TYPICAL ROOF CONDITION LAYOUT

Size: px
Start display at page:

Download "TYPICAL ROOF CONDITION LAYOUT"

Transcription

1 FIXED POINTS TYPICAL ROOF CONDITION LAYOUT Typical Roof Condition Layout... 1 Low Eave Isometric View - Fixed/ Floating... 2 Low Eave Section - Fixed/ Floating... 3 High Eave - Floating... 4 High Eave - Fixed... 5 High Eave - Wall To Roof Connection... 6 Panel Slope Transition... 7 Panel End & Closure... 8 Fixed Center Clip... 9 Low Eave Gutter - Isometric View Low Eave Gutter -Section Internal Gutter Internal Gutter At Parapet Wall Internal Gutter At Saw Tooth Roof Ridge Cap Floating Fixed Ridge - Hip Vented Ridge Fixed Hip To Rake Ridge Detail Hip To Rake Ridge - Isometric View Rake Detail Rake At Stepped Eave Rake Installation Wall To Rake Flashing... Rake At Sloping To Flat Roof... Wall To Rake Step Flashing... Wall To Rake Expansion Joint... Panel Expansion Joint... Rake At Valley Assembly- Isometric View... Rake At Valley Assembly... Equipment Curb Flashing... Equipment Curb Flashing Isometric View(A)... Equipment Curb Flashing - Section - B... Equipment Curb Flashing - Section - C... Equipment Curb Flashing - Section - D... Pipe Penetration... Gutter Flashing Condition... Rake And Eave Flashing Condition... Ridge And Hip Flashing Condition... Downspout... Snow Guard Isometric View... Snow Guard Detail MANUAL DOES NOT APPLY TO ZINC OR COPPER APPLICATIONS REV 12/17 1

2 MORZIP PANEL FIXED OR SLIDING PANEL CLIP KEY HOLE CLOSURE DRIP ANGLE ROOF DECK (NBM) RIGID INSULATION (NBM) 40 MIL ICE AND WATER SHIELD UNDERLAYMENT (NBM) #6 HEX TEK. (4) PER PANEL MIN. OR POP RIVETS BUTYL SEALANT EAVE FLASHING LOW EAVE DETAIL 2

3 MORZIP PANEL MORZIP 2 PIECE SLIDING CLIP OR 1 PIECE FIXED CLIP UNDERLAYMENT (NBM) KEY HOLE CLOSURE 1"X1" DRIP ANGLE EAVE TRIM RIGID INSULATION (NBM) ROOF DECK (NBM) FASTENERS (2) PER CLIP MIN. Eave design must be able to allow for the total amount of expansion of the panel if the ridge is fixed. A drip trim should be used to stiffen the flat of the panel and block wind driven rain. This piece also assists in limiting the amount of bow of the flat under high wind. Since sealant between roof underlayment and panel may limit expansion or rupture, protection against wind blown water infiltration is provided by folding the panel under, which allows for thermal expansion. Detail must be designed to allow for maximum thermal movement. Floating eave requires fixed ridge. FLOATING EAVE 3

4 RIDGE CAP FASTENERS (5) PER PANEL MIN. "J" SUPPORT AT PANEL ENDS CONTINUOUS "Z" NOTCHED AROUND PANELS RIBS IN FIELD SEALANT SEALANT AROUND NOTCHED RIBS MORZIP 2 PIECE SLIDING CLIP OR 1 PIECE FIXED CLIP BEARING PLATE HIGH HEAT ICE AND WATER SHIELD REQ'D 40 MIL MIN. (NBM) RIGID INSULATION (NBM) ROOF DECK (NBM) FASTENERS (2) PER CLIP MIN. Note: -Floating high eave requires fixed low eave. -Gap as required for thermal movement. -Use larger J- support for panel with Clip Relief, Pencil Ribs and Striated. HIGH EAVE - FLOATING 4

