RSIC ACOUSTIC ASSEMBLY

Size: px
Start display at page:

Download "RSIC ACOUSTIC ASSEMBLY"

Transcription

1 RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY World Leader in Noise Control Solutions DIRECT FIX TO WOOD OPEN WEB TRUSS F STC 61 IIC 54 CONSTRUCTION Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York PB Truss L/360 Open Web 24" O.C. RSIC-1 24"x48" Clark Dietrich 087F Furring 24" O.C. National Gypsum Gold Bond Fire-Shield C Gypsum Board STC 1 Hour See IIC Test Number F STC 61 IIC PAC International, LLC. All Rights Reserved. (866) Fax (866) RSIC is a registered Trade Mark of PAC International, LLC.

2 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to HACKER INDUSTRIES INC. Series/Model: FIRM-FILL Brand Gypsum Concrete and FIRM-FILL SCM-250e Sound Control Mat - Bare Specimen Type: Open Web Truss mm Overall Size: 3023 mm by 3632 mm STC 63 IIC 54 Test Specimen Identification: Subfloor Topping: 25.4 mm Hacker Industries, Inc. FIRM-FILL Brand Gypsum Concrete Subfloor Underlayment: 6.5 mm Hacker Industries, Inc. FIRM-FILL SCM-250e Sound Control Mat Subfloor: 18.8 mm Oriented Strand Board Sheathing Insulation: 88.9 mm Guardian Faced R-13 Fiberglass Insulation Truss: mm York PB Truss L/360 Open Web Truss Ceiling Isolation: 28 mm PAC International RSIC-1 Classic Isolation Clips Ceiling Isolation: 22.3 mm ClarkDietrich 087F Furring/Hat Channel Ceiling: 15.9 mm National Gypsum Gold Bond Fire-Shield C Gypsum Board Reference should be made to Intertek-ATI Report F for complete test specimen description. This page alone is not a complete report. 130 Derry Courtaa York, PA 17406aa p f

3 Page 1 of 4 Acoustical Performance Test Report HACKER INDUSTRIES INC Newport Center Drive, Suite 275 Newport Beach, California Report F Test Date 03/07/16 Report Date 03/15/16 Revision Date 04/29/16 Project Scope Architectural Testing, Inc., a subsidiary of Intertek (Intertek-ATI), was contracted to conduct airborne sound transmission loss and impact sound transmission tests. The complete test data is included as attachments to this report. The client provided the test specimen. The specimen was constructed on the date of testing. Test Methods The acoustical tests were conducted in accordance with the following standards. The equipment listed in the attachments meets the requirements of the following standards. ASTM E 90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions ASTM E , Classification for Rating Sound Insulation ASTM E , Standard Test Method for Laboratory Measurement of Impact Sound Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine ASTM E (2012), Classification for Determination of Impact Insulation Class (IIC) ASTM E (2012) Standard Test Method for Determination of Decay Rates for Use in Sound Insulation Test Methods Test Procedure All testing was conducted in the VT test chambers at Intertek-ATI located in York, Pennsylvania. The microphones were calibrated before conducting the tests. The airborne transmission loss test was conducted in accordance with the ASTM E 90 test method using the single direction method. Two background noise sound pressure level and five sound absorption measurements were conducted at each of five microphone positions. Four sound pressure level measurements were made simultaneously in both rooms, at each of five microphone positions. 130 Derry Courtaa York, PA 17406aa p f

4 Page 2 of 4 Test Procedure (Continued) The impact sound transmission test was conducted in accordance with the ASTM E 492 test method. Two background noise sound pressure level, two sound pressure level measurements with the tapping machine operating at each position specified by ASTM E 492, and five sound absorption measurements were conducted at each of five microphone positions. The air temperature and relative humidity conditions were monitored and recorded during all measurements. Test Conditions Source Room Receive Room Average Temperature 19.4 C Average Temperature 20.3 C Average Relative Humidity 60% Average Relative Humidity 57% Test Calculations The STC (Sound Transmission Class) and IIC (Impact Insulation Class) ratings were calculated in accordance with ASTM E 413 and ASTM E 989, respectively. Test Specimen Materials and Installation Details Material Gypsum Concrete Sound Control Mat Oriented Strand Board Sheathing Fiberglass Insulation Open Web Truss Dimensions (mm) Thickness (mm) Manufacturer and Series Hacker Industries, Inc. FIRM by m² kg/m² FILL Brand Note: The gypsum concrete was allowed to cure for a minimum of 14 days. The gypsum layer had a closed cell foam perimeter isolation. The product name was specified by client. Hacker Industries, Inc. FIRM by m² 0.49 kg/m² FILL SCM-250e Note: Installed per manufacture's specifications with seams overlapping and taped 1219 by N/A m² kg/m² Note: The OSB was adhered to the trusses with Loctite PL 400 Subfloor adhesive. It was attached with 9D nails on 203 mm centers along perimeter and 305 mm centers along trusses by Guardian Faced R m² 1.33 kg/m² Note: Installed in the cavity between trusses flush with the OSB. Hanger wire was used to keep insulation secure on 305mm 88.9 by York PB Truss L/360 7 m² kg/m² Note: Installed on 610 centers using JUS414 hanger brackets. Quantity Average Weight Isolation Clips 76.9 by PAC International RSIC-1 Classic 24 clips 0.06 kg/clip Note: Fastened to joists in a 610 mm by 1220 mm traditional pattern.

