1 SECTION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work of this section. B. Division-15 Basic Materials and Methods sections apply to work of this section DESCRIPTION OF WORK A. Extent of mechanical insulation required by this section is indicated on drawings, and by requirements of this section. B. Types of mechanical insulation specified in this section include the following: 1. Piping System Insulation: a. Domestic Water Piping Systems. b. Storm Water Piping Systems. c. Condensate piping systems. d. Refrigerant Piping Systems. 2. Ductwork System Insulation: a. Cold Ductwork. b. Hot Ductwork. c. Air Plenums and Equipment Housings. d. Exposed Ductwork 3. Equipment Insulation: a. Hot Surfaces of Mechanical Equipment. b. Cold Surfaces of Mechanical Equipment. 4. Breeching Insulation: a. Breechings from Heating Equipment. C. Paint the following insulation surfaces: a. All pipe insulation (exposed and concealed). D. Refer to Division 15 section "Supports and Anchors" for protection shields and thermal hanger shields; not work of this section. E. Refer to Division 15 section "Metal Ductwork" for duct linings; not work of this section. F. Refer to Division 15 section "Mechanical Identification" for installation of identification devices for piping, ductwork and equipment; not work of this section. G. Refer to Division 15 section "Outside Utilities" for installation of pipe insulation on piping exterior to the structure Construction Issue

2 1.03 QUALITY ASSURANCE A. Manufacturers. Firms regularly engaged in manufacture of mechanical insulation products, of types and sizes required, whose products have been in satisfactory use in similar service for not less than 5 years. B. Installer. A firm with at least 10 years successful installation experience on projects with mechanical insulations similar to that required for this project. C. Flame/Smoke Ratings. Provide composite mechanical insulation (insulation, jackets, coverings, sealers, mastics and adhesives) with flame-spread rating of 25 or less, and smoke-developed rating of 50 or less, as tested by ANSI/ASTM E 84 (NFPA 255) method. In air plenums, smoke-developed rating shall be 50 or less. D. Asbestos-Free. All materials shall be guaranteed to be 100% free of any asbestos materials SUBMITTALS A. Product Data. Submit manufacturer's specifications and installation instructions for each type of mechanical insulation. Submit schedule showing manufacturer's product number, thickness, and furnished accessories for each mechanical system requiring insulation DELIVERY, STORAGE AND HANDLING A. Deliver insulation, coverings, cements, adhesives, and coatings to site in containers with manufacturer's stamp or label, affixed showing fire hazard ratings of products. B. Protect insulation against dirt, water, chemical, and mechanical damage. Do not install damaged insulation; remove from project site. PART 2 - PRODUCTS 2.01 ACCEPTABLE MANUFACTURERS A. Available Manufacturers. Subject to compliance with requirements, manufacturers offering products which may be incorporated in the work include, but are not limited to, the following: 1. Armstrong World Industries, Inc. 2. Certainteed Corp. 3. Schuller International Inc. 4. Owens-Corning Fiberglass Corp. 5. Knauf Fiberglass Co. 6. Pittsburg Corning Corp PIPE INSULATION MATERIALS A. Fiberglass Pipe Insulation: Owens-Corning One or Two Piece Pipe Insulation Fiberglass 25 ASJ/S All Service Jacket Schuller Flame Safe Pipe Insulation All Purpose Jacket - AP/S Certain-Teed/St. Gobain Fiber Glass Pipe Insulation All Service Jacket - ASJ/S Knauf F.G. Inc. Fiber Glass Pipe Insulation Construction Issue

3 All Service Jacket - ASJ/S All above with self-seal lap. B. One Piece PVC Insulated Fitting Covers: 1. JM Uni-Fit 2. Zeston 3. Speed-Line C. Flexible Elastomeric Thermal Pipe and Sheet Insulation: 1. Insulation shall meet the smoke developed and flame spread ratings listed in Article 01.03C. 2. For Service: -40 F to 220 F. Armstrong Armaflex II or AP Armaflex. D. Pipe Inserts: 1. Calcium silicate pre-formed two-piece pipe insulation with all purpose jacket. Jacket to be vapor barrier type with self-seal lap. E. Mineral Wool with Aluminum Jacket: 1. 2" thick 1200 F mineral wool finished with 0.016" aluminum jacket DUCTWORK INSULATION MATERIALS A. External Insulation (Rigid Board Type) (FSK Facing): 1. Material: 1. Certain-Teed/St. Gobain 1½" thick, 3 lb. density Fiberglass Board, (FSK Facing). 2. Owens-Corning 1½" thick, 3 lb. density Fiberglass Board (FSK Facing). 3. Schuller 1½" thick, 3 lb. density Fiberglass Board (FSK Facing). B. External Insulation (Blanket Type): 1. Material: 1. Schuller, R6. 1½" thick, FSK facing, 1-2" Tab. 2. Owens-Corning, ED75, 1½" thick, FRK " Tab. 3. Certain-Teed/St. Gobain, Type IV, 1½" thick, FSK 1-2" Tab. C. Ductwork Insulation Accessories. Provide staples, bands, wires, tape, anchors, corner angles and similar accessories as recommended by insulation manufacturer for applications indicated. D. Ductwork Insulation Compounds. Provide cements, adhesives, coatings, sealers, protective finishes and similar compounds as recommended by insulation manufacturer for applications indicated EQUIPMENT INSULATION MATERIALS A. Rigid Fiberglass Equipment Insulation. FS HH-I-558, Form A, Class as indicated: 1. Provide Class 1 (non-load-bearing) for temperatures up to and including 400 F (204 C) and where insulation is not subjected to compressive loading Construction Issue

