DETAIL 1 DETAIL 2 PARTIAL GROUND FLOOR PLAN SCALE: 1/4" = 1'-0" WOODBRIDGE 502 MECHANICAL ROOM CORRIDOR 3

Size: px
Start display at page:

Download "DETAIL 1 DETAIL 2 PARTIAL GROUND FLOOR PLAN SCALE: 1/4" = 1'-0" WOODBRIDGE 502 MECHANICAL ROOM CORRIDOR 3"

Transcription

1 MEHANIAL ROOM ORRIDOR 3 STEEL STUD FRAMING ELEVATOR LOBBY LIGHT FIXTURE BEYOND 1 A1 JANITOR LOSET A1 5/8" TYPE X GYPSUM BD. (TYP) PAINT ELEVATOR DIRETION FIXTURE WALL ANGLE EXISTING AOUSTIAL EILING DETAIL 1 SALE: 1" = 1'-0" A1 11 TRASH/OMPATOR ROOM STAIR A UP INSTALL FLOOR DESIGNATION ON EAH DOOR JAMB (2 PER DOOR). MOUNT AT 54" A.F.F. REMOVE ALL EXISTING PAINT AND PAINT HOLLOW METAL FRAME (JAMBS & HEAD) DETROIT HOUSING OMMISSION DETROIT, MIHIGAN STAINLESS STEEL ORNER GUARD REPAIR GYPSUM BOARD PRIOR TO INSTALLING ORNER GUARD UP STAIR B DETAIL 2 SALE: 1" = 1'-0" A1 ALLIANE ARHITETS PARTIAL GROUND FLOOR PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 502 A1

2 GENERAL NOTES INSTALL NEW FLOORING IN EAH ELEVATOR. WIRE BRUSH AND LEAN AR THRESHOLDS. AT EAH LANDING, AGGRESSIVELY PREPARE AND PAINT AST IRON THRESHOLDS AT EAH FLOOR. LEAN ALL STAINLESS STEEL (WALL PANELS, AR DOORS, HALL DOORS, ET.). PAINT EILING AND EXPANDED METAL OPENINGS. RE-SEURE ALL HANDRAILS. USE "LOTITE" OR EQUIVALENT. BROOM LEAN PIT. RETAIN EXISTING GUARDRAIL. REMOVE STEEL HATH. INSTALL AGE WITH GATE. SEE DETAIL 1/A PAINT ONRETE FLOOR, MU WALLS, EILING, BEAMS, ONDUITS, WIRE WAYS, STAIR STRUTURES, HANDRAILS/GUARDRAILS. ELEVATOR SUBONTRATOR SHALL PROVIDE, AND GENERAL ONTRATOR SHALL INSTALL LOK BOX (1 REQUIRED), FOR AESS TO ELEVATOR MAHINE ROOM FROM STAIR AT 14TH FLOOR. VERIFY LOATION WITH OWNER. ENLOSE ROOF DRAIN WITH NEW WALL ONSTRUTION: 2 1/2" METAL STUDS AND 5/8" TYPE 'X' GYPSUM BOARD. AVOID ONFLIT WITH ELETRI BASEBOARD HEATER. FILL/GROUT DRAIN PIPE PENETRATION THROUGH SHAFT WALL. SEE PHOTO 2. REPAIR MU WALL AT GFI OUTLET. SEE PHOTO PAINT WALLS. REPLAE VINYL BASE. (MATH EXISTING). EXISTING DISPLAY ASE & BOARDS TO REMAIN. REMOVE & REINSTALL TO FAILITATE PAINTING. REMOVE "USE STAIRS" SIGNAGE & REPAIR WALL PRIOR TO PAINTING. PATH ONRETE FLOOR WHERE PIPING/ONDUITS ARE REMOVED. SEE MEP - TYPIAL. EXISTING FIRE EXTINGUISHER TO REMAIN. LEAN ALL DUST & DEBRIS FROM SHAFT VENTS (2). OORDINATE AESS TO SREEN WITH ELEVATOR SUBONTRATOR. INFILL 24" x 24" OPENING IN MU WALL. METER LOSET METER LOSET ORRIDOR DN UP STAIR 9 DETROIT HOUSING OMMISSION DETROIT, MIHIGAN UP DN ALLIANE ARHITETS PARTIAL TYPIAL FLOOR PLAN SALE: 1/4" = 1'-0" (TYPIAL FLOORS 2-14) WOODBRIDGE 502 A2

