoro 4000K e503 29/05/12 Led 4000K e507 22/06/12 Fluoro 6500K e508 26/02/12 Met Hal 4000K e548 28/05/13 LED 4000K

22 ECOGLO INTERNATIONAL LIMITED Phone: info@ecoglo.com

Emergency Signs and Escape Routes

Emergency Signs and Escape Routes Emergency Signs and Escape Routes Solutions to meet NZBC Clause F8 Signs and Clause F6 Visibility in Escape Routes New Zealand Catalogue V19.1 100 With Ecoglo Hybrid PL exit signs the batteries can be

More information

Draft for Comment Please comments to PART C(i):

Draft for Comment Please  comments to PART C(i): Draft for Comment Please email comments to info@plcouncil.com.au PART C(i): INSPECTION AND MAINTENANCE STANDARDS FOR PHOTOLUMINESCENT EXIT SIGNS (v4.1) SECTION 1 - PRINCIPLES 1.1 Scope This standard sets

More information

CONSTRUCTION TECHNOLOGY UPDATE

CONSTRUCTION TECHNOLOGY UPDATE CONSTRUCTION TECHNOLOGY UPDATE No. 78, September 2011 Building Egress Using Photoluminescent Markings by Noureddine Benichou and Guylene Proulx The use of photoluminescent material systems in buildings

More information

2009 IBC Section 1024 Approved Luminous Egress Path Markings

2009 IBC Section 1024 Approved Luminous Egress Path Markings 2009 IBC Section 1024 Approved Luminous Egress Path Markings Where Required Buildings of Groups A (Assembly), B (Business), E (Education), I (Institutional), M (Mercantile) and R-1 (Residential transient

More information

Luminous Egress Path Markings

Luminous Egress Path Markings 2009 IBC/IFC Requirements for Luminous Egress Path Markings In New and Existing High Rise Buildings By Manny Muniz California Deputy State Fire Marshal (Ret.) Sponsored by FCIA 1 IBC 403.5.5 Luminous egress

More information

Compliance Guide for Fire Code

Compliance Guide for Fire Code Ecoglo has developed advance technology for the production of high visibility Photoluminescent and anti-slip step edge and path marking systems. These provide for the safe and efficient movement of people

More information

IBC/IFC Egress Path Marking System Compliance Manual

IBC/IFC Egress Path Marking System Compliance Manual IBC/IFC Egress Path Marking System Compliance Manual JESSUP MANUFACTURING COMPANY P.O. Box 366 McHenry, IL 60051 2815 West Route 120 McHenry, IL 60051 USA www.jessupmfg.com 1701 Rockland Road Lake Bluff

More information

New York City RS 6.1 Photoluminescent Exit Path Markings

New York City RS 6.1 Photoluminescent Exit Path Markings New York City RS 6.1 Photoluminescent Exit Path Markings 2.1.1 Door Signs Fig. 1 - Door Mounted The top of the signs shall be no higher than 18 above the finished floor. Signs shall be installed either

More information

PSA / PSPA Guide to the Use of Photoluminescent Safety Markings. Part One: Egress Markings In Stairwells

PSA / PSPA Guide to the Use of Photoluminescent Safety Markings. Part One: Egress Markings In Stairwells PSA / PSPA Guide to the Use of Photoluminescent Safety Markings Part One: Egress Markings In Stairwells August 2008 1 Forward The foundation of this guide is based on a recommendation submitted to the

More information

BRADYGLO EMERGENCY EGRESS MARKING HANDBOOK

BRADYGLO EMERGENCY EGRESS MARKING HANDBOOK BRADYGLO EMERGENCY EGRESS MARKING HANDBOOK BRADYGLO EMERGENCY EGRESS MARKING HANDBOOK Table of Contents Introduction to Code Changes...2 2009 International Building Code and International Fire Code...3

More information

Accessible Means Of Egress

Accessible Means Of Egress Accessible Means Of Egress 2 New ADA Standards DOJ s 2010 standards (mandatory as of March 15) Based on the Board s ADA-ABA Guidelines (2004) 3 Standards Department of Transportation s ADA Standards Federal

More information

REFERENCE STANDARD RS-6 MEANS OF EGRESS

REFERENCE STANDARD RS-6 MEANS OF EGRESS REFERENCE STANDARD RS-6 MEANS OF EGRESS REFERENCE STANDARD RS 6-1 PHOTOLUMINESCENT EXIT PATH MARKINGS as required by Local Law 26 of 2004, New York City Building Code 27-383(b) Introduction This standard

