1 Other HEMCO Products Installation, Operation, Maintenance Manual InsMed Inc. UniMax Ventilated Hood Enclosure Made In The U.S.A. UniFlow CE UniFlow SE AireStream High Performance Energy Efficient Laboratory Fume Hoods UniFlow LE SEFA Scientific Equipment and Furniture Association UniFlow LE FM NSPE Safety Equipment NFPA National Fire Protection Association ASME American Society of Mechanical Engineers AEE Association of Energy Engineers Visit Call Toll Free: (800) S. Powell Road Independence MO, MM-UNIMAX Lab Planning Solutions Phone (816) Fax. (816) Visit Call Toll Free: (800) S. Powell Road Independence MO, Lab Planning Solutions Phone (816) Fax. (816)

2 Table of Contents GENERAL SYSTEM DESCRIPTION...3 RECEIVING AND INSPECTING SHIPMENTS... 4 PREPARATION FOR INSTALLATION... 5 SUGGESTED TOOL LIST... 5 REQUIRED TOOL LIST... 5 INSTALLATION... 6 MAINTENANCE General System Description UniMax Floor Mount Hood is constructed and equipped with: Modular Construction featuring wall panels that are 2 thick with chemical resistant composite resin surface skin panels. Structural framework to be clear of anodized aluminum extrusions. A rear varafl ow baffle is mounted on the rear wall of hood. Top mounted exhaust collar(s). 2 19

3 Receiving and Inspecting Shipments Maintenance of the hood: For all composite surfaces use a general purpose non-abrasive cleaner, For glass surfaces use a formula glass cleaner. (Windex, etc.). For painted or powder coated metal surfaces use a general-purpose nonabrasive cleaner. For anodized surfaces use a general-purpose non-abrasive cleaner. For acrylic surfaces use a mild detergent and soft damp cloth Keep the horizontal door track clean and clear of obstructions to ensure movable door operation. Explosion proof light fi xtures can accommodate watt bulbs. Check to make sure that the duct and baffle slots are free of obstructions. Check exhaust for correct airfl ow on a yearly basis. 1 Year Limited Warranty (Effective ) HEMCO warrants UniMax Enclosures for materials, and workmanship. HEMCO s warranty shall be for a period of (1) year from the date of sale to the original purchaser. will repair or replace products found to be defective in materials or workmanship within the period set forth above, provided that:(a) the product has not been subjected to misuse, contamination, neglect, accident, incorrect wiring, improper installation or servicing, or used in violation of instructions furnished by. And (b) as to any defects in materials or workmanship covered by this warranty, the product has shall be repaired or altered by anyone authorized by HEMCO Corporation, and (c) the serial number has not been removed, defaced or other wise changed, and (d), does not assume the costs of removal and/or installation of the product or any other incidental costs of removal and/or installation of the product or any other incidental costs which may arise as a result of any defect in material or workmanship, and (e) upon discovery of defect, Buyer shall notify. Any Warranty implied by law, including warranties of merchantability or fi tness, is in effect only for the duration of the expressed warranties set forth above, no person is authorized to give any other warranty, or to assume for any other liability in connection with the sale of it s products; shall not be liable for the loss of use, revenue, or profi t or for any injury, or for any other consequential or incidental damages, buyer is not relying on seller s judgement regarding original buyer particular requirements, and has had an opportunity to inspect the product to original buyer satisfaction. This Warranty is in lieu of all other expressed or implied Warranties This warranty gives you specifi c legal rights, and you may also have other rights, which vary, from state to state. Transportation companies are responsible for shipment from the time that it is received by them until it is delivered. All shipments leaving our plant have been carefully inspected and loaded on the carrier s vehicle. If a shipment arrives with the crating or packaging damaged, have the driver note the condition on the bill of lading and inspect the contents immediately for concealed damage. Due to the crate sizes and number of components HEMCO recommends that with any crate damage, even minor, that the bill of lading be signed for noting crate damage pending further inspection for concealed product damage If the equipment has been damaged in transit, immediately notify and fi le a claim with the carrier. Do not return to HEMCO. If this procedure is not followed, the carrier will reject the claim and the consignee will suffer the loss. Please notify HEMCO so that we may help you in anyway possible with evaluation, repair, replacement, and valuation of the damage that has occurred. Preparation For Installation Read the Complete Manual Gather Required Tools/Equipment Suggested Tool List Cordless screw driver/gun Forklift Gloves Thin fl exible putty knife Required Tool List 2 screwdriver 3/8 Open-end wrench Stepladders, 2 or more 2 or more people may be needed to safely construct the hood. Handle all contents with care, some parts may be sharp. 18 3

