CITY OF LOS ANGELES CALIFORNIA

Size: px
Start display at page:

Download "CITY OF LOS ANGELES CALIFORNIA"

Transcription

1 BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI MAYOR DEPARTMENT OF BUILDING AND SAFETY 20 NORTH FIGUEROA STREET LOS ANGELES, CA 9002 RAYMOND S. CHAN, C.E., S.E. GENERAL MANAGER FRANK BUSH EXECUTIVE OFFICER HILTI, Inc. RESEARCH REPORT: RR S. 22 E. Avenue (CSI # ; ; ) Tulsa, OK 7446 BASED UPON ICC EVALUATION SERVICE Attn: Hilti Technical Support REPORT NO. ESR-66 (877) REEVALUATION DUE DATE: April, 206 Issued date: April, 205 Code: 204 LABC GENERAL APPROVAL Technical/Clerical Modification - Hilti Low-Velocity Power Driven Fasteners DETAILS The Power Driven Fasteners are approved when in compliance with the use, description, design, installation, conditions of use, and identification of ICC-ES Report No. ESR-66, reissued March, 205, of the ICC Evaluation Service, LLC. That report, in its entirety, is attached and made a part of this general approval. The parts of Report No.ESR-66 marked by the asterisks are deleted or revised by the Los Angeles Building Department from this approval. The approval is subject to the following conditions:. The fasteners are recognized for use when subjected to seismic loads as follows: a) The Hilti fasteners may be used with nonstructural components listed in Section..4 of ASCE 7, which are exempt from the requirements of ASCE 7. RR Page of 4 LADBS G-5 (Rev.06/0/) AN EQUAL EMPLOYMENT OPPORTUNITY - AFFIRMATIVE ACTION EMPLOYER

2 HILTI, Inc. RE: Hilti Low-Velocity Power Driven Fasteners b) Concrete base materials: The Hilti fasteners installed in concrete may be used to support acoustical tile or lay-in panel suspended ceiling systems, distributed systems and distribution systems where the service load on any individual fastener does not exceed the lesser of 90 lbf or the published allowable load shown in Tables of the attached ICC-ES report, as applicable. c) Steel base materials: When the Hilti fasteners are installed in steel and are subjected to seismic loads, the most critical load applied to each individual fastener must be determined from the applicable equations in IBC Section or Section , and must not exceed the allowable seismic loads shown in Table of attached report. Recognition of the Hilti fasteners for use in design of lateral force resisting systems, such as shear walls and diaphragms, is outside the scope of this report. d) For interior, nonstructural walls that are not subject to sustained tension loads and are not a bracing application, the power-driven fasteners may be used to attach steel track to concrete or steel in all Seismic Design Categories. In Seismic Design Categories D, E and F, the allowable shear load due to transverse pressure shall be no more than 90 pounds when attaching to concrete; or the allowable loads in Table of attached report when attaching to steel. Substantiating calculations shall be submitted addressing the fastener- to-base-material capacity and the fastener-to attached-material capacity. Interior nonstructural walls are limited to locations where bearing walls, shear walls or braced walls are not required by the approved plans. The design load on the fastener must not exceed the allowable load established in the attached ICC-ES report for the concrete or steel base material. 2. The fasteners are used to attach non-building components including but not limited to drywall tracks, wood, light gage steel, sprinkler pipes, furniture, cabinets, sheet metal duct work, electrical conduits, cable trays, cables, lighting, wood sill plates, acoustical ceiling, light gauge framing, non-bearing-non-structural interior partitions, and other fixtures to normal-weight and structural sand-lightweight concrete, metal decks with structural sand-lightweight concrete fill, concrete masonry units (CMUs) and steel base materials.. The fasteners shall not be used in cracked concrete or cracked masonry. 4. The allowable values listed in the attached report and tables are for the fasteners only. Connected members shall be checked for their capacity (which may govern). 5. The low velocity fasteners installed through the underside of steel deck at the ribs and into minimum 000 psi lightweight concrete shall have minimum edge distance as specified in Section of attached report. Concrete fill above top ribs shall be 2-/2 inches minimum. Refer to Figures, 2 and of the ICC-ES ESR-66 for details. RR Page 2 of 4

