AASF#2 Brooksville Lighting Upgrade PN Scope of Work Specification summary

Size: px
Start display at page:

Download "AASF#2 Brooksville Lighting Upgrade PN Scope of Work Specification summary"

Transcription

1 AASF#2 Brooksville Lighting Upgrade PN Scope of Work Specification summary General Replace light fixtures in designated areas Section 1 Removal of existing equipment 1. Contractor will remove 31 existing high bay light fixtures in designated areas Section 2 Installation of new equipment 2. Install - quantity 26 - LED High Bay light fixtures Light fixture specifications Acceptable manufacturers See Fixture Schedule No substitutions 2.2. Mounting Fixtures Fixture mounting height and locations are listed in plans Light fixtures will be pendant mounted from ¾ rigid conduit connected to T type conduit body coded to be allowed for use as a junction device Conduit bodies will be directly connected to and supported by ¾ (minimum) rigid horizontal conduit Acceptable Conduit Body manufacturers Hubbell Type RLT Conduit All weight bearing conduit will be ¾ (minimum) rigid type Horizontal (weight bearing) ¾ conduit will be supported by stainless steel cable hangers, secured to pre-drilled channel Acceptable cable hanger manufacturers Gripple All other NON weight bearing conduit will be EMT type Pre-drilled Channel ( Uni-strut ) Pre drilled channel will be secured to roof truss bottom chords by beam clamps Acceptable pre-drilled channel and mounting accessory manufacturers Thomas and Betts Kindorf B905 Series channel Thomas and Betts Kindorf U-501Beam Clamp Substitutions for materials outlined in this section must be accompanied by a manufacturer s specification and data sheet and are subject to review for approval/denial Electrical Connections Paint Shop Existing junction devices in Paint Shop are to be re-used where applicable Abandoned junction devices are to be covered/sealed in a manner consistent with current NEC and local electric code Comp Clean Room Existing direct fixture related junction devices are not to be reused for mounting new fixtures. PN Page 1 of 3

2 AASF#2 Brooksville Lighting Upgrade PN Scope of Work Technical specification summary General Replace light fixtures in designated areas Elect Room Existing direct fixture related junction devices are not to be reused for mounting new fixtures Engine Shop Existing direct fixture related junction devices are not to be reused for mounting new fixtures 2.4. Controls There is no central lighting control system requirement 2.5. Environmental The contractor is responsible for disposal of any and all waste associated with the removal of existing lighting fixtures and installation of new fixtures Copies of all records of recycling and waste disposal shall be submitted to the CFMO Environmental Office CFMO Environmental Office contact information Neal Newton Environmental Compliance Manager Phone - (904) neal.r.newton.nfg@mail.mil 3. General 3.1. All work performed must conform with current NEC Guidelines and local building codes End of Section PN Page 2 of 3

3 AASF#2 Brooksville Lighting Upgrade PN Scope of Work Technical specification summary General Replace light fixtures in designated areas Lighting Fixture Schedule Rm # Rm Descr. Qty Manufacturer Luminaire 65 Comp. Clean 2 GE ABH412H5814V23KNW 52 Elect. Room 3 GE ABH411T5814V23KNW 54 Paint Shop 8 GE AHH101T571NV23ANW 66 Engine Shop 6 GE ABH412T5814V23KNW 66 Engine Shop 3 GE ABH411T5814V23KNW 66 Engine Shop 3 GE EWS30B7D1501WHTE End of Section PN Page 3 of 3

4 2 - ABH412H5814V23KNW to be pendant mout at 12'0" AFF Indicates rigid conduit required for weight bearing application

5 3 - ABH411T5814V23KNW to be mounted at 10'0" AFF Illumination 50FC AFF Indicates rigid conduit required for weight bearing application

6 ABH412T5814V23KNW 18" ABH411T5814V23KNW EWS30B7D1501WHTE Existing HVAC Duct See Note ABH412T5814V23KNW pendant mount at 10'0" AFF 3 - ABH411T5814V23KNW pendant mounted at 14'0" AFF 3 - EWS30B7D1501WHTE to be mouned 10'0" AFF Illumination - 70FC AFF Note 1 - ABH411T5814V23KNW fixtures to be mounted 18" CL to edge of existing HVAC duct Indicates rigid conduit required for weight bearing application

7 All new fixtures AHH101T571NV23ANW All fixtures to be mounted at 10'0" AFF with exception of fixture marked PB. This fixture to be lowered to 7'6" AFF Illumination - 50FC AFF

8