1 BOARD OF BUILDING AND SAFETY COMMISSIONERS HELENA JUBANY PRESIDENT VAN AMBATIELOS VICE-PRESIDENT E. FELICIA BRANNON VICTOR H. CUEVAS GEORGE HOVAGUIMIAN CITY OF LOS ANGELES CALIFORNIA ANTONIO R. VILLARAIGOSA MAYOR DEPARTMENT OF BUILDING AND SAFETY 201 NORTH FIGUEROA STREET LOS ANGELES, CA RAYMOND S. CHAN, C.E., S.E. SUPERINTENDENT OF BUILDING INTERIM GENERAL MANAER HILTI, Inc. RESEARCH REPORT: RR S. 122 E. Avenue (CSI # ; ; ) Tulsa, OK BASED UPON ICC EVALUATION SERVICE Attn: Andrew Liechti REPORT NO. ESR-2269 (918) REEVALUATION DUE DATE: September 1, 2014 Issued date: March 1, 2014 Code: 2014 LABC GENERAL APPROVAL Clerical Modification Hilti Low-Velocity X-U and X-U 15 Powder Driven Fasteners. DETAILS The above products/assemblies are approved when in compliance with the description, identification and conditions of use in Report No.ESR-2269, reissued December 1, 2012, and revised May 201 of the ICC Evaluation Service, Incorporated. That report, in its entirety, is attached and made a part of this general approval. The parts of Report No.ESR-2269 marked by the asterisks are modified by the Los Angeles Building Department from this approval. The approval is subject to the following conditions: 1. The fasteners shall not be used to resist seismic loads, except when used with architectural, electrical and mechanical components as described in Section of ASCE 7-10 and used to fasten wood structural panel diaphragms to steel members as described in Sections 4.1. and of ICC-ES ESR-2269 and as follows: a) Concrete base materials: The Hilti fasteners installed in concrete may be used to support distributed systems and distribution systems where the service load on any individual fastener does not exceed the lesser of 90 lbf or the published allowable load shown in Tables 2, and 4 of the attached ICC-ES ESR-2269, as applicable. RR Page 1 of LADBS G-5 (Rev.02/20/14) AN EQUAL EMPLOYMENT OPPORTUNITY - AFFIRMATIVE ACTION EMPLOYER

2 HILTI, Inc. RE: Hilti Low-Velocity X-U and X-U 15 Powder Driven Fasteners b) Steel base materials: The Hilti fasteners installed in steel may be used where the service load on any individual fastener does not exceed the lesser of 250 lbf or the published allowable load shown in Table 2 of the attached ICC-ES ESR The Hilti fasteners may also be used in conjunction with wood structural panel diaphragms in accordance with Sections.5, 4.1. and of ICC-ES ESR c) For interior, nonstructural walls that are not subject to sustained tension loads and are not a bracing application, the power-driven fasteners may be used to attach steel track to concrete or steel in all Seismic Design Categories. In Seismic Design Categories D, E and F, the allowable shear load due to transverse pressure shall be no more than 90 pounds when attaching to concrete; or 250 pounds when attaching to steel. Substantiating calculations shall be submitted addressing the fastener- to-base-material capacity and the fastener-to attached-material capacity. Interior nonstructural walls are limited to locations where bearing walls, shear walls or braced walls are not required by the approved plans. The design load on the fastener must not exceed the allowable load established in the attached ICC-ES ESR-2269 for the concrete or steel base material. 2. The fasteners shall not be used in cracked concrete or cracked masonry.. The stress increases described in Section of the 2014 LABC are not allowed for wind loads acting alone or when combined with gravity loads. No increase is allowed for gravity loads acting alone. 4. Submit calculation to demonstrate that the applied loads are less than the allowable loads described in this report. Calculation must be reviewed and approved by plan check engineer. Calculations must be prepared, sealed and signed by a civil or structural engineer registered in the State of California. EXCEPTION: Anchors used for the installation of mechanical, plumbing and electrical equipment shall be designed and detailed on a plan prepared by an engineer licensed by the state of California. 5. The allowable values listed in the attached report and tables are for the fasteners only. Connected members shall be checked for their capacity (which may govern). 6. The low velocity fasteners installed through the underside of steel deck at the ribs and into minimum 000 psi lightweight concrete shall have minimum edge distance of 7/8" from the edge of the deck ribs and 6" from the end of the deck. Concrete fill above top ribs shall be a minimum of 2 1/2 inches. 7. The fasteners shall be installed per the manufacturer's instructions, a copy of which shall be available at each job site. 8. Use of Hilti X-U and X-U 15 fasteners is limited to dry interior locations. RR Page 2 of

3 HILTI, Inc. RE: Hilti Low-Velocity X-U and X-U 15 Powder Driven Fasteners 9. Use of Hilti X-U and X-U 15 fasteners in contact with fire retardant treated wood is allowed in accordance with Section of the 2011 and 2014 LABC in dry interior locations only. Under 2008 LABC the use of X-U and X-U 15 fasteners in contact with preservative-treated wood or fire-retardant-treated wood is not permitted. 10. All fasteners are identified by an H imprinted on the fastener head. Where applicable the word Hilti is stamped on the steel washers. All fasteners are packaged in containers noting the fastener type, size, manufacturer s name, and evaluation report number (ESR- 2269). DISCUSSION The Clerical Modification is to update the code to the 2014 LABC. The report is in compliance with the 2014 City of Los Angeles Building Code. The approval is based on tests conforming to AC-70, dated February 201. This general approval will remain effective provided the Evaluation Report is maintained valid and unrevised with the issuing organization. Any revision to the report must be submitted to this Department for review with appropriate fee to continue the approval of the revised report. Addressee to whom this Research Report is issued is responsible for providing copies of it, complete with any attachments indicated, to architects, engineers and builders using items approved herein in design or construction which must be approved by Department of Building and Safety Engineers and Inspectors. This general approval of an equivalent alternate to the Code is only valid where an engineer and/or inspector of this Department has determined that all conditions of this Approval have been met in the project in which it is to be used. ALLEN PEERY, Chief Engineering Research Section 201 N. Figueroa St., Room 880 Los Angeles, CA Phone Fax BG RR25675/MSWord2010 R0/10/14 5C2/ /192. Attachments: ICC ES Report No.ESR-2269 (7 Pages). RR Page of