3 HILTI, Inc. RE: Hilti Low-Velocity Power Driven Fasteners 6. When installation is in concrete, minimum spacing between fasteners shall be 4 inches on center and minimum edge distance shall be inches. Concrete thickness must be a minimum of three times the embedment depth of the fastener. For CMUs, no more than one power driven fastener may be installed per individual CMU cell. 7. Allowable loads must be in accordance to Section 4. of the attached ICC ES ESR-66. Calculations showing that the applied loads are less than the maximum allowable loads must be submitted to the structural plan check division for review and approval. The calculations must be prepared by a civil or structural engineer registered in the State of California. 8. The fasteners shall be installed per the manufacturer's instructions, a copy of which shall be available at each job site. 9. Hilti X-CR stainless steel power driven fasteners are permitted for use in exterior, damp environments. All other fasteners in this report are limited to installation in dry, interior environments, including those exterior walls protected by an exterior wall envelope. 0. Hilti X-CR fasteners may be installed in contact with preservative-treated wood, as set forth in the applicable code.. Hilti carbon steel fasteners in contact with fire retardant-treated wood may be used in contact with fire-retardant-treated wood in dry, interior locations only, in accordance with Section of the 204 LABC. Under 2008 LABC, use of Hilti carbon steel fasteners in contact with preservative-treated wood or fire-retardant-treated wood is not permitted. 2. All fasteners are identified by an H imprinted on the fastener head. Where applicable the word Hilti is stamped on the steel washers. All fasteners are packaged in containers noting the fastener type, size, manufacturer s name, and evaluation report number (ESR- 66). DISCUSSION The clerical modification is to update company contact person and phone number. The technical modification is to update allowable seismic loads for EDS, DS and X-CR fasteners installed in steel base materials. Increased allowable loads for X-C fasteners installed in concrete have also been added due to increased hardness of fastener. The new X-C fasteners can be distinguished from original fasteners by black collating strips or guidance washers. The report is in compliance with the 204 Los Angeles City Building Code. The approval is based on tests in accordance with ICC-ES Acceptance Criteria for Fasteners Power-driven into Concrete, Steel and Masonry Elements (AC70) dated October 202. RR Page of 4

4 HILTI, Inc. RE: Hilti Low-Velocity Power Driven Fasteners This general approval will remain effective provided the Evaluation Report is maintained valid and unrevised with the issuing organization. Any revisions to the report must be submitted to this Department for review with appropriate fee to continue the approval of the revised report. Addressee to whom this Research Report is issued is responsible for providing copies of it, complete with any attachments indicated, to architects, engineers and builders using items approved herein in design or construction which must be approved by Department of Building and Safety Engineers and Inspectors. This general approval of an equivalent alternate to the Code is only valid where an engineer and/or inspector of this Department has determined that all conditions of this Approval have been met in the project in which it is to be used. QUAN NGHIEM, Chief Engineering Research Section 20 N. Figueroa St., Room 880 Los Angeles, CA 9002 Phone Fax EB RR25646 R0/26/ /9/207/2204.2/.4.5, ASCE 7-0 Attachments: ICC ES Report No.ESR-66 (7 Pages). RR Page 4 of 4