3 16 PAINT EXISTING GUARD & HANDRAILS FAN ROOM DN DETROIT HOUSING OMMISSION DETROIT, MIHIGAN ALLIANE ARHITETS LOWER ELEVATOR EQUIPMENT ROOM PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 502 A3

4 11 PHOTO 1 12 PHOTO " MAX. PAINT EXISTING GUARDRAIL STEEL AGE SHALL BE REMOVABLE. HOWEVER, ALL FASTENERS SHALL BE TAMPER RESISTANT TYPE. 10 OPEN 3'-0" DOOR (FULL HGT.) 7 1 A4 MAHINE ROOM DETROIT HOUSING OMMISSION DETROIT, MIHIGAN OPEN 3" MAX. 8" EXISTING STEEL LADDER TO REMAIN - PAINT ALLIANE ARHITETS DETAIL SALE: 1/2" = 1'-0" 1 A4 UPPER ELEVATOR EQUIPMENT ROOM PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 502 A4

5 MEHANIAL ROOM ORRIDOR 3 STEEL STUD FRAMING LIGHT FIXTURE BEYOND WALL ANGLE EXISTING AOUSTIAL EILING 5/8" TYPE X GYPSUM BD. (TYP) PAINT ELEVATOR DIRETION FIXTURE 2 A5 1 A5 ELEVATOR LOBBY 12 JANITOR LOSET 2 2 DETAIL 1 SALE: 1" = 1'-0" A INSTALL FLOOR DESIGNATION ON EAH DOOR JAMB (2 PER DOOR). MOUNT AT 54" A.F.F. REMOVE ALL EXISTING PAINT AND PAINT HOLLOW METAL FRAME (JAMBS & HEAD) STAINLESS STEEL ORNER GUARD UP STAIR A TRASH/OMPATOR ROOM DETROIT HOUSING OMMISSION DETROIT, MIHIGAN REPAIR GYPSUM BOARD PRIOR TO INSTALLING ORNER GUARD DETAIL 2 SALE: 1" = 1'-0" A5 STAIR B UP ALLIANE ARHITETS PARTIAL GROUND FLOOR PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 404 A5