4 Deliver components to erection site and segregate. Note identifi cation markings on each panel and inside aluminum extrusions. Note: Insertion of the wall panels into the base may be aided by utilizing a thin flexible putty or spackling knife to guide the panel into the track. Note: Be very careful as sub-assemblies and wall sections can be very heavy, particularly the basin and the rear wall section. Use dollies or mechanical means to carry items over any distance. Orient basin so that the front is oriented to suit the customer s requirement. Note: left and right would be determined by facing front of enclosure and the drawing set. Remove banding holding grating into recess of the basin and the wood protecting the aluminum extrusions. Be sure wall panels are seated fully into the structural channels and plumb and square. Secure with provided #8 or #10 sheet metal screws. Utilized #8 screws fi rst, however, due to pre-assembly the #8 screw may strip or may not bite then utilize the #10 screw. NOTE: Some pictures shown are from different but similar style projects. NOTE: Quick ratchet bar clamps to stepladder may be used to partially support the initial panel until other panels can be permanently secured. The Fume Hood is often the primary control device for protecting laboratory workers when working with toxic and/or flammable chemicals. OSHA s Laboratory Standard (29 CF ) requires that fume hoods be maintained and function properly when used. Before using the Fume Hood: Make sure that you understand the operation of the hood enclosure. You should be trained to use it properly. Know the hazards of the chemical you are working with; refer to the chemical (MSDS) Material Data Safety Sheet if you are unsure. Ensure that the exhaust system is turned on for operation. Make sure that the doors are closed for operation. The hinged doors are open only when equipment is being set up or when samples are being loaded. When using the Fume Hood: Do not walk in or put your head inside the vertical plane of the hood door opening when fumes are present. Use appropriate safety protection. Laboratory Safety for Chemical Fume Hoods Be sure that nothing blocks the airfl ow through the baffl es or through the air inlet grills. Elevate large equipment above the fl oor to allow air to fl ow underneath. Keep all materials inside the hood at least (8) inches from the door opening. When not working in the hood, or when a process is in operation, keep the doors closed. Do not permanently store chemicals inside the hood. Promptly report any hood that is not functioning properly to your supervisor. The doors should be closed and the hood tagged and taken out of service until repairs can be completed. When using extremely hazardous chemicals, understand your laboratory s action plan in case an emergency. Wipe up spills immediately. Minimize drafts and turbulence in front of the hood. Routinely validate airfl ow. 4 17

5 Note: Panels Are marked with Location Labels Attach Panel (Right Side Walls A & B) to Back Wall Section to (Right Side Back Wall) Completed Unit Seal any air gaps and joints of the enclosure not previously sealed with silicone sealant. Typical air gaps would be walls to ceiling, fl oor perimeter, etc. General clean up of site, installation of any other equipment, etc Note: All explosion proof electrical components are required to be wired by local certifi ed electrician to comply with local codes. Secure with #8 or #10 sheet metal screws. Attach Panel (Center Back wall) to (Back Wall to Left Wall Panels) with #8 or #10 sheet metal screws. 16 5