5 FIXED FASTENERS (2) PER PANEL MIN. FASTENERS (5) PER PANEL MIN. RIDGE CAP "J" SUPPORT AT PANEL ENDS SEALANT CONTINUOUS "Z" NOTCHED AROUND PANELS RIBS IN FIELD SEALANT AROUND NOTCHED RIBS MORZIP 2 PIECE SLIDING CLIP OR 1 PIECE FIXED CLIP BEARING PLATE HIGH HEAT ICE AND WATER SHIELD REQUIRED 40 MIL MIN. (NBM) RIGID INSULATION (NBM) FASTENERS (2) PER CLIP MIN. ROOF DECK (NBM) Note: -Fixed high eave requires floating low eave -Gap as required for thermal movement - Use larger J- support for panel with Clip Relief, Pencil Ribs and Striated HIGH EAVE - FIXED 5

6 SEALANT (NBM) THROUGH WALL FLASHING URETHANE SEALANT MASONRY FASTENER BUTYL SEALANT "J" SUPPORT AT PANEL ENDS HIGH EAVE FLASHING FASTENERS (5) PER PANEL MIN. "Z" CLOSURE NOTCH AROUND RIBS IN FIELD SEALANT AROUND RIBS 2" MIN. MORZIP 2 PIECE SLIDING CLIP OR 1 PIECE FIXED CLIP ROOF DECK (NBM) FASTENERS (2) PER CLIP MIN. High eave flashings are similar to ridge conditions. Attention must be given to the design for sealing and panel movement. Where snow buildup is a concern the design of the trim must take into account the excess loading. Floating high eave requires fixed low eave.use larger J- support for panel with clip relief, pencil ribs and striated.floating high eave requires fixed low eave and fixed high eave required floating eave. WALL TO ROOF HIGH EAVE - FLOATING 6

7 MORZIP PANEL MORZIP 2 PIECE SLIDING CLIP OR 1 PIECE FIXED CLIP KEY HOLE CLOSURE CONTINUOUS "Z" CLOSURE NOTCH AROUND RIBS IN FIELD "J" SUPPORT AT PANEL ENDS TRANSITION FLASHING BASE J-TRIM SEALANT AROUND RIBS FASTENERS (2) PER CLIP MIN. METAL DECK (N.B.M.) RIGID INSULATION (N.B.M.) Note: - Floating panels require fixed connections at opposite ends. - Use larger J- support for panel with clip relief, pencil ribs and striated. PANEL SLOPE TRANSITION - FLOATING 7

8 "J" SUPPORT AT PANEL ENDS MORZIP PANEL SEALANT CONTINUOUS LINE OF DOUBLE BEADED BUTYL TAPE SEALANT 5 FASTENERS PER PANEL MIN. "Z" CLOSURE NOTCHED AROUND RIBS IN FIELD Note: - Use larger J- support for panel with clip relief, pencil ribs and striated. PANEL END & CLOSURE DETAIL 8

9 (4) #44-1 8" STAINLESS STEEL RIVETS WITH STAINLESS STEEL MANDREL MORZIP 1 PIECE FIXED CLIP MORZIP METAL PANEL 6" X 6" BEARING PLATE MORZIP METAL PANEL MORZIP 1 PIECE FIXED CLIP 6" X 6" BEARING PLATE 2 FASTENERS MINIMUM The roofing system as a floating system must have some means by which to attach it to the structure & yet not restrict its floating ability to handle the thermal expansion/ contraction found in the system. Because of the above reasons, Morin s MorZip panels must be positively attached at one or more purlins along a line perpendicular to the panel s vertical rib. The ideal location of what the panel industry calls a fix point line is at the center of the panel run. By having the fixed point at this location, the amount of travel of the panel over the clip is held to a minimum. Where you have very long panel runs, it may be required to have more then one row of fixed points. When this is necessary, then the rows should be on adjacent rows of purlins. Refer to fixed point details in this manual for methods of installation and recommended locations. Acceptable alternate locations for these fixed point are at either the ridge or eave of the roof. Exceptions to all of the recommended fixed point locations may be needed because of various design restrictions such as large roof penetrations, restraints at the ends of a panel run, an irregular shaped roof surface or at roof hip and valley locations. Panel lengths over 50' require fixed point at mid-run. FIXED CENTER CLIP 9