More information

2009 IBC/IFC Photoluminescent Signs & Pathway Marking Systems Frequently Asked Questions

2009 IBC/IFC Photoluminescent Signs & Pathway Marking Systems Frequently Asked Questions 2009 IBC/IFC Photoluminescent Signs & Pathway Marking Systems Frequently Asked Questions 1. What is the difference between IBC & IFC? a. IBC International Building Code covers new construction b. IFC International

More information

Section 1 OBC FADS /13 Access to Parking Areas

Section 1 OBC FADS /13 Access to Parking Areas Section 1 OBC 3.8.2.2 4.3.12/13 Access to Parking Areas A barrier-free path of travel is provided from: a) the entrance to the exterior parking area b) at least one parking level where a passenger elevator

More information

2006 International Building Code Modified for the 2007 Florida Building Code 6/5/06

2006 International Building Code Modified for the 2007 Florida Building Code 6/5/06 Chapter 10 Means of Egress Chapter 10 Mean of Egress 1001.3 Maintenance. Means of egress shall be maintained in accordance with the International Fire Code. na 1001.3 Maintenance. Means of egress shall

More information

The easiest way to comply with local law 26. A Review of New York City Building Code Reference Standard RS 6-1

The easiest way to comply with local law 26. A Review of New York City Building Code Reference Standard RS 6-1 The easiest way to comply with local law 26. A Review of 2 The information provided herein is intended to assist the recipient in becoming more familiar with the subject matter covered. Johnsonite makes

More information

PROMULGATION OF THE NEW YORK CITY BUILDING CODE REFERENCE STANDARD RS 6-1 AND RS 6-1A IN RELATION TO PHOTOLUMINESCENT EXIT PATH MARKINGS

PROMULGATION OF THE NEW YORK CITY BUILDING CODE REFERENCE STANDARD RS 6-1 AND RS 6-1A IN RELATION TO PHOTOLUMINESCENT EXIT PATH MARKINGS PROMULGATION OF THE NEW YORK CITY BUILDING CODE REFERENCE STANDARD RS 6-1 AND RS 6-1A IN RELATION TO PHOTOLUMINESCENT EXIT PATH MARKINGS PURSUANT TO Chapter 26 of the New York City Charter and Sections

More information

PROMULGATION OF THE NEW YORK CITY BUILDING CODE REFERENCE STANDARD RS 6-1 AND RS 6-1A IN RELATION TO PHOTOLUMINESCENT EXIT PATH MARKINGS

PROMULGATION OF THE NEW YORK CITY BUILDING CODE REFERENCE STANDARD RS 6-1 AND RS 6-1A IN RELATION TO PHOTOLUMINESCENT EXIT PATH MARKINGS PROMULGATION OF THE NEW YORK CITY BUILDING CODE REFERENCE STANDARD RS 6-1 AND RS 6-1A IN RELATION TO PHOTOLUMINESCENT EXIT PATH MARKINGS PURSUANT TO Chapter 26 of the New York City Charter and Sections

More information

PROMULGATION OF THE NEW YORK CITY BUILDING CODE REFERENCE STANDARD RS 6-1 AND RS 6-1A IN RELATION TO PHOTOLUMINESCENT EXIT PATH MARKINGS

PROMULGATION OF THE NEW YORK CITY BUILDING CODE REFERENCE STANDARD RS 6-1 AND RS 6-1A IN RELATION TO PHOTOLUMINESCENT EXIT PATH MARKINGS PROMULGATION OF THE NEW YORK CITY BUILDING CODE REFERENCE STANDARD RS 6-1 AND RS 6-1A IN RELATION TO PHOTOLUMINESCENT EXIT PATH MARKINGS PURSUANT TO Chapter 26 of the New York City Charter and Sections

More information

(Note: This document is the same as been forwarded to be published in the City Record for public hearing and comment)

(Note: This document is the same as been forwarded to be published in the City Record for public hearing and comment) NOTICE OF OPPORTUNITY TO COMMENT on the proposed promulgation of the New York City Building Code Reference Standard RS 6-1, Photoluminescent Low-level Exit Path Markings, and RS 6-1A, Additional Standards.

