CERTIFICATE OF APPROVAL No CF 579 FIRETHERM INTUMESCENT & INSULATION SUPPLIES LIMITED

Size: px
Start display at page:

Download "CERTIFICATE OF APPROVAL No CF 579 FIRETHERM INTUMESCENT & INSULATION SUPPLIES LIMITED"

Transcription

1 CERTIFICATE OF APPROVAL No CF 579 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of FIRETHERM INTUMESCENT & INSULATION SUPPLIES LIMITED Unit F, Acorn Industrial Park, Crayford Rd, Crayford, Kent DA1 4FT Tel: Fax: Have been assessed against the requirements of the Technical Schedule(s) denoted below and are approved for use subject to the conditions appended hereto: CERTIFIED PRODUCT TECHNICAL SCHEDULE TS03 Penetration Sealing Systems Signed and sealed for and on behalf of CERTIFIRE Sir Ken Knight Chairman - Management Council Reissued: 30 th May 2013 Page 1 of 7

2 1. This relates to the use of for the fire protection where there are services penetrating walls & floors. The detailed scope is given in the Approval Matrix included in this Certificate. This shows the thickness and acceptable services for required to provide fire resistance periods in accordance with BS 476: Part 20: 1987 and BSEN :2009 of up to 240 minutes for differing services and wall/floor constructions. 2. This certification is designed to demonstrate compliance of the product or system specifically with Approved Document B (England and Wales), Section 2 of the Technical Standards (Scotland), Technical Booklet E (N. Ireland). If compliance is required to other regulatory or guidance documents there may be additional considerations or conflict to be taken into account. 3. The product is approved on the basis of: iv) Initial type testing v) Audit testing at the frequency specified in TS03 iii) A design appraisal against TS03 vi) Inspection and surveillance of factory production control vii) Production surveillance under ISO 9001: The masonry or concrete walls shall be at least 150 mm thick and have at least the same fire rating as that required for the penetration seal. The concrete floors shall be at least 150 mm thick and have at least the same fire rating as that required for the penetration seal. 5. The services which may be fitted through the seals are cable ladders, cables and steel ducts, as detailed within the Approval Matrix included in this Certificate. 6. The relates to ongoing production. Product and/or its immediate packaging is identified with the manufacturers name, the product name or number, the CERTIFIRE name or name and mark, together with the CERTIFIRE certificate number and application where appropriate. Page 2 of 7 Signed

3 CERTIFICATE No CF 579 Approval Matrix - Up To 240 Minute Walls Product Name: Seal depth Service Integrity Insulation Cable Ladder (150 mm wide by 15 mm high max.) 100 mm PVC sheathed copper core cables 16 mm diameter PVC sheathed copper core cables 23 mm diameter 240 minutes 180 minutes Maximum aperture: 600 mm high by 600 mm wide The walls shall be a minimum of 150 mm thick. The minimum density for the concrete or brick of the wall is 780kg/m 3 and Walls for walls made of concrete blocks is 600kg/m 3. All concrete or masonry walls shall have at least the same fire rating as that required for the barrier. The is supplied as a dry powder which is mixed with water to create a stiff mortar. The mortar is infilled into the pre-shuttered aperture, around the services to a thickness of 100 mm. Services should not be added after installation. Service Coat-Back : Not required U Value: Not known Resistance to Smoke: Acoustic Rating: Services should be rigidly supported via steel angles, hangars or channels, not further than 460 mm from the surface of the sealing system on both faces. Weather Capability: Movement Capability: Page 3 of 7 Signed

4 CERTIFICATE No CF 579 Approval Matrix - Up To 240 Minute Product Name: Seal depth Service Integrity Insulation Cable Ladder (150 mm wide by 15 mm high max.) 75 mm PVC sheathed copper core cables 16 mm diameter PVC sheathed copper core cables 23 mm diameter 120 minutes 90 minutes 100 mm 200 x 200 mm steel duct with damper 240 minutes 120 minutes Maximum aperture: 700 mm long by 600 mm wide All concrete or aerated concrete floors shall have at least the same fire rating as that required for the barrier. The is supplied as a dry powder which is mixed with water to create a stiff mortar. The mortar is infilled into the pre-shuttered aperture, around the services to a thickness of 75 or 100 mm. Services should not be added after installation. Service Coat-Back : Not required U Value: Not known Resistance to Smoke: Acoustic Rating: Services should be rigidly supported via steel angles, hangars or channels, not further than 460 mm from the surface of the sealing system on both faces. Weather Capability: Movement Capability: Page 4 of 7 Signed