4 ICC-ES Evaluation Report (800) (562) ESR-2269* Reissued December 1, 2012 This report is subject to renewal February 1, A Subsidiary of the International Code Council DIVISION: CONCRETE Section: Concrete Accessories Section: Concrete Anchors DIVISION: MASONRY Section: Masonry Anchors DIVISION: METALS Section: Metal Fastenings DIVISION: WOOD, PLASTICS AND COMPOSITES Section: Wood, Plastic, and Composite Fastenings REPORT HOLDER: HILTI, INC SOUTH 122 nd EAST AVENUE TULSA, OKLAHOMA (800) HNATechnicalServices@hilti.com EVALUATION SUBJECT: HILTI LOW-VELOCITY X-U AND X-U 15 UNIVERSAL POWDER DRIVEN FASTENERS 1.0 EVALUATION SCOPE Compliance with the following codes: 2012 International Building Code (IBC) 2012 International Residential Code (IRC) 2009, 2006 and 200 IBC* 2009, 2006 and 200 IRC* *Codes indicated with an asterisk are addressed in Section 8.0. Property evaluated: Structural 2.0 USES 2.1 General: The Hilti X-U fasteners are used to attach wood, light gage steel, and other building elements to normal-weight and sand-lightweight concrete, steel deck panels with sandlightweight concrete fill, concrete masonry and steel base materials. The Hilti X-U 15 fasteners are used to attach light gage steel and other building elements to steel. The *Revised May 201 fasteners are alternatives to the cast-in-place anchors described in IBC Section1908 for placement in concrete; the embedded anchors described in Section of TMS 402/ACI 50/ASCE 5 (which is referenced in IBC Section 2107) for placement in grouted masonry; and the welds and bolts used to attach materials to steel, described in IBC Sections and , respectively. The fasteners may be used where an engineered design is submitted in accordance with IRC Section R Horizontal Diaphragms: The Hilti X-U fasteners may be used as alternates to 10d common nails for fastening wood structural panel horizontal diaphragms to structural steel members..0 DESCRIPTION.1 Fasteners:.1.1 X-U: The X-U fasteners are powder driven fasteners made from hardened steel complying with the manufacturer s quality documentation, austempered to a Rockwell C nominal hardness of 58 and zinc-plated in accordance with ASTM B6 SC 1, Type III. The fasteners have a shank diameter of inch (4.0 mm), a head diameter of 0.2 inch (8.2 mm) and a knurled tip, and come in lengths ranging from 0.6 inch to 2.8 inches (16 to 72 mm). See Figure 1 for the fastener configuration..1.2 X-U 15: The X-U 15 fasteners are powder driven fasteners made from hardened steel complying with the manufacturer s quality documentation, austempered to a Rockwell C nominal hardness of 59 and zinc plated in accordance with ASTM B6 SC 1, Type III. The fasteners have a shank diameter of inch (.7 mm), a head diameter of 0.2 inch (8.2 mm) and a shank length of 0.6 inch (16 mm). See Figure 2 for the fastener configuration..2 Concrete: Normal-weight and sand-lightweight concrete must conform to IBC Chapter 19 or IRC Section R402.2, as applicable. The minimum concrete compressive strength at the time of fastener installation is noted in the tables of this report.. Masonry: Masonry must be comprised of normal-weight or lightweight concrete masonry units (CMUs) complying with ASTM C90. Mortar must comply with ASTM C270 Type S in accordance with IBC Section or IRC Section R607, as applicable. The CMUs must have a minimum width of 8 inches (20 mm). Where specified in Table 6 of this report, masonry construction must be fully grouted and must have minimum prism strength, f m, of 1,500 psi (10. MPa) at the time of fastener installation. Grout must ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 201 Page 1 of

5 ESR-2269 Most Widely Accepted and Trusted Page 2 of 7 comply with Article 2.2 of TMS 602/ACI 50.1/ASCE 6 (referenced in IBC Section 210.1) or IRC Section R , as applicable..4 Steel Substrates: Structural steel must comply with the minimum strength requirements of ASTM A6, ASTM A572 Grade 50 or ASTM A992, and have a thickness as shown in Table 2. Steel deck panels comply with a code-referenced material standard and have the minimum thickness and minimum yield strength noted in Table 5. See Figures through 5 for panel configuration requirements..5 Wood Structural Panel Horizontal Diaphragms:.5.1 Wood Structural Panel: Wood structural panels must have a minimum thickness of 15 / 2 inch (11.9 mm) and must comply with the requirements of Section of AF&PA SDPWS (which is referenced in IBC Section 205)..5.2 Structural Steel Supports: Structural steel framing members supporting the wood structural panel diaphragm must comply with the minimum strength requirements of ASTM A6, ASTM A572 Grade 50 or ASTM A992, and have a thickness greater than or equal to / 16 inch (4.8 mm). 4.0 DESIGN AND INSTALLATION 4.1 Design: Allowable Loads: The allowable shear and tension loads for the X-U and X-U 15 fasteners installed in steel, and the X-U fasteners installed in normal-weight concrete, sand-lightweight concrete, sand-lightweight concrete-filled steel deck and masonry, can be found in Tables 2 through 6 as summarized in Table 1. The stress increases and load reductions described in IBC Section are not allowed for wind loads acting alone or when combined with gravity loads. No increase is allowed for vertical loads acting alone. Allowable loads apply to the connection of the fastener to the base material only. Design of the connection to the attached material must comply with the applicable requirements of the IBC. Allowable loads for fasteners subjected to combined shear and tension forces are determined by the following formula: where: (p/p a ) + (v/v a ) 1 p = Actual tension load, lbf (N). P a = Allowable tension load, lbf (N). v = Actual shear load, lbf (N). V a = Allowable shear load, lbf (N) Wood to Steel, Concrete, or Masonry: Reference lateral design values for fasteners determined in accordance with Part 11 of ANSI/AF&PA NDS are applicable to Hilti fasteners of equal or greater diameters. The wood element must be considered to be the side member. The fastener bending yield strength is allowed to be taken as the value noted in the NDS based on the fastener diameter. Hilti carbon steel fasteners may be used in contact with fire-retardant-treated wood in dry, interior locations only, in accordance with IBC Section and Hilti s recommendations. Use of fasteners in contact with preservative-treated wood or fire-retardant-treated wood in exterior applications is outside the scope of this report Wood Structural Panel Horizontal Diaphragms: When the X-U fastener is used to fasten wood structural panels to steel members, the fastener is recognized as equivalent to a 10d common nail. Diaphragm design, including fastener spacing, diaphragm capacity and diaphragm deflection, must comply with Section 4.2 of AF&PA SDPWS (which is referenced in IBC Section 205.1) and IBC Section Seismic Considerations: Use with Structural Components: Resistance to seismic loads is outside the scope of this report. Therefore, except as noted in Section 4.1., the suitability of the Hilti fasteners for use with structural components that are subjected to seismic loads is outside the scope of this report Use with Nonstructural Components: Seismic load resistance is outside the scope of this report, except when used with architectural, mechanical and electrical components described in Section of ASCE 7, and as follows: Concrete base materials: The Hilti fasteners installed in concrete may be used to support acoustical tile or lay-in panel suspended ceiling systems, distributed systems and distribution systems where the service load on any individual fastener does not exceed the lesser of 90 lbf (400 N) or the published allowable load shown in Tables, 4 and 5, as applicable. Steel base materials: The Hilti fasteners installed in steel may be used where the service load on any individual fastener does not exceed the lesser of 250 lbf (1112 N) or the published allowable load shown in Table 2. The Hilti fasteners may also be used in conjunction with wood structural panel diaphragms in accordance with Sections.5, 4.1. and For interior, nonstructural walls that are not subject to sustained tension loads and are not a bracing application, the power-driven fasteners may be used to attach steel track to concrete or steel in all Seismic Design Categories. In Seismic Design Categories D, E, and F, the allowable shear load due to transverse pressure shall be no more than 90 pounds (400 N) when attaching to concrete; or 250 pounds (1,112N) when attaching to steel. Substantiating calculations shall be submitted addressing the fastener-to-base-material capacity and the fastener-to-attached-material capacity. Interior nonstructural walls are limited to locations where bearing walls, shear walls or braced walls are not required by the approved plans. The design load on the fastener must not exceed the allowable load established in this report for the concrete or steel base material. 4.2 Installation: General: The X-U and X-U 15 fasteners must be installed in accordance with this report and the Hilti, Inc., published installation instructions. A copy of these instructions must be available on the jobsite at all times during installation. Installation must be limited to dry, interior locations. Fastener placement requires the use of a low-velocity powder-actuated tool in accordance with Hilti, Inc. recommendations. Installers must be certified by Hilti and have a current, Hilti-issued, operator s license Fastening to Steel: When installed in steel, minimum spacing between fasteners must be 1 inch (25.4 mm) and minimum edge distance must be 1 / 2 inch (12.7 mm).