More information

2015 IBC Exit Systems

2015 IBC Exit Systems Objectives 2015 IBC Exit Systems Based on the 2015 International Building Code Upon completion, participants will be better able to: Determine those means of egress components that are defined as exits

More information

EGRESS AZMIR SULTANA NICOLAS MIMU SAKUMA EDWIN VEGA CHAMORRO

EGRESS AZMIR SULTANA NICOLAS MIMU SAKUMA EDWIN VEGA CHAMORRO EGRESS AZMIR SULTANA NICOLAS CHAMORRO MIMU SAKUMA EDWIN VEGA DEFINITIONS NC ACCESSIBLE MEANS OF EGRESS. A continuous and unobstructed way of egress travel from any accessible point in a building or facility

More information

ECOGLO PTE LTD. Designers Handbook for. Ecoglo Flat Nosing. To meet the design and construction requirements of

ECOGLO PTE LTD. Designers Handbook for. Ecoglo Flat Nosing. To meet the design and construction requirements of ECOGLO PTE LTD Designers Handbook for Ecoglo Flat Nosing To meet the design and construction requirements of Singapore BCA Code on Accessibility in The Built Environment 2013 VISIBLY BETTER This handbook

More information

2012 IBC Exit Systems

2012 IBC Exit Systems Accreditation Based on the 2012 International Building Code The International Code Council has been accredited as an Authorized Provider by the International Association for Continuing Education and Training

More information

ARCHIVED. Compliance Document for New Zealand Building Code Clause G8 Artificial Light. Prepared by the Department of Building and Housing

ARCHIVED. Compliance Document for New Zealand Building Code Clause G8 Artificial Light. Prepared by the Department of Building and Housing Compliance Document for New Zealand Building Code Clause G8 Artificial Light Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building and Housing.

More information

THE JALITE 7010 EXIT SIGN SYSTEM LIT effective, efficient and elegant, exit identification solutions designed to save lives.

THE JALITE 7010 EXIT SIGN SYSTEM LIT effective, efficient and elegant, exit identification solutions designed to save lives. THE JALITE 7010 EXIT SIGN SYSTEM LIT543-12.06.2012 effective, efficient and elegant, exit identification solutions designed to save lives. 7010 Sign System 1: Ceiling mounted rod option Introducing the

More information

REQUIREMENTS FOR AMMONIA REFRIGERATION SYSTEMS AND COOLROOM CONSTRUCTION. Building Code of Australia (BCA) 2010 Compliance

REQUIREMENTS FOR AMMONIA REFRIGERATION SYSTEMS AND COOLROOM CONSTRUCTION. Building Code of Australia (BCA) 2010 Compliance REQUIREMENTS FOR AMMONIA REFRIGERATION SYSTEMS AND COOLROOM CONSTRUCTION Building Code of Australia (BCA) 2010 Compliance ISECO Consulting Services Interpretation Ammonia (Type B2) Refrigerant, Unrestricted

More information

Instructions for installation Everlux Egress Path Marking System

Instructions for installation Everlux Egress Path Marking System UL Listed Luminous Egress Path Marking Systems CAUTION SAVE THESE INSTRUCTIONS The includes the following components: Photoluminescent Egress Path marking for wall installation Photoluminescent Egress

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary Chapter 10: Means of Egress General Comments The general criteria set forth in Chapter 10 regulating the design of the means of egress are established as the primary method for protection of people in

More information

E?? , , , , , , , , , , , , Table ,

E?? , , , , , , , , , , , , Table , CTC to BCAC Unenclosed Exits 2015 Group A Code Change Cycle Copyright 2014 International Code Council, Inc. IBC 10-31 E?? 15 202, 1005.3.2, 1009.3, 1009.4, 1019.3, 1029.6, 1029.6.3, 1029.7, 1029.8, 1029.8.1,

More information

Verification Methods For New Zealand Building Code Clause G8 Artificial Light

Verification Methods For New Zealand Building Code Clause G8 Artificial Light Acceptable Solutions and Prepared by the Ministry of Business, Innovation and Employment Verification Methods For New Zealand Building Code Clause G8 Artificial Light G8 Status of Verification Methods

More information

Fire Safety Design Report

Fire Safety Design Report Fire Safety Design Report Extension to Existing Church 25 Mana Avenue Titahi Bay Reference Revision Date Comment 15166R01-11 th April 2016 - Extension to Existing Church, 25 Mana Avenue, Titahi Bay Page

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 1005 MEANS OF EGRESS SIZING [B] 1005.1 General. All portions of the means of egress system shall be sized in accordance with this section. Exception: Means of egress complying with Section 1028.