10 MORZIP PANEL FIXED OR SLIDING PANEL CLIP 40 MIL ICE AND WATER SHIELD UNDERLAYMENT (NBM) KEY HOLE CLOSURE GUTTER STRAP ROOF DECK (NBM) GUTTER RIGID INSULATION (NBM) SUPPLEMENTAL GUTTER SUPPORT STRAPS AS REQUIRED 2" WIDE LOW EAVE WITH GUTTER 10

11 MORZIP PANEL MORZIP 2 PIECE SLIDING CLIP OR 1 PIECE FIXED CLIP KEY HOLE CLOSURE 40 MIL ICE AND WATER SHIELD (NBM) 1"X1" DRIP ANGLE EAVE TRIM GUTTER STRAP ROOF DECK (NBM) GUTTER RIGID INSULATION (NBM) FASTENERS (2) PER CLIP MIN. SUPPLEMENTAL GUTTER STRAP 2" WIDE Consideration during design must be given to capacity, overflow, accessibility for cleaning, and aesthetics. Attachments must provide structural supports and allow for thermal movement. Protection from ice and snow must be considered during the detailing of this condition. Edge of gutter should be reinforced in areas of snow or ice accumulation. The edge of the gutter should be below the roof plane to allow for evacuation of the snow build-up. The gutter should be independent of the roof panel as not to inhibit the thermal movement of the roof. Floating eave requires fixed ridge. LOW EAVE WITH GUTTER 11

12 FIXED OR SLIDING PANEL CLIP KEY HOLE CLOSURE GUTTER FLASHING MORZIP PANEL DRIP ANGLE "J" SUPPORT AT PANEL ENDS "Z" CLOSURE NOTCH AROUND RIBS IN FIELD SEALANT AROUND RIBS METAL DECK (NBM) GUTTER DRAIN RIGID INSULATION (NBM) FASTENERS (2) PER CLIP MIN. Where an exposed gutter may distract from the aesthetics of the building, an internal gutter may be required. The condition and roof design must allow for this condition to be fixed against thermal movement. Considerations must be made in areas of ice or snow to avoid blockage of the gutter or drains. Overflow scuppers are required at each end of the gutter. This design relies on sealant to form the weather barrier. Designers should be aware of the hazards and allow for adequate drainage. Morin requires membrane liner for all internal gutter (NBM). Use larger J- support for panel with clip relief, pencil ribs and striated. INTERNAL GUTTER 12

13 PARAPET CAP FIXED OR SLIDING PANEL CLIP CONTINUOUS CLEAT KEY HOLE CLOSURE GUTTER FLASHING (NBM) MORZIP PANEL DRIP ANGLE FASTENERS (2) PER CLIP MIN. METAL DECK (NBM) 40 MIL ICE AND WATER SHIELD (NBM) Note: -Over flow scupper recommended at ends of gutter. -Morin recommends use of membrane liner for all internal gutter (NBM). INTERNAL GUTTER WITH PARAPET WALL 13

14 MORZIP PANEL MORZIP FIXED OR SLIDING PANEL CLIP KEY HOLE CLOSURE DRIP ANGLE FASTENERS (2) PER CLIP MIN. RIGID INSULATION (NBM) METAL DECK (NBM) OVERFLOW SCUPPER AT ENDWALLS GUTTER SUPPORT (NBM) GUTTER DRAIN Note: -Over flow scupper recommended at ends of gutter. -Morin recommends use of membrane liner for all internal gutter (NBM). INTERNAL GUTTER WITH SAW TOOTH ROOF 14

15 "Z" CLOSURE SET ON DOUBLE BEAD BUTYL SEALANT "J" SUPPORT AT PANEL ENDS RIDGE CAP FASTENERS (5) PER PANEL MIN. BEARING PLATE SEALANT AROUND RIBS MORZIP PANEL 4" MORZIP FIXED OR SLIDING PANEL CLIP RIGID INSULATION (NBM) FASTENERS (2) PER CLIP MIN. ROOF DECK (NBM) If ridge condition is required to float, slip joints at each side must be made to accommodate the required expansion. Clip fasteners must be long enough to fasten into low cells of decking. Use larger J- support for panel with clip relief, pencil ribs and striated. RIDGE CAP - FLOATING 15

