System No. SP777 (FOR HORIZONTAL OR VERTICAL SEPARATIONS)

Size: px
Start display at page:

Download "System No. SP777 (FOR HORIZONTAL OR VERTICAL SEPARATIONS)"

Transcription

1 System No. SP777 (FOR HORIZONTAL OR VERTICAL SEPARATIONS) F Rating - hr FT Rating - 0, /, 1 and 1-1/ hr (See Item ) FH Rating - hr FTH Rating - 0, /, 1 and 1-1/ hr (See Item ) A B A B C C SECTION A-A CONFIGURATION A 6 E F E H F G G 6 H SECTION B-B CONFIGURATION B

2 System No. SP777 SECTION C-C CONFIGURATION C SECTION - CONFIGURATION SECTION E-E CONFIGURATION E SECTION F-F CONFIGURATION F SECTION G-G CONFIGURATION G SECTION H-H CONFIGURATION H

3 System No. SP Floor or Wall Assembly - Minimum 11 mm thick reinforced low density or normal density (1600 to 00 kg/m ) structural concrete. Wall may also be constructed of nominal 00 mm thick concrete blocks. Maximum area of opening.7 m with maximum dimension of mm.. Through Penetrants - A maximum of 8 firestop configurations may be installed within the opening. The space between firestop configurations shall be minimum 16 mm to maximum 178 mm. The space between firestop configurations and periphery of opening shall be minimum 19 mm to maximum mm. Pipe, conduit, tubing or cable tray to be rigidly supported on both sides of floor or wall assembly. The FT and FTH rating of the system is dependent on the firestop configuration, as shown in the table below. Any combination of the following firestop configurations detailed herein may be used: Firestop Configuration FT and FTH Rating, Hr A 0 B 0 C 0 0 E 0 F / G 1-1/ H 0 and 1 (see Item ) Firestop Configuration A. Cable Trays - Maximum 91 mm wide by maximum 89 mm deep open-ladder or solid-back cable trays with channel-shaped side rails formed of minimum 1. mm thick steel. Cable trays are provided with minimum 1. mm thick steel rungs spaced a maximum of 00 mm apart, or a minimum 1. mm thick steel solid back. A maximum of cable trays are permitted per opening.. Cables - Aggregate cross-sectional area of cables in cable trays to be maximum 0 percent of the cross-sectional area of the cable tray based on a maximum 7 mm cable loading depth within the cable tray. Any combination of the following types and sizes of copper conductor cables may be used: A. Max 1/C 00 kcmil cable with cross-linked polyethylene (XLPE) jacket and insulation. B. Max /C No. AWG cable with XLPE jacket and insulation.. Batts and Blankets - Minimum 9 mm thickness of minimum 7 kg/m mineral wool batt insulation, *. Firestop System Components (Guide No. 0 U19.1) - Self Seal GG-00 (Floors or Walls) or Self

4 System No. SP777 Firestop Configuration B. Cable Tray - Maximum 91 mm wide by maximum 89 mm deep open-ladder cable tray with channelshaped side rails formed of minimum. mm thick aluminum. Cable trays are provided with minimum. mm thick aluminum rungs spaced a maximum of 00 mm apart. One cable tray to be installed in the opening.. Nonmetallic Sleeve - (Optional) - Nominal 89 mm diameter (or smaller) Schedule 10 polyvinyl chloride pipe. In floors, sleeve installed with nominal 0 mm projecting above floor. In walls, sleeve installed to project minimum 0 mm beyond each surface of the wall. A maximum of nonmetallic sleeves to be installed in the cable tray. The space between the sleeves and the cable tray should be minimum mm.. Cables - A maximum of eleven 1/C No. 1 AWG cables with cross-linked polyethylene (XLPE) jacket and insulation to be installed within the cable tray. Within each sleeve a maximum of two 1/C No. AWG cables may be installed.. Batts and Blankets - Minimum 9 mm thickness of minimum 7 kg/m mineral wool batt insulation, compressed minimum 0%, and firmly packed into the opening and sleeves as a permanent form. Material to be recessed from top surface of floor or from both surfaces of wall as required to accomodate the *6. Firestop System Components (Guide No. 0 U19.1) - Self Seal GG-00 (Floors or Walls) or Self Firestop Configuration C. Cable Tray - Maximum 91 mm wide by maximum 89 mm deep open-ladder cable tray with channelshaped side rails formed of minimum 1. mm thick steel. Cable trays are provided with minimum 1. mm thick steel rungs spaced a maximum of 00 mm apart. One cable tray to be installed in the opening.. Cables - A maximum of four 1/C No. 1 AWG cables with cross-linked polyethylene (XLPE) jacket and insulation to be installed within the cable tray.. Batts and Blankets - Minimum 9 mm thickness of minimum 7 kg/m mineral wool batt insulation, *. Firestop System Components (Guide No. 0 U19.1) - Self Seal GG-00 (Floors or Walls) or Self

