System S 3 cliq. Exposed, seismic resistant. OWAlifetime collection

Size: px
Start display at page:

Download "System S 3 cliq. Exposed, seismic resistant. OWAlifetime collection"

Transcription

1 System S cliq Exposed, seismic resistant OWAlifetime collection

2 System S cliq exposed, seismic resistant ASTM E 80/E 80M-0a The system fulfills the requirements according to ASTM E 80MN-0a, Heavy Duty, according to ASTM C and all requirements according to EN. Stretched hanger wire, tied at least times, Thickness >.0 mm, by customer Main tee cliq--mr, slots at 00 mm Cross tee cliq--ct, length 00 mm, mm or Cross tee cliq--ct, length 00 mm, 0 mm or Wall angle, for example no. / Space bar no., short Space bar no., long 8 Screw or pop by customer Strut no. 0 or CD-Profiles 0/ 0. mm by customer 0 Seismic joint coupling no. sjc0 for cliq--mr Seismic joint coupling no. sjc0 for cliq--ct short Wall perimeter no. /, / mm or similar Modul distance The grid system S cliq fulfills the essential requirements according to ASTM E 80M-0a. The grid system is tested according to ASTM C - and EN by a notified body and ISO 0 certified Lab MPA Braunschweig, Germany). The tests for the pull out force of the cross tees were carried out with. kn (approx. kg) tension. This system achieved the highest load bearing classification according to ASTM C as Heavy Duty with more than.0 lb/linear feet (.8 kg/m) for the main tees. These are the essential requirements according to the seismic design categories D, E and F defined in ASTM E 80M-0a. Section dimensions: Main tee cliq--mr 8 Cross tee cliq--ct long Cross tee cliq--ct short Technical data mineral tiles Dimensions 00 x 00 mm, x mm, x, 00 x 00 mm, 0 x mm, x Edge details Thickness approx. mm and 0 mm (OWAcoustic premium) Reaction to fire A-s,d0 in accordance with EN 0- Class A in accordance with ASTM E class I in accordance with ASTM E 8 Metal suspensions Suspension depth All profiles are zinc galvanized and exposed faces are white painted. For further details please consult our OWAlifetime collection price list mm (from underside of soffit). For ease of panel removal 0 mm is recommended.

3 Installation examples in accordance with ASTM E 80/E 80M-0a (also for module mm and ): Areas m 00 A 00 A B The hanger fixings must be installed according to ASTM E 80M-0a, paragraph... and... B Areas > m till m A < < 800 B Additional tasks for areas > m Lateral force bracings are required for all ceiling areas greater than 000 ft (approx. m ). max. distace: from the wall.8 m centres of horizontal restraint points. m Four -gauge (>.0 mm) wires in all directions secured to the main runner. Angle should not exceed from the plane of the ceiling. A strut must be installed in this area (for example section no. 0, see page 8). B Areas > m < A 00 A < 800 B Additional tasks for areas > m Expansion joints are necessary Separate seismic joints for each type of tees (MT, CT) None force-locked connection, must be moveable B force-locked connection

4 System S cliq exposed, seismic resistant ASTM E 80/E 80M-0a Cross-section: Section: Wall perimeter: For other examples of wall perimeters and installation see OWA-Installation guide no. 80 E and ASTM E 80/E 80M-0a. Wall perimeter A Wall perimeter A 8 max min. 0 min. 0 Wall perimeter B Wall perimeter B 8 max min. 0 8 min. 0 Installation after connecting B/B Installation after connecting A/A The connection must be force-locked Loosely fitted

5 Lateral force bracing for horizontal restraint according to ASTM E 80/E 80M-0a: Type : Type : < 0 < 0 Lateral force bracing with stretched hanger wire according ot ASTM E 80/E 80M-0a for Type and : The force-locked connection of the CD-Profiles must be < 0 mm. To connect the profiles with the grid-system the lower end has to be notched. Top view 0 0

6 System S cliq exposed, seismic resistant CISCA recommendations The system can be installed as per CISCA recommendations 0 Stretched hanger wire, tied at least times, Thickness >.0 mm, by customer Main tee cliq--mr, slots at 00 mm Cross tee cliq--ct, length 00 mm, mm or Cross tee cliq--ct, length 00 mm, 0 mm or Wall angle, for example no. / Seismic perimeter clip no. spc0 Strut no. 0 or CD-Profiles 0/ 0. mm by customer 8 Seismic joint coupling no. sjc0 for cliq--mr and cliq--ct long Seismic joint coupling no. sjc0 for cliq--ct short Wall perimeter no. /, / mm or similar 0 Modul distance The grid system S cliq fulfills the essential requirements according to ASTM E 80M-0a. The grid system is tested according to ASTM C - and EN by a notified body and ISO 0 certified Lab (MPA Braunschweig, Germany). The tests for the pull out force of the cross tees were carried out with. kn (approx. kg) tension. This system achieved the highest load bearing classification according to ASTM C as Heavy Duty with more than.0 lb/ linear feet (.8 kg/m) for the main tees. These are the essential requirements according to the seismic design categories D, E and F defined in ASTM E 80M-0a. Section dimensions: Main tee cliq--mr 8 Cross tee cliq--ct long Cross tee cliq--ct short Technical data mineral tiles Dimensions 00 x 00 mm, x mm, x, 00 x 00 mm, 0 x mm, x Edge details Thickness approx. mm and 0 mm (OWAcoustic premium) Reaction to fire A-s,d0 in accordance with EN 0- Class A in accordance with ASTM E Metal suspensions Suspension depth All profiles are zinc galvanized and exposed faces are white painted. For further details please consult our OWAlifetime collection price list mm (from underside of soffit). For ease of panel removal 0 mm is recommended.