More information

STEP GLOW. A Step ahead

STEP GLOW. A Step ahead STEP A Step ahead NO STEP- - Lights on STEP- Visual guidance products offer the the most advanced photoluminescent technology available today. Bright & Long Lasting, STEP- is over 80% brighter then ASTM

More information

Date of Authorization September 30, 2004 BMEC Authorization # BMEC Application A

Date of Authorization September 30, 2004 BMEC Authorization # BMEC Application A Building Materials Evaluation Commission 777 Bay Street, 2 nd Floor Toronto, Ontario, M5G 2E5 Tel: 416: 585. 4234 / Fax: 416. 585. 7531 www.obc.mah.gov.on.ca Date of Authorization September 30, 2004 BMEC

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory 191-192 Baizid Bostami Road, Nasirabad Industrial Area, Chittagong 24 May 2014 The Alliance for Bangladesh Worker Safety Page 1/13 24 May 2014 Introduction

More information

SFS Form: 4 PROJECT NAME ADDRESS FIRE SAFETY ENGINEERING DESIGN REPORT. Date. 1.0 Introduction

SFS Form: 4 PROJECT NAME ADDRESS FIRE SAFETY ENGINEERING DESIGN REPORT. Date. 1.0 Introduction PROJECT NAME ADDRESS FIRE SAFETY ENGINEERING DESIGN REPORT Date 1.0 Introduction 1.01 This report describes the fire safety requirements and the provisions for this project. This fire safety report has

More information

Standard for Bleachers, Folding and Telescopic Seating, and Grandstands

Standard for Bleachers, Folding and Telescopic Seating, and Grandstands International Code Council Standard for Bleachers, Folding and Telescopic Seating, and Grandstands ICC 300-2017 edition Public Comment Draft October 2017 The ICC Consensus Committee on Bleachers, Folding

More information

JC Code & Construction Consultants, Inc. Advanced 2010 FBC Update Ch. 1 to 16

JC Code & Construction Consultants, Inc. Advanced 2010 FBC Update Ch. 1 to 16 JC Code & Construction Consultants, Inc. Advanced 2010 FBC Update Ch. 1 to 16 Welcome! This course is designed to provide an overview of the most significant changes to the 2010 edition of the Florida

More information

Project: MOE Nationwide FLS - Avalon Block Accessibility Report

Project: MOE Nationwide FLS - Avalon Block Accessibility Report Project: MOE Nationwide FLS - Avalon Block Accessibility Report Reference: 246313 Prepared for: Ministry of Education Revision: A 28 September 2015 Document Control Record Document prepared by: Aurecon

More information

VISIBLY BETTER. Photoluminescent Emergency Path Marking Solutions for Indoor and Outdoor Use. IFC/IBC, NYC LL and NFPA Compliant Guidance Systems

VISIBLY BETTER. Photoluminescent Emergency Path Marking Solutions for Indoor and Outdoor Use. IFC/IBC, NYC LL and NFPA Compliant Guidance Systems R VISIBLY BETTER Photoluminescent Emergency Path Marking Solutions for Indoor and Outdoor Use IFC/IBC, NYC LL and NFPA Compliant Guidance Systems Ecoglo Inc. www.ecoglo.us Our Mission: Our mission at Ecoglo

More information

CITY OF DANA POINT WINDOW REPLACEMENTS FOR R-3 B030 WINDOWS

CITY OF DANA POINT WINDOW REPLACEMENTS FOR R-3 B030 WINDOWS CITY OF DANA POINT COMMUNITY DEVELOPMENT BUILDING AND SAFETY 33282 Golden Lantern, Suite 209 Dana Point, CA 92629 949 248-3594 www.danapoint.org WINDOW REPLACEMENTS FOR R-3 B030 WINDOWS 2016 CALIFORNIA

More information

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS November 2018 Contents 1. Introduction... 1 2. Ontario Building Code and Second Dwelling Units... 1 3. How Do I Make My Secondary Dwelling Unit

More information

Air Quality and Lighting Environment for Traincrew Inside Railway Vehicles

Air Quality and Lighting Environment for Traincrew Inside Railway Vehicles Air Quality and Lighting Environment for Traincrew Inside Railway Vehicles Signatures removed from electronic version Submitted by... D. Boocock Nominated Responsible Manager Approved by... C.P. Boocock

More information

NCC Volume Two Energy Efficiency

NCC Volume Two Energy Efficiency NCC Volume Two Energy Efficiency Insert Corporate logo here Commonwealth of Australia and States and Territories of Australia, 2016 2016 Commonwealth of Australia and States and Territories of Australia

More information

UL 1994 Listed Code Compliant Photoluminescent Egress Path Markings per IBC & IFC

UL 1994 Listed Code Compliant Photoluminescent Egress Path Markings per IBC & IFC UL 1994 Listed Code Compliant Photoluminescent Egress Path Markings per IBC & IFC 28 For over years Dear Customer In 1994, following the first terrorist bomb attack in the World Trade Center basement parking

More information

The Web Shop. AE 482 Submission 1. Eric Anderson Lighting/Electrical. AE Faculty Consultant Dr. Kevin Houser. 4 February 2011