6 GENERAL NOTES INSTALL NEW FLOORING IN EAH ELEVATOR. WIRE BRUSH AND LEAN AR THRESHOLDS. AT EAH LANDING, AGGRESSIVELY PREPARE AND PAINT AST IRON THRESHOLDS AT EAH FLOOR. REPLAE WALL PANELS WITH STAINLESS STEEL APPLIED DIRETLY TO AR. LEAN ALL STAINLESS STEEL (WALL PANELS, AR DOORS, HALL DOORS, ET.). REMOVE EXISTING AR EILING, LIGHTS, ET. PAINT EILING AND EXPANDED METAL OPENINGS. REMOVE AND REINSTALL HANDRAILS AFTER INSTALLATION OF NEW WALL PANELS. SET AT 34" AFF TO ENTERLINE OF HANDRAIL. INSTALL W/ "LOTITE", OR EQUIVALENT PAINT ONRETE FLOOR, MU WALLS, EILING, BEAMS, ONDUITS, WIRE WAYS, STAIR STRUTURES, AND HANDRAILS/GUARDRAILS. ELEVATOR SUBONTRATOR SHALL PROVIDE, AND GENERAL ONTRATOR SHALL INSTALL LOK BOX (1 REQUIRED), FOR AESS TO ELEVATOR MAHINE ROOM FROM STAIR AT 14TH FLOOR. VERIFY LOATION WITH OWNER. ENLOSE ROOF DRAIN WITH NEW WALL ONSTRUTION: 2 1/2" METAL STUDS AND 5/8" TYPE 'X' GYPSUM BOARD. AVOID ONFLIT WITH ELETRI BASEBOARD HEATER. REPAIR MU WALL AT ELETRIAL OUTLET. SEE PHOTO INSTALL PAINTED SHEET METAL SHROUD AROUND ROOF DRAIN & PIPING. PITH TOWARD OPENING AT LADDER. SEE DETAIL 1/A8. PATH ONRETE FLOOR WHERE PIPING/ONDUITS ARE REMOVED - SEE MEP, TYPIAL. EXISTING FIRE EXTINGUISHER TO REMAIN. INFILL 24" x 24" OPENING IN MU WALL. LEAN ALL DUST & DEBRIS FROM SHAFT VENTS (2). OORDINATE AESS TO SREEN WITH ELEVATOR SUBONTRATOR. 6 7 BROOM LEAN PIT. RETAIN EXISTING GUARDRAIL. REMOVE STEEL HATH. PAINT EXISTING AGE AND GATE. 12 PAINT WALLS. REPLAE VINYL BASE (MATH EXISTING). EXISTING DISPLAY ASE & BOARDS REMAIN. REMOVE & REINSTALL TO FAILITATE PAINTING. REMOVE "USE STAIRS" SIGN & REPAIR WALL PRIOR TO PAINTING. METER LOSET METER LOSET ORRIDOR UP STAIR DN DETROIT HOUSING OMMISSION DETROIT, MIHIGAN DN UP ALLIANE ARHITETS PARTIAL TYPIAL FLOOR PLAN SALE: 1/4" = 1'-0" (TYPIAL FLOORS 2-14) WOODBRIDGE 404 A6

7 17 DN FAN ROOM PAINT EXISTING GUARD & HANDRAILS DETROIT HOUSING OMMISSION DETROIT, MIHIGAN ALLIANE ARHITETS LOWER ELEVATOR EQUIPMENT ROOM PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 404 A7

8 OPEN PITH ENLOSE ROOF DRAIN W/ PAINTED SHEET METAL ENLOSURE. SEURE TO EILING. DETAIL 1 SALE: 3/4" = 1'-0" A8 PHOTO EXISTING SEURITY AGE TO REMAIN - PAINT 7 13 DETROIT HOUSING OMMISSION DETROIT, MIHIGAN MAHINE ROOM OPEN ALLIANE ARHITETS UPPER ELEVATOR EQUIPMENT ROOM PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 404 A8

9 MEHANIAL ROOM STEEL STUD FRAMING ORRIDOR 3 LIGHT FIXTURE BEYOND WALL ANGLE EXISTING AOUSTIAL EILING 5/8" TYPE X GYPSUM BD. (TYP) PAINT ELEVATOR DIRETION FIXTURE 2 A9 1 A9 ELEVATOR LOBBY 12 2'-0" JANITOR LOSET 2 2 DETAIL 1 SALE: 1" = 1'-0" A INSTALL FLOOR DESIGNATION ON EAH DOOR JAMB (2 PER DOOR). MOUNT AT 54" A.F.F. REMOVE ALL EXISTING PAINT AND PAINT HOLLOW METAL FRAME (JAMBS & HEAD) STAINLESS STEEL ORNER GUARD UP STAIR A TRASH/OMPATOR ROOM DETROIT HOUSING OMMISSION DETROIT, MIHIGAN REPAIR GYPSUM BOARD PRIOR TO INSTALLING ORNER GUARD DETAIL 2 SALE: 1" = 1'-0" A9 STAIR B UP ALLIANE ARHITETS PARTIAL GROUND FLOOR PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 503 A9

