Project: ProposedISI BC- GYM -Building,at Bangalore Campus

Size: px
Start display at page:

Download "Project: ProposedISI BC- GYM -Building,at Bangalore Campus"

Transcription

1 1 POINT WIRING Point wiring using copper wire WITHOUT Switch 1.1 Supplying and wiring adopting loop system in existing FRLS PVC conduit /casing and capping using 1100V grade, COPPER Conductor flexible multistrand FRLS PVC insulated, 2x1.5 sqmmcable confirming to the GTP WITHOUT SWITCH,other end of the wires shall be terminated with sufficient loose length in a wood/pvc round block complete for each outlet. Group - A Materials a Short point upto 3 Mtr from tapping point to out let via switch box 5 point b Medium point above 3Mtr upto 6Mtr from tapping point to out let via 5 point switch box c Long point above 6Mtr upto 10Mtr from tapping point to out let via switch 10 point 1.2 Supplying and flush mounting powder coated/galvanised metal box suitable for mounting modular switch plates.the box should be firmly flush mounted after due groove cutting in brick/stone/cc wall a 1-3 way 4 Each b 4-5 way 6 Each c 6 way 3 Each d 8 way 2 Each e way 2 Each 1.3 Supply and fixing superior quality modular switch mounting polycorbonate plate with necessary supporting back plate with required nos, of machine screws, bolts nuts, etc.., complete on the existing metal/pvc box. a 1 to 3 Module 4 Each b 4 M 3 Each c 6 M 2 Each d 8 M 2 Each e 10 M 2 Each f 12 M 2 Each 1.4 Supplying and fixing of modular switch / socket / stepped/ electronic fan regulator / dimmer/ telephone socket etc on existing modular switch plate as per IS 3854 and IS 1293 a 6 amps one way 17 Each b 6 amps Two way 2 Each c Stepped fan regulator-2module 3 Each d watts dimmer 1 Each e 16A one way switch 1 Each 1.5 supply and fixing Metal Fan box with Round hook 3 No. 1.6 Supplying heavy gauge FRLS PVC conduit pipe 20-40mm dia 2 to2.5 mm thick confirming to IS 2509 with suitable size bends, metal / PVC junction boxes, adhesive paste etc. and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wiers and unused ways of Junction boxes and pipe ends should be covered using PVC end enclosures, run with 18 SWG GI fish wire wherever necessary. a. 20 mm dia 2 mm thick 30 Mtr b. 25 mm dia 2 mm thick 60 Mtr c. 32 mm dia 2.5 mm thick 15 Mtr 1.7 Supplying heavy gauge PVC conduit pipe 20-40mm dia 2 to2.5 mm thick with suitable bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U & J hooks and cement plastering upto the surface and run with 18 SWG of 18 swg GI Fish wire run through our the conduit wherever necessary. a. 20 mm dia 2 mm thick 15 Mtr SHEDULE-B ( ELECTRICAL)/GYM BOQ Page 1 of 6