5 ICC-ES Evaluation Report (800) (562) ESR-66 Reissued March 205 This report is subject to renewal March 207. A Subsidiary of the International Code Council DIVISION: CONCRETE Section: Concrete Accessories Section: Concrete Anchors DIVISION: MASONRY Section: Masonry Anchors DIVISION: METALS Section: Metal Fastenings DIVISION: WOOD, PLASTICS AND COMPOSITES Section: Wood, Plastic and Composite Fastenings DIVISION: FINISHES Section: Fasteners REPORT HOLDER: HILTI, INC SOUTH 22 nd EAST AVENUE TULSA, OKLAHOMA 7446 (800) HNATechnicalServices@hilti.com EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-DRIVEN S.0 EVALUATION SCOPE Compliance with the following codes: 202, 2009 and 2006 International Building Code (IBC) 202, 2009 and 2006 International Residential Code (IRC) 20 Abu Dhabi International Building Code (ADIBC) The ADIBC is based on the 2009 IBC IBC code sections referenced in this report are the same sections in the ADIBC. Properties evaluated: Structural 2.0 USES Hilti power-driven fasteners are used to attach wood, coldformed steel, and other building elements to normal-weight and sand-lightweight concrete, steel deck panels with sand-lightweight concrete fill, concrete masonry units (CMUs) and steel base materials. The fasteners are alternatives to the cast-in-place anchors described in 202 IBC Section 908 (2009 and 2006 IBC Section 9) for placement in concrete; the embedded anchors described in Section 2..4 of TMS 402/ACI 50/ASCE 5 (which is referenced in IBC Section 207); and the welds and bolts used to attach materials to steel, described in IBC Sections and , respectively. The fasteners may also be used under the IRC where an engineered design is submitted in accordance with IRC Section R DESCRIPTION. Fasteners: The fasteners are manufactured as nails or threaded studs with various shank diameters, thread diameters, lengths, and smooth or knurled shanks. The carbon steel fasteners are manufactured from austempered steel conforming to SAE 060 or 070 (modified). The carbon steel fasteners are zinc-plated to ASTM B6, SC, Type III. The stainless steel X-CR fasteners are manufactured from a proprietary CrNiMo alloy complying with the requirements of SAE 6. The premounted washers for the X-CR fasteners are manufactured from stainless steel conforming to SAE 6. All fasteners have a Rockwell C hardness ranging from 49 to 6..2 Normal-weight Concrete: Normal-weight concrete must be normal-weight, stoneaggregate concrete complying with IBC Chapter 9 or IRC Section R402.2, as applicable. The minimum concrete compressive strength at the time of fastener installation is noted in Table 2.. Lightweight Concrete: Lightweight concrete must be sand-lightweight complying with IBC Chapter 9, and must have a minimum,000 psi (9.7 MPa) compressive strength at the time of fastener installation..4 Masonry: Masonry must be comprised of normal-weight or lightweight concrete masonry units (CMUs) complying with ASTM C90 and mortar complying with ASTM C270 Type N in accordance with 202 IBC Section 20.9 (2009 and 2006 IBC Section 20.8) or IRC Section R607, as applicable. Where specified in Table 5 of this report, concrete-masonry construction must be fully grouted and have a minimum prism strength, f m, of,500 psi (0. MPa) at the time of fastener installation. Grout must comply with Article 2.2 of TMS 602/ACI 50./ASCE 6, referenced in 202 IBC Section 20. (2009 and 2006 IBC Section 20.2) or IRC Section R609.., as applicable. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 205 Page of 7 000

