SCS-01 Termination Detail for Lining at Nose Angle Iron. SCS-02 Termination Detail for Lining at Circular and Trench Flooring Drain

Size: px
Start display at page:

Download "SCS-01 Termination Detail for Lining at Nose Angle Iron. SCS-02 Termination Detail for Lining at Circular and Trench Flooring Drain"

Transcription

1 TABLE OF CONTENTS SCS-01 Termination Detail for Lining at Nose Angle Iron SCS-02 Termination Detail for Lining at Circular and Trench Flooring Drain SCS-03 Treatment for Non-moving Cracks SCS-04 Treatment for Moving Cracks SCS-05 Control Joint with No Potential Movement DETAILS GUIDE STANDARD SECONDARY CONTAINMENT SCS-06 Control Joint with Potential Movement SCS-07 Expansion/Isolation Joint Treatment Detail SCS-08 Cant Cove Detail SCS-09 Sleeved or Non-Sleeved Pipe Penetration SCS-10 Termination of Lining on Concrete Wall SCS-11 Wrap Over Termination of Lining on Concrete Walls SCS-12 Anchor Detail with Base Plate SCS-13 Anchor Detail without Base Plate COMPANY INCORPORATED 6800 Corporate Drive, Kansas City, MO Published techincal data, instructions, and pricing are subject to change without notice. Contact your Tnemec technical representative for current technical data, instructions, and pricing. Warranty information: The service life of Tnemec s coatings will vary. For warranty, limitation of seller s liability, and product information, please refer to Tnemec s Product Data Sheets at or contact your Tnemec Technical Representative

2 CONTAINMENT LINING POLYSULFIDE SEALANT (OPTIONAL) SAWCUT CONCRETE 1/4 X1/4 AND TERMINATE LINING INTO SAWCUT EMBEDDED NOSING ANGLE IRON TERMINATION DETAIL FOR LINING AT NOSE ANGLE IRON SCS-01

3 CAST-IN-PLACE CIRCULAR FLOOR DRAIN SAWCUT CONCRETE 1/4 X1/4 AND TERMINATE LINING INTO SAWCUT CONTAINMENT LINING POLYSULFIDE SEALANT (OPTIONAL) TERMINATION DETAIL FOR LINING AT CIRCULAR AND TRENCH FLOOR DRAIN SCS-02

4 PATCH WITH FILLER MATERIAL PRIOR TO INSTALLING CONTAINMENT LINING CONTAINMENT LINING NOTE: USE SERIES 215 OR SERIES 201, 237SC, OR 239SC 100% SOLIDS EPOXY MIXED WITH FUMED SILICA OR SILICA FLOUR FOR FILLER MATERIAL. ROUTE OUT CRACK PRIOR TO PATCHING IF CRACK IS LARGER THAN 1/16 (1.58mm). TREATMENT FOR NON-MOVING CRACKS SCS-03

5 POLYSULFIDE SEALANT ROUTE OUT EXISTING CRACK AND PATCH WITH FILLER MATERIAL PRIOR TO INSTALLING CONTAINMENT LINING CONTAINMENT LINING NOTE: USE SERIES 201, 237SC, 239SC 100% SOLIDS EPOXY MIXED WITH FINE AGGREGATE CREATING A MORTAR MATERIAL TO FILL ROUTED OUT AREA. FLEXIBLE JOINT SEALANT WIDTH TO DEPTH RATIO SHOWN IS APPROXIMATELY 2:1. DETAIL CAN BE BUILT BY INSTALLING CONTAINMENT LINING OVER FILLER MATERIAL, RESAWCUTTING, AND INSTALLING SEALANT. TREATMENT FOR MOVING CRACKS SCS-04

6 CONTAINMENT LINING PATCH WITH FILLER MATERIAL PRIOR TO INSTALLING CONTAINMENT LINING NOTE: USE SERIES 215 OR SERIES 201, 237SC, 239SC 100% SOLIDS EPOXY MIXED WITH FUMED SILICA, SILICA FLOUR OR FINE AGGREGATE FOR FILLER MATERIAL. FILL CONTROL JOINT PRIOR TO INSTALLING CONTAINMENT LINING. CONTROL JOINT WITH NO POTENTIAL MOVEMENT SCS-05

7 CONTAINMENT LINING POLYSULFIDE 1/2" (12.7mm) DEEP SAWCUT NOTE: POLYSULFIDE SEALANT WIDTH TO DEPTH RATIO SHOWN IS APPROXIMATELY 2:1. DETAIL CAN BE BUILT BY INSTALLING CONTAINMENT LINING OVER JOINT, RESAWCUTTING, AND INSTALLING SEALANT. CONTROL JOINT WITH POTENTIAL MOVEMENT SCS-06

8 BACKER ROD AND POLYSULFIDE SEALANT CONTAINMENT LINING 1/2" (12.7mm) 1/4" (6.35mm) EXISTING EXPANSION/ ISOLATION JOINT MATERIAL NOTE: POLYSULFIDE SEALANT WIDTH TO DEPTH RATIO SHOWN IS APPROXIMATELY 2:1. DETAIL CAN BE BUILT BY INSTALLING CONTAINMENT LINING OVER JOINT, RESAWCUTTING, AND INSTALLING BACKER ROD AND SEALANT. EXPANSION/ISOLATION JOINT TREATMENT DETAIL SCS-07

9 CONCRETE OR CMU 1" - 2" HEIGHT (25.4mm mm) CONTAINMENT LINING 45 DEGREE CANT COVE NOTE: USE SERIES 201, 237SC, 239SC 100% SOLIDS EPOXY MIXED WITH FINE AGGREGATE CREATING A MORTAR MATERIAL TO BUILD COVE PRIOR TO INSTALLING THE CONTAINMENT LINING. CANT COVE DETAIL SCS-08

10 EXISTING PIPE OR SLEEVE 1-2 (25.4mm mm) HEIGHT POLYSULFIDE SEALANT CONTAINMENT LINING BACKER ROD SLEEVED OR NON-SLEEVED PIPE PENETRATION SCS-09

11 POLYSULFIDE SEALANT (OPTIONAL) SAWCUT CONCRETE 1/4" X 1/4" AND TERMINATE LINING INTO SAWCUT CONTAINMENT LINING TERMINATION OF LINING ON CONCRETE WALL SCS-10

12 SAWCUT CONCRETE 1/4" X 1/4" AND TERMINATE LINING INTO SAWCUT CONTAINMENT LINING WRAP OVER TERMINATION OF LINING ON CONCRETE WALLS SCS-11

13 CONTAINMENT LINING ANCHOR BOLT BASE PLATE POLYSULFIDE SEALANT EPOXY GROUT ANCHOR DETAIL WITH BASE PLATE SCS-12

14 CONTAINMENT LINING POLYSULFIDE SEALANT EPOXY GROUT ANCHOR DETAIL WITHOUT BASE PLATE SCS-13