4 B. Flexible Fiberglass Equipment Insulation. FS HH-I-558, Form B, Type I, Class as indicated. 1. Provide Class 6 for temperatures up to and including 350 F (177 C). C. Cellular Glass Equipment Insulation. FS HH-I-551, Type I. D. Jacketing Material for Equipment Insulation. Provide pre-sized glass cloth jacketing material, not less than 7.8 ounces per square yard, except as otherwise indicated. E. Equipment Insulation Compounds. Provide adhesives, cements, sealers, mastics and protective finishes as recommended by insulation manufacturer for applications indicated. F. Equipment Insulation Accessories. Provide staples, bands, wire, wire netting, tape corner angles, anchors, stud pins and metal covers as recommended by insulation manufacturer for applications indicated BREECHING INSULATION MATERIALS A. Rigid Fiberglass Breeching and Stack Insulation: PSF density rigid fiberglass insulation with ASJ jacket. 2" thickness. Bigwrap or equal. B. Breeching Insulation Compounds: Provide adhesives, cements, sealers, mastics and protective finishes as recommended by insulation manufacturer for applications indicated. C. Breeching Insulation Accessories: Provide bands, wire, wire netting, tape, corner angles, anchors and stud pins as recommended by insulation manufacturer for applications indicated DUCT LAGGING A. Rigid insulation board and 5/8" thick gypboard plus fiberglass cloth PAINT A. Pipe Insulation and Equipment Insulation. Paint designed for use on insulation jackets; such as Insulcap or Insulcolor. Color: White in a shade slightly different than white jacket material. PART 3 - EXECUTION 3.01 INSPECTION A. Examine areas and conditions under which mechanical insulation is to be installed. Do not proceed with work until unsatisfactory conditions have been corrected in manner acceptable to Installer. 3.2 PLUMBING PIPING SYSTEM INSULATION A. Insulation Omitted. Omit insulation on chrome-plated exposed piping (except for handicapped fixtures), air chambers, unions, flanges, strainers, check valves, balance cocks, flow regulators, drain lines from water coolers, drainage piping located in crawl spaces or tunnels, buried piping, fire protection piping, and pre-insulated equipment. Omit insulation on exposed plumbing fixture runouts from faces of wall or floor to fixture; on unions, flanges, strainers, flexible connections, and expansion joints. B. Cold Piping: Construction Issue

5 1. Application Requirements: Insulate the following cold plumbing piping systems: a. Domestic cold water piping. Exclude concealed cold water CPVC and PB piping vertical risers serving housing units. b. Interior above-ground storm water piping (5 ft from roof drain). c. Interior above-ground overflow storm water piping (horizontal plus 5 feet of vertical, 5ft from roof drain or exterior wall outlet). d. Underside of roof drain bodies 2. Insulate each piping system specified above with one of the following types and thicknesses of insulation: a. Pipe size 1" and smaller: Flexible unicellular (Armaflex) 1/2" thick. b. Pipe size 1 ½ and less: ½ polyethylene foam(imcoa) or fiberglass. c. Pipe Size 2 and larger: 1 fiberglass DUCTWORK SYSTEM INSULATION A. Cold Ductwork (below ambient temperature): 1. Application Requirements: Insulate the following cold ductwork: 1. Outdoor air intake ductwork between air entrance and fan inlet on HVAC unit inlet. Ductwork exposed to the outdoors. 2. HVAC supply ductwork between RTU fan discharge to last supply grille. 3. HVAC return intake ductwork: include duct liner for return duct serving fan coil unit. 4. HVAC plenums and unit housings. 5. Ductwork within 15ft of exhaust fan roof or wall outlets (roof mounted exhaust fans). Ductwork withing 10ft of toilet exhast outlets. 2. Insulate each ductwork system specified above with one of the following types and thicknesses of insulation: 1. Expose locations in non finished areas: Rigid fiberglass; 1½" thick, in exposed locations similar mechanical equipment rooms. 2. Insulation: Flexible fiberglass; 1½" thick, application limited to concealed locations. 3. Exposed Locations in finish areas. Double wall duct construction with interior flexible insulation, 1 ½ thick, perforated interior face, with mylar coating vapor barrier. 4. Exposed ductwork to outdoor conditions: Double wall construction with interior fiber board insulation, 3 thick, 3lb density with vapor barrier, vapor barrier tape at seams, standing seam 22 gauge aluminum jacket. B. Hot Ductwork (above ambient temperature): Application Requirements: Insulate the following hot ductwork: 1. Hot supply and outdoor air intake ductwork between fan discharge and terminal outlet. 2. Insulate each ductwork system specified above with one of the following types and thicknesses of insulation: a. Exposed location Insulation: Rigid fiberglass; 1½" thick. b. Concealed location Insulation: Flexible fiberglass; 1½" thick Construction Issue