10 GENERAL NOTES INSTALL NEW FLOORING IN EAH ELEVATOR. WIRE BRUSH AND LEAN AR THRESHOLDS. AT EAH LANDING, AGGRESSIVELY PREPARE AND PAINT AST IRON THRESHOLDS AT EAH FLOOR. LEAN ALL STAINLESS STEEL (WALL PANELS, AR DOORS, HALL DOORS, ET.). PAINT EILING AND EXPANDED METAL OPENINGS. SEURE HANDRAILS. USE "LOTITE" OR EQUIVALENT. BROOM LEAN PIT. RETAIN EXISTING GUARDRAIL. REMOVE STEEL HATH. INSTALL AGE AND GATE PAINT ONRETE FLOOR, MU WALLS, EILING, BEAMS, ONDUITS, WIRE WAYS, STAIR STRUTURES, AND HANDRAILS/GUARDRAILS. ELEVATOR SUBONTRATOR SHALL PROVIDE, AND GENERAL ONTRATOR SHALL INSTALL LOK BOX (1 REQUIRED), FOR AESS TO ELEVATOR MAHINE ROOM FROM STAIR AT 14TH FLOOR. VERIFY LOATION WITH OWNER. ENLOSE ROOF DRAIN WITH NEW WALL ONSTRUTION: 2 1/2" METAL STUDS AND 5/8" TYPE 'X' GYPSUM BOARD. AVOID ONFLIT WITH ELETRI BASEBOARD HEATER. REPAIR MU WALL AT ELETRIAL OUTLET. SEE PHOTO PAINT WALLS. REPLAE VINYL BASE (MATH EXISTING). EXISTING DISPLAY ASE & BOARDS TO REMAIN. REMOVE & REINSTALL TO FAILITATE PAINTING. REMOVE "USE STAIR" SIGNS & REPAIR WALL PRIOR TO PAINTING. PATH ONRETE FLOOR WHERE PIPING/ONDUITS ARE REMOVED - SEE MEP, TYPIAL. EXISTING FIRE EXTINGUISHER TO REMAIN. RELOATE TO NEW LOATION TO FAILITATE AGE INSTALLATION. LEAN ALL DUST & DEBRIS FROM SHAFT VENTS (2). OORDINATE AESS TO SREEN WITH ELEVATOR SUBONTRATOR. INFILL 24" x 24" OPENING IN MU WALL. METER LOSET METER LOSET ORRIDOR UP STAIR DN DETROIT HOUSING OMMISSION DETROIT, MIHIGAN DN UP ALLIANE ARHITETS PARTIAL TYPIAL FLOOR PLAN SALE: 1/4" = 1'-0" (TYPIAL FLOORS 2-14) WOODBRIDGE 503 A10

11 15 DN FAN ROOM PAINT EXISTING GUARD & HANDRAILS DETROIT HOUSING OMMISSION DETROIT, MIHIGAN ALLIANE ARHITETS LOWER ELEVATOR EQUIPMENT ROOM PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 503 A11

12 16 PAINT EXISTING GUARDRAIL STEEL AGE SHALL BE REMOVABLE. HOWEVER, ALL FASTENERS SHALL BE TAMPER RESISTANT TYPE. 3" MAX. 10 3'-0" DOOR (FULL HGT.) OPEN MAHINE ROOM 1 A12 7 DETROIT HOUSING OMMISSION DETROIT, MIHIGAN OPEN 3" MAX. 8" EXISTING STEEL LADDER TO REMAIN - PAINT ALLIANE ARHITETS DETAIL SALE: 1/2" = 1'-0" 1 A12 UPPER ELEVATOR EQUIPMENT ROOM PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 503 A12

