1 TEST REPORT Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia PRODUCT TYPE: EIFS Panel Systems SERIES/MODEL: GP ForceField Air & Water Barrier Sheathing with Dryvit Outsulation System Reference must be made to Report No. H , dated 10/04/17 for complete test specimen description and detailed test results 1701 Westfork Drive, Suite 106 Lithia Springs, GA p f

2 Test Report No.: H Page 1 of Report Issued To: Georgia-Pacific Wood Products, LLC 133 Peachtree Street NE Atlanta, Georgia Test Laboratory: Architectural Testing, Inc., an Intertek company ("Intertek-ATI") 1701 Westfork Drive, Suite 106 Lithia Springs, Georgia Project Summary: 3.1 Product Type: EIFS Panel Systems 3.2 Series/Model: GP ForceField Air & Water Barrier Sheathing with Dryvit Outsulation System 3.3 Compliance Statement: Results obtained are tested values and were secured by using the designated test method(s). Test specimen description and results are reported herein. 3.4 Test Date(s): 07/17/17 & 07/18/ Test Record Retention End Date: All test records for this report will be retained until July 18, Test Location: Intertek-ATI test facility in Lithia Springs, Georgia. 3.7 Test Specimen Source: The test specimens were provided by the client. Representative samples of the test specimen(s) will be retained by Intertek-ATI for a minimum of two years from the test completion date. 3.8 Drawing Reference: The test specimen drawings have been reviewed by Intertek-ATI and are representative of the test specimen(s) reported herein. Test specimen construction was verified by Intertek-ATI per the drawings located in Appendix C. Any deviations are documented herein or on the drawings. 3.9 List of Official Observers: Name Company Rick Jordan Joel Ivey Ian McKenzie Ryan Hedgepeth Georgia-Pacific Wood Products, LLC Intertek-ATI Intertek-ATI Intertek-ATI

3 Test Report No.: H Page 2 of Test Method(s): ASTM E (2011), Test Method for Determining the Drainage Efficiency of Exterior Insulation and Finish Systems (EIFS) Clad Wall Assemblies 5.0 Test Specimen Description: 5.1 Product Sizes: Both Specimens Tested Are the Same Size Table 1 Overall Area: Width Height 3.0 m² (32.0 ft 2 ) millimeters inches millimeters inches Overall size Base Wall Construction: The base wall was constructed of nominal 2x4 wood studs spaced 16" on center. A sheet of nominal 7/16" thick Georgia-Pacific ForceField Air & Water Barrier Sheathing was secured to the studs with #8 x 1-1/4" Philips Bugle-Head coarse thread drywall screws spaced 8" on center. Sheathing was applied with three 4ft long horizontal seams and two 2ft long vertical seams. All seams were sealed with ForceField TM seam tape. The wall utilized two 2x8 Southern-Yellow-Pine on the jambs to facilitate testing. (Sheathing and stucco system was applied by Georgia-Pacific Gypsum representatives). Specimen #2 had a layer of Tyvek Stucco Wrap TM applied to the ForceField WRB TM. 5.3 EIFS Components: The EIFS was fabricated utilizing the members listed in Table 2. Table 2 Name Overall Cross Section Description EIFS Adhesive No adhesive Mechanically attached Insulation Board 1-1/2" thick EPS - 1-lb/ft 3 (ASTM C578, Type 1) Base Coat & Mesh on EPS 1/16" thick resistance complying with ASTM E5035 Glass fiber reinforcing mesh coated for alkali embedded in 1/16" EIFS base coat Finish N/A Acrylic Finish 6.0 Installation: Representatives of Georgia-Pacific Wood Division installed the stucco system as described in the attached drawings.

4 Test Report No.: H Page 3 of Test Results: The temperature during testing was 24 C (75 F). The results are tabulated as follows: 7.1 Calibration Data: The water spray applicator was calibrated prior to the test being completed. The calibration results are as follows: Date Total Weight (lbs) Tare Weight (lbs) Net Weight (lbs) Application Rate (gals/75 min) Required Application Rate (gals/75 min) 07/17/ Test Data: The following results are reported: Test Specimen # 1 2 Weight Water Applied Drain Time (minutes) (minutes) Total Weight (lbs) Tare Weight (lbs) Net Weight (lbs) Total Weight (lbs) Tare Weight (lbs) Net Weight (lbs) Note: Weights reported are accumulated weights at the times reported. Test Specimen #1 Test Specimen #2 Total Water Applied (lbs) Total Water Drained (lbs) % Water Drained % Water Retained General Note: All testing was performed in accordance with the referenced standard(s).

5 Test Report No.: H Page 4 of 5 Intertek-ATI will service this report for the entire test record retention period. Test records such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation, will be retained by Intertek-ATI for the entire test record retention period. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. For ARCHITECTURAL TESTING, INC.: Ryan K. Hedgepeth, E.I.T. Project Engineer Ian J. McKenzie Regional Manager IJM:jb Attachments (pages): This report is complete only when all attachments listed are included. Appendix A: Photograph(s) (2) Appendix B: Drawing(s) (3)

6 Test Report No.: H Page 5 of 5 Revision Log Rev. # Date Page(s) Revision(s) 0 09/18/17 N/A Original report issue 1 10/04/17 Cover and Page 1 Changed Series/Model to GP ForceField Air & Water Barrier Sheathing with Dryvit Outsulation System This report produced from controlled document template ATI 00479, revised 06/19/15.

7 Test Report No.: H Appendix A Photograph(s) Photo No. 1 Test Specimen #1 During Testing

8 Photo No. 2 Test Specimen #2 During Testing Test Report No.: H

9 Test Report No.: H Appendix B Drawing(s)