The Web Shop. AE 482 Submission 1. Eric Anderson Lighting/Electrical. AE Faculty Consultant Dr. Kevin Houser. 4 February 2011 The Web Shop AE 482 Submission 1 Eric Anderson Lighting/Electrical AE Faculty Consultant Dr. Kevin Houser 4 February 2011 Files Located at P:\AE482 General Building Statistics: Work Space Open Plan Office

More information

2015 International Fire Code

2015 International Fire Code 1001, 1001.1, 1001.2, 1002, [BE] 1002.1, 1003, [BE] 1003.1, [BE] 1003.2, [BE] 1003.3, [BE] 1003.3.1, [BE] 1003.3.2, [BE] 1003.3.3, [BE] 1003.3.4, [BE] 1003.4, [BE] 1003.5, [BE] 1003.6, [BE] 1003.7, 1004,

More information

Company Overview. Significant Code Changes Massachusetts State Building Code 9 th Edition (2015 International Code)

Company Overview. Significant Code Changes Massachusetts State Building Code 9 th Edition (2015 International Code) Significant Code Changes Massachusetts State Building Code 9 th Edition (2015 International Code) Company Overview R.W. Sullivan Engineering (RWS) was established in 1945 and currently has 95 employees.

More information

Michael Wynn Jones & Associates

Michael Wynn Jones & Associates Building Regulation consulting & education Building Code of Australia report Proposed early childhood centre at Farnell Ave Carlingford Reference: Farnell Ave Report 31 Mar 2016 1 Introduction... 2 1.1

More information

INTERNATIONAL EXISTING BUILDING CODE

INTERNATIONAL EXISTING BUILDING CODE INTERNATIONAL EXISTING BUILDING CODE EB10-09/10, Part I IEBC 605.1, 705.2, 706.1, 805.4 (New), 805.4.1 (New), 912.4.1, 912.4.2, 912.8.2, 1004.1(New), 1005.1, 1103.3, 1105.6; IBC 3411.4, 3411.4.1, 3411.4.2,

More information

Building Codes and Ordinances ARC 227

Building Codes and Ordinances ARC 227 Building Codes and Ordinances ARC 227 Week 6 Fire Resistive Construction 03.02.10 Instructor: Rick Staub, AIA Email: staub@pointonearchitects.com Phone: 860-434-7707 Fire Resistive Construction Passive

More information

CHAPTER 10 MEANS OF EGRESS

CHAPTER 10 MEANS OF EGRESS CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

Plan Check No. A. ELEVATORS

Plan Check No. A. ELEVATORS Elevators, Egress and Areas of Refuge, Platform Lifts Plan Check No. A. ELEVATORS NOTE: In buildings two or more stories in height, served by an elevator, or a building served by an elevator required by

More information

The Building Codes A.R.E. Building Design and Construction Exam Prep

The Building Codes A.R.E. Building Design and Construction Exam Prep Know Thy Codes! The Building Codes Building Codes The Code of Hammurabi 4000bc Developed 19 th and 20 th c. Codes define what you can and can t do Allowable area and height based on degree of danger Fire

More information

BCA Section J Compliance Report. Alterations & Additions to Cottage at St Johns College 10 Missenden Road Camperdown

BCA Section J Compliance Report. Alterations & Additions to Cottage at St Johns College 10 Missenden Road Camperdown BCA Section J Compliance Report Alterations & Additions to Cottage at St Johns College 10 Missenden Road Camperdown Prepared by: Gradwell Consulting ABN 68 872 791 784 Sustainability Consultants PO Box

More information

Fall prevention through windows: barriers and balustrades (Nat)

Fall prevention through windows: barriers and balustrades (Nat) Fall prevention through windows: barriers and balustrades (Nat) BCA Volume Two Housing Provisions has been amended under BCA 2009 to require a balustrade or other barrier where it is possible for a person

More information

March BCA 2014 Section J Amendments

March BCA 2014 Section J Amendments March 2014 BCA 2014 Section J Amendments Introduction BCA 2013 Amendments - Recap BCA 2014 Amendments Section J DTS(prescriptive) vs JV3(performance) Cost implications of DTS Building Envelope and Glazing

More information

POLICY TRAILS LIGHTING

POLICY TRAILS LIGHTING POLICY TRAILS LIGHTING Policy C7002 Adopted by Council: 2017.04.10 Administrative Responsibility: Planning and Development Council Resolution #: COU17-68 Last Review Date: Modified by Resolution #: Next

More information

Project: MOE FLS Reference Designs for Standard Classroom Upgrade 2-storey Nelson Block