5 Page 3 of 4 Test Specimen Materials and Installation Details (Continued) Material Dimensions (mm) Thickness (mm) Manufacturer and Series Quantity Average Weight Furring/Hat Channel Gypsum Board 3658 by ClarkDietrich 087F lin m 0.48 kg/m Note: Installed into the PAC International RSIC-1 Classic, spaced 610 mm on center. National Gypsum Gold Bond 1219 by m² kg/m² Fire-Shield C Note: Fastened to furring channels on 305 mm centers with 25.4 mm type S screws. Seams finished with joint compound. Perimeter sealed with acoustical caulk. Comments The total weight of the floor/ceiling assembly was kg. Intertek-ATI will store samples of the test specimen for four years. A drawing of the test specimen is included in the attachments. Intertek-ATI will service this report for the entire test record retention period. Test records, such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation, will be retained by Intertek-ATI for the entire test record retention period. The test record retention period ends four years after the test date. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen tested. This report is intended to help in the client s quality assurance program, but it does not represent a continuous or exhaustive evaluation of the specimen tested or of other products or materials that were not evaluated. The statements and data provided herein do not constitute approval, disapproval, certification, or acceptance of performance or materials. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. FOR INTERTEK-ATI: David M. Dacheux Technician II - Acoustical Testing Jordan Strybos Project Manager - Acoustical Testing Attachments (6 Pages): This report is complete only when all attachments are included. * Stated by Client/Manufacturer N/A - Non Applicable

6 Page 4 of 4 Revision Log Revision Date Page(s) Description R0 03/15/16 N/A Original Report Issue R1 04/29/16 Page 2 Clip spacing installation note corrected This report produced from controlled document template ATI 00629(d), Revised 02/09/15.

7 Attachments Instrumentation Instrument Manufacturer Model ATI Number Data Acquisition Unit National Instruments PXI /14 * Microphone Calibrator Norsonic 1251 Y /15 Receive Room Microphone Scantek 378B /15 Receive Room Microphone PCB Piezotronics 378B /15 Receive Room Microphone PCB Piezotronics 378B /15 Receive Room Microphone PCB Piezotronics 378B /15 Receive Room Microphone PCB Piezotronics 378B /15 Receive Room Environmental Indicator Source Room Microphone PCB Piezotronics 378B /15 Source Room Microphone PCB Piezotronics 378B /15 Source Room Microphone PCB Piezotronics 378B /15 Source Room Microphone PCB Piezotronics 378B /15 Source Room Microphone Scantek 378B /15 Source Room Environmental Indicator Tapping Machine Look Line s.r.l. EM50 (TM50) /15 * The calibration frequency for this equipment is every two years per the manufacturer's recommendation. Test Chambers Comet VT Receive Room Volume m³ VT Source Room Volume 190 m³ T /15 10/15 Comet T /15 Date of Calibration Page 1 of 6

8 AIRBORNE SOUND TRANSMISSION LOSS ASTM E 90 Test Date 03/07/16 Data File No. F Client Description Specimen Area m² Technician Hacker Industries Inc mm Hacker Industries, Inc. FIRM-FILL Brand Gypsum Concrete, 6.5 mm Hacker Industries, Inc. FIRM-FILL SCM- 250e Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, mm York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich 087F Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond Fire-Shield C Gypsum Board David M. Dacheux Freq Background Source Receive Specimen 95% Number Absorption SPL SPL SPL TL Confidence of (Hz) (db) (m²) (db) (db) (db) Limit Deficiencies STC Rating Deficiencies (Sound Transmission Class) (Sum of Deficiencies) Notes: 1) Receive Room levels less than 5 db above the Background levels are highlighted in yellow. 2) Specimen TL levels listed in red indicate the lower limit of the transmission loss. 3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied ATI Revised 02/09/15 Page 2 of 6

9 AIRBORNE SOUND TRANSMISSION LOSS ASTM E 90 Test Date 03/07/16 Data File No. F Client Description Specimen Area m² Technician Hacker Industries Inc mm Hacker Industries, Inc. FIRM-FILL Brand Gypsum Concrete, 6.5 mm Hacker Industries, Inc. FIRM-FILL SCM- 250e Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, mm York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich 087F Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond Fire-Shield C Gypsum Board David M. Dacheux 100 Airborne Sound Transmission Loss Sound Transmission Loss (db) Specimen TL Contour Curve Frequency (Hz) ATI Revised 02/09/15 Page 3 of 6

10 IMPACT SOUND TRANSMISSION ASTM E 492 Test Date 03/07/16 Data File No. F Client Description Specimen Area m² Technician Hacker Industries Inc mm Hacker Industries, Inc. FIRM-FILL Brand Gypsum Concrete, 6.5 mm Hacker Industries, Inc. FIRM-FILL SCM- 250e Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, mm York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich 087F Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond Fire-Shield C Gypsum Board David M. Dacheux Freq Background SPL Absorption Normalized Impact SPL 95% Number Confidence (Hz) (db) (m²) (db) Limit Deficiencies of IIC Rating Deficiencies (Impact Insulation Class) (Sum of Deficiencies) Note: Receive Room levels less than 5 db above the Background levels are highlighted in yellow. ATI Revised 02/09/15 Page 4 of 6

11 IMPACT SOUND TRANSMISSION ASTM E 492 Test Date 03/07/16 Data File No. F Client Description Specimen Area m² Technician Hacker Industries Inc mm Hacker Industries, Inc. FIRM-FILL Brand Gypsum Concrete, 6.5 mm Hacker Industries, Inc. FIRM-FILL SCM- 250e Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, mm York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich 087F Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond Fire-Shield C Gypsum Board David M. Dacheux Impact Sound Transmission Sound Pressure Level (db) Impact Insulation Class (IIC) Normalized Impact SPL Contour Curve Frequency (Hz) ATI Revised 02/09/15 Page 5 of 6

12 Drawing 1-Subfloor Topping 2-Subfloor Underlayment 3-Subfloor 4-Insulation 5-Truss 6-Ceiling Isolation 7-Ceiling Page 6 of 6