16 "Z" CLOSURE SET ON DOUBLE BEAD BUTYL SEALANT SUPPORT FLASHING 20 GA. MINIMUM RIDGE CAP BUTYL SEALANT FASTENERS (5) PER PANEL MIN. (FIXED POINT) BEARING PLATE SEALANT AROUND RIBS MORZIP PANEL 4" FIXED OR SLIDING PANEL CLIP FASTENERS (2) PER CLIP MIN. ROOF DECK (NBM) RIGID INSULATION (NBM) Note: - Clip fasteners must be long enough to fasten into low cells of decking. - Use larger J- support for panel with clip relief, pencil ribs and striated. FIXED RIDGE - HIP 16

17 SEALANT AROUND RIBS RIDGE CAP V-600TE CORE-A-VENT "Z" CLOSURE SET ON DOUBLE BEAD BUTYL SEALANT FASTENER WITH NEOPRENE WASHER AT 12" O.C MORZIP PANEL 4" BEARING PLATE FIXED PANEL CLIP ROOF DECK (NBM) FASTENERS (5) PER PANEL MIN. FASTENERS (2) PER CLIP MIN. RIGID INSULATION (NBM) Note: - Clip fasteners must be long enough to fasten into low cells of decking. - Use larger J- support for panel with clip relief, pencil ribs and striated. VENTED RIDGE - FIXED 17

18 FOAM BLOCK W/ BUTYL TAPE SEALANT #12 X 7 8", HWH, W/W, (DO NOT PENETRATE PANEL) "J" SUPPORT AT PANEL ENDS HIP/ RAKE CAP DOUBLE BEADED SEALANT GABLE SUPPORT MORZIP METAL PANEL "Z" CLOSURE NOTCH AROUND RIBS IN FIELD SEALANT AROUND RIBS MORZIP FIXED OR SLIDING CLIP RIGID INSULATION (NBM) METAL DECK (NBM) FASTENERS (2) PER CLIP MIN. OPTIONS: 1) Field cut starter panel so that rake panels on both ends of roof are of same width requires field bending of cut panel to fit under formed 18 gauge support (as shown below). 2) Start roof with full panel, insert female leg under formed 18 gauge support. 3) Use larger J- support for panel with clip relief, pencil ribs and striated. HIP TO RAKE 18

19 METAL CLOSURE NOTCHED AT THE ENDS TO ACCEPT PANELS PANEL WIDTH Note: 1) See ridge details for more information 2) Set closure in butyl tape (top and bottom) RIDGE/ HIP CAP 'Z' CLOSURE SUPPLIED 10' LONG CONTINUOUS BUTYL TAPE WALL STRUCTURE S.S. POP RIVETS (3) PER PANEL ANGLE TRIM HIP - FLOATING 19

20 FOAM BLOCK W/ BUTYL TAPE #12 X 7 8", HWH, W/W, (DO NOT PENETRATE PANEL) GABLE SUPPORT MORZIP FIXED OR SLIDING CLIP BEARING PLATE RAKE TRIM MORZIP METAL PANEL RIGID INSULATION (NBM) ROOF DECK (NBM) The roof and structure must be allowed to move independently of each other. Thermal movement cannot be restricted. The gable clip is designed to allow this movement while holding down the roof panel. It will also hold the roof panel off the structure the same distance as both hold down clips. Since the gable clip is stationary, the gable trim piece can be attached to it for positive anchoring. The design of the gable flashing can be modified to suit the individual project as long as the basic concept is maintained. Spacing for gable clip is 2 0 o.c. maximum. For longer purlin spacing a gable clip trim is available in 10 0 sections. Options: 1) Field cut starter panel so that rake panels on both ends of roof are of same width. requires field bending of cut panel to fit under formed gable support (as shown below). 2) Start roof with full panel, insert female leg under formed gable support. 3) Clip fasteners must be long enough to fasten into low cells of decking RAKE DETAIL 20