5 BSEN : Up To 240 Minute Product Name: Seal depth Service Integrity Insulation Electrical cables up to 21mm ø Electrical cables up to 80mm ø 240 minutes 120 minutes 100mm Intucompound Non sheathed electrical cables up to 240 minutes 120 minutes (50mm Shutter Batt) 24mm ø Type F telecommunication cables bundles up to 100mm ø Blank Seal 600mm x 800mm 700 mm long by 700 mm wide (0.48m 2 ) Maximum aperture: All concrete or aerated concrete floors shall have at least the same fire rating as that required for the barrier. The is supplied as a dry powder which is mixed with water to create a stiff mortar. The mortar is infilled into the pre-shuttered aperture, around the services to a thickness of 100 mm. Services should not be added after installation. A box section utilising single layer Intubatt is installed to the upper face of the seal 600mm x 600mm x 150mm depth incorporating 100mm long pig tail scews at the edges, packed with stonewool and faced with 6mm Intumastic. Refer to manufacturers instructions for further details Coat Back Not required U Value: Not known Services should be rigidly supported via steel angles, hangars or channels, not further than 600 mm from the upper surface of the sealing system. Resistance to Smoke: Weather Capability: Acoustic Rating: Movement Capability: Page 5 of 7 Signed

6 Product Name: Seal depth 100mm Intucompound (50mm Shutter Batt) Maximum aperture: BSEN : Up To 240 Minute Service Damper frame 375mm x 375mm x 78mm connected to un- insulated steel duct Terrain PVC-u 82mmø and Hunter PVC-u 110mmø and Terrain PVC-u 160mmø and Hunter PVC-u 55mmø and 2mm wall thickness Steel 55mmø and min 4mm wall thickness, insulated with 19mm 38mm thick Armaflex Intumescent Specification Integrity Insulation N/A 240 minutes 0 minutes row x 60mm wide mm long by 700 mm wide(0.48m 2 ) All concrete or aerated concrete floors shall have at least the same fire rating as that required for the barrier. The is supplied as a dry powder which is mixed with water to create a stiff mortar. The mortar is infilled into the pre-shuttered aperture, around the services to a thickness of 100 mm. Services should not be added after installation. Installed flush with the unexposed face, with a fillet of Intumsatic to the unexposed face to aid adhesion Coat Back Not required U Value: Not known Resistance to Smoke: Acoustic Rating: Services should be rigidly supported via steel angles, hangars or channels, not further than 500 mm from the upper surface of the sealing system. Weather Capability: Movement Capability: Page 6 of 7 Signed

7 BSEN : Up To 240 Minute Product Name: Seal depth Service Intumescent Specification Integrity Insulation Aquatherm Fusiotherm PPR 90mmø and 8.2mm wall thickness Intusleeve 120mmø 300mm long, 3 x Intusleeve 120mmø HDPE 82mmø and 4.2mm 300mm long, 2 x wall thickness Intusleeve 120mmø 100mm Hunter PVC-u 82mmø and 300mm long, 2 x Intucompound (50mm Shutter Intusleeve 140mmø Batt) Terrain PVC-u 110mmø and 300mm long, 3 x Intusleeve 90mmø Hunter mu PVC 55mmø and 300mm long, 1 x 2mm wall thickness Intusleeve 140mmø Terrain PVC-u 160mmø and 300mm long, 4 x Maximum aperture: 700 mm long by 700 mm wide(0.48m 2 ) All concrete or aerated concrete floors shall have at least the same fire rating as that required for the barrier. The is supplied as a dry powder which is mixed with water to create a stiff mortar. The mortar is infilled into the pre-shuttered aperture, around the services to a thickness of 100 mm. Services should not be added after installation. Intusleeve Installed flush with the unexposed face, with a fillet of Intumsatic to the unexposed face to aid adhesion Coat Back Not required U Value: Not known Services should be rigidly supported via steel angles, hangars or channels, not further than 500 mm from the upper surface of the sealing system. Resistance to Weather Capability: Smoke: Acoustic Movement Capability: Rating: Page 7 of 7 Signed