13 MEHANIAL ROOM ORRIDOR 3 ELEVATOR LOBBY JUNTION BOX W/ PAINTED OVER & WIRING FOR FUTURE KEY FOB. ROUTE ABLE THROUGH HOISTWAY IN TRAVELING ABLE TO ELEVATOR MAHINE ROOM TEST EXISTING JANITOR LOSET A REPLAE EXISTING SWITH J B B SP1 J DEMO EXISTING SURFAE MOUNTED LIGHT FIXTURE AND REPLAE WITH JUNTION BOX, EXTEND IRUIT TO NEW WALL MOUNTED FIXTURES A EMERGENY GENERATOR JEWEL. REFER TO NOTE 2 AND SPEIFIATIONS REPLAE SUMP PUMP AND REEPTALE, REONNET TO EXISTING DRAIN WITH NEW HEK VALVE. LEAN SUMP PRIOR TO INSTALLATION. MODIFY GRATE AS NEESSARY. G A TRASH/OMPATOR ROOM STAIR A REPLAE EXISTING DUPLEX WITH NEW GFI DUPLEX DETROIT HOUSING OMMISSION DETROIT, MIHIGAN STAIR B ALLIANE ARHITETS PARTIAL GROUND FLOOR MEP PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 502 MEP1

14 METER LOSET METER LOSET ORRIDOR TEST EXISTING STAIR DETROIT HOUSING OMMISSION DETROIT, MIHIGAN TYPIAL UPPER FLOOR MEP PLAN SALE: 1/4" = 1'-0" (TYPIAL FLOORS 2-14) WOODBRIDGE 502 ALLIANE ARHITETS MEP2

15 REPLAE EXISTING LIGHT SWITHES FAN ROOM AP HYDRONI SUPPLY AND RETURN LINES FOR REMOVED HEATER BELOW EILING DETROIT HOUSING OMMISSION DETROIT, MIHIGAN AP FIRE PROTETION SPRINKLER PIPING LOWER ELEVATOR EQUIPMENT ROOM MEP PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 502 ALLIANE ARHITETS MEP3

16 REMOVE 4 LIGHT FIXTURES TO BE REPLAED BASEBOARD HEATER INSTALL 6 LIGHT FIXTURES INSTALL 2 NEW LIGHT FIXTURES. EXTEND IRUIT TO EXISTING FIXTURES EB1 ELV-TRL XFMR MAHINE ROOM XFMR REMOVE HEATER ELV-TRL REMOVE PREVIOUSLY APPED FIRE PROTETION SPRINKLER PIPING. AP BELOW ELEVATOR EQUIPMENT FLOOR LEVEL. REMOVE FLOW ALARM FROM FIRE ALARM SYSTEM REMOVE HEATER - INLUDING IRUIT AND HYDRONI PIPING. AP HYDRONI PIPING BELOW FLOOR EXTEND HTR. KT. TO BASEBOARD HEATER ELV-TRL G XFMR XFMR MAHINE ROOM ELV-TRL W1 EF1 HS MS1 ROUTE LINESET, POWER ABLE, AND ONDENSATE THROUGH WALL, TERMINATE AT MS1 ON ROOF PROVIDE DISONNET WITH IRUIT OUT OF EMERGENY PANEL IN LOWER ELEVATOR EQUIP. ROOM INSTALL NEW EXHAUST FAN ON EXIST. PENETRATION AND INTERONNET TO FIRE ALARM TO OPERATE ON GENERAL ALARM. DETROIT HOUSING OMMISSION DETROIT, MIHIGAN REMOVE SPRINKLER PIPING TO BELOW FLOOR AND AP ELEVATOR EQUIP. MEP DEMO PLAN SALE: LOKABLE IRUIT BREAKER DISONNETS FOR AR LIGHT - LABEL 1/4" = 1'-0" SALE: REPLAE EXISTING DUPLEX WITH GFI DUPLEX TEST EXISTING SMOKE DETETORS, ADD RELAY TO DEDIATED SMOKE DETETOR SYSTEM AND WIRE TO FIREMAN'S HAT LIGHT SIGNAL IN ELEVATORS ELEVATOR EQUIP. MEP PLAN 1/4" = 1'-0" WOODBRIDGE 502 ALLIANE ARHITETS MEP4