6 Seal the wall to ceiling joint completely around the perimeter of the hood with 100% silicon sealant. NOTE: Ceiling panel can be set on the tines of a fork truck and lifted to the proper height and (hand over head) into final position utilizing stepladders inside and outside the enclosure or can be passed (hand over head) from (2) persons on the fl oor to (2)persons on separate stepladders. CAUTION: Roof Structure is not designed to support more than pounds of Load Secure upper (ceiling) connections with #10 machine bolt (interior) and nylon nuts (exterior) Cover screw heads with #10 PVC cover caps. Secure from back with provided #8 or #10 sheet metal screws. Attach Panel (Back Wall to Left Wall) to (Back Left Sidewall A & B panels) with #8 or #10 sheet metal screws. 6 Attach (Right Front Wall panel) to ( Right sidewall panel A). Attach (Left Front Wall panel) to ( Left sidewall panel A). Install Top Section of Light fi xture trough roof of ceiling panel Thread bottom section of Light fi xture into the top section from inside the Hood 15

7 Install: Doors Labeled ( Hinge Right Side Door & Right Side Door Hinge) into Front Right Door Frame with screws provided. Attach (Right Front Wall panel) to ( Right sidewall panel A). Install Aluminum escutcheon On Top Edges of walls Secure with provided #8 or #10 sheet metal screws. Install: Doors Labeled ( Hinge Left Side Door & Left Side Door Hinge) into Front Left Door Frame with screws provided. Install Metal Door Frame To Left and Right Walls Secure Metal Door Frame with 3/8 or 1/2 Anchors and Nuts with Washers to the Floor. 14 7

8 77-5/8 77-5/8 Note: Door Frame consists of (3) uprights and a Header. Note: distance between fl oor mounting bolts is 77-5/8 inches Secure Frame with provided #8 or #10 sheet metal screws, to (Left Front Wall) and (Right Front Wall). Install (Back Top # 5 Right) into Top Right Back wall escutcheon. Install (Back Top # 6 Center) into Top Center Back wall escutcheon. Install Aluminum Door Frames (Left) and (Right) into Metal door frame. Secure with provided #8 or #10 sheet metal screws. Install (Back Top # 7 Center Left) into Top Center Left wall escutcheon. Install Right and Left Front Post Electrical Strips on front corner posts. 8 13

9 w Install: (Left Side Wall Top #4) into escutheon on top of (Left Side Wall panels A & B) Install (Right Side Wall Top #4) into Top Right Front escutheon. Install (Small Header Piece above Left Door). Install (Small Header Piece above Right Door). 12 Install (Front Center Top #2) into Top Front wall escutcheon. Install (Left Top Panel #1) into Top Front wall escutcheon. Install Right Ceiling panel # 5, into Aluminum Escutcheons. Note: Ceiling Panels are Numbered 1 to 5, with #1 located on left over to # 5 on the right. Install Aluminum escutcheon between each Ceiling panel. 9

10 Set the #4 Center ceiling panel in place, on the seat of the h extrusions. Be careful of fl exing the ceiling panel while setting it in place to avoid damage. Secure with provided #8 or #10 sheet metal screws. Set the #3 ceiling panel in place, on the seat of the h extrusions. Light fi xtures are orientated to the front of the enclosure and the exhaust outlet is at the rear. Secure with provided #8 or #10 sheet metal screws. (Left Upper Baffle) is lifted into place. Secure lower connection with provided #8 or #10 sheet metal screws. (Center Upper Baffl e) is lifted into place. Secure lower Connection with provided #8 or #10 sheet metal screws. Set the #2 ceiling panels in place, on the seat of the h extrusions. Be careful of fl exing the ceiling panel while setting it in place to avoid damage. Secure with provided #8 or #10 sheet metal screws. 10 Set the #1 Left ceiling panel in place, on the seat of the h extrusions. Light fi xtures are orientated to the front of the enclosure and the exhaust outlet is at the rear. Secure with provided #8 or #10 sheet metal screws. (Right Upper Baffl e) is lifted into place. Secure lower connection with provided #8 or #10 sheet metal screws. Install: (Right Side Wall Top #4) into escutcheon on top of (Right Side Wall panels A & B) 11