21 MORZIP PANEL MORZIP FIXED OR SLIDING CLIP BUTYL SEALANT BEARING PLATE RAKE FLASHING RIGID INSULATION (NBM) ROOF DECK (NBM) Note: Clip fasteners must be long enough to fasten into low cells of decking. RAKE AT STEPPED EAVE 21

22 COMPLETE ASSEMBLY STEP: 1 FASTEN RAKE CLEAT STEP: 4 FIELD CUT PANEL STEP: 2 RAKE FLASHING STEP: 3 2 ROWS OF CONTINUOUS BUTYL SEALANT RAKE INSTALLATION STEP: 5 FIELD NOTCH AND BEND TO CREATE OPEN HEM 22

23 Since the width of the standing seam roof can vary due to compression or spreading during the installation, the module can be altered to minimize the endwall trim width. In cases of fixed panel width or module, the designer should center the roof panels if possible, to reduce the width of the trim pieces. The endwall flash should be sloped to allow drainage of water to avoid leaks at joints in the trim. Reinforcing of the trim may be required at large widths to support the joints. FLASHING URETHANE SEALANT BETWEEN FLASHING AND MASONRY RAKE FLASHING FOAM BLOCK #12 X 7 8", HWH, W/W, (DO NOT PENETRATE PANEL) GABLE SUPPORT FIXED OR SLIDING CLIP MORZIP PANEL 6"X6" BEARING PLATE FASTENERS AS REQUIRED METAL DECK (NBM) RIGID INSULATION (NBM) METAL WALL " MIN. RAKE FLASHING WALL TO RAKE FLASHING 23

24 TRANSITION FLASHING FIXED OR SLIDING CLIP KEY HOLE CLOSURE 3 8 " SUPPORT MATERIAL (PLYWOOD, DENSDECK OR SIMILAR - NBM) FIXED OR SLIDING CLIP 6" X 6" BEARING PLATE FASTENERS (2) PER CLIP MIN. RIGID INSULATION (NBM) METAL DECK (NBM) ALIGN FACE OF TRIM WITH CONTINUOUS RAKE CLIP AND STEP RAKE FLASHING RAKE AT SLOPING TO FLAT ROOF (FLOATING) 24

25 THROUGH-WALL FLASHING MASONRY FASTENER URETHANE SEALANT BETWEEN FLASHING AND MASONRY FOAM BLOCK MORZIP PANEL CLIP 6" X 6" BEARING PLATE #12 X 7 8", HWH, W/W, (DO NOT PENETRATE THRU THE PANEL) GABLE SUPPORT MORZIP METAL PANEL FASTENERS (2) PER CLIP MIN. METAL DECK (NBM) RIGID INSULATION (NBM) MASONRY BLOCK (NBM) STEP RAKE FLASHING " MIN. MORZIP METAL PANEL WALL TO RAKE STEP FLASHING 25

26 THROUGH-WALL FLASHING URETHANE SEALANT BETWEEN FLASHING AND MASONRY RAKE FLASHING GABLE SUPPORT FOAM BLOCK 1" 1" 1" #12 X 7 8", HWH, W/W, (DO NOT PENETRATE PANEL) 6"X6" BEARING PLATE METAL DECK (NBM) RIGID INSULATION (NBM) COMPRESSIBLE INSULATION (NBM) OPTIONS: 1) Field cut starter panel so that rake panels on both ends of roof are of same width requires field bending of cut panel to fit under continuous rake clip (as shown below). 2) start roof with full panel, insert female leg under continuous rake clip. WALL TO RAKE EXPANSION JOINT 26