17 MEHANIAL ROOM ORRIDOR 3 JUNTION BOX W/ PAINTED OVER & WIRING FOR FUTURE KEY FOB. ROUTE ABLE THROUGH HOISTWAY IN TRAVELING ABLE TO ELEVATOR MAHINE ROOM TEST EXISTING DEMO EXISTING SURFAE MOUNTED LIGHT FIXTURE AND REPLAE WITH JUNTION BOX, EXTEND IRUIT TO NEW WALL MOUNTED FIXTURES EMERGENY GENERATOR JEWEL. REFER TO NOTE 2 AND SPEIFIATIONS REPLAE SUMP PUMP AND REEPTALE, REONNET TO EXISTING DRAIN WITH NEW HEK VALVE. LEAN SUMP PRIOR TO INSTALLATION. MODIFY GRATE AS NEESSARY. B ELEVATOR LOBBY SP1 J REPLAE EXISTING SWITH B JANITOR LOSET A A A G REPLAE EXISTING DUPLEX WITH NEW GFI DUPLEX STAIR A TRASH/OMPATOR ROOM DETROIT HOUSING OMMISSION DETROIT, MIHIGAN STAIR B ALLIANE ARHITETS PARTIAL GROUND FLOOR MEP PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 404 MEP5

18 METER LOSET METER LOSET ORRIDOR TEST EXISTING STAIR DETROIT HOUSING OMMISSION DETROIT, MIHIGAN TYPIAL UPPER FLOOR MEP PLAN SALE: 1/4" = 1'-0" (TYPIAL FLOORS 2-14) WOODBRIDGE 404 ALLIANE ARHITETS MEP6

19 AP FIRE PROTETION SPRINKLER PIPING AP HYDRONI SUPPLY AND RETURN LINES FOR REMOVED HEATER BELOW EILING FAN ROOM REPLAE EXISTING LIGHT SWITHES DETROIT HOUSING OMMISSION DETROIT, MIHIGAN LOWER ELEVATOR EQUIPMENT ROOM MEP PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 404 ALLIANE ARHITETS MEP7

20 REMOVE 6 LIGHT FIXTURES TO BE REPLAED REMOVE BASEBOARD TO BE REPLAED INSTALL 6 LIGHT FIXTURES BASEBOARD HEATER REMOVE HEATER - INLUDING IRUIT AND HYDRONI PIPING. AP HYDRONI PIPING BELOW FLOOR MAHINE ROOMOM XFMR XFMR ELV-TRL ELV-TRL LOKABLE IRUIT BREAKER DISONNETS FOR AR LIGHT - LABEL ROUTE LINESET, POWER ABLE, AND ONDENSATE THROUGH WALL, TERMINATE AT MS1 ON ROOF PROVIDE DISONNET WITH IRUIT OUT OF EMERGENY PANEL IN LOWER ELEVATOR EQUIP. ROOM INSTALL NEW EXHAUST FAN ON EXIST. PENETRATION AND INTERONNET TO FIRE ALARM TO OPERATE ON GENERAL ALARM. MS1 W1 HS EF1 XFMR MAHINE ROOM ELV-TRL G ELV-TRL XFMR EB1 DETROIT HOUSING OMMISSION DETROIT, MIHIGAN TEST EXISTING SMOKE DETETORS, ADD RELAY TO DEDIATED SMOKE DETETOR SYSTEM AND WIRE TO FIREMAN'S HAT LIGHT SIGNAL IN ELEVATORS REPLAE EXISTING DUPLEX WITH GFI DUPLEX ELEVATOR EQUIP. MEP DEMO PLAN SALE: 1/4" = 1'-0" SALE: ELEVATOR EQUIP. MEP PLAN 1/4" = 1'-0" WOODBRIDGE 404 ALLIANE ARHITETS MEP8