6 ESR-66 Most Widely Accepted and Trusted Page 2 of 7.5 Steel Substrates:.5. Steel: Structural steel used in supports must comply with the minimum strength requirements of ASTM A6, ASTM A572 Grade 50 or ASTM A992, as applicable, and must have the thickness shown in Table..5.2 Steel Deck Panels: Steel deck panels must conform to a code-referenced material standard, and have the minimum thickness and minimum yield strength noted in Tables and 4. See Figures through for panel configuration requirements. 4.0 DESIGN AND INSTALLATION 4. Design: 4.. Allowable Loads: The most critical applied loads, excluding seismic load effects, resulting from the load combinations in IBC Section or must not exceed the allowable loads. For fasteners which are subjected to seismic loads, see Section 4.. for additional information. The allowable tension and shear loads, along with fastener descriptions and shank diameters for powerdriven fasteners installed in structural steel base materials, are shown in Table. The allowable tension and shear loads with minimum required embedment depths, along with fastener descriptions and shank diameters for fasteners installed in normal-weight and sand-lightweight concrete base materials, are shown in Tables 2,, and 4. The allowable tension and shear loads with minimum required embedment depths, along with fastener descriptions and shank diameters, for fasteners installed in concrete masonry units (CMUs), are shown in Table 5. The stress increases and load reductions described in IBC Section 605. are not allowed. Allowable loads apply to the connection of the fastener to the base material only. Design of the connection of the fastener to the attached material must comply with the applicable requirements of the IBC. Allowable loads for fasteners subjected to combined shear and tension forces are determined by the following formula: (p/p a ) + (v/v a ) where: p P a = Actual tension load, lbf (N). = Allowable tension load, lbf (N). v = Actual shear load, lbf (N). V a = Allowable shear load, lbf (N) Attachment of Wood to Steel, Concrete, or Masonry: Reference lateral design values for fasteners determined in accordance with Part of ANSI/AF&PA NDS are applicable to Hilti fasteners of equal or greater diameters. The wood element must be considered to be the side member. The fastener bending yield strength must be the value noted in the NDS based on the fastener diameter. Hilti X-CR stainless steel fasteners may be installed in contact with preservative-treated or fire-retardant-treated wood, as set forth in the applicable code. Hilti carbon steel fasteners may be used in contact with fire-retardant-treated wood in dry, interior locations only, in accordance with 202 and 2009 IBC Section and Hilti s recommendations. Use of the Hilti carbon steel fasteners in contact with preservative-treated wood or in contact with fire-retardant-treated wood in exterior applications is outside the scope of this report. 4.. Seismic Considerations: The Hilti fasteners are recognized for use when subjected to seismic loads as follows:. The Hilti fasteners may be used with nonstructural components, listed in Section..4 of ASCE 7, which are exempt from the requirements of ASCE Concrete base materials: The Hilti fasteners installed in concrete may be used to support acoustical tile or lay-in panel suspended ceiling systems, distributed systems and distribution systems where the service load on any individual fastener does not exceed the lesser of 90 lbf (400 N) or the published allowable load in Tables 2, and 4, as applicable.. Steel base materials: When the Hilti fasteners are installed in steel and subjected to seismic loads, the most critical load applied to each individual fastener must be determined from the applicable equations in IBC Section or Section , and must not exceed the allowable load shown in Table. Recognition of the Hilti fasteners installed in steel base material for use in the design of lateral force resisting systems, such as shear walls and diaphragms, is outside the scope of this report. 4. For interior, nonstructural walls that are not subject to sustained tension loads and are not a bracing application, the power-driven fasteners may be used to attach steel track to concrete or steel in all Seismic Design Categories. In Seismic Design Categories D, E, and F, the allowable shear load due to transverse pressure shall be no more than 90 pounds (400 N) when attaching to concrete; or the allowable load shown in Table when attaching to steel. Substantiating calculations shall be submitted addressing the fastener-to-base-material capacity and the fastener-to-attached-material capacity. Interior nonstructural walls are limited to locations where bearing walls, shear walls or braced walls are not required by the approved plans. The design load on the fastener must not exceed the allowable load established in this report for the concrete or steel base material. 4.2 Installation: 4.2. General: The fasteners must be installed in accordance with this report and the Hilti, Inc., published installation instructions. A copy of the instructions must be available on the jobsite at all times during installation. Additional installation requirements are set forth in Tables to 5 of this report. Fastener placement requires a low-velocity powderactuated tool used in accordance with Hilti, Inc. recommendations. Installers must be certified by Hilti, Inc., and have a current, Hilti-issued, operator s license Fastening to Steel: When installation is in steel, minimum spacing between fasteners must be inch (25.4 mm) on center, and minimum edge distance must be / 2 inch (2.7 mm) Fastening to Concrete: Fasteners are to be driven into the concrete after the concrete attains the concrete strength specified in the tables of this report. Unless otherwise noted, minimum spacing between fasteners must be 4 inches (02 mm) on center and minimum edge distance must be inches (76 mm). Unless otherwise noted, concrete thickness must be a minimum of three times the embedment depth of the fastener.