6 ESR-2269 Most Widely Accepted and Trusted Page of Fastening to Concrete: Fasteners must be driven into the concrete after the concrete attains the concrete strength specified in the tables of this report. Minimum spacing between fasteners must be 4 inches (102 mm) and minimum edge distance must be inches (76 mm). Unless noted otherwise in this report, concrete thickness must be a minimum of three times the penetration depth of the fastener DX-KWIK System: Installation of the X-U fastener into normal-weight concrete, using the Hilti DX-KWIK system as an alternate procedure, requires the drilling of a pilot hole using a Special DX-KWIK drill bit (TX-C) supplied by Hilti, Inc., prior to the installation of the fastener with the powder-actuated tool Fastening to Sand-lightweight Concrete-filled Steel Deck Panels: Installation in sand-lightweight concrete-filled steel deck panels must comply with Figures through 5. Minimum distances from fastener centerline to rolled deck panel flute edges must be as depicted in Figures through Fastening to Masonry: Fasteners must be driven into the masonry after the mortar and grout materials have attained the specified strength. Fasteners must be located in accordance with Table Wood Structural Panel Diaphragms: The wood structural panels must be fastened to the steel members at the spacing specified in the design. When used, the optional steel strap is placed on top of the panels and the fasteners are driven through the strap and panel into the supporting steel member. The minimum distance from the centerline of the fasteners to the edge of the panel is / 8 inch (9.5 mm). Fastener penetration and distance to the edge of the supporting steel member must be as described in Section See Figure 7 for a typical installation detail showing one row of fasteners. Multiple rows of fasteners may be installed if required by the design. The remainder of the diaphragm must be constructed in accordance with the code. 5.0 CONDITIONS OF USE The Hilti X-U and X-U 15 fasteners described in this report comply with, or are suitable alternatives to what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 The fasteners are manufactured and identified in accordance with this report. 5.2 Fastener installation complies with this report and the Hilti, Inc., instructions. In the event of conflict between this report and the Hilti, Inc., published instructions, this report governs. 5. Calculations demonstrating that the actual loads are less than the allowable loads described in Section must be submitted to the code official for approval. The calculations must be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. 5.4 Refer to Section for seismic considerations. 5.5 The use of fasteners is limited to installation in uncracked concrete or masonry. Cracking occurs when f t > f r due to service loads or deformations. 5.6 Use of fasteners is limited to dry, interior locations. 5.7 Installation must comply with Section regarding fasteners in contact with preservative-treated and fireretardant-treated wood. 5.8 Installers must be certified by Hilti, Inc., and have a current, Hilti-issued, operator s license. 6.0 EVIDENCE SUBMITTED Data in accordance with the ICC-ES Acceptance Criteria for Fasteners Power-driven into Concrete, Steel and Masonry Elements (AC70), dated February IDENTIFICATION Each package of fasteners is labeled with the fastener type and size, the manufacturer s name (Hilti) and the evaluation report number (ESR-2269). An H, for Hilti, is imprinted on the head of the fastener as shown in Figures 1 and OTHER CODES 8.1 Scope: In addition to the 2012 IBC and 2012 IRC addressed in Sections 2.0 through 7.0, the products described in this report were evaluated for compliance with the requirements of the following codes: 2009, 2006 and 200 International Building Code (2009, 2006 and 200 IBC) 2009, 2006 and 200 International Residential Code (2009, 2006 and 200 IRC) 8.2 Uses: General: The Hilti X-U and X-U 15 fasteners are used to connect materials as described in Section 2.0. The fasteners are alternatives to the cast-in-place anchors described in 2009 and 2006 IBC Sections 1911 and 1912 and 200 IBC Sections 1912 and 191 for placement in concrete; the embedded anchors described in Section 2.1 of ACI 50 (which is referenced in 2009, 2006 and 200 IBC Section 2107) for placement in grouted masonry; and the welds and bolts used to attach materials to steel, described in 2009, 2006 and 200 IBC Sections and , respectively. The fasteners may be used where an engineered design is submitted in accordance with 2009, 2006 and 200 IRC Section R01.1., as applicable Horizontal Diaphragms: See Section Description: 8..1 Fasteners: See Section Concrete: See Section Masonry: See Section.. Under the 2009 and 2006 IBC, Type S mortar must comply with IBC Section or IRC Section R607, as applicable; grout must comply with IBC Section or IRC Section R , as applicable. Under the 200 IBC, mortar and grout must comply with Sections and , respectively Steel Substrates: See Section Wood Structural Panel Diaphragms: See Section Design and Installation: Design: Allowable Loads: See Section Wood to Steel, Concrete, or Masonry: See Section 4.1.2, with the following modifications: Under the 2009 IBC: See Section regarding use in preservative-treated and fire-retardant-treated wood. Under the 2006 and 200 IBC: Use of carbon steel fasteners in contact with preservative-treated or fireretardant-treated wood is outside the scope of this report.