5 System No. SP777 Firestop Configuration. Cable Tray - Maximum 00 mm wide by maximum 89 mm deep open-ladder cable tray with channelshaped side rails formed of minimum 1.6 mm thick steel. Cable trays are provided with minimum 1. mm thick steel rungs spaced a maximum of 00 mm apart. A maximum of four cable trays to be installed in the opening.. Batts and Blankets - Minimum 9 mm thickness of minimum 7 kg/m mineral wool batt insulation, *. Firestop System Components (Guide No. 0 U19.1) - Self Seal GG-00 (Floors or Walls) or Self Firestop Configuration E. Steel Conduit - Nominal 100 mm diameter (or smaller) electrical metallic tubing or steel conduit. One conduit to be installed within the firestop system. Conduit to be rigidly supported on both sides of floor or wall assembly.. Batts and Blankets - Minimum 9 mm thickness of minimum 7 kg/m mineral wool batt insulation, *. Firestop System Components (Guide No. 0 U19.1) - Self Seal GG-00 (Floors or Walls) or Self Firestop Configuration F. Copper Tubing - Nominal 100 mm diameter (or smaller) Type M (or heavier) copper tubing or nominal 10 mm diameter (or smaller) Type L (or heavier) copper tubing. One tube to be installed within the firestop system. Tube to be wrapped in pipe covering material and rigidly supported on both sides of floor or wall assembly.. Pipe Covering - Nominal mm thick ULC labelled hollow cylindrical heavy density (minimum 11 kg/m ) mineral wool fiber units with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product.. Batts and Blankets - Minimum 9 mm thickness of minimum 7 kg/m mineral wool batt insulation,

6 System No. SP777 *. Firestop System Components (Guide No. 0 U19.1) - Self Seal GG-00 (Floors or Walls) or Self Firestop Configuration G. Cable Tray - Maximum 91 mm wide by maximum 89 mm deep open-ladder cable tray with channelshaped side rails formed of minimum 1. mm thick steel. Cable trays are provided with minimum 1. mm thick steel rungs spaced a maximum of 00 mm apart. One cable tray to be installed in the opening.. Batts and Blankets - Minimum 9 mm thickness of minimum 7 kg/m mineral wool batt insulation, *. Firestop System Components (Guide No. 0 U19.1) - Self Seal GG-00 (Floors or Walls) or Self Firestop Configuration H. Steel Pipe - Nominal 06 mm diameter (or smaller) Schedule 0 (or heavier) or nominal 610 mm diameter (or smaller) Schedule 0 (or heavier) steel pipe. Pipe may be wrapped in pipe covering material and rigidly supported on both sides of floor or wall assembly.. Pipe Covering (Optional) - Nominal mm or 8 mm thick ULC labelled hollow cylindrical heavy density (minimum 11 kg/m ) mineral wool fiber units with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. FT and FTH Rating is 0 hr when pipe covering is not used.. Batts and Blankets - Minimum 9 mm thickness of minimum 7 kg/m mineral wool batt insulation, *. Firestop System Components (Guide No. 0 U19.1) - Self Seal GG-00 (Floors or Walls) or Self *Listed by Underwriters' Laboratories of Canada for use as a component within the appropriate System. Form: SP777 Rev.: 1 ate: 0/00