7 ESR-66 Most Widely Accepted and Trusted Page of Fastening to Masonry: Fasteners are to be driven into the masonry after the mortar and grout materials have attained the specified strength. For CMUs, no more than one power-driven fastener may be installed per individual CMU cell Fastening to Sand-lightweight Concrete-filled Steel Deck Panels: Installation in sand-lightweight concrete-filled steel deck panels must comply with Tables and 4 and Figures through. Minimum distances from fastener centerline to rolled deck panel flute edges must be as depicted in Figures through. 5.0 CONDITIONS OF USE The Hilti Low-Velocity Power-Driven Fasteners described in this report comply with, or are suitable alternatives to what is specified in, those codes listed in Section.0 of this report, subject to the following conditions: 5. Fasteners must be manufactured and identified in accordance with this report. 5.2 Fasteners must be installed in accordance with this report and the Hilti, Inc., instructions. In the event of conflict between this report and Hilti, Inc., published instructions, this report governs. 5. Calculations demonstrating that the actual loads are less than the allowable loads described in Section 4. must be submitted to the code official for approval. The calculations must be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is constructed. 5.4 Refer to Section 4.. for seismic considerations. 5.5 The use of the fasteners is limited to installations in uncracked concrete or masonry. Cracking occurs when f t > f r due to service loads or deformations. 5.6 Hilti X-CR stainless steel fasteners may be used in exterior, damp environments. All other fasteners in this report must be limited to installation in dry, interior environments, which include exterior walls which are protected by an exterior wall envelope. 5.7 Installation must comply with Section 4..2 regarding fasteners in contact with preservative-treated and fireretardant-treated wood. 5.8 Installers must be certified by Hilti, Inc., and have a current, Hilti-issued, operator s license. 6.0 EVIDENCE SUBMITTED Data in accordance with the ICC-ES Acceptance Criteria for Fasteners Power-driven in Concrete, Steel, and Masonry Elements (AC70), dated June 204, including seismic load test data in accordance with Annex A of AC IDENTIFICATION All fasteners are identified by an H imprinted on the fastener head. Where applicable, the word Hilti is stamped on the steel washers. All fasteners are packaged in containers noting the fastener type, size, manufacturer s name, and evaluation report number (ESR-66). DESCRIPTION Heavy Duty Knurled Shank TABLE ALLOWABLE LOADS FOR LOW-VELOCITY S DRIVEN INTO STEEL,2,4 SHANK DIAMETER / 8 / 6 STEEL THICKNESS / 4 Shear Shear Shear Shear Shear Shear EDS Heavy Duty Smooth Shank DS Stainless Steel Smooth Shank X-CR Stainless Steel Smooth Shank X-CR For SI: inch = 25.4 mm, lbf = 4.4 N, ksi = 6.89 MPa. Fasteners must be driven to where the point of the fastener penetrates through the steel base material, unless otherwise noted. 2 Unless otherwise noted, allowable load capacities are based on base steel with minimum yield strength (F y ) of 6 ksi and minimum tensile strength (F u ) of 58 ksi. Allowable load capacity based on base steel with minimum yield strength (F y ) of 50 ksi and minimum tensile strength (F u ) of 65 ksi. 4 Allowable loads are applicable to static and seismic loads in accordance with Section 4.. / 8 / 2 / 4

8 ESR-66 Most Widely Accepted and Trusted Page 4 of 7 TABLE 2 ALLOWABLE LOADS FOR LOW-VELOCITY S DRIVEN INTO NORMAL-WEIGHT CONCRETE DESCRIPTION SHANK DIAMETER EMBEDMENT (inches) CONCRETE COMPRESSIVE STRENGTH 2,000 psi 4,000 psi 6,000 psi Shear Shear Shear / Standard Nail X-C (Black Collated Strip or Guidance / / / Standard Nail X-C (White Collated Strip or Guidance / / Drywall Track Nail X-C22 P8 TH (Black Collated Strip or Guidance 0.8 / Drywall Track Nail X-C22 P8 TH (White Collated Strip or Guidance 0.8 / / Heavy Duty Nail DS 0.77 / 4-20 Threaded Stud / 8-6 Threaded Stud X-W W / / / / / / Stainless Steel Nail X-CR 0.45 For SI: inch = 25.4 mm, psi = 6895 Pa, lbf = 4.4 N / / Fasteners must not be driven until the concrete has reached the designated minimum compressive strength.