7 ESR-2269 Most Widely Accepted and Trusted Page 4 of Wood Structural Panel Horizontal Refer to Section regardingg use in Diaphragms: See Section preservative-treated and fire-retardant-treated wood Seismic Considerations: See Section Evidence Submitted: Installation: See Section Conditions of Use: See Section 5.0, and the following: See Section Identification: : See Section 7.0. FIGURE 1 HILTI X-U FASTENER FIGURE 2 X-U 15 FASTENER TABLE 1 APPLICATION DESCRIPTIONS BASE MATERIAL POWDER-ACTUATED FASTENER INSTALLATION METHOD LOAD DATA Steel X-U and X-U 15 Fasteners Table 2 Normal-Weight Concrete Table DX-KWIK Table 4 Sand-lightweight Concrete -inch Deep Composite Floor Deck Panel 1 1 / 2 -inch Deep Composite Floor Deck Panel Table 5 Hollow Concrete Masonry Units Grout-Filled Concrete Masonry Units Table 6 TABLE 2 ALLOWABLE LOADS FOR FASTENERS DRIVEN INTO STEEL 1,2 (lbf) FASTENER FASTENER SHANK STEEL THICKNESS DESCRIPTION DIAMETER / 1 16 / 4 / 1 8 / 2 > / 4 Tensionn Shear Tension Shear Tension Shear Tension Shear Tension Shear X-U X-U For SI: 1 inch = 25.4 mm, 1 lbf = 4.44 N. 1 Allowable load capacities are based on base steel with minimum yield strength (F y ) of 6 ksi and minimum tensile strength (F u ) of 58 ksi. 2 The fasteners mustt be driven to where the point of the fastener penetrates through the steel base material, unless otherwise noted. Based upon minimum point penetration of / 8 -inch. 4 Based upon minimum point penetration of 1 / 2 -inch. 5 Based upon minimum point penetration of 15 / 2 -inch. TABLE ALLOWABLE LOADS FOR FASTENERS DRIVEN INTO NORMAL-WEIGHT CONCRETE 1,2 (lbf) FASTENER DESCRIPTION FASTENER SHANK DIAMETER X-U MINIMUM EMBEDMENT / / psi Tension Shear / / CONCRETE COMPRESSIVE STRENGTH For SI: 1 inch = 25.4 mm, 1 lbf = 4.44 N, 1 psi = 6895 Pa. 1 Fasteners must nott be driven until the t concrete has reached the designated minimum compressive strength. 2 Concrete thicknesss must be a minimum of times the embedment depth of the fastener. TABLE 4 ALLOWABLE LOADS FOR FASTENERSS 4000 psi psi Tensionn Shear Tension Shear

8 ESR-2269 Most Widely Accepted and Trusted Page 5 of 7 FASTENER DESCRIPTION FASTENER X-U 47 P8 w/ DX-KWIK DRIVEN INTO NORMAL-WEIGHT CONCRETE USING DX-KWIK 1,2, (lbf) SHANK DIAMETER For SI: 1 inch = 25.4 mm, 1 lbf = 4.4 N, 1 psi = 6895 Pa. MINIMUM EMBEDMENT CONCRETE COMPRESSIVE STRENGTH 4,000 psi 6,000 psi Tension Shear Tension Shear / is installed using the DX-KWIK drilled pilot hole installation procedure described in Section Pilot holes must not be drilled until the concrete has reached the designated minimum compressive strength. Concrete thickness must be a minimum of times the embedment depth of the fastener. FASTENER FASTENER DESCRIPTION TABLE 5 ALLOWABLE LOADS FOR FASTENERS DRIVEN INTO MINIMUM f c = 000 psi STRUCTURAL SAND-LIGHTWEIGHT CONCRETE 1 (lbf) SHANK DIAMETER MINIMUM EMBEDMENT Installed into Concrete 4 Tension Shear FASTENER LOCATION 5 Installed Through Metal Deck Panel into Concrete -inch deep composite floor deck panel 2 Tension Upper Flute Lower Flute Shear 1 1 / 2 -inch deep composite floor deck panel Tension / X-U / / For SI: 1 inch = 25.4 mm, 1 lbf = 4.4 N, 1 psi = 6895 Pa. 1 Fasteners must not be driven until the concrete has reached the designated minimum compressive strength. 2 The steel deck profile for the -inch deep composite floor deck panel has a minimum thickness of inch (0.91 mm) and a minimum F y of ksi. Lower and upper flute width must be a minimum of 4 1 / 2 inches. Figure shows the nominal flute dimensions, fastener locations, and load orientations for the deck panel profile. Sand-lightweight concrete fill above top of steel deck panel must be minimum 1 / 4 inches thick. The steel deck profile for the 1 1 / 2 -inch deep composite floor deck panel has a minimum thickness of inch (0.91 mm) and a minimum F y of ksi. Lower flute and upper flute widths must be a minimum of 1 / 4 -inch and 1 / 2 -inch, respectively. This deck panel may also be inverted as shown in Figure 5. Figures 4 and 5 show the nominal flute dimensions, fastener locations, and load orientations for the deck panel profile. Sand-lightweight concrete fill above top of steel deck panel must be minimum 2 1 / 2 inches thick. 4 Concrete thickness must be a minimum of times the embedment depth of the fastener. 5 Minimum allowable spacing parallel to the deck flutes is 5.1 inches. Upper Flute Lower Flute Shear FASTENER FASTENER DESCRIPTION TABLE 6 ALLOWABLE LOADS FOR FASTENERS DRIVEN INTO CONCRETE MASONRY UNITS 1,2, (lbf) SHANK DIAMETER MINIMUM EMBEDMENT HOLLOW CMU GROUT-FILLED CMU Face Shell Mortar Joint 4 4 Top of Face Shell Mortar Joint Grouted Cell 6 Tension Shear 7 Tension Shear 5 Tension Shear 7 Tension Shear 5 Tension Shear 7 X-U The tabulated allowable load values are for fasteners installed in masonry conforming to the requirements of Section. of this report. 2 No more than one low-velocity fastener may be installed in an individual concrete masonry unit cell. The fastener must be installed a minimum of 4 inches from the edge of the wall. Fastener can be located in the face shell or mortar joint as shown in Figure 6 of this report. 4 Fasteners must be installed a minimum of 8 inches from the end of the wall. Multiple fasteners in a bed joint must be spaced a minimum of 8 inches. 5 Shear load direction can be horizontal or vertical (bed joint or T-Joint) along the CMU wall plane. 6 Fastener located in center of grouted cell installed vertically. 7 Shear load can be in any direction.