27 #12 X 7 8", HWH, W/W, (DO NOT PENETRATE PANEL) BUTYL TUBE SEALANT ON TOP OF GABLE SUPPORT FOAM BLOCK CONTINUOUS GABLE SUPPORT 1" 1" 1" MORZIP METAL PANEL METAL DECK (NBM) RIGID INSULATION (NBM) Some building designs require an expansion joint to accommodate movement of the structure. The detail must be designed to allow movement in the anticipated directions. Several proprietary products are available which can be integrated into this basic design. Options: 1) Field cut starter panel so that rake panels on both ends of roof are of same width. Requires field bending of cut panel to fit under gable support (as shown below). 2) Start roof with full panel, insert female leg under gable support. PANEL EXPANSION JOINT 27

28 MORZIP METAL PANEL S.S. POP RIVETS (3) PER PANEL #10 X 1" TEK. WAFER HEAD FASTENERS AT 6" O.C. VALLEY FLASHING 1 8 "X1" CONTINUOUS TAPE SEALANT 4" OF SEALANT IN STIFFENING RIBS (SEE ABOVE) BASE J-TRIM 20 GA. SUB-PLATE VALLEY (FLOATING) 28

29 20 GA. SUB-PLATE KEY HOLE CLOSURE FASTENERS 6" O.C MORZIP METAL PANEL SAME HT. AS PANEL VALLEY FLASHING 6" MIN. MORZIP FIXED OR SLIDING CLIP FASTENERS (2) PER CLIP MIN. METAL DECK (NBM) RIGID INSULATION (NBM) Valley flashing must allow for sufficient area to carry anticipated runoff without overflow or backup under the roof edge. The raised center assists in diversion of water and allows for thermal movement. Floating valley requires fixed hip/ ridge. RAKE AT VALLEY FLOATING 29

30 C 12" MIN BACK PAN B CURB LENGTH 6" B C D 5" APRON D Large openings for equipment or hatchways require a curb with means of diverting the water around the opening. Set and secure roof curb on support framing. At least two parallel curb walls must be on support framing. In high load areas engineer needs to check for proper support. Loads shall not be supported by cantilever sections exceeding 1 0 in length. Cut roof panels to fit snugly around curb walls and to within 1 of the water diverter. Apply a wide band of tape caulk to the top side of curb flanges. Install and seal closures in ends of panels. Plug and caulk all rib ends. Press roof panels into place. Fasten roof panels through curb flanges to support steel using suitable fasteners for the roof system. A spacing of approximately 3 should be used. Inspect installation and fasteners. Apply an exterior sealant to seal seams around all sides of curb to insure a weathertight seal. In all cases the curb assembly is capped by a collar or skirt that extends down over the curb. Curb to be fixed to panel only. Allowance must be made at equipment curb and trim to allow for thermal movement. EQUIPMENT CURB FLASHING PLAN VIEW 30

31 12" MIN. BACK PAN CURB PENETRATION SIDE FLASHING 1" TABS EQUIPMENT CURB FLASHING 1 1 2" VARIES CURB LENGTH CURB CURB HEIGHT HEIGHT 5" 1" TABS 12" MIN. CURB HEIGHT 2" 5" 31

32 CURB CAP (NBM) 6" minimum TRANSITION FLASHING 18 GA GALVANIZED CAP (NBM) METAL DECK (NBM) RIGID INSULATION (NBM) FASTENERS (2) PER CLIP MIN. EQUIPMENT CURB - SECTION B 32

33 CURB CAP (NBM) BACK PAN BUTYL TAPE SEALANT BUTYL SEALANT DOUBLE BEAD CONTINUOUS 1 8 " x1" BUTYL TAPE SEALANT MORZIP FIXED OR SLIDING CLIP 6" - 10" MIN FASTENERS (2) PER CLIP MIN. METAL DECK (NBM) 18 GA GALVANIZED CAP (NBM) RIGID INSULATION (NBM) EQUIPMENT CURB - SECTION C 33

34 CURB CAP (NBM) APRON "J" SUPPORT AT PANEL ENDS DOUBLE BEAD 1 8"X1" BUTYL TAPE SEALANT 1" MIN. "Z" CLOSURE NOTCH AROUND RIBS IN FIELD SEALANT AROUND RIBS MORZIP CLIP 18 GA GALVANIZED CAP (NBM) RIGID INSULATION (NBM) METAL DECK (NBM) FASTENERS (2) PER CLIP MIN. EQUIPMENT CURB - SECTION D 34