Project: MOE FLS Reference Designs for Standard Classroom Upgrade 2-storey Nelson Block Project: MOE FLS Reference Designs for Standard Classroom Upgrade 2-storey Nelson Block Accessibility Report Reference: 246313 Prepared for: Ministry of Education Revision: D 2 September 2016 Document

More information

National Construction Code 2016 (NCC2016 / BCA2016) Presented by: Stuart Boyce

National Construction Code 2016 (NCC2016 / BCA2016) Presented by: Stuart Boyce National Construction Code 2016 (NCC2016 / BCA2016) Presented by: Stuart Boyce Presentation Content PURPOSE OF REVISION IMPORTANT CHANGES Focus on NCC Volume 1 and AIRAH Issues only PURPOSE OF REVISION

More information

Project Number SJ Sydney CityGrid Project. Appendix J. BCA report. Blackett Maguire + Goldsmith

Project Number SJ Sydney CityGrid Project. Appendix J. BCA report. Blackett Maguire + Goldsmith Project Number SJ-06087 Sydney CityGrid Project Appendix J BCA report Blackett Maguire + Goldsmith 21 February 2012 Preliminary BCA Report 33 BLIGH STREET, SYDNEY Office Tower & CEZS Investa Property Group

More information

Report of project list/proposed changes for Dec. 5 and 6, 2017 BCAC face-to-face committee meeting and

Report of project list/proposed changes for Dec. 5 and 6, 2017 BCAC face-to-face committee meeting and BCAC MOE Work Group Summary with Files Revised 11-20-2017 with meeting notes Report of project list/proposed changes for Dec. 5 and 6, 2017 BCAC face-to-face committee meeting ITEM Topic SECTION Notes

More information

1301: Means of egress.

1301: Means of egress. ACTION: Final DATE: 12/26/2018 8:54 AM 1301:7-7-10 Means of egress. (A) Section 1001 General (1) 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required

More information

CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY DRAFT. FLORIDA BUILDING CODE BUILDING, 5th EDITION (2014) 4.1

CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY DRAFT. FLORIDA BUILDING CODE BUILDING, 5th EDITION (2014) 4.1 CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 10 MEANS OF EGRESS

CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 10 MEANS OF EGRESS CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 10 MEANS OF EGRESS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority and building

More information

SPECIFICATIONS Aluminum Stair Nosing - Bull Nosing

SPECIFICATIONS Aluminum Stair Nosing - Bull Nosing 2009 IBC/IFC Aluminum Stair Tread Aluminum Stair Nosing - Bull Nosing ITEM NO: BPL307BNA Width 2.169, Specify Custom Length up to 12 Anti-skid stair tread marking, intended for indoor and outdoor. Apply

More information

Overview of Revised School Regulation

Overview of Revised School Regulation Office of the State Fire Marshal Overview of Revised School Regulation By: Timothee Rodrique Director, OSFM October, 2003 Training Effective Fire Prevention through Public Education Introduction! Purpose

More information

1 SAFETY ISSUES AND CONCERNS

1 SAFETY ISSUES AND CONCERNS 1 SAFETY ISSUES AND CONCERNS One of the most important issues that the design professional must consider is the personal safety of the individuals that will be using and occupying the space in the future.

More information

PRODUCTS. USLED - Safety Products - Marker & Delineators GLOW STEP. Reduce slips and falls with recycled light

PRODUCTS. USLED - Safety Products - Marker & Delineators GLOW STEP.  Reduce slips and falls with recycled light PRODUCTS Reduce slips and falls with recycled light Photoluminescent step edge, path finding, handrail and exit sign products for both indoor and out door application USLED - Safety Products - Marker &

More information

Design Approach for Performance- Based Building Codes. Scott Beverly, PE PMSFPE Fire Protection Engineer Fire & Life Safety November 2017

Design Approach for Performance- Based Building Codes. Scott Beverly, PE PMSFPE Fire Protection Engineer Fire & Life Safety November 2017 Design Approach for Performance- Based Building Codes Scott Beverly, PE PMSFPE Fire Protection Engineer Fire & Life Safety November 2017 Outline Objective Review Design Approaches Overview Australian performance

More information

A field perspective-what the inspector looks for during a Racking inspection.