9 ESR-2269 Most Widely Accepted and Trusted Page 6 of 7 FIGURE HILTI FASTENER LOCATION IN -INCH-DEEPP COMPOSITE FLOOR DECK PANEL, NORMAL DECK PANEL PROFILE ORIENTATION FIGURE 4 FASTENER LOCATION IN 1 1 / 2 -INCH-DEEP COMPOSITE FLOOR DECK PANEL, NORMAL DECK PANEL PROFILE ORIENTATION FIGURE 5 HILTI FASTENER LOCATION IN 1 1 / 2 -INCH-DEEP COMPOSITE FLOOR DECK PANEL, INVERTED DECK PANEL PROFILE ORIENTATION

10 ESR-2269 Most Widely Accepted and Trusted Page 7 of 7 FIGURE 6 LOCATIONS (NONSHADEDD AREAS) FOR HILTI FASTENERS IN CMU WALLS FIGURE 7 WOOD STRUCTURAL PANEL DECK ATTACHMENT TO STEEL LEDGER WITH HILTI X-U UNIVERSAL POWDER DRIVEN FASTENER

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information

ESR-2269 Reissued November 1, 2008 This report is subject to re-examination in one year.

ESR-2269 Reissued November 1, 2008 This report is subject to re-examination in one year. Reissued November, 008 This report is subject to re-examination in one year. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office 60 Workman Mill Road, Whittier, California 9060 (6) 699-0

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS INTERIM PRESIDENT E. FELICIA BRANNON JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI MAYOR

More information

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015 0 ICC ES Report ICC ES (800) 42 6587 (562) 699 054 www.icc es.orgg 000 Most Widely Accepted and Trusted ESR 2269 Reissued 02/205 This report is subject to renewal 02/207. DIVISION: 0 00 00 CONCRETE SECTION:

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS MARSHA L. BROWN PRESIDENT VAN AMBATIELOS VICE-PRESIDENT VICTOR H. CUEVAS HELENA JUBANY ELENORE A. WILLIAMS CITY OF LOS ANGELES CALIFORNIA ANTONIO R. VILLARAIGOSA

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS HELENA JUBANY PRESIDENT VAN AMBATIELOS VICE-PRESIDENT E. FELICIA BRANNON VICTOR H. CUEVAS GEORGE HOVAGUIMIAN CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI MAYOR

More information

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW VELOCITY X-U AND X-U 15 UNIVERSAL FASTENERS AND X-P CONCRETE FASTENERS

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW VELOCITY X-U AND X-U 15 UNIVERSAL FASTENERS AND X-P CONCRETE FASTENERS 0 ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org Most Widely Accepted and Trusted ESR-2269 Reissued 02/2017 Revised 11/2018 This report is subject to renewal 02/2019.

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS HELENA JUBANY PRESIDENT VAN AMBATIELOS VICE-PRESIDENT E. FELICIA BRANNON VICTOR H. CUEVAS SEPAND SAMZADEH CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI MAYOR DEPARTMENT

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS HELENA JUBANY PRESIDENT VAN AMBATIELOS VICE-PRESIDENT E. FELICIA BRANNON VICTOR H. CUEVAS SEPAND SAMZADEH CITY OF LOS ANGELES CALIFORNIA ANTONIO R. VILLARAIGOSA

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS MARSHA L. BROWN PRESIDENT PEDRO BIRBA VICE-PRESIDENT VAN AMBATIELOS HELENA JUBANY ELENORE A. WILLIAMS CITY OF LOS ANGELES CALIFORNIA ANTONIO R. VILLARAIGOSA MAYOR

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2269 Reissued 02/2017 This report is subject to renewal 02/2019. DIVISION: 03 00

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1663 Reissued 03/2017 This report is subject to renewal 03/2019. DIVISION: 03 00 00 CONCRETE

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS HELENA JUBANY PRESIDENT VAN AMBATIELOS VICE-PRESIDENT E. FELICIA BRANNON VICTOR H. CUEVAS GEORGE HOVAGUIMIAN CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI MAYOR

More information

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS 0 ICC-ES Evaluation Report ICC-ES 000 (800) 42-6587 (562) 699-054 www.icc-es.org Most Widely Accepted and Trusted ESR-66 Reissued 0/207 Revised 2/208 This report is subject to renewal 0/209. DIVISION:

More information

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3833 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 03 00

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 42-6587 (562) 699-054 www.icc-es.org ESR-1752 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 0 00 00

More information

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 5000 SERIES FASTENERS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 5000 SERIES FASTENERS 0 ICC-ES Report ICC-ES (800) 42-6587 (562) 699-054 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-45 Reissued 06/206 This report is subject to renewal 06/207 DIVISION: 0 00 00CONCRETE SECTION:

More information

CALIFORNIA ERIC GARCETTI MAYOR

CALIFORNIA ERIC GARCETTI MAYOR BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information

ESR ICC Evaluation Service, Inc. Reissued September 1, 2008 This report is subject to re-examination in one year.

ESR ICC Evaluation Service, Inc. Reissued September 1, 2008 This report is subject to re-examination in one year. ESR- Reissued September, 00 This report is subject to re-examination in one year. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 0 Workman Mill Road, Whittier, California 900 #

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2184 Reissued 06/2017 This report is subject to renewal 06/2019. DIVISION: 03 00

More information

where: P s = Applied service tension load, pounds (kg). P t V s V t

where: P s = Applied service tension load, pounds (kg). P t V s V t Æ Æ Æ Æ Æ Æ Æ Æ Æ ESR-1752 Most Widely Accepted and Trusted Page 2 of 7 3.1.7 X-S16P8TH: The X-S16P8TH fastener is a powder actuated fastener for installation into steel. It has a shank diameter of 0.145

More information

ESR-2036 Reissued May 1, 2013 This report is subject to renewal June 1, 2015.