9 ESR-66 Most Widely Accepted and Trusted Page 5 of 7 TABLE ALLOWABLE LOADS FOR LOW-VELOCITY S DRIVEN INTO MINIMUM f c =,000 psi SAND-LIGHTWEIGHT CONCRETE DESCRIPTION Standard Nail Standard Nail Drywall Track Nail X-C (Black Collated Strip or Guidance X-C (White Collated Strip or Guidance SHANK DIAMETER X-C20 THP 0.8 X-C22 P8TH (Black Collated Strip or Guidance X-C22 P8TH (White Collated Strip or Guidance MINIMUM EMBEDMENT (inches) Installed into Concrete Shear LOCATION Installed Through Steel Deck Panel into Concrete 2, Upper Flute Lower Flute Shear / / / / / / / / / / Heavy Duty Nail DS Stainless Steel Nail X-CR 0.45 / 4-20 Threaded Stud / 8-6 Threaded Stud X-W W For SI: inch = 25.4 mm, psi = 6895 Pa, lbf = 4.4 N / / / / / / / Fasteners must not be driven until the concrete has reached the designated minimum compressive strength. 2 The steel deck panel profile must be -inch-deep composite floor deck panel, with a minimum inch base-metal thickness, and a minimum yield strength of ksi. Lower and upper flute widths must be a minimum of 7 / 8 inches. Figure shows the nominal flute dimensions, fastener locations and load orientations for the deck panel profile. Sand-lightweight concrete fill depth above top of steel deck panel must be a minimum of / 4 inches. 4 DS fasteners installed at / 2 -inch embedment through steel deck panel into the lower flute must be installed at a minimum distance of 6 inches from the edge of the floor deck panel.

10 ESR-66 Most Widely Accepted and Trusted Page 6 of 7 DESCRIPTION TABLE 4 ALLOWABLE LOADS FOR LOW-VELOCITY S DRIVEN INTO MINIMUM f c =,000 psi SAND-LIGHTWEIGHT CONCRETE-FILLED / 2 -INCH-DEEP, B-DECK STEEL PANEL SHANK DIAMETER Drywall track nail X-C22 P8 TH Standard nail X-C For SI: inch = 25.4 mm, psi = 6895 Pa, lbf = 4.4 N. EMBEDMENT LOCATION Installed Through Steel Deck Panel Into Concrete 2, Upper Flute Lower Flute Shear / / Fasteners must not be driven until the concrete has reached the designated minimum compressive strength. 2 Steel deck panel profiles are / 2 -inch-deep, B-type deck panel with a minimum base-metal thickness of inch, and a minimum yield strength of 8 ksi. Fasteners may be installed through steel deck panels having either normal or inverted orientations with minimum lower flute widths of / 4 and / 2 inches, respectively. Fasteners must be placed at centerline of deck panel flutes. Figures 2 and describe additional flute dimensions, fastener locations, and load orientations for both deck panel profiles. Sand-lightweight concrete fill above top of steel deck panel must be a minimum of 2 / 2 inches. 4 Allowable load values apply to fasteners with black or white collated strip or guidance washer. DESCRIPTION TABLE 5 ALLOWABLE LOADS FOR LOW-VELOCITY S DRIVEN INTO CONCRETE MASONRY UNITS,2, SHANK DIAMETER EMBED- MENT HOLLOW CMU GROUT-FILLED CMU Face Shell Mortar Joint Face Shell Mortar Joint Top of Grouted Cell 5 Shear 6 Shear 6 Shear 6 Shear 4 Standard Nail X-C / 4-20 Threaded Stud X-W For SI: inch = 25.4 mm, lbf = 4.4 N. Fasteners must be installed a minimum of 8 inches from the end of the wall. Multiple fasteners in a bed joint must be spaced a minimum of 8 inches. 2 See Section.4 for CMU, mortar and grout requirements. No more than one low-velocity fastener may be installed in an individual CMU cell. 4 Shear direction must be horizontal (bed joint or t-joint) along the CMU wall plane. 5 Fastener located in center of grouted cell must be installed vertically. 6 Shear load can be in any direction. 7 Allowable load values apply to fasteners with black or white collated strip or guidance washer. Shear 6

11 ESR-66 Most Widely Accepted and Trusted Page 7 of 7 FIGURE HILTI LOCATIONS IN -INCH-DEEP COMPOSITE FLOOR DECK PANEL FIGURE 2 HILTI LOCATIONS IN / 2 -INCH-DEEP COMPOSITE FLOOR DECK PANEL, NORMAL DECK PANEL PROFILE ORIENTATION For SI: inch = 25.4 mm, psi = 6895 Pa. FIGURE HILTI LOCATIONS IN / 2 -INCH-DEEP COMPOSITE FLOOR DECK PANEL, INVERTED DECK PANEL PROFILE ORIENTATION