35 BEFORE INSTALLING THE DEKTITE, PLACE CONTINUOUS BEAD OF SEALANT AROUND PIPE AT HEIGHT OF BOOT TOP STAINLESS STEEL PIPE CLAMP LIGHTNING PROTECTION ROD DEKTITE PIPE BOOT SET ON TAPE SEALANT AND FASTEN TO ROOF PANEL #14 X 7 8", TEK 3, HWH, W/W, PAINTED 2" O.C. 1" 1" CUT SLOTTED HOLE IN PANEL MORZIP ROOF PANEL J- HOOK FOR ELECTRICAL WIRE DEKTITE PIPE BOOT SET ON TAPE SEALANT AND FASTEN TO ROOF PANEL STAINLESS STEEL PIPE CLAMP CUT SLOTTED HOLE IN PANEL #14 X 7 8", TEK 3, HWH, W/W, PAINTED 2" O.C. Notes: 1) Attach dektite to panel only to allow thermal movement. 2) Center pipe penetration within panel width if possible. 3) Keep base of dektite away from panel edges (minimum 2"). 4) Provide 1" clearance between edge of pipe and panel hole. 1" 1" PIPE PENETRATION DETAIL MORZIP ROOF PANEL 35

36 6" 1 8 " GAP GUTTER SPLICE PLATE 4" GUTTER LAP DETAIL 1" 2" 1" END CAP 1" LAP GUTTER EXPANSION DETAIL 3 4 " 1 1 2" 3 4 " SET IN SEALANT EXPANSION COVER END CAP 4" END CAP Note: Use expansion joint every 25' GUTTER EXPANSION DETAIL GUTTER FLASHING CONDITIONS 36

37 4" 4" NOTCH NOTCH IN BOTTOM LEG RAKE LAP DETAIL SPLICE PLATE 6" 6" LAP EAVE INSIDE SPLICE PLATE 4" 4" NOTCH NOTCH IN BOTTOM LEG EAVE LAP DETAIL Note: Shingle laps in direction of water flow. RAKE AND EAVE FLASHING CONDITION 37

38 BUTYL SEALANT 6" 6" LAP RIDGE CAP - LAP DETAIL 6" NOTCH IN THE BOTTOM LEG FASTEN PANEL CLOSURE TO PANEL CLOSURE TO FIX IN PLACE TYP. LAP DETAIL WATER FLOW BUTYL SEALANT 6" 6" LAP HIP CAP - LAP DETAIL Note: Field Notch Hems As Required. RIDGE AND HIP FLASHING CONDITION 38

39 4" 3" CENTER HEM DOWN SPOUT OUTLET 4" 3" TYPICAL 4" X 3" ELBOW DIMENSIONS WITH 6" RETURN DOWNSPOUT 39

40 SNOCLIP S-5-Z COLORGARD SNOW FENCE M X.062" HEX FLANGE BOLT VERSACLIP MORZIP PANEL CLIP 2" STRIP OF MATCHED GAUGE & COLOR STRIP S-5-Z CLAMP S-5-Z CLAMP KEY 12" MIN MORZIP SIDE VIEW ASSEMBLY OF THE COLORGARD CROSS MEMBER CONTINUOUS VERSACLIP SNOCLIP S-5-Z CLAMP SLOPE RUBBER FOOT TOE Note: 1) Mount s-5-z clamp directly to top of panel rib with set screw. 2) Install 2" color strip from panel flat stock into snow guard. 3) Connect clip to snow guard, one per panel, centered. 4) Connect assembly to S-5-Z clamps. SNOW GUARD 40

41 LIGHTNING ROD AIR TERMINAL CONDUCTOR CABLE S-5-Z CLAMP SECTION CUT VIEW CONDUCTOR CABLE CLAMP ALUMINUM TOP MOUNT MORZIP PANEL Note: -Coat cables and clamp with bituminous. -Coating as necessary to prevent galvanic reaction. SIDE VIEW LIGHTNING PROTECTION 41