ESR-2036 Reissued May 1, 2013 This report is subject to renewal June 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 4-6587 (56) 699-054 ESR-06 Reissued May, 0 This report is subject to renewal June, 05. A Subsidiary of the International Code Council DIVISION: 0 00 00 CONCRETE

More information

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: BLUE POINT FASTENING, INC YORBA COURT CHINO, CALIFORNIA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1530 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 03 00

More information

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3275 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 03 00

More information

CALIFORNIA ERIC GARCETTI MAYOR

CALIFORNIA ERIC GARCETTI MAYOR BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information

FROM: PROPOSED SUBSTITUTION: Use HILTI X-CW Ceiling Wire for Suspended Ceiling Systems

FROM: PROPOSED SUBSTITUTION: Use HILTI X-CW Ceiling Wire for Suspended Ceiling Systems DATE: PROJECT: TO: FROM: SUBJECT: HILTI X-CW CEILING WIRE FASTENER SUBSTITUTION REQUEST SPECIFICATION TITLE: SECTION: PAGE: ARTICLE/PARAGRAPH: DESCRIPTION: DESIGN DETAIL NO.: PROPOSED SUBSTITUTION: Use

More information

Trusted ICC ES HILTI, INC. Evaluation. report, or as to any. ICC-ES Evaluation

Trusted ICC ES HILTI, INC. Evaluation. report, or as to any. ICC-ES Evaluation 0 ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg Most Widely Accepted and Trusted ESR 2347 Reissued 12/2017 Revised 09/2018 This report is subject to renewal 12/2019.

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1678 Reissued 03/2017 This report is subject to renewal 03/2018. DIVISION: 04 00 00 MASONRY

More information

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 42 6587 (562) 699 054 www.icc es.org ESR 247 Reissued 2/207 This report is subject to renewal 2/209. DIVISION: 05 00 00 METALS

More information

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 100 PLANO, TEXAS 75024

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 100 PLANO, TEXAS 75024 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-2347 Reissued 12/2015 This report is subject to renewal 12/2017. DIVISION: 05 00 00 METALS SECTION:

More information

REPORT HOLDER: JAACO CORPORATION NE 68 TH STREET, SUITE C 130 REDMOND, WASHINGTON EVALUATION SUBJECT:

REPORT HOLDER: JAACO CORPORATION NE 68 TH STREET, SUITE C 130 REDMOND, WASHINGTON EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3009 Reissued 02/2018 This report is subject to renewal 02/2020. SECTION: 03 16 00

More information

To: Firm: Project: Product Specified: Specified Location:

To: Firm: Project: Product Specified: Specified Location: Submittal Substitution Request To: Firm: Project: Product Specified: Specified Location: Attached information includes product description, installation instructions and technical data needed for review

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3056 Reissued 10/2015 This report is subject to renewal 10/2017. DIVISION: 04 00 00 MASONRY

More information

FROM: PROPOSED SUBSTITUTION: Use HILTI X-U instead of fillet weld or arc spot puddle weld

FROM: PROPOSED SUBSTITUTION: Use HILTI X-U instead of fillet weld or arc spot puddle weld DATE: PROJECT: TO: FROM: SUBJECT: HILTI X-U POWDER-ACTUATED FASTENER SUBSTITUTION REQUEST SPECIFICATION TITLE: SECTION: PAGE: ARTICLE/PARAGRAPH: DESCRIPTION: DESIGN DETAIL NO.: PROPOSED SUBSTITUTION: Use

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: POWERS FASTENERS, INC. 701 EAST JOPPA ROAD TOWSON, MARYLAND 21286

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: POWERS FASTENERS, INC. 701 EAST JOPPA ROAD TOWSON, MARYLAND 21286 0 ICC-ES Report ICC-ES (800) -687 (6) 6-0 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-678 Reissued 0/0 This report is subject to renewal 0/06 DIVISION: 0 00 00 MASONRY SECTION: 0 0.6 MASONRY

More information

ICC-ES Evaluation Report Issued October 1, 2013 This report is subject to renewal October 1, 2014.

ICC-ES Evaluation Report Issued October 1, 2013 This report is subject to renewal October 1, 2014. ICC-ES Evaluation Report ESR-3517 Issued October 1, 2013 This report is subject to renewal October 1, 2014. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: 5956 WEST LAS POSITAS BOULEVARD PLEASANTON, CALIFORNIA 94588

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: 5956 WEST LAS POSITAS BOULEVARD PLEASANTON, CALIFORNIA 94588 0 ICC ES Report ICC ES (800) 4 687 (6) 699 04 www.icc es.org 000 Most Widely Accepted and Trusted ESR 06 Valid: 0/ to 0/6 DIVISION: 04 00 00 MASONRY SECTION: 04 0 9.6 MASONRY ANCHORS REPORT HOLDER: SIMPSON

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information

*Corrected October 2005

*Corrected October 2005 ESR-1056* Reissued December 1, 2004 This report is subject to re-examination in two years. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2966 Reissued 12/2017 This report is subject to renewal 12/2018. DIVISION: 04 00

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 42 687 (62) 699 04 www.icc es.org ESR 06 Reissued 0/207 This report is subject to renewal 0/208. DIVISION: 04 00 00 MASONRY

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 687 (6) 699 0 www.icc es.org ESR 8 Reissued 0/08 This report is subject to renewal 0/09. DIVISION: 0 00 00 MASONRY SECTION:

More information

Product Submittal/Substitution Request

Product Submittal/Substitution Request Product Submittal/Substitution Request TO: PROJECT: PROJECT LOCATION: SPECIFIED ITEM: Section Page Paragraph Description PRODUCT SUBMIT TAL / SUBSTITUTION REQUESTED: The attached submittal package includes

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 4042 Issued 07/2017 This report is subject to renewal 07/2018. DIVISION: 04 00 00

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: KWIK BOLT TZ MASONRY ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: KWIK BOLT TZ MASONRY ANCHORS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 687 (6) 699 04 www.icc es.org ESR 78 Reissued 07/018 This report is subject to renewal 07/019. DIVISION: 04 00 00 MASONRY

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3196 Reissued 10/2018 This report is subject to renewal 10/2019. SECTION: 04 05 19.16

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3196 Reissued 10/2017 This report is subject to renewal 10/2018. SECTION: 04 05 19.16