21 MEHANIAL ROOM ORRIDOR 3 JUNTION BOX W/ PAINTED OVER & WIRING FOR FUTURE KEY FOB. ROUTE ABLE THROUGH HOISTWAY IN TRAVELING ABLE TO ELEVATOR MAHINE ROOM TEST EXISTING DEMO EXISTING SURFAE MOUNTED LIGHT FIXTURE AND REPLAE WITH JUNTION BOX, EXTEND IRUIT TO NEW WALL MOUNTED FIXTURES EMERGENY GENERATOR JEWEL. REFER TO NOTE 2 AND SPEIFIATIONS REPLAE SUMP PUMP AND REEPTALE, REONNET TO EXISTING DRAIN WITH NEW HEK VALVE. LEAN SUMP PRIOR TO INSTALLATION. MODIFY GRATE AS NEESSARY. B ELEVATOR LOBBY SP1 J REPLAE EXISTING SWITH B JANITOR LOSET A A A G REPLAE EXISTING DUPLEX WITH NEW GFI DUPLEX STAIR A TRASH/OMPATOR ROOM DETROIT HOUSING OMMISSION DETROIT, MIHIGAN STAIR B ALLIANE ARHITETS PARTIAL GROUND FLOOR MEP PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 503 MEP9

22 METER LOSET METER LOSET ORRIDOR TEST EXISTING STAIR DETROIT HOUSING OMMISSION DETROIT, MIHIGAN TYPIAL UPPER FLOOR MEP PLAN SALE: 1/4" = 1'-0" (TYPIAL FLOORS 2-14) WOODBRIDGE 503 ALLIANE ARHITETS MEP10

23 AP FIRE PROTETION SPRINKLER PIPING AP HYDRONI SUPPLY AND RETURN LINES FOR REMOVED HEATER BELOW EILING FAN ROOM REPLAE EXISTING LIGHT SWITHES DETROIT HOUSING OMMISSION DETROIT, MIHIGAN LOWER ELEVATOR EQUIPMENT ROOM MEP PLAN SALE: 1/4" = 1'-0" WOODBRIDGE 503 ALLIANE ARHITETS MEP11

24 REMOVE 6 LIGHT FIXTURES TO BE REPLAED REMOVE BASEBOARD TO BE REPLAED INSTALL 6 LIGHT FIXTURES BASEBOARD HEATER REMOVE BASEBOARD HEATER. TERMINATE ELETRIAL IN JUNTION BOX REMOVE HEATER - INLUDING IRUIT AND HYDRONI PIPING. AP HYDRONI PIPING BELOW FLOOR MAHINE ROOMOM XFMR XFMR ELV-TRL ELV-TRL LOKABLE IRUIT BREAKER DISONNETS FOR AR LIGHT - LABEL ROUTE LINESET, POWER ABLE, AND ONDENSATE THROUGH WALL, TERMINATE AT MS1 ON ROOF PROVIDE DISONNET WITH IRUIT OUT OF EMERGENY PANEL IN LOWER ELEVATOR EQUIP. ROOM INSTALL NEW EXHAUST FAN ON EXIST. PENETRATION AND INTERONNET TO FIRE ALARM TO OPERATE ON GENERAL ALARM. MS1 W1 HS EF1 XFMR G MAHINE ROOM ELV-TRL ELV-TRL XFMR EB1 DETROIT HOUSING OMMISSION DETROIT, MIHIGAN TEST EXISTING SMOKE DETETORS, ADD RELAY TO DEDIATED SMOKE DETETOR SYSTEM AND WIRE TO FIREMAN'S HAT LIGHT SIGNAL IN ELEVATORS REPLAE EXISTING DUPLEX WITH GFI DUPLEX ELEVATOR EQUIP. MEP DEMO PLAN SALE: 1/4" = 1'-0" SALE: ELEVATOR EQUIP. MEP PLAN 1/4" = 1'-0" WOODBRIDGE 503 ALLIANE ARHITETS MEP12