2 b. 25 mm dia 2 mm thick 75 Mtr c. 32 mm dia 2.5 mm thick 25 Mtr 2 MCB DISTRIBUTION BOARDS Supply, store, erection, testing and commissioning of MCB Distribution Boards, wall-mounted (either surface or recessed type). The erection rates shall include fixing of DB on wall including supply of all fixing accessories, civil works etc. space provision shall be made for mounting ELCB in the incomer MCB. DOUBLE DOOR TYPE (C/D curve-type MCB) all are Group - A Materials 2.1 Supplying and fixing regular MCCB distribution panel confirm to IS 8828, on wall / woodboard / flush mounting using required calmps,bolts, nuts etc., with provision for fixing of suitable type capacity MCCB' s as an incomer for 3 phase Double door with necessary bus bar completely wired to use on 440 volts 3 phase 4 wire powder coated painting etc., complete with a provision for fixing of single/three phase suitable capacity MCCB/MCB's as outgoings confirming to IS way 1 Each 2.2 Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and ' C' Type curve,indicator ON/OFF, energy cross-3 with short circuit breaking capacity of 10KA and complete wiring as required confirming to IEC Amps SP 14 Each Amps DP 1 Each Amps DP 1 Each Amps TPN 2 Each AmpsTPN 1 Each 2.3 Supplying and fixing regular MCB distribution boards on wall /woodboard / flush mounting using required calmps, bolts, nuts etc.,with provision for fixing suitable type capacity MCB's single phase/ 3 phase /double door with powder coated painting. Made out of 14 SWG MS enclouser.1- Double Door 1 12Way SP & N 1 Each 2 4 Way TP & N 1 Each 2.4 Supplying, fixing and wiring Earthh Leakage Miniature circuit breaker ( ELMCB ) 240/450 V up to 300mA sensitivity on exisiting wood /panel board. a) Amps 2 pole 2 Each b) Amps 2 pole 1 Each c) Amps 4 pole 1 Each d) 63 Amps 4 pole 1 Each 3 UNDER GROUND CABLES Cable End Termination : Supply and fixing of heavy duty cable glands suitable for UG cables of KV class ( metal only ) a. 19/20mm dia 2 Each b. 25mm dia 2 Each 3.2 Supplying tinned copper lugs and crimping and wiring to terminal point for wire of the following sizes. a 4 sqmm 30 Each b 6 sqmm 4 Each c 10 sqmm 8 Each 3.3 Supplying and fixing of Class A ( Medium duty ) GI pipe of wall thickness not less than 3.25mm on Pole/wall/drain crossing with necessary clamping arragements for UG cable of 1.1 KV Class a. 65mm 2 Mtr. 4 SOCKET OUTLETS SHEDULE-B ( ELECTRICAL)/GYM BOQ Page 2 of 6

3 4.1 Supplying and flush mounting powder coated/galvanised metal box suitable for mounting modular switch plates.the box should be firmly flush mounted after due groove cutting in brick/stone/cc wall a 1-3 way 4 Each b 4-5 way 10 Each c 6 way 5 Each 4.2 Supply and fixing superior quality modular switch mounting polycorbonate plate with necessary supporting back plate with required nos, of machine screws, bolts nuts, etc.., complete on the existing metal/pvc box. a 1 to 3 Module 4 Each b 4 M 10 Each c 6 M 6 Each 4.3 Supplying and fixing of modular switch / socket / stepped/ electronic fan regulator / dimmer/ telephone socket etc on existing modular switch plate as per IS 3854 and IS 1293, GROUP-A a 6 amps one way 4 Each b 6 amps Two way 1 Each c 16A one way switch 2 Each d 32A Modular DP Switch 6 Each e 6A 3/5 pin socket 4 Each f 6/16A universal socket 2 Each g 25A universal socket 6 Each Supply, Erection, testing and commissioning of factory made metal clad totally enclosed with MS powder coated /thermoplastic Boxhousing with industrial socket and plug top and fixing accessories such as grip 4.4 bolts/grouting etc. 32 Amps, 3-pin single phase industrial socket with plug top, controlled by 32 Amps DP MCB. For AC UNITS 2.00 Each 5 SUBMAINS / CIRCUIT MAINS / POWER WIRING: 5.1 Supplying heavy gauge FRLS PVC conduit pipe 20-40mm dia 2 to2.5 mm thick confirming to IS 2509 with suitable size bends, metal / PVC junction boxes, adhesive paste etc. and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wiers and unused ways of Junction boxes and pipe ends should be covered using PVC end enclosures, run with 18 SWG GI fish wire wherever necessary. a. 20 mm dia 2 mm thick 50 Mtr b. 25 mm dia 2 mm thick 125 Mtr c. 32 mm dia 2.5 mm thick 25 Mtr 5.2 Supplying heavy gauge FRLS PVC conduit pipe 20-40mm dia 2 to2.5 mm thick with suitable bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U & J hooks and cement plastering upto the surface and run with 18 SWG of 18 swg GI Fish wire run through our the conduit wherever necessary. a. 20 mm dia 2 mm thick 60 Mtr b. 25 mm dia 2 mm thick 100 Mtr c. 32 mm dia 2.5 mm thick 15 Mtr 5.3 Supplying PVC/GI Flexible conduit pipe 20-50mm dia fixing on surfaces over inverted tapered wooden pluges or phill pluges or rawl plugs and clamped using heavy guage saddles at an interval of 300 mm using NF screws and the either end of the pipe terminated completely. a. 20 mm 10 Mtr b. 25 mm 10 Mtr SHEDULE-B ( ELECTRICAL)/GYM BOQ Page 3 of 6