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS MARSHA L. BROWN PRESIDENT VAN AMBATIELOS VICE-PRESIDENT VICTOR H. CUEVAS HELENA JUBANY ELENORE A. WILLIAMS CITY OF LOS ANGELES CALIFORNIA ANTONIO R. VILLARAIGOSA

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 0 ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org Most Widely Accepted and Trusted ESR-3200 Reissued 12/2017 Revised 10/2018 This report is subject to renewal 12/2018 DIVISION:

More information

CALIFORNIA ERIC GARCETTI MAYOR

CALIFORNIA ERIC GARCETTI MAYOR BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE PRESIDENT CITY OF LOS ANGELES CALIFORNIA DEPARTMENT OF BUILDING AND SAFETY 201 NORTH FIGUEROA STREET LOS ANGELES,

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS MARSHA L. BROWN PRESIDENT PEDRO BIRBA VICE-PRESIDENT VAN AMBATIELOS HELENA JUBANY ELENORE A. WILLIAMS CITY OF LOS ANGELES CALIFORNIA ANTONIO R. VILLARAIGOSA MAYOR

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2966 Reissued 12/2016 This report is subject to renewal 12/2017. DIVISION: 04 00 00 MASONRY

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3200 Reissued 12/2017 This report is subject to renewal 12/2018. DIVISION: 04 00

More information

FROM: SUBJECT: HILTI X-ENP-19, X-HSN 24 or X-U POWDER-ACTUATED FASTENER SUBSTITUTION REQUEST

FROM: SUBJECT: HILTI X-ENP-19, X-HSN 24 or X-U POWDER-ACTUATED FASTENER SUBSTITUTION REQUEST DATE: PROJECT: TO: FROM: SUBJECT: HILTI X-ENP-19, X-HSN 24 or X-U POWDER-ACTUATED FASTENER SUBSTITUTION REQUEST SPECIFICATION TITLE: SECTION: PAGE: ARTICLE/PARAGRAPH: DESCRIPTION: DESIGN DETAIL NO.: PROPOSED

More information

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2787 Reissued 05/2017 This report is subject to renewal 05/2019. DIVISION: 03 00

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: ITW BUILDEX 700 HIGH GROVE BOULEVARD GLENDALE HEIGHTS, ILLINOIS 60139

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: ITW BUILDEX 700 HIGH GROVE BOULEVARD GLENDALE HEIGHTS, ILLINOIS 60139 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1671 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 04 00

More information

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation

Trusted ICC ES TEK USA, Evaluation. report, or as to any. ICC-ES Evaluation 0 ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg Most Widely Accepted and Trusted ESR 3105 Reissued 08/2017 Revised 10/2018 This report is subject to renewal 08/2019.

More information

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH BRAND FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3145 Reissued 02/2017 This report is subject to renewal 02/2018. DIVISION: 05 00 00 METALS SECTION:

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 587 (52) 99 0543 www.icc es.org ESR 393 Reissued 12/2017 This report is subject to renewal 12/2018. DIVISION: 04 00 00 MASONRY

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3531 Reissued 04/2018 This report is subject to renewal 04/2019. DIVISION: 06 00

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-4143 Issued 01/2018 This report is subject to renewal 01/2019. DIVISION: 04 00 00

More information

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES REPORT HOLDER: NELSON STUD WELDING, INC WEST RIDGE ROAD ELYRIA, OHIO 44036

DIVISION: CONCRETE SECTION: CONCRETE ACCESSORIES REPORT HOLDER: NELSON STUD WELDING, INC WEST RIDGE ROAD ELYRIA, OHIO 44036 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 42-687 (62) 699-04 www.icc-es.org ESR-2907 Reissued 2/207 This report is subject to renewal 2/208. DIVISION: 0 00 00 CONCRETE

More information

LEGACY REPORT DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

LEGACY REPORT DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC-ES Legacy Report 21-86.01 ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org Reissued 09/2018 This report is subject to renewal 09/2019. DIVISION: 06 00 00 WOOD,

More information

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT:

REPORT HOLDER: FASTENING SPECIALISTS, INC. 726 CENTRAL FLORIDA PARKWAY ORLANDO, FLORIDA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2328 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 03 00

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: HY-TEK FASTENERS INC. EVALUATION SUBJECT: HY-TEK NAILS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: HY-TEK FASTENERS INC. EVALUATION SUBJECT: HY-TEK NAILS 0 ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org Most Widely Accepted and Trusted ESR-2648 Reissued 06/2018 Revised 10/24/2018 This report is subject to renewal 06/2020.

More information

The following excerpt are pages from the North American Product Technical Guide, Volume 1: Direct Fastening, Edition 15.

The following excerpt are pages from the North American Product Technical Guide, Volume 1: Direct Fastening, Edition 15. The following excerpt are pages from the North American Product Technical Guide, Volume 1: Direct Fastening, Edition 15. Please refer to the publication in its entirety for complete details on this product

More information

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code.

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code. LEGACY REPORT ER-2895 Reissued March 1, 2004 www.icc-es.org Business/Regional Office 5360 Workman Mill Road, Whittier, California 90601 (562) 699-0543 Regional Office 900 Montclair Road, Suite A, Birmingham,

More information

ESR ICC Evaluation Service, Inc. Issued March 1, 2006 This report is subject to re-examination in one year.

ESR ICC Evaluation Service, Inc. Issued March 1, 2006 This report is subject to re-examination in one year. ESR-1328 Issued March 1, 2006 This report is subject to re-examination in one year. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601

More information

ESR ICC Evaluation Service, Inc. Reissued January 1, 2008 This report is subject to re-examination in one year.