6 C. Duct Lagging: c. Make up Air handling unit discharge duct Insulation: 2 thick 3 lb density double wall, perforated interior face, with mylar coating vapor barrier, rated for temperatures to 250F, aluminum 22 gage jacket. 1. Refer to details on drawings. Ducts designated with "L" shall be first insulated on the exterior with 1" thick rigid fiberglass board. Insulation shall be applied with edges tightly butted and impaled over mechanical fasteners such as welded pins and secured with clips. Pins shall be spaced to hold the insulation securely in place but not 18" on centers. 2. Two layers of 5/8" gypboard shall be glued in place with joints staggered, cover with fiberglass cloth. Support weight of assembly by adding corner beads to transmit weight to trapeze hangers. Corner beads shall be fabricated from 16 gauge galvanized iron, 3" x 3". Place continuously along 2 bottom edges, overlapping 3" on ends. 3. Extend lagging through mechanical room wall construction. Seal air-tight at wall, floor or ceiling penetrations EQUIPMENT INSULATION A. Cold Equipment (below ambient temperature): 1. Application Requirements: Insulate the following cold equipment: 1. Drip pans under chilled equipment, and air handling unit cooling coils. 1. Insulate each item of equipment specified above with one of the following types and thicknesses of insulation: 1. Insulation: Armstrong Armaflex 1" thick for cold surfaces above 35 F and 2" thick for chilled surfaces (below 35 F) BREECHING INSULATION A. Application Requirements. Insulate the following breechings: 1. Breechings between heating equipment and fireplace outlets and chimney connection, except for double wall or factory insulated breechings. B. Insulate each breeching specified above with one of the following types and thicknesses of insulation: 1. Insulation: Bigwrap 2" thick INSTALLATION OF PIPING INSULATION A. General. Install insulation products in accordance with manufacturer's written instructions, and in accordance with recognized industry practices to ensure that insulation serves its intended purpose. B. Install insulation on pipe systems subsequent to testing and acceptance of tests. C. Install insulation materials with smooth and even surfaces. Insulate each continuous run of piping with full-length units of insulation, with single cut piece to complete run. Do not use cut pieces or scraps abutting each other Construction Issue

7 D. Clean and dry pipe surfaces prior to insulating. Butt insulation joints firmly together to ensure complete and tight fit over surfaces to be covered. E. Maintain integrity of vapor-barrier jackets on pipe insulation, and protect to prevent puncture or other damage. F. Pipe hangers may be attached directly to the piping for domestic water piping, rainleaders, steam and steam condensate, condenser water piping, heating hot water supply and return. On all chilled water and well water piping the hangers shall be installed outside of the insulation. G. Insulation Repair Work. Any and all insulated surfaces that are disturbed purposely or inadvertently shall be neatly repaired including finish painting to match original. H. Exposed Ends. Pipe insulation sections that have exposed ends at valves and other accessories shall be treated as follows: 1. In concealed areas such as suspended ceilings, tunnels and pipe shafts the ends may remain as cut except that such ends shall be vaporproofed with mastic sealer if installed on cold or chilled water. Other services may be left untreated. 2. In exposed areas such as mechanical spaces or finished spaces the ends shall be neatly tapered and vaporproofed with mastic sealer. I. Cover valves, fittings and similar items in each piping system with equivalent thickness and composition of insulation as applied to adjoining pipe run. Install factory molded, precut or job fabricated units (at Installer's option) except where specific form or type is indicated. 1. In all mechanical rooms, all fitting covers, etc. less than 5 feet above the floor shall be field wrapped with blanket insulation, buttered to fill in gaps and then covered with canvas or glass cloth. J. Extend piping insulation without interruption through walls, floors and similar piping penetrations, except where otherwise indicated. 1. Refer to sections pertaining to sealing of sleeves. K. Chilled water piping interior of factory fabricated or field fabricated air handling units and rooftop units shall be insulated up to cooling coil connections at headers. L. Install pipe hanger inserts to prevent compression of insulation. 1. Pipe hanger inserts shall be rigid insulation (calcium silicate) of length conforming to the following table: Pipe Size Minimum Insert Length 1½" to 2½" 10" 3" to 6" 12" 8" to 10" 16" 12" and larger 22" Inserts shall be of same thickness as adjoining insulation and shall be installed with ASJ, vapor barrier jacket and seals INSTALLATION OF DUCTWORK INSULATION A. General. Install insulation products in accord with manufacturer's written instructions and in accordance with recognized industry practices to ensure that insulation serves its intended purpose Construction Issue