A field perspective-what the inspector looks for during a Racking inspection. A field perspective-what the inspector looks for during a Racking inspection. Does existing space meet the code at time structure was built or has it been modified and now is non-conforming. LOOKING AT

More information

SUPPLEMENTAL ACCESSIBILITY NO. 5 PLAN REVIEW CHECKLIST

SUPPLEMENTAL ACCESSIBILITY NO. 5 PLAN REVIEW CHECKLIST GEORGE CHAVEZ, City Building Official DAVID YELTON, Building Inspection Manager NESTOR OTAZU, Community Preservation Manager BUILDING & SAFETY DIVISION 455 North Rexford Drive, 1 st Floor Beverly Hills,

More information

CTC MEETING #25 CHILD WINDOW SAFETY REPORT

CTC MEETING #25 CHILD WINDOW SAFETY REPORT CTC MEETING #25 CHILD WINDOW SAFETY REPORT The Child Window Safety SG has not met following the 2012 Final Action Hearing. Group B activities did not necessitate SG meetings as the activity will be limited

More information

WINDOW AND DOOR REPLACEMENT SAMPLE PLAN

WINDOW AND DOOR REPLACEMENT SAMPLE PLAN To aid in communication between yourself, the inspectors, and the plans examiners, we have prepared this sample plan to assist in the preparations of your plan for window and door replacement. Follow the

More information

High Visibility Anti Slip Tread Systems

High Visibility Anti Slip Tread Systems High Visibility Anti Slip Tread Systems Supplier and Installer of Heavy Duty Stair Treads, Nosings and Guidance Path Strips Introduction As part of a multinational civil engineering and construction organisation

More information

(1) [BE] Definitions. The following terms are defined in rule 1301: of the Administrative Code.

(1) [BE] Definitions. The following terms are defined in rule 1301: of the Administrative Code. ACTION: Final DATE: 12/04/2017 11:44 AM 1301:7-7-10 Means of egress. (A) Section 1001 General (1) 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required

More information

Compliance. Safety. Durability.

Compliance. Safety. Durability. Compliance. Safety. Durability. Products that install faster and last longer. MEA-Approved Photoluminescent Exit Path Markings for NYC Local Law 26 Compliance Code compliant products: engineered The BradyGlo

More information

EGRESS CHAPTER ,500 3 Over 2,500 4 OCCUPANT LOAD REQUIRED MEANS OF EGRESS

EGRESS CHAPTER ,500 3 Over 2,500 4 OCCUPANT LOAD REQUIRED MEANS OF EGRESS CHAPTER 4 EGRESS SECTION 401 GENERAL 401.1 General. The means of egress for new bleachers, folding and telescopic seating, and grandstands shall comply with this chapter. SECTION 402 TRAVEL 402.1 Exit

More information

Innovation Superior performance Durability Exceptional value Kinesik Engineered Products Incorporated

Innovation Superior performance Durability Exceptional value Kinesik Engineered Products Incorporated R VISIBLY BETTER Innovation Superior performance Durability Exceptional value Kinesik Engineered Products Incorporated www.kinesik.ca Kinesik Engineered Products Incorporated is a global leader of products

More information

CONCEPT DESIGN BCA REPORT

CONCEPT DESIGN BCA REPORT CONCEPT DESIGN BCA REPORT CONCEPT DESIGN DOCUMENTATION PROPOSED ZUCCOLI PRIMARY SCHOOL 13/4/17 CONCEPT DESIGN Project: Zuccoli Primary School Location: Centre Road Zuccoli NT 0382 Prepared For: MKE Architects

More information

Noise Compliance Requirements for Distribution Transformers

Noise Compliance Requirements for Distribution Transformers Noise Compliance Requirements for Distribution Transformers 1. Brief description Guideline outlining acceptable placement of new distribution transformers to ensure compliance with the Environmental Protection

More information

Supplier and Installer of Heavy Duty Stair Treads, Nosings and Guidance Path Strips

Supplier and Installer of Heavy Duty Stair Treads, Nosings and Guidance Path Strips Supplier and Installer of Heavy Duty Stair Treads, Nosings and Guidance Path Strips Robust and Hardwearing Anti Slip Tread Systems Introduction As part of a multinational civil engineering and construction

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information

General Building Information

General Building Information Software Module s Description Page 1 General Building Information BUILDING AREA AND HEIGHT - This module designed to determine the height and area of buildings on the basis of occupancy group classification

More information

Work Group Item Stairways serving an occupant load of less than 50 shall have a width of not less than 36 inches (914 mm).