ESR ICC Evaluation Service, Inc. Reissued January 1, 2008 This report is subject to re-examination in one year. ESR-1967 Reissued January 1, 2008 This report is subject to re-examination in one year. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS MARSHA L. BROWN PRESIDENT VAN AMBATIELOS VICE-PRESIDENT VICTOR H. CUEVAS HELENA JUBANY ELENORE A. WILLIAMS CITY OF LOS ANGELES CALIFORNIA ANTONIO R. VILLARAIGOSA

More information

DIVISION: WOOD, PLASTICS, AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

DIVISION: WOOD, PLASTICS, AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2553 Reissued 01/2018 This report is subject to renewal 01/2019. DIVISION: 06 00

More information

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT:

REPORT HOLDER: MITEK USA, INC. (FORMERLY USP STRUCTURAL CONNECTORS) SOUTHCROSS DRIVE, SUITE 200 BURNSVILLE, MINNESOTA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 43 6587 (56) 699 0543 www.icc es.org ESR 3754 Reissued 09/07 This report is subject to renewal 09/09. DIVISION: 03 00 00 CONCRETE

More information

Joint Evaluation Report

Joint Evaluation Report 0 Joint Evaluation Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 ESR-1210 Reissued 09/2018 This report is subject to renewal 09/2020. DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION:

More information

CALIFORNIA ERIC GARCETTI MAYOR

CALIFORNIA ERIC GARCETTI MAYOR BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: PASLODE, AN ILLINOIS TOOL WORKS COMPANY

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: PASLODE, AN ILLINOIS TOOL WORKS COMPANY 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3071 Reissued 12/2017 This report is subject to renewal 12/2018. DIVISION: 06 00

More information

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: HILTI, INC.

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: HILTI, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 43 6587 (56) 699 0543 www.icc es.org ESR 97 Reissued /7 This report is subject to renewal /8. DIVISION: 05 00 00 METALS SECTION:

More information

ESR-2961 Reissued September 1, 2011 This report is subject to renewal in two years.

ESR-2961 Reissued September 1, 2011 This report is subject to renewal in two years. ICC-ES Evaluation Report ESR-2961 Reissued September 1, 2011 This report is subject to renewal in two years. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information

Joint Evaluation Report

Joint Evaluation Report 0 Joint Evaluation Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 ESR-1040 Reissued 09/2018 This report is subject to renewal 09/2019. DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION:

More information

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: GRABBER CONSTRUCTION PRODUCTS, INC.

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: GRABBER CONSTRUCTION PRODUCTS, INC. 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1271 Reissued 07/2017 This report is subject to renewal 07/2018. DIVISION: 05 00 00 METALS SECTION:

More information

Joint Evaluation Report

Joint Evaluation Report 0 Joint Evaluation Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 ESR-1040 Reissued 09/2016 This report is subject to renewal 09/2018. DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION:

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3342 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 04 00

More information

Joint Evaluation Report

Joint Evaluation Report 0 Joint Evaluation Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 ESR 1040 Reissued 09/2018 Revised 03/2019 This report is subject to renewal 09/2019. DIVISION: 06 00 00 WOOD, PLASTICS

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 4105 Issued 08/2017 This report is subject to renewal 08/2018. DIVISION: 04 00 00

More information

C CALIFORNIA RESEARCH (CSI# 07320) Redland Clay Tile (800) with ASTM. fired. respectively. have widths at the large. Top and pan

C CALIFORNIA RESEARCH (CSI# 07320) Redland Clay Tile (800) with ASTM. fired. respectively. have widths at the large. Top and pan C ITY OF LOS L ANGELES CALIFORNIA ANTONIOO R. VILLARAIGOSA MAYOR DEPARTMENT OF BUILDING AND SAFETY 201 NORTH FIGUEROA STREET LOS ANGELES, CA 90012 ROBERT R. BUD OVROM GENERAL MANAGER RAYMOND S. CHAN, P.E.,

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information

ICC-ES Evaluation Report. ESR-3342 Reissued July 1, 2013 This report is subject to renewal August 1, 2015.

ICC-ES Evaluation Report. ESR-3342 Reissued July 1, 2013 This report is subject to renewal August 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-3342 Reissued July 1, 2013 This report is subject to renewal August 1, 2015. A Subsidiary of the International Code Council DIVISION:

More information

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: QUALITY WAY PRODUCTS, LLC 407 HADLEY STREET HOLLY, MICHIGAN 48442

DIVISION: METALS SECTION: METAL FABRICATIONS REPORT HOLDER: QUALITY WAY PRODUCTS, LLC 407 HADLEY STREET HOLLY, MICHIGAN 48442 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1729 Reissued 10/2016 This report is subject to renewal 10/2018. DIVISION: 05 00 00 METALS SECTION:

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS MARSHA L. BROWN PRESIDENT VAN AMBATIELOS VICE-PRESIDENT VICTOR H. CUEVAS HELENA JUBANY ELENORE A. WILLIAMS CITY OF LOS ANGELES CALIFORNIA ANTONIO R. VILLARAIGOSA

More information

The parts of Report No.ESR-2089 marked by the asterisks are modified by the Los Angeles Building Department from this approval.

The parts of Report No.ESR-2089 marked by the asterisks are modified by the Los Angeles Building Department from this approval. MiTek U.S.A., Inc. RESEARCH REPORT: RR 25759 14305 Southcross Drive, Suite # 200 (CSI # 06 12 19) Burnsville, MN 55306 BASED UPON ICC EVALUATION SERVICE Attn: Jim Collins REPORT NO. ESR-2089 (952) 898-8772

More information

Trusted ICC ES SECTION: Conformity! Look. Evaluation. ICC-ES Evaluation

Trusted ICC ES SECTION: Conformity! Look. Evaluation. ICC-ES Evaluation 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg ESR 3635 Reissued 04/2016 This report is subject to renewal 04/2018. DIVISION: 03 00

More information

Originally Issued: 02/11/2011 Revised: 02/23/2018 Valid Through: 02/28/2019

Originally Issued: 02/11/2011 Revised: 02/23/2018 Valid Through: 02/28/2019 MITEK USA, INC. USP HOLDOWN AND TENSION-TIE CONNECTORS CSI Section: 06 05 23 Wood, Plastic and Composite Fastenings 1.0 RECOGNITION MiTek USA, Inc. USP holdown and tension-tie connectors recognized in

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: ITW RED HEAD 700 HIGH GROVE BOULEVARD GLENDALE HEIGHTS, ILLINOIS 60139

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: ITW RED HEAD 700 HIGH GROVE BOULEVARD GLENDALE HEIGHTS, ILLINOIS 60139 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (00) 423-657 (562) 699-0543 www.icc-es.org ESR-4109 Issued 09/2017 This report is subject to renewal 09/201. DIVISION: 04 00 00 MASONRY

More information

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A.

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3831 Reissued 12/2017 This report is subject to renewal 12/2018. SECTION: 09 29 00

More information

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2254 Reissued 12/2017 This report is subject to renewal 12/2019. DIVISION: 03 00

More information

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS DIVISION: METALS SECTION: POST INSTALLED CONCRETE ANCHORS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3251 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 03 00

More information

CALIFORNIA ERIC GARCETTI MAYOR

CALIFORNIA ERIC GARCETTI MAYOR BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information