7 Installation examples in accordance with CISCA recommendations: Areas m 00 A 00 A B The hanger fixings must be installed as per CISCA recommendations. All main tees and cross tees must be fixed with wall clip no. spc0. B Areas > m till m A < A B < 800 B Additional tasks for areas > m Lateral force bracings are required for all ceiling areas greater than 000 ft (approx. m ). max. distace: from the wall.8 m centres of horizontal restraint points. m Four -gauge (>.0 mm) wires in all directions secured to the main runner. Angle should not exceed from the plane of the ceiling. A strut must be installed in this area (for example section no. 0, see page 8). Areas > m < A 00 A 8 B < 800 B Additional tasks for areas > m Expansion joints are necessary. Separate seismic joints for each type of tees (MT, CT) 8 force-locked connection None force-locked connection, must be moveable.

8 8 System S cliq exposed, seismic resistant CISCA Cross-section: Section: 0 0 Wall perimeter: For other examples of wall perimeters and installation see OWA-Installation guide no. 80 E and CISCA recommendation Wall perimeter A Wall perimeter A max. 00 min. min. Wall perimeter B Movable screw connection Wall perimeter B Movable screw connection max. 00 min. min. Installation of the seismic perimeter clip no. spc0: Connection A/ Connection B/ The connection must be force-locked The connection must be movable

9 Lateral force bracing for horizontal restraint according to ASTM E 80/E 80M-0a: Type : Type : < 0 < 0 Lateral force bracing with stretched hanger wire according ot ASTM E 80/E 80M-0a for Type and : The force-locked connection of the CD-Profiles must be < 0 mm. To connect the profiles with the grid-system the lower end has to be notched. Top view 0 0

10 0 System S cliq exposed, seismic resistant System-related accessories: 8 Seismic joint coupling no. sjc0 and sjc0 (consist of pieces and small components). This but joint has to be suspended on both sides. None force-locked connection, must be moveable. The nut has to be fixed by a locknut. force-locked connection Seismic perimeter clip no. spc0, for locking of the main runner and cross tee in the wall area Light fixtures: OWA can supply compatible light fixtures for this system. For details of performance, installation and fire resistance please see OWA-brochure no. 0 e and OWA-Installation Guide no. 80 e Installation: All integrated services should be secured separately. Installation should be carried out in accordance with the information contained in OWA-Installation guide 80 and ASTM E 80M-0a.

11 The test report of MPA Braunschweig shows the tests of the loadbearing capacity and the seismic requirements according to ASTM E 80M-0a

12 Material requirements per m (approximations): Dimensions in mm ASTM E 80/E 80M-0a CISCA recommendations No. Description 00 x 00* 00 x 00* cliq--mr Main tee 0,8 m 0,8 m cliq--ct Cross tee short 0,8 m 0,8 m cliq--ct Cross tee long, m, m Stretched hanger wire (vertical suspension) 0, pce 0, pce 0 Strut or CD profile 0,08 pce 0,08 pce / Wall angle depending on room size and shape / Wall angle depending on room size and shape Space bar depending on room size and shape spc0 Perimeter clip depending on room size and shape sjc0 Seismic joint coupling depending on room size and shape depending on room size and shape sjc0 Seismic joint coupling depending on room size and shape depending on room size and shape * other dimensions see brochure S cliq Weight per m : 00 x 00 Suspension system approx.. kg/m Tiles mm, approx.. kg/m System description: System S cliq seismic resistant Quality statement: OWAcoustic mineral tiles are firmly bound with a primer coat on both sides. The tile is free from asbestos and no formaldehyde is added in the manufacturing process of the mineral tiles. The mineral wool used for the manufacture of the tile is bio-soluble. The criteria for non-classification as a carcinogenic substance in accordance with the Chemicals Prohibition Ordinance (Section Appendix, Paragraph bio-persistent fibres) are met and guaranteed by the RAL seal of approval for mineral wool. Verification of fit for use, in according to EU CPR: CE marking and Declaration of Performance (DoP). Mineral tiles according to EN and DIN 8: Air Permeability Class PM, Formaldehyde: FH Class, TVOC: Class Installation should be carried out in accordance with the information contained in system leaflet S cliq seismic resistant and OWA-Installation Guide no. 80 e. All components are CE labelled. Component list ASTM E 80/E 80M-0a: OWAconstruct cliq--mr main tee OWAconstruct cliq--ct cross tee short OWAconstruct cliq--ct cross tee long OWAconstruct wall angle no. / OWAconstruct space bar no. OWAconstruct strut no. 0 or CD profile OWAconstruct seismic joint coupling no. sjc0 or no. sjc0 Component list CISCA-recommendations: OWAconstruct cliq--mr main tee OWAconstruct cliq--ct cross tee short OWAconstruct cliq--ct cross tee long OWAconstruct wall angle no. / OWAconstruct strut no. 0 or CD profile OWAconstruct wall clip no. spc0 OWAconstruct seismic joint coupling no. sjc0 or no. sjc0 Product Warranties The information provided in this leaflet is based on the standards and data available at the time of publication. Any performance, warranties or guarantees provided, expressed or implied, are subject to the exclusive use of OWA components and the installation of those components in accordance with our recommendations. Failure to adhere to these conditions will result in the invalidation of any performance claims, warranties or guarantees and rejection of any liability. OWA reserves the right to make any technical improvements to the products, systems or services without prior notice. All goods and services are supplied in accordance with our current Terms and Conditions of Sale. Errors excepted! Odenwald Faserplattenwerk GmbH Dr.-F.-A.-Freundt-Straße Amorbach tel info@owa.de Brochure S cliq seismic resistant e 00