Work Group Item Stairways serving an occupant load of less than 50 shall have a width of not less than 36 inches (914 mm). IBC-12/13 1009.1, 1009.4, 1009.7.2, 1009.7.4, 1009.8, 1009.10, 1009.15 (IFC [B] 1009.1, 1009.4, 1009.7.2, 1009.7.4, 1009.8, 1009.10, 1009.15) Proponent: S. Bajnai, Chesterfield County, VA, ICC Building

More information

Guarding to openable windows with low cill heights

Guarding to openable windows with low cill heights BCA Technical Guidance Note 16 Rev 1 Sept 2016 Guarding to openable windows with low cill heights Purpose BCA technical guidance notes are for the benefit of its members and the construction industry,

More information

PRESCRIPTIVE COMPLIANCE METHOD

PRESCRIPTIVE COMPLIANCE METHOD CHAPTER 3 PRESCRIPTIVE COMPLIANCE METHOD [B] SECTION 301 GENERAL 301.1 Scope. The provisions of this chapter shall control the alteration, repair, addition and change of occupancy of existing structures,

More information

LIGHTING REPORT APPENDIX ENVIRONMENTAL IMPACT STATEMENT

LIGHTING REPORT APPENDIX ENVIRONMENTAL IMPACT STATEMENT LIGHTING REPORT APPENDIX T ENVIRONMENTAL IMPACT STATEMENT Site Infrastructure Lighting Report BORAL Gold Coast Quarry, Reedy Creek B12119ESR002 April 2013 LIGHTING REPORT for ELECTRICAL SERVICES at BORAL

More information

-=== Building Safety Departnlent 'Neil Avenue, Room 202 Cheyenne, WY Phone: (307) Fax: (307) RAMPS

-=== Building Safety Departnlent 'Neil Avenue, Room 202 Cheyenne, WY Phone: (307) Fax: (307) RAMPS Building Safety Departnlent 2101 0 'Neil Avenue, Room 202 Cheyenne, WY 82001 Phone: (307) 637-6265 Fax: (307) 637-6366 A COMMUNITY -=== II January 24,2017 OF CHOICE RAMPS This handout was prepared in an

More information

NOTE: Some guidance on a performance approach to natural ventilation systems design is provided in the Supplement to this Standard.

NOTE: Some guidance on a performance approach to natural ventilation systems design is provided in the Supplement to this Standard. 19 SECTION 3 NATURAL VENTILATION 3.1 SCOPE OF SECTION This Section specifies the means of achieving the quantity of outdoor air required in a naturally ventilated enclosure. The provisions described include

More information

Project Address Applicant: (Please Print) Plan review Engineer: Phone: Date

Project Address Applicant: (Please Print) Plan review Engineer: Phone: Date BUILDING AND SAFETY Tenant Improvement Checklist Project Address Applicant: (Please Print) Plan review Engineer: Phone: Date APPLICATION The following items will be required at the permit counter before

More information

APPENDIX B SIGNAGE STANDARDS

APPENDIX B SIGNAGE STANDARDS APPENDIX B SIGNAGE STANDARDS Post-merger, The University of Toledo has two signage design specifications. The former "Black & White" signage system (described in Part 1) is being phased out and gradually

More information

SITE ACCESSIBILITY AND PARKING

SITE ACCESSIBILITY AND PARKING SITE ACCESSIBILITY AND PARKING The purpose of this handout is to clarify the requirements of site accessibility under the 2013 California Building Codes, Specifically, Section 11B. Each lot or parking

More information

Verification Methods For New Zealand Building Code Clause F6 Visibility in Escape Routes

Verification Methods For New Zealand Building Code Clause F6 Visibility in Escape Routes Acceptable Solutions and Prepared by the Ministry of Business, Innovation and Employment Verification Methods For New Zealand Building Code Clause F6 Visibility in Escape Routes Third Edition F6 Status

More information

Supplementary Standard SB-12. Energy Efficiency For Housing

Supplementary Standard SB-12. Energy Efficiency For Housing Ministry of Municipal Affairs and Housing Building and Development Branch 2006 Building Code - Supplementary Standards Supplementary Standard SB-12 Energy Efficiency For Housing January 1, 2012 update

More information

All electrical equipment must be tagged and tested by a professional and must not create any hazards to others when installed.

All electrical equipment must be tagged and tested by a professional and must not create any hazards to others when installed. Custom Stand Guidelines When building a custom stand, there are a number of rules and regulations that you must comply with. The attached document details them all for you. To get you started, here are

More information

2007 Title 24 Accessibility Code Updates and ADA Issues

2007 Title 24 Accessibility Code Updates and ADA Issues 2007 Title 24 Accessibility Code Updates and ADA Issues C.A.S.H. Workshop June 2007 Introduction Update on ADA Certification of the California Building Code Overview of significant changes to accessibility

More information

MEANS OF EGRESS CHAPTER 10

MEANS OF EGRESS CHAPTER 10 CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this

More information