4 5.4 Wiring for lighting/power circuit using one of FRLS PVC insulated 1100v grade, multistrand Copper with low conductor resistance single core wire in open or concealed system of wiring.with specified IS-694:1990 & confirming to GTP of GROUP-A a. 1 sqmm 150 Mtr b. 1.5 sqmm 175 Mtr c. 2.5 sqmm 300 Mtr d. 4 sqmm 200 Mtr e. 6 sqmm 35 Mtr f. 10 sqmm 20 Mtr g. 16 sqmm 30 Mtr 6 LIGHTING / FAN FIXTURE Supply & store the following light fixtures complete with copper ballast, HPF Condenser, starters,controlgear, connecting wire WITH LAMPS /TUBES etc.complete as required. 6.1 Supplying box type suitable for 28W T5 single/twin lamp and suspension mounted luminaire & optical reflector. prewired with HF electronic ballast, push fit type lamp holder & main connectors. channel cover shall be made of CRCA MS sheet & finishing is done with stove enameled white with end caps made of engineering plastic. 1 1 x 4' -28 watts 2 Each 2 2 x 4' -28 watts 1 Each 6.2 Supplying Surface mounted type Mirror optics Luminaries for single/twin 28 watts fluorescent lamps cross rising of stove enamelled deep coloured M.S low profile housing complete with all accessories and high purity anodized aluminium reflector assembling along with cross louvers including necessary flourecent tubes with energy saving electonic ballast 2 2 x 4' -28 watts 6 Each 6.3 Supplying of recessed/surface mount aesthetic square/rectangular modular luminary made out of single piece powder coated CRCA sheet steel accommodating all electrical accessories like electronic ballast suitable to operate on 230V 50Hz AC supply with 18 Watts PLL-compact fluorescent lamp, pre-wired up to terminal block with bright anodized aluminum reflector & P5 paralite louvers with spring loaded plastic toggles 1 1 x 18 watts 2 Each 2 2 x 18 watts 1 Each 6.4 Supplying and Fixing casraluminium round or oblong type bulkhead 2 No. fitting with GI wire guard, glass cover with 15 Watts 230 volts CFL lamp 6.5 Supplying CFL mirror light fitting with 1x11W CFL lamp, choke, perspex cover and completely wired for use on 230V 50HZ supply. 6.6 Supplying capacitor type ceiling fan complete with down rod blades,shkles, canopies etc., for operation on 230 volts,50 cycles,single phase AC supply conforming to ISS and with double ball bearing system - Regular model 48" sweep ( 1200 ) 6.7 Supplying exhaust fan of 1440 RPM of 300mm (12" ) size with bracket blades and Louveers complete for light duty suitable to operate on 230v 50Hz, AC Supply 6.8 Supplying exhaust fan of 1440 RPM of 200mm (8" ) size with bracket blades and Louveers complete for light duty suitable to operate on 230v 50Hz, AC Supply 1 Each 3 No. 2 Each 1 Each SHEDULE-B ( ELECTRICAL)/GYM BOQ Page 4 of 6