25 MOUNT TWO FIXTURES INSIDE SHEET METAL BOX MOUNT SINGLE FIXTURE INSIDE SHEET METAL BOX LIGHT FIXTURE SHEDULE MARK MAKE MODEL DESRIPTION VOLTAGE POWER BULB NOTES LIGHT MOUNTING DETAIL 1 SALE: N.T.S. GENERAL NOTES: 1. TEST ALL INDIATED EXISTING SMOKE DETETORS AND ADVISE ARHITET AND OWNER IF REPLAEMENT IS REQUIRED. 2. ROUTE NEW SIX ONDUTOR #18AWG ABLE FROM TRANSFER SWITH UP THROUGH HOISTWAY TO ELEVATOR EQUIPMENT ROOM. 3. REPLAE EXISTING TELEPHONE ABLE ROUTED THROUGH HOISTWAY TO ELEVATOR EQUIPMENT ROOM. 4. PROVIDE NEW SEURITY AMERA VIDEO ABLE IN EAH AR, ROUTED THROUGH HOISTWAY IN TRAVELING ABLE TO ELEVATOR EQUIPMENT ROOM. EXTEND ABLE(S) TO SEURITY/REORDING EQUIPMENT. 5. WHERE IRUITS AND/OR ABLES ARE ROUTED THROUGH HOISTWAY, THEY ARE TO BE ROUTED WITH THE TRAVELING ABLE - OORDINATE W/ ELEVATOR SUBONTRATOR. MEP13 A LITHONIA WL4 40L EZ1 LP835 WALL MOUNTED 39.1W LED MOUNT FIXTURE HORIZONTAL WITH LENS FAING AWAY FROM THE WALL, MATH MOUNTING ELEVATION OF EXISTING FIXTURE B LITHONIA ZL2N LM MDD MVOLT 40K 80RI WH LITHONIA ZL2N LM MDD MVOLT 40K 80RI WH D LITHONIA ZL2N LM MDD MVOLT 40K 80RI WH SUMP PUMP SHEDULE MARK MAKE MODEL DESRIPTION VOLTAGE POWER FLOW HEAD NOTES SP1 ZOELLER 188 SUBMERSIBLE SUMP PUMP EILING MOUNTED 72W LED MOUNT FIXTURE INSIDE OF SHEET METAL ENLOSURE ON TOP OF ELEVATOR AR. OORDINATE W/ ELEVATOR AR TOP EQUIPMENT EILING MOUNTED 42W LED MOUNT FIXTURE INSIDE OF SHEET METAL ENLOSURE ON TOP OF ELEVATOR AR. OORDINATE W/ ELEVATOR AR TOP EQUIPMENT EILING SUSPENDED 72W LED SUSPEND FIXTURE ON HAIN OR AIRRAFT ABLE FROM 8'-0" AFF. ONNET ALL LIGHT TO EXIST. SWITH 1/2HP 100GPM 40' INSTALL IN EXISTING SUMP PIT, INLUDE FLOAT SWITH, ORD, AND HEK VALVE, ONNET TO EXISTING REEPTALE ON WALL ABOVE. 6. REMOVE ANY UNUSED OR ABANDONED PIPING, ONDUIT ET.. EXHAUST FAN SHEDULE MARK MAKE MODEL DESRIPTION VOLTAGE POWER FM STATI NOTES EF1 SOLER & PALAU STXDE 8 SIDEWALL MOUNT EM FAN 1/4HP 200FM 0.5" -- MINISPLIT A/ SHEDULE MARK MAKE MODEL DESRIPTION VOLTAGE POWER APAITY NOTES MS1 MITSUBISHI PUY-A18NHA3 OUTDOOR ONDENSING W1 MITSUBISHI PKA-A18HAL WALL MOUNTED TERMINAL 2240W 1800BTU/HR BTU/HR -- DETROIT HOUSING OMMISSION DETROIT, MIHIGAN ELETRI BASEBOARD MARK MAKE MODEL DESRIPTION VOLTAGE POWER APAITY NOTES EB1 ADET 4F10001WP 4' ELETRI BASEBOARD W ONFIRM VOLTAGE, PROVIDE BTF2 THERMOSTAT ALLIANE ARHITETS MEP13