8 B. Install insulation materials with smooth and even surfaces. C. Clean and dry ductwork prior to insulating. Butt insulation joints firmly together to ensure complete and tight fit over surfaces to be covered. D. Maintain integrity of vapor-barrier on ductwork insulation, and protect it to prevent puncture and other damage. E. Extend ductwork insulation without interruption through walls, floors and similar ductwork penetrations, except where otherwise indicated. F. Lined Ductwork. Except as otherwise indicated, omit insulation on ductwork where internal insulation or sound absorbing linings have been installed. G. Lagged Ductwork: Install lagged ductwork where indicated. H. Corner Angles. Except for oven and hood exhaust duct insulation, install corner angles on external corners of insulation on ductwork in exposed finished spaces before covering with jacketing. I. Rigid Insulation: 1. Insulation shall be applied with edges tightly butted and impaled over mechanical fasteners such as welded pins and secured with clips. Pins shall be spaced to hold the insulation securely in place but not over 18" centers. 2. All insulation butt joints shall be sealed with 3" wide pressure sensitive joint sealing tape to match all purpose facing. On all corner joints 4" tape shall be used. All pin clips shall be sealed with matching tape patches. J. Blanket Insulation: 1. All rectangular and round ducts when scheduled shall be insulated with fiberglass blanket 1½" thick with FSK or FRK vapor barrier jacket with 1-2" tab of grades mentioned above. 2. The insulation shall be applied with edges tightly butted and secured to the metal surface with strips of insulation bonding adhesive. Foster Duct-Fas or 3M #33 adhesive applied in 6" wide strips every 18 inches. 3. On ducts over 24" wide the blanket shall be additionally secured to the bottom of the duct with welded pins and clips on not greater than 18" centers. All pins shall be sealed with matching tape patches INSTALLATION OF EQUIPMENT INSULATION A. General. Install equipment thermal insulation products in accordance with manufacturer's written instructions, and in compliance with recognized industry practices to ensure that insulation serves intended purpose. B. Install insulation materials with smooth and even surfaces and on clean and dry surfaces. Redo poorly fitted joints. Do not use mastic or joint sealer as filler for gapping joints and excessive voids resulting from poor workmanship. C. Maintain integrity of vapor-barrier on equipment insulation and protect it to prevent puncture and other damage. D. Do not apply insulation to equipment while hot Construction Issue

9 E. Apply insulation using the staggered joint method for both single and double layer construction, where feasible. Apply each layer of insulation separately. F. Coat insulated surfaces with layer of insulating cement, troweled in work-manlike manner, leaving smooth continuous surface. Fill in scored block, seams, chipped edges and depressions, and cover over wire netting and joints with cement of sufficient thickness to remove surface irregularities. G. Cover insulated surfaces with glass cloth jacketing neatly fitted and firmly secured. Lap seams at least two inches. H. Do not insulate handholes, cleanouts, ASME stamp, and manufacturer's nameplate. Provide neatly beveled edge at interruptions of insulation. I. Provide removable insulation sections to cover parts of equipment which must be opened periodically for maintenance; include metal vessel covers, fasteners, flanges, frames and accessories INSTALLATION OF BREECHING INSULATION A. Install exposed pipe insulation materials with smooth and even surfaces and on clean and dry breeching surfaces. B. Apply insulation using staggered joint method for both single and double-layer construction, where feasible. Apply each layer of insulation separately. C. Coat insulated surfaces with layer of insulating cement troweled in work-manlike manner, leaving smooth continuous surface. Fill in scored block, seams, chipped edges and depressions, and cover over wire netting and joints with cement of sufficient thickness to remove surface irregularities. D. Cover insulated surfaces with glass cloth jacketing neatly fitted and firmly secured. Lap seams at least 2 inches. E. Avoid applying insulation to hot breechings PAINTING OF INSULATED SURFACES A. Insulation shall be painted immediately after installation to prevent damage or mildew. Application (heavy) by mitt coating is acceptable PROTECTION AND REPLACEMENT A. Replace damaged insulation which cannot be repaired satisfactorily, including units with vapor barrier damage and moisture saturated units. B. Protection. Insulation Installer shall advise Contractor of required protection for insulation work during remainder of construction period, to avoid damage and deterioration. END OF SECTION Construction Issue