5 Erection of Indoor Lighting and Fan Fixture : 6.9 Fixing all types and all capacities flourescent/false ceiling/spotlight/cfl/led fittings indoor on the wall/ceiling/rafters/girders using 23/0.0076" twin twisted PVC insulated wires, required nos of round blocks and clamps. a On the wall/ceiling/rafter/girders 6 Each b Using necessary length of GI chain 2 Each Using 1 Mtr long 19mm 18 SWG enameled braized conduit of two nos 6 Each c rod pendent ball sockets with check nuts all nickle plated 6.10 Fixing a ceiling /wall Mounting fan of all capacities and all types to the 3 Each existing ' S' hook with fan regulator to the existing board together with supplying and fixing a 5 ampers ceiling rose, necessary length of 23/ inch PVC insulated twin twisted copper wire and wiring Fixing one exhaust fan after making a suitable nitch in the wall and finishing with cement mortor and colouring to match the existing wall or brackets with bolts and nuts and a 5 amps, ceiling rose with sufficient length of 23/ inch PVC insulated twin core wire of approved make with wiremesh and wooden frame. 3 Each 7 DATA/ VOICE SYSTEM : 7.1 Supply and fixing of TV socket 1 Each 7.2 Supply and fixing of I/O Voice/Data Socket with back box- single i/o 1 Each 7.3 Supply and fixing Speaker Socket 4 Each Telephone-Data/TV Wires 7.4 Supply and drawing PVC flexible 2 pair telephone unarmoured tinned copper cable 7.5 Supply and drawing PVC flexible 5 pair telephone unarmoured tinned copper cable 7.6 Supply and drawing PVC insulated gas injected physical foam jelly flooded co- axial TV cable RG Supply and drawing Twisted pair cooper Speaker wire in Existing conduit 10 Mtrs. 25 Mtrs. 25 Mtrs. 30 Mtrs. 7.8 Supplying and flush mounting powder coated/galvanised metal box suitable for mounting modular switch plates.the box should be firmly flush mounted after due groove cutting in brick/stone/cc wall a 1-3 way 2 Each b 4-5 way 2 Each 7.9 Supply and fixing superior quality modular switch mounting polycorbonate plate with necessary supporting back plate with required nos, of machine screws, bolts nuts, etc.., complete on the existing metal/pvc box. a 1 to 3 Module 2 Each b 4 M 2 Each 7.10 Fabricating supplying and mounting MS box made outt. SWG suitable for floor / wall mounting, fully weather poof with provision for better heat dissipation, provided with hinged front cover, equipped with tamper poof locking arrangements, with suitable size clamps with necessary cable entry pipe with gland and box should be finished with 2 coats of red oxide primer paint and finally finished with approved colour enameled metal paint etc., complete. a) 14 SWG 500 sq cm 8 POWER EARTHING SYSTEM SHEDULE-B ( ELECTRICAL)/GYM BOQ Page 5 of 6

6 8.1 Supplying fixing and wring earth electrode for grounding of lifts,transformers,dg set etc., using 40mm dia 2.9mm thick 2.5 mtr long GI pipe with GI funnel with mesh and suitable size reducer fixing on the top of the earth electrode. The funnel should be enclosed in a CC chamber of 400 x 400 x 400 mm with a cast iron cover. The earth electrode shall have staggered holes of 12mm dia and the electrode should be covered 150mm alround with alterate layers of salt and charcoal from the bottam of the CC chamber. The connection from the electrode is to be established through GI strip using GI bolts and nuts. 2 Each 8.2 Supply & running of GI /Copperconductor for grounding ( along with other wires in conduit system of wiring ) using necessary suitable size clamps, nails,guttas/spacers etc,. 1 8 SWG Copper wire 25 Mtr SWG Copper wire 10 Mtr. TOTAL SHEDULE-B ( ELECTRICAL)/GYM BOQ Page 6 of 6